Goodman Mfg Co LP Air Conditioner CE COMMERCIAL SPLIT SYSTEM AIR CONDITIONER User Manual

CE COMMERCIAL  
SPLIT SYSTEM AIR CONDITIONER  
PRODUCT SPECIFICATIONS  
The CE Commercial 10-ton split system air  
conditioner features the unique Goodman®  
sound control top design for quiet operation  
and is designed for ground-level or rooftop  
mount application.  
Standard Features  
• Single-scroll compressor with crankcase heater  
• Quiet operating top discharge  
• Permanently lubricated condenser motor  
• Copper tube/aluminum n coil  
• Brass suction ball valve and liquid front-seating shut-off  
valve with sweat connections  
• Large-capacity liquid line lter dryer  
• High- and low-pressure switches  
• Contactor with lug connections  
• Ground lug connection  
• ETL Listed  
Cabinet Features  
• Unique Goodman® sound control top design  
• Steel louver coil guard protects the coil from  
damage and adds strength to unit  
• Bottom pan rails elevate unit above slab  
• Heavy-gauge galvanized-steel cabinet  
• Attractive Architectural Gray powder-paint nish with 500-  
hour salt-spray approval  
50 HZ, 10-TON  
• When properly anchored, meets the 2001 Florida Building  
Code unit integrity requirements for  
hurricane-type winds  
NOMINAL COOLING CAPACITY:  
120,000 BTU/H [35.2 KW]  
SS-CE120  
11/06  
Supersedes 10/06  
PRODUCT SPECIFICATIONS  
SPECIFICATIONS  
Capacities  
CE120-5  
114,000  
9.0  
Condenser Fan / Coil  
Horsepower - RPM  
Fan Diameter/ # Fan Blades  
Outdoor Nominal CFM  
Face Area (ft²)  
CE120-5  
1-930  
26/3  
Nominal Cooling (BTU/h)  
EER¹  
Decibels  
84  
4,400  
29.4  
Compressor  
RLA / LRA  
17.2 / 118  
380-420  
Rows Deep/ Fins per Inch  
Fin Type  
1/22  
Volts  
Ripple  
40  
Condenser Fan Motor  
Horsepower / FLA  
Volts  
Coil No. of Tubes  
1 / 2  
380  
Coil Tube Diameter  
Electrical Data  
”  
Refrigeration System  
Liquid Valve Size (“O.D.)  
Suction Valve Size (“O.D.)  
Valve Type  
Voltage-Hz / Phase  
Min. Circuit Ampacity²  
Max. Overcurrent Protection³  
Min / Max Volts  
380/415-50/3  
23.6  
”  
1”  
40 amps  
342/456  
½” or ¾”  
296 [134]  
Sweat  
32  
Refrigerant Charge  
Power Supply Conduit Size  
Ship Weight (lbs-[kg])  
1 Energy Efficiency Ratio  
2 Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.  
3 May use fuses or HACR-type circuit breakers of the same size as noted.  
Note: Always check the S&R plate for electrical data on the unit being installed.  
PERFORMANCE RATINGS  
Cooling Capacity  
Outdoor  
Indoor Unit  
dBs  
Unit  
Total BTU/h  
114,000  
Sensible BTU/h  
83,000  
EER¹  
9.0  
kWI²  
12.67  
12.67  
AR-120-2  
CE120-5  
84  
(2) CA*F4860*6*  
114,000  
83,000  
9.0  
1 Energy Efficiency Ratio  
2 kWI = Compressor + Indoor Blower + Outdoor Fan Watts  
SS-CE120  
3
PRODUCT SPECIFICATIONS  
EXPANDED PERFORMANCE RATINGS — CE120-5 / AR120-00-5  
4
SS-CE120  
PRODUCT SPECIFICATIONS  
EXPANDED PERFORMANCE RATINGS— CE120-5 / AR120-00-5 (CONT.)  
SS-CE120  
5
PRODUCT SPECIFICATIONS  
DIMENSIONS  
W
D
H
Dimensions  
W x D x H  
Model  
CE120-5  
35½ x 35½ x 41½  
6
SS-CE120  
PRODUCT SPECIFICATIONS  
SCHEMATIC DIAGRAM  
LVJB  
CONTROL BOX  
OUTDOOR POWER SUPPLY  
SEE RATING PLATE  
YL  
BL  
Y
C
NOTE 1  
T1  
T3  
L1  
T2  
L3  
L2  
C
C
C
LVJB  
IO  
COLOR CODE  
L2  
BK --------------- BLACK  
BL --------------- BLUE  
C
COMP  
BR --------------- BROWN  
L1  
YL  
OR --------------- ORANGE  
FC  
L3  
PU --------------- PURPLE  
RD --------------- RED  
WH -------------- WHITE  
YL --------------- YELLOW  
YL/BK ---------- YELLOW w/BLACK  
HASH MARKS  
IO  
BL  
BK RD  
BK RD  
WIRING CODE  
FACTORY WIRING  
HIGH VOLTAGE  
LOW VOLTAGE  
OPTIONAL HIGH VOLTAGE  
CM  
T2 T3  
YL  
T1  
L1  
CH  
YL/BK  
L2 L3  
C
FIELD WIRING  
HIGH VOLTAGE  
LOW VOLTAGE  
RD  
BK  
BK  
C
PU  
FC  
BR  
BK  
LPS  
YL/BK  
HPS  
BK  
YL/BK  
BK  
Y
C
COMPONENT CODE  
C --------------- CONTACTOR  
CM ------------ OUTDOOR FAN MOTOR  
COMP -------- COMPRESSOR  
FC ------------- FAN CAPACITOR  
IO -------------- INTERNAL OVERLOAD  
LVJB ---------- LOW VOLTAGE JUNCTION BOX  
CH ------------ CRANKCASE HEATER  
LPS  
YL  
EQUIPMENT GROUND  
USE COPPER  
CONDUCTORS ONLY  
BK  
YL  
L3  
NOTES:  
1) TO INDOOR UNIT LOW VOLTAGE  
TERMINAL BLOCK & INDOOR  
THERMOSTAT.  
RD  
L1  
MAIN  
AUX  
BK  
BK  
PU  
BR  
BK  
CH  
HPS  
USE N.E.C. CLASS 2 WIRE  
CONTROLS SHOWN WITH THERMOSTAT IN 'OFF' POSITION.  
IO  
LPS ----------- LOW PRESSURE SWITCH  
HPS ---------- HIGH PRESSURE SWITCH  
L2  
COMP  
BK  
CM  
0140R00092  
ACCESSORIES  
Model  
FSK01A¹  
CHTD18-60  
CHT18-60  
LA-01  
Description  
Freeze Protection Kit  
Digital room thermostat with 1-stage cool/1-stage heat  
Standard room thermostat with 1-stage cool/1-stage heat  
Low Ambient Kit  
¹
Installed on indoor coil  
SS-CE120  
7
PRODUCT SPECIFICATIONS  
NOTES  
Goodman Manufacturing Company, L.P., reserves the right to discontinue, or change at any time, specications or designs without notice or without  
incurring obligations. Copyright © 2006-2008 • Goodman Manufacturing Company, L.P. • Houston, Texas • Printed in the USA.  
8
SS-CE120  

BT RESPONSE 15 User Manual
Canon PIXMA PRO 100 Wireless Inkjet Digital Photo Printer 6228B002 User Manual
Champion Manufacturing D1EB036 User Manual
Creda COLDAIR 56030 User Manual
Crown Equipment Walkie Stackers WE 2300 Series User Manual
Danby DAC5088M User Manual
Danby DESIGNER DAC12304D User Manual
Epson Stylus NX410 Series User Manual
Friedrich MR18Y3F User Manual
Honeywell Air Cleaner 17000 User Manual