Bryant R 410A 583B User Manual

installation, start-up,  
583B  
Sizes  
030-060  
and operating instructions  
3-PHASE SINGLE PACKAGE  
GAS HEATING/AIR CONDITIONERS  
WITH PURON® (R-410A) REFRIGERANT  
Cancels: New  
II 583B-30-1  
2-06  
Low NOx Models Available  
NOTE: Read the entire instruction manual before starting the  
installation.  
Index  
Page  
SAFETY CONSIDERATIONS.....................................................1  
RULES FOR SAFE INSTALLATION AND OPERATION....1-2  
RECEIVING AND INSTALLATION ..........................................2  
CHECK EQUIPMENT ..................................................................2  
PROVIDE UNIT SUPPORT.........................................................2  
Roof Curb..................................................................................2  
Slab Mount................................................................................2  
Ground Mount...........................................................................2  
FIELD FABRICATE DUCTWORK..........................................2-3  
PROVIDE CLEARANCES........................................................4-7  
RIG AND PLACE UNIT...........................................................7-8  
CONNECT CONDENSATE DRAIN ...........................................8  
INSTALL FLUE HOOD ...............................................................8  
INSTALL GAS PIPING............................................................... 9  
INSTALL DUCT CONNECTIONS..................................... 10-11  
INSTALL ELECTRICAL CONNECTIONS.........................12-14  
High-Voltage Connections......................................................12  
Special Procedures for 208-V Operation ...............................12  
Control Voltage Connections .................................................13  
Standard Connection...............................................................13  
Heat Anticipator Setting....................................................13-14  
Transformer Protection...........................................................14  
PRE-START-UP......................................................................... 14  
START-UP ............................................................................ 14-23  
MAINTENANCE....................................................................23-27  
REFRIGERANT SYSTEM..........................................................27  
QUICK REFERENCE GUIDE....................................................28  
TROUBLESHOOTING......................................................... 29-31  
START-UP CHECKLIST............................................................32  
C99087  
Fig. 1—Unit 583B  
RULES FOR SAFE INSTALLATION AND OPERATION  
WARNING: Improper installation, adjustment, alter-  
ation, service, maintenance, or use can cause carbon  
monoxide poisoning, fire, or an explosion which can  
result in serious injury or unit damage. Consult a quali-  
fied installer, service agency, or gas supplier for infor-  
mation or assistance. The qualified installer or agency  
must use only factory-authorized kits or accessories when  
modifying this product.  
NOTE TO INSTALLER — Before the installation, READ  
THESE INSTRUCTIONS CAREFULLY AND COMPLETELY.  
Also, make sure the User’s Manual and Replacement Guide are  
left with the unit after installation. the furnace is NOT to be used  
for temporary heating of buildings or structures under construc-  
tion.  
Understand the signal words —DANGER, WARNING, and  
CAUTION. DANGER identifies the most serious hazards which  
will result in severe serious injury or death. WARNING indicates  
a condition that could result in serious injury or death. CAUTION  
is used to identify unsafe practices which would result in minor or  
moderate injury or product and property damage.  
SAFETY CONSIDERATIONS  
Installation and servicing of air-conditioning equipment can be  
hazardous due to system pressure and electrical components. Only  
trained and qualified personnel should install, repair, or service  
air-conditioning equipment.  
The power supply (volts, phase, and hertz) must correspond to that  
specified on unit rating plate.  
The electrical supply provided by the utility must be sufficient to  
handle load imposed by this unit.  
Untrained personnel can perform basic maintenance functions of  
cleaning coils and filters. All other operations should be performed  
by trained service personnel. When working on air-conditioning  
equipment, observe precautions in the literature, tags and labels  
attached to the unit, and other safety precautions that may apply.  
This installation must conform with local building codes and with  
NEC (National Electrical Code) and NFPA 70, NFPA 54/ANSI  
Z223.1 latest revision, and NFGC (National Fuel Gas Code). Refer  
to provincial and local plumbing or waste water codes and other  
applicable local codes.  
Follow all safety codes. Wear safety glasses and work gloves. Use  
quenching cloth for unbrazing operations. Have fire extinguisher  
available for all brazing operations.  
Approved for outdoor installation on wood flooring or on class A,  
B or C roof covering materials.  
—1—  
6
C
46 3/16  
44 5/16  
B
D
17 3/8  
TYP.  
1 TYP.  
7/8  
3
13/16  
SUPPORT B  
A
B
SUPPORT A (2)  
2
SIDE  
(2)  
END VIEW  
END  
(2)  
DECK PAN (INSULATED)  
A99320  
Fig. 4—Roof Curb Dimensions  
Top View  
SIDE PANEL  
0.75"  
BASE PAN  
BOTTOM SUPPLY  
4.0"  
3.0"  
SUPPORT RIB(S)  
SEAL STRIP  
(FACTORY SUPPLIED)  
COUNTER FLASHING  
(FIELD SUPPLIED)  
NAILER  
ROOFING FELT  
(FIELD SUPPLIED)  
INSULATION  
(FIELD SUPPLIED)  
CANT STRIP  
(FIELD SUPPLIED)  
ROOFING MATERIAL  
(FIELD SUPPLIED)  
A99340  
Fig. 5—Roof Curb Dimensions  
Side View  
—3—  
TABLE 1—ROOF CURB DIMENSIONS  
A
B
C
D
UNIT SIZE  
583B030-036  
583B042-060  
ODS ORDER NUMBER  
IN. (MM)  
8 (203)  
14 (356)  
8 (203)  
14 (356)  
IN. (MM)  
IN. (MM)  
IN. (MM)  
CPRFCURB006A00  
CPRFCURB007A00  
CPRFCURB008A00  
CPRFCURB009A00  
11 27/32 (301)  
11 27/32 (301)  
15 27/32 (402)  
15 27/32 (402)  
30 5/8 (778)  
30 5/8 (778)  
42 1/8 (1070)  
42 1/8 (1070)  
28 3/4 (730)  
28 3/4 (730)  
40 1/4 (1022)  
40 1/4 (1022)  
ROOF  
CURB  
Notes:  
1. Roof curb must be set up for unit being installed.  
2. Seal strip must be applied as required to unit being installed.  
3. Dimensions in ( ) are in millimeters.  
4. Roof curb is made of 16 gauge steel.  
5. Table lists only the dimensions per part number that have changed.  
6. Attach ductwork to curb (flanges of duct rest on curb).  
7. Insulated panels: 1-in. thick fiberglass 1 lb. density.  
8. Dimensions are in inches.  
IV. PROVIDE CLEARANCES  
WARNING:  
The required minimum operating and service clearances are shown  
in Fig. 6 and 7. Adequate combustion, ventilation, and condenser  
air must be provided, in accordance with section 5.3, Air for  
Combustion and Ventilation, of the National Fuel Gas Code ANSI  
(American National Standards Institute) Z223.1 (in Canada, sec-  
tions 7.2, 7.3 or 7.4 or Can/CGA (Canadian Gas Association)  
B149 Installation Codes), or applicable provisions of local build-  
ing code.  
Never exceed 200 lbs. per bracket lifting force.  
Accessory lifting kit is only to be used with Small  
Packaged units which have a composite base pan with  
molded hand holds.  
Never stand beneath rigged units or lift over people.  
Lifting point should be directly over the center of gravity  
for the unit.  
A dropped unit could cause serious injury or death.  
CAUTION: Do not restrict condenser airflow. An air  
restriction at either the outdoor-air inlet or the fan  
discharge can be detrimental to compressor life.  
INSPECTION — Prior to initial use, and at monthly intervals, all  
rigging brackets and straps should be visually inspected for any  
damage, evidence of wear, structural deformation, or cracks.  
Particular attention should be paid to excessive wear at hoist  
hooking points and load support areas. Brackets or straps showing  
any kind of wear in these areas must not be used and should be  
discarded.  
The condenser pulls air through the condenser coil and discharges  
it through the top cover. Be sure that the fan discharge does not  
recirculate to the condenser coil. Do not locate the unit in either a  
corner or under an overhead obstruction. The minimum clearance  
under a partial overhang (such as a normal house overhang) is  
48-in. above the unit top. The maximum horizontal extension of a  
partial overhang must not exceed 48 inches.  
INSTALLATION:  
1. Position the lifting bracket assembly around the base of the  
unit. Leave the top shipping skid on the unit to act as a  
spreader bar. Be sure the strap does not twist.  
2. Place each of the four (4) metal lifting brackets into the  
handholds in the composite pan.  
Do not place the unit where water, ice, or snow from an overhang  
or roof will damage or flood the unit. Do not install the unit on  
carpeting, tile, or other combustible materials. The unit may be  
installed on wood flooring or on Class A, B, or C roof covering  
materials.  
3. Tighten the ratchet strap until tight. Lifting brackets should  
be secure in the handholds.  
4. Attach the clevis or hook of sufficient strength to hole in the  
lifting bracket as shown in Fig. 8.  
V. RIG AND PLACE UNIT  
5. Attach safety straps directly to the field supplied rigging  
straps or clevis clip. Do not attach the safety straps to the  
lifting brackets.  
Rigging and handling of this equipment can be hazardous for many  
reasons due to the installation location (roofs, elevated structures,  
etc.).  
6. Use the top of the unit as a spreader bar to prevent the  
rigging straps from damaging the unit. If the wood top is not  
available, use a spreader bar of sufficient length to not  
damage the unit.  
Only trained, qualified crane operators and ground support staff  
should handle and install this equipment.  
When working with this equipment, observe precautions in the  
literature, on tags, stickers and labels attached to the equipment,  
and any other safety precautions that might apply.  
VI. CONNECT CONDENSATE DRAIN  
NOTE: When installing condensate drain connection be sure to  
comply with local codes and restrictions.  
Training for operations of the lifting equipment should include, but  
NOT be limited to the following:  
The 583B units dispose of condensate water through a 3/4 in. NPT  
fitting which exits through the compressor access panel. See Fig.  
6 and 7 for location.  
1. Application of the lifter to the load and adjustment of the  
lifts, if any, that adapts it to various sizes or kinds of loads.  
Condensate water can be drained directly onto the roof in rooftop  
installations (where permitted) or onto a gravel apron in ground-  
level installations. Install a field-supplied condensate trap at end of  
condensate connection to ensure proper drainage. Make sure that  
the outlet of the trap is at least 1 in. lower than the drain pan  
condensate connection to prevent the pan from overflowing. See  
Fig. 9. Prime the trap with water. When using a gravel apron, make  
sure it slopes away from the unit.  
2. Instruction in any special operation or precaution.  
3. Condition of the load itself, required for operation of the  
lifting kit, such as balance, temperature, etc.  
Follow all applicable safety codes. Wear safety shoes and work  
gloves.  
—4—  
REQ’D CLEARANCES FOR OPERATION AND SERVICING. in. (mm)  
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)  
Top of unit .  
Evaporator coil access side .  
Power entry side (except for NEC requirements) .  
Unit top  
Side opposite ducts  
Duct panel  
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
. 36 (914)  
. 36 (914)  
. 48 (1219)  
. 36 (914)  
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
. 14 (355.6)  
Duct side of unit  
Side opposite ducts .  
Bottom of unit .  
.
.
.
. 2 (50.8)  
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
. 14 (355.6)  
. 0.50 (12.7)  
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
(304.8)*  
.
.
.
.
. 12  
Flue Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36 (914.4)  
NEC REQ’D CLEARANCES. in. (mm)  
Between units, power entry side  
Unit and ungrounded surfaces, power entry side .  
*Minimum distances: If unit is placed less than 12 in. (304.8 mm) from wall  
system, then the system performance may be compromised.  
LEGEND  
CG - Center of Gravity  
COND - Condenser  
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
. 42 (1066.8)  
.
.
.
.
.
.
.
. 36 (914)  
Unit and block or concrete walls and other grounded  
surfaces, control box side  
.
.
.
.
.
.
.
.
.
.
.
. 42 (1066.8)  
EVAP - Evaporator  
NEC - National Electrical Code  
REQ'D - Required  
Note: Dimensions are in in. (mm)  
C99017  
CENTER OF GRAVITY  
IN. (MM)  
UNIT HEIGHT  
IN. (MM)  
UNIT WEIGHT  
ELECTRICAL  
CHARACTERISTICS  
UNIT  
"A"  
lb.  
kg.  
X
Y
Z
583B030040/060  
583B036060/090  
208/230-3-60  
313.0  
142.0  
39.02 (991.1)  
22.0 (558.8)  
15.3 (387.4)  
17.6 (447.0)  
208/230-3-60,  
460-3-60  
321.0  
145.6  
35.02 (889.5)  
22.0 (558.8)  
15.3 (387.4)  
16.5 (419.1)  
Fig. 6—583B030, 036 Unit Dimensions  
—5—  
REQUIRED CLEARANCE FOR OPERATION AND SERVICING  
REQUIRED CLEARANCE TO COMBUSTIBLE MATL.  
in. [mm]  
in. [mm]  
EVAP. COIL ACCESS SIDE..............................................................36.00 [914.0]  
POWER ENTRY SIDE......................................................................36.00 [914.0]  
(EXCEPT FOR NEC REQUIREMENTS)  
TOP OF UNIT...................................................................................14.00 [355.6]  
DUCT SIDE OF UNIT.........................................................................2.00 [50.8]  
SIDE OPPOSITE DUCTS ................................................................14.00 [355.6]  
BOTTOM OF UNIT.............................................................................0.50 [12.7]  
UNIT TOP.........................................................................................36.00 [914.0]  
SIDE OPPOSITE DUCTS ................................................................36.00 [914.0]  
DUCT PANEL ...................................................................................12.00 [304.8] *  
FLUE HEAT PANEL  
*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 12.00 [304.8] FROM  
WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE.  
.................................................................36.00 [914.4]  
NEC. REQUIRED CLEARANCES.  
in. [mm.]  
BETWEEN UNITS, POWER ENTRY SIDE....................................42.00 [1066.8]  
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE ...36.00 [914.0]  
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER  
GROUNDED SURFACES, POWER ENTRY SIDE.........................42.00 [1066.8]  
FLUE HOOD  
C99074  
CENTER OF GRAVITY  
IN. (MM)  
UNIT HEIGHT  
IN. (MM)  
"A"  
UNIT WEIGHT  
ELECTRICAL  
CHARACTERISTICS  
UNIT  
lb.  
kg.  
X
Y
Z
208/230-3-60  
460-3-60  
583B042060/090  
583B048090/115/130  
583B060090/115/130  
382  
173.3  
38.98 (990.2)  
38.98 (990.2)  
42.98 (1091.7)  
23.0 (584.2)  
21.5 (546.1)  
23.5 (596.9)  
16.3 (412.8)  
16.6 (422.1)  
16.3 (412.8)  
16.6 (421.6)  
208/230-3-60  
460-3-60  
421  
468  
191.0  
212.3  
18.0 (457.2)  
17.6 (447.0)  
208/230-3-60,  
460-3-60  
Fig. 7—583B042-060 Unit Dimensions  
—6—  
DETAIL A  
A05179  
MAXIMUM WEIGHT  
A
B
UNIT 583B  
SIZE  
lb  
kg  
in.  
mm  
in.  
mm  
030  
036  
042  
048  
060  
335  
343  
404  
443  
490  
152  
156  
183  
201  
222  
22.0  
22.0  
23.0  
21.5  
23.5  
558.5  
558.5  
584.2  
546.1  
596.9  
15.3  
15.3  
16.3  
16.3  
16.3  
388.6  
388.6  
414.0  
414.0  
414.3  
Fig. 8—Suggested Rigging  
IN  
If the installation requires draining the condensate water away  
from the unit, install a 2-in. trap at the condensate connection to  
ensure proper drainage. See Fig. 9. Make sure that the outlet of the  
trap is at least 1 in. lower than the drain pan condensate connection  
to prevent the pan from overflowing. Prime the trap with water.  
Connect a drain tube using a minimum of 3/4 -in. PVC or 3/4 -in.  
copper pipe (all field-supplied) at the outlet end of the 2-in. trap.  
Do not undersize the tube. Pitch the drain tube downward at a  
slope of at least one in. for every 10 ft of horizontal run. Be sure  
to check the drain tube for leaks.  
TEE  
OUT  
NIPPLE  
CAP  
1” (25mm) MIN.  
3˝ MIN  
TRAP  
OUTLET  
C99020  
2” (50mm) MIN.  
Fig. 10—Sediment Trap  
These models meet the California maximum oxides of nitrogen  
(NOx) emissions requirements of 40 nanograms/joule or less as  
shipped from the factory.  
C99013  
Fig. 9—Condensate Trap  
VII. INSTALL FLUE HOOD  
NOTE: Low NOx requirements apply only to natural gas instal-  
lations.  
The flue hood assembly is shipped screwed to the coil panel in the  
indoor blower compartment. Remove the service access panel to  
locate the assembly.  
Install the flue hood as follows:  
1. This installation must conform with local building codes  
and with the National Fuel Gas Code (NFGC), ANSI  
Z223.1 (in Canada, CAN/CGA B149.1, and B149.2) or  
NFPA (National Fire Protection Association) latest revi-  
sion. Refer to Provincial and local plumbing or waste water  
codes and other applicable local codes.  
CAUTION: The venting system is designed to ensure  
proper venting. The flue hood assembly must be installed  
as indicated in this section of the unit installation instruc-  
tions.  
2. Remove flue hood from shipping location (inside the  
blower compartment). Place vent cap assembly over flue  
panel. Orient screw holes in vent cap with holes in the flue  
panel.  
NOTE: Dedicated low NOx models MUST be installed in Cali-  
fornia Air Quality Management Districts where a Low NOx rule  
exists.  
—7—  
3. Secure flue hood to flue panel by inserting a single screw on  
the right side and the left side of the hood.  
CAUTION: Unstable operation may occur when the gas  
valve and manifold assembly are forced out of position  
while connecting improperly routed rigid gas piping to  
the gas valve. Use a backup wrench when making  
connection to avoid strain on, or distortion of, the gas  
control piping.  
VIII. INSTALL GAS PIPING  
The gas supply pipe enters the unit through the access hole  
provided. The gas connection to the unit is made to the 1/2-in. FPT  
gas inlet on the manual shutoff or gas valve.  
Install a gas supply line that runs to the heating section. Refer to  
Table 4 and the NFGC for gas pipe sizing. Do not use cast-iron  
pipe. It is recommended that a black iron pipe is used. check the  
local utility for recommendations concerning existing lines. Size  
gas supply piping for 0.5 in. wg maximum pressure drop. Never  
use pipe smaller than the 1/2-in. FPT gas inlet on the unit gas  
valve.  
CAUTION: If a flexible conductor is required or al-  
lowed by the authority having jurisdiction, black iron  
pipe shall be installed at the gas valve and shall extend a  
minimum of 2 in. outside the unit casing.  
WARNING: Never use a match or other open flame  
when checking for gas leaks. Never purge gas line into  
combustion chamber. Failure to follow this warning  
could result in an explosion causing serious injury or  
death  
For natural gas applications, the gas pressure at unit gas connection  
must not be less than 4.0 in. wg or greater than 13 in. wg while the  
unit is operating. For propane applications, the gas pressure must  
not be less than 7.0 in. wg or greater than 13 in. wg at the unit  
connection.  
A 1/8-in. NPT plugged tapping accessible for test gauge connec-  
tion must be installed immediately upstream of the gas supply  
connection to the gas valve.  
8. Check for gas leaks at the field-installed and factory-  
installed gas lines after all piping connections have been  
completed. Use soap and water solution (or method speci-  
fied by local codes and/or regulations).  
When installing the gas supply line, observe local codes pertaining  
to gas pipe installations. Refer to the NFGC ANSI Z223.1, NFPA  
54 latest edition (in Canada, CAN/CGA B149.1, B149.2 latest  
edition). In the absence of local building codes, adhere to the  
following pertinent recommendations:  
IX. INSTALL DUCT CONNECTIONS  
The unit has duct flanges on the supply- and return-air openings on  
the side and bottom of the unit. For downshot applications the  
ductwork can be connected to the roof curb. See Fig. 6 and 7 for  
connection sizes and locations.  
1. Avoid low spots in long runs of pipe. Grade all pipe 1/4 in.  
in every 15 ft. to prevent traps. Grade all horizontal runs  
downward to risers. Use risers to connect to heating section  
and to meter.  
CONFIGURING UNITS FOR DOWNFLOW (VERTICAL) DIS-  
CHARGE  
WARNING: Before performing service or maintenance  
operations on the system, turn off main power to unit.  
Electrical shock could cause serious injury or death.  
2. Protect all segments of piping system against physical and  
thermal damage. Support all piping with appropriate straps,  
hangers, etc. Use a minimum of one hanger every 6 ft. For  
pipe sizes larger than 1/2 in., follow recommendations of  
national codes.  
1. Open all electrical disconnects before starting any service  
work.  
3. Apply joint compound (pipe dope) sparingly and only to  
male threads of joint when making pipe connections. Use  
only pipe dope that is resistant to action of liquefied  
petroleum gases as specified by local and/or national codes.  
Never use Teflon tape.  
2. Remove return duct cover located on duct panel by breaking  
connecting tabs with screwdriver and a hammer (Fig. 11).  
3. To remove supply duct cover, break front and right side  
connecting tabs with a screwdriver and a hammer. Push  
louver down to break rear and left side tabs (Fig. 12).  
4. Install sediment trap in riser leading to heating section per  
Fig. 10. This drip leg functions as a trap for dirt and  
condensate.  
4. If unit ductwork is to be attached to vertical opening flanges  
on the unit basepan (jackstand applications only), do so at  
this time. Collect ALL screws that were removed. Do not  
leave screws on rooftop as permanent damage to the roof  
may occur.  
5. Install an accessible, external, manual main shutoff valve in  
gas supply pipe within 6 ft. of heating section.  
5. It is recommended that the basepan insulation around the  
perimeter of the vertical return-air opening be secured to the  
basepan with aluminum tape. Applicable local codes may  
require aluminum tape to prevent exposed fiberglass.  
6. Install ground-joint union close to heating section between  
unit manual shutoff and external manual main shutoff  
valve.  
7. Pressure-test all gas piping in accordance with local and  
national plumbing and gas codes before connection of  
piping to unit.  
6. Cover both horizontal duct openings with the duct covers  
from the accessory duct cover kit. Ensure opening is air-and  
watertight.  
7. After completing unit conversion, perform all safety checks  
and power up unit.  
NOTE: The supply piping must be disconnected from the gas  
valve during the testing of the piping systems when test pressure is  
in excess of 0.5 psig (13.8 WC). If the test pressure is equal to or  
less than 0.5 psig, the unit heating section must be isolated from  
the gas piping system by closing the external main manual shutoff  
valve and slightly opening the ground-joint union.  
NOTE: The design and installation of the duct system must be in  
accordance with the standards of the NFPA for installation of  
nonresidence-type air conditioning and ventilating systems, NFPA  
90A or residence-type, NFPA 90B; and/or local codes and  
residence-type, NFPA 90B; and/or local codes and ordinances.  
—8—  
TABLE 2—PHYSICAL DATA — UNIT 583B — 030040-042090  
UNIT SIZE 583B  
NOMINAL CAPACITY (ton)  
OPERATING WEIGHT (lb)  
030040  
2 1/2  
313  
030060  
2 1/2  
313  
036060  
3
036090  
3
042060  
3 1/2  
382  
042090  
3 1/2  
382  
321  
321  
COMPRESSORS  
Quantity  
Scroll  
1
REFRIGERANT (R-410A) Qty (lb)  
5.5  
5.5  
6.9  
6.9  
9.0  
9.0  
REFRIGERANT METERING DEVICE  
Orifice ID (in.)Check-Flo-Rater® Piston  
.057  
.057  
.065  
.065  
.070  
.070  
CONDENSER COIL  
Rows...Fins/in.  
Face Area (sq ft)  
1/17  
12.7  
1/17  
12.7  
2/17  
9.1  
2/17  
9.1  
2/17  
12.3  
2/17  
12.3  
CONDENSER FAN  
Nominal CFM  
2350  
22  
1/8 (825)  
2350  
22  
1/8 (825)  
2350  
22  
1/8 (825)  
2350  
22  
1/8 (825)  
2350  
22  
1/8 (825)  
2350  
22  
1/8 (825)  
Diameter (in.)  
Motor Hp (RPM)  
EVAPORATOR COIL  
Rows...Fins/in.  
Face Area (sq ft)  
3/15  
3.7  
3/15  
3.7  
3/15  
3.7  
3/15  
3.7  
3/15  
4.7  
3/15  
4.7  
EVAPORATOR BLOWER  
Nominal Airflow (CFM)  
Size (in.)  
800  
10 x 10  
1/4  
1000  
10 x 10  
1/4  
1200  
10 x 10  
1/2  
1200  
10 x 10  
1/2  
1400  
11 x 10  
3/4  
1400  
11 x 10  
3/4  
Motor Hp  
FURNACE SECTION*  
Burner Orifice No.  
(Qty...Drill Size) Natural  
Burner Orifice No.  
(Qty...Drill Size) Propane  
2...44  
2...50  
2...38  
2...46  
2...38  
2...46  
3...38  
3...46  
2...38  
2...46  
3...38  
3...46  
HIGH-PRESSURE SWITCH (psig)  
Cutout  
610 15  
420 25  
Reset (Auto.)  
LOSS-OF-CHARGE/LOW-PRESSURE  
SWITCH (Liquid Line) (psig)  
Cutout  
20  
45 10  
5
Reset (Auto.)  
RETURN-AIR FILTERS (in.)Throwaway  
20 x 24x1  
20 x 24x1  
20 x 24x1  
20 x 24x1  
24 x 30x1  
24 x 30x1  
A. Adhere to the following criteria when selecting,  
sizing, and installing the duct system:  
of Sheet Metal and Air Conditioning Contractors National  
Association (SMACNA) and Air Conditioning Contractors  
of America (ACCA) minimum installation standards for  
heating and air conditioning systems. Secure all ducts to  
building structure.  
1. Units are shipped for side shot installation.  
2. Select and size ductwork, supply-air registers, and return-air  
grilles according to American Society of Heating, Refrig-  
eration and Air Conditioning Engineers (ASHRAE) recom-  
mendations.  
7. Flash, weatherproof, and vibration-isolate all openings in  
building structure in accordance with local codes and good  
building practices.  
3. Use flexible transition between rigid ductwork and unit to  
prevent transmission of vibration. The transition may be  
screwed or bolted to duct flanges. Use suitable gaskets to  
ensure weather tight and airtight seal.  
X. INSTALL ELECTRICAL CONNECTIONS  
WARNING: The unit cabinet must have an uninter-  
rupted, unbroken electrical ground to minimize the pos-  
sibility of serious injury if an electrical fault should occur.  
This ground may consist of an electrical wire connected  
to the unit ground lug in the control compartment, or  
conduit approved for electrical ground when installed in  
accordance with NEC (National Electrical Code) ANSI/  
NFPA 70 (latest edition) (in Canada, Canadian Electrical  
Code CSA (Canadian Standards Association) C22.1) and  
local electrical codes. Do not use gas piping as an  
electrical ground. Failure to adhere to this warning could  
result in serious injury or death.  
4. All units must have field-supplied filters or accessory filter  
rack installed in the return-air side of the unit. Recom-  
mended sizes for filters are shown in Tables 2 and 3.  
5. Size all ductwork for maximum required airflow (either  
heating or cooling) for unit being installed. Avoid abrupt  
duct size increases or decreases or performance may be  
affected.  
6. Adequately insulate and weatherproof all ductwork located  
outdoors. Insulate ducts passing through unconditioned  
space, and use vapor barrier in accordance with latest issue  
—9—  
TABLE 3—PHYSICAL DATA — UNIT 583B — 048090-060130  
UNIT SIZE 583B  
NOMINAL CAPACITY (ton)  
OPERATING WEIGHT (lb)  
048090  
4
048115  
4
048130  
4
060090  
5
060115  
5
060130  
5
421  
421  
421  
468  
468  
468  
COMPRESSORS  
Quantity  
Scroll  
1
REFRIGERANT (R-410A) Qty (lb)  
REFRIGERANT METERING DEVICE  
Orifice ID (in.)Check-Flo-Rater® Piston  
9.5  
9.5  
9.5  
10.0  
.086  
10.0  
.086  
10.0  
.086  
.073  
.073  
.073  
CONDENSER COIL  
Rows...Fins/in.  
Face Area (sq ft)  
2/17  
12.3  
2/17  
12.3  
2/17  
12.3  
2/17  
16.4  
2/17  
16.4  
2/17  
16.4  
CONDENSER FAN  
Nominal Cfm  
3300  
22  
1/4 (1100)  
3300  
22  
1/4 (1100)  
3300  
22  
1/4 (1100)  
3300  
22  
1/4 (1100)  
3300  
22  
1/4 (1100)  
3300  
22  
1/4 (1100)  
Diameter (in.)  
Motor Hp (Rpm)  
EVAPORATOR COIL  
Rows...Fins/in.  
Face Area (sq ft)  
4/15  
4.7  
4/15  
4.7  
4/15  
4.7  
4/15  
4.7  
4/15  
4.7  
4/15  
4.7  
EVAPORATOR BLOWER  
Nominal Airflow (Cfm)  
Size (in.)  
1600  
11 x 10  
3/4  
1600  
11 x 10  
3/4  
1600  
11 x 10  
3/4  
1750  
11 x 10  
1.0  
1750  
11 x 10  
1.0  
1750  
11 x 10  
1.0  
Motor Hp  
FURNACE SECTION*  
Burner Orifice No.  
(Qty...Drill Size) Natural  
Burner Orifice No.  
(Qty...Drill Size) Propane  
3...38  
3...46  
3...33  
3...42  
3...31  
3...41  
3...38  
3...46  
3...33  
3...42  
3...31  
3...41  
HIGH-PRESSURE SWITCH (psig)  
Cutout  
610 15  
420 25  
Reset (Auto.)  
LOSS-OF-CHARGE/LOW-PRESSURE  
SWITCH (Liquid Line) (psig)  
Cutout  
20  
45 10  
5
Reset (Auto.)  
RETURN-AIR FILTERS (in.)Throwaway  
24 x 30  
24 x 30  
24 x 30  
24 x 30  
24 x 30  
24 x 30  
TABLE 4—MAXIMUM GAS FLOW CAPACITY*  
LENGTH OF PIPE, FT†  
40 50 60 70 80 90 100 125 150 175 200  
82 73 66 61 57 53 50 44 40  
NOMINAL IRON PIPE SIZE (IN.) INTERNAL DIAMETER (IN.)  
10  
20  
30  
97  
1/2  
3/4  
.622  
.824  
175 120  
360 250 200 170 151 138 125 118 110 103 93 84 77 72  
680 465 375 320 285 260 240 220 205 195 175 160 145 135  
1400 950 770 600 580 530 490 460 430 400 360 325 300 280  
2100 1460 1180 990 900 810 750 690 650 620 550 500 460 430  
1
1.049  
1.380  
1.610  
1-1/4  
1-1/2  
*Capacity of pipe in cu. ft. of gas per hr. for gas pressure of 0.5 psig or less. Pressure drop of 0.5-in. wg (based on a 0.60 specific gravity gas). Refer to Table C-4, National  
Fire Protection Association NFPA 54  
†This length includes an ordinary number of fittings.  
—10—  
The field-supplied disconnect switch box may be mounted on the  
unit over the high-voltage inlet hole when the standard power and  
low-voltage entry points are used. See Fig. 6 and 7 for acceptable  
location.  
See unit wiring label and Fig. 14 for reference when making high  
voltage connections. Proceed as follows to complete the high-  
voltage connections to the unit.  
1. Run the high-voltage (L1, L2, L3) and ground leads into the  
control box.  
2. Connect ground lead to chassis ground connection.  
3. Locate the black and yellow wires connected to the lines  
side of the contactor.  
4. Connect field L1 to black wire on connection 11 of the  
compressor contactor.  
RETURN  
DUCT  
SUPPLY  
DUCT  
OPENING  
OPENING  
5. Connect field wire L2 to yellow wire on connection 13 of  
the compressor contactor.  
C99089  
Fig. 11—Supply and Return Duct Opening  
6. Connect field wire L3 to Blue wire from compressor.  
B. Special Procedures For 208-V Operation  
WARNING: Make sure that the gas supply then the  
power supply to the unit is switched OFF before making  
any wiring changes. Electrical shock or explosion could  
cause serious injury or death.  
With disconnect switch open, move yellow wire from transformer  
(3/16 in.) terminal marked 230 to terminal marked 200. This retaps  
transformer to primary voltage of 208 vac.  
C. CONTROL VOLTAGE CONNECTIONS  
NOTE: Do not use any type of power-stealing thermostat. Unit  
control problems may result.  
Use no. 18 American Wire Gage (AWG) color-coded, insulated  
(35° C minimum) wires to make the control voltage connections  
between the thermostat and the unit. If the thermostat is located  
more than 100 ft from the unit (as measured along the control  
voltage wires), use no. 16 AWG color-coded, insulated (35° C  
minimum) wires.  
DUCT COVERS REMOVED  
C99012  
Fig. 12—Vertical Duct Cover Removed  
CAUTION: Failure to follow these precautions could  
result in damage to the unit being installed:  
STANDARD CONNECTION — Remove knockout hole located  
in the flue panel adjacent to the control access panel. See Fig. 6  
and 7. Remove the rubber grommet from the installer’s packet  
(included with unit) and install grommet in the knockout opening.  
Provide a drip loop before running wire through panel.  
1. Make all electrical connections in accordance with  
NEC ANSI/NFPA 70 (latest edition) and local electri-  
cal codes governing such wiring. In Canada, all elec-  
trical connections must be in accordance with CSA  
standard C22.1 Canadian Electrical Code Part 1 and  
applicable local codes. Refer to unit wiring diagram.  
2. Use only copper conductor for connections between  
field-supplied electrical disconnect switch and unit. DO  
NOT USE ALUMINUM WIRE.  
3. Be sure that high-voltage power to unit is within  
operating voltage range indicated on unit rating plate.  
4. Do not damage internal components when drilling  
through any panel to mount electrical hardware, con-  
duit, etc.  
Run the low-voltage leads from the thermostat, through the inlet  
hole, and into unit low-voltage splice box.  
Locate five 18-gauge wires leaving control box. These low-voltage  
connection leads can be identified by the colors red, green, yellow,  
brown, and white. (See Fig. 14.) Ensure the leads are long enough  
to be routed into the low-voltage splice box (located below right  
side of control box). Stripped yellow wire is located in connection  
box. Route leads through hole in bottom of control box and make  
low-voltage connections as shown in Fig. 14. Secure all cut wires,  
so that they do not interfere with operation of unit.  
5. On 3-phase units, ensure phases are balanced within  
2%. Consult local power company for correction of  
improper voltage and/or phase imbalance (refer to  
Table 5).  
HEAT ANTICIPATOR SETTING — The room thermostat heat  
anticipator must be properly adjusted to ensure proper heating  
performance. Set the heat anticipator, using an ammeter between  
the W and R terminals to determine the exact required setting.  
NOTE: For thermostat selection purposes, use 0.18 amp for the  
approximate required setting.  
A. HIGH-VOLTAGE CONNECTIONS  
The unit must have a separate electrical service with a field-  
supplied, water-proof, disconnect switch mounted at, or within  
sight from the unit. Refer to the unit rating plate for maximum  
fuse/ circuit breaker size and minimum circuit amps (ampacity) for  
wire sizing. See Table 5 for electrical data.  
Failure to make a proper heat anticipator adjustment will result in  
improper operation, discomfort to the occupants of the conditioned  
space, and inefficient energy utilization; however, the required  
setting may be changed slightly to provide a greater degree of  
comfort for a particular installation.  
—11—  
TABLE 5—ELECTRICAL DATA — 583B  
COMPRESSOR OUTDOOR FAN MOTOR INDOOR FAN MOTOR  
VOLTAGE  
RANGE  
POWER SUPPLY  
UNIT  
V-PH-HZ  
SIZE 583B  
Min  
187  
187  
414  
187  
414  
187  
414  
187  
414  
Max  
253  
253  
506  
253  
506  
253  
506  
253  
506  
RLA  
9.6  
LRA  
63.0  
77.0  
35.0  
77.0  
39.0  
91.0  
46.0  
137.0  
62.0  
FLA  
0.8  
0.8  
0.8  
1.6  
0.9  
1.6  
0.9  
1.6  
0.9  
FLA  
2.1  
3.6  
1.9  
4.1  
2.0  
4.1  
2.0  
6.2  
3.2  
MCA  
14.9  
19.7  
9.1  
MOCP*  
20  
030  
036  
208/230-3-60  
208/230-3-60  
460-3-60  
12.2  
5.1  
30  
15  
208/230-3-60  
460-3-60  
13.5  
6.3  
22.6  
10.8  
24.1  
11.0  
30.4  
15.4  
35  
042  
048  
060  
15  
208/230-3-60  
460-3-60  
14.7  
6.5  
35  
15  
208/230-3-60  
460-3-60  
18.1  
9.0  
45  
20  
EXAMPLE: Supply voltage is 460-3-60.  
AB = 452 v  
BC = 464 v  
AC = 455 v  
LEGEND  
FLA  
LRA  
MCA  
— Full Load Amps  
— Locked Rotor Amps  
452 + 464 + 455  
®
Average Voltage =  
— Minimum Circuit Amps  
3
1371  
3
MOCP — Maximum Overcurrent Protection  
RLA  
CKT BKR  
— Rated Load Amps  
=
Circuit Breaker  
= 457  
NOTES:  
Determine maximum deviation from average voltage.  
(AB) 457 452 = 5 v  
1. In compliance with NEC (National Electrical Code) requirements  
for multimotor and combination load equipment (refer to NEC  
Articles 430 and 440), the overcurrent protective device for the  
unit shall be Power Supply fuse. Canadian units may be  
fuse or circuit breaker.  
(BC) 464 457 = 7 v  
(AC) 457 455 = 2 v  
Maximum deviation is 7 v.  
2. Minimum wire size is based on 60 C copper wire. If other than  
60 C wire is used, or if length exceeds wire length in table,  
determine size from NEC.  
Determine percent of voltage imbalance.  
7
457  
% Voltage Imbalance = 100 x  
3. Unbalanced 3-Phase Supply Voltage  
Never operate a motor where a phase imbalance in supply volt-  
age is greater than 2%. Use the following formula to determine  
the percentage of voltage imbalance.  
= 1.53%  
This amount of phase imbalance is satisfactory as it is below the  
maximum allowable 2%.  
% Voltage imbalance  
max voltage deviation from average voltage  
= 100 x  
IMPORTANT: If the supply voltage phase imbalance is  
more than 2%, contact your local electric utility company  
immediately.  
average voltage  
C99024  
Fig. 13—Electrical Data Legend  
HIGH VOLTAGE  
POWER LEADS  
(SEE UNIT WIRING  
LABEL)  
POWER  
SUPPLY  
FIELD-SUPPLIED  
FUSED DISCONNECT  
GND  
CONTROL BOX  
WHT(W1)  
W
YEL(Y)  
Y
THERMOSTAT  
(TYPICAL)  
GRN(G)  
G
R
C
LOW-VOLTAGE  
POWER LEADS  
(SEE UNIT  
RED(R)  
BRN(C)  
WIRING LABEL)  
SPLICE BOX  
C99018  
Fig. 14—High- and Control-Voltage Connections  
—12—  
TRANSFORMER PROTECTION — The transformer is of the  
energy-limiting type. It is set to withstand a 30-second overload or  
shorted secondary condition.  
ground joint union be loosened, and the supply line be  
allowed to purge until the odor of gas is detected. Never  
purge gas lines into a combustion chamber. Immediately  
upon detection of gas odor, re-tighten the union. Allow 5  
minutes to elapse, then light unit.  
PRE-START-UP  
b. Make sure that condenser-fan blade is correctly posi-  
tioned in fan orifice. Leading edge of condenser-fan  
blade should be 1/2 in. maximum from fan orifice (see  
Fig. 15).  
WARNING: Failure to observe the following warnings  
could result in serious injury or death:  
1. Follow recognized safety practices and wear protective  
goggles when checking or servicing refrigerant system.  
2. Do not operate compressor or provide any electric  
power to unit unless compressor terminal cover is in  
place and secured.  
c. Ensure fan hub is 1/8 in. max from motor housing.  
d. Make sure that air filter(s) is in place.  
e. Make sure that condensate drain trap is filled with water  
to ensure proper drainage.  
3. Do not remove compressor terminal cover until all  
electrical sources are disconnected.  
4. Relieve and recover all refrigerant from both high- and  
low-pressure sides of system before touching or dis-  
turbing anything inside terminal box if refrigerant leak  
is suspected around compressor terminals.  
5. Never attempt to repair soldered connection while  
refrigerant system is under pressure.  
f. Make sure that all tools and miscellaneous loose parts  
have been removed.  
FAN GRILLE  
MOTOR  
6. Do not use torch to remove any component. System  
contains oil and refrigerant under pressure. To remove  
a component, wear protective goggles and proceed as  
follows:  
a. Shut off gas supply and then electrical power to unit.  
b. Relieve and reclaim all refrigerant from system  
using both high- and low-pressure ports.  
c. Cut component connecting tubing with tubing cutter  
and remove component from unit.  
d. Carefully unsweat remaining tubing stubs when  
necessary. Oil can ignite when exposed to torch  
flame.  
1/2˝  
1/8" MAX BETWEEN  
MOTOR SHAFT  
MOTOR AND FAN HUB  
C99009  
Fig. 15—Fan Blade Clearance  
START-UP  
Use the Start-Up Checklist supplied at the end of this book, and  
proceed as follows:  
A. CHECK FOR REFRIGERANT LEAKS  
Proceed as follows to locate and repair refrigerant leaks and charge  
the unit:  
Proceed as follows to inspect and prepare the unit for initial  
startup:  
1. Locate leak and make sure that refrigerant system pressure  
has been relieved and refrigerant recovered from both high-  
and low-pressure ports.  
1. Remove access panel.  
2. Read and follow instructions on all DANGER, WARNING,  
CAUTION, and INFORMATION labels attached to, or  
shipped with, unit.  
2. Repair leak following accepted practices.  
NOTE: Replace filter drier whenever the system has been opened  
for repair.  
3. Make the following inspections:  
a. Inspect for shipping and handling damages such as  
broken lines, loose parts, disconnected wires, etc.  
3. Check system for leaks using an approved method.  
4. Evacuate refrigerant system and reclaim refrigerant if no  
additional leaks are found.  
b. Inspect for oil at all refrigerant tubing connections and  
on unit base. Detecting oil generally indicates a refrig-  
erant leak. Leak test all refrigerant tubing connections  
using electronic leak detector, halide torch, or liquid-  
soap solution. If a refrigerant leak is detected, see Check  
for Refrigerant Leaks section of this manual.  
5. Charge unit with R-410a refrigerant, using a volumetric-  
charging cylinder or accurate scale. Refer to unit rating  
plate for required charge.  
B. Start Up Heating Section and Make Adjustments  
c. Inspect all field- and factory-wiring connections. Be sure  
that connections are completed and tight.  
IMPORTANT: Complete the required procedures given in the  
Pre-Start-Up section above before starting the unit.  
d. Inspect coil fins. If damaged during shipping and han-  
dling, carefully straighten fins with a fin comb.  
Do not jumper any safety devices when operating the unit.  
Make sure that burner orifices are properly aligned. Unstable  
operation may occur when the burner orifices in the manifold are  
misaligned.  
4. Verify the following conditions:  
WARNING: Do not purge gas supply into the combus-  
tion chamber. Do not use a match or other open flame to  
check for gas leaks. Failure to follow this warning could  
result in an explosion causing serious injury or death.  
NOTE: Make sure that gas supply has been purged, and that all  
gas piping has been checked for leaks.  
CHECK HEATING CONTROL — Start and check the unit for  
proper heating control operation as follows. (see furnace lighting  
instructions located inside burner or blower access panel.):  
1. Place room thermostat SYSTEM switch in the HEAT  
position and the FAN switch in the AUTO position.  
a. Before lighting the unit for the first time, perform the  
following with the gas valve in the "OFF" position: If the  
gas supply pipe was not purged before connecting the  
unit, it will be full of air. It is recommended that the  
2. Set the heating temperature control of the thermostat above  
room temperature.  
—13—  
TABLE 6—HEATING INPUTS  
GAS SUPPLY PRESSURE  
(IN. WG)  
MANIFOLD PRESSURE  
(IN. WG)  
HEATING  
INPUT  
NUMBER  
OF  
Natural  
Propane†  
(BTUH)*  
ORIFICES  
Min  
4.0  
4.0  
4.0  
4.0  
4.0  
Max  
13.0  
13.0  
13.0  
13.0  
13.0  
Min  
7.0  
7.0  
7.0  
7.0  
7.0  
Max  
13.0  
13.0  
13.0  
13.0  
13.0  
Natural  
3.5  
Propane†  
3.5  
40,000  
60,000  
90,000  
115,000  
130,000  
2
2
3
3
3
3.5  
3.5  
3.5  
3.5  
3.5  
3.5  
3.5  
3.5  
*When a unit is converted to propane, different size orifices must be used. See separate natural-to-propane conversion kit instructions.  
†Based on altitudes from sea level to 2000 ft. above sea level. For altitudes above 2000 ft., reduce input rating 4% for each 1000 ft. above sea level. In Canada, from 2000  
ft. above sea level to 4500 ft. above sea level, derate the unit 10%.  
3. The induced-draft motor will start.  
6. Multiply result of Step 5 by Btu heating value of gas to  
obtain total measured input in Btuh. Compare this value  
with heating input shown in Table 6. (Consult the local gas  
supplier if the heating value of gas is not known.)  
4. After a call for heating, the main burner should light within  
5 seconds. If the burners do not light, there is a 22-second  
delay before another 5-second try. If the burners still do not  
light, this sequence is repeated. If the burners do not light  
within 15 minutes from the initial call for heat, there is a  
lockout. To reset the control, break the 24-v power to W.  
EXAMPLE: Assume that the size of test dial is 1 cu. ft., one  
revolution takes 32 seconds, and the heating value of the gas is  
1050 Btu/ft3.  
Proceed as follows:  
5. The evaporator fan will turn on 45 seconds after the flame  
has been established. The evaporator fan will turn off 45  
seconds after the thermostat has been satisfied.  
1. 32 seconds to complete one revolution.  
2. 3600 ÷ 32 = 112.5  
3. 112.5 x 1 = 112.5 ft3 of gas flow/hr.  
4. 112.5 x 1050 = 118,125 Btuh input.  
CHECK GAS INPUT—Check gas input and manifold pressure  
after unit start-up (see Table 6.) If adjustment is required, proceed  
as follows:  
If the desired gas input is 115,000 Btuh, only a minor change in the  
manifold pressure is required.  
The rated gas inputs shown in Table 6 are for altitudes from sea  
level to 2000 ft. above sea level. These inputs are based on natural  
gas with a heating value of 1050 Btu/ft3 at 0.65 specific gravity, or  
propane gas with a heating value of 2500 Btu/ft3 at 1.5 specific  
gravity. For elevations above 2000 ft., reduce input 4% for each  
1000 ft. above sea level. When the gas supply being used has a  
different heating value, or specific gravity, refer to national and  
local codes, or contact your distributor to determine the required  
orifice size.  
CAUTION: These units are designed to consume the  
rated gas inputs using the fixed orifices at specified  
manifold pressures as shown in Table 6. DO NOT  
REDRILL THE ORIFICES UNDER ANY CIRCUM-  
STANCES.  
ADJUST GAS INPUT—The gas input to the unit is determined by  
measuring the gas flow at the meter or by measuring the manifold  
pressure. Measuring the gas flow at the meter is recommended for  
natural gas units. The manifold pressure must be measured to  
determine the input of propane gas units.  
MANIFOLD  
PIPE PLUG  
C99019  
Fig. 16—Burner Assembly  
MEASURE GAS FLOW (Natural Gas Units)—Minor adjustment  
to the gas flow can be made by changing the manifold pressure.  
The manifold pressure must be maintained between 3.4 and 3.6 in.  
wg. If larger adjustments are required, change main burner orifices  
following the recommendations of national local codes.  
Observe manifold pressure and proceed as follows to adjust gas  
input:  
1. Remove cover screw over regulator adjustment screw on  
gas valve.  
2. Turn regulator adjustment screw clockwise to increase gas  
input, or turn regulator adjustment screw counterclockwise  
to decrease input. Manifold pressure must be between 3.4  
and 3.6 in. wg.  
NOTE: All other appliances that use the same meter must be  
turned off when gas flow is measured at the meter.  
Proceed as follows:  
1. Turn off gas supply to unit.  
2. Remove pipe plug on manifold (see Fig. 16) then connect  
manometer at this point. turn on gas to unit.  
WARNING: Unsafe operation of the unit may result if  
manifold pressure is outside this range. Serious injury or  
unit damage may result.  
3. Record number of seconds for gas meter test dial to make  
one revolution.  
4. Divide number of seconds in Step 3 into 3600 (number of  
seconds on one hour).  
3. Replace cover screw cap on gas valve.  
5. Multiply result of Step 4 by the number of cu. ft. shown for  
one revolution of test dial to obtain cu. ft. of gas flow per  
hour.  
4. Turn off gas supply to unit. Remove manometer from  
pressure tap and replace pipe plug on gas valve. Turn on gas  
to unit and check for leaks.  
—14—  
TABLE 7—AIR DELIVERY (CFM) AT INDICATED TEMPERATURE RISE AND RATED HEATING INPUT  
TEMPERATURE RISE °F  
HEATING  
INPUT  
(BTUH)  
INPUT  
20  
25  
30  
35  
40  
45  
50  
55  
60  
65  
70  
40,000  
60,000  
90,000  
115,000  
130,000  
1500  
2250  
1200  
1800  
2700  
1000  
1500  
2250  
857  
1286  
1929  
2464  
750  
667  
600  
900  
1125  
1688  
2156  
2438  
1000  
1500  
1917  
2167  
818  
750  
692  
1350  
1725  
1950  
1227  
1568  
1773  
1125  
1438  
1625  
1038  
1327  
1500  
964  
1393  
NOTE: Dashed areas do not fall within the approved temperature rise range of the unit.  
MEASURE MANIFOLD PRESSURE (Propane Units)—The  
main burner orifices on a propane unit are sized for the unit rated  
input when the manifold pressure reading matches the level  
specified in Table 6.  
AIRFLOW AND TEMPERATURE RISE—The heating section  
for each size unit is designed and approved for heating operation  
within the temperature rise range stamped on the unit rating plate.  
Table 7 shows the approved temperature rise range for each  
heating input, and the air delivery cfm at various temperature rises.  
The heating operation airflow must produce a temperature rise that  
falls within the approved range.  
WARNING: If converting to propane gas, remove the  
burner assembly and inspect the heat exchanger tubes. If  
there are V-shaped NOx baffles installed in the firing  
tubes, THEY MUST BE REMOVED.  
Discard the baffles after removal.  
Refer to Maintenance section for information on burner  
removal.  
Refer to Indoor Airflow and Airflow Adjustments section on the  
following pages to adjust heating airflow when required.  
HEATING SEQUENCE OF OPERATION—See Fig. 18-19 and  
unit wiring label.  
On a call for heating, terminal "W" of the thermostat is energized,  
starting the induced-draft motor. When the hall-effect sensor on  
the induced-draft motor senses that it has reached the required  
speed, the burner sequence begins. This function is performed by  
the integrated gas control (IGC). The evaporator fan motor is  
energized 45 seconds after flame is established. When the thermo-  
stat is satisfied and "W" is de-energized, the burners stop firing and  
the evaporator fan motor shuts off after a 45-second time-off delay.  
Proceed as follows to adjust gas input on a propane gas unit:  
1. Turn off gas to unit.  
2. Remove pipe plug on manifold (see Fig. 16) then connect  
manometer at this point.  
3. Turn on gas to unit.  
An LED (light-emitting diode) indicator is provided on the control  
board to monitor operation. The control board is located by  
removing the burner access panel. During normal operation, the  
LED is continuously on. See Table 8 for error codes.  
4. Remove cover screw over regulator adjustment screw on  
gas valve.  
5. Adjust regulator adjustment screw to the correct manifold  
pressure, as specified in Table 6. Turn adjusting screw  
clockwise to increase manifold pressure, or turn adjusting  
screw counterclockwise to decrease manifold pressure.  
TABLE 8—LED INDICATIONS  
ERROR CODE  
Normal Operation  
LED INDICATION  
On  
6. Replace cover screw.  
7. Turn off gas to unit. Remove manometer from pressure tap.  
Replace pipe plug on gas valve, then turn on gas to unit.  
check for leaks.  
Hardware Failure  
Off  
Fan On/Off Delay Modified  
Limit Switch Fault  
1 Flash  
2 Flashes  
3 Flashes  
4 Flashes  
5 Flashes  
6 Flashes  
7 Flashes  
8 Flashes  
9 Flashes  
Flame Sense Fault  
CHECK BURNER FLAME—With burner access panel removed,  
observe the unit heating operation. Watch the burner flames to see  
if they are light blue and soft in appearance, and that the flames are  
approximately the same for each burner. Propane will have blue  
flame with yellow tips. (See Fig. 17). Refer to Maintenance section  
for information on burner removal.  
Four Consecutive Limit Switch Faults  
Ignition Lockout Fault  
Induced-Draft Motor Fault  
Rollout Switch Fault  
Internal Control Fault  
Internal Software Fault  
BURNER FLAME  
NOTES:  
1.There is a 3-second pause between error code displays.  
2. If more than one error code exists, all applicable error codes will be  
displayed in numerical sequence.  
3. This chart is on the wiring diagram located inside the burner access  
panel.  
BURNER  
LIMIT SWITCHES—Normally closed limit switch (LS) com-  
pletes the control circuit through the thermostat R circuit. Should  
the leaving-air temperature rise above the maximum allowable  
temperature, the limit switch opens and the R control circuit  
"breaks". Any interruption in the R control circuit instantly closes  
the gas valve and stops gas flow to the burners and pilot. The  
blower motor continues to run until LS resets.  
MANIFOLD  
When the air temperature at the limit switch drops to the  
low-temperature setting of the limit switch, the switch closes and  
completes the R control circuit. The electric spark ignition system  
cycles and the unit returns to normal heating operation. When this  
fault occurs, the IGC LED will display FAULT CODE 2.  
C99021  
Fig. 17—Monoport Burners  
—15—  
AUXILIARY LIMIT SWITCH (ROLLOUT)—The function of  
the switch is to close the main gas valve in the event of flame  
rollout. The switch is located above the main burners. When the  
temperature at the auxiliary switch reaches the maximum allow-  
able temperature, the R control circuit trips, closing the gas valve  
and stopping gas flow to the burners. The indoor (evaporator) fan  
motor (IFM) and induced draft motor continue to run until switch  
is reset. The IGC LED will display FAULT CODE 7.  
IMPORTANT: When evaluating the refrigerant charge, an indi-  
cated adjustment to the specified factory charge must always be  
very minimal. If a substantial adjustment is indicated, an abnormal  
condition exists somewhere in the cooling system, such as insuf-  
ficient airflow across either coil or both coils.  
REFRIGERANT CHARGE—The amount of refrigerant charge is  
listed on the unit nameplate. Refer to Bryant Refrigeration Service  
Techniques Manual, Refrigerants section.  
Unit panels must be in place when unit is operating during  
charging procedures.  
C. Start-Up Cooling Section and Make Adjustments  
NO CHARGE: Use standard evacuating techniques. After evacu-  
ating system, weigh in the specified amount of refrigerant (refer to  
system data plate).  
CAUTION: Complete the required procedures given in  
the Pre-Start-Up section on previous pages before starting  
the unit.  
LOW CHARGE COOLING: Measure outdoor ambient using  
Cooling Charging Charts (Figs. 20-24). Vary refrigerant until the  
conditions of the chart are met. Note that charging charts are  
different from type normally used. Charts are based on charging  
the units to correct superheat for the various operating conditions.  
Accurate pressure gauge and temperature sensing devices are  
required. Connect the pressure gauge to the service port on the  
suction line. Mount the temperature sensing device on the suction  
line and insulate it so that the outdoor ambient does not effect the  
reading. Indoor air CFM must be within the normal operating  
range of the unit.  
Do not jumper any safety devices when operating the  
unit.  
Do not operate the compressor when the outdoor tem-  
perature is below 40° F (unless accessory low-ambient kit  
is installed).  
Do not rapid-cycle the compressor. Allow 5 minutes  
between "on" cycles to prevent compressor damage.  
CHECKING COOLING CONTROL OPERATION—Start and  
check the unit for proper cooling control operation as follows:  
TO USE COOLING CHARGING CHARTS: Take the outdoor  
ambient temperature and read the suction pressure gauge. Refer to  
the chart to determine what the suction temperature should be.  
NOTE: If the problem causing the inaccurate readings is a  
refrigerant leak, refer to Check for Refrigerant Leaks section in  
this document.  
1. Place room thermostat SYSTEM switch in OFF position.  
Observe that blower motor starts when FAN switch is  
placed in ON position and shuts down when FAN switch is  
placed in AUTO position.  
2. Place SYSTEM switch in COOL position and FAN switch  
in AUTO position. Set cooling control below room tem-  
perature. Observe that compressor, condenser fan, and  
evaporator blower motors start. Observe that cooling cycle  
shuts down when control setting is satisfied. The evaporator  
fan will continue to run for 30 seconds.  
D. Indoor Airflow and Airflow Adjustments  
CAUTION: For cooling operation, the recommended  
airflow is 350 to 450 cfm for each 12,000 Btuh of rated  
cooling capacity. For heating operation, the airflow must  
produce a temperature rise that falls within the range  
stamped on the unit rating plate.  
3. When using an auto-changeover room thermostat, place  
both SYSTEM and FAN switches in AUTO positions.  
Observe that unit operates in Heating mode when tempera-  
ture control is set to "call for heating" (above room  
temperature) and operates in Cooling mode when tempera-  
ture control is set to "call for cooling" (below room  
temperature).  
Table 7 shows the temperature rise at various air-flow rates. Table  
9 shows both heating and cooling airflows at various external static  
pressures. Refer to these tables to determine the airflow for the  
system being installed.  
NOTE: Be sure that all supply- and return-air grilles are open,  
free from obstructions, and adjusted properly.  
IMPORTANT: Three-phase, scroll compressor units are  
direction-oriented. These units must be checked to ensure proper  
compressor 3-phase power lead orientation. If not corrected within  
5 minutes, the internal protector will shut off the compressor. The  
3-phase power leads to the unit must be reversed to correct  
rotation. When turning backwards, scroll compressors emit el-  
evated noise levels, and the difference between compressor suction  
and discharge pressures may be dramatically lower than normal.  
WARNING: Shut off gas supply then disconnect elec-  
trical power to the unit before changing blower speed.  
Electrical shock or explosion could cause serious injury  
or death.  
CHECKING  
AND  
ADJUSTING  
REFRIGERANT  
CHARGE—The refrigerant system is fully charged with R-410A  
(Puron) refrigerant, and is tested and factory sealed.  
Airflow can be changed by changing the lead connections of the  
blower motor.  
NOTE: Adjustment of the refrigerant charge is not required  
unless the unit is suspected of not having the proper R-410A  
charge. The charging label and the tables shown refer to system  
temperatures and pressures.  
All 583B units are factory wired for low speed and may need to be  
wired for medium or high speed in the field.  
For 208/230-v — The motor leads are color-coded as follows:  
3-SPEED  
2-SPEED  
black = high speed  
---  
A refrigerant charging chart label is attached to the outside of the  
compressor access door. The chart includes the required suction  
line temperature at given suction line pressures and outdoor  
ambients..  
black = high speed  
blue = medium speed  
red = low speed  
red = low speed  
To change the speed of the blower motor (BM), remove the fan  
motor speed leg lead from the blower relay (BR). This wire is  
attached to terminal BM for single-phase and 3-phase units. To  
change the speed, remove and replace with lead for desired blower  
motor speed. Insulate the removed lead to avoid contact with  
chassis parts.  
An accurate superheat, thermocouple- or thermistor-type ther-  
mometer, and a gauge manifold are required when using the  
superheat charging method for evaluating the unit charge. Do not  
use mercury or small dial-type thermometers because they are not  
adequate for this type of measurement.  
—16—  
—17—  
—18—  
For 460-v GE Motors — The motor leads are color coded as  
follows:  
WARNING: Failure to follow these warnings could  
result in serious injury or death:  
1. Turn off gas supply, then turn off electrical power to  
the unit before performing any maintenance or service  
on the unit.  
2. Use extreme caution when removing panels and parts.  
As with any mechanical equipment, serious injury can  
result from sharp edges, etc.  
3. Never place anything combustible either on, or in  
contact with, the unit.  
3-SPEED  
black = high speed  
violet = jumper  
2-SPEED  
black = high speed  
blue = jumper  
---  
orange = medium speed  
red = low speed  
red = low speed  
To change the speed of the blower motor (BM), remove fan motor  
speed lead from the blower relay (BR) and replace with the lead  
for the desired blower motor speed. The motor speed lead is  
attached to terminal BM. For low and medium speeds black must  
be connected to the jumper wire. Insulate removed lead end to  
avoid contact with chassis parts. To select high speed on 460-v GE  
motors, separate the black female quick connect (QC) from the  
jumper lead male quick connect (QC) and connect the black lead  
to the BR. Insulate the jumper to avoid contact with any chassis  
parts.  
4. Should overheating occur, or the gas supply fail to shut  
off, shut off the external main manual gas valve to the  
unit, then shut off the electrical supply.  
CAUTION: Errors made when reconnecting wires may  
cause improper and dangerous operation. Label all wires  
prior to disconnection when servicing.  
COOLING SEQUENCE OF OPERATION — With the room  
thermostat SYSTEM switch in the COOL position and the FAN  
switch in the AUTO. position, the cooling sequence of operation is  
as follows:  
The minimum maintenance requirements for this equipment are as  
follows:  
When the room temperature rises to a point that is slightly above  
the cooling control setting of the thermostat, the thermostat  
completes the circuit between thermostat terminal R to terminals Y  
and G. These completed circuits through the thermostat connect  
contactor coil (C) (through unit wire Y) and blower relay coil (BR)  
(through unit wire G) across the 24-v secondary of transformer  
(TRAN).  
1. Inspect air filter(s) each month. Clean or replace when  
necessary.  
2. Inspect indoor coil, drain pan, and condensate drain each  
cooling season for cleanliness. Clean when necessary.  
3. Inspect blower motor and wheel for cleanliness and check  
lubrication each heating and cooling season. Clean when  
necessary. For first heating season, inspect blower wheel  
bimonthly to determine proper cleaning frequency.  
The normally open contacts of energized contactor (C) close and  
complete the circuit through compressor motor (COMP) to con-  
denser (outdoor) fan motor (OFM). Both motors start instantly.  
4. Check electrical connections for tightness and controls for  
proper operation each heating and cooling season. Service  
when necessary.  
The set of normally open contacts of energized relay BR close and  
complete the circuit through evaporator blower (indoor) fan motor  
(IFM).  
5. Check and inspect heating section before each heating  
season. Clean and adjust when necessary.  
NOTE: Once the compressor has started and then has stopped, it  
should not be started again until 5 minutes have elapsed.  
6. Check flue hood and remove any obstructions if necessary.  
The cooling cycle remains ‘‘on’’ until the room temperature drops  
to a point that is slightly below the cooling control setting of the  
room thermostat. At this point, the thermostat ‘‘breaks’’ the circuit  
between thermostat terminal R to terminals Y and G. These open  
circuits de-energize contactor coil C and relay coil BR. The  
condenser and compressor motors stop. After a 30-second delay,  
the blower motor stops. The unit is in a ‘‘standby’’ condition,  
waiting for the next ‘‘call for cooling’’ from the room thermostat.  
A. Air Filter  
IMPORTANT: Never operate the unit without a suitable air filter  
in the return-air duct system. Always replace the filter with the  
same dimensional size and type as originally installed. See Tables  
2 and 3 for recommended filter sizes.  
Inspect air filter(s) at least once each month and replace  
(throwaway-type) or clean (cleanable-type) at least twice during  
each heating and cooling season or whenever the filter(s) becomes  
clogged with dust and lint.  
MAINTENANCE  
To ensure continuing high performance, and to minimize the  
possibility of premature equipment failure, periodic maintenance  
must be performed on this equipment. This combination  
heating/cooling unit should be inspected at least once each year by  
a qualified service person. To troubleshoot heating or cooling of  
units, refer to tables at the back of the book.  
B. Evaporator Blower and Motor  
NOTE: All motors are pre-lubricated. Do not attempt to lubricate  
these motors.  
For longer life, operating economy, and continuing efficiency,  
clean accumulated dirt and grease from the blower wheel and  
motor annually.  
NOTE TO EQUIPMENT OWNER: Consult your local dealer  
about the availability of a maintenance contract.  
WARNING: Turn off the gas supply, then disconnect  
and tag electrical power to the unit before cleaning the  
blower motor and wheel. Failure to adhere to this warning  
could cause serious injury or death.  
WARNING: The ability to properly perform mainte-  
nance on this equipment requires certain expertise, me-  
chanical skills, tools, and equipment. If you do not  
possess these, do not attempt to perform any maintenance  
on this equipment other than those procedures recom-  
mended in the User’s Manual. FAILURE TO HEED  
THIS WARNING COULD RESULT IN SERIOUS IN-  
JURY AND POSSIBLE DAMAGE TO THIS EQUIP-  
MENT.  
To clean the blower motor and wheel:  
1. Remove and disassemble blower assembly as follows:  
a. Remove unit access panel.  
b. Disconnect motor lead from blower relay (BR). Discon-  
nect yellow lead from terminal L2 of the contactor.  
—19—  
(030) 60 Hz CHARGING CHART  
FOR USE WITH UNITS USING R410A REFRIGERANT  
OUTDOOR  
TEMP  
F
C
1241  
1172  
180  
170  
125  
115  
105  
52  
46  
41  
1103  
1034  
160  
150  
95  
85  
35  
29  
75  
65  
24  
18  
965  
896  
140  
130  
55  
45  
13  
7
827  
758  
690  
120  
110  
100  
20.0  
30.0  
-1  
40.0  
50.0  
60.0  
70.0  
21  
80.0  
SUCTION LINE TEMPERATURE (DEG. F)  
-7  
4
10  
16  
27  
SUCTION LINE TEMPERATURE (DEG. C)  
C99080  
Fig. 20—Cooling Charging Chart, 583B030 Units  
(036) 60 Hz CHARGING CHART  
FOR USE WITH UNITS USING R410A REFRIGERANT  
(042) 60 Hz CHARGING CHART  
FOR USE WITH UNITS USING R410A REFRIGERANT  
OUTDOOR  
TEMP  
OUTDOOR  
TEMP  
F
C
F
C
1241  
1172  
180  
170  
1241  
1172  
180  
170  
125  
52  
115  
105  
46  
41  
1103  
1034  
160  
150  
125  
115  
52  
46  
1103  
1034  
160  
150  
95  
85  
35  
29  
105  
95  
85  
41  
35  
29  
75  
65  
24  
18  
75  
65  
24  
18  
965  
896  
140  
130  
965  
896  
140  
130  
55  
45  
13  
7
55  
45  
13  
7
827  
758  
690  
120  
110  
100  
827  
758  
690  
120  
110  
100  
20.0  
30.0  
-1  
40.0  
50.0  
60.0  
70.0  
21  
80.0  
SUCTION LINE TEMPERATURE (DEG. F)  
-7  
4
10  
16  
27  
SUCTION LINE TEMPERATURE (DEG. C)  
20.0  
30.0  
-1  
40.0  
50.0  
60.0  
70.0  
21  
80.0  
SUCTION LINE TEMPERATURE (DEG. F)  
-7  
4
10  
16  
27  
SUCTION LINE TEMPERATURE (DEG. C)  
C99081  
C99082  
Fig. 21—Cooling Charging Chart, 583B036 Units  
Fig. 22—Cooling Charging Chart, 583B042 Units  
(048) 60 Hz CHARGING CHART  
FOR USE WITH UNITS USING R410A REFRIGERANT  
OUTDOOR  
TEMP  
(060) 60 Hz CHARGING CHART  
FOR USE WITH UNITS USING R410A REFRIGERANT  
OUTDOOR  
TEMP  
F
C
F
C
1241  
1172  
180  
170  
1241  
1172  
180  
170  
125  
115  
52  
46  
125  
115  
105  
52  
46  
105  
95  
41  
35  
41  
35  
29  
24  
1103  
1034  
160  
150  
1103  
1034  
160  
150  
95  
85  
29  
85  
75  
65  
55  
24  
18  
13  
75  
965  
896  
140  
130  
965  
896  
140  
130  
65  
55  
45  
18  
13  
7
45  
7
827  
758  
690  
120  
110  
100  
827  
758  
690  
120  
110  
100  
20.0  
30.0  
-1  
40.0  
50.0  
60.0  
70.0  
21  
80.0  
20.0  
30.0  
-1  
40.0  
50.0  
60.0  
70.0  
21  
80.0  
SUCTION LINE TEMPERATURE (DEG. F)  
SUCTION LINE TEMPERATURE (DEG. F)  
-7  
4
10  
16  
27  
-7  
4
10  
16  
27  
SUCTION LINE TEMPERATURE (DEG. C)  
SUCTION LINE TEMPERATURE (DEG. C)  
C99083  
A99084  
Fig. 23—Cooling Charging Chart, 583B048 Units  
Fig. 24—Cooling Charging Chart, 583B060 Units  
—20—  
TABLE 9—WET COIL AIR DELIVERY* — HORIZONTAL AND DOWNFLOW DISCHARGE  
UNIT 583B030-060 (DEDUCT 10% FOR 208 VOLTS)  
230 AND 460 VOLT  
External Static Pressure (in. wg)  
Unit  
Motor  
Speed  
583B  
0.0  
243  
885  
353  
1195  
0.1  
244  
842  
339  
1134  
0.2  
242  
786  
333  
1070  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
0.9  
1.0  
Watts  
Cfm  
Low  
Watts  
Cfm  
330  
997  
443  
1230  
432  
1281  
488  
1351  
636  
1410  
598  
1498  
733  
1746  
326  
911  
436  
1145  
418  
1205  
474  
1267  
627  
1330  
583  
1448  
704  
1688  
320  
818  
426  
1061  
403  
1118  
459  
1175  
616  
1243  
562  
1391  
672  
1630  
030  
036  
042  
048  
060  
Medium  
High  
Watts  
Cfm  
416  
977  
389  
1024  
443  
1077  
605  
1147  
534  
1326  
638  
1566  
797  
1727  
524  
1332  
627  
1520  
801  
1711  
499  
1577  
623  
1727  
750  
1824  
406  
888  
378  
921  
428  
976  
593  
1044  
502  
1257  
604  
1492  
773  
1632  
500  
1269  
602  
1455  
777  
1624  
397  
786  
Watts  
Cfm  
490  
1431  
463  
1398  
513  
1491  
446  
1347  
501  
1426  
645  
1484  
608  
1545  
Low  
Watts  
Cfm  
Medium  
High  
Watts  
Cfm  
583  
936  
473  
1189  
574  
1399  
751  
1537  
Watts  
Cfm  
634  
1669  
618  
1599  
454  
1132  
550  
1279  
727  
1423  
457  
1101  
536  
1120  
696  
1308  
Low  
Watts  
Cfm  
Medium  
High  
Watts  
Cfm  
Watts  
Cfm  
591  
1554  
755  
1834  
578  
1523  
737  
1802  
573  
1496  
719  
1758  
568  
1467  
699  
1706  
890  
1943  
566  
1779  
695  
1952  
821  
2050  
559  
1432  
678  
1648  
858  
1870  
559  
1718  
673  
1883  
795  
1974  
544  
1387  
653  
1585  
828  
1793  
541  
1651  
648  
1809  
772  
1905  
Low  
Watts  
Cfm  
579  
1392  
756  
1531  
562  
1332  
734  
1433  
556  
1276  
709  
1329  
Medium  
High  
Watts  
Cfm  
Watts  
Cfm  
589  
1946  
750  
2189  
576  
1891  
733  
2097  
879  
2337  
569  
1836  
715  
2021  
850  
2159  
Low  
Watts  
Cfm  
598  
1635  
728  
1722  
577  
1530  
701  
1597  
Medium  
High  
Watts  
Cfm  
*Air delivery values are without air filter.  
Note: Deduct field-supplied air filter pressure drop to obtain external static pressure available for ducting.  
c. On all units, remove blower assembly from unit. Re-  
move screws securing blower to blower partition and  
slide assembly out. Be careful not to tear insulation in  
blower compartment.  
3. Restore electrical power, then gas supply to unit. Start unit  
and check for proper blower rotation and motor speeds  
during heating and cooling cycles.  
INDUCED DRAFT MOTOR MOUNT  
d. Ensure proper reassembly by marking blower wheel and  
motor in relation to blower housing before disassembly.  
e. Loosen setscrew(s) that secures wheel to motor shaft,  
remove screws that secure motor mount brackets to  
housing, and slide motor and motor mount out of  
housing.  
2. Remove and clean blower wheel as follows:  
a. Ensure proper reassembly by marking wheel orientation.  
b. Lift wheel from housing. When handling and/or cleaning  
blower wheel, be sure not to disturb balance weights  
(clips) on blower wheel vanes.  
c. Remove caked-on dirt from wheel and housing with a  
brush. Remove lint and/or dirt accumulations from wheel  
and housing with vacuum cleaner, using soft brush  
attachment. Remove grease and oil with mild solvent.  
ROLLOUT  
SWITCH  
BURNER MOUNTING  
HOUSING RACK SCREW  
FLUE  
COLLECTOR  
BOX  
BLOWER  
C99022  
d. Reassemble wheel into housing.  
Fig. 25—Blower Housing and Flue Collector Box  
C. Flue Gas Passageways  
e. Reassemble motor into housing. Be sure setscrew(s) are  
tightened on motor shaft flats and not on round part of  
shaft.  
To inspect the flue collector box and upper areas of the heat  
exchanger:  
f. Reinstall unit access panel.  
—21—  
5. To remove motor and cooling fan assembly, remove 4  
screws that hold blower housing to mounting plate.  
6. To reinstall, reverse the procedure outlined above.  
BLOWER  
HOUSING  
E. Limit Switch  
Remove unit access panel. Limit switch is located on the blower  
partition.  
F. Burner Ignition  
Unit is equipped with a direct spark ignition 100% lockout system.  
Ignition module is located in the control box. Module contains a  
self-diagnostic LED. During servicing, refer to label diagram for  
LED interpretations.  
2 SETSCREWS  
(HIDDEN)  
If lockout occurs, unit may be reset by either momentarily  
interrupting power supply to unit, or turning selector switch to  
OFF position at the thermostat.  
G. Main Burners  
At the beginning of each heating season, inspect for deterioration  
or blockage due to corrosion or other causes. Observe the main  
burner flames and adjust if necessary.  
C99085  
Fig. 26—Removal of Motor and Blower Wheel  
CAUTION: When servicing gas train, do not hit or plug  
orifice spuds.  
REMOVAL OF GAS TRAIN  
1. Shut off manual gas valve.  
2. Shut off power to unit.  
3. Remove unit access panel (See Fig. 27).  
4. Disconnect gas piping at unit gas valve.  
5. Remove wires connected to gas valve. Mark each wire.  
6. Remove ignitor and sensor wires at the ignitor module.  
7. Remove the mounting screw that attaches the burner rack to  
the basepan (See Fig. 25).  
C99090  
Fig. 27—Unit Access Panel  
8. Slide the burner rack out of the unit (See Figs. 25 and 28).  
9. To reinstall, reverse the procedure outlined above.  
1. Remove the combustion blower wheel and motor assembly  
according to directions in Combustion-Air Blower section  
below.  
H. Condenser Coil, Evaporator Coil, and Condensate  
Drain Pan  
2. Remove the 3 screws holding the blower housing to the flue  
collector box cover (see Fig. 25).  
Inspect the condenser coil, evaporator coil, and condensate drain  
pan at least once each year.  
3. Remove the 12 screws holding the flue collector box cover  
(Fig. 25) to the heat exchanger assembly. Inspect the heat  
exchangers.  
The coils are easily cleaned when dry; therefore, inspect and clean  
the coils either before or after each cooling season. Remove all  
obstructions, including weeds and shrubs, that interfere with the  
airflow through the condenser coil.  
4. Clean all surfaces as required, using the wire brush.  
D. Combustion-Air Blower  
Straighten bent fins with a fin comb. If coated with dirt or lint,  
clean the coils with a vacuum cleaner, using the soft brush  
attachment. Be careful not to bend the fins. If coated with oil or  
grease, clean the coils with a mild detergent-and-water solution.  
Rinse coils with clear water, using a garden hose. Be careful not to  
splash water on motors, insulation, wiring, or air filter(s). For best  
results, spray condenser coil fins from inside to outside the unit.  
On units with an outer and inner condenser coil, be sure to clean  
between the coils. Be sure to flush all dirt and debris from the unit  
base.  
Clean periodically to assure proper airflow and heating efficiency.  
Inspect blower wheel every fall and periodically during heating  
season. For the first heating season, inspect blower wheel bi-  
monthly to determine proper cleaning frequency.  
To inspect blower wheel, remove draft hood assembly. Shine a  
flashlight into opening to inspect wheel. If cleaning is required,  
remove motor and wheel as follows:  
1. Remove unit access panel (See Fig. 24).  
Inspect the drain pan and condensate drain line when inspecting  
the coils. Clean the drain pan and condensate drain by removing all  
foreign matter from the pan. Flush the pan and drain tube with  
clear water. Do not splash water on the insulation, motor, wiring,  
or air filter(s). If the drain tube is restricted, clear it with a  
‘‘plumbers snake’’ or similar probe device. Ensure that the  
auxiliary drain port above the drain tube is also clear.  
2. Remove the 7 screws that attach induced-draft motor  
mounting plate to blower housing (See Fig. 25).  
3. Slide the motor and blower wheel assembly out of the  
blower housing (See Fig. 26). Clean the blower wheel. If  
additional cleaning is required, continue with Steps 4 and 5.  
4. To remove blower, remove 2 setscrews (See Fig. 26).  
—22—  
K. Refrigerant Circuit  
Inspect all refrigerant tubing connections and the unit base for oil  
accumulations annually. Detecting oil generally indicates a refrig-  
erant leak.  
If oil is detected or if low cooling performance is suspected,  
leak-test all refrigerant tubing using an electronic leak-detector,  
halide torch, or liquid-soap solution. If a refrigerant leak is  
detected, refer to Check for Refrigerant Leaks section on page 13.  
If no refrigerant leaks are found and low cooling performance is  
suspected, refer to Checking and Adjusting Refrigerant Charge  
section in this document.  
L. Evaporator Airflow  
The heating and/or cooling air-flow does not require checking  
unless improper performance is suspected. If a problem exists, be  
sure that all supply- and return-air grilles are open and free from  
obstructions, and that the air filter is clean. When necessary, refer  
to Indoor Airflow and Airflow Adjustments section in this docu-  
ment to check the system airflow.  
M. Metering Device–Check-Flo-Rater® Piston  
This metering device is a fixed orifice and is contained in the brass  
hex-body in the liquid line.  
C99086  
Fig. 28—Burner Rack Removed  
I. Condenser Fan  
N. Pressure Switches  
Pressure switches are protective devices wired into control circuit  
(low voltage). They shut off compressor if abnormally high or low  
pressures are present in the refrigeration circuit. These pressure  
switches are specifically designed to operate with Puron (R-410A)  
systems. R-22 pressure switches must not be used as replacements  
for the Puron (R-410A) air conditioner.  
CAUTION: Keep the condenser fan free from all ob-  
structions to ensure proper cooling operation. Never place  
articles on top of the unit. Damage to unit may result.  
1. Remove 6 screws holding condenser grille and motor to top  
cover.  
LOSS OF CHARGE/LOW-PRESSURE SWITCH (air conditioner  
only)  
This switch is located on the liquid line and protects against low  
suction pressures caused by such events as loss of charge, low  
airflow across indoor coil, dirty filters, etc. It opens on a pressure  
drop at about 20 psig. If system pressure is above this, switch  
should be closed.  
2. Turn motor/grille assembly upside down on top cover to  
expose the fan blade.  
3. Inspect the fan blades for cracks or bends.  
4. If fan needs to be removed, loosen the setscrew and slide  
the fan off the motor shaft.  
To check switch:  
5. When replacing fan blade, position blade so that the hub is  
1/8 in. away from the motor end (1/8 in. of motor shaft will  
be visible).  
1. Turn off gas and then all power to unit.  
2. Disconnect leads on switch.  
3. Apply ohmmeter leads across switch. You should have  
continuity on a good switch.  
6. Ensure that setscrew engages the flat area on the motor shaft  
when tightening.  
NOTE: Because these switches are attached to refrigeration  
system under pressure, it is not advisable to remove this device for  
troubleshooting unless you are reasonably certain that a problem  
exists. If switch must be removed, remove and recover all system  
charge so that pressure gauges read 0 psi. Never open system  
without breaking vacuum with dry nitrogen.  
7. Replace grille.  
J. Electrical Controls and Wiring  
Inspect and check the electrical controls and wiring annually. Be  
sure to turn off the gas supply, and then the electrical power to the  
unit.  
HIGH-PRESSURE SWITCH—The high-pressure switch is lo-  
cated in the discharge line and protects against excessive con-  
denser coil pressure. It opens at 610 psig.  
Remove access panel to locate all the electrical controls and  
wiring. Check all electrical connections for tightness. Tighten all  
screw connections. If any smokey or burned connections are  
noticed, disassemble the connection, clean all the parts, restrip the  
wire end and reassemble the connection properly and securely.  
High pressure may be caused by a dirty condenser coil, failed fan  
motor, or condenser air recirculation.  
To check switch:  
After inspecting the electrical controls and wiring, replace the  
access panel. Start the unit, and observe at least one complete  
heating cycle and one complete cooling cycle to ensure proper  
operation. If discrepancies are observed in either or both operating  
cycles, or if a suspected malfunction has occurred, check each  
electrical component with the proper electrical instrumentation.  
Refer to the unit wiring label when making these checkouts.  
1. Turn off gas and then all power to unit.  
2. Disconnect leads on switch.  
3. Apply ohmmeter leads across switch. You should have  
continuity on a good switch.  
O. Copeland Scroll Compressor (Puron Refrigerant  
The compressor used in this product is specifically designed to  
operate with Puron (R-410A) refrigerant and cannot be inter-  
changed.  
NOTE: Refer to the heating and/or cooling sequence of operation  
in this publication as an aid in determining proper control  
operation.  
—23—  
The compressor is an electrical (as well as mechanical) device.  
Exercise extreme caution when working near compressors. Power  
should be shut off, if possible, for most troubleshooting tech-  
niques. Refrigerants present additional safety hazards.  
R. Servicing Systems on Roofs with  
Synthetic Materials  
POE (polyolester) compressor lubricants are known to cause long  
term damage to some synthetic roofing materials. Exposure, even  
if immediately cleaned up, may cause embrittlement (leading to  
cracking) to occur in one year or more. When performing any  
service that may risk exposure of compressor oil to the roof, take  
appropriate precautions to protect roofing. Procedures which risk  
oil leakage include, but are not limited to, compressor replacement,  
repairing refrigerant leaks, replacing refrigerant components such  
as filter drier, pressure switch, metering device, coil, accumulator,  
or reversing valve.  
WARNING: Wear safety glasses and gloves when han-  
dling refrigerants. Failure to follow this warning can  
cause a fire, serious injury, or death.  
The scroll compressor pumps refrigerant throughout the system by  
the interaction of a stationary and an orbiting scroll. The scroll  
compressor has no dynamic suction or discharge valves, and it is  
more tolerant of stresses caused by debris, liquid slugging, and  
flooded starts. The compressor is equipped with an anti-rotational  
device and an internal pressure relief port. The anti-rotational  
device prevents the scroll from turning backwards and replaces the  
need for a cycle protector. The pressure relief port is a safety  
device, designed to protect against extreme high pressure. the  
relief port has an operating range between 550 and 625 psi  
differential pressure.  
SYNTHETIC ROOF PRECAUTIONARY PROCEDURE:  
1. Cover extended roof working area with an impermeable  
polyethylene (plastic) drip cloth or tarp. Cover an approxi-  
mate 10 x 10 ft. area.  
2. Cover area in front of the unit service panel with a terry  
cloth shop towel to absorb lubricant spills and prevent  
run-offs, and protect drop cloth from tears caused by tools  
or components.  
3. Place terry cloth shop towel inside unit immediately under  
component(s) to be serviced and prevent lubricant run-offs  
through the louvered openings in the base pan.  
The Copeland scroll compressor uses Mobil 3MA POE oil.  
This is the only oil allowed for oil recharge.  
P. REFRIGERANT SYSTEM  
4. Perform required service.  
5. Remove and dispose of any oil contaminated material per  
local codes.  
CAUTION: This system uses Puron (R-410A) refriger-  
ant which has higher operating pressures than R-22 and  
other refrigerants. No other refrigerant may be used in  
this system. Gage set, hoses, and recovery system must be  
designed to handle Puron. If you are unsure consult the  
equipment manufacturer.  
Failure to use Puron compatible servicing equipment or  
replacement components may result in property damage  
or injury.  
S. Liquid Line Filter Drier  
The filter drier is specifically designed to operate with Puron. Use  
only factory-authorized components. Filter drier must be replaced  
whenever the refrigerant system is opened. When removing a filter  
drier, use a tubing cutter to cut the drier from the system. Do not  
unsweat a filter drier from the system. Heat from unsweating  
will release moisture and contaminants from drier into system.  
T. Puron (R-410A) Refrigerant Charging  
Refer to unit information plate and charging chart. Some R-410A  
refrigerant cylinders contain a dip tube to allow liquid refrig-  
erant to flow from cylinder in upright position. For cylinders  
equipped with a dip tube, charge Puron units with cylinder in  
upright position and a commercial metering device in manifold  
hose. Charge refrigerant into suction-line.  
Q. Compressor Oil  
The compressor in this system uses a polyolester (POE) oil, Mobil  
3MA POE. This oil is extremely hygroscopic, meaning it absorbs  
water readily. POE oils can absorb 15 times as much water as other  
oils designed for HCFC and CFC refrigerants. Take all necessary  
precautions to avoid exposure of the oil to the atmosphere.  
—24—  
AIR CONDITIONER WITH PURON® (R-410A)—QUICK REFERENCE GUIDE  
Puron® refrigerant operates at 50%-70% higher pressures than R-22. Be sure that servicing equipment and replacement components are designed  
to operate with Puron.  
Puron refrigerant cylinders are rose colored.  
Puron refrigerant cylinders manufactured prior to March 1, 1999, have a dip tube that allows liquid to flow out of cylinder in upright position.  
Cylinders manufactured March 1, 1999 and later DO NOT have a dip tube and MUST be positioned upside down to allow liquid to flow.  
Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.  
Puron systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose.  
Manifold sets should be 750 psig high-side and 200 psig low-side with 520 psig low-side retard.  
Use hoses with 750 psig service pressure rating.  
Leak detectors should be designed to detect HFC refrigerant.  
Puron, as with other HFCs, is only compatible with POE oils.  
Vacuum pumps will not remove moisture from oil.  
Only use factory specified liquid-line filter driers with rated working pressures no less than 600 psig.  
Do not install a suction-line filter drier in liquid-line.  
POE oils absorb moisture rapidly. Do not expose oil to atmosphere.  
POE oils may cause damage to certain plastics and roofing materials.  
Wrap all filter driers and service valves with wet cloth when brazing.  
A Puron liquid-line filter drier is required on every unit.  
Do not use an R-22 TXV.  
Never open system to atmosphere while it is under a vacuum.  
When system must be opened for service, break vacuum with dry nitrogen and replace filter driers.  
Always replace filter drier after opening system for service.  
Do not vent Puron into the atmosphere.  
Observe all warnings, cautions, and bold text.  
Do not leave Puron suction line driers in place for more than 72 hours.  
—25—  
TABLE 10—TROUBLESHOOTING — COOLING  
SYMPTOM  
CAUSE  
Power failure  
REMEDY  
Call power company.  
Fuse blown or circuit breaker tripped  
Replace fuse or reset circuit breaker.  
Defective thermostat, contactor, transformer,  
control relay, high pressure, or loss of charge  
Replace component.  
switch  
Compressor and condenser fan will not start.  
Insufficient line voltage  
Incorrect or faulty wiring  
Determine cause and correct.  
Check wiring diagram and rewire correctly.  
Lower thermostat setting below room tempera-  
ture.  
Thermostat setting too high  
Faulty wiring or loose connections in compres-  
sor circuit  
Check wiring and repair or replace.  
Determine cause. Replace compressor.  
Determine cause and replace.  
Compressor motor burned out, seized, or inter-  
nal overload open  
Compressor will not start but condenser fan  
runs.  
Defective run/start capacitor, overload, start re-  
lay  
Replace fuse or reset circuit breaker. Determine  
cause.  
One leg of 3-phase power dead  
Three-phase scroll compressor makes ex-  
cessive noise, and there may be a low pres-  
sure differential.  
Correct the direction of rotation by reversing the  
3-phase power leads to the unit. Shut down unit  
to allow pressures to equalize.  
Scroll compressor is rotating in the wrong direc-  
tion  
Recover refrigerant, evacuate system, and re-  
charge to capacities shown on nameplate.  
Refrigerant overcharge or undercharge  
Defective compressor  
Insufficient line voltage  
Blocked condenser  
Replace and determine cause.  
Determine cause and correct.  
Determine cause and correct.  
Compressor cycles (other than normally sat-  
isfying thermostat).  
Defective run/start capacitor, overload or start  
relay  
Determine cause and replace.  
Defective thermostat  
Faulty condenser-fan motor or capacitor  
Restriction in refrigerant system  
Dirty air filter  
Replace thermostat.  
Replace.  
Locate restriction and remove.  
Replace filter.  
Unit undersized for load  
Decrease load or increase unit size.  
Reset thermostat.  
Thermostat set too low  
Low refrigerant charge  
Locate leak, repair, and recharge.  
Replace compressor.  
Compressor operates continuously.  
Leaking valves in compressor  
Recover refrigerant, evacuate system, and re-  
charge.  
Air in system  
Condenser coil dirty or restricted  
Dirty air filter  
Clean coil or remove restriction.  
Replace filter.  
Dirty condenser coil  
Clean coil.  
Refrigerant overcharged  
Recover excess refrigerant.  
Excessive head pressure.  
Recover refrigerant, evacuate system, and re-  
charge.  
Air in system  
Condenser air restricted or air short-cycling  
Low refrigerant charge  
Determine cause and correct.  
Check for leaks, repair and recharge.  
Replace compressor.  
Head pressure too low.  
Compressor valves leaking  
Restriction in liquid tube  
High heat load  
Remove restriction.  
Check for source and eliminate.  
Replace compressor.  
Excessive suction pressure.  
Compressor valves leaking  
Refrigerant overcharged  
Dirty air filter  
Recover excess refrigerant.  
Replace filter.  
Low refrigerant charge  
Check for leaks, repair and recharge.  
Remove source of restriction.  
Metering device or low side restricted  
Increase air quantity. Check filter — replace if  
necessary.  
Suction pressure too low.  
Insufficient evaporator airflow  
Temperature too low in conditioned area  
Outdoor ambient below 40 F  
Reset thermostat.  
Install low-ambient kit.  
Replace.  
Field-installed filter-drier restricted  
—26—  
TABLE 11—TROUBLESHOOTING — HEATING  
SYMPTOM  
CAUSE  
REMEDY  
Water in gas line  
Drain. Install drip leg.  
No power to furnace  
Miswired or loose connections  
Burned-out heat anticipator in thermostat  
Broken thermostat wire  
Check power supply fuses, wiring, or circuit breaker.  
Check all wiring and wirenut connections.  
Replace thermostat.  
Run continuity check. Replace wire if necessary.  
Burners will not ignite.  
Check flame ignition and sense electrode positioning.  
Adjust as necessary  
Misaligned spark electrodes  
1. Check gas line for air. Purge as necessary. NOTE:  
After purging gas line of air, wait at least 5 minutes for  
any gas to dissipate before attempting to light unit.  
2. Check gas valve.  
No gas at main burners  
Dirty air filter  
Clean or replace filter as necessary.  
check gas pressure at manifold. Match with that on unit  
nameplate.  
Gas input to furnace too low  
Unit undersized for application  
Restricted airflow  
Replace with proper unit or add additional unit.  
Clean or replace filter. Remove any restriction.  
Inadequate heating.  
Use faster speed tap if available, or install alternate  
motor.  
Blower speed too low  
Check rotation of blower, thermostat heat anticipator  
settings, and temperature rise of unit. Adjust as neces-  
sary.  
Limit switch cycles main burners  
1. Tighten all screws around burner compartments.  
2. Cracked heat exchanger. Replace  
Incomplete combustion results in: Aldehyde odors, car- 3. Unit overfired. Reduce input (change orifices or ad-  
Poor flame. characteristics  
bon monoxide, sooting flame, floating flame  
just gas line or manifold pressure).  
4. Check burner alignment.  
—27—  
TABLE 12—LED TROUBLESHOOTING–ERROR CODE  
CAUSE  
SYMPTOM  
REMEDY  
Check 5 amp fuse on IGC, power to unit, 24-v  
circuit breaker, and transformer. Units without a  
24-v circuit breaker have an internal overload in  
the 24-v transformer. If the overload trips, allow  
20 minutes for automatic reset.  
Hardware failure.  
(LED OFF)  
Loss of power to control module (IGC)  
High limit switch opens during heat exchanger  
warm-up period before fan-on delay expires  
Ensure unit is fired on rate and temperature rise  
is correct.  
Fan ON/OFF delay modified. (LED/FLASH)  
Limit switch opens within three minutes after  
blower-off delay timing in Heating mode  
Ensure unit’s external static pressure is within  
application guidelines.  
Check operation of indoor (evaporator) fan motor.  
Ensure that the supply-air temperature rise is in  
accordance with the range on the unit nameplate.  
Limit switch fault. (LED 2 flashes)  
Flame sense fault. (LED 3 flashes)  
High temperature limit switch is open  
The IGC sensed flame that should not be present  
Inadequate airflow to unit  
Reset unit. If problem persists, replace control  
board.  
Check operation of indoor (evaporator) fan motor  
and that supply-air temperature rise agrees with  
range on unit nameplate information.  
4 consecutive limit switch faults. (LED 4  
flashes)  
Check ignitor and flame sensor electrode spacing,  
Unit unsuccessfully attempted ignition for 15 min- gaps, etc. Ensure that flame sensor and ignition  
Ignition lockout. (LED 5 flashes)  
utes  
wires are properly terminated. Verify that unit is  
obtaining proper amount of gas.  
Check for proper voltage. If motor is operating,  
check the speed sensor plug/IGC Terminal J2  
connection. Proper connection:  
PIN 1 – White,  
IGC does not sense that induced-draft motor is  
operating  
Induce-draft motor fault. (LED 6 flashes)  
PIN 2 – Red,  
PIN 3 – Black.  
Rollout switch will automatically reset, but IGC will  
continue to lockout unit. check gas valve opera-  
tion. ensure that induced-draft blower wheel is  
properly secured to motor shaft. Reset unit at unit  
disconnect.  
Rollout switch fault. (LED 7 flashes)  
Rollout switch has opened  
Microprocessor has sensed an error in the soft-  
ware or hardware  
If error code is not cleared by resetting unit  
power, replace the IGC.  
Internal control fault. (LED 8 flashes)  
Internal software fault. (LED 9 flashes)  
Microprocessor has sensed an error in it’s redun-  
dant software comparison  
If error code is not cleared by resetting unit  
power, replace the IGC.  
CAUTION: If the IGC must be replaced, be sure to ground yourself to dissipate any electrical charge that may be present before handling  
new control board. the IGC is sensitive to static electricity and may be damaged if the necessary precautions are not taken.  
IMPORTANT: Refer to Heating Troubleshooting Chart for additional troubleshooting analysis.  
LEGEND  
IGC – Integrated Gas Unit Controller  
LED – Light-Emitting Diode  
—28—  
START-UP CHECKLIST  
(REMOVE AND STORE IN JOB FILE)  
I. PRELIMINARY INFORMATION  
MODEL NO.: _____________________________ SERIAL NO.: ________________________________________  
DATE: __________________________________ TECHNICIAN: ________________________________________  
II. PRE-START-UP (Insert checkmark in box as each item is completed)  
( ) VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT  
( ) VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS  
( ) CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS  
( ) CHECK GAS PIPING FOR LEAKS  
( ) CHECK THAT INDOOR (EVAPORATOR) AIR FILTER IS CLEAN AND IN PLACE  
( ) VERIFY THAT UNIT INSTALLATION IS LEVEL  
( ) CHECK FAN WHEEL, AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS  
III. START-UP  
ELECTRICAL  
SUPPLY VOLTAGE L1-L2__________ L2-L3__________ L3-L1__________  
COMPRESSOR AMPS L1 __________ L2 __________ L3 __________  
INDOOR (EVAPORATOR) FAN AMPS __________  
TEMPERATURES  
OUTDOOR (CONDENSER) AIR TEMPERATURE __________ DB  
RETURN-AIR TEMPERATURE __________ DB __________ WB  
COOLING SUPPLY AIR __________ DB __________ WB  
GAS HEAT SUPPLY AIR __________  
PRESSURES  
GAS INLET PRESSURE __________ IN. WG  
GAS MANIFOLD PRESSURE __________ IN. WG  
REFRIGERANT SUCTION __________ PSIG SUCTION LINE TEMP* __________  
REFRIGERANT DISCHARGE __________ PSIG DISCHARGE TEMP† __________  
( ) VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS  
( ) VERIFY THAT THREE-PHASE SCROLL COMPRESSOR IS ROTATING IN CORRECT DIRECTION.  
* Measured at suction inlet to compressor.  
† Measured at liquid line leaving condenser.  
—29—  
© 2006 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231  
Printed in U.S.A.  
Catalog No. II 583B-30-1  
—30—  

Brother IntelliFAX 4750e User Manual
Brother MFC 885CW User Manual
Campbell Hausfeld MP5141 User Manual
Cisco Systems All in One Printer C9800 GA User Manual
Continental Electric CE11105 User Manual
DCS UT624 User Manual
Epson WorkForce 610 Series User Manual
Friedrich HA24K75L User Manual
Haier AS122ADMAA User Manual
Havis Shields 1995 2007 Ford Crown Victoria Trak Mount Kit C TM CV User Manual