Carrier 50VL A User Manual

50VL---A  
Performancet 14 SEER Single---Packaged Air Conditioner  
System with Puron® (R---410A) Refrigerant  
Single and Three Phase  
2 --- 5 N o m i n a l To n s ( S i z e s 2 4 --- 6 0 )  
Installation Instructions  
NOTE: Read the entire instruction manual before starting the  
installation.  
NOTE: Installer: Make sure the Owner’s Manual and Service  
Instructions are left with the unit after installation.  
TABLE OF CONTENTS  
PAGE  
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . 1--2  
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
RECEIVING AND INSTALLATION . . . . . . . . . . . . . . . . . 2--10  
Check Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
Identify Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
Inspect Shipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
Provide Unit Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
Roof Curb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
Slab Mount . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
Provide Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7  
Field Fabricate Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7  
Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7  
Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7  
Rigging/Lifting of Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7  
A09033  
Fig. 1 -- Unit 50VL--A  
Connect Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . 8  
Install Duct Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8  
Configuring Units for Downflow (Vertical) Discharge . . . . 8  
Install Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . 9  
High--Voltage Connections . . . . . . . . . . . . . . . . . . . . . . . . . 9  
Special Procedures for 208v Operation . . . . . . . . . . . . . . . 10  
Control Voltage Connections . . . . . . . . . . . . . . . . . . . . . . . 10  
Standard Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10  
Transformer Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . 10  
PRE--START--UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12  
START--UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12--14  
Check for Refrigerant Leaks . . . . . . . . . . . . . . . . . . . . . . . . . 12  
Start--Up Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12  
Checking Cooling Control Operation . . . . . . . . . . . . . . . . 12  
Checking and Adjusting Refrigerant Charge . . . . . . . . . . . 12  
Indoor Airflow and Airflow Adjustments . . . . . . . . . . . . . 13  
Continuous Fan Operation . . . . . . . . . . . . . . . . . . . . . . . . 14  
Cooling Sequence of Operation . . . . . . . . . . . . . . . . . . . . . 14  
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24--26  
Air Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24  
Indoor Blower and Motor . . . . . . . . . . . . . . . . . . . . . . . . . 24  
Outdoor Coil, Indoor Coil, and Condensate Drain Pan . . . 25  
Outdoor Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25  
Electrical Controls and Wiring . . . . . . . . . . . . . . . . . . . . . 25  
Refrigerant Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26  
Evaporator Airflow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26  
Puron Items . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26  
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27  
START--UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27  
SAFETY CONSIDERATIONS  
Improper installation adjustment, alteration, service, maintenance,  
or use can cause explosion, fire, electrical shock, or other  
conditions which may cause death, personal injury, or property  
damage. Consult a qualified installer, service agency, or your  
distributor or branch for information or assistance. The qualified  
installer or agency must use factory--authorized kits or accessories  
when modifying this product Refer to the individual instructions  
packaged with the kits or accessories when installing.  
Follow all safety codes. Wear safety glasses, protective clothing,  
and work gloves. Use quenching cloth for brazing operations.  
Have  
a
fire extinguisher available. Read these instructions  
thoroughly and follow all warnings or cautions included in  
literature and attached to the unit. Consult local building codes, the  
current editions of the National Electrical Code (NEC) NFPA 70.  
In Canada refer to the current editions of the Canadian electrical  
Code CSA C22.1.  
Recognize safety information. This is the safety--alert symbol  
.
When you see this symbol on the unit and in instructions or  
manuals, be alert to the potential for personal injury. Understand  
these signal words; DANGER, WARNING, and CAUTION. These  
words are used with the safety--alert symbol. DANGER identifies  
the most serious hazards which will result in severe personal injury  
or death. WARNING signifies hazards which could result in  
personal injury or death. CAUTION is used to identify unsafe  
practices which may result in minor personal injury or product and  
property damage. NOTE is used to highlight suggestions which  
will result in enhanced installation, reliability, or operation.  
1
A09462  
Fig. 2 -- 50VL--A24--36 Unit Dimensions  
3
A09463  
Fig. 3 -- 50VL--A42--60 Unit Dimensions  
4
Dashed lines show cross support  
location for large basepan units.  
B
G
C
HVAC unit  
basepan  
HVAC unit  
base rails  
Sealing  
Gasket  
Roofcurb  
H
F
A
Anchor screw  
Wood nailer*  
Roofcurb*  
Flashing field  
supplied  
Insulation  
(field supplied)  
Roofing material  
field supplied  
E
D
Cant strip  
field supplied  
A09413  
SMALL/COMMON CURB  
*Provided with roofcurb  
A09090  
ROOF CURB DETAIL  
B
C
SMALL  
BASE  
UNIT  
SUPPLY  
AIR  
G
H
A
LARGE  
BASE  
UNIT  
F
RETURN  
AIR  
E
D
UNIT PLACEMENT ON  
COMMON CURB  
A09094  
A09415  
SMALL OR LARGE BASE UNIT  
LARGE CURB  
A09414  
B
A
B
C
D
E
F
UNIT  
SIZE  
CATALOG  
NUMBER  
G
H
(small/common  
base)  
IN.  
(large base)  
IN. (mm)*  
IN.  
IN.  
IN.  
IN.  
IN. (mm)  
IN. (mm)  
(mm)  
(mm)  
(mm)  
(mm)  
(mm)  
IN. (mm)*  
11  
CPRFCURB010A00  
CPRFCURB011A00  
CPRFCURB012A00  
CPRFCURB013A00  
Small  
or  
(279)  
32.4  
10 (254)  
14 (356)  
30.6 (778)  
(822)  
14  
(356)  
11  
(279)  
14  
(356)  
Large  
16  
(406)  
47.8  
(1214)  
2.7  
(69)  
14 (356)  
46.1 (1170)  
43.9  
(1116)  
Large  
42.2 (1072)  
* Part Numbers CPRCURB010A00 and CPRCURB011A00 can be used on both small and large basepan units. The cross supports must be located based on  
whether the unit is a small basepan or a large basepan.  
NOTES:  
1. Roof curb must be set up for unit being installed.  
2. Seal strip must be applied, as required, to unit being installed.  
3. Roof curb is made of 16--gauge steel.  
4. Attach ductwork to curb (flanges of duct rest on curb).  
5. Insulated panels: 1--in. (25.4 mm) thick fiberglass 1 lb. density.  
Fig. 4 -- Roof Curb Dimensions  
5
CAUTION - NOTICE TO RIGGERS  
PRUDENCE - AVIS AUX MANIPULATEUR  
ACCESS PANELS MUST BE IN PLACE WHEN RIGGING.  
PANNEAUX D'ACCES DOIT ÊTRE EN PLACE POUR MANIPULATION.  
Use top skid as spreader bar. / Utiliser la palette du haut comme barre de répartition  
DUCTS  
MINIMUM HEIGHT: 36" (914.4 mm)  
HAUTEUR MINIMUM  
BANDE SCELLANT DOIT ÊTRE  
EN PLACE AVANT DE PLACER  
L'UNITÉ SUR LA BASE DE TOIT  
SEAL STRIP MUST BE IN  
PLACE BEFORE PLACING  
UNIT ON ROOF CURB  
UNIT HEIGHT  
HAUTEUR D'UNITÉ  
DETAIL A  
VOIR DÉTAIL A  
SEE DETAIL A  
VOIR DÉTAIL A  
50CY502286 2.0  
A09051  
SMALL CABINET  
30  
LARGE CABINET  
24  
36  
kg  
42  
kg  
48  
60  
Unit*  
Unit*  
lb  
kg  
lb  
kg  
lb  
365  
lb  
421  
lb  
kg  
lb  
kg  
Rigging  
Weight  
Rigging  
Weight  
295  
134  
307  
139  
166  
191  
439  
199  
467  
212  
* For 460 volt units, add 14 lb (6.35 kg) to the rigging weight.  
NOTE: See dimensional drawing for corner weighs.  
Fig. 5 -- 50VL--A Unit Suggested Rigging  
6
INSPECTION  
Step 3 — Provide Clearances  
The required minimum service clearances are shown in Fig. 2 and  
3. Adequate ventilation and outdoor air must be provided. The  
outdoor fan draws air through the outdoor coil and discharges it  
through the top fan grille. Be sure that the fan discharge does not  
recirculate to the outdoor coil. Do not locate the unit in either a  
corner or under an overhead obstruction. The minimum clearance  
under a partial overhang (such as a normal house overhang) is 48  
in. (1219 mm) above the unit top. The maximum horizontal  
extension of a partial overhang must not exceed 48 in. (1219 mm)  
IMPORTANT: Do not restrict outdoor airflow. An air restriction  
at either the outdoor--air inlet or the fan discharge may be  
detrimental to compressor life.  
Prior to initial use, and at monthly intervals, all rigging shackles,  
clevis pins, and straps should be visually inspected for any damage,  
evidence of wear, structural deformation, or cracks. Particular  
attention should be paid to excessive wear at hoist hooking points  
and load support areas. Materials showing any kind of wear in  
these areas must not be used and should be discarded.  
!
WARNING  
UNIT FALLING HAZARD  
Failure to follow this warning could result in personal  
injury or death.  
Do not place the unit where water, ice, or snow from an overhang  
or roof will damage or flood the unit. Do not install the unit on  
carpeting or other combustible materials. Slab--mounted units  
should be at least 4 in. (102 mm) above the highest expected water  
and runoff levels. Do not use unit if it has been under water.  
Never stand beneath rigged units or lift over people.  
1. Leave top shipping skid on the unit for use as a spreader bar  
to prevent the rigging straps from damaging the unit. If the  
skid is not available, use a spreader bar of sufficient length  
to protect the unit from damage.  
Step 4 — Field--Fabricate Ductwork  
Secure all ducts to roof curb and building structure on vertical  
discharge units. Do not connect ductwork to unit. For horizontal  
applications, unit is provided with flanges on the horizontal  
openings. All ductwork should be secured to the flanges. Insulate  
and weatherproof all external ductwork, joints, and roof openings  
with counter flashing and mastic in accordance with applicable  
codes.  
!
WARNING  
PROPERTY DAMAGE HAZARD  
Failure to follow this warning could result in personal  
When straps are taut, the clevis should be a minimum of 36  
in. (914 mm) above the unit top cover.  
Ducts passing through an unconditioned space must be insulated  
and covered with a vapor barrier. If a plenum return is used on a  
vertical unit, the return should be ducted through the roof deck to  
comply with applicable fire codes. See unit rating plate for any  
required clearances around ductwork. Cabinet return--air static  
shall not exceed --.25 IN. W.C.  
Step 5 — Rig and Place Unit  
Rigging and handling of this equipment can be hazardous for  
many reasons due to the installation location (roofs, elevated  
structures, etc.).  
Rigging/Lifting of Unit (See Fig. 5)  
!
WARNING  
UNIT FALLING HAZARD  
Failure to follow this warning could result in personal  
injury or death.  
Only trained, qualified crane operators and ground support staff  
should handle and install this equipment.  
Large base units must be secured to common curb before  
allowing full weight of unit to rest on curb. Install screws  
through curb into unit base rails while rigging crane is still  
supporting unit.  
When working with this equipment, observe precautions in the  
literature, on tags, stickers, and labels attached to the equipment,  
and any other safety precautions that might apply.  
Training for operators of the lifting equipment should include, but  
not be limited to, the following:  
Lifting holes are provided in base rails as shown.  
1. Attach shackles, clevis pins, and straps to the base rails of  
the unit. Be sure materials are rated to hold the weight of the  
unit (See Fig. 5).  
2. Attach a clevis of sufficient strength in the middle of the  
straps. Adjust the clevis location to ensure unit is lifted level  
with the ground.  
1. Application of the lifter to the load, and adjustment of the  
lifts to adapt to various sizes or kinds of loads.  
2. Instruction in any special operation or precaution.  
3. Condition of the load as it relates to operation of the lifting  
kit, such as balance, temperature, etc.  
Follow all applicable safety codes. Wear safety shoes and work  
gloves.  
After the unit is placed on the roof curb or mounting pad, remove  
the top skid.  
OPTIONAL  
RETURN  
AIR  
OPTIONAL  
SUPPLY  
AIR  
OPENING  
OPENING  
A
C
MAXIMUM ALLOWABLE  
DIFFERENCE in. (mm)  
B
B-C  
(6.35)  
A-B  
(6.35)  
A-C  
(6.35)  
1/4  
1/4  
1/4  
2˝  
(50.8mm)  
A07925  
Fig. 6 -- Unit Leveling Tolerances  
EVAP. COIL  
COND. COIL  
A07926  
Fig. 7 -- Slab Mounting Detail  
7
Air Conditioning Contractors National Association  
(SMACNA) and Air Conditioning Contractors Association  
(ACCA) minimum installation standards for residential  
heating and air conditioning systems.  
Step 6 — Connect Condensate Drain  
NOTE: When installing condensate drain connection be sure to  
comply with local codes and restrictions.  
Model 50VL--A disposes of condensate water through a 3/4 in.  
NPT fitting which exits through the base on the evaporator coil  
access side. See Fig. 2 and 3 for location.  
5. Secure all ducts to building structure. Flash, weatherproof,  
and vibration--isolate duct openings in wall or roof  
according to good construction practices.  
Condensate water can be drained directly onto the roof in rooftop  
installations (where permitted) or onto a gravel apron in ground  
CONFIGURING UNITS FOR DOWNFLOW  
(VERTICAL) DISCHARGE  
level installations. Install  
a
field--supplied 2--in. (51 mm)  
condensate trap at end of condensate connection to ensure proper  
drainage. Make sure that the outlet of the trap is at least 1 in. (25  
mm) lower than the drain pan condensate connection to prevent the  
pan from overflowing (See Fig. 8). When using a gravel apron,  
make sure it slopes away from the unit.  
Connect a drain tube using a minimum of 3/4 --in. PVC or 3/4 --in.  
copper pipe (all field--supplied) at the outlet end of the 2--in. (51  
mm) trap. Do not undersize the tube. Pitch the drain tube  
downward at a slope of at least 1--in. (25 mm) for every 10 ft (3.1  
m) of horizontal run. Be sure to check the drain tube for leaks.  
Prime trap at the beginning of the cooling season start--up.  
!
WARNING  
ELECTRICAL SHOCK HAZARD  
Failure to follow this warning could result in personal  
injury or death.  
Before performing service or maintenance operations on the  
system, turn off main power to unit and install lockout tag.  
1. Open all electrical disconnects and install lockout tag before  
starting any service work.  
2. Remove horizontal (metal) ductcovers to access vertical  
(downflow) discharge duct knockouts in unit basepan. (See  
Fig. 9.)  
TRAP  
OUTLET  
1-in. (25 mm) min.  
To remove downflow return and supply knockout covers, break  
front and right side connecting tabs with a screwdriver and  
hammer. Push cover down to break rear and left side tabs.  
2-in. (51 mm) min.  
NOTE: These panels are held in place with tabs similar to an  
electrical knockout. Reinstall horizontal duct covers (Fig. 9)  
shipped on unit from factory. Insure openings are air and  
watertight.  
A09052  
Fig. 8 -- Condensate Trap  
NOTE: The design and installation of the duct system must be in  
accordance with the standards of the NFPA for installation of  
nonresidence--type air conditioning and ventilating systems, NFPA  
90A or residence--type, NFPA 90B; and/or local codes and  
ordinances.  
Step 7 — Install Duct Connections  
The design and installation of the duct system must be in  
accordance with the standards of the NFPA for installation of  
non--residence type air conditioning and ventilating systems,  
NFPA 90A or residence type, NFPA 90B and/or local codes and  
ordinances.  
Select and size ductwork, supply--air registers, and return air grilles  
according to ASHRAE (American Society of Heating,  
Refrigeration, and Air Conditioning Engineers) recommendations.  
The unit has duct flanges on the supply-- and return--air openings  
on the side of the unit.  
Adhere to the following criteria when selecting, sizing, and  
installing the duct system:  
1. Units are shipped for side shot installation.  
2. Select and size ductwork, supply--air registers, and  
return--air grilles according to American Society of Heating,  
Refrigeration and Air Conditioning Engineers (ASHRAE)  
recommendations.  
3. Use flexible transition between rigid ductwork and unit to  
prevent transmission of vibration. The transition may be  
screwed or bolted to duct flanges. Use suitable gaskets to  
ensure weather--tight and airtight seal.  
4. All units must have field--supplied filters or accessory filter  
rack installed in the return--air side of the unit.  
Recommended sizes for filters are shown in Table 1.  
5. Size all ductwork for maximum required airflow (either  
heating or cooling) for unit being installed. Avoid abrupt  
duct size increases or decreases or performance may be  
affected.  
6. Adequately insulate and weatherproof all ductwork located  
outdoors. Insulate ducts passing through unconditioned  
space, and use vapor barrier in accordance with latest issue  
of Sheet Metal and Air Conditioning Contractors National  
Association (SMACNA) and Air Conditioning Contractors  
of America (ACCA) minimum installation standards for  
heating and air conditioning systems. Secure all ducts to  
building structure.  
When designing and installing ductwork, consider the following:  
1. All units should have field--supplied filters or accessory  
filter rack installed in the return--air side of the unit.  
Recommended sizes for filters are shown in Table 1.  
2. Avoid abrupt duct size increases and reductions. Abrupt  
change in duct size adversely affects air performance.  
IMPORTANT: Use flexible connectors between ductwork and  
unit to prevent transmission of vibration. Use suitable gaskets to  
ensure weather--tight and airtight seal. When electric heat is  
installed, use fireproof canvas (or similar heat resistant material)  
connector between ductwork and unit discharge connection. If  
flexible duct is used, insert a sheet metal sleeve inside duct. Heat  
resistant duct connector (or sheet metal sleeve) must extend 24--in.  
(610 mm) from electric heater element.  
3. Size ductwork for cooling air quantity (cfm). The minimum  
air quantity for proper electric heater operation is listed in  
Table 2. Heater limit switches may trip at air quantities  
below those recommended.  
4. Seal, insulate, and weatherproof all external ductwork. Seal,  
insulate and cover with a vapor barrier all ductwork passing  
through conditioned spaces. Follow latest Sheet Metal and  
7. Flash, weatherproof, and vibration--isolate all openings in  
building structure in accordance with local codes and good  
building practices.  
8
!
CAUTION  
UNIT COMPONENT DAMAGE HAZARD  
Failure to follow this caution may result in damage to the  
unit being installed.  
1. Make all electrical connections in accordance with  
NFPA 70 (NEC) (latest edition) and local electrical codes  
governing such wiring. In Canada, all electrical  
connections must be in accordance with CSA standard  
C22.1 Canadian Electrical Code Part 1 and applicable  
local codes. Refer to unit wiring diagram.  
2. Use only copper conductor for connections between  
field--supplied electrical disconnect switch and unit. DO  
NOT USE ALUMINUM WIRE.  
3. Be sure that high--voltage power to unit is within  
operating voltage range indicated on unit rating plate. On  
3--phase units, ensure phases are balanced within 2  
percent. Consult local power company for correction of  
improper voltage and/or phase imbalance.  
Horizontal Duct Covers  
A09076  
Basepan  
Downflow  
(Vertical)  
Supply  
4. Do not damage internal components when drilling  
through any panel to mount electrical hardware, conduit,  
etc.  
Basepan  
Downflow  
(Vertical)  
Return  
Knockout  
Knockout  
HIGH-VOLTAGE CONNECTIONS  
The unit must have  
a
separate electrical service with  
a
field--supplied, waterproof disconnect switch mounted at, or within  
sight from the unit. Refer to the unit rating plate, NEC and local  
codes for maximum fuse/circuit breaker size and minimum circuit  
amps (ampacity) for wire sizing.  
A09093  
Fig. 9 -- Supply and Return Duct Opening  
The field--supplied disconnect may be mounted on the unit over  
the high--voltage inlet hole when the standard power and  
low--voltage entry points are used. See Fig. 2 and 3 for acceptable  
location.  
Step 8 — Install Electrical Connections  
!
WARNING  
See unit wiring label (Fig. 12, 13 and 14) and Fig. 10 for reference  
when making high voltage connections. Proceed as follows to  
complete the high--voltage connections to the unit.  
ELECTRICAL SHOCK HAZARD  
Failure to follow this warning could result in personal  
injury or death.  
Single phase units:  
1. Run the high--voltage (L1, L2) and ground lead into the  
control box.  
2. Connect ground lead to chassis ground connection.  
The unit cabinet must have an uninterrupted, unbroken  
electrical ground to minimize the possibility of personal  
injury if an electrical fault should occur. This ground may  
consist of an electrical wire connected to the unit ground  
screw in the control compartment, or conduit approved for  
electrical ground when installed in accordance with NFPA  
70 (NEC) (latest edition) (in Canada, Canadian Electrical  
Code CSA C22.1) and local electrical codes.  
3. Locate the black and yellow wires connected to the line side  
of the contactor.  
4. Connect field L1 to black wire on connection 11 of the  
compressor contactor.  
9
SPECIAL PROCEDURES FOR 208-V OPERATION  
HIGH VOLTAGE  
POWER LEADS  
(SEE UNIT WIRING  
LABEL)  
!
POWER  
SUPPLY  
WARNING  
ELECTRICAL SHOCK HAZARD  
3-PHASE SHOWN  
1-PHASE USES  
TWO POWER  
Failure to follow this warning could result in personal  
injury or death.  
EQUIP GR  
LEADS  
FIELD-SUPPLIED  
FUSED DISCONNECT  
Before installing or servicing system, always turn off main  
power to system and install lockout tag. With disconnect  
switch open, move black wire from transformer (3/16  
in.)(4.8 mm) terminal marked 230 to terminal marked 208.  
This retaps transformer to primary voltage of 208 vac.  
CONTROL BOX  
WHT(W1)  
W1  
VIO (W2)  
W2  
YEL(Y)  
Y
GRN(G)  
CONTROL VOLTAGE CONNECTIONS  
G
LOW-VOLTAGE  
POWER LEADS  
(SEE UNIT  
THERMOSTAT NOTE: Do not use any type of power--stealing thermostat. Unit  
RED(R)  
R
)
(TYPICAL  
control problems may result.  
BRN(C)  
WIRING LABEL)  
C
Use no. 18 American Wire Gage (AWG) color--coded, insulated  
(35°C minimum) wires to make the control voltage connections  
between the thermostat and the unit. If the thermostat is located  
more than 100 ft (30.5 m) from the unit (as measured along the  
control voltage wires), use no. 16 AWG color--coded, insulated  
(35° C minimum) wires.  
BLU (DH)  
DH  
GRA (Y2)  
3-Phase  
Only  
SPLICE BOX  
A09066  
STANDARD CONNECTION  
Fig. 10 -- High-- and Control--Voltage Connections  
Locate the seven (eight for 3--phase) low voltage thermostat leads  
in 24 volt splice box. A gray wire is standard on 3--phase units for  
connection to an economizer. See Fig. 10 for connection diagram.  
Run the low--voltage leads from the thermostat, through the control  
wiring inlet hole grommet (Fig. 2 and 3), and into the low--voltage  
splice box. Provide a drip loop before running wires through panel.  
Secure and strain relief all wires so that they do not interfere with  
operation of unit.  
If an accessory electric heater is installed, low voltage leads from  
heater must be connected to factory supplied control leads from  
Indoor Fan Board P4 connector.  
NOTE: If the unit 24V wires do not have a matching receptacle,  
cut the 24V wires from the electric heater plug, strip the ends, and  
wire nut together to match the schematic connections. If the electric  
heater 24V wires do not have a matching plug, cut the 24V wires  
from the unit receptacle, strip the ends, and wire nut together to  
match the schematic connections.  
5. Connect field wire L2 to yellow wire on connection 23 of  
the compressor contactor.  
Three--phase units:  
1. Run the high--voltage (L1, L2, L3) and ground lead into the  
control box.  
2. Connect ground lead to chassis ground connection.  
3. Locate the black and yellow wires connected to the line side  
of the contactor.  
4. Connect field L1 to black wire on connection 11 of the  
compressor contactor.  
5. Connect field wire L3 to yellow wire on connection 13 of  
the compressor contactor.  
6. Connect field wire L2 to blue wire from compressor.  
Factory wires are provided for electric heat staging W1 and W2  
(W2 and W3 on IFB). If room thermostat has only one stage of  
supplemental heat, connect white and violet wires shown in Fig. 10  
to second stage heat field wire.  
Some electric heaters have four control wires (plus common wire).  
Consult unit wiring diagram and electric heater wiring diagram for  
additional details.  
TRANSFORMER PROTECTION  
The transformer is of the energy--limiting type, however a direct  
short will likely blow a secondary fuse. If an overload or short is  
present, correct overload condition and check for blower fuse on  
Indoor Fan Board. Replace fuse as required with correct size and  
rating.  
10  
Table 1 – Physical Data--Unit 50VL--A  
UNIT SIZE  
24  
30  
36  
42  
48  
60  
NOMINAL CAPACITY (ton)  
2
2 --- 1/2  
3
3 --- 1/2  
4
5
SHIPPING WEIGHT* lb.  
SHIPPING WEIGHT* (kg)  
307  
139  
365  
166  
421  
191  
439  
199  
467  
212  
295  
134  
Scroll  
1
COMPRESSORS  
Quantity  
REFRIGERANT (R---410A)  
Quantity lb  
Quantity (kg)  
6.0  
2.7  
5.6  
2.5  
9.5  
4.3  
8.8  
4.0  
9.4  
4.3  
12.5  
5.7  
REFRIGERANT METERING DEVICE  
TXV  
OUTDOOR COIL  
Rows...Fins/in.  
Face Area (sq ft)  
1...21  
11.9  
1...21  
13.6  
2...21  
15.4  
2...21  
13.6  
2...21  
17.5  
2...21  
21.4  
OUTDOOR FAN  
Nominal Cfm  
2500  
24  
2700  
24  
2800  
24  
609.6  
1/5 (810)  
3000  
26  
660.4  
1/5 (810)  
3200  
26  
660.4  
1/5 (810)  
3600  
26  
660.4  
1/5 (810)  
Diameter in.  
Diameter (mm)  
Motor Hp (Rpm)  
609.6  
609.6  
1/10 (810)  
1/10 (810)  
INDOOR COIL  
Rows...Fins/in.  
Face Area (sq ft)  
3...17  
3.7  
3...17  
3.7  
3...17  
3.7  
3...17  
4.7  
3...17  
4.7  
3...17  
5.7  
INDOOR BLOWER  
Nominal Cooling Airflow (Cfm)  
Size in.  
1600  
11x10  
279.4x254  
1.0 (1075)  
1750  
11x10  
279.4x254  
1.0 (1040)  
800  
1000  
10x10  
254x254  
1/2 (1050)  
1200  
1400  
10x10  
11x10  
11x10  
Size (mm.)  
254x254  
1/2 (1050)  
279.4x254  
3/4 (1000)  
279.4x254  
3/4 (1075)  
Motor HP (RPM)  
HIGH---PRESSURE SWITCH  
(psig) Cut---out Reset (Auto)  
650 +/--- 15  
420 +/--- 25  
L O S S --- O F --- C H A R G E / L O W --- P R E S -  
SURE SWITCH (Liquid Line) (psig)  
cut---out Reset (auto)  
20 +/ --- 5  
45 +/--- 10  
RETURN---AIR FILTERS}  
Throwaway Size in.  
Throwaway Size (mm)  
20x20x1  
508x508x25  
20x24x1  
508x610x25  
24x30x1  
610x762x25  
24x36x1  
610x914x25  
*For 460 volt units add 14 lb (6.35 kg) to the shipping weight.  
{
Required filter sizes shown are based on the larger of the AHRI (Air Conditioning Heating and Refrigeration Institute) rated cooling airflow or the heating air-  
flow velocity of 300 ft/minute for throwaway type or 450 ft/minute for high---capacity type. Air filter pressure drop for non---standard filters must not exceed 0.08  
in. W.C.  
} If using accessory filter rack refer to the filter rack installation instructions  
for correct filter sizes and quantity.  
Table 2 – Minimum Airflow for Safe Electric Heater Operation (CFM)  
SIZE  
Cfm  
24  
800  
30  
36  
42  
48  
60  
1750  
1000  
1200  
1400  
1600  
11  
2. Repair leak following accepted practices.  
PRE--START--UP  
NOTE: Install a filter drier whenever the system has been opened  
for repair.  
!
WARNING  
3. Add a small charge of Puron (R--410A) refrigerant vapor to  
system and leak--test unit.  
4. Recover refrigerant from system and evacuate to 500  
microns if no additional leaks are found.  
ENVIRONMENTAL,  
ELECTRICAL SHOCK HAZARD  
FIRE,  
EXPLOSION,  
Failure to follow this warning could result in personal  
injury or death and/or property damage.  
5. Charge unit with Puron (R--410A) refrigerant, using an  
accurate scale. Refer to unit rating plate for required charge.  
1. Follow recognized safety practices and wear protective  
goggles when checking or servicing refrigerant system.  
2. Relieve and recover all refrigerant from system before  
touching or disturbing compressor plug if refrigerant  
leak is suspected around compressor terminals.  
3. Never attempt to repair soldered connection while  
refrigerant system is under pressure.  
4. Do not use torch to remove any component. System  
contains oil and refrigerant under pressure.  
Step 2 — Start--Up Cooling Section And Make  
Adjustments  
Complete the required procedures given in the Pre--Start--Up  
section before starting the unit. Do not jumper any safety devices  
when operating the unit. Do not operate the unit when the outdoor  
temperature is below 40°F (4°C) (unless accessory low--ambient  
kit is installed). Do not rapid cycle the compressor. Allow 5  
minutes between “on” cycles to prevent compressor damage.  
CHECKING COOLING CONTROL OPERATION  
Start and check the unit for proper cooling control operation as  
follows:  
5. To remove a component, wear protective goggles and  
proceed as follows:  
a. Shut off electrical power to unit and install  
lockout tag.  
1. Place room thermostat SYSTEM switch in OFF position.  
Observe that blower motor starts when FAN switch is  
placed in ON position and shuts down when FAN switch is  
placed in AUTO position.  
2. Place SYSTEM switch in COOL position and FAN switch  
in AUTO position. Set cooling control below room  
temperature. Observe that compressor, condenser fan, and  
evaporator blower motors start. Observe that compressor  
and outdoor fan shut down when control setting is satisfied  
and that indoor blower shuts down after 90 second fan time  
delay expires.  
b. Relieve and reclaim all refrigerant from system  
using both high-- and low--pressure ports.  
c. Cut component connecting tubing with tubing  
cutter and remove component from unit.  
d. Carefully unsweat remaining tubing stubs when  
necessary. Oil can ignite when exposed to torch  
flame.  
Proceed as follows to inspect and prepare the unit for initial  
start--up:  
IMPORTANT: Three--phase, scroll compressors are direction  
oriented. Unit must be checked to ensure proper compressor  
3--phase power lead orientation. If not corrected within 5 minutes,  
the internal protector will shut off the compressor. The 3--phase  
power leads to the unit must be reversed to correct rotation. When  
turning backwards, the difference between compressor suction and  
discharge pressures may be minimal.  
1. Remove all access panels (see Fig. 17).  
2. Read and follow instructions on all DANGER, WARNING,  
CAUTION, and INFORMATION labels attached to, or  
shipped with unit.  
3. Make the following inspections:  
a. Inspect for shipping and handling damages, such as  
broken lines, loose parts, disconnected wires, etc.  
CHECKING AND ADJUSTING REFRIGERANT  
CHARGE  
The refrigerant system is fully charged with Puron (R--410A)  
refrigerant and is tested and factory sealed.  
b. Inspect for oil at all refrigerant tubing connections and  
on unit base. Detecting oil generally indicates a  
refrigerant leak. Leak test all refrigerant tubing  
connections using electronic leak detector, or  
liquid--soap solution. If a refrigerant leak is detected, see  
following Check for Refrigerant Leaks section.  
c. Inspect all field-- and factory--wiring connections. Be  
sure that connections are completed and tight.  
NOTE:  
Adjustment of the refrigerant charge is not required  
unless the unit is suspected of not having the proper Puron  
(R--410A) charge.  
A subcooling charging chart is attached to the inside of the  
compressor access panel (see Fig. 17). The chart includes the  
required liquid line temperature at given discharge line pressures  
and outdoor ambient temperatures.  
An accurate thermocouple-- or thermistor--type thermometer, and a  
gauge manifold are required when using the subcooling charging  
method for evaluating the unit charge. Do not use mercury or small  
dial--type thermometers because they are not adequate for this type  
of measurement.  
d. Ensure wires do not touch refrigerant tubing or sharp  
sheet metal edges.  
e. Inspect coil fins. If damaged during shipping and  
handling, carefully straighten fins with a fin comb.  
4. Verify the following conditions:  
a. Make sure that condensate drain pan and trap are filled  
with water to ensure proper drainage.  
b. Make sure that all tools and miscellaneous loose parts  
have been removed.  
NOTE: Allow system to operate for a minimum of 15 minutes  
before checking or adjusting refrigerant charge.  
START--UP  
Step 1 — Check for Refrigerant Leaks  
Proceed as follows to locate and repair a refrigerant leak and to  
charge the unit:  
IMPORTANT: When evaluating the refrigerant charge, an  
indicated adjustment to the specified factory charge must always be  
very minimal. If a substantial adjustment is indicated, an abnormal  
condition exists somewhere in the cooling system, such as  
insufficient airflow across either coil or both coils.  
1. Locate leak and make sure that refrigerant system pressure  
has been relieved and reclaimed from both high-- and  
low--pressure ports.  
12  
Proceed as follows:  
shipped loose with vinyl caps and are located in the control box,  
near the interface fan board (IFB) (See Fig. 11).  
1. Remove caps from low-- and high--pressure service fittings.  
SINGLE COOLING FAN SPEED SET-UP (Dehumidi-  
fication feature not used)  
To change cooling speed:  
2. Using hoses with valve core depressors, attach low-- and  
high--pressure gauge hoses to low-- and high--pressure  
service fittings, respectively.  
3. Start unit and let run until system pressures stabilize.  
4. Measure and record the following:  
1. Remove the vinyl cap off of the desired speed tap wire  
(Refer to Table 3 for color coding). Add the wet coil  
pressure drop in Table 6 to the system static to determine the  
correct cooling airflow speed in Table 4 that will deliver the  
nominal cooling airflow as listed in Table 1 for each size.  
a. Outdoor ambient--air temperature (°F [°C] db).  
b. Liquid line temperature (°F [°C]) at TXV.  
c. Discharge (high--side) pressure (psig).  
2. Remove the current speed tap wire from the “LOW”  
terminal on the interface fan board (IFB) (See Fig. 11) and  
place vinyl cap over the connector on the wire.  
d. Suction (low--side) pressure (psig) (for reference only).  
5. Using Cooling Charging Charts compare outdoor--air  
temperature (°F [°C] db) with the discharge line pressure  
(psig) to determine desired system operating liquid line  
temperature (See Fig. 15).  
3. Connect the desired speed tap wire to the “LOW” terminal  
on the interface fan board (IFB).  
NOTE: If accessory electric heat is installed, and the electric heat  
fan speed is chosen to be the same as the normal cooling fan speed,  
the dry airflow must meet or exceed the minimum airflow speed  
specified in Table 2 for the specific size unit.  
6. Compare actual liquid line temperature with desired liquid  
line temperature. Using a tolerance of ±2°F (±1.1°C), add  
refrigerant if actual temperature is more than 2°F (1.1°C)  
higher than proper liquid line temperature, or remove  
refrigerant if actual temperature is more than 2°F (1.1°C)  
lower than required liquid line temperature.  
TWO COOLING FAN SPEEDS SET-UP (Dehumidi-  
fication feature used)  
NOTE:  
If the problem causing the inaccurate readings is a  
IMPORTANT: Dehumidification control must open control  
circuit on humidity rise above set point.  
refrigerant leak, refer to Check for Refrigerant Leaks section.  
INDOOR AIRFLOW AND AIRFLOW ADJUST-  
MENTS  
Use of the dehumidification cooling fan speed requires use of  
either a 24 VAC dehumidistat or a thermostat which includes  
control of a 24 VAC dehumidistat connection. In either case, the  
dehumidification control must open the control circuit on humidity  
rise above the dehumidification set point.  
!
CAUTION  
1. Using Fig. 11, move the two pin DEHUM jumper from the  
“STD” position to the “DEHUM” position.  
UNIT OPERATION HAZARD  
Failure to follow this caution may result in unit damage.  
2. Remove fan speed tap wire from the “LOW” terminal on  
the interface fan board (IFB) (See Fig. 11).  
For cooling operation, the recommended airflow is 350 to  
450 cfm for each 12,000 Btuh of rated cooling capacity. For  
heating operation, the airflow must produce a temperature  
rise that falls within the range stamped on the unit rating  
plate.  
3. Determine correct normal cooling fan speed for unit and  
application. Add the wet coil pressure drop in Table 6 to  
the system static to determine the correct cooling airflow  
speed in Table 4 that will deliver the nominal cooling  
airflow as listed in Table 1 for each size.  
NOTE: Be sure that all supply--and return--air grilles are open,  
free from obstructions, and adjusted properly.  
NOTE: If accessory electric heat is installed, the dry  
airflow must meet or exceed the minimum airflow speed  
specified in Table 2 for the specific size unit. The electric  
heat fan speed will be the same as the normal cooling fan  
speed.  
!
WARNING  
ELECTRICAL SHOCK HAZARD  
4. Remove the vinyl cap off of the desired speed tap wire  
(Refer to Table 3 for color coding) for the normal cooling  
fan speed and place desired speed tap wire on “HIGH” on  
the interface board.  
Failure to follow this warning could result in personal  
injury or death.  
Disconnect electrical power to the unit and install lockout  
tag before changing blower speed.  
5. Refer to airflow tables (Table 4) to determine allowable  
speeds for the dehumidification cooling fan speed. In Table  
4, speeds that are not allowed for dehumidification cooling  
are shaded.  
This unit is factory-set up for use with a single cooling fan speed.  
In addition, this unit has the field-selectable capability to run two  
different cooling fan speeds: The rated cooling fan speed (350~400  
CFM/Ton) and an enhanced dehumidification fan speed (As low as  
320 CFM/Ton) for use with either a dehumidistat or a thermostat  
that supports dehumidification.  
6. Remove the vinyl cap off of the desired speed tap wire  
(Refer to Table 3 for color coding) for the dehumidification  
cooling fan speed and place desired speed tap wire on the  
“LOW” connection on the interface board (IFB). Verify  
that static pressure is in the acceptable range for the speed  
tap to be used for dehumidification cooling.  
The cooling speed is marked “LOW” on the interface fan board  
(IFB) (See Fig. 11) . The factory-shipped settings are noted in  
Table 4. There are 4 additional speed tap wires available for use in  
either electric heating or cooling (For color coding on the indoor  
fan motor leads, see Table 3). The additional 4 speed tap wires are  
7. Use any spare vinyl plugs to cap any unused speed tap  
wires.  
13  
Table 3 – Color Coding for Indoor Fan Motor Leads  
Black = High Speed  
HIGH  
QC5  
LOW  
QC4  
COM  
QC3  
Orange = Med--High Speed  
Red = Med Speed  
Pink = Med--Low Speed  
KL  
D2  
KZ  
DCR  
QCR  
QC1  
Blue = Low Speed  
C
R13 C8 R11  
Q1  
07 09 0L0 08  
ALO  
Q3  
AL2  
!
WARNING  
C9  
RL  
C4  
G1  
G2  
01  
ELECTRICAL SHOCK HAZARD  
Failure to follow this warning could result in personal  
injury or death.  
QIL  
Z2 06 04  
A7 R9 AB A15  
F1  
C0  
Z1  
Disconnect electrical power to the unit and install lockout  
tag before changing blower speed.  
U1  
R4  
RL4  
C3  
D5 D3  
C7  
CONTINUOUS FAN OPERATION  
JWZ  
JW5  
QCB  
R3 R5 R6  
P2 JW3  
When the DEHUM feature is not used, the continuous fan speed  
will be the same as cooling fan speed. When the DEHUM feature  
is used, the continuous fan will operate on IFB “LOW” speed  
when the DH control lead is not energized, or IFB “HIGH” speed  
when the DH lead is energized (see Fig. 11).  
R2  
P4  
Y
R
W2  
Y
C
W3 W3 W2 W2  
JW4  
C
SSTZ-8  
COOLING SEQUENCE OF OPERATION  
P1  
Y2  
DH  
Y1  
Y
W3 W2  
G
C
R
With the room thermostat SYSTEM switch in the COOL position  
and the FAN switch in the AUTO position, the cooling sequence of  
operation is as follows:  
A09059  
Fig. 11 -- Interface Fan Board (IFB)  
When the room temperature rises to a point that is slightly above  
the cooling control setting of the thermostat, the thermostat  
completes the circuit between thermostat terminal R to terminals Y  
and G. These completed circuits through the thermostat connect  
contactor coil (C) (through unit wire Y) and time delay relay  
(TDR) (through unit wire G) across the 24--V secondary of  
transformer (TRAN).  
SINGLE SPEED COOLING WITH HIGHER  
ELECTRIC HEAT SPEED  
This unit can also be configured to operate with single speed  
cooling and a higher speed for an accessory electric heater.  
1. Using Fig. 11, move the two pin DEHUM jumper from the  
“STD” position to the “DEHUM” position.  
The normally open contacts of energized contactor (C) close and  
complete the circuit through compressor motor (COMP) to  
condenser (outdoor) fan motor (OFM). Both motors start instantly.  
2. See Table 2 for minimum airflow for electric heat operation.  
Add electric heater and filter pressure drop to duct system  
static pressure to determine total external static pressure.  
A set of normally open contacts on the interface fan board (IFB)  
are closed which energizes a circuit to the indoor fan motor (IFB).  
3. Select speed tap from Table 4 that will achieve required  
airflow from Table 2.  
NOTE: Once the compressor has started and then has stopped, it  
should not be started again until 5 minutes have elapsed.  
4. Remove the vinyl cap off of the desired speed tap wire  
(Refer to Table 3 for color coding).  
5. Connect the desired speed tap wire to the “HIGH” terminal  
on the interface fan board (IFB).  
The cooling cycle remains on until the room temperature drops to a  
point that is slightly below the cooling control setting of the room  
thermostat. At this point, the thermostat breaks the circuit between  
thermostat terminal R to terminals Y and G. These open circuits  
deenergize contactor coil  
C
and IFB. The condenser and  
!
CAUTION  
compressor motors stop. After a 90--second delay, the blower  
motor stops. The unit is in a standby condition, waiting for the next  
call for cooling from the room thermostat.  
UNIT OPERATION HAZARD  
Failure to follow this caution may result in unit component  
damage or improper operation.  
To use this mode, a speed connection must be made on the  
“HIGH” terminal that meets or exceeds the minimum  
airflow found in Table 2.  
14  
15  
16  
A11004  
Fig. 12 -- Connection Wiring Diagram 208/230--1--60  
17  
A11003  
Fig. 12 Cont. -- Ladder Wiring Diagram 208/230--1--60  
18  
A11010  
Fig. 13 -- Connection Wiring Diagram 208/230--3--60  
19  
A11009  
Fig. 13 Cont. -- Ladder Wiring Diagram 208/230--3--60  
20  
CONNECTION WIRING DIAGRAM  
DANGER: ELECTRICAL SHOCK HAZARD DISCONNECT POWER BEFORE SERVICING  
SCHEMATIC  
460-3-60  
IF USED  
CCH  
BLK  
GRN  
RED  
FOR WIRING WITH  
ELECTRIC HEATERS  
SEE SCHEMATIC  
ON HEATER  
FIELD  
SUPPLY  
POWER  
BLK  
BLK  
YEL  
C
1
L1  
OFM  
11  
13  
21  
BLK  
YEL  
UNIT ONLY  
MAXIMUM WIRE  
SIZE 2 AWG.  
ACCESSORY.  
1
L3  
23  
YEL  
CAP  
BRN  
COMPRESSOR PLUG  
T1  
T3  
T2  
1
L2  
BLU  
YEL  
COMP  
EQUIP_GND  
BLK  
BLU  
FU1 5 AMP  
FU2 5 AMP  
SEE NOTE  
YEL  
8
BLK  
RED  
ECON  
PLUG  
L2  
BLK  
GRN-YEL  
GND  
GND  
ECON  
7
6
7
L1  
COM  
PNK  
BLU  
RED YEL  
IFM  
SAT  
6
BLK  
BLK  
BLU  
PNK  
YEL  
C
C
460V  
3
230V  
4
11 11  
10 10  
GRN/YEL  
BRN  
1
2
2
3 4  
5
1
8
2
8
AUTOTRANSFORMER  
460  
GRY  
2
SEE NOTE 5  
&
6
460  
3
4
3
4
RED  
BRN  
BLU  
1
5
1
5
YEL  
TRAN  
9
9
24  
24  
YEL  
12 12  
BRN  
BRN  
BLK  
RED  
SEE NOTE  
4
GRY  
Y2  
TSTAT  
SEE NOTE  
9
SEE NOTE  
7
RED  
BRN  
R
ACCESSSORY ELECTRIC HEAT  
HR1 (5 KW)  
C
1
BRN  
BRN  
WHT  
VIO  
WHT  
1
HR1  
HR4  
3
YEL  
Y1  
BRN  
BRN  
1
VIO  
PNK  
GRY  
1
3
GRN  
BLU  
G
DH  
W2  
IFB  
HR1,2,3  
& 4 (20 KW)  
1
PNK  
GRY  
HR2  
HR3  
BRN  
WHT  
HR1 & 2 (10 KW)  
1
HR1,2 & 3 (15 KW)  
1
BRN  
BRN  
VIO  
W3  
LPS  
HPS  
BLU  
C
C1  
C2  
BLK  
BLU  
BLK  
LEGEND  
UNIT COMPONENT ARRANGEMENT  
C
CONTACTOR  
FIELD SPLICE  
CAP CAPACITOR  
OUTDOOR FAN  
SECTION  
TERMINAL (MARKED)  
CCH CRANK CASE HEATER  
ENERGIZED  
COLOR CODE  
BLK BLACK  
BLU BLUE  
OFM  
COMP COMPRESSOR MOTOR  
DH DEHUMIDIFICATION MODE  
DEHUM DEHUMIDIFICATION MODE  
ECON ECONOMIZER  
TERMINAL (UNMARKED)  
SPLICE (IF USED)  
SPLICE (MARKED)  
FACTORY WIRING  
FIELD CONTROL WIRING  
BRN BROWN  
GRY GRAY  
GRN GREEN  
ORN ORANGE  
PNK PINK  
GND GROUND  
HPS HIGH PRESSURE SWITCH  
HR HEATER RELAY  
COMPRESSOR  
SECTION  
INDOOR FAN  
SECTION  
CONTROL BOX AREA  
21  
23  
FIELD POWER WIRING  
ACCESSORY OR OPTIONAL  
WIRING  
11  
13  
IFB INTERFACE FAN BOARD  
IFM INDOOR FAN MOTOR  
LPS LOW PRESSURE SWITCH  
OFM OUTDOOR FAN MOTOR  
STD STANDARD MODE  
C
RED RED  
LPS  
SINGLE PT.  
CONNECTION  
FOR  
VIO VIOLET  
WHT WHITE  
YEL YELLOW  
TO INDICATE COMMON  
POTENTIAL ONLY:  
NOT TO REPRESENT WIRING  
ELECT.HEAT  
TRAN TRANSFORMER  
NOTES:  
IFM  
HPS  
CAP  
TRAN  
IFB  
1. IF ANY OF THE ORIGINAL WIRES FURNISHED ARE REPLACED,  
IT MUST BE REPLACED WITH TYPE 90 DEGREE C WIRE OR  
IT'S EQUIVALENT.  
2. SEE PRICE PAGES FOR THERMOSTAT AND SUBBASES.  
3. USE 75 DEGREE COPPER CONDUCTORS FOR FIELD INSTALLATION.  
4. REFER TO INSTALLATION INSTRUCTIONS  
C
F
H
COMP  
EQUIP.  
GND  
FOR CORRECT SPEED SELECTION OF IFM.  
5. RELOCATION OF SPEED TAPS MAY BE REQUIRED  
WHEN USING FIELD INSTALLED ELECTRIC HEATERS,  
CONSULT INSTALLATION INSTRUCTIONS TO  
DETERMINE CORRECT SPEED TAP SETTING.  
6. "DO NOT DISCONNECT PLUG UNDER LOAD."  
7. THIS FUSE IS MANUFACTURED BY LITTELFUSE, P/N 257003  
8. THESE FUSES ARE MANUFACTURED BY COOPER BUSSMAN, P/N FNQ-R-5  
9. DEHUM FEATURE CANNOT BE USED WHEN ECONOMIZER IS INSTALLED.  
UNIT FACTORY-SHIPPED IN STD MODE.  
SEE HEATER  
SCHEMATIC  
FOR WIRING  
DISCONNECT  
PER NEC  
C
S
CCH  
R
24V SPLICE  
BOX  
24V POWER ENTRY  
A10204C  
Fig. 14 -- Connection Wiring Diagram 460--3--60  
21  
LADDER WIRING DIAGRAM  
DANGER: ELECTRICAL SHOCK HAZARD DISCONNECT POWER BEFORE SERVICING  
L3  
YEL  
L1  
11  
11  
L2  
G/Y  
BLK  
BLK  
IF USED  
RED  
C
CCH  
21  
23  
BLK  
BLK  
13  
GRN  
YEL  
OFM  
C
R
S
BRN  
YEL  
CAP  
BLU  
YEL  
T2  
T1 T3  
COMP  
BLK  
13  
11  
BLK  
YEL  
L G  
C
NX  
G/Y  
IFM  
460V  
TRAN  
460V  
YEL  
24V  
G/Y  
13  
BLK  
RED  
24V  
SEE NOTE  
7
RED  
24VAC  
IFB  
FUSE  
3A  
P1-1  
P1-2  
RED  
BRN  
YEL  
"R"  
"C"  
R
C
P1-3  
"Y1/Y"  
"G"  
"Y2/DH"  
Y1  
G
DH  
P1-4  
P1-5  
GRN  
BLU  
P1-6  
P1-7  
"W2"  
W2  
W3  
WHT  
VIO  
"W3"  
Y2  
VIO  
P2-1  
P2-2  
P2-3  
P2-4  
LPS  
HPS  
C2  
C1  
Y
BLK  
BLU  
BLU  
C
BLK  
C,TRAN  
BRN  
ACCESSORY  
ELECTRIC HEAT  
BRN  
P4-1  
BRN  
HR1  
HR4  
HR2  
WHT  
VIO  
WHT  
VIO  
BLK  
P4-2  
P4-3  
P4-4  
P4-5  
ECON  
HARNESS  
BRN  
PNK  
GRY  
BRN  
PNK  
GRY  
BRN  
YEL  
2
3
4
HR3  
BRN  
COM C  
BRN  
9
5
6
LOW  
SEE NOTE  
BLU  
BLU  
PNK  
PNK  
SAT  
STD  
BLU  
PNK  
RED  
ORN  
1
2
3
4
5
7
8
C
IFM  
BRN  
DEHUM  
HIGH  
SEE NOTE  
4
BLK  
C
BRN  
RED  
G/Y  
50VL500271  
D
A10204  
Fig. 14 Cont. -- Ladder Wiring Diagram 460--3--60  
22  
A09089  
Fig. 15 -- Cooling Charging Chart  
23  
Air Filter  
MAINTENANCE  
IMPORTANT: Never operate the unit without a suitable air filter  
in the return--air duct system. Always replace the filter with the  
same dimensional size and type as originally installed. See Table 1  
for recommended filter sizes.  
To ensure continuing high performance, and to minimize the  
possibility of premature equipment failure, periodic maintenance  
must be performed on this equipment. This cooling unit should be  
inspected at least once each year by a qualified service person. To  
troubleshoot unit, refer to Table 8, Troubleshooting Chart.  
NOTE TO EQUIPMENT OWNER: Consult your local dealer  
about the availability of a maintenance contract.  
Inspect air filter(s) at least once each month and replace  
(throwaway--type) or clean (cleanable--type) at least twice during  
each cooling season and twice during the heating season, or  
whenever the filter becomes clogged with dust and lint.  
Indoor Blower and Motor  
NOTE: All motors are pre--lubricated. Do not attempt to lubricate  
these motors.  
!
WARNING  
PERSONAL INJURY AND UNIT DAMAGE  
HAZARD  
For longer life, operating economy, and continuing efficiency,  
clean accumulated dirt and grease from the blower wheel and  
motor annually.  
Failure to follow this warning could result in personal  
injury or death and possible unit component damage.  
The ability to properly perform maintenance on this  
equipment requires certain expertise, mechanical skills,  
tools and equipment. If you do not possess these, do not  
attempt to perform any maintenance on this equipment,  
other than those procedures recommended in the Owner’s  
Manual.  
!
WARNING  
ELECTRICAL SHOCK HAZARD  
Failure to follow this warning could result in personal  
injury or death.  
Disconnect and tag electrical power to the unit before  
cleaning the blower motor and wheel.  
!
WARNING  
To clean the blower motor and wheel:  
ELECTRICAL SHOCK AND FIRE HAZARD  
1. Remove and disassemble blower assembly as follows:  
a. Remove blower access panel (see Fig. 17).  
Failure to follow these warnings could result in personal  
injury or death:  
b. Disconnect 5 pin plug and 4 pin plug from indoor  
blower motor. Remove capacitor if required.  
1. Turn off electrical power to the unit and install lockout  
tag before performing any maintenance or service on this  
unit.  
c. On all units remove blower assembly from unit.  
Remove screws securing blower to blower partition and  
slide assembly out. Be careful not to tear insulation in  
blower compartment.  
d. Ensure proper reassembly by marking blower wheel and  
motor in relation to blower housing before disassembly.  
2. Use extreme caution when removing panels and parts.  
3. Never place anything combustible either on or in contact  
with the unit.  
e. Loosen setscrew(s) that secures wheel to motor shaft,  
remove screws that secure motor mount brackets to  
housing, and slide motor and motor mount out of  
housing.  
!
CAUTION  
UNIT OPERATION HAZARD  
2. Remove and clean blower wheel as follows:  
Failure to follow this caution may result in equipment  
damage or improper operation.  
a. Ensure proper reassembly by marking wheel orientation.  
b. Lift wheel from housing. When handling and/or  
cleaning blower wheel, be sure not to disturb balance  
weights (clips) on blower wheel vanes.  
Errors made when reconnecting wires may cause improper  
and dangerous operation. Label all wires prior to  
disconnecting when servicing.  
c. Remove caked--on dirt from wheel and housing with a  
brush. Remove lint and/or dirt accumulations from  
wheel and housing with vacuum cleaner, using soft  
brush attachment. Remove grease and oil with mild  
solvent.  
The minimum maintenance requirements for this equipment are as  
follows:  
1. Inspect air filter(s) each month. Clean or replace when  
necessary.  
2. Inspect indoor coil, drain pan, and condensate drain each  
cooling season for cleanliness. Clean when necessary.  
3. Inspect blower motor and wheel for cleanliness each  
cooling season. Clean when necessary.  
d. Reassemble wheel into housing.  
e. Reassemble motor into housing. Be sure setscrews are  
tightened on motor shaft flats and not on round part of  
shaft. Reinstall blower into unit.  
f. Connect 5 pin plug and 4 pin plug to indoor blower  
motor. Reinstall capacitor if required.  
g. Reinstall blower access panel (see Fig. 17).  
4. Check electrical connections for tightness and controls for  
proper operation each cooling season. Service when  
necessary.  
5. Ensure electric wires are not in contact with refrigerant  
tubing or sharp metal edges.  
3. Restore electrical power to unit. Start unit and check for  
proper blower rotation and motor speeds during cooling  
cycles.  
24  
FAN GRILLE  
MOTOR  
A
MOTOR SHAFT  
A08505  
MAX DISTANCE BETWEEN TOP OF FAN GRILLE AND BOTTOM OF FAN BLADE  
“A”  
SIZE  
IN.  
6.3  
6.3  
7.3  
7.6  
7.6  
7.6  
MM  
160  
160  
185  
193  
193  
193  
24  
30  
36  
42  
48  
60  
Fig. 16 -- Fan Blade Position  
air filter(s). If the drain trough is restricted, clear it with a  
“plumbers snake” or similar probe device.  
OUTDOOR FAN  
!
CAUTION  
UNIT OPERATION HAZARD  
Failure to follow this caution may result in damage to unit  
components.  
Keep the condenser fan free from all obstructions to ensure  
proper cooling operation. Never place articles on top of the  
unit.  
Control  
Access  
Panel  
1. Remove 6 screws holding condenser grille and motor to top  
cover.  
2. Turn motor/grille assembly upside down on top cover to  
expose the fan blade.  
Blower  
Access  
Panel  
Compressor  
Access Panel  
A09214  
Fig. 17 -- Unit Access Panels  
3. Inspect the fan blades for cracks or bends.  
4. If fan needs to be removed, loosen the setscrew and slide the  
fan off the motor shaft.  
5. When replacing fan blade, position blade as shown in Fig.  
16.  
Outdoor Coil, Indoor Coil, and Condensate Drain Pan  
Inspect the condenser coil, evaporator coil, and condensate drain  
pan at least once each year.  
The coils are easily cleaned when dry; therefore, inspect and clean  
the coils either before or after each cooling season. Remove all  
obstructions, including weeds and shrubs, that interfere with the  
airflow through the condenser coil.  
6. Ensure that setscrew engages the flat area on the motor shaft  
when tightening  
7. Replace grille.  
Straighten bent fins with a fin comb. If coated with dirt or lint,  
clean the coils with a vacuum cleaner, using the soft brush  
attachment. Be careful not to bend the fins. If coated with oil or  
grease, clean the coils with a mild detergent and water solution.  
Rinse coils with clear water, using a garden hose. Be careful not to  
splash water on motors, insulation, wiring, or air filter(s). For best  
results, spray condenser coil fins from inside to outside the unit. On  
units with an outer and inner condenser coil, be sure to clean  
between the coils. Be sure to flush all dirt and debris from the unit  
base.  
Inspect the drain pan and condensate drain line when inspecting  
the coils. Clean the drain pan and condensate drain by removing all  
foreign matter from the pan. Flush the pan and drain trough with  
clear water. Do not splash water on the insulation, motor, wiring, or  
Electrical Controls and Wiring  
Inspect and check the electrical controls and wiring annually. Be  
sure to turn off the electrical power to the unit.  
Remove access panels (see Fig. 17) to locate all the electrical  
controls and wiring. Check all electrical connections for tightness.  
Tighten all screw connections. If any smoky or burned connections  
are noticed, disassemble the connection, clean all the parts, restrip  
the wire end and reassemble the connection properly and securely.  
After inspecting the electrical controls and wiring, replace the  
access panels (see Fig. 17). Start the unit, and observe at least one  
complete heating cycle and one complete cooling cycle to ensure  
proper operation. If discrepancies are observed in either or both  
operating cycles, or if a suspected malfunction has occurred, check  
25  
each electrical component with the proper electrical  
instrumentation. Refer to the unit wiring label when making these  
checkouts.  
charge so that pressure gauges read 0 psi (0 Pa). Never open system  
without breaking vacuum with dry nitrogen.  
High-Pressure Switch  
NOTE: Refer to the heating and/or cooling sequence of operation  
in this publication as an aid in determining proper control  
operation  
The high--pressure switch is located in the discharge line and  
protects against excessive condenser coil pressure. It opens at 650  
psig (31.1 kPa). High pressure may be caused by a dirty condenser  
coil, failed fan motor, or condenser air recirculation.  
Refrigerant Circuit  
To check switch:  
Inspect all refrigerant tubing connections and the unit base for oil  
accumulations annually. Detecting oil generally indicates  
refrigerant leak.  
a
1. Turn off all power to unit.  
2. Disconnect leads on switch.  
3. Apply ohmmeter leads across switch. You should have  
continuity on a good switch.  
!
WARNING  
Copeland Scroll Compressor (Puron Refrigerant)  
EXPLOSION, SAFETY AND ENVIRONMENTAL  
HAZARD  
The compressor used in this product is specifically designed to  
operate with Puron (R--410A) refrigerant and cannot be  
interchanged.  
Failure to follow this warning could result in personal  
injury, death or equipment damage.  
The compressor is an electrical (as well as mechanical) device.  
Exercise extreme caution when working near compressors. Power  
should be shut off, if possible, for most troubleshooting techniques.  
Refrigerants present additional safety hazards.  
This system uses Puron (R--410A) refrigerant which has  
higher operating pressures than R--22 and other refrigerants.  
No other refrigerant may be used in this system. Gauge set,  
hoses, and recovery system must be designed to handle  
Puron. If you are unsure, consult the equipment  
manufacturer.  
!
WARNING  
FIRE/EXPLOSION HAZARD  
If oil is detected or if low cooling performance is suspected,  
leak--test all refrigerant tubing using an electronic leak--detector,  
halide torch, or liquid--soap solution. If a refrigerant leak is  
detected, refer to Check for Refrigerant Leaks section.  
Failure to follow this warning could result in personal  
injury or death and/or property damage.  
Wear safety glasses and gloves when handling refrigerants.  
Keep torches and other ignition sources away from  
refrigerants and oils.  
If no refrigerant leaks are found and low cooling performance is  
suspected, refer to Checking and Adjusting Refrigerant Charge  
section.  
The scroll compressor pumps refrigerant throughout the system by  
the interaction of a stationary and an orbiting scroll. The scroll  
compressor has no dynamic suction or discharge valves, and it is  
more tolerant of stresses caused by debris, liquid slugging, and  
flooded starts. The compressor is equipped with a noise reducing  
shutdown device and an internal pressure relief port. The pressure  
relief port is a safety device, designed to protect against extreme  
high pressure. The relief port has an operating range between 550  
(26.3 kPa) and 625 (29.9 kPa) psig differential pressure.  
Evaporator Airflow  
The heating and/or cooling air--flow does not require checking  
unless improper performance is suspected. If a problem exists, be  
sure that all supply-- and return--air grilles are open and free from  
obstructions, and that the air filter is clean. When necessary, refer to  
Indoor Airflow and Airflow Adjustments section to check the  
system airflow.  
Puron Items  
The indoor metering device is a TXV type device.  
Refrigerant  
Pressure Switches  
!
WARNING  
Pressure switches are protective devices wired into the control  
circuit (low voltage). They shut off compressor if abnormally high  
or low pressures are present in the refrigeration circuit. These  
pressure switches are specifically designed to operate with Puron  
(R--410A) systems. R--22 pressure switches must not be used as  
replacements for the Puron (R--410A) air conditioner.  
EXPLOSION, ENVIRONMENTAL HAZARD  
Failure to follow this warning could result in personal  
injury, death or equipment damage.  
This system uses Puron (R--410A) refrigerant which has  
higher operating pressures than R--22 and other refrigerants.  
No other refrigerant may be used in this system. Gauge set,  
hoses, and recovery system must be designed to handle  
Puron. If you are unsure, consult the equipment  
manufacturer.  
Loss of Charge/Low-Pressure Switch (Air Conditioner  
Only)  
This switch is located on the liquid line and protects against low  
suction pressures caused by such events as loss of charge, low  
airflow across indoor coil, dirty filters, etc. It opens on a pressure  
drop at about 20 psig (957 Pa). If system pressure is above this,  
switch should be closed.  
This system uses Puron (R--410A) refrigerant which has higher  
operating pressures than R--22 and other refrigerants. No other  
refrigerant may be used in this system. Gage set, hoses, and  
recovery system must be designed to handle Puron. If you are  
unsure, consult the equipment manufacturer. Failure to use Puron  
compatible servicing equipment or replacement components may  
result in property damage or injury.  
To check switch:  
1. Turn off all power to unit.  
2. Disconnect leads on switch.  
3. Apply ohmmeter leads across switch. You should have  
continuity on a good switch.  
Compressor Oil  
NOTE:  
Because these switches are attached to refrigeration  
The Copeland scroll compressor uses 3MAF POE oil. If additional  
oil is needed, use Uniqema RL32--3MAF. If this oil is not  
available, use Copeland Ultra 32 CC or Mobil Arctic EAL22 CC.  
This oil is extremely hygroscopic, meaning it absorbs water  
system under pressure, it is not advisable to remove this device for  
troubleshooting unless you are reasonably certain that a problem  
exists. If switch must be removed, remove and recover all system  
26  
readily. POE oils can absorb 15 times as much water as other oils  
designed for HCFC and CFC refrigerants. Take all necessary  
precautions to avoid exposure of the oil to the atmosphere.  
Liquid Line Filter Drier  
The filter drier is specifically designed to operate with Puron. Use  
only factory--authorized components. Filter drier must be replaced  
whenever the refrigerant system is opened. When removing a filter  
drier, use a tubing cutter to cut the drier from the system. Do not  
unsweat a filter drier from the system. Heat from unsweating will  
release moisture and contaminants from drier into system.  
Servicing Systems on Roofs with Synthetic Materials  
POE (polyolester) compressor lubricants are known to cause long  
term damage to some synthetic roofing materials. Exposure, even if  
immediately cleaned up, may cause embrittlement (leading to  
cracking) to occur in one year or more. When performing any  
service that may risk exposure of compressor oil to the roof, take  
appropriate precautions to protect roofing. Procedures which risk  
oil leakage include, but are not limited to, compressor replacement,  
repairing refrigerant leaks, replacing refrigerant components such  
as filter drier, pressure switch, metering device, coil, accumulator,  
or reversing valve.  
Puron (R-410A) Refrigerant Charging  
Refer to unit information plate and charging chart. Some R--410A  
refrigerant cylinders contain a dip tube to allow liquid refrigerant to  
flow from cylinder in upright position. For cylinders equipped  
with a dip tube, charge Puron units with cylinder in upright  
position and a commercial metering device in manifold hose.  
Charge refrigerant into suction--line.  
TROUBLESHOOTING  
Refer to the Troubleshooting Chart (Table 10) for troubleshooting  
information.  
Synthetic Roof Precautionary Procedure  
1. Cover extended roof working area with an impermeable  
polyethylene (plastic) drip cloth or tarp. Cover an  
approximate 10 x 10 ft (3 x 3 m) area.  
START--UP CHECKLIST  
Use the Start--Up Checklist at the back of this manual.  
2. Cover area in front of the unit service panel with a terry  
cloth shop towel to absorb lubricant spills, prevent run--offs,  
and protect drop cloth from tears caused by tools or  
components.  
3. Place terry cloth shop towel inside unit immediately under  
component(s) to be serviced and prevent lubricant run--offs  
through the louvered openings in the unit base.  
4. Perform required service.  
5. Remove and dispose of any oil contaminated material per  
local codes.  
27  
Table 10 – Troubleshooting Chart  
SYMPTOM  
CAUSE  
REMEDY  
Call power company  
Power failure  
Fuse blown or circuit breaker tripped  
Replace fuse or reset circuit breaker  
Defective contactor, transformer, control relay, or high--  
pressure, loss--of--charge or low--pressure switch  
Insufficient line voltage  
Incorrect or faulty wiring  
Thermostat setting too low/too high  
Replace component  
Compressor and outdoor fan will not start  
Determine cause and correct  
Check wiring diagram and rewire correctly  
Reset thermostat setting  
Faulty wiring or circuit  
Loose connections in compressor  
Check wiring and repair or replace  
Compressor motor burned out, seized, or  
internal overload open  
Defective run capacitor, overload, or PTC (positive  
temperature coefficient) thermistor  
Determine cause  
Replace compressor  
Compressor will not start but condenser fan  
runs  
Determine cause and replace  
Replace fuse or reset circuit breaker  
Determine cause  
Determine cause and correct  
One leg of 3--phase power dead  
Low input voltage  
Three--phase scroll compressor (size 30--  
60 unit) has a low pressure differential  
Correct the direction of rotation by reversing the  
3--phase power leads to the unit  
Scroll compressor is rotating in the wrong direction  
Recover refrigerant, evacuate system, and re-  
charge to capacities shown on rating plate  
Refrigerant overcharge or undercharge  
Defective compressor  
Insufficient line voltage  
Blocked outdoor coil  
Defective run/start capacitor, overload or start relay  
Faulty outdoor fan motor or capacitor  
Restriction in refrigerant system  
Dirty air filter  
Replace and determine cause  
Determine cause and correct  
Determine cause and correct  
Determine cause and replace  
Replace  
Compressor cycles (other than normally  
satisfying) cooling/heating calls  
Locate restriction and remove  
Replace filter  
Unit undersized for load  
Thermostat temperature set too low  
Low refrigerant charge  
Decrease load or increase unit size  
Reset thermostat setting  
Locate leak, repair, and recharge  
Compressor operates continuously  
Recover refrigerant, evacuate system, and re-  
charge  
Air in system  
Outdoor coil dirty or restricted  
Dirty air filter  
Clean coil or remove restriction  
Replace filter  
Dirty indoor or outdoor coil  
Refrigerant overcharged  
Clean coil  
Recover excess refrigerant  
Recover refrigerant, evacuate system, and re-  
charge  
Excessive head pressure  
Air in system  
Indoor or outdoor air restricted or air short--cycling  
Low refrigerant charge  
Restriction in liquid tube  
Determine cause and correct  
Check for leaks, repair and recharge  
Remove restriction  
Head pressure too low  
Excessive suction pressure  
Refrigerant overcharged  
Dirty air filter  
Recover excess refrigerant  
Replace filter  
Low refrigerant charge  
Metering device or low side restricted  
Insufficient coil airflow  
Temperature too low in conditioned area  
Outdoor ambient below 55°F (13°C)  
Filter drier restricted  
Check for leaks, repair and recharge  
Remove source of restriction  
Check filter–replace if necessary  
Reset thermostat setting  
Install low--ambient kit  
Suction pressure too low  
Replace  
28  
AIR CONDITIONER WITH PURON (R--410A) QUICK REFERENCE GUIDE  
Puron refrigerant operates at 50--70 percent higher pressures than R--22. Be sure that servicing equipment and replacement components are  
designed to operate with Puron. Puron refrigerant cylinders are rose colored.  
S Puron refrigerant cylinders manufactured prior to March 1, 1999, have a dip tube that allows liquid to flow out of cylinder in upright  
position.  
Cylinders manufactured March 1, 1999 and later DO NOT have a dip tube and MUST be positioned upside down to allow liquid to flow.  
S Recovery cylinder service pressure rating must be 400 psig. DOT 4BA400 or DOT BW400.  
S Puron systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose.  
S Manifold sets should be minimum 700 psig high--side and 180 psig low--side with 550 psig low--side retard.  
S Use hoses with minimum 700 psig service pressure rating.  
S Leak detectors should be designed to detect HFC refrigerant.  
S Puron, as with other HFCs, is only compatible with POE oils.  
S Vacuum pumps will not remove moisture from oil.  
S Only use factory specified liquid--line filter driers with rated working pressures no less than 600 psig.  
S Do not install a suction--line filter drier in liquid line.  
S POE oils absorb moisture rapidly. Do not expose oil to atmosphere.  
S POE oils may cause damage to certain plastics and roofing materials.  
S Wrap all filter driers and service valves with wet cloth when brazing.  
S A Puron liquid--line filter drier is required on every unit.  
S Do not use an R--22 TXV.  
S Never open system to atmosphere while it is under a vacuum.  
S When system must be opened for service, break vacuum with dry nitrogen and replace filter driers.  
S Always replace filter drier after opening system for service.  
S Do not vent Puron into the atmosphere.  
S Observe all warnings, cautions, and bold text.  
S Do not leave Puron suction line driers in place for more than 72 hrs.  
29  
START--UP CHECKLIST  
(Remove and Store in Job Files)  
I. PRELIMINARY INFORMATION  
MODEL NO.:  
SERIAL NO.:  
DATE:  
TECHNICIAN:  
II. PRESTART--UP (Insert check mark in box as each item is completed)  
( ) VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT  
( ) REMOVE ALL SHIPPING HOLD DOWN BOLTS AND BRACKETS PER INSTALLATION INSTRUCTIONS  
( ) CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS  
( ) CHECK THAT INDOOR (EVAPORATOR) AIR FILTER IS CLEAN AND IN PLACE  
( ) VERIFY THAT UNIT INSTALLATION IS LEVEL  
( ) CHECK FAN WHEEL, AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS  
III. START--UP  
ELECTRICAL  
SUPPLY VOLTAGE  
COMPRESSOR AMPS  
INDOOR (EVAPORATOR) FAN AMPS  
TEMPERATURES  
OUTDOOR (CONDENSER) AIR TEMPERATURE  
RETURN--AIR TEMPERATURE  
DB  
DB  
WB  
COOLING SUPPLY AIR  
PRESSURES  
DB  
WB  
REFRIGERANT SUCTION  
REFRIGERANT DISCHARGE  
PSIG, SUCTION LINE TEMP*  
PSIG, LIQUID TEMP{  
( ) VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS  
* Measured at suction inlet to compressor  
{
Measured at liquid line leaving condenser.  
Catalog No:50VL---08SI  
Copyright 2011 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231  
Edition Date: 01/11  
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.  
Replaces: 50VL---07SI  
30  

Briggs Stratton 82300 User Manual
Canon PIXMA MP760 User Manual
Carrier LIGHT COMMERCIAL CONDENSING UNITS 38HDL018 060 User Manual
Dakota Digital Led Tail Lights LAT NR112 User Manual
Datalogic Scanning GRYPHONTM DX30 User Manual
Epson STYLUS PRO 9880 User Manual
Epson WF 2540 User Manual
GE General Electric Air Conditioner 3828A User Manual
Honda Automobiles GXV620 User Manual
HP Hewlett Packard CH350 90038 User Manual