TECHNICAL MANUAL
GSX/VSX 13 SEER Condensing Units
with R-410A
•
•
•
•
Refer to Service Manual RS6200006 for installation, operation, and troubleshooting information.
All safety information must be followed as provided in the Service Manual.
Refer to the appropriate Parts Catalog for part number information.
Models listed on page 3.
This manual is to be used by qualified, professionally trained HVAC technicians
only. Goodman does not assume any responsibility for property damage or
personal injury due to improper service procedures or services performed by an
unqualified person.
RT6113005r9
August 2010
Copyright © 2007 - 2010 Goodman Manufacturing Company, L.P.
PRODUCT IDENTIFICATION
The model number is used for positive identification of component parts used in manufacturing. Please use this number
when requesting service or parts information.
GSX130363A*
GSX130483A*
GSX130484A*
GSX130603A*
GSX130604A*
VSX130181A*
VSX130241A*
VSX130301A*
VSX130361A*
VSX130421A*
VSX130481A*
GSX130181A*
GSX130241A*
GSX130301A*
GSX130361A*
GSX130421A*
GSX130481A*
GSX130601A*
VSX130181B*
VSX130601B*
GSX130181B*
GSX130241B*
GSX130301B*
GSX130361B*
GSX130421B*
GSX130481B*
GSX130601B*
GSX130181C*
* Indicates minor revision & is not used for order entry or inventory management
The United States Environmental Protection Agency (“EPA”) has issued various regulations re-
garding the introduction and disposal of refrigerants introduced into this unit. Failure to follow
these regulations may harm the environment and can lead to the imposition of substantial fines.
These regulations may vary by jurisdiction. Should questions arise, contact your local EPA office.
WARNING
WARNING
Do not connect or use any device
To prevent the risk of property
WARNING
thatisnotdesigncertifiedbyGood-
man for use with this unit. Serious
property damage, personal injury, reduced unit perfor-
mance and/or hazardous conditions may result from the
use of such non-approved devices.
damage, personal injury, or death,
do not store combustible materi-
als or use gasoline or other flammable liquids or vapors
in the vicinity of this appliance.
3
PRODUCT DESIGN
GSX/VSX13 models are available in 1 1/2 through 5 ton sizes
and use R-410A refrigerant. They are designed for 208/230
volt single phase applications.
WARNING
To avoid possible injury, explosion or death, practice
safe handling of refrigerants.
Select GSX13 models are available in 208/230 and 460 volt
3-phase applications. These models use R-410A refrigerant.
Special consideration must be given to location of the con-
densing unit(s) in regard to structures, obstructions, other
units, and any/all other factors that may interfere with air
circulation. Where possible, the top of the unit should be
completely unobstructed; however, if vertical conditions re-
quire placement beneath an obstruction there should be a
minimum of 60 inches between the top of the unit and
the obstruction(s). The specified dimensions meet require-
ments for air circulation only. Consult all appropriate regula-
tory codes prior to determining final clearances.
The condenser air is pulled through the condenser coil by a
direct drive propeller fan. This condenser air is then dis-
charged out of the top of the cabinet.
These units are designed for free air discharge, so no addi-
tional resistance like duct work shall be attached.
The suction and liquid line connections on present models
are of the sweat type for field piping with refrigerant type cop-
per. Front seating valves are factory installed to accept the
field run copper. The total refrigerant charge for a normal in-
stallation is factory installed in the condensing unit. GSX/
VSX units are charged for the matching evaporator coil and a
15 foot refrigerant line set.
Another important consideration in selecting a location for
the unit(s) is the angle to obstructions. Either side adjacent
the valves can be placed toward the structure provided the
side away from the structure maintains minimum service clear-
ance. Corner installations are strongly discouraged.
Systems should be properly sized by heat gain and loss
calculations made according to methods of the Air Condi-
tioning Contractors Association (ACCA) or equivalent. It is
the contractors responsibility to ensure the system has ad-
equate capacity to heat or cool the conditioned space.
DO NOT locate the unit:
–
–
–
Directly under a vent termination for a gas appliance.
Within 3 feet of a clothes dryer vent.
Where the refreezing of defrost water would create a
hazard.
GSX/VSX models use the Copeland Scroll "Ultratech" Se-
ries compressors which are specifically designed for R-410A
refrigerant. There are a number of design characteristics which
are different from the traditional reciprocating and/or scroll
compressors.
–
Where water may rise into the unit.
"Ultratech" Series scroll compressors will not have a dis-
charge thermostat, some of the early model scroll compres-
sors required discharge thermostats.
Due to their design Scroll compressors are inherently more
tolerant of small quantities of liquid refrigerant.
NOT
RECOMMENDED
OK!
B
OK!
NOTE: Even though the compressor section of a Scroll com-
pressor is more tolerant of liquid refrigerant, continued
floodback or flooded start conditions may wash oil from the
bearing surfaces causing premature bearing failure.
B
B
B
A
AA
AA
AA
"Ultratech" Series scroll compressors use "POE" or
polyolester oil which is NOT compatible with mineral oil based
lubricants like 3GS. "POE" oil must be used if additional oil
is required.
OK!
C
C
OK!
AA
AA
AA
OK!
OK!
Operating pressures and amp draws may differ from stan-
dard reciprocating and/or scroll compressors. This informa-
tion may be found in the "Cooling Performance Data" sec-
tion.
AA
A
C
C
IMPORTANT NOTE: Because of the potential damage to
compressors, do not allow suction pressure at service valve
to drop below 20 PSIG when pumping unit system down for
repair. Outdoor section, depending on line set length and
amount of charge in system, may not be able to hold the
entire system charge.
Minimum Airflow Clearance
Model Type
Residential
A
B
C
AA
20"
24"
10"
12"
10"
12"
18"
18"
Light Commercial
4
DIMENSIONS
PRODUCT DESIGN
W
D
H
Model
Dimensions - W x D x H
VSX130181A*
VSX130241A*
VSX130301A*
VSX130361A*
VSX130421A*
VSX130481A*
26" x 26" x 27½"
26" x 26" x 27½"
26" x 26" x 27½"
29" x 29" x 28¾"
29" x 29" x 36¼"
29" x 29" x 36¼"
GSX130181A*
26" x 26" x 32¼"
GSX130241A*
GSX130301A*
GSX130361A*
GSX130421A*
GSX130481A*
GSX130601A*
26" x 26" x 32¼"
26" x 26" x 32¼"
29" x 29" x 32¼
29" x 29" x 34¼"
29" x 29" x 38¼"
35½" x 35½" x 38¼"
VSX130181B*
VSX130601B*
26" x 26" x 27½"
29" x 29" x 40"
GSX130181B*
GSX130241B*
GSX130301B*
26" x 26" x 27½"
26" x 26" x 27½"
26" x 26" x 27½"
GSX130361B*
GSX130363A*
29" x 29" x 28¾"
29" x 29" x 36¼"
GSX130421B*
GSX130481B*
GSX130483A*
GSX130484A*
29" x 29" x 36¼"
GSX130601B*
GSX130603A*
GSX130604A*
29" x 29" x 40"
GSX130181C*
26" x 26" x 27½"
5
CONDENSING UNIT SPECIFICATIONS
GSX130[18-60]1A*
GSX130181A* GSX130241A* GSX130301A* GSX130361A*
Cooling Capacity, BTUH
Compressor
18,000
24,000
30,000
36,000
R.L. Amps
9.00
48.0
13.4
58.3
12.8
64.0
16.6
79.0
L.R. Amps
High Pressure Switch
Open
610 PSIG
420 PSIG
610 PSIG
420 PSIG
610 PSIG
420 PSIG
610 PSIG
420 PSIG
Close
Condenser Fan Motor
Horsepower
1/6
1.10
1/6
1.10
1/6
1.10
1/6
1.10
F.L. Amps
Liquid Line, Inches O.D.*
Suction Line, Inches O.D.*
Refrigerant Charge
Power Supply
Minimum Circuit Ampacity(1)
Maximum Overcurrent Device(2)
Electrical Conduit Size
3/8"
3/8"
3/8"
3/8"
3/4"
3/4"
3/4"
3/4"
120.0
208/230-60-1
12.3
116.0
208/230-60-1
17.9
129.0
208/230-60-1
17.1
131.0
208/230-60-1
21.9
20
30
30
35
Power Supply (Inches)
1/2 or 3/4
178
1/2 or 3/4
178
1/2 or 3/4
180
1/2 or 3/4
197
Approximate Shipping Weight
GSX130421A* GSX130481A* GSX130601A*
Cooling Capacity, BTUH
Compressor
42,000
48,000
60,000
R.L. Amps
17.9
19.8
26.4
L.R. Amps
112.0
109.0
134.0
High Pressure Switch
Open
610 PSIG
420 PSIG
610 PSIG
420 PSIG
610 PSIG
420 PSIG
Close
Condenser Fan Motor
Horsepower
1/6
1.10
3/8"
7/8"
1/4
1.50
3/8"
7/8"
1/4
1.50
3/8"
7/8"
F.L. Amps
Liquid Line, Inches O.D.*
Suction Line, Inches O.D.*
Refrigerant Charge
Power Supply
151.0
166.0
184.0
208/230-60-1
208/230-60-1
208/230-60-1
Minimum Circuit Ampacity(1)
Maximum Overcurrent Device(2)
23.5
40
26.3
45
34.5
60
Electrical Conduit Size
Power Supply (Inches)
1/2 or 3/4
219
1/2 or 3/4
225
1/2 or 3/4
240
Approximate Shipping Weight
(1) Wire size should be determined in acordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
(2)
Maximum Overcurrent Protection Device: MUST use time delay fuses or HACR-type Circuit Breakers of the same size as noted.
NOTES:
* Always check the S&R plate for electrical data on the unit being installed.
* Installer will need to supply 7/8" to 1 1/8" adapters for suction line connections.
* Unit is charged with refrigerant for 15' of 3/8" liquid line. System charge must be adjusted per Installation Instructions Final Charge Procedure.
* Installation of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED
BY THE OUTDOOR UNIT NOT THE INDOOR COIL.
NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance
with all national and/or local electrical codes. Use copper wire only.
6
CONDENSING UNIT SPECIFICATIONS
GSX130[18-60]1B*
GSX130181B* GSX130241B* GSX130301B*
Cooling Capacity, BTUH
Compressor
18,000
24,000
30,000
R.L. Amps
9.00
48.0
13.5
58.3
12.8
64.0
L.R. Amps
High Pressure Switch
Open
N/A
N/A
N/A
N/A
N/A
N/A
Close
Condenser Fan Motor
Horsepower
1/6
1.10
1/6
1.10
1/6
1.10
F.L. Amps
Liquid Line, Inches O.D.*
Suction Line, Inches O.D.*
Refrigerant Charge
Power Supply
3/8"
3/8"
3/8"
3/4"
3/4"
3/4"
72.0
79.0
81.0
208/230-60-1
12.4
208/230-60-1
18.0
208/230-60-1
17.1
Minimum Circuit Ampacity(1)
Maximum Overcurrent Device(2)
20
30
30
Electrical Conduit Size
Power Supply (Inches)
1/2 or 3/4
149
1/2 or 3/4
151
1/2 or 3/4
152
Approximate Shipping Weight
GSX130361B* GSX130421B* GSX130481B* GSX130601B*
Cooling Capacity, BTUH
Compressor
36,000
42,000
48,000
60,000
R.L. Amps
16.7
79.0
17.9
19.9
25.0
L.R. Amps
112.0
109.0
134.0
High Pressure Switch
Open
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Close
Condenser Fan Motor
Horsepower
1/6
1.10
1/4
1.50
3/8"
7/8"
1/4
1.50
3/8"
7/8"
1/4
1.50
3/8"
7/8"
F.L. Amps
Liquid Line, Inches O.D.*
Suction Line, Inches O.D.*
Refrigerant Charge
Power Supply
Minimum Circuit Ampacity(1)
Maximum Overcurrent Device(2)
Electrical Conduit Size
3/8"
3/4"
92.0
124.0
128.0
125.0
208/230-60-1
22.0
208/230-60-1
208/230-60-1
208/230-60-1
23.9
40
26.4
45
32.8
50
35
Power Supply(Inches)
1/2 or 3/4
159
1/2 or 3/4
194
1/2 or 3/4
195
1/2 or 3/4
200
Approximate Shipping Weight
(1) Wire size should be determined in acordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
(2)
Maximum Overcurrent Protection Device: MUST use time delay fuses or HACR-type Circuit Breakers of the same size as noted.
NOTES:
* Always check the S&R plate for electrical data on the unit being installed.
* Installer will need to supply 7/8" to 1 1/8" adapters for suction line connections.
* Unit is charged with refrigerant for 15' of 3/8" liquid line. System charge must be adjusted per Installation Instructions Final Charge Procedure.
* Installation of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED
BY THE OUTDOOR UNIT NOT THE INDOOR COIL.
NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance
with all national and/or local electrical codes. Use copper wire only.
7
CONDENSING UNIT SPECIFICATIONS
GSX130181C*
GSX130181C*
Cooling Capacity, BTUH
SEER/EER
18,000
13 / 11
Compressor
R.L. Amps
6.70
40.0
L.R. Amps
High Pressure Switch
Open
N/A
N/A
Close
Condenser Fan Motor
Horsepower
1/6
1.10
F.L. Amps
Liquid Line, Inches O.D.*
Suction Line, Inches O.D.*
Refrigerant Charge
Power Supply
3/8"
3/4"
71.0
208/230-60-1
9.5
Minimum Circuit Ampacity(1)
Maximum Overcurrent Device(2)
15
Electrical Conduit Size
Power Supply(Inches)
1/2 or 3/4
135
Approximate Shipping Weight
(1) Wire size should be determined in acordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
(2)
Maximum Overcurrent Protection Device: MUST use time delay fuses or HACR-type Circuit Breakers of the same size as noted.
NOTES:
* Always check the S&R plate for electrical data on the unit being installed.
* Installer will need to supply 7/8" to 1 1/8" adapters for suction line connections.
* Unit is charged with refrigerant for 15' of 3/8" liquid line. System charge must be adjusted per Installation Instructions Final Charge Procedure.
* Installation of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED
BY THE OUTDOOR UNIT NOT THE INDOOR COIL.
NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance
with all national and/or local electrical codes. Use copper wire only.
8
GSX130[36-60][3,4]**
CONDENSING UNIT SPECIFICATIONS
GSX130363A* GSX130483A* GSX130484A* GSX130603A* GSX130604A*
Cooling Capacity, BTUH
Decibels
36,000
74
48,000
76
48,000
76
60,000
77
60,000
77
Compressor
R.L. Amps
10.40
73.0
13.1
83.1
6.1
41.0
Scroll
15.9
110.0
Scroll
7.1
L.R. Amps
52.0
Scroll
Type
Scroll
Scroll
Condenser Fan Motor
Horsepower
1/6
1/4
1/4
1/4
1/4
F.L. Amps
1.10
1.50
0.80
1.50
0.80
Refrigerant System
Liquid Line, Inches O.D.*
Suction Line, Inches O.D.*
Liquid Valve Connection, Inches O.D.*
3/8"
7/8"
3/8"
3/8"
1 1/8"
3/8"
3/8"
1 1/8"
3/8"
3/8"
1 1/8"
3/8"
3/8"
1 1/8"
3/8"
Suction Valve Connection, Inches O.D.* 3
3/4" 3
7/8" 4
128.0
0.080
7/8" 4
128.0
0.080
460-60-3
8.4
7/8" 4
7/8" 4
125.0
0.086
460-60-3
9.7
Refrigerant Charge
92.0
125.0
Piston Size
0.068
0.086
Power Supply
208/230-60-3 208/230-60-3
208/230-60-3
21.4
Minimum Circuit Ampacity(1)
Maximum Overcurrent Device(2)
Min / Max Volts
14.1
20
17.9
30
15
35
15
197 / 253
197 / 253
414 / 506
197 / 253
414 / 506
Electrical Conduit Size
Power Supply(Inches)
1/2 or 3/4
196
1/2 or 3/4
190
1/2 or 3/4
189
1/2 or 3/4
197
1/2 or 3/4
196
Approximate Shipping Weight
(1) Wire size should be determined in acordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
(2)
Maximum Overcurrent Protection Device: MUST use time delay fuses or HACR-type Circuit Breakers of the same size as noted.
Installer must supply a 3/4" to 7/8" adapter for suction line connections.
Installer must supply a 7/8" to 1 1/8" adapter for suction line connections.
(3)
(4)
NOTES:
* Always check the S&R plate for electrical data on the unit being installed.
* Installer will need to supply 7/8" to 1 1/8" adapters for suction line connections.
* Unit is charged with refrigerant for 15' of 3/8" liquid line. System charge must be adjusted per Installation Instructions Final Charge Procedure.
* Installation of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED
BY THE OUTDOOR UNIT NOT THE INDOOR COIL.
NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance
with all national and/or local electrical codes. Use copper wire only.
9
CONDENSING UNIT SPECIFICATIONS
VSX130[18-60]1A*
VSX130181A* VSX130241A* VSX130301A*
Cooling Capacity, BTUH
SEER/EER
18,000
13 / 11
24,000
13 / 11
30,000
13 / 11
Compressor
R.L. Amps
9.00
48.0
13.5
58.3
12.8
64.0
L.R. Amps
High Pressure Switch
Open
N/A
N/A
N/A
N/A
N/A
N/A
Close
Condenser Fan Motor
Horsepower
1/6
1.10
1/6
1.10
1/6
1.10
F.L. Amps
Liquid Line, Inches O.D.*
Suction Line, Inches O.D.*
Refrigerant Charge
Power Supply
3/8"
3/8"
3/8"
3/4"
3/4"
3/4"
72.0
79.0
81.0
208/230-60-1
12.3
208/230-60-1
18.0
208/230-60-1
17.1
Minimum Circuit Ampacity(1)
Maximum Overcurrent Device(2)
20
30
30
Electrical Conduit Size
Power Supply (Inches)
1/2 or 3/4
149
1/2 or 3/4
151
1/2 or 3/4
152
Approximate Shipping Weight
VSX130361A* VSX130421A* VSX130481A*
Cooling Capacity, BTUH
SEER/EER
36,000
13 / 11
42,000
13 / 11
48,000
13 / 11
Compressor
R.L. Amps
16.7
79.0
17.9
19.9
L.R. Amps
112.0
109.0
High Pressure Switch
Open
N/A
N/A
N/A
N/A
N/A
N/A
Close
Condenser Fan Motor
Horsepower
1/6
1.10
1/4
1.50
3/8"
7/8"
1/4
1.50
3/8"
7/8"
F.L. Amps
Liquid Line, Inches O.D.*
Suction Line, Inches O.D.*
Refrigerant Charge
Power Supply
Minimum Circuit Ampacity(1)
Maximum Overcurrent Device(2)
Electrical Conduit Size
3/8"
3/4"
95.0
124.0
128.0
208/230-60-1
21.9
208/230-60-1
208/230-60-1
23.9
40
26.3
45
35
Power Supply (Inches)
1/2 or 3/4
197
1/2 or 3/4
194
1/2 or 3/4
195
Approximate Shipping Weight
(1) Wire size should be determined in acordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
(2)
Maximum Overcurrent Protection Device: MUST use time delay fuses or HACR-type Circuit Breakers of the same size as noted.
NOTES:
* Always check the S&R plate for electrical data on the unit being installed.
* Installer will need to supply 7/8" to 1 1/8" adapters for suction line connections.
* Unit is charged with refrigerant for 15' of 3/8" liquid line. System charge must be adjusted per Installation Instructions Final Charge Procedure.
* Installation of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED
BY THE OUTDOOR UNIT NOT THE INDOOR COIL.
NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance
with all national and/or local electrical codes. Use copper wire only.
10
VSX130[18 & 60]1B*
CONDENSING UNIT SPECIFICATIONS
VSX130181B* VSX130601B*
Cooling Capacity, BTUH
SEER/EER
18,000
13 / 11
60,000
13 / 11
Compressor
R.L. Amps
6.70
40.0
25.0
L.R. Amps
134.0
High Pressure Switch
Open
N/A
N/A
N/A
N/A
Close
Condenser Fan Motor
Horsepower
1/6
1.10
1/4
1.50
3/8"
F.L. Amps
Liquid Line, Inches O.D.*
Suction Line, Inches O.D.*
Refrigerant Charge
Power Supply
Minimum Circuit Ampacity(1)
Maximum Overcurrent Device(2)
3/8"
3/4"
1 1/8"
71.0
125.0
208/230-60-1
9.5
208/230-60-1
26.3
45
15
Electrical Conduit Size
Power Supply(Inches)
1/2 or 3/4
135
1/2 or 3/4
200
Approximate Shipping Weight
(1) Wire size should be determined in acordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
(2)
Maximum Overcurrent Protection Device: MUST use time delay fuses or HACR-type Circuit Breakers of the same size as noted.
NOTES:
* Always check the S&R plate for electrical data on the unit being installed.
* Installer will need to supply 7/8" to 1 1/8" adapters for suction line connections.
* Unit is charged with refrigerant for 15' of 3/8" liquid line. System charge must be adjusted per Installation Instructions Final Charge Procedure.
* Installation of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED
BY THE OUTDOOR UNIT NOT THE INDOOR COIL.
NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance
with all national and/or local electrical codes. Use copper wire only.
11
COOLING PERFORMANCE DATA
GSX130181A*
12
GSX130181A*
COOLING PERFORMANCE DATA
13
COOLING PERFORMANCE DATA
GSX130241A*
14
COOLING PERFORMANCE DATA
GSX130241A*
15
COOLING PERFORMANCE DATA
GSX130301A*
16
COOLING PERFORMANCE DATA
GSX130301A*
17
COOLING PERFORMANCE DATA
GSX130361A*
18
COOLING PERFORMANCE DATA
GSX130361A*
19
COOLING PERFORMANCE DATA
GSX130421A*
20
COOLING PERFORMANCE DATA
GSX130421A*
21
COOLING PERFORMANCE DATA
GSX130481A*
22
COOLING PERFORMANCE DATA
GSX130481A*
23
COOLING PERFORMANCE DATA
GSX130601A*
24
COOLING PERFORMANCE DATA
GSX130601A*
25
COOLING PERFORMANCE DATA
GSX130181B*/VSX130181A*
26
COOLING PERFORMANCE DATA
GSX130181B*/VSX130181A*
27
GSX130181C*/VSX130181B*
COOLING PERFORMANCE DATA
28
COOLING PERFORMANCE DATA
GSX130181C*/VSX130181B*
29
COOLING PERFORMANCE DATA
GSX130241B*/VSX130241A*
30
COOLING PERFORMANCE DATA
GSX130241B*/VSX130241A*
31
COOLING PERFORMANCE DATA
GSX130301B*/VSX130301A*
32
COOLING PERFORMANCE DATA
GSX130301B*/VSX130301A*
33
COOLING PERFORMANCE DATA
GSX130361B*/VSX130361A*
34
COOLING PERFORMANCE DATA
GSX130361B*/VSX130361A*
35
COOLING PERFORMANCE DATA
GSX130421B*/VSX130421A*
36
COOLING PERFORMANCE DATA
GSX130421B*/VSX130421A*
37
COOLING PERFORMANCE DATA
GSX130481B*/VSX130481A*
38
COOLING PERFORMANCE DATA
GSX130481B*/VSX130481A*
39
COOLING PERFORMANCE DATA
GSX130601B*/VSX130601B*
40
COOLING PERFORMANCE DATA
GSX130601B*/VSX130601B*
41
COOLING PERFORMANCE DATA
GSX130363A*
42
COOLING PERFORMANCE DATA
GSX130363A*
43
COOLING PERFORMANCE DATA
GSX130483A*
44
COOLING PERFORMANCE DATA
GSX130483A*
45
COOLING PERFORMANCE DATA
GSX130484A*
46
COOLING PERFORMANCE DATA
GSX130484A*
47
COOLING PERFORMANCE DATA
GSX130603A*
48
COOLING PERFORMANCE DATA
GSX130603A*
49
COOLING PERFORMANCE DATA
GSX130604A*
50
COOLING PERFORMANCE DATA
GSX130604A*
51
PERFORMANCE DATA
PERFORMANCE TEST
All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor
air cubic feet per minute (CFM) as listed in the Performance Data Sheets:
If conditions vary from this, results will change as follows:
1. As indoor dry bulb temperatures increase, a slight increase will occur in indoor air temperature drop (Delta T). Low and
high side pressures and power will not change.
2. As indoor CFM decreases, a slight increase will occur in indoor temperature drop (Delta T). A slight decrease will
occur in low and high side pressures and power.
A properly operating unit should be within plus or minus 2 degrees of the subcooling value shown in the installation
instructions.
A properly operating unit should be within plus or minus 3 degrees of the typical (Delta T) value shown.
A properly operating unit should be within plus or minus 10 PSIG of the HI PR shown.
A properly operating unit should be within plus or minus 5 PSIG of the LO PR shown.
A properly operating unit should be within plus or minus 3 Amps of the typical value shown.
NOTE: Pressures are measures at the liquid and suction service valve ports.
52
WIRING DIAGRAMS
GSX130[18-60]1A*
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
Y L N R O O T A C
C E O L N T P O
E L U B D E O T R E N T A L
Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
53
GSX130[18-60]1B*/GSX130181C*
VSX130[18-60]1A*
WIRING DIAGRAMS
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
L Y N O R O T A T C N O C E P O L
L E B U O E D A T N R E T A L
Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
54
WIRING DIAGRAMS
VSX130181B*
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
55
WIRING DIAGRAMS
GSX130[36-60][3,4]A*
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
56
|