2 0 1 0
Room Air Conditioners
T
e
m
p
e
r
a
t
u
r
e
C
o
o
le
r
W
a
rm
e
r
C
n
o
o
l
P
o
w
e
r
F
a
F
a
n
M
o
n
O
n
ly
e
y
S
p
e
e
d
T
im
e
r
S
a
O
v
e
p
e
®
r
r
a
rt
t
O
n
/
io
n
S
ta
S
to
p
S
e
t
H
r.
R-410A Models
Cool Only
115-Volt: XQ05M10A, XQ06M10A, XQ08M10A, XQ10M10A
Cool with Electric Heat
115-Volt: EQ08M11A
X-Star-ServMan (4-10)
IMPORTANT SAFETY INFORMATION
The information contained in this manual is intended for use by a qualified service technician who is familiar
with the safety procedures required for installation and repair, and who is equipped with the proper tools and
test instruments required to service this product.
Installation or repairs made by unqualified persons can result in subjecting the unqualified person making
such repairs as well as the persons being served by the equipment to hazards resulting in injury or electrical
shock which can be serious or even fatal.
Safety warnings have been placed throughout this manual to alert you to potential hazards that may be
encountered. If you install or perform service on equipment, it is your responsibility to read and obey these
warnings to guard against any bodily injury or property damage which may result to you or others.
Your safety and the safety of others are very important.
We have provided many important safety messages in this manual and on your appliance. Always read
and obey all safety messages.
This is a Safety Alert symbol.
This symbol alerts you to potential hazards that can kill or hurt you and others.
All safety messages will follow the safety alert symbol with the word “WARNING”
or “CAUTION”. These words mean:
You can be killed or seriously injured if you do not follow instructions.
WARNING
You can receive minor or moderate injury if you do not follow instructions.
CAUTION
All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury,
and tell you what will happen if the instructions are not followed.
A message to alert you of potential property damage will have the
word “NOTICE”. Potential property damage can occur if instructions
are not followed.
NOTICE
PERSONAL INJURY OR DEATH HAZARDS
ELECTRICAL HAZARDS:
•
Unplug and/or disconnect all electrical power to the unit before performing inspections,
maintenance, or service.
•
•
•
Make sure to follow proper lockout/tag out procedures.
Always work in the company of a qualified assistant if possible.
Capacitors, even when disconnected from the electrical power source, retain an electrical charge
potential capable of causing electric shock or electrocution.
•
•
Handle, discharge, and test capacitors according to safe, established, standards, and approved
procedures.
Extreme care, proper judgment, and safety procedures must be exercised if it becomes necessary
to test or troubleshoot equipment with the power on to the unit.
2
•
•
Do not spray or pour water on the return air grille, discharge air grille, evaporator coil, control panel,
and sleeve on the room side of the air conditioning unit while cleaning.
Electrical component malfunction caused by water could result in electric shock or other electrically
unsafe conditions when the power is restored and the unit is turned on, even after the exterior is dry.
•
•
•
•
•
•
•
Never operate the A/C unit with wet hands.
Use air conditioner on a single dedicated circuit within the specified amperage rating.
Use on a properly grounded outlet only.
Do not remove ground prong of plug.
Do not cut or modify the power supply cord.
Do not use extension cords with the unit.
Follow all safety precautions and use proper and adequate protective safety aids such as: gloves,
goggles, clothing, adequately insulated tools, and testing equipment etc.
•
Failure to follow proper safety procedures and/or these warnings can result in serious injury or death.
REFRIGERATION SYSTEM HAZARDS:
•
•
•
Use approved standard refrigerant recovering procedures and equipment to relieve pressure before
opening system for repair.
Do not allow liquid refrigerant to contact skin. Direct contact with liquid refrigerant can result in minor
to moderate injury.
Be extremely careful when using an oxy-acetylene torch. Direct contact with the torch’s flame or hot
surfaces can cause serious burns.
•
•
•
Make sure to protect personal and surrounding property with fire proof materials.
Have a fire extinguisher at hand while using a torch.
Provide adequate ventilation to vent off toxic fumes, and work with a qualified assistant whenever
possible.
•
•
•
Always use a pressure regulator when using dry nitrogen to test the sealed refrigeration system for
leaks, flushing etc.
Make sure to follow all safety precautions and to use proper protective safety aids such as: gloves,
safety glasses, clothing etc.
Failure to follow proper safety procedures and/or these warnings can result in serious injury or death.
MECHANICAL HAZARDS:
•
Extreme care, proper judgment and all safety procedures must be followed when testing,
troubleshooting, handling, or working around unit with moving and/or rotating parts.
•
Be careful when, handling and working around exposed edges and corners of sleeve, chassis, and
other unit components especially the sharp fins of the indoor and outdoor coils.
•
•
Use proper and adequate protective aids such as: gloves, clothing, safety glasses etc.
Failure to follow proper safety procedures and/or these warnings can result in serious injury or death.
3
PROPERTY DAMAGE HAZARDS
FIRE DAMAGE HAZARDS:
•
•
•
•
•
•
•
Read the Installation/Operation Manual for this air conditioning unit prior to operating.
Use air conditioner on a single dedicated circuit within the specified amperage rating.
Connect to a properly grounded outlet only.
Do not remove ground prong of plug.
Do not cut or modify the power supply cord.
Do not use extension cords with the unit.
Failure to follow these instructions can result in fire and minor to serious property damage.
WATER DAMAGE HAZARDS:
•
Improper installation maintenance, or servicing of the air conditioner unit, or not following the above
Safety Warnings can result in water damage to personal items or property.
•
•
•
Insure that the unit has a sufficient pitch to the outside to allow water to drain from the unit.
Do not drill holes in the bottom of the drain pan or the underside of the unit.
Failure to follow these instructions can result in result in damage to the unit and/or minor to serious
property damage.
INTRODUCTION
This service manual is designed to be used in conjunction with the operation and installation manual provided
with each unit.
This service manual was written to assist the professional HVAC service technician to quickly and accurately
diagnose and repair any malfunctions of this product.
This manual, therefore, will deal with all subjects in a general nature. (i.e. All text will pertain to all models).
IMPORTANT:
It will be necessary for you to accurately identify the unit you are
servicing, so you can be certain of a proper diagnosis and repair.
(See Unit Identification.)
Compressor
Liquid Filter Driers
Condenser Coil
Discharge Air
Front Cover
System Controls
Outdoor Grille
Sleeve
Evaporator Coil
Return Air Grille/Filter
Blower Wheel
Blower Motor
Condenser Fan Blade
Basepan
4
UNIT IDeNTIfICATION
Model Number Code
X Q 08 M 1 0 A
8th Digit – Engineering
Major change
1st Digit – Function
E = Electric Heat
X = Straight Cool
7th Digit – Options
0 = Straight Cool
1 = 1 KW Heat Strip, Nominal
2nd Digit
Q = Q-Star Chassis Size
6th Digit – Voltage
1 = 115 Volts
5th Digit
Alphabetical Modifier
3rd and 4th Digit - Approximate
BTU/HR in 1000s (Cooling)
Heating BTU/Hr capacity listed in the
Specification/Performance Data Section
RAC Serial Number Identification Guide
Serial Number
Decade Manufactured
A
K
A
R
00001
L=0
A=1
B=2
C=3
D=4
E=5
F=6
G=7
H=8
J=9
Production Run Number
Year Manufactured
Product Line
R = RAC
A=1
B=2
C=3
D=4
E=5
F=6
G=7
H=8
J=9
K=0
Month Manufactured
A=Jan D=Apr G=Jul K=Oct
B=Feb E=May H=Aug L=Nov
C=Mar F=Jun J=Sept M=Dec
5
PeRfORMANCe DATA
R-410A
REF.
EVAP. AIR TEMP. DEG. F
OPERATING PRESSURES
ELECTRICAL RATINGS
BREAKER FUSE
60 Hertz Amps
COOLING
CONDENSER
Discharge Temp Suction Temp Super Heat Sub-Cooling
Voltage
PERFORMANCE DATA*
TEMPERATURE DEG. F
Temp.
Drop F.
Locked Rotor Charge in
Discharge Air
Suction
Discharge
Amps Cool Amps Heat
Amps
OZ.
XQ05M10A
XQ06M10A
XQ08M10A
XQ10M10A
EQ08M11A
57
54
51
47
49
23
26
29
33
31
117
120
119
131
120
133
152
160
176
162
60
63
63
59
60
5
19
18
25
32
27
157
150
138
132
133
410
410
420
490
420
4.5
4.9
6.3
9.8
24.0
25.0
32.0
57.0
32.0
27.0
21.0
25.5
24.0
25.5
115
115
115
115
115
15
15
15
15
15
12
13
12
14
7.0
7.6
*Rating Conditions: 80 degrees F, room air temp. & 50% relative humidity, with 95 degree F, outside air temp & 40% relative humidity, all systems use R410A.
Energy
Estimated
Yearly
Room Side
Air
Moisture
Net
Cooling
Capacity Btu Capacity Btu
Heating
Volts
Rated
Cooling
Amps
Cooling
Watts
Heating
Amps
Heating
Watts
Ratio
EER
Operating Removal Circulation
Weight
Sleeve Lbs
Model
COP
Cost
Pints/HR
CFM
XStar
®
XQ05M10A
XQ06M10A
XQ08M10A
XQ10M10A
5500
6000
7500
9500
—
—
—
—
115
115
115
115
4.5
4.9
6.9
9.0
491
500
701
970
—
—
—
—
—
—
—
—
11.2
12.0
10.7
9.8
$39
†
1.0
1.0
1.7
2.5
170
175
175
180
Q
Q
Q
Q
72
72
71
71
$56
$56
XStar
®
Electric Heat
EQ08M11A 7500
4000
115
6.3
701
11.2
1290
2.8
10.7
$56
1.9
175
Q
72
As an ENERGY STAR® partner, Friedrich Air Conditioning Co. has determined that the selected ENERGY STAR® () models
meet the ENERGY STAR®
Estimated yearly operating cost based on a 2007 national average electricity cost of 10.65 cents per kWh.
† The estimated yearly operating cost of this model was not available at the time the range was published.
Installation Information / Sleeve Dimensions
Thru-the-wall Installation
Finished Hole
Depth Shell Depth to
Window Width
Minimum
Extension
Into Room*
Minimum
Extension
Outside*
with Front
Louvers
Sleeve
Height
Width
19
Minimum** Maximum Height
Width
Max. Depth
3
Q
14"
21 /8"
22"
42"
14 ¼"
20"
8 ½”
¾
"
8
½"
5
½"
10 ¾"
* Minimum extensions when mounted in a window.
** Minimum widths achieved using one side curtain assembly as opposed to both in a standard installation.
Circuit Rating/ Breaker
Circuit Rating
Breaker or
T-D Fuse
Plug
Face
(NEMA#)
Wall Outlet
Appearance
Power Cord
Length (ft.)
Model
XQ05M10A, XQ06M10A,
XQ08M10A, XQ10M10A
EQ08M11A
7
125V - 15A
5 - 15P
6
Front
SIDE VIEW
(
Window Mounting Kits
Heat/Cool Models
Kit No.
EQ08M11A
WIKQ
Friedrich heat/cool models include accessories for
thru-the-wall installation only. Window mounting requires
use of optional accessory kit as listed above.
6
eleCTRICAl DATA
WARNING
ELECTRIC SHOCK HAZARD
Turn off electric power before service or
installation.
All electrical connections and wiring MUST be
installedbyaqualifiedelectricianandconformto
the National Electrical Code and all local codes
which have jurisdiction.
Failure to do so can result in personal injury or
death.
NOTICE
FIRE HAZARD
Not following the above WARNING could result in fire or
electically unsafe conditions which could cause moderate
or serious property damage.
Read, understand and follow the above warning.
Wire Size
Use ONLY wiring size recommended for single outlet branch circuit.
Fuse/Circuit Breaker
Use ONLY the correct HACR type and size fuse/circuit breaker. Read electrical ratings on unit’s
rating plate. Proper circuit protection is the responsibiity of the homeowner.
Grounding
Unit MUST be grounded from branch circuit through service cord to unit, or through separate
ground wire provided on permanently connected units. Be sure that branch circuit or general
purpose outlet is grounded.
Receptacle
The field supplied outlet must match plug on service cord and be within reach of service cord.
Do NOT alter the service cord or plug. Do NOT use an extension cord. Refer to the table above
for proper receptacle and fuse type.
The consumer - through the AHAM Room Air Conditioner Certification Program - can
be certain that the AHAM Certification Seal accurately states the unit’s cooling and
heating capacity rating, the amperes and the energy efficiency ratio.
*HACR: Heating Air Conditioning and Refrigeration
7
WARNING: Before operating unit
Make sure the wiring is adequate for your unit.
If you have fuses, they should be of the time delay type. Before you install
or relocate this unit, be sure that the amperage rating of the circuit breaker
or time delay fuse does not exceed the amp rating listed in Figure 1.
WARNING
ELECTRICAL SHOCK HAZARD
Make sure your electrical receptacle has the same
configuration as your air conditioner’s plug. If
different, consult a Licensed Electrician.
Do not use plug adapters.
Do not use an extension cord.
Do not remove ground prong.
DO NOT use an extension cord.
The cord provided will carry the proper amount of electrical power to the
unit; an extension cord will not.
Always plug into a grounded 3 prong outlet.
Failure to follow these instructions can result in
electrical shock, serious injury or death.
Make sure that the receptacle is compatible with
the air conditioner cord plug provided.
This insures proper grounding. If you have a two prong receptacle you
will need to have it replaced with a grounded receptacle by a certified
electrician. The grounded receptacle should meet all national and local
codes and ordinances. Under no circumstances should you remove the
ground prong from the plug. You must use the three prong plug furnished
with the air conditioner.
CIRCUIT RATING
REQUIRED WALL
OR TIME DELAY
RECEPTACLE
FUSE
MODEL
NEMA
NO.
AMP
VOLT
XQ05
EQ08
• XQ06 • XQ08 • XQ10
15
125
5-15R
Test the power cord
Figure 1
All Friedrich room air conditioners are shipped from the factory with a
Leakage Current Detection Interrupter (LCDI) equipped power cord. The
LCDI device meets the UL and NEC requirements for cord connected air
conditioners.
To test your power supply cord:
1. Plug power supply cord into a grounded 3 prong outlet.
2. Press RESET (See Figure 2).
RESET
TEST
3. Press TEST (listen for click; Reset button trips and pops out).
WARNING
TEST BEFORE EACH USE
1. PRESS RESET BUTTON
2. PLUG LDCI INTO POWER
RECEPTACLE
3. PRESS TEST BUTTON,
RESET BUTTON SHOULD
POP UP
4. Press and release RESET (listen for click; Reset button latches and
remains in). The power supply cord is ready for operation.
4. PRESS TEST BUTTON,
FOR USE
DO NOT USE IF ABOVE TEST
FAILS
NOTE: LCDI device is not intended to be used as a switch.
WHEN GREEN LIGHT IS ON
IT IS WORKING PROPERLY
Once plugged in the unit will operate normally without the need to reset
the LCDI device.
If the device fails to trip when tested or if the power supply cord is
damaged it must be replaced with a new supply cord from the manufac-
turer. We recommend you contact our Technical Assistance Line at
(800) 541-6645 ext. 845. To expedite service, please have your model
and serial number available.
Figure 2
For the best cooling performance and highest energy efficiency
Keep the filter clean
Insulation
Make sure that your air conditioner is always in top performing condition
by cleaning the filter regularly.
Good insulation will be a big help in maintaining desirable comfort levels.
Doors should have weather stripping. Be sure to caulk around doors and
windows.
Provide good air flow
Make sure the airflow to and from the unit is clear. Your air conditioner puts the
conditioned air out at the top of the unit, and takes in unconditioned air at the
bottom. Airflow is critical to good operation. It is just as important on the outside
of the building that the airflow around the unit exterior is not blocked.
Proper installation ofchassis seal gasket
Make sure the seal gasket has been installed properly to minimize noise
and improve efficiency. If the chassis seal gasket has not been installed,
please
refer to Step 14 of the installation instructions.
Also, if you switch from Cool mode to Fan Only, and switch back to
COOL mode, there is a three minute delay before the compressor comes
back on.
Unit placement
If your air conditioner can beplaced in a window or wall that isshaded by atree
or another building, the unit will operate even more efficiently. Using drapes or
blinds on the sunny side of the dwelling will also add to your unit’s efficiency.
8
How to operate the Friedrich room air conditioner (XQ models)
To start unit
Figure 3
8
9
2
3
4
1
If your air conditioner is installed and plugged into a proper receptacle, it is
ready to go. The firsttimethe unit is started, thecompressorwilldelay for three
minutes. See Automatic Component Protection on the following page.
X Star
Touch the Power button once. The unit will automatically be in Cool
mode with the temperature set at 75°F (24°C) and the fan speed at
F1, the sleep setting.
1
PM
Power
To set mode of operation
When you rst turn the unit on, it will be in the Cool mode (light on), with
constant fan.
Cool
Mode
Fan
®
MoneySaver
Speed
Fan Only
Clock
Touch the Mode button once to activate the MoneySaver® (light on).
2
Timer
Set
Start Time
On/Off
Hour
Temp/Hour
MoneySaver® is a feature that cycles the fan with the compressor
so that the fan does not run all the time. This saves energy and
improves dehumidi cation. Or you may prefer constant fan for more
air movement (to return to constant fan, touch the Mode button two
more times).
Stop Time
6
5
13
10 11 12
7
In order to run the fan by itself, do the following:
To set the hour clock
Continuing fromMoneySaver® mode (light on), touchtheModebutton
once to activate the FAN ONLY feature (light on).
3
Touch the Set Hour button to see the current setting (clock light
10
comes on). The number that is displayed is the approximate time
The FAN ONLY setting will circulate air in the room without the com-
(hour only). Use the and
buttons to change the settings. BE
pressor coming on.
SURE TO SET A.M. AND P.M. ACCORDINGLY. (P.M. is indicated
by a red light in the upper left corner of the display).
To adjust temperature
Use the Mode button to select either the COOL or MoneySaver®
function
To set the timer
NOTE: Set the HOUR CLOCK before attempting to set timer functions.
4
You can set the START and STOP times a minimum of one hour apart, and
a maximum of twenty-three hours apart.
COOLER – Touch the
button to lower the room air temperature.
button to raise the room air temperature.
and buttons at the same time to switch the
5
6
7
WARMER – Touch the
After setting the time, press the Set Hour button once (Start light
11
12
comes on). Use the
and
buttons to select the time that the
Press both the
temperature readout from Fahrenheit (°F) to Celsius (°C).
unit will START.
Repeat step 7 to switch from °C back to °F.
After selecting the STARTtime, press theSetHourbutton once more
(Stop light comes on). Use the and buttons to select the time
To adjust fan speed
that the unit will STOP. After selecting the stopping time, press the
Set Hour button once.
Touch the FanSpeedbutton to see the current setting. Touch it again
to change speed. F1 is the lowest setting (SLEEP SETTING / LOW),
F2 is MEDIUM, and F3 is HIGH.
8
Press the Timer On/Off button (light turns on) to activate the timer
function. To deactivate this function, press theTimer On/Off button
once again (light turns off). Once the on and off times have been
selected, they will remain in memory and cycle daily until changed.
13
To activate Smart Fan
NOTE: If the unit is unplugged or the power is interrupted, the HOUR
must be reset or the Timer On/Off will not function when desired.
There is a fourth option, SF, when selecting the fan speed. This is
the SMART FAN function. SMART FAN DOES NOT OPERATE IN
CONJUCTION WITH THE FAN ONLY MODE.
9
Automatic component protection
Smart Fan will adjust the fan speed automatically to maintain the
desired comfort level. For example, if the outside doors in your home
are opened for an extended period of time, or more people enter a
room, Smart Fan may adjust to a higher fan speed to compensate
for the increased heat load. This keeps you from having to adjust the
fan speed on your own.
Your unit is equipped with Automatic Component Protection. To protect the
compressor of the unit, there is a three minute start delay if you turn the unit
off or if power is interrupted. The fan operationwill not be affected. Also, if you
switch from Cool mode to Fan Only, and switch back to Cool mode, there
is a three minute delay before the compressor comes back on.
9
How to use the remote control (XQ models)
To start unit
To set the timer
NOTE: You can set the START and STOP times a minimum of one hour
POWER - Press the Power button once. The unit will automatically
start in the mode and fan speed it was last left on.
1
apart, and a maximum of 23 hours apart.
TIMER START - Press Start to view the current start time for cooling.
Continue pressing the Start button until you arrive at the start time
you desire. The start time for cooling will then be set.
9
To set mode of operation
COOL - Press the Cool button to automatically switch the operating
mode to COOL.
2
3
4
TIMER STOP - Press the Stop button. Continue pressing the Stop
button until you arrive at the stop time you desire. The stop time for
cooling will then be set.
10
11
FAN ONLY - Press the Fan Only button if you want to run the fan
only.
TIMER ON / OFF - Press the On/Off button to activate (light on) or
deactivate (light off) the timer. Once the on and off times have been
selected, they will remain in memory and cycle daily until changed.
MoneySaver® - Press the MoneySaver® button to activate the
MoneySaver® feature. This feature cycles the fan with the compres-
sor so that the fan does not run all the time.
NOTE: If the unit is unplugged or the power is interrupted, the Set Hr.
function must be reset or the On/Off function will not work.
To adjust temperature setting
WARMER - Press the Warmer button to raise the temperature
setting.
5
COOLER - Press the Cooler button to lower the temperature
setting.
6
Temperature
Cooler
Warmer
Power
6
5
To adjust fan speed
Cool
2
3
1
4
7
8
FAN SPEED - Press the Fan Speed button to see the current set-
ting. Press again to change the fan speed. F1 is the lowest setting
(SLEEP / LOW), F2 is MEDIUM, F3 is HIGH, and SF is the SMART
FAN setting.
7
Fan
Fan
Money
Saver®
Only
Speed
Timer Operation
On/Oꢀ Start
Stop Set Hr.
11
9
10
To set the hour clock
SET HOUR CLOCK - Press Set Hr. once to see the current clock
setting. Continue pressing the button until you arrive at the current
time (Hour only). Minutes are not shown on the display. Make sure
that the A.M. / P.M. setting is correct.
8
Additional RC1 wireless remote controls can be purchased from your Friedrich dealer.
How To Operate The EQ08
Function Control Knob
The left knob is a six position control that allows you to
select heat or cool in either low speed or high speed. Plus
you can select fan only if you wish.
Thermostat Knob
The right hand knob is the thermostat - turn it clockwise for
cooler, counter-clockwise for warmer.
10
eleCTRONIC CONTROl SeQUeNCe Of OPeRATION
MODE CONTROL
FAN ONLY MODE
The mode control pad(s) allow the selection of the operating
modes of the unit.
When in the FAN ONLY mode, the compressor will not
operate. The fan will run continuously at the user-selected
speed (see “Fan Speed Set” below). Smart Fan is not
available in FAN ONLY Mode.
There is a two second delay before the mode activates its
appropriate relay.
FAN SPEED SET
OPERATING SEQUENCE / CHARACTERISTICS
AND FEATURES
Compressor Operation
The run state of the compressor is determined by the
difference between the indoor ambient temperature and
the set temperature. See specific mode of operation for
details.
XQ fan speed is changed by pressing FAN SPEED button
and scrolling through F1, F2, F3 and SF (Smart Fan) in the
digital display.
Therewillbea2seconddelaybeforethefanspeedchanges
to prevent unnecessary switching of the relays during fan
speed selection.
Compressor Time Delay: 180 seconds
This feature is initiated every time the compressor is de-
energized, either due to:
(1) satisfying the temperature set point
(2) changing mode to fan only
SMART FAN
On the XQ model, smart fan is activated by pressing the
FAN SPEED button and scrolling through speeds until
“SF” appears in the digital display. Using the remote
control, Smart Fan is selected by the fourth push of Fan
Speed button.
(3) a power interruption or
(4) turning the unit off
Smart fan changes fan speeds based on the temperature
differential between the ambient and set temperatures.
The compressor is also time delayed for 3 minutes when the
control is first plugged in or power is restored after failure.
When the compressor cycles off as a result of satisfying the
“load”, the time delay is typically timed out during the off
cycle. Compressor time delay is bypassed by “Test Mode”.
CHECKING ROOM TEMPERATURE
Check the room temperature at the electronic control
pad by pressing the “FAN SPEED” button and the
“TEMP ” button at the same time on XQ models.
Return Air Temperature Sensor
The control range is 60°F to 90°F +/- 2.0°F.
The indoor temperature will display for 10 seconds. Indoor
temperature can be viewed in all modes, including the
TEST mode. The display can be changed back to SET
temperature by pressing any key, except the ON/OFF
button, or after 10 seconds has elapsed.
Frost Protection Sensor
Temperature settings:
Disable the compressor when sensing 30 +/- 3°F for 2 min.
continuously.
Enable compressor @ 55 +/- 5°F.
KEEP ALIVE
The fan should not be affected by the Frost Protection. It
should continue to function normally if freeze protection is
called for.
The electronic control has a memory to retain all functions
and status as set up by the user in the event of a power
failure. Once power is restored to the unit there is a two
second delay before the fan comes on and approximately
three minutes delay before the compressor is activated,
providing that the mode was set for cooling and the set
point temperature has not been met in the room.
COOL MODE FOR XQ MODELS
When in the COOL mode, the control will turn on the
compressor when the indoor temperature is 1.5°F above the
set point and turn off the compressor when the ambient gets
below the set point by 1.5°F. The fan will run continuously.
REbOOT/RESET THE CONTROL bOARD
With unit on, press “MODE” and “TEMP/HOUR ” buttons
simultaneously for 10 seconds. If the panel will reboot, you
will hear the fan come on and the temperature window will
read 60 degrees. If this happens, turn the unit off for about
10 seconds and then turn it back on to finish the reboot
cycle. If the panel does not reboot, you possibly need to
replace it.
MONEY SAVER MODE
When in MONEY SAVER mode, the system will be turned
on when the indoor temperature gets above the set point by
0.75°F and turns off when the indoor temperature gets below
the set point by 0.75°F. The fan will turn on 5 seconds before
the compressor and turn off 5 seconds after the compressor
stops. If the compressor is delayed the fan will continue to
run while the compressor restarts. If the thermostat remains
satisfied for more than approximately 9 minutes, the fan will
turn on for a period of 90 seconds for air sampling. Operation
in MONEY SAVER mode will light both the MONEY SAVER
and COOL indicators.
11
FUNCTIONAL COMPONENT DEFINITIONS
MECHANICAL COMPONENTS
Plenum assembly Diffuser with directional louvers used
to direct the conditioned airflow.
Blower wheel Attaches to the indoor side of the fan motor
shaft and is used for distributing unconditioned, room side
air though the heat exchanger and delivering conditioned
air into the room.
Slinger fan blade Attaches to the outdoor side of the fan
motor shaft and is used to move outside air through the
condenser coil, while slinging condensate water out of the
base pan and onto the condenser coil, thus lowering the
temperature and pressures within the coil.
ELECTRICAL COMPONENTS
Thermostat Used to maintain the specified room side
comfort level
System switch Used to regulate the operation of the fan
motor, the compressorortoturnthe unitoff. Fortroubleshoot-
ing, refer to the wiring diagrams and schematics in the back
of this service manual.
Capacitor Reduces line current and steadies the voltage
supply, while greatly improving the torque characteristics of
the fan motor and compressor motor.
Smart Fan
Automatically adjusts the fan speed to main-
tain the desired room temp.
MoneySaver® switch When engaged, it sends the power
supply to the fan motor through the thermostat, which allows
for a cycle-fan operation.
Fan Motor Dual-shafted fan motor operates the indoor
blower wheel and the condenser fan blade simultaneously.
Heatingelement Electricresistanceheater, availablein
EQ08 model.
Heat anticipator Used to provide better thermostat and
room air temperature control.
HERMETIC COMPONENTS
Compressor Motorizeddeviceusedtocompressrefrigerant
through the sealed system.
Capillarytube Acylindrical meter deviceusedto evenly dis-
tribute the flow of refrigerant to the heat exchangers (coils.)
12
COMPONeNTS TeSTING
TESTING THE ELECTRONIC CONTROL
ERROR CODE LISTINGS
bOARDS FOR XQ MODELS
E1 SHORT CYCLE SITUATION: Defined as (compressor
powered on before the three minute time delay ten times in
one hour. Investigate and correct short cycling problem.
X Star
PM
E2 KEYbOARD STUCK ERROR: If key button(s) are
pressed continuously for twenty seconds or more. If MODE
key is stuck, unit will default to cool. Exit Error Code
Mode to see if error “E2” is no longer displayed and unit is
functioning. Replace board if “E2” still displays after exiting
Error Code Mode.
Power
Cool
Fan
®
MoneySaver
Speed
Mode
Fan Only
Clock
Timer
On/Off
Set
Start Time
Stop Time
E3 FROST PRObE OPEN: Normal operation is allowed.
Ohm frost probe. Replace probe if ohm value not read. If
ohm value is present replace board.
Hour
Temp/Hour
E4 FROST PRObE SHORT: Normal operation allowed.
Replace probe.
Activating Test Mode:
Activate test mode by pressing at the same time the
“MODE” button and the “TEMP ” button on XQ
models. LEDs for Hour, Start, and Stop will blink 1 bps
while Test Mode is active.
E5 INDOOR PRObE OPEN: Control assumes indoor
ambient temperature is 90 degree F and unit will operate.
Ohm indoor probe. Replace probe if ohm value not read.
Test Mode has duration of 90 minutes. Test Mode can
be activated under any conditions, including Off. Test
Mode is cancelled by pressing the On/Off button,
unplugging the unit, or when the 90 minutes is timed
out. All settings revert to the factory default settings of
Cool, 75 degrees F, Timer and Set Hour features are
nonfunctional.
E6 INDOOR PRObE SHORT: Control assumes ambient
temperature is 90 degree F and unit will operate. Replace
probe.
NOTE: All Error Code displays for Frost & Indoor Probe
will allow unit to operate. Unit may or will ice up if faulty
components not replaced.
Test Mode overrides the three-minute lockout, all
delays for compressor and fan motor start / speed
change, and no delay when switching modes.
FROST PRObE SENSOR: disables compressor at 35
degrees F.
INDOOR PRObE SENSOR: Control range is 60 degrees F
to 90 degrees F +/- 2 degrees F.
Test Mode default settings are ON, Money Saver, 60
degrees F, and High fan speed.
Indoor temperature will be displayed by pressing:
(XQ units) The Fan Speed button and the “TEMP
button.
”
Activating Error Code Mode: (Submode of Test Mode)
Unit must be in Test Mode to enter Error Code Mode
The indoor temperature will be displayed for 10 seconds.
The display will change back to the Set Point temperature
by pressing any key button except for the On/Off button.
The indoor temperature can be viewed in all modes,
including test mode.
1. Activate Error Code Mode by pressing the “TIMER ON/
OFF” button on XQ models. LED for the “TIMER ON/OFF”
will flash 1 bps while Error Code Mode is active. Pressing
the “TEMP/HR
” button will display 00. Consecutive
presses will scroll through all error codes logged. Press
the “TEMP/HR ” button to see the reverse order of all
error codes logged. When the end of logged error codes is
reached the temperature set point will appear.
IMPORTANT: Error Codes are cleared from the
log by exiting from Error Code Mode. To exit on XQ
models, press Timer On/Off button. Or unplug unit to
exit Error Code Mode. Plug unit in after 5 seconds to
resume normal operation of unit.
13
COMPONeNTS TeSTING (Continued)
EQ08 SYSTEM CONTROL SWITCH - TEST
4. Turn thermostat knob counterclockwise to its warmest
position.
“EQ08” SYSTEM CONTROL SWITCH – TEST
5. Test for continuity - contacts should be open.
Turn knob to phase of switch to be tested. There must be
continuity as follows:
NOTE: The thermostat must be within the temperature
range listed to open and close.
1. “Fan Only” Position – between terminals “MS” and “H”
To maintain the comfort level desired, a cross ambient type
thermostat is used. The thermostat has a range from 60°
±2°F to 92° ±3°F. The thermostat bulb is positioned in front
of the evaporator coil to sense the return air temperature.
Thermostat malfunction or erratic operation is covered in
the troubleshooting section of this manual.
2. “Hi Cool” Position – between terminals “L1” and “C” and
“MS” and “H”
3. “Low Cool” Position – between terminals “L1” and “C”
and “MS” and “LO”
4. “Low Heat” Position – between terminals “L2” and “2”
and “MS” and “LO”
TEST:
Cooling/Heating Models: Remove wires from thermostat
and check continuity between terminal “2” (common) and
“3” for cooling. Check between terminals “2” (common)
and “1” for heating. Also check that contacts in thermostat
open after placing in either position. NOTE: Temperature
must be within range listed to check thermostat. Refer to
the troubleshooting section in this manual for additional
information on thermostat testing.
5. “Hi Heat” Position – between terminals “L2” and “2” and
“MS” and “H”
L1
System Control Switch
(EQ Models)
B1
L2
MS
THERMOSTAT ADJUSTMENT
No attempt should be made to adjust thermostat. Due
to the sensitivity of the internal mechanism and the
sophisticated equipment required to check the calibration,
it is suggested that the thermostat be replaced rather than
calibrated. Thermostat bulb must be straight to insure
proper performance.
C
H
2
LO
THERMOSTAT (“EQ08” Models)
This thermostat is single pole-double throw, cross ambient
with a range of 60° to 92°F and a differential of ±2°F. Terminal
“2” is common.
Thermostat
Thermostat
(EQ Model)
THERMOSTAT BULB LOCATION
The position of the bulb is important in order for the
thermostat to function properly. The bulb of the thermostat
should be located approximately 45° to a maximum of 60°
from horizontal. Also, do not allow the thermostat bulb to
touch the evaporator coil.
WARNING
ELECTRIC SHOCK HAZARD
Disconnect power to the unit before
servicing. Failure to follow this warning
could result in serious injury or death.
Thermostat Bulb Location
(EQ Model)
TEST:
Thermostat sensor holder 020
to be positioned between the
4th and 5th and 6th and 7th
rows of tubes from the bottom
of the coil at dimension shown
1. Remove leads from thermostat.
2. Turn thermostat knob clockwise to its coldest
position.
3. Test for continuity between the two terminals. Contacts
should be closed.
14
COMPONeNTS TeSTING (Continued)
FAN MOTOR
Asingle phase permanentsplit capacitor motor is usedto drive
the evaporator blower and condenser fan. A self-resetting
overload is located inside the motor to protect against high
temperature and high amperage conditions.
Many motor capacitors are internally fused. Shorting the
terminals will blow the fuse, ruining the capacitor. A 20,000
ohm 2 watt resistor can be used to discharge capacitors
safely. Remove wires from capacitor and place resistor
across terminals. When checking a dual capacitor with
a capacitor analyzer or ohmmeter, both sides must be
tested.
WARNING
ELECTRIC SHOCK HAZARD
Capacitor Check with Capacitor Analyzer
Disconnect power to the unit before
servicing. Failure to follow this warning
could result in serious injury or death.
The capacitor analyzer will show whether the capacitor is
“open” or “shorted.” It will tell whether the capacitor is within
its micro farads rating and it will show whether the capacitor
is operating at the proper power-factor percentage. The
instrument will automatically discharge the capacitor when
the test switch is released.
BLOWER/FAN MOTOR - TEST
1. Determine that capacitor is serviceable.
2. Disconnect fan motor wires from fan speed switch or
system switch.
Capacitor Connections
The starting winding of a motor can be damaged by a
shorted and grounded running capacitor. This damage
usually can be avoided by proper connection of the running
capacitor terminals.
3. Apply “live”testcordprobesonblackwire andcommon
terminal of capacitor. Motor should run at high speed.
4. Apply “live” test cord probes on red wire and common
terminal of capacitor. Motor should run at low speed.
From the supply line on a typical 230 volt circuit, a 115 volt
potential exists from the “R” terminal to ground through a
possible short in the capacitor. However, from the “S” or
start terminal, a much higher potential, possibly as high as
400 volts, exists because of the counter EMF generated
in the start winding. Therefore, the possibility of capacitor
failure is much greater when the identified terminal is
connected to the “S” or start terminal. The identified
terminal should always be connected to the supply line, or
“R” terminal, never to the “S” terminal.
5. Apply “live” test cord probes on each of the remaining
wires from the speed switch or system switch to test
intermediatespeeds. Ifthecontrolisinthe“MoneySaver”
mode and the thermostat calls for cooling, the fan will
start-thenstopafterapproximately2minutes;thenthe
fan and compressor will start together approximately 2
minutes later.
Blower/Fan Motor
When connected properly, a shorted or grounded running
capacitor will result in a direct short to ground from the “R”
terminal and will blow the line fuse. The motor protector
will protect the main winding from excessive temperature.
Dual Rated Run Capacitor Hook-up
CAPACITORS
WARNING
ELECTRIC SHOCK HAZARD
Turn off electric power before servicing.
Discharge capacitor with a 20,000 Ohm 2 Watt
resistor before handling.
Failure to do so may result in personal injury,
or death.
15
COMPONeNTS TeSTING (Continued)
HEATING ELEMENT
DRAIN PAN VALVE
All electric heat models are equipped with a heating element.
The EQ08 has a 1.15 KW element.
During the cooling mode of operation, condensate which
collects in the drain pan is picked up by the condenser fan
blade and sprayed onto the condenser coil. This assists
in cooling the refrigerant plus evaporating the water.
Heating Element
During the heating mode of operation, it is necessary that
water be removed to prevent it from freezing during cold
outside temperatures. This could cause the condenser
fan blade to freeze in the accumulated water and prevent
it from turning.
To provide a means of draining this water, a bellows type
drain valve is installed over a drain opening in the base
pan.
The heating element contains a fuse link and a heater limit
switch. The fuse link is in series with the power supply and
will open and interrupt the power when the temperature
reaches 199°F or a short circuit occurs in the heating
element. Once the fuse link separates, a new fuse link
must be installed.
This valve is temperature sensitive and will open when
the outside temperature reaches 40°F. The valve will
close gradually as the temperature rises above 40°F to
fully close at 60°F.
NOTE: Always replace with the exact replacement.
The heater element has a high limit control. This control
is a bimetal thermostat mounted in the top of the heating
element.
Bellows Assembly
Drain Pan Valve
Should the fan motor fail or filter become clogged, the high
limit control will open and interrupt power to the heater
before reaching an unsafe temperature condition.
The control is designed to open at 110°F ±6°F. Test
continuity below 110°F and for open above 110°F.
TESTING THE HEATING ELEMENT
WARNING
ELECTRIC SHOCK HAZARD
Disconnect power to the unit before
servicing. Failure to follow this warning
could result in serious injury or death.
Testing of the elements can be made with an ohmmeter
across the terminals after the connecting wires have been
removed. A cold resistance reading of approximately 10.11
ohms for the 1.15 KW heater should be registered.
16
RefRIGeRATION SeQUeNCe Of OPeRATION
A good understanding of the basic operation of the
refrigeration system is essential for the service technician.
Without this understanding, accurate troubleshooting of
refrigeration system problems will be more difficult and time
consuming, if not (in some cases) entirely impossible. The
refrigeration system uses four basic principles (laws) in its
operation they are as follows:
The refrigerant leaves the condenser Coil through the liquid
line as a warm high pressure liquid. It next will pass through
the refrigerant drier (if so equipped). It is the function of the
driertotrapanymoisturepresentinthesystem,contaminants,
and large particulate matter.
The liquid refrigerant next enters the metering device. The
metering device is a capillary tube. The purpose of the
metering device is to “meter” (i.e. control or measure) the
quantity of refrigerant entering the evaporator coil.
1. “Heat always flows from a warmer body to a cooler
body.”
2. “Heat must be added to or removed from a substance
before a change in state can occur”
In the case of the capillary tube this is accomplished (by
design) through size (and length) of device, and the pressure
difference present across the device.
3. “Flow is always from a higher pressure area to a lower
pressure area.”
Since the evaporator coil is under a lower pressure (due to
the suction created by the compressor) than the liquid line,
the liquid refrigerant leaves the metering device entering the
evaporator coil. As it enters the evaporator coil, the larger
area and lower pressure allows the refrigerant to expand
and lower its temperature (heat intensity). This expansion is
often referred to as “boiling”. Since the unit’s blower is moving
indoor air across the finned surface of the evaporator coil,
the expanding refrigerant absorbs some of that heat. This
results in a lowering of the indoor air temperature, hence the
“cooling” effect.
4. “The temperature at which a liquid or gas changes state
is dependent upon the pressure.”
The refrigeration cycle begins at the compressor. Starting
the compressor creates a low pressure in the suction line
which draws refrigerant gas (vapor) into the compressor.
The compressor then “compresses” this refrigerant, raising
its pressure and its (heat intensity) temperature.
The refrigerant leaves the compressor through the discharge
Line as a hot High pressure gas (vapor). The refrigerant
enters the condenser coil where it gives up some of its
heat. The condenser fan moving air across the coil’s finned
surface facilitates the transfer of heat from the refrigerant to
the relatively cooler outdoor air.
The expansion and absorbing of heat cause the liquid
refrigerant to evaporate (i.e. change to a gas). Once the
refrigerant has been evaporated (changed to a gas), it is
heated even further by the air that continues to flow across
the evaporator coil.
When a sufficient quantity of heat has been removed from
the refrigerant gas (vapor), the refrigerant will “condense”
(i.e. change to a liquid). Once the refrigerant has been
condensed (changed) to a liquid it is cooled even further by
the air that continues to flow across the condenser coil.
The particular system design determines at exactly what
point (in the evaporator) the change of state (i.e. liquid to a
gas) takes place. In all cases, however, the refrigerant must
be totally evaporated (changed) to a gas before leaving the
evaporator coil.
The RAC design determines at exactly what point (in the
condenser) the change of state (i.e. gas to a liquid) takes
place. In all cases, however, the refrigerant must be
totally condensed (changed) to a Liquid before leaving the
condenser coil.
The low pressure (suction) created by the compressor
causes the refrigerant to leave the evaporator through the
suction line as a cool low pressure vapor. The refrigerant then
returns to the compressor, where the cycle is repeated.
Suction
Line
Discharge
Line
Condenser
Coil
Evaporator
Coil
Compressor
Metering
Device
Refrigerant Drier
Liquid
Line
Refrigerant
Strainer
17
R-410A SeAleD SYSTeM RePAIR CONSIDeRATIONS
WARNING
Refrigeration system under high pressure
Do not puncture, heat, expose to flame or incinerate.
Only certified refrigeration technicians should
service this equipment.
R410Asystems operate at higher pressures than
R22 equipment.Appropriate safe service and
handling practicces must be used.
Only use gauge sets designed for use with R410A.
Do not use standard R22 gauge sets.
The following is a list of important considerations when working with R-410A equipment
•
•
•
R-410A pressure is approximately 60% higher than R-22 pressure.
R-410A cylinders must not be allowed to exceed 125 F, they may leak or rupture.
R-410A must never be pressurized with a mixture of air, it may become
flammable.
•
•
Servicing equipment and components must be specifically designed for use with R-410A and
dedicated to prevent contamination.
Manifold sets must be equipped with gauges capable of reading 750 psig (high side) and 200
psig (low side), with a 500-psig low-side retard.
•
•
Gauge hoses must have a minimum 750-psig service pressure rating
Recovery cylinders must have a minimum service pressure rating of 400 psig, (DOT 4BA400
and DOT BW400 approved cylinders).
•
•
POE (Polyol-Ester) lubricants must be used with R-410A equipment.
To prevent moisture absorption and lubricant contamination, do not leave the refrigeration
system open to the atmosphere longer than 1 hour.
•
•
•
•
Weigh-in the refrigerant charge into the high side of the system.
Introduce liquid refrigerant charge into the high side of the system.
For low side pressure charging of R-410A, use a charging adaptor.
Use Friedrich approved R-410A filter dryers only.
18
R-410A SeAleD RefRIGeRATION SYSTeM RePAIRS
IMPORTANT
SEALED SYSTEM REPAIRS TO COOL-ONLY MODELS REQUIRE THE INSTALLATION OF A LIQUID LINE DRIER.
EQUIPMENT REQUIRED:
9. High Pressure Gauge - (0 to 750 lbs.)
10. Low Pressure Gauge - (-30 to 200 lbs.)
11. Vacuum Gauge - (0 - 1000 microns)
1. Voltmeter
2. Ammeter
3. Ohmmeter
12. Facilities for flowing nitrogen through refrigeration tubing
4. E.P.A. Approved Refrigerant Recovery System
during all brazing processes.
5. Vacuum Pump (capable of 200 microns or less
vacuum.)
EQUIPMENT MUST bE CAPAbLE OF:
6. Acetylene Welder
1. Recovering refrigerant to EPA required levels.
7. Electronic Halogen Leak Detector capable of
2. Evacuation from both the high side and low side of the
system simultaneously.
detecting HFC (Hydrofluorocarbon) refrigerants.
8. Accurate refrigerant charge measuring device such
as:
3. Introducing refrigerant charge into high side of the
system.
a. Balance Scales - 1/2 oz. accuracy
b. Charging Board - 1/2 oz. accuracy
4. Accurately weighing the refrigerant charge introduced
into the system.
Proper refrigerant charge is essential to proper unit operation.
Operating a unit with an improper refrigerant charge will
result in reduced performance (capacity) and/or efficiency.
Accordingly, the use of proper charging methods during
servicing will insure that the unit is functioning as designed
and that its compressor will not be damaged.
WARNING
RISK OF ELECTRIC SHOCK
Unplug and/or disconnect all electrical power
to the unit before performing inspections,
maintenances or service.
Failure to do so could result in electric shock,
serious injury or death.
Too much refrigerant (overcharge) in the system is just as bad
(if not worse) than not enough refrigerant (undercharge). They
both can be the source of certain compressor failures if they
remain uncorrected for any period of time. Quite often, other
problems (such as low air flow across evaporator, etc.) are
misdiagnosed as refrigerant charge problems. The refrigerant
circuit diagnosis chart will assist you in properly diagnosing
these systems.
WARNING
HIGH PRESSURE HAZARD
SealedRefrigerationSystemcontainsrefrigerant
and oil under high pressure.
An overcharged unit will at times return liquid refrigerant
(slugging) back to the suction side of the compressor eventually
causing a mechanical failure within the compressor. This
mechanical failure can manifest itself as valve failure, bearing
failure, and/or other mechanical failure. The specific type of
failure will be influenced by the amount of liquid being returned,
and the length of time the slugging continues.
Proper safety procedures must be followed,
and proper protective clothing must be worn
when working with refrigerants.
Failure to follow these procedures could
result in serious injury or death.
Refrigerant Charging
Not enough refrigerant (undercharge) on the other hand, will
cause the temperature of the suction gas to increase to the point
where it does not provide sufficient cooling for the compressor
motor. When this occurs, the motor winding temperature will
increase causing the motor to overheat and possibly cycle open
the compressor overload protector. Continued overheating of
the motor windings and/or cycling of the overload will eventually
lead to compressor motor or overload failure.
NOTE: Because the XStar system is a sealed system,
service process tubes will have to be installed. First install a
line tap and remove refrigerant from system. Make necessary
sealed system repairs and vacuum system. Crimp process
tube line and solder end shut. Do not leave a service valve in
the sealed system.
19
Method Of Charging / Repairs
The acceptable method for charging the RAC system is the
Weighed in Charge Method. The weighed in charge method is
applicable to all units. It is the preferred method to use, as it is
the most accurate.
The weighed in method should always be used whenever
a charge is removed from a unit such as for a leak repair,
compressor replacement, or when there is no refrigerant
charge left in the unit. To charge by this method, requires the
following steps:
1. Install a piercing valve to remove refrigerant from the
sealedsystem. (Piercing valve must be removed from the
system before recharging.)
2. Recover Refrigerant in accordance with EPA regulations.
WARNING
bURN HAZARD
Proper safety procedures must be followed,
and proper protective clothing must be worn
when working with a torch.
Failure to follow these procedures could
result in moderate or serious injury.
3. Install a process tube to sealed system.
CAUTION
FREEZE HAZARD
Proper safety procedures must be followed,
and proper protective clothing must be worn
when working with liquid refrigerant.
Failure to follow these procedures could
result in minor to moderate injury.
4. Make necessary repairs to system.
5. Evacuate system to 200 microns or less.
6. Weigh in refrigerant with the property quantity of R410-A
refrigerant.
7. Start unit, and verify performance.
WARNING
bURN HAZARD
Proper safety procedures must be followed,
and proper protective clothing must be worn
when working with a torch.
Failure to follow these procedures could
result in moderate or serious injury.
8. Crimp the process tube and solder the end shut.
20
WARNING
WARNING
ELECTRIC SHOCK HAZARD
Turn off electric power before service or
installation.
HIGH PRESSURE HAZARD
SealedRefrigerationSystemcontainsrefrigerant
and oil under high pressure.
Extreme care must be used, if it becomes
necessary to work on equipment with power
applied.
Proper safety procedures must be followed,
and proper protective clothing must be worn
when working with refrigerants.
Failure to do so could result in serious injury or
death.
Failure to follow these procedures could
result in serious injury or death.
Undercharged Refrigerant Systems
An undercharged system will result in poor performance
(low pressures, etc.) in both the heating and cooling
cycle.
A check of the amperage drawn by the compressor
motor should show a lower reading. (Check the Unit
Specification.) After the unit has run 10 to 15 minutes,
check the gauge pressures. Gauges connected to system
with an undercharge will have low head pressures and
substantially low suction pressures.
Whenever you service a unit with an undercharge of
refrigerant, always suspect a leak. The leak must be
repaired before charging the unit.
To check for an undercharged system, turn the unit on,
allow the compressor to run long enough to establish
working pressures in the system (15 to 20 minutes).
During the cooling cycle you can listen carefully at the exit
of the metering device into the evaporator; an intermittent
hissing and gurgling sound indicates a low refrigerant
charge. Intermittent frosting and thawing of the evaporator
is another indication of a low charge, however, frosting
and thawing can also be caused by insufficient air over
the evaporator.
Checks for an undercharged system can be made at
the compressor. If the compressor seems quieter than
normal, it is an indication of a low refrigerant charge.
of the evaporator will not be encountered because the
refrigerant will boil later if at all. Gauges connected to
system will usually have higher head pressure (depending
upon amount of over charge). Suction pressure should be
slightly higher.
Overcharged Refrigerant Systems
Compressor amps will be near normal or higher.
Noncondensables can also cause these symptoms. To
confirm, remove some of the charge, if conditions improve,
system may be overcharged. If conditions don’t improve,
Noncondensables are indicated.
Whenever an overcharged system is indicated, always
make sure that the problem is not caused by air flow
problems. Improper air flow over the evaporator coil may
indicate some of the same symptoms as an over charged
system.
An overcharge can cause the compressor to fail, since it
would be “slugged” with liquid refrigerant.
Thechargeforanysystemiscritical. Whenthecompressor
is noisy, suspect an overcharge, when you are sure that
the air quantity over the evaporator coil is correct. Icing
21
Restricted Refrigerant System
Troubleshooting a restricted refrigerant system can be
difficult. The following procedures are the more common
problems and solutions to these problems. There are two
types of refrigerant restrictions: Partial restrictions and
complete restrictions.
at the metering device entrance to the evaporator. The
evaporator in a partial restriction could be partially frosted
or have an ice ball close to the entrance of the metering
device. Frost may continue on the suction line back to the
compressor.
A partial restriction allows some of the refrigerant to
circulate through the system.
Often a partial restriction of any type can be found by feel,
as there is a temperature difference from one side of the
restriction to the other.
With a complete restriction there is no circulation of
refrigerant in the system.
With a complete restriction, there will be no sound at the
metering device entrance. An amperage check of the
compressor with a partial restriction may show normal
current when compared to the unit specifi cation. With a
complete restriction the current drawn may be considerably
less than normal, as the compressor is running in a deep
vacuum (no load.) Much of the area of the condenser will
be relatively cool since most or all of the liquid refrigerant
will be stored there.
Restricted refrigerant systems display the same symptoms
as a “low-charge condition.”
When the unit is shut off, the gauges may equalize very
slowly.
Gauges connected to a completely restricted system will
run in a deep vacuum. When the unit is shut off, the gauges
will not equalize at all.
The following conditions are based primarily on a system
in the cooling mode.
A quick check for either condition begins at the evaporator.
With a partial restriction, there may be gurgling sounds
22
COMPRESSOR CHECKS
External Overload
WARNING
ELECTRIC SHOCK HAZARD
The compressor is equipped with an external overload
which senses both motor amperage and winding tem-
perature. High motor temperature or amperage heats the
overload causing it to open, breaking the common circuit
within the compressor.
Turn off electric power before service or
installation. Extreme care must be used, if it
becomes necessary to work on equipment with
power applied.
Heat generated within the compressor shell, usually due
to recycling of the motor, is slow to dissipate. It may take
anywhere from a few minutes to several hours for the
overload to reset.
Failure to do so could result in serious injury or
death.
Locked Rotor Voltage (L.R.V.) Test
Locked rotor voltage (L.R.V.) is the actual voltage available
at the compressor under a stalled condition.
Checking the External Overload
Single Phase Connections
WARNING
Disconnect power from unit. Using a voltmeter, attach one
lead of the meter to the run “R” terminal on the compressor
and the other lead to the common “C” terminal of the com-
pressor. Restore power to unit.
ELECTRIC SHOCK HAZARD
Turn off electric power before service or
installation. Extreme care must be used, if it
becomes necessary to work on equipment
with power applied.
Failure to do so could result in serious injury or
death.
Determine L.R.V.
Start the compressor with the volt meter attached; then stop
the unit. Attempt to restart the compressor within a couple
of seconds and immediately read the voltage on the meter.
The compressor under these conditions will not start and will
usually kick out on overload within a few seconds since the
pressures in the system will not have had time to equalize.
Voltage should be at or above minimum voltage of 197 VAC,
as specified on the rating plate. If less than minimum, check
for cause of inadequate power supply; i.e., incorrect wire
size, loose electrical connections, etc.
WARNING
BURN HAZARD
Certain unit components operate at
temperatures hot enough to cause burns.
Proper safety procedures must be followed,
and proper protective clothing must be
worn.
Amperage (L.R.A.) Test
Failure to follow this warning could result
in moderate to serious injury.
The running amperage of the compressor is the most impor-
tant of these readings. A running amperage higher than that
indicated in the performance data indicates that a problem
exists mechanically or electrically.
With power off, remove the leads from compressor termi-
nals. If the compressor is hot, allow the overload to cool
before starting check. Using an ohmmeter, test continu-
ity across the terminals of the external overload. If you
do not have continuity; this indicates that the overload is
open and must be replaced.
Single Phase Running and L.R.A. Test
NOTE: Consult the specification and performance section
for running amperage. The L.R.A. can also be found on the
rating plate.
Select the proper amperage scale and clamp the meter
probe around the wire to the “C” terminal of the compres-
sor. Turn on the unit and read the running amperage on
the meter. If the compressor does not start, the reading
will indicate the locked rotor amperage (L.R.A.).
23
Single Phase Resistance Test
Remove the leads from the compressor terminals and set
the ohmmeter on the lowest scale (R x 1).
Many compressor failures are caused by the following
conditions:
1. Improper air flow over the evaporator.
Touch the leads of the ohmmeter from terminals common
to start (“C” to “S”). Next, touch the leads of the ohmmeter
from terminals common to run (“C” to “R”).
2. Overcharged refrigerant system causing liquid to be
returned to the compressor.
Add values “C” to “S” and “C” to “R” together and
check resistance from start to run terminals (“S” to “R”).
Resistance “S” to “R” should equal the total of “C” to “S”
and “C” to “R.”
3. Restricted refrigerant system.
4. Lack of lubrication.
5. Liquid refrigerant returning to compressor causing oil
In a single phase PSC compressor motor, the highest
value will be from the start to the run connections (“S” to
“R”). The next highest resistance is from the start to the
common connections (“S” to “C”). The lowest resistance
is from the run to common. (“C” to “R”) Before replacing a
compressor, check to be sure it is defective.
to be washed out of bearings.
6.
Noncondensables such as air and moisture in
the system. Moisture is extremely destructive to a
refrigerant system.
7. Defective capacitors.
GROUND TEST
Use an ohmmeter set on its highest scale. Touch one
lead to the compressor body (clean point of contact as
a good connection is a must) and the other probe in turn
to each compressor terminal. If a reading is obtained the
compressor is grounded and must be replaced.
Check the complete electrical system to the compressor
and compressor internal electrical system, check to be
certain that compressor is not out on internal overload.
Complete evaluation of the system must be made
whenever you suspect the compressor is defective. If
the compressor has been operating for sometime, a
careful examination must be made to determine why the
compressor failed.
24
COMPReSSOR RePlACeMeNT
Recommendedprocedure forcompressor
replacement
3. After all refrigerant has been recovered, disconnect
suction and discharge lines from the compressor and
remove compressor. Be certain to have both suction
and discharge process tubes open to atmosphere.
WARNING
4. Carefully pour a small amount of oil from the suction
RISK OF ELECTRIC SHOCK
Unplug and/or disconnect all electrical power
to the unit before performing inspections,
maintenances or service.
stub of the defective compressor into a clean
container.
5. Using an acid test kit (one shot or conventional kit), test
the oil for acid content according to the instructions
with the kit.
Failure to do so could result in electric shock,
serious injury or death.
6. If any evidence of a burnout is found, no matter how
slight, the system will need to be cleaned up following
proper procedures.
1. Be certain to perform all necessary electrical and
refrigeration tests to be sure the compressor is
actually defective before replacing.
7. Install the replacement compressor.
WARNING
WARNING
HIGH PRESSURE HAZARD
SealedRefrigerationSystemcontainsrefrigerant
and oil under high pressure.
EXPLOSION HAZARD
The use of nitrogen requires a pressure
regulator. Follow all safety procedures and
wear protective safety clothing etc.
Proper safety procedures must be followed,
and proper protective clothing must be worn
when working with refrigerants.
Failure to follow proper safety procedures
result in serious injury or death.
Failure to follow these procedures could
result in serious injury or death.
8. Pressurize with a combination of R410-A and nitrogen
and leak test all connections with an electronic or
Halide leak detector. Recover refrigerant and repair
any leaks found.
2. Recover all refrigerant from the system though
the process tubes. PROPER HANDLING OF
RECOVERED REFRIGERANT ACCORDING TO
EPA REGULATIONS IS REQUIRED. Do not use
gauge manifold for this purpose if there has been
a burnout. You will contaminate your manifold and
hoses. Use a Schrader valve adapter and copper
tubing for burnout failures.
Repeat Step 8 to insure no more leaks are present.
9. Evacuate the system with a good vacuum pump capable
of a final vacuum of 200 microns or less. The system
should be evacuated through both liquid line and suction
line gauge ports. While the unit is being evacuated, seal
all openings on the defective compressor. Compressor
manufacturers will void warranties on units received not
properly sealed. Do not distort the manufacturers tube
connections.
WARNING
HIGH TEMPERATURES
Extreme care, proper judgment and all safety
procedures must be followed when testing,
troubleshooting, handling or working around
unit while in operation with high temperature
components. Wear protective safety aids
such as: gloves, clothing etc.
CAUTION
FREEZE HAZARD
Proper safety procedures must be followed,
and proper protective clothing must be worn
when working with liquid refrigerant.
Failure to do so could result in serious burn
injury.
Failure to follow these procedures could
result in minor to moderate injury.
NOTICE
FIRE HAZARD
10. Recharge the system with the correct amount of
refrigerant. The proper refrigerant charge will be
found on the unit rating plate. The use of an accurate
measuring device, such as a charging cylinder,
The use of a torch requires extreme care and proper
judgment. Follow all safety recommended precautions
and protect surrounding areas with fire proof materials.
Have a fire extinguisher readily available. Failure to follow
this notice could result in moderate to serious property
damage.
electronic scales or similar device is necessary.
25
SPECIAL PROCEDURE IN THE CASE OF MOTOR
COMPRESSOR bURNOUT
WARNING
ELECTRIC SHOCK HAZARD
Turn off electric power before service or
installation.
Failure to do so may result in personal injury,
or death.
WARNING
HIGH PRESSURE HAZARD
SealedRefrigerationSystemcontainsrefrigerant
and oil under high pressure.
Proper safety procedures must be followed,
and proper protective clothing must be worn
when working with refrigerants.
Failure to follow these procedures could
result in serious injury or death.
WARNING
EXPLOSION HAZARD
The use of nitrogen requires a pressure
regulator. Follow all safety procedures and
wear protective safety clothing etc.
Failure to follow proper safety procedures
result in serious injury or death.
1.
2.
Recover all refrigerant and oil from the system.
Remove compressor, capillary tube and filter drier
from the system.
3.
Flush evaporator condenser and all connecting
tubing with dry nitrogen or equivalent. Use approved
flushing agent to remove all contamination from
system. Inspect suction and discharge line for
carbon deposits. Remove and clean if necessary.
Ensure all acid is neutralized.
4. Reassemble the system, including new drier strainer
and capillary tube.
5. Proceed with step 8-10 on previous page.
ROTARY COMPRESSOR SPECIAL TROUbLESHOOTING
AND SERVICE
Basically, troubleshooting and servicing rotary compres-
sors is the same as on the reciprocating compressor with
only one main exception:
NEVER, under any circumstances, liquid charge a rotary
compressor through the LOW side. Doing so would cause
permanent damage to the new compressor.
26
ROUTINe MAINTeNANCe
AIR FILTER
WARNING
Clean the unit air intake filter at least every 300 to 350 hours
of operation. Clean the filters with a mild detergent in warm
water and allow to dry thoroughly before reinstalling.
ELECTRIC SHOCK HAZARD
Turn off electric power before inspections,
maintenances, or service.
COILS AND bASE PAN
Extreme care must be used, if it becomes
necessary to work on equipment with power
applied.
The indoor coil (evaporator coil), the outdoor coil (condenser
coil) and base pan should be inspected periodically
(yearly or bi-yearly) and cleaned of all debris (lint, dirt,
leaves, paper, etc.). Clean the coils and base pan with a soft
brush and compressed air or vacuum. If using a pressure
washer, be careful not to bend the aluminium fin pack. Use
a sweeping up and down motion in the direction of the verti-
cal aluminum fin pack when pressure cleaning coils. Cover
all electrical components to protect them from water or spray.
Allow the unit to dry thoroughly before reinstalling it in the
sleeve.
Failure to do so could result in serious injury
or death.
WARNING
EXCESSIVE WEIGHT HAZARD
Use two people to lift or carry the unit, and wear
proper protective clothing.
bLOWER WHEEL / HOUSING / CONDENSER FAN /
SHROUD
Failure to do so may result in personal injury.
Inspect the indoor blower housing, evaporator blade, con-
denser fan blade and condenser shroud periodically (yearly
or bi-yearly) and clean of all debris (lint, dirt, mold, fungus,
etc.). Clean the blower housing area and blower wheel with
an antibacterial / antifungal cleaner. Use a biodegradable
cleaning agent and degreaser on condenser fan and con-
denser shroud. Use warm or cold water when rinsing these
items. Allow all items to dry thoroughly before reinstalling
them.
WARNING
CUT/SEVER HAZARD
Be careful with the sharp edges and corners.
Wear protective clothing and gloves, etc.
Failure to do so could result in serious injury.
ELECTRONIC / ELECTRICAL / MECHANICAL
NOTICE
Units are to be inspected and serviced by qualified service
personnel only. Use proper protection on surrounding
property. Failure to follow this notice could result in
moderate or serious property damage.
Periodically (at least yearly or bi-yearly): inspect all control
components: electronic, electrical and mechanical, as well as
the power supply. Use proper testing instruments (voltmeter,
ohmmeter, ammeter, wattmeter, etc.) to perform electrical
tests. Use an air conditioning or refrigeration thermometer
to check room, outdoor and coil operating temperatures.
Use an electronic tester to measure wet bulb temperatures
indoors and outdoors.
NOTICE
Do not use a caustic coil cleaning agent on coils or base
pan. Use a biodegradable cleaning agent and degreaser,
to prevent damage to the coil and/or base pan.
27
ROUTINe MAINTeNANCe (Continued)
NOTICE
Do not drill holes in the bottom of the drain pan or the
underside of the unit. Not following this notice could
result in damage to the unit or condensate water leaking
inappropriately which could cause water damage to
surrounding property.
SLEEVE / DRAIN
Inspect the sleeve and drain system periodically (at least yearly or bi-yearly) and clean of all obstructions and
debris. Clean both areas with an antibacterial and antifungal cleaner. Rinse both items thoroughly with water and
ensure that the drain outlets are operating correctly. Check the sealant around the sleeve and reseal areas as
needed.
FRONT COVER
Clean the front cover when needed. Use a mild detergent. Wash and rinse with warm water. Allow it to dry
thoroughly before reinstalling it in the chassis.
CLEARANCES
Inspect the surrounding area (inside and outside) to ensure that the unit’s clearances have not been compromised or
altered.
Compressor
Liquid Filter Driers
Condenser Coil
Discharge Air
Front Cover
System Controls
Outdoor Grille
Sleeve
Evaporator Coil
Return Air Grille/Filter
Blower Wheel
Blower Motor
Condenser Fan Blade
Basepan
28
ROOM AIR CONDITIONeR UNIT
PeRfORMANCe TeST DATA SHeeT
DATE: _______________ MODEL:_______________ SERIAL:________________
YES
____
____
____
NO
IS THERE A FRIEDRICH SLEEVE INSTALLED?
IS THERE A FRIEDRICH OUTDOOR GRILL INSTALLED?
IS MAINTENANCE BEING PERFORMED?
____
____
____
If NO is checked use back of sheet for explanation
ELECTRICAL:
LINE VOLTAGE (STATIC)
START UP VOLTAGE
AMPERAGE DRAW
--------- VOLTS
--------- VOLTS
--------- AMPS (COOL)
--------- AMPS (HEAT)
AMPERAGE DRAW
COMPRESSOR
LOCKED ROTOR AMPS
RUNNING AMPERAGE DRAW
--------- AMPS
--------- AMPS
INDOOR TEMPERATURES:
INDOOR AMBIENT TEMPERATURE
RELATIVE HUMIDITY (RH) INDOOR
-------- F
-------- %
COOL
HEAT
DISCHARGE AIR TEMPERATURE (INDOOR)
RETURN AIR TEMPERATURE (INDOOR)
---------- F --------- F
---------- F --------- F
OUTDOOR TEMPERATURE:
OUTDOOR AMBIENT TEMPERATURE
RH OUTDOOR
--------- F
--------- %
DISCHARGE AIR TEMPERATURE (OUTDOOR)
INTAKE AIR TEMPERATURE (OUTDOOR
--------- F ---------- F
--------- F ---------- F
APPLICATION USE ------------------------- ROOM (RESIDENTIAL OR COMMERCIAL)
COOLING OR HEATING AREA W ---------- X L ----------- X H ----------- = SQ/CU/FT ------------
This is a general guide.
Please consult manual J or M for exact load calculations.
Due to variations in room design, climate zone and occupancy, larger areas
may require the use of multiple units to provide the optimal cooling solution.
29
29
GENERAL TROUBLESHOOTING TIPS
Problem
Possible Cause
Possible Solution
Turn the unit to the on position and raise or
lower temperature setting (as appropriate) to
call for operation.
The unit is turned to the off position,
Plug into a properly grounded 3 prong
receptacle. See “Electrical Rating Tables” on
pg. 6 for the proper receptacle type for your
unit.
The LCDI power cord is unplugged.
Press and release RESET (listen for click;
Reset button latches and remains in) to resume
operation.
Unit does not operate.
The LCDI power cord has tripped
(Reset button has popped out).
Reset the circuit breaker, or replace the fuse as
applicable. If the problem continues, contact a
licensed electrician.
The circuit breaker has tripped or
the supply circuit fuse has blown.
There has been a local power
failure.
The unit will resume normal operation once
power has been restored.
Other appliances are being used on
the same circuit.
The unit requires a dedicated outlet circuit, not
shared with other appliances.
Do NOT use an extension cord with this or any
other air conditioner.
An extension cord is being used.
Unit Trips Circuit Breaker or
Blows Fuses.
Replace with a circuit breaker or time-delay
fuse of the proper rating. See “Electrical
Rating Tables” on pg. 6 for the proper circuit
breaker/fuse rating for your unit. If the problem
continues, contact a licensed electrician.
The circuit breaker or time-delay
fuse is not of the proper rating.
The LCDI power cord can trip
(Reset button pops out) due to
disturbances on your power supply
line.
Press and release RESET (listen for click;
Reset button latches and remains in) to resume
normal operation.
LCDI Power Cord Trips (Reset
Button Pops Out).
Electrical overload, overheating, or
cord pinching can trip (Reset button
pops out) the LCDI power cord.
Once the problem has been determined and
corrected, press and release RESET (listen for
click; Reset button latches and remains in) to
resume normal operation.
NOTE: A damaged power supply cord must be replaced with a new power supply cord
obtained from the product manufacturer and must not be repaired.
Ensure that the return and/or discharge air
The return/discharge air grille is
paths are not blocked by curtains, blinds,
blocked.
furniture, etc.
Windows or doors to the outside are
Ensure that all windows and doors are closed.
open.
The temperature is not set at a cool
enough/warm enough setting.
Adjust the Temperature control to a cooler or
warmer setting as necessary.
Unit Does Not Cool/Heat
On And Off Too Frequently.
remove obstruction.
The indoor coil or outdoor coil is
dirty or obstructed.
Clean the coils, (See Routine Maintenance), or
remove obstruction.
Be sure to use exhaust vent fans while cooking
or bathing and, if possible, try not to use heat
producing appliances during the hottest part of
the day.
There is excessive heat or moisture
(cooking, showers, etc.) in the room.
The temperature of the room you
are trying to cool is extremely hot.
Allow additional time for the air conditioner to
cool off a very hot room.
30
GENERAL TROUBLESHOOTING TIPS (CONTINUED)
Problem
Possible Cause
Possible Solution
Do not try to operate your air conditioner in the
cooling mode when the outside temperature
is below 60° F (16° C). The unit will not cool
properly, and the unit may be damaged.
The outside temperature is below
60° F (16° C).
Since the fan does not circulate the room
air continuously at this setting, the room air
does not mix as well and hot (or cold) spots
may result. Using the continuous fan setting
is recommended to obtain optimum comfort
levels.
The digital control is set to fan
cycling mode.
Unit Does Not Cool/Heat
On And Off Too Frequently
(continued).
Check the cooling capacity of your unit to
ensure it is properly sized for the room in which
it is installed. Room air conditioners are not
designed to cool multiple rooms.
cooling capacity to match the heat
gain of the room.
Check the heating capacity of your unit. Air
conditioners are sized to meet the cooling load,
and heater size is then selected to meet the
heating load. In extreme northern climates,
room air conditioners may not be able to be
used as a primary source of heat.
heating capacity to match the heat
loss of the room.
If there are heat producing appliances in use
in the room, or if the room is heavily occupied,
the unit will need to run longer to remove the
additional heat.
This may be due to an excessive
heat load in the room.
Be sure to use exhaust vent fans while cooking
or bathing and, if possible, try not to use heat
producing appliances during the hottest part of
the day.
It may also be due to an improperly
sized unit.
your new air conditioner may result in the
unit running longer than you feel it should.
This may be more apparent, if it replaced an
This may be normal for higher
Unit Runs Too Much.
compared to older models.
You may notice that the discharge
air temperature of your new air
conditioner may not seem as cold
as you may be accustomed to from
older units. This does not, however,
indicate a reduction in the cooling
capacity of the unit.
capacity rating (Btu/h) listed on the unit’s rating
31
COOlING ONlY ROOM AIR CONDITIONeRS: TROUBleSHOOTING TIPS
Problem
Possible Cause
Low voltage
Action
Check voltage at compressor. 115V & 230V
units will operate at 10% voltage variance
T-stat not set cold enough or
inoperative or electronic control
board is bad
Set t-stat to coldest position. Test t-stat &
replace if inoperative
Compressor hums but cuts off on
overload
Hard start compressor. Direct test compressor.
If compressor starts, add starting components
Compressor
does not run
Open or shorted compressor
windings
Check for continuity & resistance
Open overload
Test overload protector & replace if inoperative
Test capacitor & replace if inoperative
Test for continuity in all positions. Replace if
inoperative switch or electronic board.
Refer to appropriate wiring diagrams to check
wiring
Open capacitor
Inoperative system switch,
thermistor or electronic board
Broken, loose or incorrect wiring
Problem
Possible Cause
Inoperative system switch
Broken, loose or incorrect wiring
Open capacitor
Action
Test switch & replace if inoperative
Refer to applicable wiring diagram
Test capacitor & replace if inoperative
Test switch & replace if inoperative
Test fan motor & replace if inoperative (be sure
internal overload has had time to reset)
Fan motor
does not run
Fan speed switch open
Inoperative fan motor
Problem
Possible Cause
Action
Undersized unit
Refer to industry standard sizing chart
Thermistor or electronic board is bad,
T-stat open or inoperative
Set to coldest position. Test t-stat or electronic
control board & replace if necessary.
Dirty filter
Clean as recommended in Owner’s Manual
Use pressure wash or biodegradable cleaning
agent to clean
Dirty or restricted condenser or
evaporator coil
Does not cool or
only cools slightly
Poor air circulation
Adjust discharge louvers. Use high fan speed
Close doors. Instruct customer on use of this
feature
Fresh air or exhaust air door open
on applicable models
Low capacity - undercharge
Check for leak & make repair
Check amperage draw against nameplate. If
not conclusive, make pressure test
Compressor not pumping properly
32
COOlING ONlY ROOM AIR CONDITIONeRS: TROUBleSHOOTING TIPS
Problem
Possible Cause
Action
Replace fuse, reset breaker. If repeats, check
fuse or breaker size. Check for shorts in unit
wiring & components
Fuse blown or circuit tripped
Power cord not plugged in
Plug it in
System switch in “OFF” position
Set switch correctly
Unit does not run
Inoperative system switch or open
electronic control board
Test for continuity
Loose or disconnected wiring at
Check wiring & connections. Reconnect per
wiring diagram
switch, control board or other com-
ponents
Problem
Possible Cause
Action
Dirty filter
Clean as recommended in Owner’s Manual
Check for dirty or obstructed coil. Use
pressure wash or biodegradable cleaning
agent to clean
Restricted airflow
Inoperative t-stat or thermistors
Short of refrigerant
Test for continuity
Evaporator coil
freezes up
De-ice coil & check for leak
Inoperative fan motor
Test fan motor & replace if inoperative
De-ice coil. Check temp. differential (delta T)
across coil. Touch test coil return bends for
same temp. Test for low running current
Partially restricted capillary tube
Problem
Possible Cause
Action
Unit undersized. Test cooling performance &
replace with larger unit if needed
Check for partially iced coil & check
temperature split across coil
Excessive heat load
Restriction in line
Refrigerant leak
Check for oil at silver soldered connections.
Check for partially iced coil. Check split across
coil. Check for low running amperage
Check operation of t-stat. Replace if contacts
remain closed.
Compressor runs
continually & does
not cycle off
T-stat contacts stuck
T-stat incorrectly wired
Thermistor shorted
Refer to appropriate wiring diagram
Replace thermistor or electronic control board
Problem
Possible Cause
Action
Disconnect power to unit. Remove cover
of t-stat & check if contacts are stuck. If so,
replace t-stat
T-stat contacts stuck
Turn to higher temp. setting to see if unit
cycles off
T-stat set at coldest point
Incorrect wiring
T-stat does not
turn unit off
Refer to appropriate wiring diagrams
Refer to industry standard sizing chart
Replace thermistor or electronic control board
Unit undersized for area to be
cooled
Defective thermistor
33
COOlING ONlY ROOM AIR CONDITIONeRS: TROUBleSHOOTING TIPS
Problem
Possible Cause
Overload inoperative. Opens too
soon
Action
Check operation of unit. Replace overload if
system operation is satisfactory
Allow a minimum of 2 minutes to allow
pressures to equalize before attempting to
restart. Instruct customer of waiting period
Check voltage with unit operating. Check for
other appliances on circuit. Air conditioner
should be in separate circuit for proper voltage
& fused separately
Compressor restarted before
system pressures equalized
Compressor runs
for short periods
only. Cycles on
overload
Low or fluctuating voltage
Incorrect wiring
Refer to appropriate wiring diagram
Check by substituting a known good capacitor
of correct rating or test cap
Shorted or incorrect capacitor
Restricted or low air flow through
Check for proper fan speed or blocked
coils
condenser coil or evaporator coil
Check for kinked discharge line or restricted
condenser. Check amperage
Compressor running abnormally
hot
Problem
Possible Cause
Action
Place jumper across t-stat terminals to check if
unit operates. If unit operates, replace t-stat.
Check as above
Loss of charge in t-stat bulb
T-stat does not
turn unit on
Loose or broken parts in t-stat
Incorrect wiring
Refer to appropriate wiring diagram
Replace thermistor or electronic control board
Defective thermistor
Problem
Possible Cause
Poorly installed
Action
Refer to Installation Manual for proper
installation
Fan blade striking chassis
Reposition - adjust motor mount
Check that compressor grommets have not
deteriorated. Check that compressor mounting
parts are not missing
Noisy operation
Compressor vibrating
Improperly mounted or loose
cabinet parts refrigerant tubes
Check assembly & parts for looseness,
rubbing & rattling. Correct as needed
Problem
Possible Cause
Action
Evaporator drain pan overflowing
Clean obstructed drain trough
Evaporator drain pan broken or cracked.
Reseal or replace. No chassis gasket installed.
Install chassis gasket
Condensation forming underneath
base pan
Poor installation resulting in rain
entering the room
Check installation instructions. Reseal as
required
Water leaks into
the room
Dirty evaporator coil. Use pressure wash
or biodegradable cleaning agent to clean.
Environmental phenomena: point supply
louvers upward
Condensation on discharge grille
louvers
Chassis gasket not installed
Downward slope of unit is too
steep inward
Install gasket, per Installation manual
Refer to installation manual for proper
installation
34
COOlING ONlY ROOM AIR CONDITIONeRS: TROUBleSHOOTING TIPS
Problem
Possible Cause
Sublimation:
Action
Ensure that foam gaskets are installed in
between window panes & in between the
unit & the sleeve. Also, ensure that fresh
air/exhaust vents (on applicable models) are in
the closed position & are in tact
When unconditioned saturated,
outside air mixes with conditioned
air, condensation forms on the
cooler surfaces
Water “spitting”
into room
Follow installation instructions to ensure that
downward pitch of installed unit is no less than
1/4” & no more than 3/8”
Downward pitch of installation is
too steep towards back of unit
Clean & advise customer of periodic cleaning
& maintenance needs of entire unit
Restricted coil or dirty filter
Problem
Possible Cause
Insufficient air circulation thru area
to be air conditioned
Action
Adjust louvers for best possible air circulation
Operate in “MoneySaver” position
Advise customer
Excessive
moisture
Oversized unit
Inadequate vapor barrier in building
structure, particularly floors
Problem
Possible Cause
Defective thermistor
Action
Replace thermistor or electronic control board
Replace t-stat
T-stat differential too narrow
Plenum gasket not sealing,
allowing discharge air to short
cycle t-stat
T-stat or
thermistor
short cycles
Check gasket. Reposition or replace as
needed
Clean & advise customer of periodic cleaning
& maintenance needs of entire unit
Restricted coil or dirty filter
Problem
Possible Cause
Heat anticipator (resistor) wire
disconnected at t-stat or system
switch
Action
Refer to appropriate wiring diagram
Disconnect plus from outlet. Remove resistor
from bracket. Insert plug & depress “COOL”
& “FAN AUTOMATIC” buttons. Place t-stat to
warmest setting. Feel resistor for temperature.
If no heat, replace resistor
Prolonged off
cycles (automatic
operation)
Heat anticipator (resistor) shorted or
open
Partial loss of charge in t-stat bulb
causing a wide differential
Replace t-stat
Defective thermistor
Replace thermistor or electronic control board
Problem
Possible Cause
Evaporator drain pan cracked or
obstructed
Action
Repair, clean or replace as required
Detach shroud from pan & coil. Clean &
remove old sealer. Reseal, reinstall & check
Use pressure wash or biodegradable cleaning
agent to clean
Water in compressor area
Obstructed condenser coil
Outside water
leaks
Fan blade/slinger ring improperly
positioned
Adjust fan blade to 1/2” of condenser coil fin
pack
35
HeAT / COOl ONlY ROOM AIR CONDITIONeRS: TROUBleSHOOTING TIPS
Problem
Possible Cause
Action
Disconnect power to unit. Remove resistor from
t-stat bulb block. Plug in unit & allow to operate.
Feel resistor for heat. If not heat, replace resistor
Heat anticipator (resistor) shorted (on applicable
models)
Room temperature
uneven
(Heating cycle)
Wide differential - partial loss of t-stat bulb charge Replace t-stat
Refer to appropriate wiring diagram. Resistor is
Incorrect wiring
energized during "ON" cycle of compressor or
fan.
Problem
Possible Cause
Action
Close doors or windows.
Opened doors or windows
Dirty filter
Clean as recommended in Owner's Manual
Check heat rise across coil. If unit operates
efficiently, check if insulation can be added
to attic or walls. If insulation is adequate,
recommend additional unit or larger one
Unit undersized
Does not heat
adequately
Check for adequate fan air across heater. Check
control for open at 110°F & close at 100°F
Heater hi-limit control cycling on & off
Shorted or opened heater
Incorrect wiring
Ohmmeter/continuity check
Check applicable wiring diagram
36
eleCTRONIC CONTROl
COOl ONlY MODelS:
XQ05M10A XQ06M10A XQ08M10A XQ10M10A
37
eleCTROMeCHANICAl CONTROl
COOl WITH eleCTRIC HeAT MODel:
eQ08M11A
38
INSTRUCTIONS FOR USING COOLING LOAD ESTIMATE
FORM FOR ROOM AIR CONDITIONERS
(AHAM PUB. NO. RAC-1)
A. This cooling load estimate form is suitable for estimating the cooling load for comfort air conditioning installations
which do not require specific conditions of inside temperature and humidity.
B. The form is based on an outside design temperature of 95°F dry bulb and 75°F wet bulb. It can be used for areas
in the continental United States having other outside design temperatures by applying a correction factor for the
particular locality as determined from the map.
C. The form includes “day” factors for calculating cooling loads in rooms where daytime comfort is desired (such as
living rooms, offices, etc.)
D. The numbers of the following paragraphs refer to the corresponding numbered item on the form:
1. Multiply the square feet of window area for each exposure by the applicable factor. The window area is the
area of the wall opening in which the window is installed. For windows shaded by inside shades or venetian
blinds, use the factor for “Inside Shades.” For windows shaded by outside awnings or by both outside aw-
nings and inside shades (or venetian blinds), use the factor for “Outside Awnings.” “Single Glass” includes
all types of single thickness windows, and “Double Glass” includes sealed airspace types, storm windows,
and glass block. Only one number should be entered in the right hand column for Item 1, and this number
should represent only the exposure with the largest load.
2. Multiply the total square feet of all windows in the room by the applicable factor.
3a. Multiply the total length (linear feet) of all walls exposed to the outside by the applicable factor. Doors should
be considered as being part of the wall. Outside walls facing due north should be calculated separately from
outside walls facing other directions. Walls which are permanently shaded by adjacent structures should be
considered “North Exposure.” Do not consider trees and shrubbery as providing permanent shading. An
uninsulated frame wall or a masonry wall 8 inches or less in thickness is considered “Light Construction.” An
insulated wall or masonry wall over 8 inches in thickness is considered “Heavy Construction.”
3b. Multiply the total length (linear feet) of all inside walls between the space to be conditioned and any uncondi-
tioned spaces by the given factor. Do not include inside walls which separate other air conditioned rooms.
4. Multiply the total square feet of roof or ceiling area by the factor given for the type of construction most nearly
describing the particular application (use one line only.)
5. Multiply the total square feet of floor area by the factor given. Disregard this item if the floor is directly on the
ground or over a basement.
6. Multiply the number of people who normally occupy the space to be air conditioned by the factor given. Use
a minimum of 2 people.
7. Determine the total number of watts for light and electrical equipment, except the air conditioner itself, that
will be in use when the room air conditioning is operating. Multiply the total wattage by the factor given.
8. Multiply the total width (linear feet) of any doors or arches which are continually open to an unconditioned
space by the applicable factor.
NOTE: Where the width of the doors or arches is more than 5 feet, the actual load may exceed the calculated
value. In such cases, both adjoining rooms should be considered as a single large room, and the room air
conditioner unit or units should be selected according to a calculation made on this new basis.
9. Total the loads estimated for the foregoing 8 items.
10. Multiply the subtotal obtained in item 9 by the proper correction factor, selected from the map, for the particular
locality. The result is the total estimated design cooling load in BTU per hour.
E. For best results, a room air conditioner unit or units having a cooling capacity rating (determined in accordance
with the NEMAStandards Publication for RoomAir Conditioners, CN 1-1960) as close as possible to the estimated
load should be selected. In general, a greatly oversized unit which would operate intermittently will be much less
satisfactory than one which is slightly undersized and which would operate more nearly continuously.
F. Intermittent loads such as kitchen and laundry equipment are not included in this form.
39
COOLING LOAD ESTIMATE FORM
FACTORS
BTU/Hr.
(Quantity x Factor)
HEAT GAIN FROM
QUANTITY
DAY
No
Shades*
60
Outside
(Area
Inside
1.
WINDOWS: Heat gain from the sun.
Awnings* X Factor)
Shades*
Northeast
East
____sq. ft.
____sq. ft.
____sq. ft.
____sq. ft.
____sq. ft.
____sq. ft.
____sq. ft.
____sq. ft.
Use
only
the
largest ____
load. ____
Use
only
one.
____
____
____
20 ____
25 ____
20 ____
20 ____
30 ____
45 ____
35 ____
0 ____
25
40
30
35
45
65
50
0
* These factors are for single glass
only. For glass block, multiply the
above factors by 0.5; for double
glass or storm windows, multiply the
above factors by 0.8.
80
Southeast
South
Southwest
West
75
75
110
150
120
0
____
____
____
Northwest
North
2.
3.
WINDOWS: Heat by conduction
(Total of all windows.)
_____
_____
Single glass
14
7
____sq. ft.
____sq. ft.
Double glass or glass block
WALLS: (Based on linear feet of wall)
a. Outside walls
Light Construction
Heavy Construction
_____
_____
North Exposure
30
60
____ ft.
____ ft.
20
30
Other than North exposure
b. Inside Walls (between conditioned and
unconditioned spaces only.)
_____
30
____sq. ft.
4.
5.
ROOF OR CEILING: (Use one only)
a. Roof, uninsulated
b. Roof, 1 inch or more insulation
c. Ceiling, occupied space above
d. Ceiling, insulated, with attic space above
e. Ceiling, uninsulated, with attic space above
_____
_____
_____
_____
_____
19
8
____sq. ft.
____sq. ft.
____sq. ft.
____sq. ft.
____sq. ft.
3
5
12
_____
Floor: (Disregard if floor is directly on ground or
over a basement.
3
____sq. ft.
_____
_____
6.
7.
8.
NUMBER OF PEOPLE
600
3
____
LIGHTS AND ELECTRICAL EQUIPMENT IN USE
____watts
DOORS AND ARCHES CONTINUOUSLY
OPENED TO UNCONDITIONED SPACE: (TOTAL
LINEAR FEET OF WIDTH.)
_____
_____
300
____ft.
*****
9.
SUBTOTAL
*****
10. TOTAL COOLING LOAD (BTU per hour to be used
for selection of room air conditioner(s).)
____ Total in Item 9 X ____ (Factor from Map) =
____
40
HEAT LOAD FORM
The heat load form on the following page may be used by
Following is an example using the heat load form:
servicingpersonneltodeterminetheheatlossofaconditioned
space and the ambient winter design temperatures in which
the unit will heat the calculated space.
A space to be conditioned is part of a house geographically
located in an area where the lowest outdoor ambient winter
temperature is 40°F. The calculated heat loss is 184 BTU/
Hr./°F.
The upper half of the form is for computing the heat loss of
the space to be conditioned. It is necessary only to insert
the proper measurements on the lines provided and multiply
by the given factors, then add this result for the total heat
loss in BTU/Hr./°F.
Subtract 40°F (lowest outdoor ambient temperature for the
geographical location) from 70°F (inside design temperature
of the unit) for a difference of 30°F. Multiply 184 by 30 for a
5500 BTU/Hr. total heat loss for the calculated space.
The BTU/Hr. per °F temperature difference is the 70°F
inside winter designed temperature minus the lowest outdoor
ambient winter temperature of the area where the unit is
installed. This temperature difference is used as the multiplier
when calculating the heat loss.
On the graph, plot the base point (70°) and a point on the
40°F line where it intersects with the 5500 BTU/Hr. line on
the left scale. Draw a straight line from the base point 70
through the point plotted at 40°F. This is the total heat loss
line.
The graph shows the following:
Knowing that we have a 5500 BTU/Hr. heat loss, and
we expect that our heat pump will maintain a 70°F inside
temperature at 40°F outdoor ambient, we plot the selected
unit capacity BTU/Hr. of the unit between 35° and 60° on the
graph and draw a straight line between these points. Where
the total heat loss line and the unit capacity line intersect,
read down to the outdoor ambient temperature scale and
find that this unit will deliver the required BTU/Hr. capacity
to approximately 30°F.
Left Hand Scale
Unit capacity BTU/Hr. or heat loss
BTU/Hr.
Bottom Scale
Outdoor ambient temperature, base
point.
Heat Pump Model
Balance Point
BTU/Hr. capacity heat pump will
deliver at outdoor temperatures.
Maximum BTU/Hr. heat pump
will deliver at indicated ambient
temperature.
41
HEATING LOAD FORM
FRIEDRICH ROOM UNIT HEAT PUMPS
BTU/HR PER
WALLS: (Linear Feet)
2” Insulation
°F TEMP. DIFFERENCE
Lin. Ft. x 1.6
Average
Lin. Ft. x 2.6
WINDOWS & DOORS (Area, sq. ft.)
Single Glass:
Sq. Ft. x 1.13
Sq. Ft. x 0.61
Double Glass:
INFILTRATION - WINDOWS & DOORS: AVG.
Lin. Ft. x 1.0
Lin. Ft. x 2.0
Loose
CEILING: (Area, Sq. Ft.)
Insulated (6”)
Sq. Ft. x 0.07
Sq. Ft. x 0.10
Sq. Ft. x 0.10
Sq. Ft. x 0.20
Sq. Ft. x 0.33
Insulated (2”)
Built-up Roof (2” insulated
Built-up Roof (1/2” insulated)
No Insulation
FLOOR: (Area, Sq. Ft.)
Above Vented Crawl space
Insulated (1:)
Sq. Ft. x 0.20
Sq. Ft. x 0.50
Uninsulated
* Slab on Ground
1” Perimeter insulation
* Based on Linear Feet of outside wall
Lin. Ft. x 1.70
Lin. Ft. x 1.00
TOTAL HEAT LOSS PER °F BTU/HR/°F
Multiply total BTU/HR/°F X 30 and plot on the graph below at 40°F. Draw a straight line from
the 70 base point thru the point plotted at 40°F. The intersection of this heat loss line with the
unit capacity line represents the winter design heating load.
42
Friedrich Air Conditioning Company
P.O. Box 1540
San Antonio, TX 78295
210.357.4400
ROOM AIR CONDITIONERS
LIMITED WARRANTY
FIRST YEAR
ANY PART: If any part supplied by FRIEDRICH fails because of a defect in workmanship or material within twelve months from date of original
purchase, FRIEDRICH will repair the product at no charge, provided room air conditioner is reasonably accessible for service. Any additional labor
cost for removing inaccessible units and/or charges for mileage related to travel by a Service Agency that exceeds 25 miles one way will be the
responsibility of the owner. This remedy is expressly agreed to be the exclusive remedy within twelve months from the date of the original purchase.
SECOND THROUGH FIFTH YEAR
SEALED REFRIGERANT SYSTEM:
because of a defect in workmanship or material within sixty months from date of purchase, FRIEDRICH will pay a labor allowance and parts
necessary to repair the Sealed Refrigeration System; PROVIDED FRIEDRICH will not pay the cost of diagnosis of the problem, removal, freight
charges, and transportation of the air conditioner to and from the Service Agency, and the reinstallation charges associated with repair of the
Sealed Refrigeration System. All such cost will be the sole responsibility of the owner. This remedy is expressly agreed to be the exclusive remedy
within sixty months from the date of the original purchase.
APPLICABILITY AND LIMITATIONS: This warranty is applicable only to units retained within the Fifty States of the U.S.A., District of Columbia,
and Canada. This warranty is not applicable to:
1.
A
2. Products on which the model and serial numbers have been removed.
3. Products which have defects or damage which results from improper installation, wiring, electrical current characteristics, or
installed in a corrosive atmosphere, default or delay in performance caused by war, government restrictions or restraints, strikes,
material shortages beyond the control of FRIEDRICH, or acts of God.
OBTAINING WARRANTY PERFORMANCE: Service will be provided by the FRIEDRICH Authorized Dealer or Service Organization in your
area. They are listed in the Yellow Pages. If assistance is required in obtaining warranty performance, write to: Room Air Conditioner Service
Manager, Friedrich Air Conditioning Co., P.O. Box 1540, San Antonio, TX 78295-1540.
LIMITATIONS: THIS WARRANTY IS GIVEN IN LIEU OF ALL OTHER WARRANTIES. Anything in the warranty notwithstanding, ANY
IMPLIED WARRANTIES OF FITNESS FOR PARTICULAR PURPOSE AND/OR MERCHANTABILITY SHALL BE LIMITED TO THE DURATION
OF THIS EXPRESS WARRANTY. MANUFACTURER EXPRESSLY DISCLAIMS AND EXCLUDES ANY LIABILITY FOR CONSEQUENTIAL
OR INCIDENTAL DAMAGE FOR BREACH OF ANY EXPRESSED OR IMPLIED WARRANTY.
Performance of Friedrich’s Warranty obligation is limited to one of the following methods:
1. Repair of the unit
2. A refund to the customer for the prorated value of the unit based upon the remaining warranty period of the unit.
3. Providing a replacement unit of equal value
NOTE: Some states do not allow limitations on how long an implied warranty lasts, or do not allow the limitation or exclusion of consequential or
incidental damages, so the foregoing exclusions and limitations may not apply to you.
OTHER:
PROOF OF PURCHASE: Owner must provide proof of purchase in order to receive any warranty related services.
All service calls for explaining the operation of this product will be the sole responsibility of the consumer.
All warranty service must be provided by an Authorized FRIEDRICH Service Agency, unless authorized by FRIEDRICH prior to repairs being made.
(10-08)
43
TECHNICAL SUPPORT
CONTACT INFORMATION
FRIEDRICH AIR CONDITIONING CO.
Post Office Box 1540 · San Antonio, Texas 78295-1540
4200 N. Pan Am Expressway · San Antonio, Texas 78218-5212
(210) 357-4400 · 877-599-5665 x 846 · FAX (210) 357-4490
Email: [email protected]
Printed in the U.S.A.
44
FRIEDRICH AIR CONDITIONING CO.
Post Office Box 1540 · San Antonio, Texas 78295-1540
4200 N. Pan Am Expressway · San Antonio, Texas 78218-5212
(210) 357-4400 · FAX (210) 357-4490
X-Star-ServMan (4-10)
Printed in the U.S.A.
|