Friedrich WallMaster PACKAGED TERMINAL AIR CONDITIONERS AND HEAT PUMPS User Manual

AMERICA'S BEST AIR CONDITIONER  
PRODUCT PROFILE  
PACKAGED TERMINAL AIR CONDITIONERS AND HEAT PUMPS  
®
The All-new Friedrich  
WallMaster  
WallMaster® is a perfect fit  
7,000 / 9,000 / 12,000 / 15,000 Btu/h  
for:  
New construction in hotels/  
motels, medical facilities, assisted  
living centers, apartments/condos,  
office suites, dormitories and  
remodels.  
The New WallMaster® retrofits  
into existing 16" x 42" sleeves  
more easily than other  
manufacturer's PTACs.  
Standard Features  
! Ultrahigh efficiency. Up to 12.2 EER.  
! Available in heat pump or electric heat.  
! Unique component mounting and isolation  
provide ultraquiet operation and vibration  
dampening.  
! Front cover fastens to chassis with  
thumbscrews hidden from user.  
! Emergency heat compressor override  
! Large well spaced control panel with  
universal markings and non-removable  
controls  
switch on all heat pumps.  
! Single, totally enclosed "clam shell" motor  
design protects against premature failure.  
! Attractive front cover and tamper resistant  
contoured discharge grille blend with any  
decor.  
! Optional seacoast protection for harsh  
coastal environments.  
! Complete line of accessories.  
! Quiet and efficient rotary compressor  
mounted on vibration isolators, with internal  
high temperature overload protection.  
! Remote thermostat control units are  
available.  
! Built-in damper allows up to 70 CFM of  
! Units are rated in accordance with ARI  
fresh air.  
Standard 310/380.  
! Convenient top-mounted return air filters.  
! Manufactured in the U.S.A.  
Extended Cooling Performance, PE07/09/12/15  
Outdoor Dry Bulb Temp. (°F at 40% R.H.)  
85 95 105  
Indoor Wet Bulb Temp. (°F at 80°F D.B.)  
67 62 72 67 62 72  
75  
67  
115  
67  
72  
62  
72  
67  
62  
72  
62  
Btuh  
8820 8483 7853 8400 7920 7305 8070 7500 6638 7560 6713 5918 6728 5790 5115  
502  
2.5  
510  
2.5  
515  
2.5  
547  
2.7  
552  
2.7  
559  
2.7  
615  
3
615  
615  
3
665  
3.2  
664  
3.2  
0.8  
666  
3.2  
725  
3.5  
725  
3.5  
728  
3.5  
Watts  
Amps  
SHR  
PE07  
PE09  
3.00  
0.52 0.71  
0.95  
0.53 0.73  
0.97  
0.53  
0.76 0.98  
0.55  
0.98  
0.57 0.86 0.97  
10819 10405 9632 10304 9715 8961 9899 9200 8142 9274 8234 7259 8252 7102 6274  
Btuh  
664  
3.2  
0.51 0.70  
675  
3.2  
682  
3.3  
0.94  
724  
3.5  
0.52 0.72  
731  
3.5  
740  
3.5  
0.96  
814  
3.9  
0.53  
814  
3.90  
814  
3.9  
0.75 0.96  
880  
4.2  
0.54  
879  
4.2  
0.79 0.97  
882  
4.2  
960  
4.6  
960  
4.6  
964  
4.6  
Watts  
Amps  
SHR  
0.57 0.84 0.96  
14112 13572 12564 13440 12672 11688 12912 12000 10620 12096 10740 9468 10764 9264 8184  
Btuh  
915  
4.2  
0.49 0.67  
929  
4.2  
939  
4.3  
0.9  
997 1007 1019 1121 1091 1121 1212 1211 1214 1322 1322 1327  
4.5  
0.5  
Watts  
Amps  
SHR  
PE12  
PE15  
4.6  
0.7  
4.6  
0.92  
5.1  
0.51  
5.10  
5.1  
5.5  
0.52  
5.5  
0.76 0.93  
5.5  
6
6
6
0.72 0.92  
0.54 0.81 0.92  
17640 16965 15705 16800 15840 14610 16140 15000 13275 15120 13425 11835 13455 11580 10230  
1288 1309 1323 1404 1418 1435 1579 1579 1579 1707 1705 1710 1862 1862 1870  
Btuh  
Watts  
Amps  
SHR  
5.5  
5.5  
5.6  
0.94  
5.9  
5.9  
5.9  
0.96  
6.6  
0.53  
6.60  
6.6  
7.1  
0.54  
7.1  
7.1  
7.7  
7.7  
7.8  
0.51 0.70  
0.52 0.72  
0.72 0.96  
0.79 0.97  
0.57 0.84 0.96  
RATING POINT  
ARI 310/380  
Extended Cooling Performance, PH07/09/12/15  
Outdoor Dry Bulb Temp. (°F at 40% R.H.)  
85 95 105  
Indoor Wet Bulb Temp. (°F at 80°F D.B.)  
67 62 72 67 62 72  
75  
67  
115  
72  
62  
72  
67  
62  
72  
67  
62  
Btuh  
8820 8483 7853 8400 7920 7305 8070 7200 6638 7560 6713 5918 6728 5790 5115  
502  
2.5  
510  
2.5  
515  
2.5  
547  
2.7  
552  
2.7  
559  
2.7  
615  
3
595  
615  
3
665  
3.2  
664  
3.2  
0.8  
666  
3.2  
725  
3.5  
725  
3.5  
728  
3.5  
Watts  
Amps  
SHR  
PH07  
PH09  
3.00  
0.52 0.71  
0.95  
0.53 0.73  
0.97  
0.53  
0.76 0.98  
0.55  
0.98  
0.57 0.86 0.97  
10819 10405 9632 10304 9715 8961 9899 9100 8142 9274 8234 7259 8252 7102 6274  
Btuh  
657  
3.2  
0.51  
667  
3.2  
0.7  
675  
3.3  
0.94  
716  
3.5  
0.52 0.72  
723  
3.5  
732  
3.5  
0.96  
805  
3.9  
0.53  
805  
3.90  
805  
3.9  
0.75 0.96  
870  
4.2  
0.54  
869  
4.2  
0.79 0.97  
872  
4.2  
949  
4.6  
949  
4.6  
953  
4.6  
Watts  
Amps  
SHR  
0.57 0.84 0.96  
14112 13572 12564 13440 12672 11688 12912 12000 10620 12096 10740 9468 10764 9264 8184  
Btuh  
915  
4.2  
0.49 0.67  
929  
4.2  
939  
4.3  
0.9  
997 1007 1019 1121 1121 1121 1212 1211 1214 1322 1322 1327  
4.5  
0.5  
Watts  
Amps  
SHR  
PH12  
PH15  
4.6  
0.7  
4.6  
0.92  
5.1  
0.51  
5.10  
5.1  
5.5  
0.52  
5.5  
0.76 0.93  
5.5  
6
6
6
0.72 0.92  
0.54 0.81 0.92  
17640 16965 15705 16800 15840 14610 16140 14700 13275 15120 13425 11835 13455 11580 10230  
1288 1309 1323 1404 1418 1435 1579 1581 1579 1707 1705 1710 1862 1862 1870  
Btuh  
Watts  
Amps  
SHR  
5.5  
5.5  
5.6  
0.94  
5.9  
5.9  
5.9  
0.96  
6.6  
0.53  
6.6  
6.6  
7.1  
0.54  
7.1  
7.1  
7.7  
7.7  
7.8  
0.51 0.70  
0.52 0.72  
0.72 0.96  
0.79 0.97  
0.57 0.84 0.96  
RATING POINT  
ARI 310/380  
Extended Heating Performance  
Outdoor Dry Bulb Temp. (°F)  
37  
42  
47  
52  
57  
Btuh  
Watts  
Amps  
Btuh  
5366  
536  
2.5  
5663  
545  
2.6  
6400  
568  
2.6  
7053  
577  
2.7  
7789  
610  
2.8  
PH07  
6005  
6399  
8100  
8647  
9245  
Watts  
Amps  
Btuh  
Watts  
Amps  
Btuh  
PH09  
PH12  
PH15  
666  
3.1  
7799  
893  
676  
3.1  
8611  
927  
742  
3.2  
747  
3.2  
757  
3.3  
10800  
1021  
4.3  
13500  
1413  
5.8  
11383  
1051  
4.5  
14769  
1497  
6.1  
12349  
1085  
4.7  
16180  
1564  
6.3  
3.8  
3.9  
10688  
1301  
5.3  
11013  
1318  
5.4  
Watts  
Amps  
RATING POINT  
ARI 310/380  
3
Electric Heat Data, PE/PH 07/09K/R  
M
O
D
E
L
S
:
PE/PH07K  
PE/PH07R  
PE/PH09K  
PE/PH09R  
P
E
R
F
O
R
M
A
N
C
E
D
A
T
A
:
3400  
265  
3400  
3400/2780  
230/208  
11600/9500  
3500/2880  
15.3/13.9  
19  
2500/2050  
3400/2780  
2500  
2500/2050  
5000/4090  
2500  
5000  
Heater Watts  
Voltage  
Heating Btuh  
230/208  
8500/7000  
265  
11600  
3490  
13.2  
16.4  
20  
11600  
3490  
13.2  
16.4  
20  
8500  
2590  
9.8  
8500/7000  
2600/2150  
11.4/10.4  
14.1  
8500  
2590  
9.8  
17000  
5210  
19.5  
24.2  
30  
11600/9500  
3500/2880  
15.3/13.9  
19  
17000/13900  
5210/4300  
22.3/20.3  
27.8  
Heating Power (Watts)  
Heating Current (Amps)  
Minimum Circuit Ampacity  
Branch Circuit Fuse (Amps)  
Nema Plug Face  
2600/2150  
11.4/10.4  
14.1  
12.2  
15  
12.2  
15  
20  
15  
20  
15  
30  
N/A  
6-20  
6-15  
6-20  
6-15  
6-30  
N/A  
Electric Heat Data, PE/PH 12/15K/R  
M
O
D
E
L
S
:
PE/PH12K  
PE/PH12R  
PE/PH15K  
PE/PH15R  
E
L
E
C
T
R
I
C
H
E
A
T
D
A
T
A
:
Heater Watts  
Voltage  
Heating Btuh  
Heating Power (Watts)  
Heating Current (Amps)  
Minimum Circuit Ampacity  
BranchCircuitFuse(Amps)  
Nema Plug Face  
5000/4090  
3400/2780  
230/208  
11600/9500  
3500/2880  
15.3/13.9  
19  
3400/2780  
2500  
3400  
265  
5000  
2500/2050  
5000/4090  
2500  
3400  
265  
5000  
2500/2050  
230/208  
17000/13900  
5210/4300  
22.3/20.3  
27.8  
8500  
2590  
9.8  
17000  
5210  
19.5  
24.2  
30  
8500/7000  
2600/2150  
11.4/10.4  
14.1  
17000/13900  
5210/4300  
22.3/20.3  
27.8  
8500  
2590  
9.8  
11600  
3490  
13.2  
16.4  
20  
17000  
5210  
19.5  
24.2  
30  
8500/7000 11600/9500  
2600/2150 3500/2880  
11600  
3490  
13.2  
16.4  
20  
11.4/10.4  
14.1  
15.3/13.9  
19  
12.2  
15  
12.2  
15  
30  
20  
20  
15  
30  
15  
6-30  
6-20  
6-15  
6-20  
N/A  
6-15  
6-30  
N/A  
®
WallMaster PTAC/PTHP Model Identification Guide  
3
S
A
1
P H 07 K  
Engineering Digit  
Design Series  
Series  
P = Packaged Terminal Unit  
Options  
S = Standard  
System  
X = Accessory  
R = Remote Thermostat  
C = Seacoast Protection  
X = Remote Thermostat and  
Seacoast Protection  
E = Cooling with or  
without electric heat  
H = Heat Pump with  
Auxiliary Heat  
Nominal Cooling Capacity  
Nominal Heater Size  
(@ 230V or 265V)  
0 = No Heater  
2 = 2.5 KW  
07 =  
09 =  
12 =  
15 =  
7,000  
9,000  
Btuh  
Btuh  
Btuh  
Btuh  
12,000  
15,000  
3 = 3.4 KW  
5 = 5.0 KW  
Voltage  
K = 230/208V - 1Ph. - 60 Hz.  
R = 265V - 1Ph. - 60 Hz.  
Typical Unit Components and Dimensions  
Outdoor  
Wall  
Front Cover  
Dimensions:  
16" H x 42" W x 7½" D  
Filters  
PXWS Wall  
Sleeve  
Dimensions:  
16" H x 42" W  
x 13¾" D  
Cut-Out Dimensions:  
Chassis  
Front  
Cover  
16¼" x 42¼"  
Return  
Air Grille  
4
Typical Wall Sleeve Installation (PXWS)  
Electrical Receptacle  
Insulation  
Lintel Used To Support  
Masonry Walls  
16¼"  
50"Max  
Electrical  
Receptacle  
Main Studs  
Smoothside of clip on Room side  
Jack  
Stud  
Note the use of a lintel under the first course  
of bricks above the wall sleeve. Do not use  
the wall sleeve as a lintel. The mounting  
screw holes shown are to be made by the  
installer.  
LINTEL  
No holes are permitted in the top or bottom of  
the sleeve. (Exception: PXDR10 Drain Kit)  
Extended Wall Sleeve Installation and Sealant Locations (PXWE)  
Wall Sleeve Extension, 42" X 16"  
Frame, 20 gauge minimum,  
painted or aluminum  
Wall Sleeve  
Outside Edge  
Insulation  
Air  
Baffles  
Sealant inside (4) bottom  
corners  
IMPORTANT NOTE: The  
silicone bead MUST  
extend 3" up the side of  
the two flanges to  
Width of Wall  
Four  
Condensate  
Notches  
prevent condensate  
from leaking.  
5
Internal Drain Kit Location and Installation (PXDR10)  
Primary Area:  
Condensation from the  
chassis collects in the  
sleeve in this area. The  
Primary Area is the  
preferred installation  
location.  
Wall Sleeve  
Bottom  
Foam Gasket  
Mounting Plate  
Tube  
Screw  
PXDR10 DRAIN KIT  
Screw  
1/2" O.D. Tube  
Gasket  
Mounting Plate  
External Drain  
When using an external drain system, the  
condensate is removed through either of two  
drain holes on the back of the wall sleeve. Select  
the drain hole which best meets your drainage  
situation and install the drain kit. Seal off the  
other with a cover plate.  
Foam Gasket  
Cover Plate  
Place the drain tube through the gasket and the  
mounting plate with the flange toward the wall  
sleeve.  
Attach the drain tube assembly to one of the  
two drain holes at the rear of the wall sleeve.  
The large flange on the mounting plate is  
positioned at the bottom of the sleeve facing  
toward the sleeve. When the drain tube is  
positioned at the desired angle, tighten the  
screws.  
Back  
of wall  
sleeve  
1/2" O.D. Tube  
Mounting  
Plate  
Foam Gasket  
Architectural Louver Installation (PXAA)  
Installation  
1. Screw a threaded metal stud into each of  
the holes at the four corners of the louver.  
2. From inside the building, grasp the louver at  
the vertical supports and maneuver the  
louver through the wall sleeve. Pull towards  
you until the threaded studs are inserted into  
the four holes of the wall sleeve.  
3. While holding the louver with one hand, start  
washers and nuts on each of the four studs.  
Tighten the nuts securely.  
CAUTION:  
Bodily injury can be caused by louvers falling from a  
building during installation. It is recommended that a  
safety line be attached to the louver and an anchor  
point inside the building during installation.  
6
WallMaster® PTAC/PTHP Engineering Specifications  
All units shall be factory assembled, piped, wired and fully charged with R-22. All units shall be certified in accordance with  
ARI Standard 310 for air conditioners and ARI Standard 380 for heat pumps. Units shall be UL listed and carry a UL label.  
All units shall be factory run-tested to check operation and be Friedrich WallMaster® or equivalent.  
The basic unit shall not exceed 16" high x 42" wide. Overall depth of the unit from the rear of the Friedrich wall sleeve to the  
front of the decorative front cover shall not exceed 21¼". The unit shall be designed so that room intrusion may be as little  
as 7¼". Installations in walls deeper than 13 ¼" may be accomplished with the use of a wall sleeve extension (PXWE). Unit  
shall draw in ambient air through both sides of an outdoor architectural louver or grille measuring 42" wide x 16" high and  
shall exhaust heated air out the middle portion of the louver. The architectural louver and wall sleeve shall be designed so  
that the louver may be installed from the inside of the building.  
REFRIGERATION SYSTEM - The refrigeration system shall consist of a hermetically sealed rotary compressor that is  
externally mounted on vibration isolators no smaller than 1 ¾" dia. X 1 ½" high; condenser and evaporator coils constructed  
of copper tubes and aluminum plate fins; and capillaries as expansion devices. Unit shall have a fan slinger ring to increase  
efficiency and condensate disposal and have a drain pan capable of retaining 1½ gallons of condensate. A tertiary condensate  
removal system shall also be incorporated for back up and shall overflow through the wall sleeve and to the outside of the  
building as a safeguard against damage to the interior room.  
AIR HANDLING SECTION - The evaporator and condenser fans shall be driven by a single, totally enclosed, ball bearing,  
permanently lubricated split capacitor, "clam-shell" style fan motor. Airflow shall be directed into the room by a single,  
injection molded, high-impact polystyrene discharge grille. The grill shall have openings no larger than 3/8" high x 3" wide  
to prevent personal injury or damage to the PTAC unit, and will be reversible to allow air to be directed upward or outward as  
determined by the installer.  
The chassis shall have a built-in damper capable of providing at least 60 CFM of fresh air into the conditioned area. A fine  
mesh screen shall filter the incoming fresh air. There must be a provision for locking the damper closed to ensure a proper  
seal.  
CONTROLS - Covered controls shall be accessible in a compartment at least 9" wide with the controls no deeper than 1¼" in  
the opening to facilitate easy operation of the unit. Controls shall include dual rotary knobs for setting of the thermostat and  
for mode control. The knobs will be tamper proof to prohibit the removal of knobs by the user and shall feature a temperature-  
limiting device adjustable by the owner. The control panel shall be clearly marked and easy to read. Universal symbols shall  
be used with markings no smaller than 12-point type. The chassis may be ordered with the option of remote thermostat  
control.  
Other controls accessible without removal of the chassis shall include fan cycle switch, fresh air vent control and emergency  
heat override switch (heat pump only).  
GENERAL CONSTRUCTION - The wall sleeve shall be constructed of 18 gauge G90 zinc-coated steel. It shall be prepared  
by a process where it is zinc phosphate pretreated and sealed with a chromate rinse, then powder coated for maximum  
coverage and protection. The sleeve shall be shipped with a protective weatherboard and a structural center support, and be  
insulated for thermal efficiency. The grille or louver shall be shipped separately and made from stamped or extruded  
anodized aluminum. All louvers shall be in the horizontal plane.  
The front panel shall lock to the chassis by means of two factory-supplied thumbscrews to prevent tampering. The front  
panel will feature a contoured discharge with no sharp corners. The air filters shall be reusable and be accessible without  
removal of the front cover.  
All 265V units shall possess an integral, over-current time-delay protective device.  
The unit shall have a plastic fan, fan shroud and drain pan for corrosion protection and to help prevent rust on the side of the  
building below the outdoor louver.  
A complete line of accessories shall be available from Friedrich to equip the PTAC for a multitude of applications.  
Friedrich Installation/Start-Up Specialists shall be available to answer questions regarding proper installation practices and  
in some cases for on-site start-up inspections.  
7
Friedrich PTAC Accessories  
New Construction Accessories  
MODEL NUMBER  
DESCRIPTION  
PHOTO  
WALL SLEEVE G-90 zinc coated steel is prepared  
in an eleven-step process, then powder coated for  
maximum coverage and protection. The wall  
sleeve is insulated for thermal efficiency. 16" High  
x 42" Wide x 13¾" Deep.  
PXWS  
PXWS  
GRILLE Standard, stamped aluminum, anodized  
to resist chalking and oxidation.  
PXGA  
ARCHITECTURAL GRILLES Consist of heavy-  
gauge 6063-T5 aluminum alloy:  
– Clear, extruded aluminum  
PXAA  
PXDB  
PXSC  
– Dark bronze acrylic enamel  
– Also available in custom colors.  
PXDB  
CONDENSATE DRAIN KIT Attaches to the bottom  
of the wall sleeve for internal draining of condensate  
or to the rear wall sleeve flange for external draining.  
Recommended on all units to remove excess  
condensate. Packaged in quantities of ten.  
PXDR10  
PXWE  
PXDR10  
DEEP WALL SLEEVE EXTENSION A four inch  
deep anodized aluminum extension that attaches  
to the outside of the wall sleeve when the wall is  
greater than thirteen inches thick (11¾" when a  
subbase is used, 12¼" when a lateral duct is used).  
PXWE  
DECORATIVE SUBBASE Provides unit support  
for walls less than six inches thick. Includes leveling  
legs, side filler panels and mounting brackets for  
electrical accessories. Accepts circuit breaker,  
power disconnect switch, or conduit kit.  
PXSB  
PXCJ  
PXSB  
CONDUIT KIT WITH JUNCTION BOX Hard wire  
conduit kit with junction box for 208/230V and 256V  
units (subbase not required). Kit includes a means  
of quick disconnect for easy removal of the chassis.  
*Required for 265V installations.  
PXCJ  
8
New Construction Accessories (Continued)  
MODEL NUMBER  
DESCRIPTION  
PHOTO  
DESK CONTROL KIT A field installed kit which  
allows the unit to be turned on or off from a remote  
central station via a 24V interface. This kit is  
compatable with all chassis models.  
PXDC  
PXDC  
DIGITAL REMOTE THERMOSTAT A Honeywell  
wall mounted remote thermostat. Compatable only  
with "RT" suffix chassis.  
RT1  
RT1  
Additional Accessories  
MODEL NUMBER  
DESCRIPTION  
PHOTO  
SLEEVE EXTENSION RETROFIT KIT G-90 zinc  
coated steel, 2¼" sleeve extension attached to the  
room side of the sleeve to allow for the installation  
of a P-Series Friedrich PTAC in a T-Series sleeve.  
PXSE  
PXDA  
PXSE  
LATERAL DUCT ADAPTER Attaches to the PTAC/  
PTHP unit and provides a transition to direct up to  
35% of the total CFM to a secondary room, either  
left or right of the unit. Kit includes duct plenum  
with discharge grille and internal baffle, adapter and  
end cap.  
LATERAL DUCT EXTENSION A three foot  
insulated plenum that attaches to the left or right  
side of the duct adapter. The extension can be cut  
to length by the installer. Maximum allowable  
straight extension is fifteen feet.  
PXDA  
PXDE  
PXFT  
REPLACEMENT FILTER PACK These are original  
equipment return air filters. They are reusable and  
can be cleaned by vacuuming, washing, or blowing  
out, and are sold in convenient ten packs. (Two  
filters per chassis).  
PXFT  
Chassis Options  
ITEM  
DESCRIPTION  
STANDARD UNIT Standard PTAC/PCHP chassis. Can be 230/208V or 265V, electric  
or heat pump.  
S
REMOTE THERMOSTAT Chassis option necessary for wall mounted thermostat  
control of the unit.  
R
C
SEACOAST PROTECTION Additional protection for PTAC/PTHP units in a coastal or  
corrosive environment. The entire outdoor coil is submerged in a specially formulated  
enamel coating, then oven-cured for a tough, corrosion-resistant finish.  
9
Friedrich WallMaster® P-Series  
Packaged Terminal Air Conditioners  
Limited Warranty  
FRIEDRICH AIR CONDITIONING CO.  
Post Office Box 1540 · San Antonio, Texas 78295-1540  
(210) 357-4400 · FAX (210) 357-4480  
SAVE THIS CERTIFICATE. It gives you specific rights, you may also have other rights which may vary from state to state and province to  
province.  
In the event that your unit needs servicing, contact your nearest authorized service center. If you do not know the nearest service center, ask  
the company that installed your unit or contact us - see address and telephone number above.  
When requesting service: please have the model and serial number from your unit readily available.  
Unless specified otherwise herein, the following applies:  
PACKAGED TERMINAL AIR CONDITIONERS AND HEAT PUMPS  
LIMITED WARRANTY - FIRST YEAR (Eighteen (18) Months from the original date of purchase or twelve (12) months from  
installation). Any defect in the unit’s material or workmanship will be repaired or replaced free of charge by our authorized service center  
during the normal working hours; and  
LIMITED WARRANTY - SECOND THROUGH FIFTH YEAR (Sixty-six (66) months from the date of purchase) ON THE SEALED REFRIG-  
ERATION SYSTEM. Any part of the sealed refrigeration system on the P-series that is defective in material or workmanship will be repaired or  
replaced free of charge (excluding freight charges) by our authorized service center during normal working hours. The sealed refrigeration  
system consists of the compressor, metering device, evaporator, condenser, reversing valve, check valve, and the interconnecting tubing.  
These warranties apply only while the unit remains at the original site and only to units installed inside the continental United  
States, Alaska, Hawaii, Puerto Rico and Canada. The warranty applies only if the unit is installed and operated in accordance  
with the printed instructions and in compliance with applicable local installation and building codes and good trade practices.  
For international warranty information, contact the Friedrich Air Conditioning Company - International Division.  
Reasonable proof must be presented to establish the original purchase date, otherwise the beginning date of this certificate will be considered  
to be our shipment date plus sixty days. Replacement parts can be new or remanufactured. Replacement parts and labor are only warranted  
for any unused portion of the unit’s warranty.  
We will not be responsible for and the user will pay for:  
1. Service calls to:  
A) Instruct on unit operation. B) Replace house fuses or correct house wiring. C) Clean or replace air filters. D) Remove  
the unit from inaccessible locations. E) Correct improper installations.  
2. Parts or labor provided by anyone other than an authorized service center.  
3. Damage caused by:  
A) Accident, abuse, negligence, misuse, riot, fire, flood, or acts of God. B) Operating the unit where there is a corrosive atmo-  
sphere containing chlorine, fluorine, or any damaging chemicals (other than in a normal residential environment). C) Unauthorized  
alteration or repair of the unit, which in turn affects its stability or performance. D) Failing to provide proper maintenance and  
service. E) Using other than a "Seacoast Protected" unit in a coastal environment. F) Using an incorrect power source. G) Faulty  
installation or application of the unit.  
We shall not be liable for any incidental, consequential, or special damages or expenses in connection with any use or failure  
of this unit. We have not made and do not make any representation or warranty of fitness for a particular use or purpose and  
there is no implied condition of fitness for a particular use or purpose. We make no expressed warranties except as stated in  
this certificate. No one is authorized to change this certificate or to create for us any other obligation or liability in connection  
with this unit. Any implied warranties shall last for one year after the original purchase date. Some states and provinces do  
not allow limitations on how long an implied warranty or condition lasts, so the above limitations or exclusions may not apply  
to you. The provisions of this warranty are in addition to and not a modification of or subtraction from the statutory warran-  
ties and other rights and remedies provided by law.  
In case of any questions regarding the provisions of this warranty, the English version will govern.  
Revised 8/01  
10  
WALLMASTER® P-SERIES  
PACKAGED TERMINAL AIR CONDITIONERS  
Purchaser:  
Project:  
P.O. #  
Date:  
Location:  
Architect:  
For Approval:  
Engineer:  
Submitted By:  
For Reference:  
ITEM  
PLAN DESIGNATION  
QUANTITY  
COOLING BTU/H  
VOLTAGE  
FRIEDRICH MODEL  
ACCESSORIES  
Qty  
PXDR10  
Qty  
Qty  
Qty  
Qty  
Qty  
Qty  
Qty  
Qty  
PXWS  
PXWE  
PXGA  
PXAA  
PXDB  
PXSC  
RT1  
Wall Sleeve  
Condensate Drain Kit (pkg/10)  
Subbase  
Qty  
Qty  
Qty  
Qty  
Qty  
PXSB  
PXDS  
PXCJ  
PXSE  
PXDA  
PXDE  
PXDC  
Deep Wall Extension  
Standard Outdoor Louver  
Architectural Louver, clear  
Architectural Louver, dark bronze  
Architectural Louver, color matched  
Power Disconnect Switch  
Conduit Kit w/Junction Box  
T-Series Sleeve Adapter  
Lateral Duct Adapter  
Lateral Duct Extension  
Desk Control Relay  
Electronic Digital Remote Wall  
Mounted Thermostat  
Qty  
FEATURES  
"
"
"
"
"
"
Ultraquiet operation  
Super high energy efficiency, up to 12.2 EER  
Easy to use controls feature tamper-proof knobs  
Built-in fresh air damper provides up to 70 CFM  
Two cooling and heating speeds plus fan-only setting  
Front cover fastens to chassis easily with thumbscrews hidden  
from user  
"
"
"
"
"
Thermostat limiter switch  
Emergency heat switch (heat pump models)  
Easy access, easy-to-clean filter  
Made in the U.S.A.  
UL Listed and ARI Certified  
DIMENSIONS  
Wall Sleeve  
Overall Depth  
Sleeve with Front  
21¼"  
Width  
42"  
Height  
16"  
Depth  
13¾"  
Wall Opening - 42¼" wide x 16¼" high  
NOTES:  
11  
Multiplesolutions.  
One trusted name.  
Friedrich Air Conditioning Co.  
Post Office Box 1540 · San Antonio, Texas 78295-1540  
4200 N. Pan Am Expressway · San Antonio, Texas 78218-5212  
(210) 357-4400 · FAX (210) 357-4480  
Printed in the U.S.A.  
PTACBW02 (04/02)  
12  

Aiphone LAF C CONSOLE MASTER LAF 20C User Manual