Friedrich MW09Y3H User Manual

MANUAL  
MODE D’EMPLOI  
MW09Y3H  
MW12Y3H  
MR09Y3H  
MR12Y3H  
CONSERVEZ CE MODE D'EMPLOI  
POUR RÉFÉRENCE ULTÉRIEUR  
9332280005-01  
FEATURES AND FUNCTIONS  
INVERTER  
SWING OPERATION  
At the start of operation, a large power is used to bring the  
room quickly to the desired temperature. Afterward, the air  
conditioner automatically switches to a low power setting  
for economic and comfortable operation.  
The Air Flow Direction Louvers swings automatically up and  
down so that the air speeds to every nook and corner of  
your room.  
REMOVABLE INTAKE GRILLE  
COIL DRY OPERATION  
The indoor units Intake Grille can be removed for easy clean-  
ing and maintenance.  
The Indoor unit can be dried by pressing the COIL DRY but-  
ton on the Remote Control Unit so as to avoid going moldy  
and restrain the breed of bacterium.  
MILDEW-RESISTANT FILTER  
The AIR FILTER has been treated to resist mildew growth,  
thus allowing cleaner use and easier care.  
AUTO CHANGEOVER  
The operation mode (cooling, dry, heating) is switched au-  
tomatically to maintain the set temperature, and the tem-  
perature is kept constant at all times.  
SUPER QUIET OPERATION  
When the FAN button is used to select QUIET, the indoor  
unit begins super-quiet operation; the indoor units airflow  
is reduced to produce quieter operation.  
MINIMUM HEAT OPERATION  
The room temperature can be maintained at 50 °F so as to  
prevent the room temperature from falling too far.  
PROGRAM TIMER  
The program timer allows you to integrate OFF timer and  
ON timer operations in a single sequence. The sequence  
can involve one transition from OFF timer to ON timer, or  
from ON timer to OFF timer, within a twenty-four hour pe-  
riod.  
SLEEP TIMER  
When the SLEEP button is pressed during Heating mode,  
the indoor units thermostat setting is gradually lowered  
during the period of operation; during cooling mode, the  
thermostat setting is gradually raised during the period of  
operation. When the set time is reached, the indoor unit au-  
tomatically turns off.  
WIRELESS REMOTE CONTROL UNIT  
The Wireless Remote Control Unit allows convenient con-  
trol of indoor unit operation.  
WIRED REMOTE CONTROL UNIT (OPTION)  
The optional wired remote control unit (model No.: UTY-RNBLU) can be used.  
It requires the Communication Box Kit (Model Name: UTY-XCBXZ1) to connect the wired remote control.  
When you use remote control unit, there are following different points as compared with using wireless remote control unit.  
[The additional functions for wired ones]  
• Weekly timer  
Temperature set back timer  
[The restricted functions for wired ones]  
• Horizontal Airflow Direction and swing  
• MAINTENANCE  
And you can use both wired and wireless remote control unit simultaneously.  
(But function is limited.)  
[The restricted function for wireless ones]  
• SLEEP  
• TIMER  
• COIL DRY  
• MIN. HEAT  
En-2  
NAME OF PARTS  
Fig. 1  
a-1  
a-2  
a-8  
a-9  
a-1  
Fig.2  
a-3  
OPERATION  
TIMER  
a-5  
a-6  
a-7  
a-3  
a-10 a-11 a-12  
a-13  
COIL DRY  
a-4  
Fig.3  
Fig. 5  
a-8  
a-16  
a-14  
a-15  
Fig.4  
a-17  
Fig. 6  
b-1  
c-1  
c-7  
c-8  
c-2  
c-3  
c-9  
b-8  
b-2  
b-3  
b-9  
c-4  
c-5  
b-10  
b-4  
b-5  
c-10  
c-11  
b-11  
b-12  
b-6  
c-6  
b-7  
b-14  
b-16  
b-13  
b-15  
Fig. 7  
To facilitate explanation, the accompanying illustra-  
tion has been drawn to show all possible indicators;  
in actual operation, however, the display will only  
show those indicators appropriate to the current op-  
eration.  
En-3  
Fig. 1 Indoor Unit  
Fig. 6 Remote Control Unit  
a-1 Operating Control Panel (Fig. 2)  
a-2 MANUAL AUTO button  
b-1 Signal Transmitter  
b-2 MODE button  
G When kept on pressing the MANUAL  
AUTO button for more than 10 seconds,  
the forced cooling operation will start.  
G The forced cooling operation is used at  
the time of installation.  
b-3 MIN. HEAT button  
b-4 SET TEMP. button (  
b-5 COIL DRY button  
b-6 SLEEP button  
b-7 TIMER MODE button  
b-8 FAN button  
/
)
Only for authorized service personnel's  
use.  
G When the forced cooling operation  
starts by any chance, press the START/  
STOP button to stop the operation.  
b-9 START/STOP button  
b-10 ECONOMY button  
b-11 SET button  
b-12 SWING button  
b-13 TIMER SET (  
b-14 CLOCK ADJUST button  
b-15 TEST RUN button  
a-3 Indicator (Fig. 3)  
/
) button  
a-4 Remote Control Signal Receiver  
a-5 OPERATION Indicator Lamp (green)  
a-6 TIMER Indicator Lamp (orange)  
G This button is used when installing the  
air conditioner, and should not be used  
under normal conditions, as it will cause  
the indoor units thermostat function to  
operate incorrectly.  
G If the TIMER indicator lamp flashes when  
the timer is operating, it indicates that a  
fault has occurred with the timer setting  
(See Page 15 Auto Restart).  
a-7 COIL DRY Indicator Lamp (yellow)  
G If this button is pressed during normal  
operation, the indoor unit will switch to  
test operation mode, and the Indoor  
Units OPERATION Indicator Lamp and  
TIMER Indicator Lamp will begin to flash  
simultaneously.  
a-8 Intake Grille (Fig. 4)  
a-9 Front Panel  
a-10 Air Filter  
a-11 Airflow Direction Louver  
a-12 Right-Left Louver  
(behind Airflow Direction Louver)  
a-13 Drain Hose  
G To stop the test operation mode, press  
the START/STOP button to stop the air  
conditioner.  
b-16 RESET button  
c-1 Remote Control Unit Display (Fig. 7)  
c-2 Transmit Indicator  
c-3 Fan Speed Display  
c-4 SWING Display  
Fig. 5 Outdoor Unit  
a-14 Intake Port  
a-15 Outlet Port  
a-16 Pipe Unit  
c-5 Timer Mode Display  
c-6 Clock Display  
a-17 Drain port (bottom)  
c-7 Temperature SET Display  
c-8 ECONOMY Display  
c-9 Operation Mode Display  
c-10 COIL DRY Display  
c-11 SLEEP Display  
En-4  
PREPARATION  
CAUTION!  
Load Batteries (AAA/R03/LR03 × 2)  
G Take care to prevent infants from  
accidentally swallowing batteries.  
G When not using the Remote Control Unit  
for an extended period, remove the  
batteries to avoid possible leakage and  
damage to the unit.  
Press and slide the battery compartment lid on the re-  
1
verse side to open it.  
Slide in the direction of the arrow while pressing the  
mark.  
G If leaking battery fluid comes in contact  
with your skin, eyes, or mouth, immedi-  
ately wash with copious amounts of  
water, and consult your physician.  
G Dead batteries should be removed  
immediately and disposed of properly,  
either in a battery collection receptacle  
or to the appropriate authority.  
Insert batteries.  
Be sure to align the battery polarities (  
2
3
) correctly.  
Close the battery compartment lid.  
G Do not attempt to recharge dry batteries.  
Set the Current time  
Never mix new and used batteries, or  
batteries of different types.  
Batteries should last about one year  
under normal use. If the Remote Con-  
trol Units operating range becomes ap-  
preciably reduced, replace the batteries  
and press the RESET button with the tip  
of a ballpoint pen or other small object.  
Press the CLOCK ADJUST button (Fig. 6 b-14).  
1
2
Use the tip of a ball-point pen or other small object to press the button.  
Use the TIMER SET (  
/
) buttons (Fig. 6 b-13) to  
adjust the clock to the current time.  
button: Press to advance the time.  
button: Press to reverse the time.  
(Each time the buttons are pressed, the time will be advanced/reversed in  
five-minute increments; hold the buttons depressed to change the time  
quickly in ten-minute increments.)  
Press the CLOCK ADJUST button (Fig. 6 b-14) again.  
This completes the time setting and starts the clock.  
3
To Use the Remote Control Unit  
G The Remote Control Unit must be pointed at signal receiver (Fig. 3 a-4) to operate  
correctly.  
G Operating Range: About 23ft (7 meters).  
G When a signal is properly received by the indoor unit, a beeping sound will be  
heard.  
G If no beep is heard, press the Remote Control Unit button again.  
Remote Control Unit Holder  
Insert  
Slide up  
Pull out  
Press in  
Screws  
1
Mount the Holder.  
2
Set the Remote Control  
Unit.  
3
To remove the Remote  
Control Unit (when use at  
hand).  
En-5  
OPERATION  
To Select Mode Operation  
Press the START/STOP button (Fig.6 b-9).  
1
2
The indoor units OPERATION Indicator Lamp (green) (Fig. 3 a-5) will light.  
The air conditioner will start operating.  
Press the MODE button (Fig.6 b-2) to select the desired  
mode.  
Each time the button is pressed, the mode will change in the following  
order.  
s
s
s
AUTO  
COOL  
DRY  
t
t
HEAT  
FAN  
About three seconds later, the entire display will reappear.  
Example: When set to COOL.  
To Set the Thermostat  
Press the SET TEMP. button (Fig. 6 b-4).  
button: Press to raise the thermostat setting.  
button: Press to lower the thermostat setting.  
GThermostat setting range:  
AUTO .................................. 64-88 °F  
Heating ............................... 60-88 °F  
Cooling/Dry ........................ 64-88 °F  
The thermostat cannot be used to set room temperature during the FAN mode (the  
temperature will not appear on the Remote Control Units Display).  
About three seconds later, the entire display will reappear.  
Example: When set to 80°F.  
The thermostat setting should be considered a standard value, and may differ  
somewhat from the actual room temperature.  
To Set the Fan Speed  
Press the FAN button (Fig. 6 b-8).  
Each time the button is pressed, the fan speed changes in the following order:  
s
AUTO  
s
s
s
s
HIGH  
MED  
LOW  
QUIET  
About three seconds later, the entire display will reappear.  
When set to AUTO:  
Heating: Fan operates so as to optimally circulate warmed air.  
However, the fan will operate at very low speed when the temperature  
of the air issued from the indoor unit is low.  
Cooling: As the room temperature approaches that of the thermostat setting,  
the fan speed becomes slower.  
Fan  
:
The fan runs at the low fan speed.  
Example: When set to AUTO.  
The fan will operate at a very low setting during Monitor operation and at the  
start of the Heating mode.  
En-6  
OPERATION  
To Stop Operation  
Press the START/STOP button (Fig. 6 b-9).  
The OPERATION Indicator Lamp (green) (Fig. 3 a-5) will go out.  
About AUTO CHANGEOVER Operation  
AUTO:  
G When AUTO CHANGEOVER operation first selected, the fan will oper-  
ate at very low speed for about one minute, during which time the  
indoor unit detects the room conditions and selects the proper operation  
mode.  
If the difference between thermostat setting and actual room tempera-  
ture is more than +4 °F Cooling or dry operation  
If the difference between thermostat setting and actual room tempera-  
ture is within 4 °F Monitor operation  
If the difference between thermostat setting and actual room tempera-  
ture is more than –4 °F Heating operation  
G When the indoor unit has adjusted your rooms temperature to near  
the thermostat setting, it will begin monitor operation. In the monitor  
operation mode, the fan will operate at low speed. If the room tem-  
perature subsequently changes, the indoor unit will once again select  
the appropriate operation (Heating, Cooling) to adjust the temperature  
to the value set in the thermostat.  
(The monitor operation range is 4 °F relative to the thermostat set-  
ting.)  
G If the mode automatically selected by the indoor unit is not what you  
wish, select one of the mode operation (HEAT, COOL, DRY, FAN).  
About Mode Operation  
During Heating mode:  
Set the thermostat to a temperature set-  
ting that is higher than the present room  
temperature. The Heating mode will not  
operate if the thermostat is set lower than  
the actual room temperature.  
Heating: G Use to warm your room.  
G When Heating mode is selected, the indoor unit will operate at very  
low fan speed for about 3 to 5 minutes, after which it will switch to the  
selected fan setting. This period of time is provided to allow the indoor  
unit to warm up before begin full operation.  
During Cooling/Dry mode:  
G When the room temperature is very low, frost may form on the outdoor  
unit, and its performance may be reduced. In order to remove such  
frost, the air conditioner will automatically enter the defrost cycle from  
time to time. During Automatic Defrosting operation, the OPERATION  
Indicator Lamp (Fig. 3 a-5) will flash, and the heat operation will be  
interrupted.  
Set the thermostat to a temperature set-  
ting that is lower than the present room  
temperature. The Cooling and Dry modes  
will not operate if the thermostat is set  
higher than the actual room temperature  
(in Cooling mode, the fan alone will oper-  
ate).  
Cooling: G Use to cool your room.  
During Fan mode:  
You can not use the indoor unit to heat  
and cool your room.  
Dry:  
G Use for gently cooling while dehumidifying your room.  
G You cannot heat the room during Dry mode.  
G During Dry mode, the indoor unit will operate at low speed; in order to  
adjust room humidity, the indoor units fan may stop from time to time.  
Also, the fan may operate at very low speed when adjusting room  
humidity.  
G The fan speed cannot be changed manually when Dry mode has been  
selected.  
Fan:  
G Use to circulate the air throughout your room.  
En-7  
TIMER OPERATION  
Before using the timer function, be sure that the Remote Control Unit is set to the correct current time (P. 4).  
To Use the ON timer or OFF timer  
To Cancel the Timer  
Press the START/STOP button (Fig. 6 b-9)  
(if the indoor unit is already operating, proceed to step 2).  
The indoor units OPERATION Indicator Lamp (green) (Fig. 3 a-5) will light.  
1
Use the TIMER button to select “CANCEL”.  
The indoor unit will return to normal  
operation.  
To Change the Timer Settings  
Press the TIMER MODE button (Fig. 6 b-7) to select the  
OFF timer or ON timer operation.  
Each time the button is pressed the timer function changes in the follow-  
ing order:  
Perform steps 2 and 3.  
2
To Stop Air Conditioner Operation  
while the Timer is Operating  
Press the START/STOP button.  
s
s
s
ON  
CANCEL  
OFF  
To Change Operating Conditions  
If you wish to change operating conditions  
(Mode, Fan Speed, Thermostat Setting,  
SUPER QUIET mode), after making the  
timer setting and waiting until the entire  
display reappears, then press the appropri-  
ate buttons to change the operating  
condition desired.  
t
PROGRAM(OFF ON, OFF ON)  
The indoor unitsTIMER Indicator Lamp (orange) (Fig. 3 a-6) will light.  
Use the TIMER SET buttons (Fig. 6 b-13) to set the de-  
3
sired OFF time or ON time.  
Set the time while the time display is flashing (the flashing will continue  
for about five seconds).  
button: Press to advance the time.  
button: Press to reverse the time.  
About five seconds later, the entire display will reappear.  
To Use the Program timer  
Press the START/STOP button (Fig. 6 b-9)  
(if the indoor unit is already operating, proceed to step 2).  
The indoor units OPERATION Indicator Lamp (green) (Fig. 3 a-5) will light.  
To Cancel the Timer  
1
Use the TIMER MODE button to select  
“CANCEL”.  
The air conditioner will return to normal  
operation.  
Set the desired times for OFF timer and ON timer.  
To Change the Timer Settings  
2
See the section “To Use the ON timer or OFF timer” to set the desired  
1. Follow the instructions given in the section  
To Use the ONTimer or OFFTimer” to se-  
lect the timer setting you wish to change.  
mode and times.  
About three seconds later, the entire display will reappear.  
The indoor unitsTIMER Indicator Lamp (orange) (Fig. 3 a-6) will light.  
2. Press the TIMER MODE button to select  
either OFF  
ON or OFF  
ON.  
Press the TIMER MODE button (Fig. 6 b-7) to select the  
To Stop Air Conditioner Operation  
while the Timer is Operating  
3
PROGRAM timer operation (OFF  
will display).  
ON or OFF  
ON  
Press the START/STOP button.  
The display will alternately show “OFF timer” and “ON timer”, then change  
to show the time setting for the operation to occur first.  
To Change Operating Conditions  
If you wish to change operating conditions  
(Mode, Fan Speed, Thermostat Setting,  
SUPER QUIET mode), after making the timer  
setting and waiting until the entire display  
reappears, then press the appropriate  
buttons to change the operating condition  
desired.  
G The program timer will begin operation. (If the ON timer has been se-  
lected to operate first, the indoor unit will stop operating at this point.)  
About five seconds later, the entire display will reappear.  
About the Program timer  
G The program timer allows you to integrate OFF timer and ON timer operations in  
a single sequence. The sequence can involve one transition from OFF timer to  
ON timer, or from ON timer to OFF timer, within a twenty-four hour period.  
G The first timer function to operate will be the one set nearest to the current time.  
The order of operation is indicated by the arrow in the Remote Control Units  
Display (OFF ON, or OFF ON).  
G One example of Program timer use might be to have the air conditioner auto-  
matically stop (OFF timer) the operation after you go to sleep, then start (ON  
timer) the operation automatically in the morning before you arise.  
En-8  
SLEEP TIMER OPERATION  
Unlike other timer functions, the SLEEP timer is used to set the length of time until air conditioner operation is stopped.  
To Use the SLEEP Timer  
To Cancel the Timer:  
While the air conditioner is operating or stopped, press the  
SLEEP button (Fig. 6 b-6).  
The indoor units OPERATION Indicator Lamp (green) (Fig. 3 a-5) lights and theTIMER  
Use the TIMER MODE button to select  
“CANCEL”.  
The air conditioner will return to normal  
operation.  
Indicator Lamp (orange) (Fig. 3 a-6) light.  
To Stop the Air Conditioner During  
Timer Operation:  
To Change the Timer Settings  
Press the START/STOP button.  
Press the SLEEP button (Fig. 6 b-6) once again and set the  
time using the TIMER SET (  
/
) buttons (Fig. 6 b-13).  
Set the time while the Timer Mode Display is flashing (the flashing will continue  
about five seconds).  
button: Press to advance the time.  
button: Press to reverse the time.  
About five seconds later, the entire display will reappear.  
About the SLEEP Timer  
To prevent excessive warming or cooling during sleep, the SLEEP timer function automatically modifies the thermostat setting  
in accordance with the set time setting. When the set time has elapsed, the air conditioner completely stops.  
During Heating operation:  
During Cooling/Dry operation:  
When the SLEEP timer is set, the thermostat setting is  
automatically lowered 2 °F every thirty minutes. When the  
thermostat setting is lowered a total of 8 °F, the thermostat  
setting at that time is maintained until the set time elapses, at  
which time the air conditioner automatically turns off.  
When the SLEEP timer is set, the thermostat setting is auto-  
matically raised 2 °F every sixty minutes. When the thermo-  
stat setting is raised a total of 4 °F, the thermostat setting at  
that time is maintained until the set time elapses, at which  
time the air conditioner automatically turns off.  
SLEEP timer setting  
SLEEP timer setting  
2 °F  
4 °F  
6 °F  
8 °F  
Set time  
30  
minutes  
1 hour  
1 hour  
4 °F  
2 °F  
1 hour  
30 minutes  
Set time  
En-9  
ADJUSTING THE DIRECTION OF AIR CIRCULATION  
Vertical (up-down) direction of airflow is adjusted by pressing the Remote Control Units SET button. Horizontal (right-left)  
airflow direction is adjusted manually, by moving the Air Flow Direction Louvers.  
Whenever making horizontal airflow adjustments, start air conditioner operation and be sure that the vertical air direction  
louvers are stopped.  
R
Vertical Air Direction Adjustment  
DANGER!  
G Never place fingers or foreign objects in-  
side the outlet ports, since the internal fan  
operates at high speed, and personal injury  
could be caused.  
Press the SET button (Fig. 6 b-11).  
Each time the button is pressed, the air direction range will change as follows:  
1
2
3
4
5
6
G Always use the Remote Control Units  
SET button to adjust the vertical airflow  
louvers. Attempting to move them  
manually could result in improper op-  
eration; in this case, stop operation and  
restart. The louvers should begin to  
operate properly again.  
Types of Air flow Direction Setting:  
For better heating/cooling effect, it is recommended to set the air direction in the  
following range.  
1, 2, 3 :  
4, 5, 6 :  
During Cooling/Dry modes  
During Heating mode  
G During use of the Cooling and Dry  
modes, do not set the Airflow Direc-  
tion Louvers in the Heating range  
(4 - 6) for many hours, since water  
vapor may condense near the outlet  
louvers and drops of water may drip  
from the indoor unit. During the Cool-  
ing and Dry modes, if the Airflow Di-  
rection Louvers are left in the heating  
range for more than 30 minutes, they  
will automatically return to position 3.  
The Remote Control Units display does  
not change.  
1
2
3
4
5
6
G Use the air direction adjustments within the ranges shown above.  
G The vertical airflow direction is set automatically as shown, in accordance with  
the type of operation selected.  
G When used in a room with infants, chil-  
dren, elderly or sick persons, the airflow  
direction and room temperature should  
be considered carefully when making  
settings.  
During Cooling/Dry mode : Horizontal flow 1  
During Heating mode  
: Downward flow 6  
G During AUTO/HEAT mode operation, for the first one minute after beginning op-  
eration, airflow will be horizontal 1; the air direction cannot be adjusted during  
this period.  
The air flow direction setting will temporarily become 1 when the temperature of  
the air flow is low at the start of the Heating mode.  
R
DANGER!  
G When adjusting the Right-Left Louvers, it  
is necessary to stop the Air-Conditioner  
first and make sure that it stops completely  
before adjusting the direction.  
Right-Left Adjustment  
Adjust the Right-Left louvers.  
G Move the Right-Left louvers to adjust air flow in the direction you prefer.  
Right-Left Louvers  
knob  
knob(two places)  
En-10  
MINIMUM HEAT OPERATION  
The room temperature can be maintained at 50 °F by pressing the MIN. HEAT button  
(Fig.6 b-3) so as to prevent the room temperature from falling too far.  
While MINIMUM HEAT OPERATION  
is in progress, the following opera-  
tions/features cannot be used  
TIMER  
To use MINIMUM HEAT OPERATION  
Press the MIN. HEAT button (Fig.6 b-3)  
SLEEP  
FAN speed  
Swing  
To stop MINIMUM HEAT OPERATION  
Press the START/STOP button (Fig.6 b-9)  
Then the operation stops.  
About the MINIMUM HEAT OPERATION  
The Heating mode will not operate if the room temperature is high enough.  
ECONOMY OPERATION  
Begin Air Conditioner operation before performing this procedure.  
To Use the ECONOMY Operation  
Press the ECONOMY button (Fig.6 b-10).  
ECOappears on the Remote Control Unit display.  
Economy operation begins.  
To Stop the ECONOMY Operation  
Press the ECONOMY button (Fig.6 b-10) again.  
ECOdisappears from the Remote Control Unit display.  
Normal operation begins.  
About ECONOMY Operation  
At the maximum output, ECONOMY Operation is approximately 70% of normal air conditioner operation for cooling and  
heating.  
When ECONOMY operation is performed during the cooling mode, dehumidification is improved. This function is especially  
convenient when you want to remove the humidity in the room without significantly lowering the room temperature.  
During ECONOMY operation, the thermostat setting automatically changes according to the temperature to avoid Unneces  
sary cooling and heating for the most economical operation.  
G If the room is not cooled (or heated) well during economy operation, select normal operation.  
G Once air conditioner operation is stopped, normal operation begins when the indoor unit is turned on again.  
G During the monitor period in the AUTO mode, the air conditioner operation will not change to ECONOMY operation even if  
ECONOMY operation is selected by pressing the ECONOMY operation button.  
En-11  
SWING OPERATION  
Begin air conditioner operation before performing this procedure.  
To select SWING Operation  
Press the SWING button (Fig. 6 b-12).  
The SWING Display (Fig. 7 c-4) will light.  
In this mode, the Air Flow Direction Louvers will swing automatically to direct the  
air flow both up and down.  
To stop SWING Operation  
Press the SWING button (Fig. 6 b-12) once again.  
The SWING Display (Fig. 7 c-4) will go out.  
Airflow direction will return to the setting before swing was begun.  
About Swing Operation  
During cooling/Dry mode : Swings between 1 and 4.  
During heating mode  
: Swings between 4 and 6.  
G The SWING operation may stop temporarily when the air conditioners fan is not  
operating, or when operating at very low speeds.  
COIL DRY OPERATION  
The Indoor unit can be dried by pressing the COIL DRY button on the Remote Control Unit so as to avoid going moldy and  
restrain the breed of bacterium.  
The COIL DRY operation will operate for 90 minutes after pressing the COIL DRY button and it will stop automatically.  
To select COIL DRY Operation  
Press the COIL DRY button (Fig. 6 b-5) during operation or when  
it stops.  
The COIL DRY Display (Fig. 7 c-10) will light.Then, it will disappear after 10 seconds.  
To cancel COIL DRY Operation  
Press the START/STOP button (Fig. 6 b-9) during COIL DRY  
Operation.  
The indoor unit COIL DRY Indicator Lamp (yellow) (Fig.1 a-7) will go out.Then, the  
operation stops.  
About COIL DRY Operation  
G Press the COIL DRY button again during COIL DRY Operation, COIL DRY Opera-  
tion can be reset.  
G The COIL DRY Operation cannot get rid of the existed mold or bacterium, and it  
has no sterilization effect either.  
MANUAL AUTO OPERATION  
Use the MANUAL AUTO operation in the event the Remote Control Unit is lost or otherwise unavailable.  
How To Use the Main Unit Controls  
G When the air conditioner is operated  
by the controls on the Main Unit, it will  
operate under the same mode as the  
AUTO mode selected on the Remote  
Control Unit (see page 6).  
Press the MANUAL AUTO button (Fig. 2 a-2) for three sec-  
onds on the main unit control panel.  
To stop operation, press the MANUAL AUTO button (Fig. 2 a-2) for three seconds.  
G The fan speed selected will be AUTO”  
and the thermostat setting will be  
standard (76 °F).  
En-12  
CLEANING AND CARE  
G Before cleaning the indoor unit, be sure to turn it off and disconnect the Power Supply Cord.  
CAUTION!  
G Be sure the Intake Grille (Fig. 1 a-8) is installed securely.  
G When removing or replacing the air filters, be sure not to touch the heat exchanger, as personal  
injury may result.  
Cleaning the Intake Grille  
1. Remove the Intake Grille.  
Cleaning the Air Filter  
1. Open the Intake Grille, and remove the air  
1 Place your fingers at both lower ends of the grille  
panel, and lift forward; if the grille seems to catch  
partway through its movement, continue lifting up-  
ward to remove.  
filter.  
Lift up the air filters handle, disconnect the two lower  
tabs, and pull out.  
Air filter (Right & Left)  
2 Pull past the intermediate catch and open the Intake  
Grille wide so that it become horizontal.  
Intake Grille  
Air filter handle  
Hooks(two places)  
2. Remove dust with a vacuum cleaner or by  
washing.  
After washing, allow to dry thoroughly in a shaded place.  
Mounting  
shaft  
3. Replace the Air Filter and close the Intake  
Grille.  
Knob  
1 Align the sides of the air filter with the panel, and push  
in fully, making sure the two lower tabs are returned  
properly to their holes in the panel.  
2. Clean with water.  
Remove dust with a vacuum cleaner; wipe the indoor  
unit with warm water, then dry with a clean, soft cloth.  
3. Replace the Intake Grille.  
Hooks(two places)  
2 Close the Intake Grille.  
1 Pull the knobs all the way.  
(For purposes of example, the illustration shows the indoor  
unit without Intake Grille installed.)  
2 Hold the grille horizontal and set the left and right  
mounting shafts into the bearings at the top of the  
panel.  
3 Press the place where the arrow on the diagram indi-  
cates and close the Intake Grille.  
G Dust can be cleaned from the air filter either with a vacuum  
cleaner, or by washing the filter in a solution of neutral  
detergent and warm water. If you wash the filter, be sure  
to allow it to dry thoroughly in a shady place before rein-  
stalling.  
G If dust is allowed to accumulate on the air filter, airflow  
will be reduced, lowering operating efficiency and increas-  
ing noise.  
2
2
G During periods of normal use, the Air Filters should be  
cleaned every two weeks.  
Mounting  
shaft  
G Don't operate the air conditioner with being opened the  
intake grille.  
1
3
1 3  
Bearing  
Knob  
G When used for extended periods, the indoor unit may accumulate dust inside, reducing its performance.We recommend  
that the indoor unit be inspected regularly, in addition to your own cleaning and care. For more information, consult  
authorized service personnel.  
G When cleaning the indoor units body, do not use water hotter than 104 °F, harsh abrasive cleansers, or volatile agents  
like benzene or thinner.  
G Do not expose the indoor units body to liquid insecticides or hairsprays.  
G When shutting down the indoor unit for one month or more, first allow the fan mode to operate continuously for about  
one-half day to allow internal parts to dry thoroughly.  
En-13  
TROUBLESHOOTING  
In the event of a malfunction (burning smell, etc.), immediately stop operation, turn off breaker,  
and consult authorized service personnel.  
WARNING!  
Merely turning off the indoor units power switch will not completely disconnect the unit from  
the power source. Always be sure to disconnect the Power Supply Plug or turn off your circuit  
breaker to ensure that power is completely off.  
Before requesting service, perform the following checks:  
Symptom  
See Page  
Problem  
NORMAL  
FUNCTION  
Doesnt operate immedi-  
ately:  
G If the indoor unit is stopped and then immediately started again,  
the compressor will not operate for about 3 minutes, in order to  
prevent fuse blowouts.  
G
Whenever the Power Supply Plug is disconnected and then recon-  
nected to a power outlet, the protection circuit will operate for about  
3 minutes, preventing unit operation during that period.  
Noise is heard:  
G During operation or immediately after stopping the unit, the sound  
of water flowing in the air conditioners piping may be heard.  
Also, noise may be particularly noticeable for about 2 to 3 min-  
utes after starting operation (sound of refrigerant flowing).  
G During operation, a slight squeaking sound may be heard. This is  
the result of minute expansion and contraction of the front panel  
due to temperature changes.  
G
During Heating operation, a sizzling sound may be heard occasional.  
This sound is produced by the Automatic Defrosting operation.  
15  
Smells:  
G Some smell may be emitted from the indoor unit. This smell is  
the result of room smells (furniture, tobacco, etc.) which have  
been taken into the indoor unit.  
Mist or steam is  
emitted:  
G During Cooling or Dry operation, a thin mist may be seen emitted  
from the indoor unit. This results from the sudden cooling of room  
air by the cool air emitted from the indoor unit, resulting in con-  
densation and misting.  
G During Heating operation, the outdoor units fan may stop, and  
steam may be seen rising from the unit. This is due to Automatic  
Defrosting operation.  
15  
Airflow is weak or stops:  
G When Heating operation is started, fan speed is temporarily very  
low, to allow internal parts to warm up.  
G During Heating operation, if the room temperature rises above  
the thermostat setting, the outdoor unit will stop, and the indoor  
unit will operate at very low fan speed. If you wish to warm the  
room further, set the thermostat for a higher setting.  
G During Heating operation, the indoor unit will temporarily stop  
operation (between 7 and 15 minutes) as the Automatic Defrost-  
ing mode operates. During Automatic Defrosting operation, the  
OPERATION Indicator Lamp will flash.  
15  
G The fan may operate at very low speed during Dry operation or  
when the unit is monitoring the rooms temperature.  
6
6
6
G During SUPER QUIET operation, the fan will operate at very low  
speed.  
G In the monitor of AUTO operation, the fan will operate at very  
low speed.  
Water is produced from  
the outdoor unit:  
G During Heating operation, water may be produced from the out-  
door unit due to Automatic Defrosting operation.  
15  
En-14  
TROUBLESHOOTING  
Items to check  
Symptom  
See Page  
G Is the Power Supply Plug disconnected its outlet?  
G Has there been a power failure?  
CHECK ONCE Doesnt operate at all:  
MORE  
G Has a fuse blown out, or a circuit breaker been tripped?  
G Is the timer operating?  
8 - 9  
G Is the Air Filter dirty?  
G Air the air conditioners intake grille or outlet port blocked?  
Poor Cooling performance:  
G Did you adjust the room temperature settings (thermostat) cor-  
rectly?  
G Is there a window or door open?  
G In the case of Cooling operation, is a window allowing bright sun-  
light to enter? (Close the curtains.)  
G In the case of Cooling operation, are there heating apparatus and  
computers inside the room, or are there too many people in the  
room?  
G Is the unit set for SUPER QUIET operation?  
6
5
The unit operates  
differently from the Remote  
Control Units setting:  
G Are the Remote Control Units batteries dead?  
G Are the Remote Control Units batteries loaded properly?  
If the problem persists after performing these checks, or if you notice burning smells, or the OPERATION Indicator Lamp  
(Fig. 3 a-5) and the TIMER Indicator Lamp (Fig. 3 a-6) flashes, immediately stop operation, disconnect the Power Supply  
Plug, and consult authorized service personnel.  
OPERATING TIPS  
Operation and Performance  
Microcomputer-controlled Automatic Defrosting  
Heating Performance  
G When using the Heating mode under conditions of low  
outdoor temperature and high humidity, frost may form  
on the outdoor unit, resulting in reduced operating per-  
formance.  
In order to prevent this kind of reduced performance, this  
air conditioner is equipped with a Microcomputer-  
controlled Automatic Defrosting function. If frost forms,  
the air conditioner will temporarily stop, and the  
defrosting circuit will operate briefly (for about 7-15 min-  
utes).  
G This air conditioner operates on the heat-pump princi-  
ple, absorbing heat from outdoor air and transferring that  
heat to indoor unit. As a result, the operating perform-  
ance is reduced as outdoor air temperature drops. If you  
feel that insufficient heating performance is being  
produced, we recommend you use this air conditioner in  
conjunction with another kind of heating appliance.  
G Heat-pump air conditioners heat your entire room by  
recirculating air throughout the room, with the result that  
some time may be required after first starting the air con-  
ditioner until the room is heated.  
During Automatic Defrosting operation, the OPERATION  
Indicator Lamp (green) will flash.  
AUTO Restart  
In Event of Power Interruption  
G
If a power interruption occurs during TIMER operation, the  
timer will be reset and the indoor unit will begin (or stop)  
operation at the new time setting. In the event that this kind  
of timer fault occurs, the TIMER Indicator Lamp will flash  
(see Page. 4).  
G The power supply to the air conditioner is stopped by a  
power interruption. The air conditioner will then restart  
automatically in its previous mode when the power is  
restored.  
G Use of other electrical appliances (electric shaver, etc.) or  
nearby use of a wireless radio transmitter may cause the  
air conditioner to malfunction. In this event, temporarily  
disconnect the Power Supply Plug, reconnect it, and then  
use the Remote Control Unit to resume operation.  
En-15  
OPERATING TIPS  
Temperature and Humidity Range  
Cooling Mode  
Dry Mode  
Heating Mode  
About 5 to 75 °F  
About 86 °F or less  
Outdoor temperature  
Indoor temperature  
About 14 to 115 °F  
About 64 to 90 °F  
About 14 to 115 °F  
About 64 to 90 °F  
G If the air conditioner is used under higher temperature conditions than those listed, the built-in protection circuit may  
operate to prevent internal circuit damage. Also, during Cooling and Dry modes, if the air conditioner is used under conditions  
of lower temperature than those listed above, the heat-exchanger may freeze, leading to water leakage and other damage.  
G Do not use this air conditioner for any purposes other than the Cooling, Heating, Dehumidifying, and air-circulation of  
rooms in ordinary dwellings.  
G If the air conditioner is used for many hours under high-humidity conditions about 80% or more, condensation may form on  
the surface of the indoor unit, and drip onto the floor or other objects underneath. (About 80% or more)  
SPECIFICATION  
TYPE  
HEAT & COOL MODEL  
MODEL INDOOR UNIT  
OUTDOOR UNIT  
MW09Y3H  
MR09Y3H  
MW12Y3H  
MR12Y3H  
POWER SUPPLY  
COOLING  
208/230 V 60 Hz  
208/230 V 60 Hz  
8500 BTU/h  
0.68 kW  
3.3 A  
11500 BTU/h  
0.92 kW  
4.3 A  
CAPACITY  
INPUT POWER  
CURRENT  
HEATING  
CAPACITY  
10000 BTU/h  
0.76 kW  
3.6 A  
14000 BTU/h  
1.12 kW  
INPUT POWER  
CURRENT  
5.2 A  
En-16  
Friedrich Air Conditioning Co.  
4200 N. Pan Am  
San Antonio, Texas 78218 USA  
Tel. (210) 357-4400 Fax (210) 357-4490  

Briggs Stratton 589447 User Manual
Briggs Stratton Automobile Parts 246400 User Manual
Brother MFC 8220 User Manual
Brother MFC 295CN User Manual
Cornelius A8530 User Manual
Epson All in One Printer C11CB92201 User Manual
Friedrich WS13B30B C User Manual
Garmin STYLUS CX5800F User Manual
Havis Shields Interior Dome Light User Manual
Hisense Group KFR 25GWE User Manual