Residential & Light Commercial HVAC
Split System Air Conditioner
11⁄
208/230 Volt, 1-Phase, 60 Hz
2
thru 5 Tons
Performance:
Efficiency rating of 13 SEER and 14 SEER
Cooling capacities from 11⁄
to 5 tons
2
Refrigerant Circuit:
Factory installed liquid line filter drier
Long life copper tubes, aluminum fins
State-of-the-art compressors
Large, wrap-around coil surface
Quality Built:
Galvanized steel exterior cabinet with
1,000-hour salt spray, powder-coated finish
Powder-coated fan guard
Full louvered panel to protect coil
Formed base with 21⁄2" ground clearance
Limited 5-year warranty on parts
Easy To Install:
Factory-charged with R-22 refrigerant
Only three screws to access electrical controls
Easy access to service valves
Rated in Accordance with ARI Standard 210.
Certification Applies Only When Used with
Proper Components as Listed with ARI.
Additional rating information can be found
Model
Number
Size
(tons)
Nominal
BTUH
Min. Circuit
Ampacity
Max. Fuse or
Breaker
Operating Dimensions
H x W x D (inches)
Min. Mounting Ship / Operating
Pad Size (inches)
Weight (lbs)
144 / 138
142 / 136
169 / 163
189 / 180
213 / 204
217 / 208
230 / 220
1
1
1
1
C18ABD1VF
C24ABD1VF
C30ABD1VF
C36ACD1VF
C42ACD1VF
C48ACD1VF
C60ACD1VF
1 ⁄2
18,000
24,000
30,000
36,000
42,000
48,000
60,000
9.1
15
15
20
30
35
40
50
26 ⁄2 X 21 ⁄2 X 21 ⁄2
24 x 24
1
1
1
2
11.5
14.3
18.7
20.3
23.1
30.1
26 ⁄2 X 21 ⁄2 X 21 ⁄2
24 x 24
1
1
1
1
2 ⁄2
32 ⁄2 X 21 ⁄2 X 21 ⁄2
24 x 24
1
1
1
3
32 ⁄2 X 29 ⁄2 X 29 ⁄2
32 x 32
1
1
1
1
3 ⁄2
32 ⁄2 X 29 ⁄2 X 29 ⁄2
32 x 32
1
1
1
4
5
32 ⁄2 X 29 ⁄2 X 29 ⁄2
32 x 32
1
1
39 X 29 ⁄2 X 29 ⁄2
32 x 32
Product Specifications
ARI CERTIFIED COMBINATION PERFORMANCE RATINGS
Cooling Capacity (BTUH)
Factory
Supplied
Enhancement
UNIT
SIZE
Outdoor Unit
Indoor Unit
SEER1
EER
Total
Sensible
AC1A024A
AFPB24A1
TXV
17,500
17,500
18,000
21,600
21,600
21,600
21,600
26,600
26,600
26,600
28,000
28,000
34,000
34,000
35,000
35,000
40,000
40,000
41,500
44,000
44,000
53,000
53,000
12,750
12,750
13,500
15,750
15,750
17,000
17,000
19,500
19,500
19,500
21,000
21,000
24,750
24,750
25,500
25,500
29,250
29,250
31,000
32,250
32,250
38,750
38,750
13
13
14
13
13
14
14
13
13
13
14
14
13
13
14
14
13
13
14
13
13
13
13
11.3
11.3
12.0
11.3
11.3
12.2
12.2
11.4
11.4
11.4
12.0
12.0
11.4
11.4
11.8
11.8
11.5
11.5
12.0
11.5
11.5
11.5
11.5
18
24
C18ABD1VF
TXV/TDR
TXV/TDR
TXV
AC1A036 + FV80A070-4
AC1A024A
AFPB24A1
TXV/TDR
TXV/TDR
TXV/TDR
TXV
C24ABD1VF
C30ABD1VF
AC1A042A + FV80A070-4
AC1A042A + FV80A085-4
AC1A030A
AC1A036A
TXV
30
AFPB36A1
TXV/TDR
TXV/TDR
TXV/TDR
TXV
AC1A060A + FV80A085-4
AC1A060A + FV80A115-5
AC1A036A
AFPB36A1
TXV/TDR
TXV/TDR
TXV/TDR
TXV
36
42
C36ACD1VF
C42ACD1VF
AC1A060A + FV80A085-4
AC1A060A + FV80A115-4
AC1A042A
AFPC48A1
TXV/TDR
TXV/TDR
TXV
AC1A060A + FV80A115-5
AC1A060A
48
60
C48ACD1VF
C60ACD1VF
AFPC48A1
TXV/TDR
TXV
AC1A060A
AFPC60A1
TXV/TDR
1. TDR required to obtain SEER rating
Notes:
a. Fedders coils include factory installed TXV. Fedders gas furnaces and air handlers
contain the TDR as standard equipment.
b. TDR kit available as accessory. Part Number TDR001A.
c. Tested outdoor and indoor combinations have been tested in accordance with
DOE test procedures for central air conditioners.
d. Above ratings based on 80ºF (27ºC) DB and 67ºF (19ºC) WB indoor entering
air temperature and 95ºF (35ºC) DB air entering outdoor unit.
EER
-
-
-
-
Energy Efficiency Ratio
Seasonal Energy Efficiency Ratio
Time-Delay Relay
SEER
TDR
TXV
Thermostatic Expansion Valve
3
Specifications subject to change without notice.
Product Specifications
LINE SET LENGTH AND SIZE
SUCTION LINE SIZES
LIQUID LINE SIZES
25 ft. 50 ft.
3/8" 3/8"
BTUH
15 ft.
3/4"
3/4"
7/8"
7/8"
7/8"
7/8"
1 1/8"
25 ft.
3/4"
3/4"
7/8"
7/8"
7/8"
7/8"
1 1/8"
50 ft.
3/4"
3/4"
7/8"
7/8"
7/8"
7/8"
1 1/8"
75 ft.
3/4"
15 ft.
3/8"
3/8"
3/8"
3/8"
3/8"
3/8"
1/2"
75 ft.
3/8"
3/8"
3/8"
3/8"
3/8"
3/8"
1/2"
18
24
30
36
42
48
60
3/4"
3/8"
3/8"
3/8"
3/8"
3/8"
1/2"
3/8"
3/8"
3/8"
3/8"
3/8"
1/2"
7/8"
7/8"
1 1/8"
1 1/8"
1 1/8"
Recommended liquid and suction tube line size is for standard installations. The unit charge is correct for the outdoor unit, matched indoor coil and
15 feet of refrigerant tubing. For tubing length other than 15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied
by the per foot value. These recommendations do not apply to Long Line Length Installations that exceed 75 feet or where there is more than 40 feet
vertical separation between indoor and outdoor units. (Lengths in excess of 75 feet or more than 40 feet vertical separation are not recommended.)
Note: See unit installation instructions for proper installation.
EXTENDED COOLING CAPACITIES
RATINGS AT
CONDENSER ENTERING AIR TEMPERATURE DEGREES (F)
OUTDOOR
UNIT MODEL
STANDARD CONDITIONS
INDOOR UNIT
BTUH SEER*
CFM
80
85
90
95
100
105
110
115
TOTAL
SENSIBLE 13,900 13,550 13,150 12,750 12,250 11,800 11,300 10,850
TOTAL 19,700 19,100 18,600 18,000 17,400 16,900 16,300 15,800
SENSIBLE 14,300 14,000 13,800 13,500 13,200 12,900 12,500 12,100
TOTAL 23,700 22,900 22,150 21,600 20,700 19,950 19,150 18,400
SENSIBLE 17,300 16,750 16,200 15,750 15,100 14,550 14,000 13,500
TOTAL 24,000 23,200 22,400 21,600 20,600 19,800 19,000 18,200
SENSIBLE 17,900 17,600 17,300 17,000 16,600 16,300 16,000 15,700
TOTAL 29,150 28,300 27,500 26,600 25,650 24,750 23,850 23,000
SENSIBLE 21,300 20,750 20,100 19,500 18,750 18,100 17,500 16,800
TOTAL 31,000 30,000 29,000 28,000 27,000 26,000 25,000 24,200
SENSIBLE 22,200 21,800 21,400 21,000 20,600 20,200 19,800 19,400
TOTAL 37,000 36,200 35,150 34,000 32.900 31,800 30,700 29,650
SENSIBLE 27,000 26,450 25,650 24,750 24,000 23,250 22,500 21,650
TOTAL 39,000 37,600 36,400 35,000 34,000 33,000 31,800 30,600
SENSIBLE 27,200 26,600 26,200 25,500 25,000 24,600 24,200 23,600
TOTAL 43,450 42,300 41,150 40,000 38,800 37,650 36,550 35,500
SENSIBLE 31,750 30,850 30,100 29,250 28,350 27,500 26,700 25,950
TOTAL 47,650 46,400 45,250 44,000 42,700 41,550 40,330 39,200
SENSIBLE 34,750 33,850 33,100 32,250 31,200 30,500 29,400 28,650
TOTAL 56,600 55,400 54,150 53,000 51,800 50,600 49,500 48,600
19,100 18,550 18,025 17,500 16,800 16,150 15,550 14,850
AC1A024A
17,500
18,000
21,600
21,600
26,600
28,000
34,000
35,000
40,000
44,000
53,000
13
14
13
14
13
14
13
14
13
13
13
650
C18ABD1VF
C24ABD1VF
C30ABD1VF
C36ACD1VF
AC1A036A + FV80A070-4
AC1A024A
640
810
AC1A042A + FV80A070-4 /
AC1A042A + FV80A085-4
810
AC1A030A
1,000
1,000
1,150
1,150
1,350
1,550
1,750
AC1A060A + FV80A085-4 /
AC1A060A + FV80A115-5
AC1A036A
AC1A060A + FV80A085-4 /
AC1A060A + FV80A115-5
C42ACD1VF
C48ACD1VF
C60ACD1VF
AC1A042A
AC1A048A
AC1A060A
SENSIBLE 41,250 40,500 39,550 38,750 37,850 36,950 36,150 35,500
*TDR required to obtain SEER rating.
4
Specifications subject to change without notice.
Product Specifications
5
Specifications subject to change without notice.
Product Specifications
Residential & Light Commercial
AC Condensing Units
Model Number Identification
C 24 A B D 1 V F * A
Product Type
C = Air Conditioner
CH = Heat Pump
Brand
Fitting Type
V = Sweat
Nominal Capacity
18 = 18,000 BTUH [5.28 kW]
24 = 24,000 BTUH [7.03 kW]
30 = 30,000 BTUH [8.79 kW]
36 = 36,000 BTUH [10.55 kW]
42 = 42,000 BTUH [12.31 kW]
48 = 48,000 BTUH [14.07 kW]
60 = 60,000 BTUH [17.58 kW]
Electrical Designation
1 = 208 / 230 Volts, 1 Phase, 60 Hz
2 = 220 Volts, 1 Phase, 50 Hz
3 = 208 / 230 Volts, 3 Phase, 60 Hz
4 = 460 Volts, 3 Phase, 60 Hz
5 = 230 Volts, 3 Phase, 50 Hz
6 = 380 Volts, 3 Phase, 50 Hz
Series
Chassis Size
Refrigerant Variations
D = R-22 Refrigerant
B = 211⁄2" W x 211⁄2" D x H - Determined by BTU Size
C = 291⁄2" W x 291⁄2" D x H - Determined by BTU Size
Fedders Corporation
505 Martinsville Rd.
Liberty Corner, NJ 07938
(908) 604-8686
All product specifications reflect available information at the printing of this brochure.
Fedders reserves the right to revise or modify products and/or specifications without notice.
©2007 Fedders North America, Inc. Fedders is a registered trademark of Fedders North America, Inc.
FD-071 0507
Form No. F-C13
|