Carrier SINGLE PACKAGED ELECTRIC COOLING UNITS 50GX User Manual

50GS, 50GX  
Single Packaged Electric Cooling Units  
Installation, Start-Up, and Operating Instructions  
50GS Sizes 018-060, 50GX Sizes 024-060  
NOTE: Read the entire instruction manual before starting the  
installation.  
METERING DEVICE — ACUTROL DEVICE .............25  
LIQUID LINE STRAINER ..............................................25  
This symbol indicates a change since the last issue.  
Troubleshooting............................................................................25  
Start-Up Checklist........................................................................25  
TABLE OF CONTENTS  
NOTE TO INSTALLER — Before the installation, READ THESE  
INSTRUCTIONS CAREFULLY AND COMPLETELY. Also,  
make sure the User’s Manual and Replacement Guide are left with  
the unit after installation.  
SAFETY CONSIDERATIONS.....................................................1  
Introduction ....................................................................................2  
RECEIVING AND INSTALLATION ..........................................2  
Check Equipment......................................................................2  
IDENTIFY UNIT ................................................................2  
INSPECT SHIPMENT........................................................2  
Provide Unit Support................................................................2  
ROOF CURB.......................................................................2  
SLAB MOUNT ...................................................................2  
GROUND MOUNT ............................................................2  
Provide Clearances....................................................................2  
Field Fabricate Ductwork.........................................................2  
Rig and Place Unit....................................................................2  
INSPECTION ......................................................................3  
INSTALLATION ................................................................3  
Connect Condensate Drain.......................................................7  
Install Duct Connections ..........................................................7  
CONFIGURING UNITS FOR DOWNFLOW (VERTI-  
CAL) DISCHARGE............................................................8  
Install Electrical Connection ....................................................9  
HIGH-VOLTAGE CONNECTIONS................................10  
SPECIAL PROCEDURES FOR 208-V OPERATION ...10  
CONTROL VOLTAGE CONNECTIONS.......................10  
STANDARD CONNECTION ..........................................10  
TRANSFORMER PROTECTION....................................13  
SAFETY CONSIDERATIONS  
Installation and servicing of air-conditioning equipment can be  
hazardous due to system pressure and electrical components. Only  
trained and qualified personnel should install, repair, or service  
air-conditioning equipment.  
Untrained personnel can perform basic maintenance functions of  
cleaning coils and filters. All other operations should be performed  
by trained service personnel. When working on air-conditioning  
equipment, observe precautions in the literature, tags, and labels  
attached to the unit, and other safety precautions that may apply.  
Follow all safety codes. Wear safety glasses and work gloves. Use  
quenching cloth for unbrazing operations. Have fire extinguisher  
available for all brazing operations. Consult a qualified installer or  
service agency for information or assistance. The qualified in-  
staller or agency must use only factory-authorized kits or acces-  
sories when modifying this product.  
PRE-START-UP ..........................................................................13  
START-UP...................................................................................14  
CHECK FOR REFRIGERANT LEAKS..........................14  
START UP COOLING SECTION AND MAKE ADJUST-  
MENTS..............................................................................14  
CHECKING COOLING CONTROL OPERATION .......14  
CHECKING AND ADJUSTING REFRIGERANT  
CHARGE...........................................................................14  
INDOOR AIRFLOW AND AIRFLOW ADJUST-  
MENTS..............................................................................18  
For 208/230V.....................................................................18  
FOR 460-V GE MOTORS................................................18  
COOLING SEQUENCE OF OPERATION.....................18  
MAINTENANCE.........................................................................18  
AIR FILTER......................................................................22  
EVAPORATOR BLOWER AND MOTOR.....................22  
CONDENSER COIL, EVAPORATOR COIL, AND CON-  
DENSATE DRAIN PAN..................................................24  
CONDENSER FAN ..........................................................24  
ELECTRICAL CONTROLS AND WIRING ..................24  
REFRIGERANT CIRCUIT...............................................24  
EVAPORATOR AIRFLOW.............................................25  
C99001  
Fig. 1—Unit 50GS and 50GX  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book  
Tab 6 8  
1
6
PC 101  
Catalog No. 535–00130  
Printed in U.S.A.  
Form 50GS,GX-4SI  
Pg 1  
9–03  
Replaces: 50GS,GX-3SI  
REQUIRED CLEARANCE FOR OPERATION AND SERVICING  
REQUIRED CLEARANCE TO COMBUSTIBLE MATL.  
INCHES [mm]  
INCHES [mm]  
EVAP. COIL ACCESS SIDE............................................................36.00 [914.0]  
POWER ENTRY SIDE....................................................................42.00 [1066.8]  
(EXCEPT FOR NEC REQUIREMENTS)  
UNIT TOP.......................................................................................48.00 [1219.2]  
SIDE OPPOSITE DUCTS ..............................................................36.00 [914.0]  
DUCT PANEL .................................................................................12.00 [304.8]  
TOP OF UNIT...................................................................................14.00 [355.6]  
DUCT SIDE OF UNIT.........................................................................2.00 [50.8]  
SIDE OPPOSITE DUCTS ................................................................14.00 [355.6]  
BOTTOM OF UNIT.............................................................................0.50 [12.7]  
ELECTRIC HEAT PANEL .................................................................36.00 [914.4]  
*
NEC. REQUIRED CLEARANCES.  
*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 304.8 [12.00] FROM  
WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE.  
INCHES [mm]  
BETWEEN UNITS, POWER ENTRY SIDE....................................42.00 [1066.8]  
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00 [914.0]  
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER  
GROUNDED SURFACES, POWER ENTRY SIDE.........................42.00 [1066.8]  
C99007  
CENTER OF GRAVITY  
IN. (MM)  
UNIT HEIGHT  
IN. (MM)  
”A”  
UNIT WEIGHT  
UNIT  
ELECTRICAL CHARACTERISTICS  
lb.  
kg  
X
Y
Z
50GS018  
50GS024  
50GS030  
50GS036  
50GS042  
50GX024  
50GX030  
50GX036  
208/230-1-60  
208/230-1-60  
208/230-1-60, 208/230-3-60  
208/230-1-60, 208/230-3-60, 460-3-60  
208/230-1-60, 208/230-3-60, 460-3-60  
208/230-1-60  
254  
260  
258  
268  
294  
270  
291  
299  
115.2  
117.9  
117.0  
121.6  
133.3  
122.5  
132.0  
135.6  
35.02 (889.5)  
35.02 (889.5)  
35.02 (889.5)  
37.02 (940.3)  
35.02 (889.5)  
37.02 (940.3)  
39.02 (991.1)  
35.02 (889.5)  
20.0 (508.0)  
19.0 (482.6)  
19.0 (482.6)  
20.0 (508.0)  
19.0 (482.6)  
18.5 (469.9)  
19.5 (495.3)  
19.5 (495.3)  
13.0 (330.2)  
13.0 (330.2)  
14.0 (355.6)  
14.0 (355.6)  
14.0 (355.6)  
14.5 (368.3)  
15.5 (393.7)  
15.25 (387.4)  
15.0 (381.0)  
15.0 (381.0)  
15.0 (381.0)  
13.0 (330.2)  
13.0 (330.2)  
16.0 (406.4)  
17.6 (447.0)  
16.5 (419.1)  
208/230-1-60, 208/230-3-60  
208/230-1-60, 208/230-3-60, 460-3-60  
Fig. 2— 50GS018-042 and 50GX024-036 Unit Dimensions  
of wear, structural deformation, or cracks. Particular attention  
should be paid to excessive wear at hoist hooking points and load  
support areas. Brackets or straps showing any kind of wear in these  
areas must not be used and should be discarded.  
Accessory lifting kit is only to be used with Small Packaged  
units which have a composite base pan with molded rigging  
holds.  
INSTALLATION  
INSPECTION  
1. Position the lifting bracket assembly around the base of the  
unit. Leave the top shipping skid on the unit to act as a  
spreader bar. Be sure the strap does not twist.  
Prior to initial use, and at monthly intervals, all rigging brackets  
and straps should be visually inspected for any damage, evidence  
3
REQUIRED CLEARANCE FOR OPERATION AND SERVICING  
REQUIRED CLEARANCE TO COMBUSTIBLE MATL.  
INCHES [mm]  
INCHES [mm]  
EVAP. COIL ACCESS SIDE............................................................36.00 [914.0]  
POWER ENTRY SIDE....................................................................36.00 [914.0]  
(EXCEPT FOR NEC REQUIREMENTS)  
UNIT TOP.......................................................................................48.00 [1219.2]  
SIDE OPPOSITE DUCTS ..............................................................36.00 [914.0]  
DUCT PANEL .................................................................................12.00 [304.8]  
TOP OF UNIT...................................................................................14.00 [355.6]  
DUCT SIDE OF UNIT.........................................................................2.00 [50.8]  
SIDE OPPOSITE DUCTS ................................................................14.00 [355.6]  
BOTTOM OF UNIT.............................................................................0.50 [12.7]  
ELECTRIC HEAT PANEL .................................................................36.00 [914.4]  
*
NEC. REQUIRED CLEARANCES.  
*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 304.8 [12.00] FROM  
WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE.  
INCHES [mm]  
BETWEEN UNITS, POWER ENTRY SIDE....................................42.00 [1066.8]  
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00 [914.0]  
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER  
GROUNDED SURFACES, POWER ENTRY SIDE.........................42.00 [1066.8]  
C99006  
CENTER OF GRAVITY  
IN. (MM)  
UNIT HEIGHT  
IN. (MM)  
”A”  
UNIT WEIGHT  
UNIT  
ELECTRICAL CHARACTERISTICS  
lb.  
kg  
X
Y
Z
50GS048  
50GS060  
50GX042  
50GX048  
50GX060  
208/230-1-60, 208/230-3-60, 460-3-60  
208/230-1-60, 208/230-3-60, 460-3-60  
208/230-1-60, 208/230-3-60, 460-3-60  
208/230-1-60, 208/230-3-60, 460-3-60  
208/230-1-60, 208/230-3-60, 460-3-60  
324  
389  
321  
326  
399  
145  
176  
146  
148  
181  
38.98 (990.2)  
38.98 (990.2)  
38.98 (990.2)  
38.98 (990.2)  
42.98 (1091.1)  
20.0 (508.0)  
19.0 (482.6)  
20.5 (520.7)  
19.5 (495.3)  
20.5 (520.7)  
17.0 (432.0)  
16.0 (406.0)  
16.75 (425.5)  
17.6 (447.6)  
16.2 (412.8)  
17.0 (432.0)  
17.0 (432.0)  
16.6 (421.6)  
18.0 (457.2)  
17.6 (447.0)  
Fig. 3— 50GS048–060 and 50GX042–060 Unit Dimensions  
2. Place each of the four (4) metal lifting brackets into the  
rigging holds in the composite pan.  
5. Attach safety straps directly to the field supplied rigging straps  
or clevis clip. Do not attach the safety straps to the lifting  
brackets.  
3. Tighten the ratchet strap unit tight. Lifting brackets should be  
secure in the rigging holds.  
6. Use the top of the unit as a spreader bar to prevent the rigging  
straps from damaging the unit. If the wood top is not available,  
use a spreader bar of sufficient length to not damage the unit.  
4. Attach the clevis or hook of sufficient strength to hole in the  
lifting bracket (See Fig. 6).  
4
HVACunit  
base  
HVAC unit  
base  
Gask eting  
inner flange*  
Screw  
(NOTE A)  
Screw  
(NOTE A)  
Gasketing  
inner flange*  
*Gasketing  
outer flange  
*Gasketing  
outer flange  
Wood nailer*  
Wood nailer*  
Flashing field  
supplied  
Flashing field  
supplied  
Roofcurb*  
Roofcurb*  
Insulation(field  
supplied)  
Insulation(field  
supplied)  
Roofing material  
field supplied  
Roofing material  
field supplied  
Duct wo rk  
field supplied  
Duct wo rk  
field supplied  
Cant strip  
field supplied  
Cant strip  
field supplied  
Roof  
Roof  
*Provided with roofcurb  
*Provided with roofcurb  
Roof Curb for Small Cabinet  
Roof Curb for Large Cabinet  
Note A:When unit mounting screw is use,d  
retainer bracke t must also be used.  
Note A:When unit mounting screw is use,d  
retainer bracket must also be used.  
Supply opening  
(B x C)  
BTyp.  
D
CTyp.  
445/16"  
R/A  
S/A  
A
Gasket around  
duct  
Short  
Support  
Insulated  
deck pan  
Gasket around  
outer edge  
Insulated  
deck pan  
Long  
Support  
Return opening  
(B X C)  
C00076  
A
B
C
D
UNIT SIZE  
ODS CATALOG NUMBER  
IN. (MM)  
IN. (MM)  
IN. (MM)  
IN. (MM)  
CPRFCURB006A00  
CPRFCURB007A00  
CPRFCURB008A00  
CPRFCURB009A00  
8 (203)  
14 (356)  
8 (203)  
11(279)  
11(279)  
16-3/16 (411)  
16-3/16 (411)  
16-1/2 (419)  
16-1/2 (419)  
17-3/8 (441)  
17-3/8 (441)  
28-3/4 (730)  
28-3/4 (730)  
40-1/4 (1022)  
40-1/4 (1022)  
50GS018-042  
50GS048-060  
50GX024-036  
50GX042-060  
14 (356)  
NOTES:  
1. Dimensions in ( ) are in millimeters.  
2. Roof curb is made of 16-gage steel.  
3. Table lists only the dimensions per part number that have changed  
4. Insulated panels: 1-in. thick fiberglass 1 lb. density.  
Fig. 4A— Roof Curb Dimensions  
5
1
4
2
3
y
x
C00071  
50GS  
036  
62  
50GX  
CORNER #  
018  
58  
024  
60  
030  
59  
042  
76  
048  
69  
060  
84  
024  
76  
030  
84  
036  
85  
042  
71  
048  
78  
060  
85  
1
2
47  
50  
48  
50  
50  
45  
54  
49  
60  
60  
55  
56  
66  
3
55  
56  
56  
58  
71  
88  
106  
145  
389  
57  
61  
64  
85  
80  
108  
140  
399  
4
94  
94  
95  
98  
97  
122  
324  
88  
86  
90  
110  
321  
112  
326  
TOTAL WEIGHT  
254  
260  
258  
268  
294  
270  
291  
299  
Fig. 4B—50GS and 50GX Unit Corner Weights  
A
C
MAXIMUM ALLOWABLE  
DIFFERENCE (in.)  
B
A-B  
1/4  
B-C  
1/4  
A-C  
1/4  
C99065  
Fig. 5A—Unit Leveling Tolerances  
OPTIONAL  
RETURN  
AIR  
OPTIONAL  
SUPPLY  
AIR  
OPENING  
OPENING  
2"  
EVAP. COIL  
COND. COIL  
C99096  
Fig. 5B—Slab Mounting Detail  
6
914-137"  
(36"-54")  
“A”  
“B”  
DETAIL A  
SCALE 0.250  
TIGHTEN STRAPPING SECURELY  
WITH TENSION BUCKLE  
INSTALL SAFETY STRAPS TO  
RIGGING CLEVIS AT 4 RIGGING BRACKETS  
PLACE RIGGING BRACKET ASSEMBLY IN 4  
RIGGING HOLES AND INSTALL TIE DOWN STRAP  
AROUND PERIMETER OF UNIT AND THROUGH  
SPACE IN BRACKET ASSEMBLY  
SEE DETAIL A  
C99066  
MAXIMUM WEIGHT  
A
B
SIZE  
lb.  
kg  
in.  
mm.  
in.  
mm.  
UNIT 50GS  
018  
024  
030  
036  
042  
048  
060  
276  
282  
280  
290  
316  
346  
411  
125.2  
127.9  
127.0  
131.5  
143.3  
156.9  
186.4  
20  
19  
19  
20  
19  
508.0  
482.6  
482.6  
508.0  
482.6  
508  
13  
13  
14  
14  
14  
17  
16  
330.2  
330.2  
355.6  
355.6  
355.6  
431.8  
406.4  
20  
19  
482.6  
UNIT 50GX  
18.5  
19.5  
19.5  
20.5  
19.5  
20.5  
024  
030  
036  
042  
048  
060  
292  
313  
321  
343  
348  
421  
132.5  
142.5  
145.6  
155.6  
157.9  
191.0  
469.9  
495.3  
495.3  
520.7  
495.3  
520.7  
14.50  
15.50  
15.25  
16.75  
17.62  
16.25  
368.3  
393.7  
387.4  
425.5  
447.6  
412.8  
Fig. 6—Suggested Rigging  
Do not undersize the tube. Pitch the drain tube downward at a  
slope of at least 1-in. for every 10 ft. of horizontal run. Be sure to  
check the drain tube for leaks. Prime trap at the beginning of the  
cooling season start-up.  
Lifting point should be directly over the center of gravity for  
the unit.  
Step 7—Install Duct Connections  
Step 6—Connect Condensate Drain  
The unit has duct flanges on the supply- and return-air openings on  
the side and bottom of the unit. For downshot applications the  
ductwork can be connected to the roof curb. See Fig. 2 & 3 for  
connection sizes and locations.  
NOTE: When installing condensate drain connection be sure to  
comply with local codes and restrictions.  
Models 50GS and 50GX dispose of condensate water through a  
3/4 in. NPT fitting which exits through the base on the evaporator  
coil access side. See Fig. 2 & 3 for location.  
IMPORTANT: Use flexible connectors between ductwork and  
unit to prevent transmission of vibration. Use suitable gaskets to  
ensure weathertight and airtight seal. When electric heat is  
installed, use fire proof canvas (or similar heat resistant material)  
connector between ductwork and unit discharge connection. If  
flexible duct is used, insert a sheet metal sleeve inside duct. Heat  
resistant duct connector (or sheet metal sleeve) must extend 24-in.  
from the unit discharge connection flange into the ductwork.  
Condensate water can be drained directly onto the roof in rooftop  
installations (where permitted) or onto a gravel apron in ground-  
level installations. Install a field-supplied condensate trap at end of  
condensate connection to ensure proper drainage. Make sure that  
the outlet of the trap is at least 1 in. lower than the drainpan  
condensate connection to prevent the pan from overflowing (See  
Fig. 7). When using a gravel apron, make sure it slopes away from  
the unit.  
Connect a drain tube using a minimum of 3/4 -in. PVC or 3/4 -in.  
copper pipe (all field-supplied) at the outlet end of the 2-in. trap.  
7
Table 1—Physical Data—Unit 50GS  
UNIT SIZE  
018  
1-1/2  
254  
024  
2
260  
030  
2-1/2  
258  
036  
3
268  
042  
3-1/2  
294  
048  
4
324  
Scroll  
060  
5
389  
NOMINAL CAPACITY (ton)  
OPERATING WEIGHT (lb.)  
COMPRESSOR  
Reciprocating  
Reciprocating  
REFRIGERANT (R-22)  
Quantity (lb.)  
2.6  
3.5  
3.65  
4.4  
6.4  
5.1  
7.4  
Accurater  
.032  
REFRIGERANT METERING DEVICE  
Orifice ID (in.)  
.034  
.034  
.034  
.034  
.032  
.030  
CONDENSER COIL  
Rows...Fins/in.  
Face Area (sq. ft.)  
1...17  
6.1  
1...17  
9.1  
1...17  
9.1  
1...17  
10.9  
1...17  
9.1  
1...17  
12.3  
2...17  
12.3  
CONDENSER FAN  
Nominal Cfm  
Diameter  
2000  
22  
1/8 (825)  
2400  
22  
1/8 (825)  
2400  
22  
1/8 (825)  
3000  
18  
1/4 (1100)  
3000  
22  
1/4 (1100)  
3600  
22  
1/4 (1100)  
3600  
22  
1/4 (1100)  
Motor Hp (Rpm)  
EVAPORATOR COIL  
Rows...Fins/in.  
Face Area (sq. ft.)  
2...15  
3.1  
2...15  
3.1  
2...15  
3.7  
3...15  
3.06  
4...15  
3.06  
3...15  
4.7  
4...15  
4.7  
EVAPORATOR BLOWER  
Nominal Airflow (Cfm)  
Size (in.)  
600  
800  
1000  
10x10  
1/4 (1075)  
1200  
11x10  
1/2 (1075)  
1400  
11x10  
3/4 (1075)  
1600  
11x10  
3/4 (1075)  
2000  
11x10  
1.0 (1100)  
10x10  
10x10  
1/4 (825)  
1/4 (1075)  
Motor HP (RPM)  
RETURN-AIR FILTERS (in.)*  
Throwaway  
20x20  
20x20  
20x20  
20x24  
20x24  
24x30  
24x30  
* Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300  
ft./min. for throwaway type or 450 ft./min. for high-capacity type. Air filter pressure drop for non-standard filters must not exceed 0.08 in. wg.  
Table 2—Physical Data—Unit 50GX  
UNIT SIZE  
024  
2
270  
030  
2-1/2  
291  
036  
3
299  
042  
3-1/2  
321  
048  
4
326  
060  
5
399  
NOMINAL CAPACITY (ton)  
OPERATING WEIGHT (lb.)  
COMPRESSOR  
Scroll  
REFRIGERANT (R-22)  
Quantity (lb.)  
3.7  
4.4  
5.2  
7.6  
8.3  
8.1  
Accurater  
REFRIGERANT METERING DEVICE  
Orifice ID (in.)  
.034  
.030  
.032  
.034  
.034  
.032  
CONDENSER COIL  
Rows...Fins/in.  
Face Area (sq. ft.)  
1...17  
10.8  
1...17  
12.7  
2...17  
9.1  
2...17  
9.1  
2...17  
12.3  
2...17  
16.4  
CONDENSER FAN  
Nominal Cfm  
2350  
22  
1/8 (825)  
2350  
22  
1/8 (825)  
2350  
22  
1/8 (825)  
3300  
22  
1/4 (1100)  
3300  
22  
1/4 (1100)  
3300  
22  
1/4 (1100)  
Diameter (in.)  
Motor Hp (Rpm)  
EVAPORATOR COIL  
Rows...Fins/in.  
Face Area (sq. ft.)  
3...15  
3.1  
3...15  
3.1  
3...15  
3.7  
3...15  
4.7  
4...15  
4.7  
4...15  
4.7  
EVAPORATOR BLOWER  
Nominal Airflow (Cfm)  
Size (in.)  
800  
1000  
10x10  
1/4 (1075)  
1200  
11x10  
1/2 (1075)  
1400  
11x10  
3/4 (1075)  
1600  
11x10  
3/4 (1075)  
1750  
11x10  
1.0 (1040)  
10x10  
1/4 (1075)  
Motor Hp (RPM)  
RETURN-AIR FILTERS (in.)*  
Throwaway  
20x20  
20x20  
20x24  
20x30  
24x30  
24x30  
*Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300  
ft./min. for throwaway type or 450 ft./min. for high-capacity type. Air filter pressure drop for non-standard filters must not exceed 0.08 in. wg.  
CONFIGURING UNITS FOR DOWNFLOW (VERTICAL) DIS-  
CHARGE  
2. Remove return duct cover located on duct panel by breaking  
four (4) connecting tabs with screwdriver and a hammer. (Fig.  
8 & 9)  
3. To remove supply duct cover, break front and right side  
connecting tabs with a screwdriver and a hammer. Push louver  
down to break rear and left side tabs. (Fig. 8 & 9)  
Before performing service or maintenance operations on the  
system, turn off main power to unit and install lockout tag or  
electrical shock could result.  
4. If unit ductwork is to be attached to vertical opening flanges  
on the unit composite base (jackstand applications only), do so  
at this time. Collect ALL screws that were removed. Do not  
leave screws on rooftop as permanent damage to the roof may  
occur.  
1. Open all electrical disconnects and install lockout tag before  
starting any service work.  
8
1” (25mm) MIN.  
TRAP  
OUTLET  
2” (50mm) MIN.  
C99013  
Fig. 7—Condensate Trap  
Table 3—Minimum Airflow for Safe Electric Heater  
Operation (Cfm)  
SIZE  
018  
700  
024  
800  
030  
1000  
036  
1200  
042  
1400  
048  
1600  
060  
2000  
5. It is recommended that the unit base insulation around the  
perimeter of the vertical return-air opening be secured to the  
unit base with aluminum tape. Applicable local codes may  
require aluminum tape to prevent exposed fiberglass.  
6. Cover both horizontal duct openings with the duct covers from  
the accessory duct cover kit. Ensure opening is air-and  
watertight.  
7. After completing unit conversion, perform all safety checks  
and power up unit.  
NOTE: The design and installation of the duct system must be in  
accordance with the standards of the NFPA for installation of  
nonresidence-type air conditioning and ventilating systems, NFPA  
90A or residence-type, NFPA 90B; and/or local codes and  
ordinances.  
Adhere to the following criteria when selecting, sizing, and  
installing the duct system:  
8. Units are shipped for side shot installation.  
9. Select and size ductwork, supply-air registers, and return-air  
grilles according to American Society of Heating, Refrigera-  
tion and Air Conditioning Engineers (ASHRAE) recommen-  
dations.  
RETURN  
DUCT  
OPENING  
SUPPLY  
DUCT  
OPENING  
C99011  
Fig. 8—Supply and Return Duct Opening  
Step 8—Install Electrical Connection  
10. Use flexible transition between rigid ductwork and unit to  
prevent transmission of vibration. The transition may be  
screwed or bolted to duct flanges. Use suitable gaskets to  
ensure weathertight and airtight seal.  
11. All units must have field-supplied filters or accessory filter  
rack installed in the return-air side of the unit. Recommended  
sizes for filters are shown in Tables 1 and 2.  
The unit cabinet must have an uninterrupted, unbroken  
electrical ground to minimize the possibility of personal  
injury if an electrical fault should occur. This ground may  
consist of an electrical wire connected to the unit ground lug  
in the control compartment, or conduit approved for electrical  
ground when installed in accordance with NEC (National  
Electrical Code) ANSI/NFPA (latest edition) and local elec-  
trical codes. In Canada, follow Canadian Electrical Code  
CSA (Canadian Standards Association) C22.1 and local  
electrical codes. Failure to adhere to this warning could result  
in personal injury or death.  
12. Size all ductwork for maximum required airflow (either  
heating or cooling) for unit being installed. Avoid abrupt duct  
size increases or decreases or performance may be affected.  
13. Adequately insulate and weatherproof all ductwork located  
outdoors. Insulate ducts passing through unconditioned space,  
and use vapor barrier in accordance with latest issue of Sheet  
Metal and Air Conditioning Contractors National Association  
(SMACNA) and Air Conditioning Contractors of America  
(ACCA) minimum installation standards for heating and air  
conditioning systems. Secure all ducts to building structure.  
14. Flash, weatherproof, and vibration-isolate all openings in  
building structure in accordance with local codes and good  
building practices.  
9
4. Connect L2 to pressure lug connection 23 of the compressor  
contactor.  
Three phase units:  
1. Run the high-voltage (L1, L2, L3) and ground leads into the  
control box.  
2. Connect ground lead to chassis ground connection.  
3. Locate the black and yellow wires connected to the lines side  
of the contactor.  
4. Connect field L1 to black wire on connection 11 of the  
compressor contactor.  
5. Connect field wire L2 to yellow wire on connection 13 of the  
compressor contactor.  
6. Connect field wire L3 to Blue wire from compressor.  
SPECIAL PROCEDURES FOR 208-V OPERATION  
Make sure that the power supply to the unit is switched OFF  
and lockout tag installed before making any wiring changes.  
Electrical shock can cause serious injury or death.  
DUCT COVERS REMOVED  
C99012  
Fig. 9—Vertical Duct Cover Removed  
CONTROL VOLTAGE CONNECTIONS  
Failure to follow these precautions could result in damage to  
the unit being installed:  
HIGH VOLTAGE  
POWER LEADS  
POWER  
1. Make all electrical connections in accordance with NEC  
ANSI/NFPA (latest edition) and local electrical codes  
governing such wiring. In Canada, all electrical connec-  
tions must be in accordance with CSA standard C22.1  
Canadian Electrical Code Part 1 and applicable local  
codes. Refer to unit wiring diagram.  
2. Use only copper conductor for connections between  
field-supplied electrical disconnect switch and unit. DO  
NOT USE ALUMINUM WIRE.  
(SEE UNIT WIRING  
SUPPLY  
LABEL)  
FIELD-SUPPLIED  
FUSED DISCONNECT  
GND  
CONTROL BOX  
YEL(Y)  
Y
3. Be sure that high-voltage power to unit is within operating  
voltage range indicated on unit rating plate.  
THERMOSTAT  
(TYPICAL)  
GRN(G)  
G
R
C
LOW-VOLTAGE  
POWER LEADS  
(SEE UNIT  
4. Do not damage internal components when drilling through  
any panel to mount electrical hardware, conduit, etc. On  
3-phase units, ensure phases are balanced within 2 percent.  
Consult local power company for correction of improper  
voltage and/or phase imbalance.  
RED(R)  
BRN(C)  
WIRING LABEL)  
SPLICE BOX  
LEGEND  
Field Control-Voltage Wiring  
Field High-Voltage Wiring  
NOTE: Use blue wire for 3-phase units only.  
HIGH-VOLTAGE CONNECTIONS  
The unit must have a separate electrical service with a field-  
supplied, waterproof, disconnect switch mounted at, or within  
sight from, the unit. Refer to the unit rating plate for maximum  
fuse/circuit breaker size and minimum circuit amps (ampacity) for  
wire sizing. See Tables 4 and 5 for electrical data.  
C99010  
Fig. 10—High- and Control-Voltage Connections  
NOTE: Do not use any type of power-stealing thermostat. Unit  
The field-supplied disconnect switch box may be mounted on the  
unit over the high-voltage inlet hole when the standard power and  
low-voltage entry points are used. See Fig. 2 & 3 for acceptable  
location.  
control problems may result.  
Use no. 18 American Wire Gage (AWG) color-coded, insulated  
(35 C minimum) wires to make the control voltage connections  
between the thermostat and the unit. If the thermostat is located  
more than 100 ft. from the unit (as measured along the control  
voltage wires), use no. 16 AWG color-coded, insulated (35 C  
minimum) wires.  
See unit wiring label and Fig. 10 for reference when making high  
voltage connections. Proceed as follows to complete the high-  
voltage connections to the unit.  
Single phase units:  
STANDARD CONNECTION  
1. Run the high-voltage (L1, L2) and ground leads into the  
control box.  
Remove knockout hole located in the electric heat panel adjacent  
to the control access panel. See Fig. 2 & 3. Remove the rubber  
grommet from the installer’s packet (included with unit) and install  
grommet in the knockout opening. Provide a drip loop before  
running wire through panel.  
2. Connect ground lead to chassis ground connection.  
3. Connect L1 to pressure lug connection 11 of the compressor  
contactor.  
10  
Table 4—Electrical Data—50GS  
VOLTAGE  
RANGE  
COMPRESSOR  
OFM  
FLA  
IFM  
ELECTRIC HEAT  
POWER SUPPLY  
UNIT 50GS  
SIZE  
V-PH-HZ  
Min  
Max  
RLA  
LRA  
FLA Nominal Kw*  
FLA  
MCA  
Max Fuse orCkt Bkr  
MOCP  
-/-  
-/-  
13.9/13.9  
24.8/28.3  
34.7/39.8  
47.4/54.3  
20/20  
25/30  
35/40  
50/60  
3.8/5.0  
18.1/20.8  
26.0/30.0  
36.1/41.7  
018  
024  
208/230–1–60  
187  
254  
9
45  
0.8  
0.8  
1.8  
5.4/7.2  
7.5/10.0  
-/-  
-/-  
18.8/18.8  
25.1/28.5  
35/40  
25/25  
25/30  
35/40  
50/60  
3.8/5.0  
18.1/20.8  
2/30  
208/230–1–60  
208/230–1–60  
208/230–3–60  
208/230–1–60  
187  
187  
187  
187  
254  
254  
254  
254  
12.8  
14.4  
8.3  
61  
73  
68  
82  
2
5.4/7.2  
7.5/10.0  
36.1/41.7  
47.6/54.6  
-/-  
3.8/5.0  
5.4/7.2  
7.5/10.0  
11.3/15.0  
-/-  
20.8/20.8  
25.1/28.5  
35/40  
47.6/54.6  
70.2/80.6  
25/25  
25/30  
35/40  
50/60  
18.1/20.8  
26.0/30.0  
36.1/41.7  
54.2/62.5  
0.8  
0.8  
1.4  
2
2
80/90  
030  
-/-  
-/-  
13.2/13.2  
15.5/17.5  
28.6/32.6  
41.6/47.6  
20/20  
20/20  
30/35  
45/50  
3.8/5.0  
7.5/10.0  
11.3/15.0  
10.4/12 .0  
20.8/24.1  
31.3/36.1  
-/-  
-/-  
24.3/24.3  
27.7/31.2  
37.6/42.6  
50.3/57.2  
72.8/83.3  
30/30  
30/35  
40/45  
60/60  
3.8/5.0  
5.4/7.2  
7.5/10.0  
11.3/15.0  
18.1/20.8  
26.0/30.0  
36.1/41.7  
54.2/62.5  
15.0  
4.1  
80/90  
-/-  
-/-  
16.8/16.8  
18.2/20.2  
31.2/35.2  
44.2/50.2  
20/20  
20/20  
35/40  
45/60  
036  
3.8/5.0  
7.5/10.0  
11.3/15.0  
10.4/12.0  
20.8/24.1  
31.3/36.1  
208/230–3–60  
460–3–60  
187  
414  
254  
508  
9.0  
4.5  
78  
40  
1.4  
0.8  
4.1  
1.4  
-
5
10  
15  
-
6
12  
18  
7.8  
9.3  
16.8  
24.3  
15  
15  
20  
25  
-/-  
-/-  
28.7/28.7  
28.7/31.0  
37.5/42.5  
50.1/57.1  
72.7/83.1  
95.3/109.2  
35/35  
35/35  
40/45  
60/60  
3.8/5.0  
18.1/20.8  
26.0/30.0  
36.1/41.7  
54.2/62.5  
72.2/83.3  
5.4/7.2  
208/230–1–60  
187  
254  
18.6  
105  
1.4  
4
7.5/10.0  
11.3/15.0  
15.0/20.0  
80/90  
100/110  
-/-  
-/-  
18.8/18.8  
18.8/20.0  
31.1/35.1  
44.1/50.1  
57.0/65.0  
25/25  
25/25  
35/40  
45/60  
3.8/5.0  
10.4/12.0  
20.8/24.1  
31.3/36.1  
41.6/48.0  
042  
048  
060  
208/230–3–60  
460–3–60  
187  
414  
254  
508  
10.7  
5.3  
85  
42  
1.4  
0.8  
4
2
7.5/10.0  
11.3/15.0  
15.0/19.9  
60/70  
-
-
6
12  
18  
24.1  
9.4  
15  
15  
20  
30  
35  
5
10.0  
17.5  
25.1  
32.6  
10  
15  
20  
-/-  
-/-  
38.7/38.7  
38.7/38.7  
38.7/43.8  
51.4/58.3  
73.9/84.4  
96.5/110.4  
40/40  
40/40  
40/45  
60/60  
80/90  
100/125  
3.8/5.0  
18.1/20.8  
26.0/30.0  
36.1/41.7  
54.2/62.5  
72.2/83.3  
5.4/7.2  
208/230–1–60  
187  
254  
25.3  
131  
2.1  
5
7.5/10.0  
11.3/15.0  
15.0/20.0  
-/-  
3.8/5.0  
7.5/10.0  
11.3/15.0  
15.0/19.9  
-/-  
25.4/25.4  
25.4/25.4  
32.3/36.3  
45.3/51.4  
58.2/66.2  
30/30  
30/30  
35/40  
50/60  
10.4/12.0  
20.8/24.1  
31.3/36.1  
41.6/48.0  
208/230–3–60  
460–3–60  
187  
414  
254  
508  
14.6  
7.3  
108  
48  
2.1  
1.1  
5
60/70  
-
5
10  
15  
20  
-
6
12  
18  
24.1  
12.5  
12.5  
17.9  
25.4  
32.9  
15  
15  
20  
30  
35  
2.3  
-/-  
-/-  
45.0/45.0  
45.0/45.0  
45.0/46.0  
53.6/60.6  
76.2/86.6  
98.8/112.7  
60/60  
60/60  
45/50  
60/70  
80/90  
100/125  
3.8/5.0  
18.1/20.8  
26.0/30.0  
36.1/41.7  
54.2/62.5  
72.2/83.3  
5.4/7.2  
208/230–1–60  
187  
254  
28.9  
147  
2.1  
6.8  
7.5/10.0  
11.3/15.0  
15.0/20.0  
-/-  
3.8/5.0  
7.5/10.0  
11.3/15.0  
15.0/19.9  
-/-  
32.2/32.2  
32.2/32.2  
34.6/38.6  
47.6/53.6  
60.5/68.5  
40/40  
35/35  
35/35  
50/60  
10.4/12.0  
20.8/24.1  
31.3/36.1  
41.6/48.0  
208/230–3–60  
460–3–60  
187  
414  
254  
508  
18.6  
8.5  
125  
2.1  
1.1  
6.8  
3.2  
70/70  
-
5
10  
15  
20  
-
6
12  
18  
24  
14.9  
14.9  
19.0  
26.6  
34.1  
20  
15  
15  
30  
35  
66.5  
(See legend following Electrical Data charts)  
11  
Table 5—Electrical Data—50GX  
VOLTAGE  
RANGE  
COMPRESSOR  
OFM  
IFM  
ELECTRIC HEAT  
POWER SUPPLY  
UNIT 50GX  
SIZE  
V-PH-HZ  
Max Fuse  
or  
Ckt Bkr  
Min  
Max  
RLA  
LRA  
FLA  
FLA  
Nominal Kw*  
FLA  
MCA  
MOCP  
-/-  
-/-  
16.5/16.5  
25.1/28.5  
35.0/40.0  
47.6/54.6  
20/20  
30/30  
35/40  
50/60  
3.8/5.0  
5.4/7.2  
7.5/10.0  
18.1/20.8  
26.0/30.0  
36.1/41.7  
024  
030  
208/230–1–60  
208/230–1–60  
208/230–3–60  
208/230–1–60  
187  
187  
187  
187  
253  
10.9  
54.0  
0.9  
0.8  
0.8  
0.8  
2.0  
2.1  
2.1  
4.1  
-/-  
-/-  
19.8/19.8  
25.2/28.7  
35.1/40.1  
47.8/54.7  
70.3/80.8  
25/25  
25/30  
40/45  
50/60  
3.8/5.0  
5.4/7.2  
7.5/10.0  
11.3/15.0  
18.1/20.8  
26.0/30.0  
36.1/41.7  
54.2/62.5  
253  
253  
253  
13.5  
9.0  
73.0  
63.0  
97.0  
80/90  
-/-  
-/-  
14.2/14.2  
15.7/17.7  
28.7/32.7  
41.7/47.7  
20/20  
20/20  
30/35  
45/50  
3.8/5.0  
7.5/10.0  
11.3/15.0  
10.4/12.0  
20.8/24.1  
31.3/36.1  
-/-  
-/-  
25.8/25.8  
27.7/31.2  
37.6/42.6  
50.3/57.2  
72.8/83.3  
30/30  
30/35  
40/45  
60/60  
3.8/5.0  
5.4/7.2  
7.5/10.0  
11.3/15.0  
18.1/20.8  
26.0/30.0  
36.1/41.7  
54.2/62.5  
16.7  
80/90  
-/-  
-/-  
18.9/18.9  
18.9/20.2  
3102/35.2  
44.2/50.2  
25/25  
25/25  
35/40  
45/60  
036  
3.8/5.0  
7.5/10.0  
11.3/15.0  
10.4/12.0  
20.8/24.1  
31.3/36.1  
208/230–3–60  
460–3–60  
187  
414  
253  
506  
11.2  
5.4  
75.0  
37.5  
0.8  
0.9  
4.1  
1.9  
-
5
10  
15  
-/-  
6
12  
18  
9.6  
9.9  
17.4  
24.9  
15  
15  
20  
25  
-/-  
-/-  
28.1/28.1  
28.1/31.2  
37.6/42.6  
50.3/57.2  
72.8/83.3  
95.4/109.3  
35/35  
35/35  
40/45  
60/60  
3.8/5.0  
18.1/20.8  
26.0/30.0  
36.1/41.7  
54.2/62.5  
72.2/83.3  
5.4/7.2  
208/230–1–60  
187  
253  
17.9  
104.0  
1.6  
4.1  
7.5/10.0  
11.3/15.0  
15.0/20.0  
80/90  
100/110  
-/-  
-/-  
21.2/21.2  
21.2/21.2  
31.2/35.2  
44.2/50.2  
57.2/65.3  
25/25  
25/25  
35/40  
45/60  
3.8/5.0  
10.4/12.0  
20.8/24.1  
31.3/36.1  
41.7/48.1  
042  
208/230–3–60  
460–3–60  
187  
414  
253  
506  
12.4  
6.1  
88.0  
44.0  
1.6  
0.9  
4.1  
2.0  
7.5/10.0  
11.3/15.0  
15.0/20.0  
60/70  
-
-/-  
10.5  
10.5  
17.5  
25.1  
32.6  
15  
15  
20  
30  
35  
5
6.0  
10  
15  
20  
12.0  
18.0  
24.1  
-/-  
-/-  
34.9/34.9  
34.9/34.9  
37.6/42.6  
50.3/57.2  
72.8/83.3  
95.4/109.3  
45/45  
35/35  
40/45  
60/60  
3.8/5.0  
18.1/20.8  
26.0/30.0  
36.1/41.7  
54.2/62.5  
72.2/83.3  
5.4/7.2  
208/230–1–60  
187  
253  
23.4  
126.0  
1.5  
4.1  
7.5/10.0  
11.3/15.0  
15.0/20.0  
80/90  
100/110  
-/-  
-/-  
21.9/21.9  
21.9/21.9  
31.2/35.2  
44.2/50.2  
57.2/65.3  
30/30  
25/25  
35/40  
45/60  
3.8/5.0  
10.4/12.0  
20.8/24.1  
31.3/36.1  
41.7/48.1  
048  
208/230–3–60  
460–3–60  
187  
414  
253  
506  
13.0  
6.4  
93.0  
46.5  
1.5  
0.9  
4.1  
1.9  
7.5/10.0  
11.3/15.0  
15.0/20.0  
60/70  
-
-/-  
10.8  
10.8  
17.4  
24.9  
32.4  
15  
15  
20  
25  
35  
5
6.0  
10  
15  
20  
12.0  
18.0  
24.1  
-/-  
-/-  
43.8/43.8  
43.8/43.8  
40.2/45.3  
52.9/59.8  
75.4/85.9  
98.0/111.9  
60/60  
45/45  
45/50  
60/60  
3.8/5.0  
18.1/20.8  
26.0/30.0  
36.1/41.7  
54.2/62.5  
72.2/83.3  
5.4/7.2  
208/230–1–60  
187  
253  
28.8  
169.0  
1.6  
6.2  
7.5/10.0  
11.3/15.0  
15.0/20.0  
80/90  
100/125  
-/-  
-/-  
29.4/29.4  
29.4/29.4  
33.8/37.8  
46.8/52.9  
59.9/67.9  
35/35  
30/30  
30/40  
50/60  
3.8/5.0  
10.4/12.0  
20.8/24.1  
31.3/36.1  
41.7/48.1  
060  
208/230–3–60  
460–3–60  
187  
414  
253  
506  
17.3  
9.0  
123.0  
62.0  
1.6  
0.9  
6.2  
3.2  
7.5/10.0  
11.3/15.0  
15.0/20.0  
60/70  
-
-/-  
15.4  
15.4  
19.0  
26.6  
34.1  
20  
20  
15  
30  
35  
5
6.0  
10  
15  
20  
12.0  
18.0  
24.1  
(See legend following Electrical Data charts)  
12  
EXAMPLE: Supply voltage is 460-3-60.  
AB = 452 v  
BC = 464 v  
AC = 455 v  
LEGEND  
FLA  
LRA  
MCA  
— Full Load Amps  
— Locked Rotor Amps  
— Minimum Circuit Amps  
452 + 464 + 455  
®
Average Voltage =  
3
1371  
3
MOCP — Maximum Overcurrent Protection  
RLA  
CKT BKR  
— Rated Load Amps  
=
Circuit Breaker  
= 457  
NOTES:  
Determine maximum deviation from average voltage.  
(AB) 457 452 = 5 v  
1. In compliance with NEC (National Electrical Code) requirements  
for multimotor and combination load equipment (refer to NEC  
Articles 430 and 440), the overcurrent protective device for the  
unit shall be Power Supply fuse. Canadian units may be  
fuse or circuit breaker.  
(BC) 464 457 = 7 v  
(AC) 457 455 = 2 v  
Maximum deviation is 7 v.  
2. Minimum wire size is based on 60 C copper wire. If other than  
60 C wire is used, or if length exceeds wire length in table,  
determine size from NEC.  
Determine percent of voltage imbalance.  
7
457  
% Voltage Imbalance = 100 x  
3. Unbalanced 3-Phase Supply Voltage  
Never operate a motor where a phase imbalance in supply volt-  
age is greater than 2%. Use the following formula to determine  
the percentage of voltage imbalance.  
= 1.53%  
This amount of phase imbalance is satisfactory as it is below the  
maximum allowable 2%.  
% Voltage imbalance  
max voltage deviation from average voltage  
= 100 x  
IMPORTANT: If the supply voltage phase imbalance is  
more than 2%, contact your local electric utility company  
immediately.  
average voltage  
C99024  
Run the low-voltage leads from the thermostat, through the inlet  
hole, and into unit low-voltage splice box.  
PRE-START-UP  
Locate five 18-gage wires leaving control box. These low-voltage  
connection leads can be identified by the colors red, green, yellow,  
brown, and white (See Fig. 10). Ensure the leads are long enough  
to be routed into the low-voltage splice box (located below right  
side of control box). Stripped yellow wire is located in connection  
box. Route leads through hole in bottom of control box and make  
low-voltage connections (See Fig. 10). Secure all cut wires, so that  
they do not interfere with operation of unit.  
Failure to observe the following warnings could result in  
serious personal injury:  
1. Follow recognized safety practices and wear protective  
goggles when checking or servicing refrigerant system.  
2. Do not operate compressor or provide any electric power to  
unit unless compressor terminal cover is in place and  
secured.  
TRANSFORMER PROTECTION  
3. Do not remove compressor terminal cover until all electri-  
cal sources are disconnected.  
The transformer is of the energy-limiting type. It is set to  
4. Relieve and recover all refrigerant from system before  
touching or disturbing anything inside terminal box if  
refrigerant leak is suspected around compressor terminals.  
5. Never attempt to repair soldered connection while refrig-  
erant system is under pressure.  
withstand a 30-second overload or shorted secondary condition.  
6. Do not use torch to remove any component. System  
contains oil and refrigerant under pressure. To remove a  
component, wear protective goggles and proceed as fol-  
lows:  
a. Shut off electrical power to unit.  
b. Relieve and reclaim all refrigerant from system using  
both high- and low-pressure ports.  
c. Cut component connecting tubing with tubing cutter and  
remove component from unit.  
d. Carefully unsweat remaining tubing stubs when neces-  
sary. Oil can ignite when exposed to torch flame.  
Proceed as follows to inspect and prepare the unit for initial  
startup:  
1. Remove access panel.  
2. Read and follow instructions on all WARNING, CAUTION,  
and INFORMATION labels attached to, or shipped with, unit.  
3. Make the following inspections:  
a. Inspect for shipping and handling damages such as broken  
lines, loose parts, disconnected wires, etc.  
b. Inspect for oil at all refrigerant tubing connections and on  
unit base. Detecting oil generally indicates a refrigerant  
13  
leak. Leak test all refrigerant tubing connections using  
electronic leak detector, halide torch, or liquid-soap solu-  
tion. If a refrigerant leak is detected, see Check for  
Refrigerant Leaks section.  
START UP COOLING SECTION AND MAKE ADJUST-  
MENTS  
c. Inspect all field- and factory-wiring connections. Be sure  
that connections are completed and tight.  
Complete the required procedures given in the Pre-Start- Up  
section before starting the unit. Do not jumper any safety  
devices when operating the unit. Do not operate the compres-  
sor when the outdoor temperature is below 40°F (unless  
accessory low-ambient kit is installed). Do not rapid-cycle the  
compressor. Allow 5 minutes between “on” cycles to prevent  
compressor damage.  
d. Ensure electrical wiring does not contact refrigerant tubes  
or sharp metal edges.  
e. Inspect coil fins. If damaged during shipping and handling,  
carefully straighten fins with a fin comb.  
Verify the following conditions:  
CHECKING COOLING CONTROL OPERATION  
a. Make sure that condenser-fan blade is correctly positioned  
in fan orifice. Leading edge of condenser-fan blade should  
be 1/2 in. maximum from fan orifice (See Fig. 11).  
Start and check the unit for proper cooling control operation as  
follows:  
b. Make sure that air filter(s) is in place.  
1. Place room thermostat SYSTEM switch in OFF position.  
Observe that blower motor starts when FAN switch is placed  
in ON position and shuts down after 30 second fan time delay  
expires when FAN switch is placed in AUTO position.  
c. Make sure that condensate drain trap is filled with water to  
ensure proper drainage.  
d. Make sure that all tools and miscellaneous loose parts have  
been removed.  
2. Place SYSTEM switch in COOL position and FAN switch in  
AUTO position. Set cooling control below room temperature.  
Observe that compressor, condenser fan, and evaporator  
blower motors start. Observe that compressor and outdoor fan  
shut down when control setting is satisfied and that indoor  
blower shuts down after 30 second fan time delay expires.  
START-UP  
CHECK FOR REFRIGERANT LEAKS  
Proceed as follows to locate and repair a refrigerant leak and to  
charge the unit:  
1. Locate leak and make sure that refrigerant system pressure has  
been relieved and reclaimed from both high- and low-pressure  
ports.  
3. When using an auto-changeover room thermostat, place both  
SYSTEM and FAN switches in AUTO positions. Observe that  
unit operates in heating mode when temperature control is set  
to “call for heating” (above room temperature) and operates in  
cooling mode when temperature control is set to “call for  
cooling” (below room temperature).  
FAN GRILLE  
MOTOR  
IMPORTANT: Three-phase, scroll compressor units (50GS048,  
50GX030-060) are direction-oriented. These units must be  
checked to ensure proper compressor 3-phase power lead orienta-  
tion. If not corrected within 5 minutes, the internal protector will  
shut off the compressor. The 3-phase power leads to the unit must  
be reversed to correct rotation. When turning backwards, scroll  
compressors emit elevated noise levels, and the difference between  
compressor suction and  
1/2˝  
1/8" MAX BETWEEN  
MOTOR SHAFT  
MOTOR AND FAN HUB  
C99009  
Fig. 11—Fan Blade Clearance  
discharge pressures may be  
dramatically lower than normal.  
2. Repair leak following accepted practices. NOTE: Install a  
filter drier whenever the system has been opened for repair.  
CHECKING AND ADJUSTING REFRIGERANT CHARGE  
3. Add a small charge of R-22 refrigerant vapor to system and  
leak-test unit.  
The refrigerant system is fully charged with R-22 refrigerant,  
tested, and factory-sealed.  
4. Recover refrigerant from refrigerant system and evacuate to  
500 microns if no additional leaks are not found.  
NOTE: Adjustment of the refrigerant charge is not required  
unless the unit is suspected of not having the proper R-22 charge.  
5. Charge unit with R-22 refrigerant, using a volumetric-  
charging cylinder or accurate scale. Refer to unit rating plate  
for required charge. Be sure to add extra refrigerant to  
compensate for internal volume of filter drier.  
A superheat charging chart is attached to the outside of the service  
access panel. The chart includes the required suction line tempera-  
ture at given suction line pressures and outdoor ambient tempera-  
tures (See Fig. 15–27).  
An accurate superheat, thermocouple- or thermistor-type ther-  
mometer, a sling psychrometer, and a gauge manifold are required  
when using the superheat charging method for evaluating the unit  
charge. Do not use mercury or small dial-type thermometers  
because they are not adequate for this type of measurement.  
NOTE: Allow system to operate in the cooling mode for a  
minimum of 10 minutes before checking or adjusting refrigerant  
charge.  
14  
C99003  
Fig. 12—Wiring Diagram (208/230-60-1)  
15  
C99004  
Fig. 13—Wiring Diagram (208/230-60-3)  
16  
C99005  
Fig. 14—Wiring Diagram (460-60-3)  
17  
Table 6—Color Coding for 208/230–V Motor Leads  
When evaluating the refrigerant charge, an indicated adjust-  
ment to the specified factory charge must always be very  
minimal. If a substantial adjustment is indicated, an abnormal  
condition exists somewhere in the cooling system, such as  
insufficient airflow across either coil or both coils.  
3-SPEED  
2-SPEED  
black = high speed  
-
black = high speed  
blue = medium speed  
red = low speed  
red = low speed  
units. To change the speed, remove and replace with lead for  
desired blower motor speed. Insulate the removed lead to avoid  
contact with chassis parts.  
Proceed as follows:  
1. Remove caps from low- and high-pressure service fittings.  
2. Using hoses with valve core depressors, attach low- and  
high-pressure gauge hoses to low- and high-pressure service  
fittings, respectively.  
FOR 460-V GE MOTORS  
For color coding on the 460-v GE motor leads, see Table 7.  
3. Start unit in Cooling mode and let unit run until system  
pressures stabilize.  
Table 7—Color Coding for 460-V GE Motor Leads  
3-SPEED  
black = high  
violet = jumper  
orange = medium  
red = low  
2-SPEED  
black = high  
blue = jumper  
-
4. Measure and record the following:  
a. Outdoor ambient-air temperature (°F db).  
b. Evaporator inlet-air temperature (°F wb).  
c. Suction-tube temperature (°F) at low-side service fitting.  
d. Suction (low-side) pressure (psig).  
red = low  
5. Using “Cooling Charging Charts” compare outdoor-air tem-  
perature (°F db) with the suction line pressure (psig) to  
determine desired system operating suction line temperature.  
See Fig. 15-27.  
To change the speed of the indoor fan motor (IFM), remove fan  
motor speed lead from the time delay relay (TDR) and replace with  
the lead for the desired blower motor speed. The motor speed lead  
is attached to terminal–3 of TDR. For low and medium speeds  
black must be connected to the jumper wire. Insulate removed lead  
end to avoid contact with chassis parts. To select high speed on  
460-v GE motors, separate the black female quick connect (QC)  
from the jumper lead male quick connect (QC) and connect the  
black lead to the BR. Insulate the jumper to avoid contact with any  
chassis parts.  
6. Compare actual suction-tube temperature with desired  
suction-tube temperature. Using a tolerance of ±3°F, add  
refrigerant if actual temperature is more than 3°F higher than  
proper suction-tube temperature, or remove refrigerant if  
actual temperature is more than 3°F lower than required  
suction-tube temperature.  
COOLING SEQUENCE OF OPERATION  
NOTE: If the problem causing the inaccurate readings is a  
With the room thermostat SYSTEM switch in the COOL position  
and the FAN switch in the AUTO position, the cooling sequence  
of operation is as follows:  
refrigerant leak, refer to Check for Refrigerant Leaks section.  
INDOOR AIRFLOW AND AIRFLOW ADJUSTMENTS  
When the room temperature rises to a point that is slightly above  
the cooling control setting of the thermostat, the thermostat  
completes the circuit between thermostat terminal R to terminals Y  
and G. These completed circuits through the thermostat connect  
contactor coil (C) (through unit wire Y) and time delay relay  
(TDR) (through unit wire G) across the 24-v secondary of  
transformer (TRAN).  
For cooling operation, the recommended airflow is 350 to 450  
cfm for each 12,000 Btuh of rated cooling capacity.  
Tables 8 and 9 show cooling airflows at various external static  
pressures. Refer to these tables to determine the airflow for the  
system being installed.  
The normally open contacts of energized contactor (C) close and  
complete the circuit through compressor motor (COMP) to con-  
denser (outdoor) fan motor (OFM). Both motors start instantly.  
NOTE: Be sure that all supply- and return-air grilles are open,  
free from obstructions, and adjusted properly.  
The set of normally open contacts of energized relay TDR close  
and complete the circuit through evaporator blower (indoor) fan  
motor (IFM).  
Disconnect electrical power to the unit and install lockout tag  
before changing blower speed. Electrical shock can cause  
serious injury or death.  
NOTE: Once the compressor has started and then has stopped, it  
should not be started again until 5 minutes have elapsed.  
Airflow can be changed by changing the lead connections of the  
blower motor.  
The cooling cycle remains “on” until the room temperature drops  
to a point that is slightly below the cooling control setting of the  
room thermostat. At this point, the thermostat “breaks” the circuit  
between thermostat terminal R to terminals Y and G. These open  
circuits deenergize contactor coil C and relay coil TDR. The  
condenser and compressor motors stop. After a 30-second delay,  
the blower motor stops. The unit is in a “standby” condition,  
waiting for the next “call for cooling” from the room thermostat.  
Unit 50GS two- or three-speed motors (except size 030) are  
factory wired for low speed operation. Unit 50GS030 is factory  
wired for medium speed.  
All 50GX units are factory wired for low speed and may need to  
be wired for medium or high speed in the field.  
FOR 208/230V  
For color coding on the 208/230V motor leads, see Table 6.  
MAINTENANCE  
To change the speed of the indoor fan motor (IFM), remove the fan  
motor speed leg lead from the time delay relay (TDR). This wire  
is attached to terminal–3 of TDR for single-phase and 3-phase  
To ensure continuing high performance, and to minimize the  
possibility of premature equipment failure, periodic maintenance  
must be performed on this equipment. This cooling unit should be  
18  
Table 8—Wet Coil Air Delivery (Deduct 10 percent for 208v)*  
Horizontal and Downflow Discharge  
Unit 50GS018-060  
230 AND 460 VOLT  
External Static Pressure (in. wg)  
Motor  
Unit  
018  
Speed  
0.0  
227  
1000  
-
0.1  
212  
915  
-
0.2  
196  
825  
-
0.3  
177  
710  
-
0.4  
165  
530  
-
0.5  
153  
340  
-
0.6  
-
-
0.7  
-
0.8  
-
0.9  
-
1.0  
-
Watts  
Cfm  
Watts  
Cfm  
Watts  
Cfm  
Watts  
Cfm  
Watts  
Cfm  
Watts  
Cfm  
Watts  
Cfm  
Watts  
Cfm  
Watts  
Cfm  
Watts  
Cfm  
Watts  
Cfm  
Watts  
Cfm  
Watts  
Cfm  
Watts  
Cfm  
Watts  
Cfm  
Watts  
Cfm  
Low  
Med  
High  
Low  
Med  
High  
Low  
Med  
High  
Low  
Med  
High  
Low  
Med  
High  
Low  
Med  
High  
Low  
Med  
High  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
287  
1150  
280  
880  
380  
1136  
485  
1415  
280  
880  
380  
1136  
485  
1415  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
275  
1032  
275  
825  
375  
1085  
475  
1332  
275  
825  
375  
1085  
475  
1332  
470  
1352  
-
266  
963  
270  
765  
365  
1010  
470  
1266  
270  
765  
365  
1010  
470  
1266  
458  
1257  
514  
1338  
-
253  
807  
267  
693  
360  
946  
460  
1180  
267  
693  
360  
946  
460  
1180  
445  
1240  
501  
1295  
646  
1385  
650  
1275  
825  
1350  
1000  
1488  
700  
1575  
821  
1770  
943  
1997  
836  
1905  
994  
2058  
1152  
2207  
242  
698  
264  
600  
355  
865  
455  
1100  
264  
600  
355  
865  
455  
1100  
430  
1199  
487  
1288  
636  
1268  
640  
1204  
795  
1285  
950  
1424  
688  
1505  
807  
1700  
927  
1922  
822  
1880  
971  
2000  
1120  
2124  
234  
503  
262  
450  
350  
787  
445  
1000  
262  
450  
350  
787  
445  
1000  
415  
1107  
471  
1181  
626  
1196  
630  
1142  
778  
1224  
925  
1360  
666  
1450  
782  
1642  
897  
1845  
808  
1820  
955  
1932  
1102  
2041  
226  
250  
260  
281  
344  
650  
437  
900  
260  
281  
344  
650  
437  
900  
399  
1015  
455  
1111  
614  
1159  
620  
1081  
765  
1163  
910  
1296  
644  
1390  
756  
1565  
868  
1750  
772  
1775  
928  
1885  
1084  
2000  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
335  
495  
430  
780  
-
312  
360  
415  
480  
-
-
-
-
-
-
-
024  
030  
036  
042  
048  
060  
385  
256  
-
-
-
-
-
-
335  
495  
430  
780  
384  
924  
438  
968  
602  
1032  
610  
995  
750  
1091  
890  
1233  
622  
1300  
730  
1482  
838  
1600  
737  
1695  
897  
1829  
1056  
1960  
312  
360  
415  
480  
-
-
-
-
-
-
-
-
-
-
-
-
385  
256  
-
-
-
-
-
-
580  
850  
718  
932  
855  
1071  
569  
1145  
667  
1290  
766  
1425  
674  
1530  
835  
1638  
997  
1748  
-
422  
813  
589  
948  
595  
918  
735  
1013  
875  
1148  
595  
1205  
699  
1385  
802  
1550  
705  
1627  
867  
1740  
1029  
1856  
-
-
-
-
-
-
-
675  
1387  
886  
1458  
-
660  
1326  
855  
1406  
-
700  
870  
833  
1005  
-
-
-
727  
1640  
853  
1860  
979  
2090  
949  
2000  
1054  
2179  
-
712  
1600  
836  
1830  
959  
2048  
864  
1945  
1024  
2110  
1184  
2278  
-
Watts  
Cfm  
Watts  
Cfm  
Watts  
Cfm  
Watts  
Cfm  
640  
1210  
730  
1380  
642  
1480  
803  
1569  
965  
1645  
1033  
2050  
1084  
2248  
-
Watts  
Cfm  
-
-
* Air delivery values are based on operating voltage of 230v or 460v, wet coil, without filter or electric heater. Deduct filter and electric heater pressure drops to obtain  
static pressure available for ducting.  
NOTES:  
1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occur at airflows below  
this point.  
2. Dashes indicate portions of table that are beyond the blower motor capacity or are not recommended.  
inspected at least once each year by a qualified service person. To  
troubleshoot heating or cooling of units, refer to tables at the back  
of the book.  
The following are 50GS Cooling Charging Charts:  
The following are 50GX Cooling Charging Charts:  
NOTE TO EQUIPMENT OWNER: Consult your local dealer  
about the availability of a maintenance contract.  
19  
Table 9—Wet Coil Air Delivery (Deduct 10 percent for 208v)*  
Horizontal and Downflow Discharge  
Unit 50GX024-060  
230 AND 460 VOLT  
External Static Pressure (in. wg)  
Motor  
Unit  
024  
Speed  
0.0  
281  
833  
-
-
-
-
246  
910  
343  
1148  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
0.1  
282  
776  
-
-
-
-
244  
806  
339  
1104  
-
-
470  
1352  
-
-
-
-
625  
1540  
-
-
-
0.2  
281  
702  
-
-
-
-
243  
749  
336  
1028  
-
0.3  
278  
638  
375  
894  
-
0.4  
276  
554  
370  
800  
-
0.5  
-
0.6  
-
0.7  
-
0.8  
-
0.9  
-
1.0  
-
Watts  
Cfm  
Watts  
Cfm  
Watts  
Cfm  
Watts  
Cfm  
Watts  
Cfm  
Watts  
Cfm  
Watts  
Cfm  
Watts  
Cfm  
Watts  
Cfm  
Watts  
Cfm  
Watts  
Cfm  
Watts  
Cfm  
Watts  
Cfm  
Watts  
Cfm  
Watts  
Cfm  
Watts  
Cfm  
Low  
Med  
High  
Low  
Med  
High  
Low  
Med  
High  
Low  
Med  
High  
Low  
Med  
High  
Low  
Med  
High  
363  
754  
468  
884  
-
357  
636  
457  
802  
-
352  
518  
444  
697  
-
-
-
-
-
-
-
-
-
431  
467  
-
423  
397  
-
-
-
-
241  
680  
332  
958  
-
-
-
-
-
-
-
-
-
-
-
-
-
328  
850  
441  
1102  
430  
1199  
487  
1288  
636  
1268  
593  
1396  
726  
1648  
-
322  
782  
432  
988  
415  
1107  
471  
1181  
626  
1196  
574  
1348  
695  
1593  
-
317  
645  
421  
896  
399  
1015  
455  
1111  
614  
1159  
549  
1288  
661  
1530  
-
030  
036  
042  
048  
060  
-
-
-
-
410  
783  
384  
924  
438  
968  
602  
1032  
518  
1192  
625  
1446  
790  
1616  
517  
1237  
623  
1421  
800  
1547  
764  
1744  
839  
1852  
1008  
2000  
400  
529  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
458  
1257  
514  
1338  
-
445  
1240  
501  
1295  
646  
1385  
605  
1473  
-
-
422  
813  
589  
948  
485  
1124  
591  
1352  
766  
1492  
491  
1161  
596  
1357  
775  
1565  
743  
1678  
798  
1727  
972  
1802  
-
614  
1510  
-
-
-
454  
1037  
561  
1237  
7421  
1394  
-
-
540  
1114  
713  
1283  
-
-
-
-
-
-
-
-
-
588  
1514  
756  
1785  
-
577  
1543  
738  
1765  
-
572  
1467  
719  
1706  
-
566  
1408  
699  
1628  
896  
1880  
814  
1958  
941  
2120  
1080  
2181  
556  
1374  
676  
1577  
862  
1804  
792  
1866  
914  
2020  
1066  
2122  
539  
1324  
650  
1503  
829  
1704  
777  
1822  
880  
1952  
1041  
2101  
-
-
572  
1298  
752  
1406  
701  
1535  
764  
1617  
938  
1672  
555  
1253  
728  
1367  
618  
1377  
750  
1549  
-
-
-
-
903  
2190  
-
-
-
-
898  
2158  
1002  
2389  
-
873  
2081  
978  
2291  
-
842  
2026  
960  
2216  
1080  
2316  
Watts  
Cfm  
Watts  
Cfm  
-
-
-
* Air delivery values are based on operating voltage of 230v or 460v, wet coil, without filter or electric heater. Deduct filter and electric heater pressure drops to obtain  
static pressure available for ducting.  
NOTES:  
1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occur at airflows below  
this point.  
2. Dashes indicate portions of table that are beyond the blower motor capacity or are not recommended.  
The ability to properly perform maintenance on this equip-  
ment requires certain expertise, mechanical skills, tools, and  
equipment. If you do not possess these, do not attempt to  
perform any maintenance on this equipment other than those  
procedures recommended in the User’s Manual. FAILURE  
TO HEED THIS WARNING COULD RESULT IN SERI-  
OUS PERSONAL INJURY AND POSSIBLE DAMAGE TO  
THIS EQUIPMENT.  
Failure to follow these warnings could result in serious  
personal injury:  
1. Turn off electrical power to the unit and install lockout tag  
before performing any maintenance or service on the unit.  
2. Use extreme caution when removing panels and parts. As  
with any mechanical equipment, personal injury can result  
from sharp edges, etc.  
3. Never place anything combustible either on, or in contact  
with, the unit.  
20  
C99037  
C99039  
Fig. 15—Cooling Charging Chart, 50GS018 Units  
Fig. 16—Cooling Charging Chart, 50GS024 Units  
C99038  
C99040  
Fig. 17—Cooling Charging Chart, 50GS030 Units  
Fig. 18—Cooling Charging Chart, 50GS036 Units  
4. Check electrical connections for tightness and controls for  
proper operation each heating and cooling season. Service  
when necessary.  
Errors made when reconnecting wires may cause improper  
and dangerous operation. Label all wires prior to disconnec-  
tion when servicing.  
5. Ensure electric wires are not in contact with refrigerant tubing  
or sharp metal edges.  
The minimum maintenance requirements for this equipment are as  
follows:  
1. Inspect air filter(s) each month. Clean or replace when  
necessary.  
2. Inspect indoor coil, drain pan, and condensate drain at least  
each cooling season for cleanliness. Clean when necessary.  
3. Inspect blower motor and wheel for cleanliness and check  
lubrication each heating and cooling season. Clean when  
necessary.  
21  
OUTDOOR TEMP  
° F ° C  
115 46  
105 41  
95 35  
85 29  
75 24  
65 18  
55 13  
45  
7
°
C99041  
C99042  
Fig. 19—Cooling Charging Chart, 50GS042 Units  
Fig. 20—Cooling Charging Chart, 50GS048 Units  
(024) 60HZ CHARGING CHART  
OUTDOOR TEMP  
OUTDOOR TEMP  
° F  
° C  
° F  
° C  
115 46  
115 46  
105 41  
105 41  
95 35  
85 29  
75 24  
65 18  
55 13  
95 35  
85 29  
75 24  
65 18  
55 13  
45  
7
45  
7
°
°
C99043  
C99044  
Fig. 21—Cooling Charging Chart, 50GS060 Units  
Fig. 22—Cooling Charging Chart, 50GX024 Units  
AIR FILTER  
For longer life, operating economy, and continuing efficiency,  
clean accumulated dirt and grease from the blower wheel and  
motor annually.  
Never operate the unit without a suitable air filter in the  
return-air duct system. Always replace the filter with the same  
dimensional size and type as originally installed. See Tables  
1 and 2 for recommended filter sizes.  
Disconnect and tag electrical power to the unit before  
cleaning the blower motor and wheel. Failure to adhere to this  
warning could cause personal injury or death.  
Inspect air filter(s) at least once each month and replace  
(throwaway-type) or clean (cleanable-type) at least twice during  
each heating and cooling season or whenever the filter(s) becomes  
clogged with dust and lint.  
To clean the blower motor and wheel:  
1. Remove and disassemble blower assembly as follows:  
a. Remove unit access panel.  
EVAPORATOR BLOWER AND MOTOR  
NOTE: All motors are prelubricated. Do not attempt to lubricate  
these motors.  
b. Disconnect motor lead from time delay relay (TDR).  
Disconnect yellow lead from terminal L2 of the contactor.  
22  
(030) 60HZ CHARGING CHART  
(036) 60HZ CHARGING CHART  
OUTDOOR TEMP  
° F ° C  
OUTDOOR TEMP  
° F ° C  
115 46  
105 41  
115 46  
105 41  
95 35  
85 29  
95 35  
85 29  
75 24  
75 24  
65 18  
65 18  
55 13  
55 13  
45  
7
45  
7
°
°
C99046  
C99045  
Fig. 23—Cooling Charging Chart, 50GX030 Units  
Fig. 24—Cooling Charging Chart, 50GX036 Units  
(042) 60HZ CHARGING CHART  
(048) 60HZ CHARGING CHART  
OUTDOOR TEMP  
OUTDOOR TEMP  
° F  
° C  
° F  
° C  
115 46  
115 46  
105 41  
95 35  
85 29  
75 24  
105 41  
95 35  
85 29  
75 24  
65 18  
55 13  
65 18  
45  
7
55 13  
45  
7
°
°
C99047  
C99048  
Fig. 25—Cooling Charging Chart, 50GX042 Units  
Fig. 26—Cooling Charging Chart, 50GX048 Units  
c. On all units remove blower assembly from unit. Remove  
screws securing blower to blower partition and slide  
assembly out. Be careful not to tear insulation in blower  
compartment.  
c. Remove caked-on dirt from wheel and housing with a  
brush. Remove lint and/or dirt accumulations from wheel  
and housing with vacuum cleaner, using soft brush attach-  
ment. Remove grease and oil with mild solvent.  
d. Reassemble wheel into housing.  
d. Ensure proper reassembly by marking blower wheel and  
motor in relation to blower housing before disassembly.  
e. Reassemble motor into housing. Be sure setscrews are  
tightened on motor shaft flats and not on round part of  
shaft.  
e. Loosen setscrew(s) that secures wheel to motor shaft,  
remove screws that secure motor mount brackets to hous-  
ing, and slide motor and motor mount out of housing.  
f. Reinstall unit access panel.  
3. Restore electrical power to unit. Start unit and check for  
proper blower rotation and motor speeds during heating and  
cooling cycles.  
2. Remove and clean blower wheel as follows:  
a. Ensure proper reassembly by marking wheel orientation.  
b. Lift wheel from housing. When handling and/or cleaning  
blower wheel, be sure not to disturb balance weights (clips)  
on blower wheel vanes.  
23  
(060) 60HZ CHARGING CHART  
OUTDOOR TEMP  
° F ° C  
115 46  
105 41  
95 35  
85 29  
75 24  
65 18  
55 13  
45  
7
°
C99049  
Fig. 27—Cooling Charging Chart, 50GX060 Units  
CONDENSER COIL, EVAPORATOR COIL, AND CONDEN-  
SATE DRAIN PAN  
4. If fan needs to be removed, loosen the setscrew and slide the  
fan off the motor shaft.  
5. When replacing fan blade, position blade so that the hub is 1/8  
in. away from the motor end (1/8 in. of motor shaft will be  
visible).  
Inspect the condenser coil, evaporator coil, and condensate drain  
pan at least once each year.  
The coils are easily cleaned when dry; therefore, inspect and clean  
the coils either before or after each cooling season. Remove all  
obstructions, including weeds and shrubs, that interfere with the  
airflow through the condenser coil.  
6. Ensure that setscrew engages the flat area on the motor shaft  
when tightening  
7. Replace grille.  
Straighten bent fins with a fin comb. If coated with dirt or lint,  
clean the coils with a vacuum cleaner, using the soft brush  
attachment. Be careful not to bend the fins. If coated with oil or  
grease, clean the coils with a mild detergent-and-water solution.  
Rinse coils with clear water, using a garden hose. Be careful not to  
splash water on motors, insulation, wiring, or air filter(s). For best  
results, spray condenser coil fins from inside to outside the unit.  
On units with an outer and inner condenser coil, be sure to clean  
between the coils. Be sure to flush all dirt and debris from the unit  
base.  
ELECTRICAL CONTROLS AND WIRING  
Inspect and check the electrical controls and wiring annually. Be  
sure to turn off the electrical power to the unit and install lockout  
tag.  
Remove access panel to locate all the electrical controls and  
wiring. Check all electrical connections for tightness. Tighten all  
screw connections. If any smoky or burned connections are  
noticed, disassemble the connection, clean all the parts, restrip the  
wire end and reassemble the connection properly and securely.  
After inspecting the electrical controls and wiring, replace the  
access panel. Start the unit, and observe at least one complete  
heating cycle and one complete cooling cycle to ensure proper  
operation. If discrepancies are observed in either or both operating  
cycles, or if a suspected malfunction has occurred, check each  
electrical component with the proper electrical instrumentation.  
Refer to the unit wiring label when making these checkouts.  
Inspect the drain pan and condensate drain line when inspecting  
the coils. Clean the drain pan and condensate drain by removing all  
foreign matter from the pan. Flush the pan and drain tube with  
clear water. Do not splash water on the insulation, motor, wiring,  
or air filter(s). If the drain tube is restricted, clear it with a  
“plumbers snake” or similar probe device. Ensure that the auxiliary  
drain port above the drain tube is also clear  
NOTE: Refer to the heating and/or cooling sequence of operation  
in this publication as an aid in determining proper control  
operation  
CONDENSER FAN  
REFRIGERANT CIRCUIT  
Inspect all refrigerant tubing connections and the unit base for oil  
accumulations annually. Detecting oil generally indicates a refrig-  
erant leak.  
Keep the condenser fan free from all obstructions to ensure  
proper cooling operation. Never place articles on top of the  
unit. Damage to unit may result.  
1. Remove 6 screws holding condenser grille and motor to top  
cover.  
2. Turn motor/grille assembly upside down on top cover to  
expose the fan blade.  
3. Inspect the fan blades for cracks or bends.  
24  
obstructions, and that the air filter is clean. When necessary, refer  
to Indoor Airflow and Airflow Adjustments section to check the  
system airflow.  
System under pressure. Relieve pressure and recover all  
refrigerant before system repair or final unit disposal to avoid  
personal injury or death. Use all service ports and open all  
flow-control devices, including solenoid valves.  
METERING DEVICE — ACUTROL DEVICE  
This metering device is a fixed orifice and is located in the header  
to the evaporator coil.  
If oil is detected or if low cooling performance is suspected,  
leak-test all refrigerant tubing using an electronic leak-detector,  
halide torch, or liquid-soap solution. If a refrigerant leak is  
detected, refer to Check for Refrigerant Leaks section.  
LIQUID LINE STRAINER  
The liquid line strainer (to protect metering device) is made of wire  
mesh and located in the liquid line on the inlet side of the metering  
device.  
If no refrigerant leaks are found and low cooling performance is  
suspected, refer to Checking and Adjusting Refrigerant Charge  
section.  
TROUBLESHOOTING  
Use the Troubleshooting–Cooling guide (see Table 10) if problems  
occur with these units.  
EVAPORATOR AIRFLOW  
START-UP CHECKLIST  
Use the Start-Up checklist to ensure proper start-up procedures are  
followed.  
The heating and/or cooling air-flow does not require checking  
unless improper performance is suspected. If a problem exists, be  
sure that all supply- and return-air grilles are open and free from  
25  
Table 10—Troubleshooting—Cooling  
SYMPTOM  
CAUSE  
Power Failure  
REMEDY  
Call power company  
Fuse blown or circuit breaker tripped  
Replace fuse or reset circuit breaker  
Defective thermostat, contractor, transformer, or  
control relay  
Replace component  
Compressor and condenser fan will not start.  
Insufficient line voltage  
Incorrect or faulty wiring  
Determine cause and correct  
Check wiring diagram and rewire correctly  
Lower thermostat setting below  
room temperature  
Thermostat setting too high  
Faulty wiring or loose connections in compressor  
circuit  
Check wiring and repair or replace  
Compressor motor burned out, seized, or internal  
overload open  
Determine cause  
Compressor will not start but condenser fan  
runs.  
Replace compressor  
Defective run/start capacitor, overload, start relay  
Determine cause and replace  
Replace fuse or reset circuit breaker  
Determine cause  
One leg of 3-phase power dead  
Three-phase scroll compressor (50GS048,  
50GX030-060) makes excessive noise, and  
there may be a low pressure differential.  
Correct the direction of rotation by reversing the  
3-phase power leads to the unit. Shut down unit  
to allow pressures to equalize.  
Scroll compressor is rotating  
in the wrong direction  
Recover refrigerant, evacuate system, and re-  
charge to capacities shown on nameplate  
Refrigerant overcharge or undercharge  
Defective compressor  
Insufficient line voltage  
Blocked condenser  
Replace and determine cause  
Determine cause and correct  
Determine cause and correct  
Compressor cycles  
(other than normally satisfying thermostat).  
Defective run/start capacitor, overload or start  
relay  
Determine cause and replace  
Defective thermostat  
Faulty condenser-fan motor or capacitor  
Restriction in refrigerant system  
Dirty air filter  
Replace thermostat  
Replace  
Locate restriction and remove  
Replace filter  
Unit undersized for load  
Decrease load or increase unit size  
Reset thermostat  
Thermostat set too low  
Low refrigerant charge  
Locate leak, repair, and recharge  
Replace compressor  
Compressor operates continuously.  
Leaking valves in compressor  
Recover refrigerant, evacuate system, and re-  
charge  
Air in system  
Condenser coil dirty or restricted  
Dirty air filter  
Clean coil or remove restriction  
Replace filter  
Dirty condenser coil  
Clean coil  
Refrigerant overcharged  
Recover excess refrigerant  
Excessive head pressure.  
Recover refrigerant, evacuate system, and re-  
charge  
Air in system  
Condenser air restricted or air short-cycling  
Low refrigerant charge  
Determine cause and correct  
Check for leaks, repair and recharge  
Replace compressor  
Head pressure too low.  
Compressor valves leaking  
Restriction in liquid tube  
High heat load  
Remove restriction  
Check for source and eliminate  
Replace compressor  
Excessive suction pressure.  
Compressor valves leaking  
Refrigerant overcharged  
Dirty air filter  
Recover excess refrigerant  
Replace Filter  
Low refrigerant charge  
Check for leaks, repair, and recharge  
Remove source of restriction  
Metering device or low side restricted  
Increase air quantity  
Check filter- replace if necessary  
Suction pressure too low.  
Insufficient evaporator airflow  
Temperature too low in conditioned area  
Outdoor ambient below 40°F  
Reset thermostat  
Install low-ambient kit  
Replace  
Field-installed filter-drier restricted  
26  
START-UP CHECKLIST  
(REMOVE AND STORE IN JOB FILE)  
I. PRELIMINARY INFORMATION  
Model No .............................................................................................................................................................  
Serial No ..............................................................................................................................................................  
Date .....................................................................................................................................................................  
Technician ...........................................................................................................................................................  
Job/ Location...............................................................................................................................................  
II. PRE-START-UP  
____ Verify that all packing materials have been removed from unit  
____ Verify that condensate connection is installed per installation instructions  
____ Check all electrical connections and terminals for tightness  
____ Check that indoor (evaporator) air filter is clean and in place  
____ Verify that unit installation is level  
____ Check fan wheel propeller for location in housing and setscrew tightness  
III. START-UP  
Supply Voltage: L1-L2(C-S) __________ L2-L3(S-R) __________ L3-L1(R-C) __________  
Compressor Amps: L1(C) __________ L2(S) __________ L3(R) __________  
Indoor (Evaporator) Fan Amps: __________  
TEMPERATURE  
Outdoor (Condenser) Air Temperature: __________ DB  
Return-Air Temperature: __________ DB __________ WB  
Cooling Supply Air: __________ DB __________ WB  
PRESSURES  
Refrigerant Suction __________ psig  
Suction Line Temp*__________  
Refrigerant Discharge __________ psig  
Discharge Temp† __________  
____ Verify Refrigerant charge using charging tables  
____ Verify that 3-phase scroll compressor (50GS048 and 50GX030–060) is rotating in correct direction.  
* Measured at suction inlet to compressor  
† Measured at liquid line leaving condenser  
27  
Copyright 2003 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book  
Replaces: 50GS,GX-3SI  
50gsgx4si  
1
6
PC 101  
Catalog No. 535–00130  
Printed in U.S.A.  
Form 50GS,GX-4SI  
Pg 28  
9–03  
Tab 6 8  

Brother DCP 7030 User Manual
Bryant Air Conditioner 552A User Manual
Cornelius 560003870 User Manual
Crown Audio ADDENDUM 28M User Manual
Epson Artisan 810 Series User Manual
Friedrich Air Conditioner CP15 User Manual
Friedrich MW30C3G User Manual
Fujitsu Printer DL7400 User Manual
Goodman Mfg ARUF486016CA User Manual
Haier Air Conditioner AC60FS1ERA User Manual