Emerson Air Conditioner 1F78H User Manual

CONTENTS  
Installation Instructions for  
Preparations.................................................. 1  
Thermostat Details ........................................ 1  
Removing Old Thermostat ............................ 1  
Mounting and Wiring ..................................... 2  
Check Thermostat Operation ........................ 3  
Configuration Menu ....................................... 4  
Specifications ................................................ 5  
Troubleshooting ............................................ 5  
Heating & Air Conditioning  
1F78H  
Non-Programmable Thermostat  
YOUR THERMOSTAT REPLACES  
PREPARATIONS  
1
Typical System Compatibility Chart  
1F78H  
Assemble tools required as shown below.  
Standard Heat Only Gas or Oil Fired Systems (24 volt)*  
Electronic Ignition Heat Only Two Wire Systems (24 volt)*  
Electronic Ignition Heat Only Gas or Oil Fired Systems (24 volt)*  
Standard Heat/Cool Systems (24 volt)*  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
No  
Heat/Cool Systems Electric Heat (24 volt)*  
Heat Only Electric Heat Systems (24 volt)*  
Cool Only Systems (24 volt)*  
FLAT BLADE SCREWDRIVER  
WIRE CUTTER/STRIPPER  
HAND OR POWER  
DRILL WITH 3/16 INCH  
DRILL BIT, IF NEEDED  
Heat Pump Systems (No Aux or Emergency Heat)*  
Hot Water Zone Heat Only Systems  
SPIRIT LEVEL OR PLUMB BOB AND LINE OPTIONAL—  
THERMOSTAT DOES NOT NEED TO BE LEVEL TO WORK PROPERLY  
Hot Water Zone Heat Only (Three Wire) Systems  
Line Voltage Heating or Baseboard 110/240 Volt Systems  
Millivolt Systems Floor or Wall Furnaces  
12 VDC Mobile Home Application  
No  
No  
No  
No  
Failure to follow and read all instructions carefully  
before installing or operating this control could cause  
personal injury and/or property damage  
Multistage Systems  
No  
Systems Exceeding 30VAC, 1.5 Amp  
No  
* Requires common wire for 24VAC at the thermostat  
THERMOSTAT DETAILS  
REMOVING OLD THERMOSTAT  
2
3
Mounting  
hole  
CAUTION  
!
To prevent electrical shock and/or equipment damage,  
disconnect electrical power to the system at the main  
fuse or circuit breaker until installation is complete.  
Before removing wires from old thermostat’s switching subbase,  
label each wire with the terminal designation it was removed from.  
W
C
RH  
B
RC  
1. Remove Old Thermostat: A standard heat/cool thermostat  
consists of three basic parts:  
a. The cover, which may be either a snap-on or hinge type.  
b. The base, which is removed by loosening all captive screws.  
G
O
Y
Mounting  
hole  
W904  
W905  
W905  
Clip for  
Hydronic  
System  
c. The switching subbase, which is removed by unscrewing  
themountingscrewsthatholditonthewalloradaptorplate.  
ELEC GAS  
2. Shut off electricity at the main fuse box until installation is  
complete. Ensure that electrical power is disconnected.  
3. Remove the front cover of the old thermostat. With wires still  
attached, removewallplatefromthewall.Iftheoldthermostat  
has a wall mounting plate, remove the thermostat and the wall  
mounting plate as an assembly.  
W904  
Clip for  
Celsius Display  
Electric/Gas  
Switch  
Figure 1. Thermostat base  
4. Identify each wire attached to the old thermostat.  
5. Disconnect the wires from the old thermostat one at a time.  
DO NOT LET WIRES FALL BACK INTO THE WALL.  
6. Install new thermostat using the following procedures.  
WHITE-RODGERS  
EMERSON ELECTRIC CO.  
9797 REAVIS ROAD  
ST. LOUIS, MISSOURI 63123-5398  
PART NO. 37-6450A  
Printed in U.S.A.  
0247  
MOUNTING AND WIRING  
CONTINUED FROM SECOND PAGE  
4
JUMPER  
THERMOSTAT  
SYSTEM  
Hot  
WIRE  
Y
C
B
O
G
W
RC  
RH  
THERMOSTAT  
SYSTEM  
Y
C
B
O
G
W
RC  
RH  
Cooling  
System Relay System  
Fan  
Heating  
24 VAC  
120 VAC  
Neutral  
NOTE  
For Heat only,  
attach to RH and W  
Fan  
Relay  
Heating  
System  
Hot  
HEATING  
TRANSFORMER  
24 VAC  
120 VAC  
Neutral  
Hot  
TRANSFORMER  
24 VAC  
120 VAC  
Neutral  
Figure 2. Typical wiring diagram for  
heat only, 4-wire, single transformer systems  
COOLING TRANSFORMER  
Figure 5. Typical wiring diagram for  
heat/cool, 6-wire, two-transformer systems  
JUMPER  
WIRE  
THERMOSTAT  
Y
C
B
O
G
W
RC  
RH  
SYSTEM  
JUMPER  
WIRE  
JUMPER  
WIRE  
THERMOSTAT  
SYSTEM  
Cooling  
System Relay  
Fan  
Y
C
B
O
G
W
RC RH  
Hot  
24 VAC  
120 VAC  
Neutral  
Reversing Compressor Fan  
Valve*  
Contactor Relay  
Hot  
TRANSFORMER  
24 VAC  
120 VAC  
Neutral  
Figure 3. Typical wiring diagram for  
cool only, 4-wire, single transformer systems  
* Reversing valve is energized when the  
system switch is in the COOL position  
TRANSFORMER  
Figure 6. Typical wiring diagram for heat pump  
with reversing valve energized in COOL  
NOTE  
RED jumper wire (provided with thermostat) must be  
connected between thermostat RH and RC terminals  
for proper thermostat operation with this system.  
JUMPER  
WIRE  
JUMPER  
WIRE  
JUMPER  
WIRE  
THERMOSTAT  
SYSTEM  
THERMOSTAT  
SYSTEM  
Y
C
B
O
G
W
RC RH  
Y
C
B
O
G
W
RC RH  
Cooling  
System Relay  
Fan  
Heating  
System  
Reversing Compressor Fan  
Valve*  
Contactor Relay  
Hot  
Hot  
24 VAC  
120 VAC  
Neutral  
24 VAC  
120 VAC  
Neutral  
* Reversing valve is energized when the  
system switch is in the HEAT position  
TRANSFORMER  
TRANSFORMER  
Figure 7. Typical wiring diagram for heat pump  
with reversing valve energized in HEAT  
Figure 4. Typical wiring diagram for  
heat/cool, 5-wire, single transformer systems  
CHECK THERMOSTAT OPERATION  
5
This thermostat has a time delay between cooling cycles to allow  
the head pressure in the compressor to stabilize. If the tempera-  
ture is adjusted to call for cool within 5 minutes of the last cycle the  
snowflake icon will blink indicating the thermostat is locked out.  
After 3 to 5 minutes, the compressor will start and the snowflake  
icon will stop flashing. This helps prevent the compressor from  
cycling too quickly and is normal operation for the thermostat.  
NOTE  
To prevent static discharge problems, touch side of ther-  
mostattoreleasestaticbuild-upbeforetouchinganykeys.  
If at any time during testing your system does not operate  
properly, contact a qualified serviceperson.  
Fan Operation  
If your system does not have a G terminal connection, skip to  
Heating System.  
1. Move SYSTEM switch to COOL position.  
2. Press  
to adjust thermostat setting below room tempera-  
ture. The blower should come on immediately on high speed,  
followed by cold air circulation  
1. Turn on power to the system.  
2. Move fan switch to ON position. The blower should begin to  
3. Press  
to adjust temperature setting above room tem-  
operate.  
perature. The cooling system should stop operating.  
3. Move fan switch to AUTO position. The blower should stop  
Heating System  
immediately.  
1. Move SYSTEM switch to HEAT position. If the heating system  
Cooling System  
has a standing pilot, be sure to light it.  
2. Press  
to adjust thermostat setting above room tempera-  
ture. The heating system should begin to operate.  
CAUTION  
!
3. Press  
to adjust temperature setting below room tem-  
To prevent compressor and/or property damage, if the  
outdoortemperatureisbelow50°F, DONOToperatethe  
cooling system.  
perature. The heating system should stop operating.  
CHECK THERMOSTAT OPERATION  
CONTINUED FROM THIRD PAGE  
5
1
2
Before you begin using your thermostat, you should be familiar  
with its features and with the display and the location and  
operation of the thermostat buttons. Your thermostat consists of  
two parts: the thermostat cover and the base. To remove the  
cover, gently pull it straight out from the base. To replace the  
cover, line up the cover with the base and press gently until the  
cover snaps onto the base.  
WHITE-RODGERS  
FAN  
SYSTEM  
The Thermostat Buttons and Switches  
ON AUTO COOL OFF HEAT  
1
2
3
4
(Up arrow) Raises temperature setting.  
(Down arrow) Lowers temperature setting.  
3
4
FAN switch (ON, AUTO).  
SYSTEM switch (COOL, OFF, HEAT).  
The Display  
6
7
5
is displayed when the SYSTEM switch is in the HEAT  
position.  
is displayed (non-flashing) when the SYSTEM  
is displayed (flashing)  
switch is in the COOL position.  
5
when the compressor is in lockout mode.  
6
7
Displays current temperature.  
Figure 8. Thermostat display, buttons, and switches  
Displays currently set temperature (this is blank when  
SYSTEM switch is in the OFF position).  
CONFIGURATION MENU  
Operating Features  
6
Now that you are familiar with the thermostat buttons and display,  
read the following information to learn about the many features of  
the thermostat.  
The configuration menu allows you to set certain thermostat oper-  
ating characteristics to your system or personal requirements.  
SIMULTANEOUS HEATING/COOLING SETPOINT  
STORAGE — You can enter both your heating and cooling  
setpoints at the same time. There is no need to re-enter the  
thermostat at the beginning of each season.  
With the system switch in “OFF” mode, press  
at the same time to enter the configuration menu. The display will  
show the first item in the configuration menu.  
and  
keys  
The configuration menu table summarizes the configuration  
options. An explanation of each option follows.  
TEMPERATURE SETTING — Press  
or  
until the  
display shows the temperature you want. The thermostat will  
keep the room temperature at the selected temperature.  
Press  
and  
together momentarily to change to the next  
menu item. To exit the menu, change the system switch from OFF  
to HEAT or COOL. If no action is taken within fifteen minutes, the  
thermostat will revert to normal operation.  
°F/°C CONVERTIBILITY — The factory default setting is  
Fahrenheit. If you need Celsius temperature setting, go to  
menu mode and change the fifth option to C (see configura-  
tion menu, page 5).  
2) Select FA or SL (Fast or Slow) Heating Cycle Rate—The  
FA setting is frequently used for gas, oil or electric heat. The  
SL setting produces a longer heating cycle which is normally  
for hot water or steam (hydronic) systems. Both settings  
produce very accurate temperature control and can be set to  
your personal preference. FA cycles the system just under  
1°F and the SL setting cycles at approximately 1.5F°.  
TEMPERATURE DISPLAY ADJUSTMENT — Your new  
thermostathasbeenaccuratelysetinourfactory. However,if  
you wish, you may adjust your new thermostat temperature  
display to match your old thermostat. This can be accom-  
plished(withina±4° range)bygoingintothemenumode(see  
configuration menu, page 5).  
3) Not Available  
4) Select Compressor Lockout LOC OFF or ON—Selecting  
LOC ON will cause the thermostat to wait 5 minutes before  
turning on the compressor if the heating and cooling system  
loses power. It will also wait 5 minutes minimum between  
cooling cycles. This is intended to help protect the compres-  
sor from short cycling. Some newer compressors already  
Configuration Menu  
Step  
Displayed (Factory Default)  
Comments  
Press Button(s)  
Press  
or  
to select:  
1
System switch must be OFF to configure thermostat  
Set system switch  
to OFF  
2
3
4
5
6
7
(FA)  
d-L (ON)  
LOC (OFF)  
0 HI (0)  
(F)  
Select FA or SL (Fast or Slow) heating cycle rate  
N/A  
and  
and  
and  
and  
and  
SL  
OFF  
ON  
Select compressor lockout OFF or ON  
Select temperature display adjustment higher or lower  
Select temperature display to F or C  
Returns to normal operation  
4 LO to 4 HI  
C
Move system  
switch from OFF  
to HEAT or COOL  
* Press  
and  
simultaneously to advance to next item  
have a time delay built in and do not require this feature. Your  
compressor manufacturer can tell you if the feature is already  
present in their system. When the compressor time delay  
SPECIFICATIONS  
ELECTRICAL DATA  
7
Electrical Rating:  
occurs it will flash the  
the compressor.  
for about five minutes then turn on  
20 to 30 VAC 50/60 Hz.  
0.05 to 1.2 Amps (Load per terminal)  
1.5 Amps Maximum Total Load (All terminals combined)  
5) Select Temperature Display Adjustment 4 LO to 4 HI—  
Allows you to adjust the room temperature display 4° higher  
or lower. Your thermostat was accurately calibrated at the  
factory but you have the option to change the display tem-  
perature to match your previous thermostat.  
THERMAL DATA  
Setpoint Temperature Range: 45°F to 90°F (7°C to 32°C)  
Operating Ambient Temperature Range: 32°F to 105°F  
Operating Humidity Range: 0 to 90% RH (non-condensing)  
Shipping Temperature Range: -40°F to 150°F  
6) Select F° or C° Readout—Changes the display readout to  
Centigrade or Fahrenheit as required.  
TROUBLESHOOTING  
8
Symptom  
Possible Cause  
Corrective Action  
No Heat/No Cool/No Fan  
(common problems)  
1. Blown fuse or tripped circuit breaker.  
2. Furnace power switch to OFF.  
Replace fuse or reset breaker.  
Turn switch to ON.  
3. Furnace blower compartment door or  
panel loose or not properly installed.  
Replace door panel in proper position to engage  
safety interlock or door switch.  
No Heat  
1. Pilot light not lit.  
Re-light pilot.  
2. System Switch not set to Heat.  
Set System Switch to Heat and raise temperature  
above room temperature.  
3. Loose connection to thermostat or system.  
Verify thermostat and system wires are securely  
attached.  
4. Furnace Lock-Out Condition. Heat may also  
be intermittent.  
Many furnaces have safety devices that shut down  
when a lock-out condition occurs. If the heat works  
intermittently contact the furnace manufacturer or  
local service person for assistance.  
5. Heating system requires service or  
thermostat requires replacement.  
Diagonistic: Set System Switch to Heat and raise  
the setpoint above room temperature. Within a few  
seconds the thermostat should make a soft click  
sound. This sound usually indicates the thermo-  
stat is operating properly. If the thermostat does  
not click on, contact your heating and cooling  
service person or place of purchase for a  
replacement. If the thermostat clicks, contact the  
furnace manufacturer or a service person to verify  
the heating is operating correctly.  
TROUBLESHOOTING  
8
Symptom  
Possible Cause  
Corrective Action  
No Cool  
1. System Switch not set to Cool.  
Set System Switch to Cool and lower temp below  
room temp.  
2. Loose connection to thermostat or system.  
Verify thermostat and system wires are securely  
attached.  
3. Cooling system requires service or  
thermostat requires replacement.  
Same procedure as diagnostic for No Heat  
condition except set the thermostat to Cool and  
lower the setpoint below the room temperature.  
There may be up to a five minute delay before the  
thermostat clicks in Cooling.  
Heat, Cool or Fan Runs Constantly.  
1. Possible short in wiring.  
Check each wire connection to verify they are not  
shorted or touching together. No bare wire should  
stick out from under terminal screws. If the  
condition persists the manufacturer of your  
system or service person can instruct you on how  
to test the Heat/Cool system for correct operation.  
If the system operates correctly, replace the  
thermostat.  
2. Possible short in thermostat.  
3. Possible short in heat/cool/fan system.  
4. Fan Switch set to Fan On.  
Furnace Cycles Too Fast or Too Slow  
(narrow or wide temperature swing)  
1. The location of the thermostat and/or the  
size of the Heating System may be  
influencing the cycle rate.  
Digital thermostats normally provide precise  
temperature control and may cycle faster than  
some older mechanical models. A faster cycle  
rate means the unit turns on and off more  
frequently but runs for a shorter time so there is  
no increase in energy use. If you would like to  
increase the cycle time, go to menu mode as  
mentioned in the instructions for Hydronic Heating  
Systems. It is not possible to shorten the cycle  
time. If an acceptable cycle rate is not achieved as  
received or by changing cycle time from FAST to  
SLOW on the menu mode contact a local  
service person for additional suggestions.  
Cooling Cycles Too Fast or Too Slow  
(narrow or wide temperature swing)  
1. The location of the thermostat and the size  
of the Cooling System can influence the  
cycle rate.  
The cycle rate for cooling is fixed and can not be  
adjusted. Contact a local service person for  
suggestions.  
Thermostat Setting and Thermostat  
Thermometer Disagree  
1. Thermostat thermometer setting requires  
adjustment.  
The thermometer can be adjusted +/- 4 degrees.  
See Temperature Display Adjustment in the  
Operation section.  
Blank Display and/or Keypad  
Not Responding  
1. Thermostat loss of power  
2. Voltage spike or static discharge.  
Check possible blown fuse or tripped breaker.  
Turn the system power off. Wait for 5 minutes and  
turn the power on.  

ADTRAN NIU3 User Manual
Briggs Stratton 80400 User Manual
Cannon All in One Printer C5051 User Manual
Carrier MODULINE 37HS User Manual
Danby DESIGNER DPAC1011BL User Manual
Friedrich MS24Y3F User Manual
Friedrich WS13B30B User Manual
Honda Automobiles Bed Extender 08L26 SJC 1000 81 User Manual
Honda Automobiles Plusone Console 4521011B User Manual
HP Hewlett Packard XU700 User Manual