Emerson Precision Cooling For Business Critical Continuity Figure i User Manual

Precision Cooling  
For Business-Critical Continuity™  
Liebert Prop Fan Condensing Unit™  
Installation, Operation and Maintenance Manual - 50 & 60Hz  
TABLE OF CONTENTS  
5.0  
i
FIGURES  
Figure i  
TABLES  
ii  
Product Description  
1.0 PRODUCT DESCRIPTION  
1.1 Prop Fan Condensing Units  
Liebert propeller fan condensing units are available in a range of sizes and configurations to offer  
flexibility in designing a precision environmental control system. The appropriate propeller fan con-  
densing unit paired with a corresponding Liebert fan coil evaporator model such as Liebert Data-  
Mate, Liebert Mini-Mate2 or Liebert Challenger 3000 is an effective solution for your environmental  
control application requirements.  
Split system condensing units are connected to the evaporator unit by two refrigerant lines (four in  
8-ton systems) and a low-voltage control cable. The condensing unit requires a separate power source  
and power disconnect switch.  
1.1.1 Base System 95°F (35°C) Ambient Models  
The heart of the refrigeration system is a quiet, high efficiency scroll compressor with internal vibra-  
tion isolation mountings, pressure safety controls and built-in overload protection. Standard features  
include crankcase heater, high pressure switch, condenser coil, sight glass, filter drier, hot gas bypass  
system with liquid quenching valve, direct drive propeller fan and motor, and Liebert Lee-Temp flood-  
back head pressure control. These models are designed to provide catalog capacity of the appropriate  
evaporator section up to 95°F (35°C) outside ambient temperature.  
1.1.2 105°F (41°C) Ambient Models  
These models contain similar components to the base models except the coils and fans are sized to  
provide catalog capacity of the appropriate evaporator section up to 105°F (41°C) outside ambient  
temperature.  
1.1.3 Quiet-Line Models  
These models contain similar components to the base models except the coils and fans are sized to  
provide catalog capacity of the appropriate evaporator section up to 95°F (35°C) outside ambient tem-  
perature with a noise level of less than 58 dBA.  
1.2  
Optional Equipment  
1.2.1 Coated Coil  
This option provides a phenolic coating for the condenser coil (extended lead time is required for this  
option; consult factory).  
1.2.2 Pre-Charged Refrigeration Line Sets  
For efficient condenser/evaporator connection, factory pre-charged line sets with quick connect fit-  
tings are available in 15-ft. and 30-ft. (4.5m and 9m) lengths. Each set includes an insulated copper  
suction line and copper liquid line, both charged with R-407C refrigerant and sealed. Line sets are  
only available for 1 to 3.5 Ton Units.  
1.2.3 Refrigerant Line Sweat Adapter Kit  
This kit includes the compatible fittings required (two for the insulated suction line and two for the liq-  
uid line) when using field-supplied interconnecting refrigerant lines instead of the pre-charged line sets.  
1.2.4 277V Step-Down Transformer  
A 37.5A, 277V step-down transformer is available for 1-to 3-Ton 60Hz condensing units needing  
277/1/60 input power. Apply this transformer to a 208/230/1/60 condensing unit. The transformer is  
coated with epoxy and contained in an enclosed, non-ventilated electrical box with adaptable mount-  
ing brackets.  
1
                   
Installation  
2.0 INSTALLATION  
Read this entire installation section before starting installation. This section details dimensional,  
electrical and piping information and specifications that affect the placement of the PFH unit in rela-  
tion the connected evaporator unit, other outside units, barriers and walls.  
Be particularly mindful of service and airflow clearances and maximum equirvalent piping distances  
and in elevation differences between PFH and connected evaporator unit. Consult and confirm appli-  
cations with your Emerson Network Power representative when applications exceed any of these  
specifications.  
2.1  
2.2  
Equipment Inspection  
When the unit arrives, inspect all items for any visible or concealed damage. Report any damage to  
the carrier immediately and file a damage claim; send a copy of the claim to Emerson Network Power  
or your local Emerson sales representative.  
If possible, maintain equipment and packaging until it is at the installation location.  
Location Considerations  
To ensure an adequate air supply, locate all condensing units in a clean-air area, away from loose dirt  
and debris that can clog the coil. Avoid ground-level sites with public access or areas that are exposed  
to heavy snow accumulation. Locate unit to allow maximum security and maintenance accessibility.  
Do not locate condensing units near steam, hot air or fume exhausts. Do locate units at least 18 in.  
(457mm) from walls, obstructions or adjacent units. For multiple unit installations, space unit so that  
the hot condenser exhaust air is not directed toward the condenser air inlet of an adjacent unit.  
Install a solid base at least 2 in. (51mm) higher than the surrounding grade and 2 in. (51mm) larger  
than condensing unit base dimensions and capable of supporting the condenser’s weight.  
2
     
Installation  
2.3  
Dimensional Data  
Figure 1  
Dimensions, horizontal air discharge  
Removable (right) panel  
for access to  
refrigeration component  
Fan Rotation  
CCW  
(left side)  
A
Right Air Discharge  
Left Air Intake  
Shaded area  
indicates a minimum  
clearance of 18" (457mm)  
for proper air flow.  
B
Shaded area  
indicates a recommended  
clearance of 24" (610mm)  
for component access and  
removal.  
C
Shaded area  
Removable panel for access  
indicates a minimum  
clearance of 18" (457mm)  
for proper air flow  
to high-voltage and low-voltage  
connections and refrigeration  
components  
DPN000130  
Rev. 0  
Table 1  
Cabinet and floor planning data, horizontal air discharge  
Net Weight  
lb. (kg)  
Model Numbers  
Dimensional Data, in. (mm)  
B
60Hz  
50Hz  
A
C
PFH014A-L  
PFH020A-L  
PFH027A-L  
PFH027A-H  
PFHZ27A-L  
PFH037A-L  
PFH042A-L  
PFH037A-H  
PFHZ37A-L  
PFH042A-H  
PFHZ42A-L  
PFH067A-L  
PFH013A-L  
PFH019A-L  
PFH026A-L  
PFH026A-H  
PFHZ26A-L  
PFH036A-L  
PFH041A-L  
PFH036A-H  
PFHZ36A-L  
PFH041A-H  
PFHZ41A-L  
PFH066A-L  
40 (1016)  
23-1/2 (597)  
18 (457)  
200 (91)  
48 (1219)  
31 (787)  
18 (457)  
18 (457)  
241 (109)  
53 (1343)  
36-1/4 (918)  
351 (159)  
3
     
Installation  
Figure 2  
Dimensions, top air discharge  
Top Air  
Discharge  
Guard Height  
Fan Rotation  
CW  
Right Air Intake  
Shaded area  
indicates a minimum  
clearance of 18" (457mm)  
for proper air flow.  
Left Air  
Intake  
2"  
(51mm)  
Shaded area  
indicates a minimum  
clearance of 18" (457mm)  
for proper air flow  
Removable panel for access  
to high-voltage and low-voltage  
connections and refrigeration  
components  
Shaded area  
indicates a recommended  
clearance of 24" (610mm)  
for component access and  
removal.  
53-3/16"  
(1351mm)  
36-1/8"  
(918mm)  
4"  
(102mm) typ.  
2"  
(51mm) typ.  
1/2" Bolt-Down Holes  
(6 places)  
4-23/32"  
(120mm)  
2"  
(51mm)  
32-1/8"  
(816mm)  
25-3/32"  
(637mm)  
2"  
(51mm)  
46-7/32"  
(1174mm)  
DPN000131  
Rev. 0  
FOOTPRINT DIMENSIONS  
Table 2  
Electrical and piping connections, top air discharge  
Model Numbers  
Dimensional Data in. (mm)  
Module Net  
Weight lb.  
60Hz  
50Hz  
A
B
C
D
(kg) .  
PFH067A-H  
PFHZ67A-L  
PFH096A-L  
PFH066A-H  
PFHZ66A-L  
PFH095A-L  
488 (222)  
570 (259)  
53 (1343)  
36-1/4 (918)  
38-1/2 (978)  
5-1/2 (140)  
4
   
Installation  
Figure 3  
Dimensional data, 277V step-down transformer  
.31" (8mm) Dia.  
For rigid mounting  
and shipping  
.281" (7mm) Dia.  
For wall mounting  
1/4-20 (2 screws &  
1D18214P1  
lock washers) for  
rigid mounting and  
shipping  
10.3" (262mm)  
1D18214P2  
11.68" (297mm)  
Remove screws &  
attach bracket  
5.5"  
(140mm)  
4.92"  
(125mm)  
Access to electrical  
connections from  
bottom  
WALL MOUNTING  
RIGID MOUNTING  
Notes:  
1. 1D18214P1 = Acme catalog no. T-1-37921 for all small systems except 3-ton Liebert DataMate  
with integral condenser.  
2. 1D18214P2 = Acme catalog no. T-1-37922 for 3-ton Liebert DataMate with integral condenser.  
3. Epoxy coated. Suitable for indoor/outdoor service. Horizontal- or vertical-mount.  
Totally enclosed, non-ventilated.  
4. Both brackets are shipped loose with transformer.  
WIRING FOR TRANSFORMER  
277V line voltage  
Jumpers  
H4  
H2  
H1  
X4  
H3  
X3  
X2  
X1  
Notes:  
1. Jumper as shown.  
2. Connect 277V line to H4 and X1  
3. Connect 230V load to H1 and H4  
DPN000647  
REV. 0  
230V to unit  
5
 
Installation  
2.4  
Piping and Electrical Connections  
Figure 4  
Piping and electrical connections, horizontal discharge  
Liquid Line  
Quick Connect  
(Male Coupling)  
Suction Line  
Quick Connect  
(Male Coupling)  
A
F
G
Electrical Entrance for  
High-Voltage Connection  
B
C
Electrical Entrance for  
Low-Voltage Connection  
D
DPN000132  
Rev. 0  
E
Table 3  
Electrical and piping connections, horizontal air discharge  
Electrical Connections, in (mm)  
Model Numbers  
Piping Connections, in. (mm)  
60Hz  
50Hz  
A
B
C
D
E
F
G
PFH014A-L  
PFH020A-L  
PFH027A-L  
PFH027A-H  
PFHZ27A-L  
PFH037A-L  
PFH042A-L  
PFH037A-H  
PFHZ37A-L  
PFH042A-H  
PFHZ42A-L  
PFH067A-L  
PFH013A-L  
PFH019A-L  
PFH026A-L  
PFH026A-H  
PFHZ26A-L  
PFH036A-L  
PFH041A-L  
PFH036A-H  
PFHZ36A-L  
PFH041A-H  
PFHZ41A-L  
PFH066A-L  
2-1/4 (57) 5-1/4 (133) 7-3/4 (197) 8-3/4 (222)  
5 (127) 7-1/4 (184)  
2 (51)  
2 (51)  
5-3/4 (146) 8-1/2 (216) 4-3/4 (121) 6-3/4 (171)  
8-1/2 (216)  
8-1/2 (216)  
6 (152)  
8-1/2 (216) 4-3/4 (121) 7-3/4 (197)  
6
     
Installation  
Figure 5  
Piping and electrical connections, top air discharge  
* System 2 (5 Ton)  
Electrical Entrance for  
High-Voltage Connection  
Liquid Line  
Quick Connect  
(Male Coupling)  
Electrical Entrance for  
Low-Voltage Connection  
* System 1 (3 Ton)  
Suction Line  
Quick Connect  
(Male Coupling)  
DPN000133  
Rev. 0  
* System 1 and System 2 on 8 Ton only  
Table 4 Piping and electrical connections, top air discharge  
Electrical Connections  
in. (mm)  
Piping Connections  
in. (mm)  
Model Numbers  
60Hz 50Hz  
A
B
C
D
E
F
G
PFH067A- H PFH066A-H  
PFHZ67A- L PFHZ66A-L  
2
(51)  
6
8-1/2  
(216)  
4-3/4  
(121)  
7-3/4  
(197)  
8-1/2  
(216)  
(152)  
PFH096A- L  
PFH095A-L  
11-1/2 (292)  
7
   
Installation  
Figure 6  
General piping arrangement  
SINGLE CIRCUIT = 1 - 5 Tons  
DUAL CIRCUIT = 8 Tons  
Condenser  
Coil  
High Pressure  
Switch  
Compressor *  
Liquid Injection  
Valve Bulb  
Hot Gas Bypass  
Solenoid Valve  
3 - Way Head  
Pressure  
Pressure Relief Valve  
Suction Line  
Male Quick  
Control Valve  
Sight  
Glass  
Connect Coupling  
Hot Gas Bypass  
Control Valve  
Check Valve  
Liquid Injection  
Valve  
Liquid Line  
Liebert Lee-Temp  
Receiver  
Solenoid Valve  
Receiver Heater  
Pressure Limiting  
Switch  
Pressure Balancing  
Valve  
Liquid Line Male Quick  
Connect Coupling  
SINGLE CIRCUIT SHOWN  
DPN000129 REV 1  
* Reciprocating compressor 1 Ton, 60Hz  
Scroll compressor 1 Ton, 50Hz and 1-1/2 to 8 Tons  
8
 
Installation  
Figure 7  
Electrical field connections, 1- to 5-ton units  
Field-supplied unit  
disconnect switch  
Field-supplied unit  
disconnect switch  
Single- or three-phase  
electric service not provided  
by Liebert  
Single- or three-phase  
electric service not provided  
by Liebert  
Field-supplied 24V  
NEC Class 2 wiring  
to evaporator module  
Field-supplied 24V  
NEC Class 2 wiring  
to evaporator module  
Horizontal Air Discharge Models  
Top Air Discharge Models  
(5 Ton High Ambient or 5 Ton Quiet-Line)  
Electric service connection  
to contactor or terminal block  
Factory-wired  
to components on  
electric panel  
Single- or three-phase electric  
service not provided by Liebert  
High-voltage electric power  
supply entrance  
Heat rejection connection.  
Field-supplied 24V NEC  
Class 2 wiring.  
Wire connections from  
evaporator module:  
1. 24V GND  
Low-voltage electric  
power supply  
entrance  
Earth ground connection  
terminal for field wiring  
2. 24V Supply  
3. High Pressure Alarm  
4. Hot Gas Bypass Connection  
DPN000134  
Refer to tables or unit serial label  
for FLA, WSA and OPD values.  
Rev. 1  
9
 
Installation  
Figure 8  
Electrical field connections, 8-ton units  
Field-supplied unit  
disconnect switch  
Single- or three-phase  
electric service not provided  
by Liebert  
Field-supplied 24V  
NEC Class 2 wiring  
to evaporator module  
Electric service  
connection to contactor  
or terminal block  
Factory-wired  
to components on  
electric panel  
Single- or three-phase electric  
service not provided by Liebert  
High-voltage  
electric power  
supply entrance  
Heat rejection connection.  
Field-supplied 24V NEC  
Class 2 wiring.  
Low-voltage electric  
power supply  
entrance  
Wire connections from evaporator module:  
1. 24V GND System 1  
2. 24V Supply System 1  
3. High Pressure Alarm System 1  
4. Hot Gas Bypass Connection System 1  
5. 24V GND System 2  
Earth ground connection  
terminal for field wiring  
6. 24V Supply System 2  
7. High Pressure Alarm System 2  
8. Hot Gas Bypass Connection System 2  
9. 24V GND Condenser Fan  
10. 24V SUPPLY Condenser Fan  
Refer to tables or unit serial label  
for FLA, WSA and OPD values.  
DPN000135  
Rev. 1  
10  
 
Installation  
Figure 9  
Single-phase, 1-3 ton model schematic, typical  
Conductors Field-Supplied  
(See Note 5)  
NOMENCLATURE  
OUTDOOR CONDENSING MODULE  
EVAPORATOR UNIT  
Standard Devices  
BDR -- Bleed Resistor  
Unit Alarm  
3
3
2
BL  
W
Input  
C1 -- Condenser Contactor  
CAP1 -- Compressor Capacitor  
Run  
CAP2 -- Fan Motor Capacitor  
CAP3 -- Compressor Capacitor  
Start  
CHTR -- Compressor Heater  
COMP -- Compressor  
FM -- Fan Motor  
Connection  
HP1  
24V Power  
2
C1  
BK  
Supply  
25,  
27  
From Unit  
Min 40 Va  
BR  
HP1 -- High Pressure Switch  
(Auto Reset)  
HP2 -- Pressure Switch Receiver  
(Auto Reset)  
LLSV -- Liquid Line Solenoid Valve  
PR -- Potential Relay  
RHTR -- Receiver Heater  
HGBP Signal  
Output  
Connection  
4
1
4
BR  
BR  
HG1  
See Note 6  
BK  
BK  
1
24V Ground  
HP2  
RHTR  
R
Optional Devices  
CSR -- Compressor Start Resistor  
HG1 -- Hot Gas Relay  
HGSV -- Hot Gas Solenoid Valve  
HG1  
BK  
R
BK  
1C1  
HGSV  
L1  
1-Phase Line  
Voltage Supply  
By Others  
(See Notes 1 & 3)  
BK  
2C1  
L2  
LLSV  
BK  
CHTR  
BK  
Supplied on  
1-Ton PFC  
Models Only  
WIRE COLOR CODE  
BK  
OR - Orange  
R - Red  
R
BR - Brown  
P - Purple  
GN - Green  
Y - Yellow  
BL - Blue  
BK - Black  
W - White  
Insulation Color  
GN / Y  
CAP3  
BDR  
Earth Ground  
By Others  
BK  
CAP1  
R
BK  
R
R
R
PR  
5
1
R
R
CAP2  
BR  
2
Y
BR  
Tracer Color  
C
CSR  
'FM'  
FAN  
C
S
COMP  
MOTOR  
A
B
Y
Optional on  
Selected Units  
Factory-Supplied Line Voltage  
Field-Installed Line Voltage Wiring  
Optional Line Voltage Wiring  
Factory-Supplied 24V NEC Class 2 Wiring  
Optional 24V Wiring  
Factory-Supplied 24V NEC Class 2 Wiring  
Factory-Supplied Earth Grounding Wire  
Pigtail Leads 24V Wiring  
1. All units 208/230V, 1 phase. On 208/230V units installed  
in Canada only, CSA requires that L1 and L2 are non-neutral  
supply conductors. L1 et L2 pour conducteurs d'alimentation  
non-neutres. On other units, L2 is designated neutral. See  
unit name plate and installation manual for main supply wiring  
information. Use copper conductors only.  
2. Use copper conductors only. See unit nameplate for main supply  
wire sizing data. Wire per local codes.  
3. A remote disconnect switch is to be field-supplied and mounted  
within sight of the condensing unit. See unit nameplate for voltage  
and amperage requirements.  
Terminal Strip Connection  
Grounding Lug Connection  
4. All motors have internal line break overload protectors.  
191642  
Rev. 0  
Three-phase motors protected for primary single-phasing conditions.  
5. Terminals 1,2,3, and 4 are for connection of control circuit from  
evaporator unit. Wiring by others to be NEC Class 2 and sized  
for 1V maximum drop.  
6. Wire '1' is connected to the grounded side of the 24V Class 2 circuit.  
11  
 
Installation  
Figure 10 Three-phase, 3-5 ton model schematic, typical  
Conductors Field-Supplied  
(See Note 5)  
NOMENCLATURE  
Standard Devices  
OUTDOOR CONDENSING MODULE  
EVAPORATOR UNIT  
Unit Alarm  
Input  
3
2
C1 -- Condenser Contactor  
CAP2 -- Fan Motor Capacitor  
CHTR -- Compressor Heater  
COMP -- Compressor  
F1 -- Transformer Fuse 1  
F2 -- Transformer Fuse 2  
FM -- Fan Motor  
HP1 -- High Pressure Switch  
(Auto Reset)  
HP2 -- Pressure Switch Receiver  
(Auto Reset)  
3
BL  
W
Connection  
24V Power  
2
HP1  
BK  
C1  
27,29,30  
Supply  
From Unit  
Min 40VA  
BR  
HGBP Signal  
Output  
Connection  
LLSV -- Liquid Line Solenoid Valve  
RHTR1 -- Receiver Heater No. 1  
RHTR2 -- Receiver Heater No. 2  
(3-,4-,and 5-ton only)  
TX1 -- Transformer Line  
Voltage to230V  
Optional Devices  
HG1 -- Hot Gas Relay  
HGSV -- Hot Gas Solenoid Valve  
4
1
4
1
BR  
HG1  
27  
See Note 6  
BR  
24V Ground  
See Note 1  
See Note 7  
BK  
HP2  
F1  
F2  
TX1  
BK  
R
R
RHTR1  
HG1  
RHTR2  
BK  
BK  
HGSV  
1C1  
2C1  
3C1  
L1  
L2  
L3  
3-Phase Line  
Voltage Supply  
By Others  
WIRE COLOR CODE  
OR - Orange  
R - Red  
LLSV1  
(See Note 3)  
BR - Brown  
P - Purple  
GN - Green  
Y - Yellow  
BL - Blue  
BR  
CHTR  
BR  
BR  
BK  
R OR  
R
Earth Ground  
By Others  
BK - Black  
W - White  
CAP2  
Y
Insulation Color  
GN / Y  
BR  
Tracer Color  
'FM'  
Fan  
Motor  
T2  
T1  
T3  
COMP  
1. Transformer 'TX1' provided on units with nameplate voltages greater  
than 240V.  
2. Use copper conductors only. See unit nameplate for main supply wire  
sizing data. Wire per local codes.  
3. A remote disconnect switch is to be field supplied and mounted  
within sight of the condensing unit. See unit nameplate for voltage  
and amperage requirements.  
4. All motors have internal line break overload protectors. Three-phase  
motors protected for primary single-phasing conditions.  
Factory-Supplied Line Voltage  
Field-Installed Line Voltage Wiring  
Optional Line Voltage Wiring  
Factory-Supplied 24V NEC Class 2 Wiring  
Optional 24V Wiring  
Factory-Supplied 24V NEC Class 2 Wiring  
Factory-Supplied Earth Grounding Wire  
Pigtail Leads 24V Wiring  
Terminal Strip Connection  
5. Terminals 1, 2, 3 and 4 are for connection of control circuit from evaporator  
unit. Wiring by others to be NEC Class 2 and sized for 1 volt maximum drop.  
6. Wire '1' is connected to the grounded side of the 24V Class 2 circuit.  
7. Receiver heater No.2 'RHTR2' supplied on 4- and 5-ton standard models and  
3/3.5-ton high ambient and Quiet-Line models.  
191643  
Rev. 0  
Grounding Lug Connection  
12  
 
Installation  
Figure 11 Three-phase, 8 ton model schematic, typical  
Conductors Field-Supplied  
(See Note 5)  
STANDARD DEVICES  
OUTDOOR CONDENSING MODULE  
Evaporator Unit  
HIGH HEAD 1  
3
3
C1 - Compressor Contactor 1  
C2 - Compressor Contactor 2  
CHTR1 - Compressor Heater 1  
CHTR2 - Compressor Heater 2  
COMP1 - Compressor #1  
COMP2 - Compressor #2  
F1 - Transformer Fuse  
F2 - Transformer Fuse  
FM - Fan Motor  
HP1 - High Pressure Switch 1  
(Auto Reset)  
HP2 - High Pressure Switch 2  
(Auto Reset)  
BL  
See Note 6  
HP1  
2
2
COOLING 1  
W
R
BK  
C1  
C1 Aux.  
C2 Aux.  
10  
10  
MF  
See Note 8  
BR  
9
9
24V GND  
HGBP1  
See Note 7  
4
1
7
4
1
7
R
HG1  
See Note 8  
See Note 6  
BR  
BL  
COMP1  
HIGH HEAD 2  
HP3 - Pressure Switch 3  
Receiver (Auto Reset)  
HP2  
6
6
COOLING 2  
W
BK  
C2  
HP4 - Pressure Switch 4  
Receiver (Auto Reset)  
See Note 7  
See Note 8  
8
5
8
5
HG2  
LLSV1 - Liquid Line Solenoid Valve 1  
LLSV2 - Liquid Line Solenoid Valve 2  
MF - Fan Motor Contactor  
RHTR1 - Receiver Heater No.1  
RHTR2 - Receiver Heater No.2  
TX1 - Transformer Line Voltage to 230V  
OPTIONAL DEVICES  
HG1 - Hot Gas Relay 1  
HG2 - Hot Gas Relay 2  
HGSV1 - Hot Gas Solenoid 1  
HGSV2 - Hot Gas Solenoid 2  
R
HGBP2  
COMP2  
BR  
HP4  
BK  
See Note 1  
R
BK  
HP3  
F1  
TX1  
BK  
R
R
RHTR2  
HGSV1  
RHTR1  
HG1  
F2  
BK  
BK  
1C1  
2C1  
3C1  
L1  
L2  
L3  
3-Phase Line  
Voltage Supply  
By Others  
LLSV1  
WIRE COLOR CODE  
(See Notes 2 and 3)  
OR - Orange  
R - Red  
BR - Brown  
P - Purple  
GN - Green  
Y - Yellow  
BL - Blue  
BK - Black  
W - White  
BR  
CHTR1  
BR  
BR R OR  
Earth Ground  
By Others  
BR  
BR  
BR  
CHTR2  
T2  
T3 T1  
Insulation Color  
COMP1  
GN / Y  
Tracer Color  
1MF  
2MF  
3MF  
HG2  
HGSV2  
1C2  
2C2  
3C2  
LLSV2  
BR R OR  
T2  
T3 T1  
FM  
Fan  
Motor  
COM2P  
NOTES  
1. Transformer TX1 provided on units with nameplate voltages greater than 250V.  
2. Use copper conductors only. See unit nameplate for main supply wire sizing data.  
Wire per local codes.  
3. A remote disconnect switch is to be field-supplied and mounted within sight of the  
condensing unit. See unit nameplate for voltage and amperage.  
4. All motors have internal line break overload protectors.Three-phase motors  
protected for primary single-phasing conditions.  
WIRING LEGEND  
Factory-supplied line voltage  
Field-installed line voltage wiring  
Optional line voltage wiring  
Factory-supplied 24V NEC Class 2 wiring  
Optional 24V wiring  
Field-supplied 24V NEC Class 2 wiring  
Field-supplied earth grounding wire  
Pigtail leads  
5. Terminals 1 thru 8 are for connection of control circuit from evaporator unit.  
(Terminals 4 and 8 are not used by some evaporator models . See Note 7). Wiring by  
others to be NEC Class 2 and sized for 1V maximum drop.  
6. Connection to Terminals 3 and 7 is used for high head alarm input connection in  
evaporator unit.  
Terminal strip connection  
Grounding lug connection  
7. Connection to Terminals 4 and 8 is required only on models with (HGBP) hot gas  
bypass control signal output in evaporator unit.  
8. Wires 1, 5 and 9 are separately connected to the grounded side of the 24V  
Class 2 circuit. Do not connect them together.  
13  
 
Installation  
2.5  
Piping Considerations  
The Liebert Mini-Mate2, Liebert DataMate and the 3-ton Liebert Challenger 3000 split system units  
are designed with quick-connect fittings and are factory-charged to proper refrigerant levels. This  
permits connecting units without brazing inside critical spaces. These split systems require two  
refrigerant lines—an insulated copper suction line and a copper liquid line—between the evaporator  
and condensing units. The 8-ton Liebert Mini-Mate2 split system units will require four refrigerant  
lines between the evaporator and condensing units. Each refrigeration circuit will need one insulated  
copper suction line and one copper liquid line.  
Two methods exist for installing the copper suction and liquid lines:  
• Using optional pre-charged line sets (for 1- to 3.5-ton R-407C model units only).  
• Using optional Sweat Adapter Kit(s) and hard piping between units.  
NOTICE  
Risk of improper handling of refrigerant. Can cause environmental damage and violation of  
environmental regulations.  
Refrigerant must handled in accordance with all national, regional and local codes.  
NOTE  
Proper safety equipment and proper refrigeration tools are required in working with R-407C  
refrigerant. Check unit serial tag for correct refrigerant type before topping off or recharging a  
system.  
NOTE  
Refrigerant R-407C uses a POE (polyol ester) lubricant. The R-407C refrigerant must be  
introduced and charged from the cylinder only as a liquid.  
NOTE  
When installing field piping, care must be taken to protect all refrigerant lines from the  
atmosphere, especially when using refrigerants with POE oils. Do not allow the piping to stand  
open to air for more than 15 minutes. Units designed for R-407C have a compressor which  
contains POE oil that is very hygroscopic; that is, it quickly absorbs water from the air. The  
longer the compressor piping is left open to air, the harder it will be to fully evacuate. If left  
open too long, the POE oil may need to be replaced before achieving the required vacuum level.  
NOTE  
Complete all piping and evacuate lines before connecting quick connects when using an  
optional sweat adapter kit and field installed hard piping.  
Follow all proper brazing practices including a dry nitrogen purge to maintain system  
cleanliness.  
2.5.1 Piping for Elevation Differences between PFH and Evaporator  
System sizes affect the maximum equivalent piping lengths and maximum relative elevation differ-  
ences between evaporator and condensing unit mounting locations. See Table 5 for requirements.  
Traps in refrigerant piping are required when elevation differences exist between evaporator and con-  
densing unit mounting locations. See Figure 12 for requirements. Table 6 should be used when  
traps are required with field-fabricated piping assemblies, to calculate equivalent pipe lengths to  
determine if installation will comply with Table 5 requirements.  
14  
   
Installation  
Figure 12 Refrigerant piping diagram  
Pitch down 1/2" (13mm) per 10 ft. (3m)  
Evaporator  
NOTE  
When installing remote condensing units below the  
evaporator, the suction gas line should be trapped  
with an inverted trap to the height of the evaporator.  
This prevents refrigerant migration to the compres-  
Suction Line Piping  
Condensing Unit  
Below Evaporator  
sors during off cycles. Maximum recommended verti-  
cal level drop to condensing unit is 15 ft. (4.6m).  
Condensing  
Unit  
Condensing  
Unit  
See Table 5 for maximum  
vertical rise recommendation  
above evaporator.  
Evaporator  
Suction Line Piping  
Condensing Unit Above Evaporator  
Traps recommended at the base of riser  
exceeding 5 ft (1.5m) and every20 feet  
(6m) of vertical rise.  
Table 5  
Nominal  
System Size  
Tons  
Pipe length and condenser elevation relative to evaporator  
Max. Equiv.  
Pipe Length  
ft. (m)  
Maximum PFH  
Level Above  
Evaporator, ft. (m) Evaporator, ft. (m)  
Maximum PFH  
Level Below  
1 or 1.5  
2
50 (15)  
100 (30)  
150 (45)  
40 (12)  
40 (12)  
50 (15)  
15 (4.6)  
15 (4.6)  
15 (4.6)  
3, 3.5, 5 or 8  
Table 6  
Equivalent lengths for various pipe fittings, ft (m)  
Copper Pipe  
OD, in.  
90 Degree  
Elbow Copper Elbow Cast  
90 Degree  
45 Degree  
Elbow  
Gate  
Valve  
Globe  
Valve  
Angle  
Valve  
Tee  
1/2  
5/8  
0.8 (0.24)  
0.9 (0.27)  
1.0 (0.3)  
1.3 (0.39)  
1.4 (0.42)  
1.5 (0.45)  
1.8 (0.54)  
2.2 (0.67)  
2.9 (0.88)  
3.5 (1.06)  
0.4 (0.12) 2.5 (0.76) 0.26 (0.07)  
0.5 (0.15) 2.5 (0.76) 0.28 (0.08)  
0.6 (0.18) 2.5 (0.76) 0.3 (0.09)  
0.8 (0.24) 3.6 (1.09) 0.36 (0.1)  
7.0 (2.13)  
9.5 (2.89)  
12.0 (3.65)  
17.2 (5.24)  
22.5 (6.85)  
32.0 (9.75)  
4.0 (1.21)  
5.0 (1.52)  
6.5 (1.98)  
9.5 (2.89)  
12.0 (3.65)  
16.0 (4.87)  
3/4  
7/8  
1.45 (0.44)  
1.85 (0.56)  
2.4 (0.73)  
2.9 (0.88)  
1-1/8  
1-3/8  
1-5/8  
1.0 (0.3)  
4.6 (1.4) 0.48 (0.14)  
1.3 (0.39) 6.4 (1.95) 0.65 (0.19)  
1.6 (0.48) 7.2 (2.19) 0.72 (0.21) 36.0 (10.97) 19.5 (5.94)  
Refrigerant trap = Four times equivalent length of pipe per this table  
15  
     
Installation  
2.5.2 Pre-Charged Line Sets  
Liebert pre-charged line sets are available in 15 ft (4.5m) and 30 ft (9m) lengths (see Table 7).  
NOTICE  
Risk of improper handling and installation of pre-charged lines. Can cause kinks and similar  
damage to lines.  
Care must be taken to prevent kinking the pre-charged lines for 1-ton and 3.5-ton units.  
Use tube benders and make all bends before making connections to either end of the pre-  
charged pipes. Coil any excess tubing in a horizontal plane with the slope of the tubing toward  
the condensing unit. Use a soft, flexible material to pack around the tubes when sealing  
openings in walls to prevent tube damage and to reduce vibration transmission.  
Table 7  
Refrigerant charge in Liebert pre-charged R-407C line sets  
Line Size, Length, Charge R-407C,  
in.  
ft. (m)  
15 (4.5)  
30 (9)  
lb-oz (kg)  
0-5 (0.14)  
0-10 (0.28)  
0-5 (0.14)  
0-10 (0.28)  
3/8 liquid  
15 (4.5)  
30 (9)  
5/8 or 7/8  
suction  
2.5.3 Field-Fabricated Line Sets  
All field-fabricated refrigeration piping should be copper piping, brazed using a brazing alloy with a  
minimum temperature of 1350°F (732°C), such as Sil-Fos. Use a flow of dry nitrogen through the pip-  
ing during brazing to prevent formation of copper oxide scale inside the piping. Avoid soft solders such  
as 50/50 or 95/5.  
Use the sweat adapter kits to terminate the piping at each unit end. Consult factory representatives  
to obtain the proper sweat adapter kit. Table 8 has PFH unit connection sizes. Use Table 9 for rec-  
ommended line sizes.  
Prevailing good refrigeration practices should be employed for piping supports, leak testing, evacua-  
tion, dehydration and charging of the refrigeration circuits. The refrigeration piping should be iso-  
lated from the building by the use of vibration-isolating supports. Use a soft, flexible material to pack  
around the tubes when sealing openings in walls to prevent tube damage and to reduce vibration  
transmission.  
Before connecting units together with field-fabricated piping, check for leaks and dehydrate  
the field piping as follows:  
1. Pressurize the field piping to 150 psig (1034 kPa) using dry nitrogen with a trace of refrigerant.  
Check system for leaks with a suitable leak detector.  
2. After completion of leak testing, release the test pressure (per local code) and triple evacuate the  
field piping to 250 microns or lower, breaking the vacuum between the first two evacuations with  
dry nitrogen.  
3. After the third evacuation, verify 250 microns is maintained for at least one minute after the  
piping is isolated from the vacuum pump by a shutoff valve.  
Field piping is now ready to be installed between evaporator and condensing units.  
16  
     
Installation  
Table 8  
Liebert PFH unit charge levels and coupling size  
Model Numbers  
60 Hz 50 Hz  
95°F (35°C) Standard Sound  
R-407C Charge  
lb-oz (kg)  
Coupling Size  
Liquid  
Suction  
PFH014A-_L7  
PFH020A-_L7  
PFH027A-_L7  
PFH037A-_L7  
PFH042A-_L7  
PFH067A-_L7  
PFH096A-_L7  
3-ton Circuit  
PFH013A-_L7  
PFH019A-_L7  
PFH026A-_L7  
PFH036A-_L7  
PFH041A-_L7  
PFH066A-_L7  
PFH095A-_L7  
3-ton Circuit  
8-6 (3.8)  
#6  
#11  
13-5 (6.04)  
#6  
#11  
#12  
26-10 (12.08)  
#10  
22-9 (10.23)  
36-5 (16.47)  
#6  
#11  
#12  
5-Ton Circuit  
5-Ton Circuit  
#10  
105°F (41°C) High Ambient  
PFH027A-_H7 PFH026A-_H7  
PFH037A-_H7 PFH036A-_H7  
PFH042A-_H7 PFH041A-_H7  
PFH067A-_H7 PFH066A-_H7  
Quiet-Line  
13-5 (6.04)  
26-10 (12.08)  
51-11 (23.45)  
#6  
#11  
#12  
#12  
#10  
#10  
PFHZ27A-_L7  
PFHZ37A-_L7  
PFHZ42A-_L7  
PFHZ67A-_L7  
PFHZ26A-_L7  
PFHZ36A-_L7  
PFHZ41A-_L7  
PFHZ66A-_L7  
13-5 (6.04)  
26-10 (12.08)  
51-11 (23.45)  
#6  
#11  
#12  
#12  
#10  
#10  
Table 9  
Recommended line sizes, OD Cu  
PFH_36A  
PFH_37A  
3-ton circuit  
of 8-ton model  
PFH_67A  
PFH_66A  
5-ton circuit  
of 8-ton model  
PFH_14A  
PFH_13A  
PFH_20A  
PFH_19A  
PFH_27A  
PFH_26A  
PFH_42A  
PFH_41A  
Equiv.  
ft. (m)  
Suction Liquid Suction Liquid Suction Liquid Suction Liquid Suction Liquid Suction Liquid  
50 (15.2)  
75 (22.9)  
100 (30.5)  
125 (38.1)  
150 (45.7)  
5/8"  
3/8"  
5/8"  
3/8"  
7/8"  
7/8"  
7/8"  
*
3/8"  
1/2"  
1/2"  
*
7/8"  
7/8"  
1/2"  
1/2"  
1/2"  
1/2"  
5/8"  
7/8"  
7/8"  
1/2"  
1/2"  
1/2"  
5/8"  
5/8"  
1-1/8"  
1-1/8"  
1-1/8"  
1-3/8"  
1-3/8"  
1/2"  
5/8"  
5/8"  
5/8"  
5/8"  
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
1-1/8"  
1-1/8"  
1-1/8"  
1-1/8"  
1-1/8"  
1-1/8"  
*
*
* Exceeds maximum recommended line length  
17  
   
Installation  
2.5.4 Installation of Piping to Units  
NOTE  
When using hard piping, complete all piping and evacuate the lines before connecting  
quick-connects.  
NOTE  
Liebert Challenger 5-ton evaporator includes a nitrogen holding charge only. This holding  
charge must be evacuated and unit placed in a 250 micron vacuum prior to connecting piping.  
See Table 12 for field charge required.  
Use caution when connecting the quick-connect fittings. Read through the following steps before mak-  
ing the connections.  
1. Remove protector caps and plugs.  
2. Carefully wipe coupling seats and threaded surfaces with a clean cloth.  
3. Lubricate the male diaphragm and synthetic rubber seal with refrigeration grade oil.  
4. Thread the coupling halves together by hand to ensure that the threads mate properly.  
5. Tighten the coupling body hex nut and union nut with the proper sized wrench until the coupling  
bodies bottom out or until you feel a definite resistance.  
6. Using a marker or pen, make a line lengthwise from the coupling union nut to the bulkhead.  
7. Tighten the nuts an additional quarter turn; the misalignment of the lines shows how much the  
coupling has been tightened. This final quarter turn is necessary to ensure that the joint will not  
leak. Refer to Table 10 for torque requirements.  
8. Add liquid refrigerant charge for any field-fabricated piping (refer to Table 11) and the 5-ton  
Liebert Challenger evaporator if used (refer to Table 12).  
Table 10 Piping connection sizes and torque  
Line Size OD Cu Coupling Size Torque, lb-ft. (N-m)  
1/4 or 3/8  
5/8 thru 7/8  
1-1/8  
#6  
#10 or #11  
#12  
10-12 (145-175)  
35-45 (510-655)  
50-65 (730-950)  
Table 11  
Line charges - refrigerant per 100 ft. (30m) of Type L copper tube  
R-407C, lb/100 ft. (kg/30m)  
Line Size,  
O.D., in.  
Liquid Line Suction Line  
3/8  
1/2  
3.7 (1.7)  
6.9 (3.1)  
11.0 (5.0  
15.7 (7.1)  
23.0 (10.4)  
5/8  
0.4 (0.2)  
0.6 (0.3)  
1.0 (0.4)  
1.7 (0.7)  
2.7 (1.1)  
3/4  
7/8  
1-1/8  
1-3/8  
2.5.5 R-407C PFH Installed as a Replacement Condensing Unit in an R-22 System  
When replacing the condensing unit of an existing Liebert split system containing R-22 and mineral  
oil, the following should be considered.  
1. Check for proper operation of the system prior to replacing the outdoor unit. If this is not possible,  
at minimum perform a leak check to ensure that the components that remain (line set,  
evaporator) are leak tight.  
2. Check for acid or contaminants in the mineral oil.  
18  
       
Installation  
Remove Existing Condensing Unit  
1. Recover refrigerant in system using proper refrigeration practices.  
2. Oil removal: The majority of the oil will be in the old condensing unit (compressor, condenser and  
receiver), which will be replaced with the new unit.  
3. Remove high-voltage and low-voltage wiring.  
NOTE  
Wiring should be removed by a licensed electrician.  
Existing low-voltage wiring may have a 3-wire lead. A 4-wire lead is required for hot gas  
bypass control on the new condensing unit.  
4. Cut the line set before the Aeroquip fittings entering the condensing unit.  
5. Remove the existing filter drier in evaporator unit and discard. The filter drier may contain  
contaminants that can be released out of the drier because of the POE oil.  
Filter Drier Selection and Installation  
Recommended  
1. Install a replaceable-core filter drier approved for POE oil. The existing drier must be removed.  
The replaceable core drier will not fit in the same location as the existing drier.  
2. Ensure there is enough clearance for replacing cores when choosing a location.  
3. Replace core a week after startup and inspect the removed replaceable core for contaminants to  
determine if another replacement is needed. (If the system experienced a burnout, shorter  
interval replacements will be needed.)  
Optional  
Install a new filter drier approved for POE oil in place of the existing one.  
Install the New Condensing Unit  
1. Install a stub tube kit on the existing line set connecting to the new condensing unit. This kit is  
available from Emerson or your local Emerson representative.  
2. Evacuate the evaporator-piping system twice to a minimum 250 microns, breaking the vacuum  
with dry nitrogen each time.  
3. Evacuate a third time to 250 microns and verify the above levels are maintained for at least one  
minute after the unit is isolated from the vacuum pump by a shutoff valve.  
4. Connect the condensing unit with the evaporator and piping (see 2.5.4 - Installation of Piping  
5. Add enough R-407C refrigerant for the evaporator unit and line set. See Table 11 for line set  
charges required and Table 12 for standard evaporator units. If a non-standard evaporator was  
used, refer to evaporator unit serial tag for charge amounts and use 1 oz. (0.0283kg) R-407C for  
every 1 oz. (0.0283kg) R-22 used in old evaporator and piping.  
19  
Installation  
2.5.6 General System Charge Requirements  
Liebert split system units are designed with quick-connect fittings and are factory-charged to proper  
levels. Due to the wide range of operating ambients and sensitivity of the system components to  
charge level, the system charge must be maintained at recommended levels.  
If there is any doubt that the system has the correct refrigerant charge level, the correct  
procedure is to remove the entire system charge, evacuate the system and weigh in the  
recommended factory charge total for both units and any line sets or field piping.  
Tables 7, 8, 11 and 12 are included for field piping allowances, condensing unit charges, line sets and  
evaporator charges.  
Total refrigerant charge = evaporator + lines + condensing unit  
NOTE  
All condensing units and most evaporator units are fully charged with refrigerant. Some  
evaporator units are shipped from the factory with a nitrogen holding charge only. (Refer to  
evaporator serial tags.) If field-supplied refrigerant piping is installed, refrigerant must be  
added to the system. Refer to Figure 12 for field-supplied piping guidelines.  
Table 12 Evaporator Charge Levels  
Evaporator  
Models  
Charge R-407C  
oz (kg)  
Indoor Unit  
MMD11/12E  
MMD17/18E  
MMD23/24E  
MMD35/36E  
MMD59/60E  
3 (0.085)  
4 (0.113)  
7 (0.198)  
7 (0.198)  
4 (0.113)  
Liebert  
Mini-Mate2  
MMD95/96E 7 (0.198) each circuit  
DME020E  
DME027E  
DME037E  
BF/BU036E  
BF/BU060E*  
4 (0.113)  
5 (0.141)  
6.5 (0.184)  
9 (0.255)  
13 (0.368)  
Liebert DataMate  
Liebert Challenger  
3000  
*
Evaporator is charged with nitrogen at the factory  
20  
   
Installation  
2.6  
Electrical Connections  
Each unit is shipped from the factory with all internal wiring completed. All power, control wiring  
and ground connections must be made in accordance with the National Electrical Code and local  
codes. Refer to equipment nameplate regarding wire size and circuit protection requirements. Refer to  
Figures 5, 7 and 8 and electrical schematic (reference Figures 9 through 11) when making connec-  
tions. A manual electrical disconnect switch should be installed within 5 feet (1.6 m) of the unit in  
accordance with codes.  
WARNING  
!
Use voltmeter to be sure power is turned off before making any electrical connections.  
CAUTION  
that scroll compressor rotates in the correct direction.  
!
Three-phase power must be connected to the unit line voltage terminals in proper sequence so  
The three-phase scroll compressor requires proper phasing to ensure correct motor rotation. The com-  
ponent connections have been phase synchronized at the factory. Power phasing should be changed  
only at the line voltage supply to the unit. To change phasing, switch any two power leads to the unit.  
Observe system pressures to determine whether the unit is operating properly.  
CAUTION  
!
Apply power to condenser 8 hours before operating system. This time is required to allow  
liquid refrigerant to be driven out of the compressor. This is especially important at low  
ambient temperatures. The compressor crankcase heater is energized as long as power is  
supplied to the unit.  
Table 13 Design refrigerant pressures  
53 - 95 PSIG  
Suction  
(365 to 655 kPa)  
Discharge  
280 psig (1930 kPa)  
(At Design Ambient)  
High Pressure Cutout 400 psig (2760 kPa)  
Table 14 Application limits  
Input voltage  
Dry Bulb Air Temperature at Condenser  
Minimum  
Maximum  
Minimum  
Maximum  
115°F (46°C) Std  
Ambient & Quiet-Line  
-10%  
+10%  
-30°F (-34°C)  
-5% 208/230V  
single-phase  
125°F (52°C)  
High Ambient Models  
2.6.1 Low-Voltage Control Wire Connections  
Field-supplied four-wire control connection (10-wire on 8-ton units) is required between the outdoor  
condensing unit and the evaporator. Refer to Figures 5, 7 and 8 and to unit electrical schematic and  
Figures 9 through 11.  
2.6.2 Low-Voltage Control Wire Sizing  
Low-voltage wiring should be sized to allow a 1 volt maximum drop due to line resistance between the  
evaporator and condensing unit. Use NEC Class 1 or 2 wiring according to wire routing conditions  
chosen, local codes and application limits in Tables 14 and 15.  
Table 15 Recommended minimum wire size  
Max. Distance* Min. Wire Gauge  
ft. (m)  
50 (15)  
100 (30)  
150 (45)  
AWG (mm2)  
20 (0.75)  
18 (1.0)  
16 (1.5)  
*
One-way control wire run between outdoor condensing unit and evaporator.  
21  
           
Installation  
2.7  
Electrical Data  
Table 16 Electrical data—Standard sound and ambient models (95°F/35°C) 60Hz  
Nominal  
Capacity  
Tons  
Input Voltage- Phase  
* Electrical  
Model #  
Characteristic 208/230-1 208/230-3 460-3  
575-3  
FLA  
WSA  
OPD  
FLA  
8.4  
10.2  
15  
14  
1
1.5  
2
12.1  
14.8  
25  
20  
27  
37  
42  
67  
96  
WSA  
OPD  
FLA  
13.5  
16.5  
25  
WSA  
OPD  
FLA  
19.3  
23.8  
40  
12.8  
15.7  
25  
6.4  
7.8  
15  
5.9  
7.1  
15  
3
WSA  
OPD  
FLA  
15.3  
18.8  
30  
7.1  
8.7  
15  
6.6  
8.0  
15  
3.5  
5
WSA  
OPD  
FLA  
24.1  
29.3  
45  
11.7  
14.2  
20  
9.1  
11.1  
15  
WSA  
OPD  
FLA  
35.6  
40.8  
60  
17.4  
19.9  
25  
13.5  
15.4  
20  
8
WSA  
OPD  
*
FLA = Full Load Amps  
WSA = Wire Size Amps (minimum supply circuit current capacity)  
OPD = Overcurrent Protection Device (fuse or circuit breaker)  
Table 17 Electrical data—High ambient models (105°F/41°C) 60Hz  
Nominal  
Capacity,  
Tons  
Input Voltage-Phase  
* Electrical  
Characteristic 208/230-1 208/230-3  
Model #  
460-3  
7.4  
575-3  
FLA  
WSA  
OPD  
FLA  
21.3  
25.8  
40  
14.8  
17.7  
25  
5.9  
7.1  
15  
37  
3
3.5  
5
8.8  
15  
17.3  
20.8  
30  
8.1  
6.6  
8.0  
15  
42  
67  
WSA  
OPD  
FLA  
9.7  
15  
24.2  
29.4  
50  
11.7  
14.2  
20  
9.3  
11.3  
15  
WSA  
OPD  
*
FLA = Full Load Amps  
WSA = Wire Size Amps (minimum supply circuit current capacity)  
OPD = Overcurrent Protection Device (fuse or circuit breaker)  
Model # 14, 20 and 96 are not available in high ambient versions.  
22  
     
Installation  
Table 18  
Electrical data—Quiet-Line models (95°F/35°C) 60Hz  
Nominal  
Capacity  
Tons  
Input Voltage-Phase  
* Electrical  
Characteristic 208/230-1 208/230-3 460-3  
Model #  
575-3  
FLA  
WSA  
OPD  
FLA  
13.0  
16.0  
25  
27  
2
3
18.8  
23.3  
40  
12.3  
15.2  
25  
6.4  
7.8  
15  
5.2  
6.4  
15  
37  
42  
67  
WSA  
OPD  
FLA  
14.8  
18.3  
30  
6.9  
8.5  
15  
5.9  
7.3  
15  
3.5  
5
WSA  
OPD  
FLA  
21.1  
25.9  
45  
10.9  
13.4  
20  
8.8  
10.8  
15  
WSA  
OPD  
*
FLA = Full Load Amps  
WSA = Wire Size Amps (minimum supply circuit current capacity)  
OPD = Overcurrent Protection Device (fuse or circuit breaker)  
Model # 14, 20 and 96 are not available in Quiet-Line versions.  
Table 19 Electrical data—Standard sound and ambient models (95°F/35°C) 50Hz  
Nominal  
Capacity  
Tons  
Input Voltage-Phase  
220-1 200/230-3 380/415-3  
* Electrical  
Characteristic  
Model #  
13  
1
1.5  
2
FLA  
FLA  
FLA  
FLA  
FLA  
FLA  
FLA  
9.9  
10.9  
12.7  
18.4  
19  
26  
4.9  
7.0  
8.5  
13.2  
20.3  
36  
3
41  
3.5  
5
15.3  
24.1  
66  
95  
8
*
FLA = Full Load Amps  
Table 20 Electrical data—High ambient models (105°F/41°C) 50Hz  
Nominal  
Capacity  
Tons  
Input Voltage-Phase  
* Electrical  
Characteristic  
Model #  
13  
220-1 200/230-3 380/415-3  
1
1.5  
2
FLA  
FLA  
FLA  
FLA  
FLA  
FLA  
FLA  
19  
26  
14.8  
20.5  
6.0  
13.1  
9.6  
13.2  
36  
3
41  
3.5  
5
19.8  
24.2  
66  
95  
8
*
FLA = Full Load Amps  
23  
     
Installation  
Table 21 Electrical data - Quiet-Line models (95°F/35°C) 50Hz  
Nominal  
Capacity  
Tons  
Input Voltage-Phase  
* Electrical  
Characteristic  
Model #  
13  
220-1 200/230-3 380/415-3  
1
1.5  
2
FLA  
FLA  
FLA  
FLA  
FLA  
FLA  
FLA  
19  
26  
12.3  
18.0  
4.8  
6.9  
8.4  
12.4  
36  
3
41  
3.5  
5
17.3  
22.5  
66  
95  
8
*
FLA = Full Load Amps  
2.8  
Checklist for Completed Installation  
___ 1. All items unpacked and checked.  
___ 2. Proper clearances for service access maintained around equipment.  
___ 3. Equipment is level and mounting fasteners are tight.  
___ 4. Piping completed to refrigerant loop.  
___ 5. All piping connections are tight.  
___ 6. Piping routed to prevent chafing and rub-through.  
___ 7. Piping has been evacuated and refrigerant charge added (if required).  
___ 8. Line voltage to power wiring matches equipment nameplate.  
___ 9. Power wiring connections completed, including earth ground.  
___ 10. Power line circuit breakers or fuses have proper ratings for equipment installed.  
___ 11. Control wiring connections completed.  
___ 12. All wiring connections are tight.  
___ 13. Foreign materials have been removed from area: in and around all equipment installed  
(shipping materials, construction materials, tools, etc.).  
___ 14. Fans and blowers rotate freely and in the proper direction.  
___ 15. Blank startup sheet has been sent with the evaporator unit and is ready to be completed by  
the installer.  
24  
   
Operation  
3.0 OPERATION  
3.1  
Compressor  
The scroll compressor is equipped with a band type crankcase heater to resist liquid refrigerant  
migration into the compressor during the Off cycle. The three-phase scroll compressor requires proper  
phasing to ensure correct motor rotation. The component connections have been phase synchronized  
at the factory. Refer to 2.6 - Electrical Connections to verify proper compressor wiring.  
3.2  
High Head Pressure  
Compressor high head pressure is monitored with a pressure switch. One SPDT pressure switch is  
used for each compressor in the unit. If head pressure exceeds 400 psig (2760 kPa), the switch opens  
the compressor contactor and sends an input signal to the evaporator wall-box control. The high head  
pressure condition is acknowledged by pressing the alarm silence button, which will clear the alarm if  
the high head pressure condition no longer exists.  
If the compressor is off for 1 hour, the control goes into a special cold-start mode. In the cold-start  
mode on a call for cooling or dehumidification, the liquid line solenoid valve (LLSV) is energized. If  
the high pressure switch does NOT trip within 10 seconds, the control returns to normal operation of  
monitoring the high head pressure switch for three occurrences in a 12-hour period. It is a rolling  
timer and after the third high head alarm occurs and is acknowledged by the user, it will lock off the  
compressor. If while in the cold-start mode the high head pressure switch DOES trip within 10 sec-  
onds of the activation of the LLSV, the control does not annunciate the alarm. The control will turn off  
the LLSV and delay 10 seconds. The control will permit this occurrence two more times, or a total of  
three times. If on the fourth try the high head pressure switch trips within 10 seconds, the control will  
annunciate the alarm, turn off the LLSV, wait for the user to acknowledge the alarm and hold the  
compressor off for 3 minutes, which is the normal short cycle control. The control will permit this  
occurrence three times. On the third occurrence, the control will lock the compressor off until the con-  
trol power is reset.  
Check for these conditions:  
• Power shut off to the condensing unit  
• Condensing unit fan not working  
• Defective head pressure control valves  
• Closed services valves  
• Dirty condensing coils  
• Crimped lines  
3.3  
Liebert Lee-Temp Flood Back Head Pressure Control  
Outdoor condensing unit components for head pressure control include a receiver, heater and  
three-way head pressure control valve. The head pressure control valve operates to maintain a mini-  
mum condensing pressure. During low ambient temperature operation, the valve meters discharge  
gas into the receiver to maintain a discharge pressure operating against the valve dome. This closes  
the condenser port, backing liquid refrigerant into the condenser coil, reducing its area available for  
condensing. A receiver sized to hold the additional charge required to flood the condenser is provided.  
A temperature-compensated heater maintains the liquid refrigerant pressure during Off cycles. A liq-  
uid pressure switch is also installed to turn the heater Off during operation, when the receiver pres-  
sure is high. The heater pressure switch has a cutout of 150 PSIG (1034 kPa) and a cut-in of 100 PSIG  
(690 kPa). The receiver includes a pressure relief valve set for 475 PSIG (3275 kPa).  
25  
       
Operation  
3.4  
Hot Gas Bypass  
3.4.1 Operation  
When applying hot gas bypass with split system condensing units, bypassing discharge gas to the  
compressor suction line offers more flexibility than conventional hot gas bypass to the evaporator  
unit.  
The hot gas bypass valve is installed between the compressor discharge piping and suction piping,  
bypassing the condenser and evaporator coils. The discharge gas mixes with the suction gas, raising  
the suction temperature and pressure and decreasing the mass flow through the evaporator. The  
higher suction temperatures could cause compressor overheating, therefore a separate liquid quench-  
ing valve is provided to mix refrigerant from the system liquid line with the discharge gas before mix-  
ing with the suction gas entering the compressor. (Refer to Figure 13).  
During normal operation, when the evaporator is under full load the hot gas bypass equalizer pres-  
sure will remain high enough to keep the valve port closed. If the evaporator load decreases the evap-  
orator temperature and pressure will drop. When the suction pressure reduces below the hot gas  
bypass valve setting, the hot gas bypass valve opens, diverting some of the refrigerant flow back to  
the compressor suction. The liquid quenching valve bulb senses this increased superheat and opens,  
allowing liquid refrigerant to mix with the discharge gas, desuperheating it.  
Proper mixing of the three refrigerant paths ensures stable operation and system performance. The  
liquid quenching valve bulb must be located downstream of all these connections to control superheat  
at the compressor inlet. Superheat settings for the liquid quenching valve are chosen to maintain con-  
sistency with the system expansion valve. During hot gas bypass operation higher superheats,  
50-60°F (10-15°C), may be observed at the compressor. The liquid-quenching valve is internally  
equalized and superheat is not adjustable.  
To aid in lubricating the compressor, the hot gas bypass solenoid is delayed for 30 seconds on the ini-  
tial call for cooling and de-energized for 30 seconds during every 60 minutes of continuous operation.  
3.4.2 Adjustment  
Upon deciding what evaporator temperature is desired, the following procedure should be used to  
adjust the hot gas bypass valve:  
1. Install the suction and discharge pressure gauge.  
2. Adjust temperature setpoint to call for cooling so that the refrigeration compressor will run  
continuously.  
3. Remove the TOP adjusting nut from the valve.  
4. Insert an Allen wrench in the brass hole at top of valve in adjusting port and turn clockwise if a  
higher evaporator temperature is required. Adjust no more than 1/4 turn at a time. Let the  
system stabilize for 15 minutes before determining if additional adjustments are necessary.  
5. After obtaining the suction pressure required, reinstall cap tightly making sure there are no  
leaks.  
6. Let the system operate for approximately 10 to 15 minutes to make sure the suction pressure is  
within the range desired.  
7. There may be a variation of approximately 3 to 6 PSIG (21 to 41 kPa) on the evaporator due to the  
differential on the hot gas bypass.  
8. Return temperature setpoint to the desired setting.  
26  
     
Operation  
Figure 13 Hot gas bypass diagram  
27  
 
Maintenance  
4.0 MAINTENANCE  
4.1 General  
Access the condensing unit by removing the unit housing panel. Clean the air cooled condenser coil of  
all debris that will inhibit airflow. This can be done with compressed air or with a commercial coil  
cleaner. Check for bent or damaged coil fins and repair as necessary. During winter, do not permit  
snow to accumulate on or around the condensing unit. Check all refrigerant lines and capillaries for  
vibration isolation and support as necessary. Check all refrigerant lines for signs of leaks.  
WARNING  
!
Turn Off power to unit at disconnect switch unless you are performing tests that require  
power. With power and controls energized, unit could begin operating automatically at any  
time.  
WARNING  
panel. To isolate unit for maintenance, turn the unit Off at disconnect switch.  
!
Hazardous voltage will still be present at condenser even with power turned Off at the control  
CAUTION  
!
If condenser power is disconnected for a long period, do not attempt to start the condensing  
unit until 8 hours after restoring power. This allows time for liquid refrigerant to be driven  
out of the compressor. This is especially important at low ambient temperatures.  
4.2  
Compressor Failure  
If a compressor motor burns out, the stator wiring insulation decomposes, forming carbon, water and  
acid. Not only must the compressor be replaced, but the entire refrigeration circuit must be cleaned of  
the harmful contaminants left by the burnout. Successive burnouts of the same system can usually be  
attributed to improper system cleaning.  
WARNING  
under the terms of the warranty.  
!
Damage to a replacement compressor caused by improper system cleaning constitutes abuse  
Before proceeding with a suspected burnout, check all electrical components: fuses, contactors and  
wiring. Check high-pressure switch operation. If a compressor failure has occurred, determine  
whether it is an electrical or mechanical failure. An electrical failure will be indicated by a distinct,  
pungent odor. If a severe burnout has occurred, the oil will be black and acidic. In the case of a  
mechanical failure, there will be no burn odor and the motor will attempt to run.  
4.2.1 Electrical Failure—Burnout  
In the event that there is an electrical failure and a complete burnout of the refrigeration compressor  
motor, the proper procedures must be performed in order to clean the system to remove any acids that  
would cause a future failure.  
NOTE  
Failure to properly clean the system after a compressor motor burnout will void the compressor  
warranty. Follow the manufacturer’s procedure.  
CAUTION  
long rubber gloves in handling contaminated parts.  
!
Avoid touching or contacting the gas and oils with exposed skin. Severe burns may result. Use  
4.2.2 Mechanical Failure  
If a mechanical failure has occurred, the compressor must be replaced.  
28  
         
Maintenance  
4.3  
Compressor Replacement  
Replacement compressors are available from Emerson. They will be shipped in a permanent crate to  
the job site as required by the service contractor.  
Upon shipping a replacement compressor, the service contractor will be billed in full for the compres-  
sor. Credit for warranty replacement compressors will not be issued until the replacement has been  
returned to the factory. The compressor should be returned in the same container used for shipping to  
the job. The possible damage causes or conditions that were found must be recorded by marking the  
compressor return tag.  
CAUTION  
!
Do not loosen any refrigeration or electrical connections before relieving pressure.  
NOTE  
Release of refrigerant to the atmosphere is harmful to the environment. Refrigerant must be  
recycled or discarded in accordance with federal, state, and local regulations.  
1. Disconnect power.  
2. Attach suction and discharge gauges to access fittings.  
3. Recover refrigerant using approved recovery procedures and equipment. Use a filter drier when  
charging the system with recovered refrigerant.  
4. Unsweat refrigerant connections and disconnect electrical connections.  
5. Remove failed compressor.  
6. Install replacement compressor and make all connections.  
7. Pressurize and leak test the system.  
8. Follow manufacturer’s instructions for cleanout kits.  
9. Evacuate the system twice to a minimum 250 microns, breaking the vacuum with dry nitrogen  
each time. The third time, evacuate to 250 microns and verify the above levels are maintained for  
at least one minute after the unit is isolated by a shutoff valve from the vacuum pump.  
10. With the system in a 250 micron or lower vacuum, charge the system with liquid refrigerant  
based on requirements of the evaporator, condensing unit and lines. Refer to 2.5.6 - General  
System Charge Requirements or unit nameplate for system charge requirements.  
11. Apply power and operate system. Check for proper operation. Refer to design pressures in  
29  
 
Maintenance  
4.4  
Field Charge Verification  
An integral sightglass is provided with the receiver to assist in field charge verification. During  
charge verification set the control temperature down to keep the system running. If the system is  
equipped with hot gas bypass, de-energize it by removing power from the hot gas solenoid valve coil.  
To remove power, disconnect the solenoid leads from the unit contactor in the electric box (refer to  
specific unit schematic; reference Figures 7 through 10). When charge verification has been com-  
pleted, replace and secure all wire connections and covers.  
During operation at design ambients (95 or 105°F; 35 or 41°C) the charge level will be above the sight-  
glass in the receiver. If levels are below the sightglass an undercharge condition is likely. If levels are  
above the sightglass and higher discharge pressures than normal are observed an overcharge condi-  
tion may be likely. However, verify that other high discharge pressure causes such as dirty coil and  
restricted airflow are not responsible before removing charge.  
At temperatures below design ambient, refrigerant backs into the condenser coil and the level in the  
receiver will drop below the sightglass. If you are trying to verify charge level at lower ambients, block  
the condenser coil to maintain 230 psig (1585 kPa) discharge pressure to ensure the head pressure con-  
trol valve is closed. At these conditions the charge level should be above the sightglass in the receiver.  
NOTE  
The 5-ton high ambient, 5-ton Quiet-Line and 8-ton models consist of two condenser coils and  
two receivers. When restricting airflow on these units, the coils should be blocked off  
proportionally. If one coil is restricted significantly more than the other, liquid can remain in  
the restricted coil causing lower levels in the receivers. The receiver liquid level should be above  
the sightglasses in both receivers. There may be some variation in charge level between the two  
receiver sightglasses due to piping and assembly variations. When adding charge, determine  
which receiver level is lower and use that sightglass to gauge charge level.  
NOTE  
If no level is visible in the sightglass, add charge until the level is in the middle of the  
sightglass. Check the discharge pressure during this procedure and adjust coil restrictions to  
maintain 230 psig (1585 kPa). Once the charge is in the middle of the sightglass, add  
additional system charge per Table 22. After charging, unblock the coil and allow the unit to  
operate normally. After conditions have stabilized, restrict the coil if required to maintain 230  
psig (1585 kPa) discharge pressure and verify that the charge level is above the sightglass.  
Table 22 Field verification charge  
Model Numbers  
R-407C  
oz (kg)  
60 Hz  
50 Hz  
PFH014A-_L  
PFH020A-_L  
PFH027A-_L  
PFH027A-_H  
PFHZ27A-_L  
PFH037A-_L  
PFH042A-_L  
PFH037A-_H  
PFHZ37A-_L  
PFH042A-_H  
PFHZ42A-_L  
PFH067A-_L  
PFH067A-_H  
PFHZ67A-_L  
PFH013A-_L  
PFH019A-_L  
PFH026A-_L  
PFH026A-_H  
PFHZ26A-_L  
PFH036A-_L  
PFH041A-_L  
PFH036A-_H  
PFHZ36A-_L  
PFH041A-_H  
PFHZ41A-_L  
PFH066A-_L  
PFH066A-_H  
PFHZ66A-_L  
4 (0.11)  
18 (0.51)  
8 (0.23)  
18 (0.51)  
50 (1.42)  
PFH096A-_L  
3-ton circuit  
5-ton circuit  
PFH095A-_L  
3-ton circuit  
5-ton circuit  
18 (0.51)  
18 (0.51)  
30  
   
Troubleshooting  
5.0 TROUBLESHOOTING  
Table 23 Troubleshooting  
Problem  
Cause  
Remedy  
No power to unit  
Check voltage at input terminal block.  
Check for 24VAC ±2VAC at control connections 1 & 2. If  
no voltage, check control setting requires cooling. If there  
Compressor contactor not pulling in is voltage, lockout relay may be energized. Check for  
24VAC at control connections 2 & 3. If there is voltage,  
Unit will not start  
see compressor high-discharge pressure/lockout relay.  
Control voltage circuit breaker (at  
transformer in evaporator module)  
Locate short and reset circuit breaker.  
open  
Control software delays compressor 3 minutes from stop  
to start.  
Short cycle prevention control  
Check for 24VAC ±2VAC at control connections 2 & 3.  
Remove 24VAC signal at Connection 2 by turning indoor  
unit control off, then back on, or by raising the setpoint to  
remove the cab for cooling, then resetting to re-establish  
operation.  
Compressor high discharge  
pressure/ lockout relay  
Insufficient air flow across  
condenser coil  
Check fan operation. Remove debris from coil and air  
inlets.  
High discharge  
pressure  
High refrigerant charge  
Check refrigerant charge.  
Replace if defective.  
Faulty head pressure control valve  
Low discharge pressure  
Compressor rotation in reverse  
direction  
Check for proper power phase wiring to unit and to  
compressor motor.  
Insufficient refrigerant in system  
Plugged filter drier  
Check for leaks; repair and add refrigerant.  
Replace filter drier.  
Low suction pressure /  
compressor cycling  
Reset expansion valve for 10-15°F (5.6 to 8.4°C)  
superheat at evaporator.  
Improper superheat adjustment  
Defective liquid line solenoid valve  
Defective liquid line solenoid valve  
Check valve and coil; replace if necessary.  
Check valve and coil; replace if necessary.  
Check pressure drop across filter drier. Replace filter  
drier.  
Plugged filter drier  
Low compressor  
capacity/ no cooling  
Check for normal system operating pressures. Refer to  
abnormal pressure causes if applicable. Check for leaks.  
Proper refrigerant charge is very important at low ambient  
operation.  
Low refrigerant charge  
Loose compressor or piping  
support  
Tighten clamps.  
Compressor noisy  
Pipe Rattle  
Compressor rotation in reverse  
direction  
Check for proper power phase wiring to unit and to  
compressor motor.  
Loose pipe connections  
Check pipe connections.  
Check for normal system operating pressures. Refer to  
abnormal pressure causes if applicable.  
Compressor running hot Compression ratio too high  
High discharge pressure  
Check for blocked condenser fan or coil.  
Check expansion valve and hot gas bypass valve setting.  
Check liquid quenching valve operation.  
High suction temperature  
Compressor motor  
protectors tripping or  
cycling  
Loose power or control circuit  
wiring connection  
Check all power and control circuit connections.  
Check for motor ground or short. Replace compressor if  
either condition is found.  
Defective motor  
Low line voltage  
Check line voltage and determine location of voltage drop.  
Check for motor winding short or ground.  
Compressor cycles on  
locked rotor  
Compressor motor defective  
Check voltage across all 3 legs at contactor. Correct  
source of problem.  
Single phasing  
Check control panel for welded  
contactor contacts or welded  
overload contacts.  
Motor burnout  
Replace defective components.  
31  
   
Ensuring The High Availability  
Of Mission-Critical Data And Applications.  
Emerson Network Power, the global leader in enabling business-critical  
continuity, ensures network resiliency and adaptability through  
a family of technologies—including Liebert power and cooling  
technologies—that protect and support business-critical systems.  
Liebert solutions employ an adaptive architecture that responds  
to changes in criticality, density and capacity. Enterprises benefit  
from greater IT system availability, operational flexibility and  
reduced capital equipment and operating costs.  
Technical Support / Service  
Web Site  
Monitoring  
800-222-5877  
Outside North America: +800 1155 4499  
Single-Phase & Three-Phase UPS  
800-222-5877  
Outside North America: +800 1155 4499  
Environmental Systems  
800-543-2778  
Outside the United States: 614-888-0246  
Locations  
United States  
1050 Dearborn Drive  
P.O. Box 29186  
Columbus, OH 43229  
Europe  
Via Leonardo Da Vinci 8  
Zona Industriale Tognana  
35028 Piove Di Sacco (PD) Italy  
+39 049 9719 111  
Fax: +39 049 5841 257  
Asia  
29/F, The Orient Square Building  
F. Ortigas Jr. Road, Ortigas Center  
Pasig City 1605  
While every precaution has been taken to ensure the accuracy  
and completeness of this literature, Liebert Corporation assumes no  
responsibility and disclaims all liability for damages resulting from use of  
this information or for any errors or omissions.  
© 2008 Liebert Corporation  
All rights reserved throughout the world. Specifications subject to change  
without notice.  
Philippines  
+63 2 687 6615  
® Liebert is a registered trademark of Liebert Corporation.  
All names referred to are trademarks  
Fax: +63 2 730 9572  
or registered trademarks of their respective owners.  
SL-10059_REV02_10-09  
Emerson Network Power.  
The global leader in enabling Business-Critical Continuity.  
EmersonNetworkPower.com  
AC Power  
Connectivity  
DC Power  
Embedded Computing  
Embedded Power  
Monitoring  
Outside Plant  
Racks & Integrated Cabinets  
Power Switching & Controls  
Services  
Precision Cooling  
Surge Protection  
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.  
©2008 Emerson Electric Co.  

Canon Pixma Inkjet Multifunction Printer Mg3220 User Manual
Canon PIXMA MX882 User Manual
Continental Refrigerator KC69 CT User Manual
Danby DWC172BL User Manual
Fedders C48ACD1VF User Manual
Friedrich SM21 User Manual
Haier AB184FCAHA User Manual
Honda Automobiles 2008 Accord Cargo Management User Manual
Honeywell M847D User Manual
HP Hewlett Packard HP LaserJet Printer 8100 MFP User Manual