Carrier 30GX080 265 User Manual

30GX-4SB  
30GX080-265  
AIR-COOLED LIQUID CHILLER  
— PERFORMANCE DATA  
— CERTIFIED DIMENSION PRINT  
— FIELD WIRING DIAGRAM  
1997 Carrier Corporation • Syracuse, New York 13221  
Form 30GX-4SB Supersedes 30GX-3SB  
Printed in U.S.A.  
12-97  
Catalog No. 513-450  
CUT ALONG DOTTED LINE  
CUT ALONG DOTTED LINE  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
CERTIFIED DIMENSION PRINT  
CERTIFIED DIMENSION PRINT  
CUT ALONG DOTTED LINE  
CUT ALONG DOTTED LINE  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
CERTIFIED DIMENSION PRINT  
CERTIFIED DIMENSION PRINT  
CUT ALONG DOTTED LINE  
CUT ALONG DOTTED LINE  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
CERTIFIED DIMENSION PRINT  
CERTIFIED DIMENSION PRINT  
TOTAL OPERATING  
WEIGHT  
TOTAL OPERATING  
WEIGHT  
UNIT  
30GX  
Aluminum Fin  
Copper Fin  
lb  
kg  
lb  
kg  
205  
225  
12,184  
12,364  
5,538  
5,620  
13,569  
13,749  
6,168  
6,250  
NOTES:  
1. Unit must have clearances for air flow as follows:  
Top — Do not restrict in any way  
Ends — (1524 mm) 5 ft (from solid surface)  
Sides — (1829 mm) 6 ft  
2. Unit with sound hoods requires clearances for air flow as  
follows:  
Top — Do not restrict in any way  
Ends — (1829 mm) 6 ft  
Sides — (2134 mm) 7 ft  
3. Center of gravity shown is for aluminum fin coil. See instal-  
lation instructions for all other values.  
CUT ALONG DOTTED LINE  
CUT ALONG DOTTED LINE  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
CERTIFIED DIMENSION PRINT  
TOTAL OPERATING TOTAL OPERATING  
WEIGHT  
WEIGHT  
UNIT  
30GX  
Aluminum Fin  
Copper Fin  
lb  
kg  
lb  
kg  
206  
226  
250  
12,794  
12,974  
13,194  
5,815  
5,897  
5,997  
14,462  
14,642  
14,862  
6,574  
6,655  
6,755  
NOTES:  
1. Unit must have clearances for air flow as follows:  
Top — Do not restrict in any way  
Ends — (1524 mm) 5 ft (from solid surface)  
Sides — (1829 mm) 6 ft  
2. Unit with sound hoods requires clearances for air flow  
as follows:  
Top — Do not restrict in any way  
Ends — (1829 mm) 6 ft  
Sides — (2134 mm) 7 ft  
3. Center of gravity shown is for aluminum fin coil. See in-  
stallation instructions for all other values.  
CERTIFIED DIMENSION PRINT  
TOTAL OPERATING  
WEIGHT  
TOTAL OPERATING  
WEIGHT  
UNIT  
30GX  
Aluminum Fin  
Copper Fin  
lb  
kg  
lb  
kg  
251  
265  
13,774  
13,829  
6,621  
6.286  
15,549  
15,604  
7,068  
7,093  
NOTES:  
1. Unit must have clearances for air flow as follows:  
Top — Do not restrict in any way  
Ends — (1524 mm) 5 ft (from solid surface)  
Sides — (1829 mm) 6 ft  
2. Unit with sound hoods requires clearances for air flow  
as follows:  
Top — Do not restrict in any way  
Ends — (1829 mm) 6 ft  
Sides — (2134 mm) 7 ft  
3. Center of gravity shown is for aluminum fin coil. See  
installation instructions for all other values.  
CUT ALONG DOTTED LINE  
CUT ALONG DOTTED LINE  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
FIELD WIRING DIAGRAM  
NOTES:  
LEGEND  
1. Factory wiring is in accordance with National Electrical Code (NEC). Field modifica-  
tions or additions must be in compliance with all applicable codes.  
2. Wiring for main field power supply must be rated 75° C minimum. Use copper for all  
units. Maximum incoming wire size for each terminal block is 500 kcmil.  
3. Power for control circuit should be supplied from a separate source through a field  
supplied fused disconnect with 30 amp maximum protection for 115 volt control circuits  
and 15 amp maximum protection for 230 volt control circuit. Connect control circuit  
power to terminals 1 and 2 of TB4. Connect neutral side of supply to terminal 2 of TB4.  
Control circuit conductors for all units must be coppr only. 380/415 control power wired  
at factory. Requires field supplied neutral connection.  
CCN  
Carrier Comfort Network  
CWFS  
CWP  
Chilled Water Flow Switch  
Chilled Water Pump  
CWPI  
EQUIP  
GND,GRD  
TB  
Chilled Water Pump Interlock  
Equipment  
Ground  
Terminal Block  
Field Power Wiring  
Field Control Wiring  
Factory Installed Wiring  
4. Terminals 13 and 14 of TB2 are for field external connection for remote ON-OFF. The  
contacts must be rated for dry circuit application capable of handling a 24 vac to 50 mA  
load.  
5. Terminals 11 and 12 of TB2 are for chilled water flow switch (CWFS) and chilled water  
pump interlock (CWPI) functions. The contacts must be rated for dry circuit application  
capable of handling a 24 vac to 50 mA load.  
6. Terminals T3 and T4 on relay board are for chilled water pump. The maximum load  
allowed for the chilled water pump relay is 125 va sealed, 1250 va inrush at 115 or  
230 volt.  
FIELD WIRING DIAGRAM  
NOTES:  
LEGEND  
Carrier Comfort Network  
1. Factory wiring is in accordance with National Electrical Code (NEC). Field modifi-  
cations or additions must be in compliance with all applicable codes.  
2. Wiring for main field power supply must be rated 75° C minimum. Use copper for  
all units. Maximum incoming wire size for each terminal block is 500 kcmil.  
3. Power for control circuit should be supplied from a separate source through a field  
supplied fused disconnect with 30 amp maximum protection for 115 volt control  
circuits and 15 amp maximum protection for 230 volt control circuit. Connect con-  
trol circuit power to terminals 1 and 2 of TB4. Connect neutral side of supply to  
terminal 2 of TB4. Control circuit conductors for all units must be coppr only. 380/  
415 control power wired at factory. Requires field supplied neutral connection.  
4. Terminals 13 and 14 of TB2 are for field external connection for remote ON-OFF.  
The contacts must be rated for dry circuit application capable of handling a 24 vac  
to 50 mA load.  
CCN  
TB  
Terminal Block  
CWFS  
CWP  
CWPI  
EQUIP  
GND  
Chilled Water Flow Switch  
Chilled Water Pump  
Chilled Water Pump Interlock  
Equipment  
Field Power Wiring  
Field Control Wiring  
Factory Installed Wiring  
Ground  
5. Terminals 11 and 12 of TB2 are for chilled water flow switch (CWFS) and chilled  
water pump interlock (CWPI) functions. The contacts must be rated for dry circuit  
application capable of handling a 24 vac to 50 mA load.  
6. Terminals T3 and T4 on relay board are for chilled water pump. The maximum load  
allowed for the chilled water pump relay is 125 va sealed, 1250 va inrush at 115 or  
230 volt. Minimum load required is 25 va sealed.  

Admiral AAW 05CM1FHU User Manual
Carrier 48TM007 012 User Manual
Cornelius 318949000 User Manual
Epson Stylus CX9400Fax User Manual
Frigidaire HOME COMFORT FRA054XT7 User Manual
GE ASQ10AL User Manual
Graco UltraClear 2755B User Manual
Havis Shields C SM MMP User Manual
Honeywell Automobile Parts ALF502R User Manual
HP Hewlett Packard Hewlett Packard All in One Printer L1908W User Manual