Friedrich WallMaster PACKAGED TERMINAL AIR CONDITIONERS AND HEAT PUMPS User Manual |
AMERICA'S BEST AIR CONDITIONER
PRODUCT PROFILE
PACKAGED TERMINAL AIR CONDITIONERS AND HEAT PUMPS
®
The All-new Friedrich
WallMaster
WallMaster® is a perfect fit
7,000 / 9,000 / 12,000 / 15,000 Btu/h
for:
New construction in hotels/
motels, medical facilities, assisted
living centers, apartments/condos,
office suites, dormitories and
remodels.
The New WallMaster® retrofits
into existing 16" x 42" sleeves
more easily than other
manufacturer's PTACs.
Standard Features
! Ultrahigh efficiency. Up to 12.2 EER.
! Available in heat pump or electric heat.
! Unique component mounting and isolation
provide ultraquiet operation and vibration
dampening.
! Front cover fastens to chassis with
thumbscrews hidden from user.
! Emergency heat compressor override
! Large well spaced control panel with
universal markings and non-removable
controls
switch on all heat pumps.
! Single, totally enclosed "clam shell" motor
design protects against premature failure.
! Attractive front cover and tamper resistant
contoured discharge grille blend with any
decor.
! Optional seacoast protection for harsh
coastal environments.
! Complete line of accessories.
! Quiet and efficient rotary compressor
mounted on vibration isolators, with internal
high temperature overload protection.
! Remote thermostat control units are
available.
! Built-in damper allows up to 70 CFM of
! Units are rated in accordance with ARI
fresh air.
Standard 310/380.
! Convenient top-mounted return air filters.
! Manufactured in the U.S.A.
Extended Cooling Performance, PE07/09/12/15
Outdoor Dry Bulb Temp. (°F at 40% R.H.)
85 95 105
Indoor Wet Bulb Temp. (°F at 80°F D.B.)
67 62 72 67 62 72
75
67
115
67
72
62
72
67
62
72
62
Btuh
8820 8483 7853 8400 7920 7305 8070 7500 6638 7560 6713 5918 6728 5790 5115
502
2.5
510
2.5
515
2.5
547
2.7
552
2.7
559
2.7
615
3
615
615
3
665
3.2
664
3.2
0.8
666
3.2
725
3.5
725
3.5
728
3.5
Watts
Amps
SHR
PE07
PE09
3.00
0.52 0.71
0.95
0.53 0.73
0.97
0.53
0.76 0.98
0.55
0.98
0.57 0.86 0.97
10819 10405 9632 10304 9715 8961 9899 9200 8142 9274 8234 7259 8252 7102 6274
Btuh
664
3.2
0.51 0.70
675
3.2
682
3.3
0.94
724
3.5
0.52 0.72
731
3.5
740
3.5
0.96
814
3.9
0.53
814
3.90
814
3.9
0.75 0.96
880
4.2
0.54
879
4.2
0.79 0.97
882
4.2
960
4.6
960
4.6
964
4.6
Watts
Amps
SHR
0.57 0.84 0.96
14112 13572 12564 13440 12672 11688 12912 12000 10620 12096 10740 9468 10764 9264 8184
Btuh
915
4.2
0.49 0.67
929
4.2
939
4.3
0.9
997 1007 1019 1121 1091 1121 1212 1211 1214 1322 1322 1327
4.5
0.5
Watts
Amps
SHR
PE12
PE15
4.6
0.7
4.6
0.92
5.1
0.51
5.10
5.1
5.5
0.52
5.5
0.76 0.93
5.5
6
6
6
0.72 0.92
0.54 0.81 0.92
17640 16965 15705 16800 15840 14610 16140 15000 13275 15120 13425 11835 13455 11580 10230
1288 1309 1323 1404 1418 1435 1579 1579 1579 1707 1705 1710 1862 1862 1870
Btuh
Watts
Amps
SHR
5.5
5.5
5.6
0.94
5.9
5.9
5.9
0.96
6.6
0.53
6.60
6.6
7.1
0.54
7.1
7.1
7.7
7.7
7.8
0.51 0.70
0.52 0.72
0.72 0.96
0.79 0.97
0.57 0.84 0.96
RATING POINT
ARI 310/380
Extended Cooling Performance, PH07/09/12/15
Outdoor Dry Bulb Temp. (°F at 40% R.H.)
85 95 105
Indoor Wet Bulb Temp. (°F at 80°F D.B.)
67 62 72 67 62 72
75
67
115
72
62
72
67
62
72
67
62
Btuh
8820 8483 7853 8400 7920 7305 8070 7200 6638 7560 6713 5918 6728 5790 5115
502
2.5
510
2.5
515
2.5
547
2.7
552
2.7
559
2.7
615
3
595
615
3
665
3.2
664
3.2
0.8
666
3.2
725
3.5
725
3.5
728
3.5
Watts
Amps
SHR
PH07
PH09
3.00
0.52 0.71
0.95
0.53 0.73
0.97
0.53
0.76 0.98
0.55
0.98
0.57 0.86 0.97
10819 10405 9632 10304 9715 8961 9899 9100 8142 9274 8234 7259 8252 7102 6274
Btuh
657
3.2
0.51
667
3.2
0.7
675
3.3
0.94
716
3.5
0.52 0.72
723
3.5
732
3.5
0.96
805
3.9
0.53
805
3.90
805
3.9
0.75 0.96
870
4.2
0.54
869
4.2
0.79 0.97
872
4.2
949
4.6
949
4.6
953
4.6
Watts
Amps
SHR
0.57 0.84 0.96
14112 13572 12564 13440 12672 11688 12912 12000 10620 12096 10740 9468 10764 9264 8184
Btuh
915
4.2
0.49 0.67
929
4.2
939
4.3
0.9
997 1007 1019 1121 1121 1121 1212 1211 1214 1322 1322 1327
4.5
0.5
Watts
Amps
SHR
PH12
PH15
4.6
0.7
4.6
0.92
5.1
0.51
5.10
5.1
5.5
0.52
5.5
0.76 0.93
5.5
6
6
6
0.72 0.92
0.54 0.81 0.92
17640 16965 15705 16800 15840 14610 16140 14700 13275 15120 13425 11835 13455 11580 10230
1288 1309 1323 1404 1418 1435 1579 1581 1579 1707 1705 1710 1862 1862 1870
Btuh
Watts
Amps
SHR
5.5
5.5
5.6
0.94
5.9
5.9
5.9
0.96
6.6
0.53
6.6
6.6
7.1
0.54
7.1
7.1
7.7
7.7
7.8
0.51 0.70
0.52 0.72
0.72 0.96
0.79 0.97
0.57 0.84 0.96
RATING POINT
ARI 310/380
Extended Heating Performance
Outdoor Dry Bulb Temp. (°F)
37
42
47
52
57
Btuh
Watts
Amps
Btuh
5366
536
2.5
5663
545
2.6
6400
568
2.6
7053
577
2.7
7789
610
2.8
PH07
6005
6399
8100
8647
9245
Watts
Amps
Btuh
Watts
Amps
Btuh
PH09
PH12
PH15
666
3.1
7799
893
676
3.1
8611
927
742
3.2
747
3.2
757
3.3
10800
1021
4.3
13500
1413
5.8
11383
1051
4.5
14769
1497
6.1
12349
1085
4.7
16180
1564
6.3
3.8
3.9
10688
1301
5.3
11013
1318
5.4
Watts
Amps
RATING POINT
ARI 310/380
3
Electric Heat Data, PE/PH 07/09K/R
M
O
D
E
L
S
:
PE/PH07K
PE/PH07R
PE/PH09K
PE/PH09R
P
E
R
F
O
R
M
A
N
C
E
D
A
T
A
:
3400
265
3400
3400/2780
230/208
11600/9500
3500/2880
15.3/13.9
19
2500/2050
3400/2780
2500
2500/2050
5000/4090
2500
5000
Heater Watts
Voltage
Heating Btuh
230/208
8500/7000
265
11600
3490
13.2
16.4
20
11600
3490
13.2
16.4
20
8500
2590
9.8
8500/7000
2600/2150
11.4/10.4
14.1
8500
2590
9.8
17000
5210
19.5
24.2
30
11600/9500
3500/2880
15.3/13.9
19
17000/13900
5210/4300
22.3/20.3
27.8
Heating Power (Watts)
Heating Current (Amps)
Minimum Circuit Ampacity
Branch Circuit Fuse (Amps)
Nema Plug Face
2600/2150
11.4/10.4
14.1
12.2
15
12.2
15
20
15
20
15
30
N/A
6-20
6-15
6-20
6-15
6-30
N/A
Electric Heat Data, PE/PH 12/15K/R
M
O
D
E
L
S
:
PE/PH12K
PE/PH12R
PE/PH15K
PE/PH15R
E
L
E
C
T
R
I
C
H
E
A
T
D
A
T
A
:
Heater Watts
Voltage
Heating Btuh
Heating Power (Watts)
Heating Current (Amps)
Minimum Circuit Ampacity
BranchCircuitFuse(Amps)
Nema Plug Face
5000/4090
3400/2780
230/208
11600/9500
3500/2880
15.3/13.9
19
3400/2780
2500
3400
265
5000
2500/2050
5000/4090
2500
3400
265
5000
2500/2050
230/208
17000/13900
5210/4300
22.3/20.3
27.8
8500
2590
9.8
17000
5210
19.5
24.2
30
8500/7000
2600/2150
11.4/10.4
14.1
17000/13900
5210/4300
22.3/20.3
27.8
8500
2590
9.8
11600
3490
13.2
16.4
20
17000
5210
19.5
24.2
30
8500/7000 11600/9500
2600/2150 3500/2880
11600
3490
13.2
16.4
20
11.4/10.4
14.1
15.3/13.9
19
12.2
15
12.2
15
30
20
20
15
30
15
6-30
6-20
6-15
6-20
N/A
6-15
6-30
N/A
®
WallMaster PTAC/PTHP Model Identification Guide
3
S
A
1
P H 07 K
Engineering Digit
Design Series
Series
P = Packaged Terminal Unit
Options
S = Standard
System
X = Accessory
R = Remote Thermostat
C = Seacoast Protection
X = Remote Thermostat and
Seacoast Protection
E = Cooling with or
without electric heat
H = Heat Pump with
Auxiliary Heat
Nominal Cooling Capacity
Nominal Heater Size
(@ 230V or 265V)
0 = No Heater
2 = 2.5 KW
07 =
09 =
12 =
15 =
7,000
9,000
Btuh
Btuh
Btuh
Btuh
12,000
15,000
3 = 3.4 KW
5 = 5.0 KW
Voltage
K = 230/208V - 1Ph. - 60 Hz.
R = 265V - 1Ph. - 60 Hz.
Typical Unit Components and Dimensions
Outdoor
Wall
Front Cover
Dimensions:
16" H x 42" W x 7½" D
Filters
PXWS Wall
Sleeve
Dimensions:
16" H x 42" W
x 13¾" D
Cut-Out Dimensions:
Chassis
Front
Cover
16¼" x 42¼"
Return
Air Grille
4
Typical Wall Sleeve Installation (PXWS)
Electrical Receptacle
Insulation
Lintel Used To Support
Masonry Walls
16¼"
50"Max
Electrical
Receptacle
Main Studs
Smoothside of clip on Room side
Jack
Stud
Note the use of a lintel under the first course
of bricks above the wall sleeve. Do not use
the wall sleeve as a lintel. The mounting
screw holes shown are to be made by the
installer.
LINTEL
No holes are permitted in the top or bottom of
the sleeve. (Exception: PXDR10 Drain Kit)
Extended Wall Sleeve Installation and Sealant Locations (PXWE)
Wall Sleeve Extension, 42" X 16"
Frame, 20 gauge minimum,
painted or aluminum
Wall Sleeve
Outside Edge
Insulation
Air
Baffles
Sealant inside (4) bottom
corners
IMPORTANT NOTE: The
silicone bead MUST
extend 3" up the side of
the two flanges to
Width of Wall
Four
Condensate
Notches
prevent condensate
from leaking.
5
Internal Drain Kit Location and Installation (PXDR10)
Primary Area:
Condensation from the
chassis collects in the
sleeve in this area. The
Primary Area is the
preferred installation
location.
Wall Sleeve
Bottom
Foam Gasket
Mounting Plate
Tube
Screw
PXDR10 DRAIN KIT
Screw
1/2" O.D. Tube
Gasket
Mounting Plate
External Drain
When using an external drain system, the
condensate is removed through either of two
drain holes on the back of the wall sleeve. Select
the drain hole which best meets your drainage
situation and install the drain kit. Seal off the
other with a cover plate.
Foam Gasket
Cover Plate
Place the drain tube through the gasket and the
mounting plate with the flange toward the wall
sleeve.
Attach the drain tube assembly to one of the
two drain holes at the rear of the wall sleeve.
The large flange on the mounting plate is
positioned at the bottom of the sleeve facing
toward the sleeve. When the drain tube is
positioned at the desired angle, tighten the
screws.
Back
of wall
sleeve
1/2" O.D. Tube
Mounting
Plate
Foam Gasket
Architectural Louver Installation (PXAA)
Installation
1. Screw a threaded metal stud into each of
the holes at the four corners of the louver.
2. From inside the building, grasp the louver at
the vertical supports and maneuver the
louver through the wall sleeve. Pull towards
you until the threaded studs are inserted into
the four holes of the wall sleeve.
3. While holding the louver with one hand, start
washers and nuts on each of the four studs.
Tighten the nuts securely.
CAUTION:
Bodily injury can be caused by louvers falling from a
building during installation. It is recommended that a
safety line be attached to the louver and an anchor
point inside the building during installation.
6
WallMaster® PTAC/PTHP Engineering Specifications
All units shall be factory assembled, piped, wired and fully charged with R-22. All units shall be certified in accordance with
ARI Standard 310 for air conditioners and ARI Standard 380 for heat pumps. Units shall be UL listed and carry a UL label.
All units shall be factory run-tested to check operation and be Friedrich WallMaster® or equivalent.
The basic unit shall not exceed 16" high x 42" wide. Overall depth of the unit from the rear of the Friedrich wall sleeve to the
front of the decorative front cover shall not exceed 21¼". The unit shall be designed so that room intrusion may be as little
as 7¼". Installations in walls deeper than 13 ¼" may be accomplished with the use of a wall sleeve extension (PXWE). Unit
shall draw in ambient air through both sides of an outdoor architectural louver or grille measuring 42" wide x 16" high and
shall exhaust heated air out the middle portion of the louver. The architectural louver and wall sleeve shall be designed so
that the louver may be installed from the inside of the building.
REFRIGERATION SYSTEM - The refrigeration system shall consist of a hermetically sealed rotary compressor that is
externally mounted on vibration isolators no smaller than 1 ¾" dia. X 1 ½" high; condenser and evaporator coils constructed
of copper tubes and aluminum plate fins; and capillaries as expansion devices. Unit shall have a fan slinger ring to increase
efficiency and condensate disposal and have a drain pan capable of retaining 1½ gallons of condensate. A tertiary condensate
removal system shall also be incorporated for back up and shall overflow through the wall sleeve and to the outside of the
building as a safeguard against damage to the interior room.
AIR HANDLING SECTION - The evaporator and condenser fans shall be driven by a single, totally enclosed, ball bearing,
permanently lubricated split capacitor, "clam-shell" style fan motor. Airflow shall be directed into the room by a single,
injection molded, high-impact polystyrene discharge grille. The grill shall have openings no larger than 3/8" high x 3" wide
to prevent personal injury or damage to the PTAC unit, and will be reversible to allow air to be directed upward or outward as
determined by the installer.
The chassis shall have a built-in damper capable of providing at least 60 CFM of fresh air into the conditioned area. A fine
mesh screen shall filter the incoming fresh air. There must be a provision for locking the damper closed to ensure a proper
seal.
CONTROLS - Covered controls shall be accessible in a compartment at least 9" wide with the controls no deeper than 1¼" in
the opening to facilitate easy operation of the unit. Controls shall include dual rotary knobs for setting of the thermostat and
for mode control. The knobs will be tamper proof to prohibit the removal of knobs by the user and shall feature a temperature-
limiting device adjustable by the owner. The control panel shall be clearly marked and easy to read. Universal symbols shall
be used with markings no smaller than 12-point type. The chassis may be ordered with the option of remote thermostat
control.
Other controls accessible without removal of the chassis shall include fan cycle switch, fresh air vent control and emergency
heat override switch (heat pump only).
GENERAL CONSTRUCTION - The wall sleeve shall be constructed of 18 gauge G90 zinc-coated steel. It shall be prepared
by a process where it is zinc phosphate pretreated and sealed with a chromate rinse, then powder coated for maximum
coverage and protection. The sleeve shall be shipped with a protective weatherboard and a structural center support, and be
insulated for thermal efficiency. The grille or louver shall be shipped separately and made from stamped or extruded
anodized aluminum. All louvers shall be in the horizontal plane.
The front panel shall lock to the chassis by means of two factory-supplied thumbscrews to prevent tampering. The front
panel will feature a contoured discharge with no sharp corners. The air filters shall be reusable and be accessible without
removal of the front cover.
All 265V units shall possess an integral, over-current time-delay protective device.
The unit shall have a plastic fan, fan shroud and drain pan for corrosion protection and to help prevent rust on the side of the
building below the outdoor louver.
A complete line of accessories shall be available from Friedrich to equip the PTAC for a multitude of applications.
Friedrich Installation/Start-Up Specialists shall be available to answer questions regarding proper installation practices and
in some cases for on-site start-up inspections.
7
Friedrich PTAC Accessories
New Construction Accessories
MODEL NUMBER
DESCRIPTION
PHOTO
WALL SLEEVE G-90 zinc coated steel is prepared
in an eleven-step process, then powder coated for
maximum coverage and protection. The wall
sleeve is insulated for thermal efficiency. 16" High
x 42" Wide x 13¾" Deep.
PXWS
PXWS
GRILLE Standard, stamped aluminum, anodized
to resist chalking and oxidation.
PXGA
ARCHITECTURAL GRILLES Consist of heavy-
gauge 6063-T5 aluminum alloy:
– Clear, extruded aluminum
PXAA
PXDB
PXSC
– Dark bronze acrylic enamel
– Also available in custom colors.
PXDB
CONDENSATE DRAIN KIT Attaches to the bottom
of the wall sleeve for internal draining of condensate
or to the rear wall sleeve flange for external draining.
Recommended on all units to remove excess
condensate. Packaged in quantities of ten.
PXDR10
PXWE
PXDR10
DEEP WALL SLEEVE EXTENSION A four inch
deep anodized aluminum extension that attaches
to the outside of the wall sleeve when the wall is
greater than thirteen inches thick (11¾" when a
subbase is used, 12¼" when a lateral duct is used).
PXWE
DECORATIVE SUBBASE Provides unit support
for walls less than six inches thick. Includes leveling
legs, side filler panels and mounting brackets for
electrical accessories. Accepts circuit breaker,
power disconnect switch, or conduit kit.
PXSB
PXCJ
PXSB
CONDUIT KIT WITH JUNCTION BOX Hard wire
conduit kit with junction box for 208/230V and 256V
units (subbase not required). Kit includes a means
of quick disconnect for easy removal of the chassis.
*Required for 265V installations.
PXCJ
8
New Construction Accessories (Continued)
MODEL NUMBER
DESCRIPTION
PHOTO
DESK CONTROL KIT A field installed kit which
allows the unit to be turned on or off from a remote
central station via a 24V interface. This kit is
compatable with all chassis models.
PXDC
PXDC
DIGITAL REMOTE THERMOSTAT A Honeywell
wall mounted remote thermostat. Compatable only
with "RT" suffix chassis.
RT1
RT1
Additional Accessories
MODEL NUMBER
DESCRIPTION
PHOTO
SLEEVE EXTENSION RETROFIT KIT G-90 zinc
coated steel, 2¼" sleeve extension attached to the
room side of the sleeve to allow for the installation
of a P-Series Friedrich PTAC in a T-Series sleeve.
PXSE
PXDA
PXSE
LATERAL DUCT ADAPTER Attaches to the PTAC/
PTHP unit and provides a transition to direct up to
35% of the total CFM to a secondary room, either
left or right of the unit. Kit includes duct plenum
with discharge grille and internal baffle, adapter and
end cap.
LATERAL DUCT EXTENSION A three foot
insulated plenum that attaches to the left or right
side of the duct adapter. The extension can be cut
to length by the installer. Maximum allowable
straight extension is fifteen feet.
PXDA
PXDE
PXFT
REPLACEMENT FILTER PACK These are original
equipment return air filters. They are reusable and
can be cleaned by vacuuming, washing, or blowing
out, and are sold in convenient ten packs. (Two
filters per chassis).
PXFT
Chassis Options
ITEM
DESCRIPTION
STANDARD UNIT Standard PTAC/PCHP chassis. Can be 230/208V or 265V, electric
or heat pump.
S
REMOTE THERMOSTAT Chassis option necessary for wall mounted thermostat
control of the unit.
R
C
SEACOAST PROTECTION Additional protection for PTAC/PTHP units in a coastal or
corrosive environment. The entire outdoor coil is submerged in a specially formulated
enamel coating, then oven-cured for a tough, corrosion-resistant finish.
9
Friedrich WallMaster® P-Series
Packaged Terminal Air Conditioners
Limited Warranty
FRIEDRICH AIR CONDITIONING CO.
Post Office Box 1540 · San Antonio, Texas 78295-1540
(210) 357-4400 · FAX (210) 357-4480
SAVE THIS CERTIFICATE. It gives you specific rights, you may also have other rights which may vary from state to state and province to
province.
In the event that your unit needs servicing, contact your nearest authorized service center. If you do not know the nearest service center, ask
the company that installed your unit or contact us - see address and telephone number above.
When requesting service: please have the model and serial number from your unit readily available.
Unless specified otherwise herein, the following applies:
PACKAGED TERMINAL AIR CONDITIONERS AND HEAT PUMPS
LIMITED WARRANTY - FIRST YEAR (Eighteen (18) Months from the original date of purchase or twelve (12) months from
installation). Any defect in the unit’s material or workmanship will be repaired or replaced free of charge by our authorized service center
during the normal working hours; and
LIMITED WARRANTY - SECOND THROUGH FIFTH YEAR (Sixty-six (66) months from the date of purchase) ON THE SEALED REFRIG-
ERATION SYSTEM. Any part of the sealed refrigeration system on the P-series that is defective in material or workmanship will be repaired or
replaced free of charge (excluding freight charges) by our authorized service center during normal working hours. The sealed refrigeration
system consists of the compressor, metering device, evaporator, condenser, reversing valve, check valve, and the interconnecting tubing.
These warranties apply only while the unit remains at the original site and only to units installed inside the continental United
States, Alaska, Hawaii, Puerto Rico and Canada. The warranty applies only if the unit is installed and operated in accordance
with the printed instructions and in compliance with applicable local installation and building codes and good trade practices.
For international warranty information, contact the Friedrich Air Conditioning Company - International Division.
Reasonable proof must be presented to establish the original purchase date, otherwise the beginning date of this certificate will be considered
to be our shipment date plus sixty days. Replacement parts can be new or remanufactured. Replacement parts and labor are only warranted
for any unused portion of the unit’s warranty.
We will not be responsible for and the user will pay for:
1. Service calls to:
A) Instruct on unit operation. B) Replace house fuses or correct house wiring. C) Clean or replace air filters. D) Remove
the unit from inaccessible locations. E) Correct improper installations.
2. Parts or labor provided by anyone other than an authorized service center.
3. Damage caused by:
A) Accident, abuse, negligence, misuse, riot, fire, flood, or acts of God. B) Operating the unit where there is a corrosive atmo-
sphere containing chlorine, fluorine, or any damaging chemicals (other than in a normal residential environment). C) Unauthorized
alteration or repair of the unit, which in turn affects its stability or performance. D) Failing to provide proper maintenance and
service. E) Using other than a "Seacoast Protected" unit in a coastal environment. F) Using an incorrect power source. G) Faulty
installation or application of the unit.
We shall not be liable for any incidental, consequential, or special damages or expenses in connection with any use or failure
of this unit. We have not made and do not make any representation or warranty of fitness for a particular use or purpose and
there is no implied condition of fitness for a particular use or purpose. We make no expressed warranties except as stated in
this certificate. No one is authorized to change this certificate or to create for us any other obligation or liability in connection
with this unit. Any implied warranties shall last for one year after the original purchase date. Some states and provinces do
not allow limitations on how long an implied warranty or condition lasts, so the above limitations or exclusions may not apply
to you. The provisions of this warranty are in addition to and not a modification of or subtraction from the statutory warran-
ties and other rights and remedies provided by law.
In case of any questions regarding the provisions of this warranty, the English version will govern.
Revised 8/01
10
WALLMASTER® P-SERIES
PACKAGED TERMINAL AIR CONDITIONERS
Purchaser:
Project:
P.O. #
Date:
Location:
Architect:
For Approval:
Engineer:
Submitted By:
For Reference:
ITEM
PLAN DESIGNATION
QUANTITY
COOLING BTU/H
VOLTAGE
FRIEDRICH MODEL
ACCESSORIES
Qty
PXDR10
Qty
Qty
Qty
Qty
Qty
Qty
Qty
Qty
PXWS
PXWE
PXGA
PXAA
PXDB
PXSC
RT1
Wall Sleeve
Condensate Drain Kit (pkg/10)
Subbase
Qty
Qty
Qty
Qty
Qty
PXSB
PXDS
PXCJ
PXSE
PXDA
PXDE
PXDC
Deep Wall Extension
Standard Outdoor Louver
Architectural Louver, clear
Architectural Louver, dark bronze
Architectural Louver, color matched
Power Disconnect Switch
Conduit Kit w/Junction Box
T-Series Sleeve Adapter
Lateral Duct Adapter
Lateral Duct Extension
Desk Control Relay
Electronic Digital Remote Wall
Mounted Thermostat
Qty
FEATURES
"
"
"
"
"
"
Ultraquiet operation
Super high energy efficiency, up to 12.2 EER
Easy to use controls feature tamper-proof knobs
Built-in fresh air damper provides up to 70 CFM
Two cooling and heating speeds plus fan-only setting
Front cover fastens to chassis easily with thumbscrews hidden
from user
"
"
"
"
"
Thermostat limiter switch
Emergency heat switch (heat pump models)
Easy access, easy-to-clean filter
Made in the U.S.A.
UL Listed and ARI Certified
DIMENSIONS
Wall Sleeve
Overall Depth
Sleeve with Front
21¼"
Width
42"
Height
16"
Depth
13¾"
Wall Opening - 42¼" wide x 16¼" high
NOTES:
11
Multiplesolutions.
One trusted name.
Friedrich Air Conditioning Co.
Post Office Box 1540 · San Antonio, Texas 78295-1540
4200 N. Pan Am Expressway · San Antonio, Texas 78218-5212
(210) 357-4400 · FAX (210) 357-4480
Printed in the U.S.A.
PTACBW02 (04/02)