Carrier 38TRA User Manual

38TRA  
Air Conditioning Unit  
Installation and Start-Up Instructions  
NOTE: Read the entire instruction manual before starting the  
installation.  
SAFETY CONSIDERATIONS  
Improper installation, adjustment, alteration, service, maintenance,  
or use can cause explosion, fire, electrical shock, or other  
conditions which may cause personal injury or property damage.  
Consult a qualified installer, service agency, or your distributor or  
branch for information or assistance. The qualified installer or  
agency must use factory-authorized kits or accessories when  
modifying this product. Refer to the individual instructions pack-  
aged with the kits or accessories when installing.  
Follow all safety codes. Wear safety glasses and work gloves. Use  
quenching cloth for brazing operations. Have fire extinguisher  
available. Read these instructions thoroughly and follow all  
warnings or cautions attached to the unit. Consult local building  
codes and the National Electrical Code (NEC) for special instal-  
lation requirements.  
Recognize safety information. This is the safety-alert symbol  
.
When you see this symbol on the unit or in instructions and  
manuals, be alert to the potential for personal injury.  
Understand the signal word DANGER, WARNING, or CAU-  
TION. These words are used with the safety-alert symbol. DAN-  
GER identifies the most serious hazards which will result in severe  
personal injury or death. WARNING signifies hazards that could  
result in personal injury or death. CAUTION is used to identify  
unsafe practices which would result in minor personal injury or  
product and property damage.  
A92446  
Fig. 1—Model 38TRA  
clearance on 1 side of unit and 12 in. on all remaining sides must  
be maintained. Maintain a distance of 24 in. between air condi-  
tioners. Position so snow, ice, and water from roof or eaves cannot  
fall directly on unit.  
On rooftop applications, locate unit at least 6 in. above roof  
surface. Where possible, place unit above a load-bearing wall.  
Before installing or servicing system, always turn off main  
power to system. There may be more than 1 disconnect  
switch. Turn off accessory heater power if applicable. Elec-  
trical shock can cause personal injury or death.  
Arrange supporting members to adequately support unit and  
minimize transmission of vibration to building. Consult local  
codes governing rooftop applications.  
Step 3—Replace Indoor AccuRater® Piston, If Required  
INSTALLATION  
Check indoor coil piston to see if it matches the required piston  
shown on unit rating plate. (See Fig. 2.) If it does not match,  
replace indoor coil piston with piston shipped with this unit. The  
piston shipped with outdoor unit is correct for any approved indoor  
coil combination.  
Step 1—Check Equipment and Jobsite  
UNPACK UNIT — Move to final location. Remove carton taking  
care not to damage unit.  
INSPECT EQUIPMENT — File claim with shipping company,  
prior to installation, if shipment is damaged or incomplete. Locate  
unit rating plate on unit corner panel. (See Fig. 2.) It contains  
information needed to properly install unit. Check rating plate to  
be sure unit matches job specifications.  
If unit is to be installed on system with a thermostatic  
expansion valve (TXV), removal of the indoor coil piston is  
required.  
Step 2—Install on a Solid, Level Mounting Pad  
If conditions or local codes require the unit be attached to pad,  
tiedown bolts should be used and fastened through knockouts  
provided in unit base pan. Refer to unit mounting pattern in Fig. 2  
to determine base pan size and knockout hole location.  
When installing, allow sufficient space for airflow clearance,  
wiring, refrigerant piping, and service. Allow 30-in. clearance to  
service end of unit and 48 in. above unit. For proper airflow, a 6-in.  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book  
Tab 3a 2a  
1
4
PC 101  
Catalog No. 563-793  
Printed in U.S.A.  
Form 38TRA-3SI  
Pg 1  
1-94  
Replaces: 38TRA-2SI  
INSTALL SOLENOID VALVE IN LIQUID TUBE  
NOTE:  
AVOID CONTACT BETWEEN TUBING AND STRUCTURE  
INDOOR WALL  
Solenoid valve must be energized during evacuation for  
effective evacuation.  
OUTDOOR WALL  
CAULK  
Before making liquid tube connections, install factory-supplied  
solenoid valve on indoor liquid fitting. (See Fig. 4.) Be sure to use  
flare adapter supplied with the indoor coil when making connec-  
tions.  
INSULATION  
If a field-supplied control power source is needed when  
adding solenoid, wiring must comply with local codes and  
NEC requirements.  
VAPOR LINE  
LIQUID LINE  
THROUGH THE WALL  
1. Remove coil liquid connection cap and discard.  
2. Mount solenoid valve on liquid tube, making sure valve flow  
arrow points toward indoor coil. Mount valve in any position  
except valve body at top and electric coil at bottom. (See Fig.  
4.) The solenoid valve is to be installed a maximum of 24 in.  
from indoor coil.  
JOIST  
HANGER STRAP  
(AROUND VAPOR  
LINE ONLY)  
VAPOR LINE  
3. Braze valve onto end of liquid tube using silver bearing or  
non-silver bearing brazing material. Consult local code re-  
quirements.  
4. Braze flare adapter onto outlet end of the solenoid valve.  
5. Wire solenoid coil into system control circuit as shown in Fig.  
6.  
Table 1—Refrigerant Connections and Recom-  
mended Liquid and Vapor Tube Diameters (In.)  
INSULATION  
1″  
MIN  
LIQUID  
LINE  
LIQUID  
Connect  
VAPOR  
Connect  
UNIT  
SIZE  
Tube  
Tube  
SUSPENSION  
Diameter  
Diameter  
Diameter  
Diameter  
018, 024  
030, 036  
042, 048  
060  
3/8  
3/8  
3/8  
3/8  
3/8  
5/8  
5/8  
3/4  
A92469  
3/8  
3/4  
Fig. 3—Piping Installation  
3/8  
7/8  
7/8  
3/8  
7/8  
1-1/8  
ELECTRICAL JUNCTION  
ELECTRICAL COIL  
Notes: 1. Tube diameters are for lengths up to 50 ft. For tubing lengths greater  
than 50 ft, consult Long-Line Application Guideline.  
2. Do not apply capillary-tube indoor coils to these units.  
REFRIGERANT TUBING — Connect tubing to fittings on out-  
door unit vapor and liquid service valves. (See Fig. 2.)  
A brazing shield MUST be used when tubing sets are being  
brazed to the service valves to prevent damage to the painted  
unit surface.  
Relieve pressure and recover all refrigerant before system  
repair or final unit disposal to avoid personal injury or death.  
Use all service ports and open all flow control devices,  
including solenoid valves.  
VALVE  
FLOW ARROW  
3
STRAIGHT  
/
IN. STUD  
8
NOTE:System flow direction  
must match arrow on  
bottom of body.  
A87044  
Fig. 4—Solenoid Valve Installation  
To avoid valve damage while brazing, service valves must be  
wrapped with a heat-sinking material such as a wet cloth.  
connected by 15 ft of field-supplied or factory-accessory tubing.  
Check refrigerant charge for maximum efficiency. (See Step  
8—Checking Charge.)  
SWEAT CONNECTION — Use refrigerant grade tubing. Service  
valves are closed from factory and ready for brazing. After  
wrapping the service valve with a wet cloth, the tubing set can be  
brazed to the service valve using either silver bearing or non-silver  
3
bearing brazing material. Consult local code requirements. Refrig-  
erant tubing and indoor coil are now ready for leak testing. This  
check should include all field and factory joints.  
Use No. 18 AWG color-coded, insulated (35° C minimum) wire.  
If thermostat is located more than 100 ft from unit (as measured  
along the control voltage wires), use No. 16 AWG color-coded  
wire to avoid excessive voltage drop.  
Step 5—Make Electrical Connections  
Use furnace transformer, fan coil transformer, or accessory trans-  
former for control power, 24-v/40va minimum.  
Be sure field wiring complies with local and national fire, safety,  
and electrical codes, and voltage to system is within limits shown  
on unit rating plate. Contact local power company for correction of  
improper voltage. See unit rating plate for recommended circuit  
protection device. (See Fig. 2.)  
NOTE: Use of available 24-v accessories may exceed the mini-  
mum 40-va power requirement. Determine total transformer load-  
ing and increase the transformer capacity or split the load with an  
accessory transformer as required.  
Step 6—Install Electrical Accessories  
NOTE: Operation of unit on improper line voltage constitutes  
abuse and could affect unit reliability. See unit rating plate.  
Refer to the individual instructions packaged with the kits or  
accessories when installing.  
NOTE: Use only copper wire between disconnect switch and  
unit.  
Step 7—Start-up  
1. Fully back seat (open) liquid and vapor service valves.  
NOTE: Install branch circuit disconnect per NEC of adequate  
size to handle unit starting current, but not larger than maximum  
fuse size shown on unit rating plate. Locate disconnect within sight  
from and readily accessible from unit, per Section 440-14 of NEC.  
2. Unit is shipped with valve stem(s) front seated and caps  
installed. Replace stem caps after system is opened to refrig-  
erant flow (back seated). Replace caps finger tight and tighten  
additional 1/6 turn with wrench.  
ROUTE GROUND AND POWER WIRES — Remove access  
panel and control box cover to gain access to unit wiring. Extend  
wires from disconnect through power wiring hole provided and  
into unit control box. (See Fig. 2.) Size wires per NEC but not  
smaller than minimum wire size shown in presale literature.  
3. Close electrical disconnects to energize system.  
4. Set room thermostat at desired temperature. Be sure set point  
is below indoor ambient temperature.  
5. Set room thermostat at COOL and fan switch at FAN or  
AUTO, as desired. Operate unit for 15 minutes. Check system  
refrigerant charge. (See Step 8—Checking Charge.)  
Step 8—Checking Charge  
The cabinet must have an uninterrupted or unbroken ground  
according to NEC, ANSI/NFPA 70-1993 or local codes to  
minimize personal injury if an electrical fault should occur.  
This may consist of electrical wire or conduit approved for  
electrical ground when installed in accordance with existing  
electrical codes. Failure to follow this warning could result in  
an electrical shock, fire, or death.  
Factory charge is shown on unit rating plate. (See Fig. 2.)  
Do not disable low-pressure switch during a condenser pump  
down. Compressor damage may occur if run at a negative  
suction pressure.  
Compressor damage may occur if system is overcharged.  
To avoid personal injury or death, do not supply power to unit  
with compressor terminal box cover removed.  
Service valve gage ports are not equipped with Schrader  
valves. To prevent personal injury, make sure valves are fully  
back seated before removing gage port caps. Wear safety  
glasses and gloves when handling refrigerant.  
CONNECT GROUND AND POWER WIRES — Connect ground  
wire to ground connection in control box for safety. Connect  
power wiring to contactor as shown in Fig. 5.  
DISCONNECT  
PER N. E. C. AND/OR  
LOCAL CODES  
Adjust charge by following procedure shown on the superheat  
charging tables located on unit information plate.  
CONTACTOR  
FIELD POWER  
WIRING  
Do not vent refrigerant to atmosphere. Recover during system  
repair or final unit disposal.  
CARE AND MAINTENANCE  
FIELD GROUND  
For continuing high performance and to minimize possible equip-  
ment failure, it is essential that periodic maintenance be performed  
on this equipment. Consult your servicing contractor or User’s  
Manual for the proper frequency of maintenance. Frequency of  
maintenance may vary depending upon geographic areas, such as  
coastal applications.  
WIRING  
GROUND  
LUG  
A91056  
Fig. 5—Line Power Connections  
Step 1—Leave User’s Manual With Homeowner  
CONNECT CONTROL WIRING — Route 24-v control wires  
through control wiring grommet and connect to brown and blue  
pigtails supplied in unit splice box. (See Fig. 6.)  
Explain system operation and maintenance procedures outlined in  
User’s Manual.  
4
TRANS  
SEE NOTE 2  
THERMOSTAT  
SUBASE  
TRANS  
MIN 60VA  
4
RH  
RC  
B
LEAVE JUMPER  
ON SUBASE  
(RH TO RC)  
R
LLS  
NC  
LLS  
NC  
Y1  
Y2  
Y
TO IFM LINE  
Y
C
TO IFM LINE  
VOLTAGE  
POWER  
VOLTAGE  
POWER  
SUPPLY  
C
BLU  
BRN  
C
BLU  
COND UNIT  
BRN  
SUPPLY  
G
G
A
IFR  
IFR  
W1  
W2  
HC  
1
HC  
2
W
ARRANGEMENT A–COOLING ONLY  
TRANS  
ARRANGEMENT C–1 TRANSFORMER;  
COOLING AND 2-STAGE HEATING  
:
NOTES 1. REFER TO UNIT LABEL WIRING DIAGRAM FOR  
WIRE COLORS. IFR, IFM AND LLS ARE LOCATED  
INDOORS ON HEATING-COOLING APPLICATIONS.  
IF ACCESSORY IFR IS REQUIRED FOR COOLING-  
ONLY APPLICATIONS, LOCATE IFR IN FAN COIL.  
SEE NOTE 2  
4
ADD JUMPER  
R
LLS  
NC  
2. N.E.C. CLASS 2, 24V CIRCUIT, MIN 40VA REQUIRED.  
– CONTACTOR  
C
Y
HC  
IFM  
LLS  
NC  
– HEATING CONTROL  
– INDOOR FAN MOTOR  
– LIQUID LINE SOLENOID VALVE  
– NORMALLY CLOSED  
TO IFM LINE  
VOLTAGE  
POWER  
SUPPLY  
C
TRANS – TRANSFORMER  
BLU  
BRN  
G
A
IFR  
W
HC  
ARRANGEMENT B – 1 TRANSFORMER;  
COOLING AND 1-STAGE HEATING  
A93199  
Fig. 6—24-V Control Circuit Connector  
5
Copyright 1993 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231  
33026c  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book  
Tab 3a 2a  
1
4
PC 101  
Catalog No. 563-793  
Printed in U.S.A.  
Form 38TRA-3SI  
Pg 6  
1-94  
Replaces: 38TRA-2SI  

Briggs Stratton Automobile Parts User Manual
Bryant 342S User Manual
Bryant 664A User Manual
Canon Wireless Photo All In One 4502B017 User Manual
Daewoo DPB 280LH User Manual
Friedrich KS15 User Manual
Goodman Mfg 13 SEER GPC13M User Manual
Haier HSU 07HS03 User Manual
Hollywood Sport Rider HR1000 User Manual
HP Hewlett Packard HP StorageWorks Disk Array XP operating system configuration manual XP12000 User Manual