Bryant High Wall Duct Free Split System 619E User Manual

Bryant  
Day & Night  
Payne  
Model 619E  
HIGH WALL DUCT-FREE,  
SPLIT SYSTEMS  
Sizes 009-024  
3
Air Conditioning  
4
to 2 Tons  
PRELIMINARY PRODUCT DATA  
619E  
538A  
538C/D009,012  
538S (048 Shown)  
DESCRIPTION  
through ductwork. Also, since the outdoor units can be installed  
6-in. away from outside walls, coils are protected from vandals  
and severe weather.  
These duct-free split systems cool, heat (heat pump systems  
only) dehumidify, circulate, and filter the air — with minimum  
maintenance. They are the ideal complement to your ducted  
system when it is impractical or prohibitively expensive to use a  
ducted system. The outdoor units, when matched with model  
619E fan coil units, offer many technological features and reli-  
able operation.  
In addition, the compact duct-free split systems take only a few  
hours to installl, without any major interruptions to the custom-  
ers’ workplace or home.  
STANDARD SYSTEM FEATURES  
The duct-free split systems are perfect for add-ons, such as an  
office or family room addition, and whenever you have special  
space requirements; like for a computer room. Or consider duct-  
free split systems when changes in the cooling load cannot be  
handled by the existing system; for instance, when adding heat-  
generating equipment to an already air-conditioned space.  
HIGH-EFFICIENCY design with SEERs (Seasonal Energy Effi-  
ciency Ratios) up to 12.0 and HSPFs (heating seasonal perfor-  
mance factors; heat pump systems only) of 6.8.  
MICROPROCESSOR CONTROL for accurate control of the de-  
sired comfort level.  
EXTENSIVE DIAGNOSTICS alert the user to the existence of  
problems.  
Split systems can also be used when adding air conditioning to  
spaces that are heated by hydronic or electric heat, and no  
ductwork exists. Historical renovations are another application  
for which duct-free split systems are well suited, especially  
when preserving the looks of the original structure is essential.  
BUILT-IN RELIABILITY COMPONENTS include a suction-line  
accumulator that safeguards the compressor against loss of lu-  
brication, while start capacitors and relays (non-scroll units) as-  
sure dependable start-ups, especially during low-voltage  
conditions (down to 187 v). High- and low-pressure safety  
switches, crankcase heater (non-scroll units), liquid line filter  
drier (538A, 538C, 538S), bi-flow liquid line filter drier (538D),  
and lock-out protection are also standard on most sizes.  
When noise is a concern, these whisper-quiet split systems are  
your answer because you don’t have to worry about duct  
design.  
If security is an issue, outdoor and indoor units are connected  
only by refrigerant piping to prevent intruders from crawling  
Form No. PDS 619E.09.1  
STANDARD FEATURES AND FIELD-INSTALLED ACCESSORIES  
HIGH WALL  
SYSTEMS  
(619B,D)  
STANDARD FEATURE/FIELD-INSTALLED  
ACCESSORY  
Internal Condensate Pump  
A
S
S
S
S
S
S
S
S
S
S
S
S
S
S†  
S
S
S
S
S
S
S
S
S
A
S
S
S
S
S
S
S
S
A
A
S
A
A
Mounting Brackets  
Microprocessor Controls  
Cleanable Filters  
3-Speed Indoor-Fan Motor  
Automatic Indoor-Fan Speed Control  
Extensive Diagnostics  
Wireless Remote Controllers  
Fully Insulated Indoor Unit Cabinet  
Automatic Air Sweep  
Auto. Restart Function  
24-Hour Automatic Start/Stop Timer  
Refrigerant Line Turn Elbow*  
High- and Low-Voltage Terminal Blocks (Indoor)  
AccuRaterRefrigerant Metering Device  
Manual Defrost**  
Demand Defrost**  
Warm Start (in heating)**  
Heating Operation to −20 F**  
Auto. Changeover from Cooling to Heating**  
Evaporator Coil Freeze Protection  
Outdoor Low-Voltage Terminal Block  
Accumulator  
Crankcase Heater (Reciprocating Compressor Units)  
Crankcase Heater (Scroll Compressor Units)  
High-Pressure Switch*  
Low-Pressure Switch*  
5-Year Compressor Warranty  
Compressor Start Assistance (non-scroll units)  
Cycle-LOC™ Device*  
Suction and Discharge Service Taps††  
Totally Enclosed Fan Motor  
Acoustically-Lined Compressor Compartment  
Winter Start Control*  
Low Ambient Temperature Controls (down to −20 F)†  
Time GuardCycle Protector*  
Liquid Solenoid Valve*  
Condensing Unit Wall Mount Kit  
LEGEND  
A
S
Field-Installed Accessory  
Standard from the Factory  
*For size 018 and larger.  
†Not used on 38HDS systems.  
**Heat pump systems only.  
††The outdoor units are equipped with 4 taps; one for each service valve, and one each  
on compressor suction and discharge.  
3
MODEL DESCRIPTION  
OUTDOOR UNITS  
*009 systems only.  
†538C,D only.  
**538A, 538D only.  
††538A, 538D, 538S only.  
538S only.  
FAN COIL UNITS  
*009 systems ony.  
4
SYSTEM CAPACITIES  
TOTAL  
INDOOR SECTIONS  
NOMINAL  
SYSTEM  
CAPACITY  
(Tons)  
SYSTEM  
NET  
SYSTEM  
NET  
OUTDOOR  
SOUND  
OUTDOOR STANDARD  
SYSTEM  
TYPE  
FAN COIL  
TYPE(S)  
SECTION  
538  
CFM (AT  
HIGH  
SPEED)  
SEER HSPF*  
COOLING HEATING  
RATING  
Model  
Ckt  
Qty  
(Btuh)  
(Btuh)*  
(Decibels)  
No. 619  
3
4
A
1
1
1
1
1
1
1
1
2
E
E
E
E
E
E
E
E
E
009  
012  
018  
024  
009  
012  
018  
024  
018  
A
A
C
C
D
D
D
D
S
009  
012  
018  
024  
009  
012  
018  
024  
024  
286  
358  
534  
521  
293  
350  
502  
574  
1000  
8,500  
11,800  
17,300  
22,600  
9,000  
10.5  
11.0  
11.5  
12.0  
10.5  
10.5  
11.5  
11.0  
11.0  
65  
65  
70  
68  
65  
65  
70  
68  
68  
1
112  
Cooling  
Only  
High Wall  
2
3
4
9,000  
12,500  
16,900  
21,400  
6.8  
6.8  
6.8  
6.8  
1
112  
2
12,500  
17,300  
23,200  
23,000  
Heat  
Pump  
High Wall  
High Wall  
In-Ceiling Cassette  
High Wall  
A
A
1
1
F
E
024  
018  
S
S
S
S
S
024  
024  
048  
048  
048  
1059  
1034  
1068  
1589  
1042  
23,000  
23,000  
46,000  
46,000  
46,000  
11.0  
11.0  
11.0  
11.0  
11.0  
68  
68  
72  
72  
72  
2
Ceiling Suspended  
High Wall  
A
A
1
1
C
E
024†  
018  
A
B
2
2
E
E
018  
018  
High Wall  
High Wall  
High Wall  
A
B
1
2
E
E
024  
018  
A
B
1
1
E
E
024  
024  
High Wall  
A
B
B
2
1
1
E
E
C
018  
High Wall  
018  
S
S
048  
048  
2102  
2127  
46,000  
46,000  
11.0  
11.0  
72  
72  
Ceiling-Suspended  
024†  
High Wall  
A
B
B
2
1
1
E
E
F
018  
018  
024  
High Wall  
In-Ceiling Cassette  
High Wall  
A
B
2
2
E
C
018  
S
S
048  
048  
2068  
2118  
47,000  
46,000  
11.0  
11.0  
72  
72  
Ceiling Suspended  
024†  
High Wall  
In-Ceiling Cassette  
A
B
2
2
E
F
018  
024  
High Wall  
A
B
B
2
1
1
E
C
F
018  
Ceiling Suspended  
In-Ceiling Cassette  
024†  
024  
S
S
S
S
S
048  
048  
048  
048  
048  
2059  
2034  
2059  
2109  
2084  
46,000  
47,000  
47,000  
46,000  
46,000  
11.0  
11.0  
11.0  
11.0  
11.0  
72  
72  
72  
72  
72  
Multi-  
Split  
Ceiling Suspended  
Ceiling Suspended  
High Wall  
A
B
B
2
1
1
C
C
E
024†  
024†  
018  
4
Ceiling Suspended  
In-Ceiling Cassette  
High Wall  
A
B
B
2
1
1
C
F
E
024†  
024  
018  
In-Ceiling Cassette  
In-Ceiling Cassette  
High Wall  
A
B
B
2
1
1
F
F
E
024  
024  
018  
In-Ceiling Cassette  
Ceiling Suspended  
High Wall  
A
B
B
2
1
1
F
C
E
024  
024†  
018  
High Wall  
A
B
2
1
E
F
018  
036  
S
S
S
S
S
048  
048  
048  
048  
048  
1983  
1668  
1521  
1559  
1436  
47,000  
45,800  
46,800  
45,800  
46,800  
11.0  
11.0  
11.0  
11.0  
11.0  
72  
72  
72  
72  
72  
In-Ceiling Cassette  
High Wall  
Ceiling Suspended  
A
B
2
1
E
C
018  
024  
High Wall  
In-Ceiling Cassette  
A
B
1
1
E
F
024  
036  
High Wall  
Ceiling Suspended  
A
B
1
1
E
C
024  
024  
Ceiling Suspended  
High Wall  
A
B
2
1
C
E
024†  
024  
Ceiling Suspended  
In-Ceiling Cassette  
High Wall  
A
A
B
1
1
1
C
F
E
024†  
024  
024  
S
048  
1121  
45,600  
11.0  
72  
LEGEND  
NOTES:  
1. Rating condition is 80 F db, 67 F wb air entering indoor air section  
and 95 F db air entering outdoor air section.  
Decibels  
Ckt  
Sound Levels  
Circuit  
Heating Seasonal Performance Factors  
Seasonal Energy Efficiency Ratio  
2. Total kW is for total system, including compressor and outdoor and  
indoor fans.  
3. Ratings are based on 25 ft of interconnecting refrigerant line.  
4. All system ratings are based on fan coil units operating at high fan  
speed. Consult Specifications tables for airflows at all available fan  
speeds.  
HSPF  
SEER  
*Heat pump systems only.  
†Unit must be reconfigured for 112 ton (18,000 Btuh) operation. Refer to  
installation instructions included with the fan coil unit for more details.  
5
SPECIFICATIONS — 538A AND 538C CONDENSING UNITS  
UNIT  
538C 009  
538C 012  
538A 018  
112  
538A 024  
3
NOMINAL CAPACITY (Tons)  
OPERATING WEIGHT (lb)  
REFRIGERANT TYPE  
4
1
2
55.0  
62.0  
150  
154  
R-22  
Control (Cooling)  
Capillary  
Carlyle Rotary  
AccuRaterPiston at Fan Coil Unit  
Factory Charge (lb)*  
1.5  
1.5  
4.6  
5.3  
COMPRESSOR TYPE  
Tecumseh  
Copeland  
Scroll  
Reciprocating  
Model  
EAA090111A  
EBB120111A  
AW5517G  
ZR23K1  
OUTDOOR FAN  
Propeller Type  
Rpm  
1050  
1050  
850  
1720  
850  
1720  
Nominal Air Cfm (High Speed)  
OUTDOOR COIL  
Copper Tube, Aluminum Fin  
Face Area (sq ft)...No. of Rows  
Fins/in.  
3.5...1  
18  
3.5...2  
18  
6.1...1.5  
15  
6.1...2  
15  
CONTROLS  
High-Pressure (psig)  
Cutout  
426 ±  
7
Cut-in  
320 ± 20  
Low-Pressure (psig)  
Cutout  
Cut-in  
Fusible Plug  
Control Voltage†  
210 F  
115  
210 F  
230  
7 ±  
22 ±  
210 F  
24  
3
5
REFRIGERANT LINES  
Connection Type  
Flare  
Grey  
Sweat  
1
1
3
3
Liquid Line OD (in.)  
4
2
4
2
8
8
8
8
1
1
5
5
Vapor Line OD (in.)  
Maximum Length (ft)  
Maximum Lift (Fan Coil Above Outdoor) (ft)  
Maximum Lift (Fan Coil Below Outdoor) (ft)  
35  
16  
30  
35  
16  
30  
200  
65  
150  
200  
65  
150  
EXTERNAL FINISH  
Alpine Mist (Beige)  
*See System Piston Guide and Refrigerant Charges tables in Application section on page 21 for proper  
charge and piston with each fan coil type. Charge is based on duct-free fan coil requiring smallest  
amount of refrigerant and 25 ft of interconnecting line.  
†24 v and a minimum of 40 va is provided in the fan coil unit.  
6
SPECIFICATIONS — 538D HEAT PUMP UNITS  
UNIT 538D  
009  
012  
1
018  
112  
154  
024  
2
3
NOMINAL CAPACITY (Tons)  
OPERATING WEIGHT (lb)  
REFRIGERANT TYPE  
4
60.7  
66.6  
167  
R-22  
Control (Cooling)  
Control (Heating)  
Factory Charge (lb)*  
Fixed Orifice at Outdoor Unit  
Fixed Orifice at Outdoor Unit  
AccuRaterPiston at Fan Coil Unit  
AccuRater Piston at Outdoor Unit  
1.5  
2.0  
5.0  
5.1  
COMPRESSOR TYPE  
Model  
Carlyle Rotary  
Tecumseh Reciprocating  
EBA095111H  
EBB130111H  
AW5519G  
AW5524G  
OUTDOOR FAN  
Propeller Type  
Propeller, Direct Drive  
Rpm (Cooling and Heating)  
Nominal Air Cfm (High Speed)  
1050  
1050  
850  
1720  
850  
1720  
OUTDOOR COIL  
Copper Tube, Aluminum Fin  
Face Area (sq ft)...No. of Rows  
Fins/in.  
3.5...1  
18  
3.5...2  
18  
6.1...1.5  
15  
6.1...2  
15  
CONTROLS  
High-Pressure (psig)  
Cutout  
320 ± 20  
Cut-in  
426 ±  
7
Liquid Line Low-Pressure (psig)  
Cutout  
Cut-in  
Fusible Plug  
Defrost Method†  
Accumulator  
Control Voltage**  
210 F  
210 F  
7 ±  
3
5
22 ±  
210 F  
Time and Temperature Defrost  
Yes  
115  
Time and Temperature Defrost  
Yes  
230  
Yes  
24  
REFRIGERANT LINES  
Connection Type  
Flare  
Sweat—Suction; Flare—Liquid  
1
1
3
5
3
5
Mixed Phase Line OD (in.)  
Suction Line OD (in.)  
4
2
4
2
8
8
1
1
8
8
Maximum Length (ft)  
Maximum Lift (Fan Coil Above Outdoor) (ft)  
Maximum Lift (Fan Coil Below Outdoor) (ft)  
35  
16  
30  
35  
16  
30  
200  
65  
150  
200  
65  
150  
EXTERNAL FINISH  
Grey  
Alpine Mist (Beige)  
*Units are shipped with charge listed (smallest applicable system charge). Refer to Piston Guide tables on page 21  
for proper charge for your application.  
†Demand defrost.  
**A 24-v transformer is provided in the 018, 024 fan coil unit.  
7
SPECIFICATIONS — 538S CONDENSING UNITS  
UNIT 538S  
024  
2
048  
4
NOMINAL CAPACITY (Tons)  
OPERATING WEIGHT (lb)  
REFRIGERANT TYPE  
159  
292  
R-22  
Control (Cooling)  
Factory Charge (lb)*  
Circuit A  
TXV in Condensing Unit  
5.0  
5.5  
5.5  
Circuit B  
COMPRESSOR TYPE  
Copeland Scroll  
Quantity...Model  
Oil (Recharge) (oz)  
1...ZR23K1  
25  
2...ZR23K1  
25  
OUTDOOR FAN  
Propeller, Direct Drive  
Rpm  
Nominal Air Cfm  
850  
1720  
850  
3900  
OUTDOOR COIL  
Copper Tube, Aluminum Fin  
Face Area (sq ft)...No. of Rows  
Fins/in.  
6.1...2  
15  
12.3...2  
15  
CONTROLS  
High-Pressure (psig)  
Cut-in  
320 ± 20  
Cutout  
426 ±  
7
Low-Pressure (psig)  
Cut-in  
Cutout  
Fusible Plug  
Control Voltage  
22 ± 5  
7 ± 3  
210 F  
24  
REFRIGERANT LINES  
Connection Type  
Sweat  
Vapor Supply Line Quantity...OD (in.)  
Vapor Return Line Quantity...OD (in.)  
Maximum Length (ft)  
2...38  
2...58  
50  
30†  
30†  
4...38  
4...58  
50  
30†  
30†  
Maximum Lift (Fan Coil Above Outdoor) (ft)  
Maximum Lift (Fan Coil Below Outdoor) (ft)  
EXTERNAL FINISH  
Alpine Mist (Beige)  
LEGEND  
TXV  
Thermostatic Expansion Valve  
*Charges are preliminary estimates and are based on 25 ft of intercon-  
necting line.  
†Maximum system lift is 30 ft between lowest system component and  
highest system component.  
SPECIFICATIONS — 619E FAN COIL UNITS  
UNIT 619E  
009*  
012*  
009†  
012†  
018  
024  
OPERATING WEIGHT (lb)  
REFRIGERANT**  
FAN  
18.7  
24.2  
18.7  
24.2  
39  
43  
R-22  
R-22 with AccuRaterControl or TXV  
Centrifugal Blower  
Rpm  
1250  
215  
1150  
302  
1250  
252  
1150  
302  
1300  
480/455**  
1505  
550/525**  
Nominal Cfm (High Speed)  
COIL  
Face Area (sq ft)...Rows  
Fins/in.  
1.45...2  
18  
1.60...3  
17  
1.45...2  
18  
1.60...3  
17  
2.56...2  
15.9  
2.56...3  
18.1  
CONNECTIONS (MPT)  
1
5
3
Vapor (in.) Flare  
Liquid (in.) Flare  
2
4
8
8
1
5
5
Condensate Drain  
LINE SIZES  
8
8
1
1
5
5
3
5
Vapor (in.)  
2
4
8
8
8
8
Liquid (in.)  
Condensate Drain  
LEGEND  
TXV  
Thermostatic Expansion Valve (538S Systems Only)  
*Cooling-only fan coil unit.  
†Heat pump fan coil unit. Cooling only/Heat pump.  
**See outdoor unit nameplate for correct system charge.  
8
DIMENSIONAL DRAWING, BASE UNIT — 538C/D009,012 COOLING ONLY AND HEAT PUMP UNITS  
NOTES:  
1. Dimensions in [ ] are in millimeters.  
2.  
Direction of airflow.  
3.  
Center of gravity.  
4. Minimum clearances, 4 in. on coil sides, 24 in. on fan  
side, and 30 in. service side.  
WEIGHT  
UNIT  
538  
Lb  
Kg  
C
009  
012  
009  
012  
55.0  
62.0  
60.7  
66.5  
25.0  
28.1  
27.5  
30.2  
C
D
D
9
DIMENSIONAL DRAWING — BASE UNIT — 538A018-024 CONDENSING UNITS  
A
B
C
D
E
F
G
H
UNIT  
538A  
ft-in. mm ft-in.  
mm  
ft-in. mm ft-in. mm  
ft-in.  
mm ft-in. mm ft-in. mm ft-in. mm  
018 2-118 638.2 3-01516 938.2 1-2916 369.9 1-4 406.4 1-11716 595.3 1-5316 436.6 1-512 444.5 1-818 511.2  
024 2-118 638.2 3-01516 938.2 1-2916 369.9 1-4 406.4 1-11716 595.3 1-5316 436.6 1-512 444.5 1-818 511.2  
OPERATING  
J
K
L
M
N
R
S
UNIT  
538A  
WT  
ft-in. mm ft-in. mm  
ft-in.  
mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm  
Lb  
kg  
018 1-114 336.6 0-658 168.3 0-101316 274.6 0-058 15.00 0-038 9.52 0-412 115.0 0-612 166.0 150  
024 1-2716 366.7 0-634 171.4 1- 0 304.8 0-058 15.00 0-038 9.52 0-412 115.0 0-612 166.0 154  
68.0  
69.0  
MINIMUM MOUNTING PAD DIMENSIONS  
Support Feet Snow Stand Ice Stand  
ft-in.  
mm  
ft-in.  
mm  
ft-in.  
mm  
1-11 x  
3-6  
584.2 x  
1066.8  
2-2 x  
3-6  
660.4 x  
1066.8  
2-2 x  
3-6  
660.4 x  
1066.8  
NOTES:  
1. Required clearances, with coil facing wall, allow  
6 in. minimum clearance on coil side and coil end,  
and 3 ft minimum clearance on compressor end  
and fan side. With fan facing wall, allow 8 in. mini-  
mum clearance on fan side and coil end, and 3 ft  
minimum clearance on compressor end and coil  
side. With multi-unit application, arrange units so  
discharge of one does not enter inlet of another.  
2. Dimensions in parenthesis are in millimeters.  
3.  
Center of Gravity.  
10  
DIMENSIONAL DRAWING, BASE UNIT — 538D018,024 HEAT PUMP UNITS  
A
B
C
D
E
F
UNIT  
538D  
ft-in.  
mm  
ft-in.  
mm  
ft-in.  
mm ft-in. mm  
ft-in.  
mm  
ft-in.  
mm  
018  
024  
2-118 638.2 3-01516  
2-118 638.2 3-01516  
938.2 1-2916 369.9 1-4  
938.2 1-2916 369.9 1-4  
406.4 1-11716 595.3 1-5316 436.6  
406.4 1-11716 595.3 1-5316 436.6  
OPERATING  
G
H
J
K
L
M
UNIT  
538D  
WEIGHT  
ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm  
1-512 444.5 1-818 511.2 1-1 330.2 0-658 168.3 0-1114 285.8 0-058 15.88 154  
1-512 444.5 1-818 511.2 1-1 330.2 0-634 171.5 0-1158 295.3 0-058 15.88 167  
lb  
Kg  
018  
024  
69.8  
75.7  
LEGEND  
Connection  
CONN  
MINIMUM MOUNTING PAD DIMENSIONS  
Support Feet Snow Stand Ice Stand  
ft-in.  
mm  
ft-in.  
mm  
ft-in.  
mm  
1-11 x  
3-6  
584.2 x  
1066.8  
2-2 x  
3-6  
660.4 x  
1066.8  
2-2 x  
3-6  
660.4 x  
1066.8  
NOTES:  
1. Required clearances, with coil facing wall; allow  
6 in. minimum clearance on coil side and coil end,  
and 3 ft minimum clearance on compressor end  
and fan side. With fan facing wall; allow 8 in. mini-  
mum clearance on fan side and coil end, and 3 ft  
minimum clearance on compressor end and coil  
side. With multi-unit application; arrange units so  
discharge of one does not enter inlet of another.  
2. Dimensions in [ ] are in millimeters.  
3.  
Center of gravity.  
11  
DIMENSIONAL DRAWING, BASE UNIT — 538S CONDENSING UNITS  
A
B
C
D
E
F
G
H
UNIT  
538S  
Ft-in. mm Ft-in. mm Ft-in. mm Ft-in. mm Ft-in. mm Ft-in. mm Ft-in. mm Ft-in. mm  
406 1-11716 595 1-5316 437 1-512 445 1-818 511  
024 2-118 638 3-01516 938 1-2916 370 1-4  
048 3-1316 945 3-8916 1132 1-5116 433 1-6716 468 2- 612 775 1-758 499 2-558 753 2-8316 818  
OPERATING  
J
K
L
M
N
R
S
UNIT  
538S  
WEIGHT  
Ft-in. mm Ft-in. mm Ft-in. mm Ft-in. mm Ft-in. mm Ft-in. mm Ft-in. mm Lb  
1-2716 367 0-634 171 1-0 305 0-058 16 0-038 10  
159  
Kg  
024  
048  
72.0  
1-234 375 0-712 191 1-6 457 0-058 16 0-038 10 0-6516 160 0-578 149 292 132.3  
NOTES:  
MINIMUM MOUNTING PAD DIMENSIONS  
SUPPORT FEET SNOW STAND ICE STAND  
Ft-in. mm Ft-in. mm Ft-in. mm  
1. Required clearances: with coil facing wall; allow 6 in. mini-  
mum clearance on coil side and coil end, and 3 ft minimum  
clearance on compressor end and fan side. With fan facing  
wall; allow 8 in. minimum clearance on fan side and coil  
end, and 3 ft minimum clearance on compressor end and  
coil side. With multi-unit application: arrange units so dis-  
charge of one does not enter inlet of another.  
UNIT  
538S  
024  
048  
1-11 x 3-6 584 x 1067 2-2 x 3-6 660 x 1067 2-2 x 3-6 660 x 1067  
2-0 x 4-2 610 x 1270 2-4 x 4-4 711 x 1270 2-2 x 4-2 660 x 1270  
2. Dimensions in [ ] are in millimeters.  
3.  
Center of gravity.  
12  
DIMENSIONAL DRAWING, BASE UNIT — 619E009,012 FAN COIL UNITS  
NOTES:  
WEIGHT  
A
B
C
UNIT  
619E  
1. Dimensions are in inches. Dimensions in [ ] are in millimeters.  
Lb  
Kg  
in.  
mm  
in.  
mm  
in.  
mm  
2.  
Direction of airflow.  
009  
012  
18.7  
8.5 33.46 850 11.02 280 6.29 160  
3. Refrigerant, drain and power connections may be made rear, left side or right side.  
4. Refrigerant is metered by capillary tubes in the outdoor unit. Insulate both refrig-  
erant lines.  
24.2 11.0 36.61 930 11.81 300 7.28 185  
5. Clearances of 312Љ on top and to the left of the fan coil unit are absolute minimums.  
Clearances of 10Љ are recommended.  
13  
DIMENSIONAL DRAWING, BASE UNIT — 619E018,024 FAN COIL UNITS  
NOTES:  
UNIT  
619E  
1. Dimensions in [ ] are in millimeters.  
WEIGHT  
2.  
Direction if airflow.  
018  
024  
39 Lb [17.5 Kg]  
43 Lb [19.5 Kg]  
3. Refrigerant, drain, and power connections may be made in unit rear, bottom,  
left side, or right side.  
4. Refrigerant is metered by AccuRaterdevice at the fan coil unit on 538A and  
538D018,024 applications. A thermostatic expansion valve is used in the out-  
door unit on 538S applications. Insulate both refrigerant lines on 538S and  
538D018,024 applications.  
5. The 4Љ top and left clearances are absolute minimums. Clearances of 10Љ are  
recommended.  
14  
ELECTRICAL DATA  
CONDENSING UNITS  
OPERATING  
VOLTAGE  
MINIMUM*  
OPERATING  
VOLTAGE  
MAXIMUM*  
POWER  
MOCP†  
VOLTAGE  
(Single Ph, 60 Hz)  
COMP  
RLA  
FAN  
FLA  
UNIT  
MCA†  
538A 018  
538A 024  
538C 009  
538C 012  
8.0  
12.9  
7.6  
10.7  
16.8  
12.1  
8.5  
15  
25  
15  
15  
208/230  
187  
254  
0.70  
115  
104  
187  
127  
253  
0.76  
0.35  
208/230  
5.5  
LEGEND  
NOTES:  
1. The 018 and 024 outdoor units contain a 24-v transformer; additional  
transformers are not required. The 009, 012 outdoor units use high  
voltage controls.  
FLA  
Full Load Amps  
Heating, Air Conditioning, Refrigeration  
Locked Rotor Amps  
Minimum Circuit Amps per NEC Section 430-24  
National Electrical Code  
Rated Load Amps (Compressor)  
HACR  
LRA  
MCA  
NEC  
RLA  
2. All motors and compressors contain internal overload protection.  
3. In compliance with NEC requirements for multimotor and combina-  
tion load equipment (refer to NEC Articles 430 and 440), the over-  
current protective device for the unit shall be fuse or HACR breaker.  
4. Motor RLA values are established in accordance with UL (Underwrit-  
ers’ Laboratories) Standard 1995.  
*Permissible limits of the voltage range at which unit will operate  
satisfactorily.  
†Cooling only fan coil unit.  
**Heat pump fan coil unit.  
HEAT PUMP UNITS  
OPERATING  
VOLTAGE  
MINIMUM*  
OPERATING  
POWER  
MOCP  
UNIT  
538D  
VOLTAGE  
(Single Ph, 60 Hz)  
COMP  
RLA  
FAN  
FLA  
VOLTAGE  
MCA  
MAXIMUM*  
009  
012  
018  
024  
115  
104  
187  
127  
254  
9.0  
5.8  
0.76  
0.35  
11.2  
13.9  
13.0  
15.3  
15  
15  
20  
25  
208/230  
9.8  
208/230  
187  
254  
0.70  
11.7  
LEGEND  
NOTES:  
1. The 018 and 024 outdoor units contain a 24-v transformer; additional  
transformers are not required. The 009, 012 outdoor units use high  
voltage controls.  
FLA  
Full Load Amps  
Heating, Air Conditioning, Refrigeration  
Locked Rotor Amps  
Minimum Circuit Amps per NEC Section 430-24  
National Electrical Code  
Rated Load Amps (Compressor)  
HACR  
LRA  
2. All motors and compressors contain internal overload protection.  
3. In compliance with NEC requirements for multimotor and combina-  
tion load equipment (refer to NEC Articles 430 and 440), the over-  
current protective device for the unit shall be fuse or HACR breaker.  
4. Motor RLA values are established in accordance with UL (Underwrit-  
ers’ Laboratories) Standard 1995.  
MCA  
NEC  
RLA  
*Permissible limits of the voltage range at which unit will operate  
satisfactorily.  
†Cooling only fan coil unit.  
**Heat pump fan coil unit.  
MULTI-SPLIT CONDENSING UNITS  
COMPRESSOR  
FAN  
FLA  
POWER SUPPLY  
OPERATING  
VOLTAGE  
MINIMUM*  
OPERATING  
UNIT SIZE  
538S  
Max Fuse  
or HACR-Type  
Circuit Breaker Amps  
V-PH-Hz  
VOLTAGE  
RLA  
(Ea)  
LRA  
(Ea)  
Quantity  
MCA  
MAXIMUM*  
024  
048  
1
2
0.70  
1.45  
16.8  
30.5  
25  
40  
208/230-1-60  
187  
254  
12.9  
62.5  
LEGEND  
NOTES:  
1. The 024 and 048 outdoor units contain a 24-v transformer; additional  
transformers are not required.  
FLA  
Full Load Amps  
Heating, Air Conditioning, Refrigeration  
Locked Rotor Amps  
Minimum Circuit Amps per NEC Section 430-24  
National Electrical Code  
Rated Load Amps (Compressor)  
HACR  
LRA  
2. All motors and compressors contain internal overload protection.  
3. In compliance with NEC requirements for multimotor and combina-  
tion load equipment (refer to NEC Articles 430 and 440), the over-  
current protective device for the unit shall be fuse or HACR breaker.  
4. Motor RLA values are established in accordance with UL (Underwrit-  
ers’ Laboratories) Standard 1995.  
MCA  
NEC  
RLA  
*Permissible limits of the voltage range at which unit will operate  
satisfactorily.  
†Cooling only fan coil unit.  
**Heat pump fan coil unit.  
15  
ELECTRICAL DATA (cont)  
FAN COIL UNITS  
INDOOR  
UNIT  
619E  
OPERATING VOLTAGE*  
FAN  
FLA  
V (Single-  
Ph, 60 Hz)  
Minimum  
Maximum  
009†  
012†  
009**  
012**  
018†  
024†  
018**  
024**  
115  
208/230  
115  
104  
187  
104  
187  
127  
253  
127  
253  
208/230  
208/230  
187  
253  
0.53  
LEGEND  
Full Load Amps  
NOTES:  
1. The 018, 024, 048 outdoor units contain a 24-v transformer; addi-  
tional transformers are not required. The 009, 012 outdoor units use  
230-v (high voltage) controls.  
FLA  
HACR  
LRA  
MCA  
NEC  
RLA  
Heating, Air Conditioning, Refrigeration  
Locked Rotor Amps  
2. All motors and compressors contain internal overload protection.  
3. In compliance with NEC requirements for multimotor and combina-  
tion load equipment (refer to NEC Articles 430 and 440), the over-  
current protective device for the unit shall be fuse or HACR breaker.  
4. Motor RLA values are established in accordance with UL (Underwrit-  
ers’ Laboratories) Standard 1995.  
Minimum Circuit Amps per NEC Section 430-24  
National Electrical Code  
Rated Load Amps (Compressor)  
*Permissible limits of the voltage range at which unit will operate  
satisfactorily.  
†Cooling only fan coil unit.  
**Heat pump fan coil unit.  
16  
TYPICAL INSTALLATION — HIGH-WALL SYSTEMS, 9,000 AND 12,000 BTUH  
(Cooling-Only System Shown)  
LEGEND  
National Electrical Code  
NEC  
*Standard.  
†Field supplied.  
NOTES:  
1. All piping must follow standard refrigerant techniques.  
2. Do not install a filter drier in mixed phase liquid line.  
3. All wiring must comply with applicable local and national codes.  
4. Capillary tube expansion device (cooling-only systems only) is located in the  
outdoor unit. Both refrigerant lines must be insulated.  
5. Wiring and piping shown are general points-of-connection guides only and are  
not intended to include all details for a specific installation.  
6. Insulate condensate line drain if installed in a conditioned space.  
17  
TYPICAL INSTALLATION — HIGH-WALL SYSTEMS, 18,000 AND 24,000 BTUH  
(Cooling Only System Shown)  
LEGEND  
NEC  
National Electrical Code  
Piping  
Line Voltage  
24 V  
Thermistor  
*Standard.  
†Field supplied.  
NOTES:  
1. All piping must follow standard  
refrigerant piping techniques.  
2. All wiring must comply with the  
applicable local and national  
codes.  
3. Liquid line need not be insulated.  
4. Wiring and piping shown are gen-  
eral points-of-connection guides  
only and are not intended for a  
specific installation.  
5. Insulate condensate drain if in-  
stalled in a conditioned space.  
18  
APPLICATION DATA  
5. Mounting template  
1. Unit selection  
The fan coil units are furnished with a mounting template to  
mark the location of the mounting brackets, wiring, and re-  
frigeration hole locations.  
Select equipment to either match or be slightly less than an-  
ticipated peak load. This provides better humidity control,  
fewer unit cycles, and less part-load operation.  
6. Support  
For units used in spaces with high sensible loads, base  
equipment selection on unit sensible load, not on total an-  
ticipated load. Adjust for anticipated room wet bulb tem-  
perature to avoid undersizing equipment.  
Adequate support must be provided to support the weight  
of all fan coils. Refer to the Specification tables on  
page 8 for fan coil weights, and the base unit dimensional  
drawings on pages 13 and 14 for the location of mounting  
brackets.  
For heat pump systems, heating load using outdoor air  
must be checked in addition to cooling load. Heating load of  
outdoor air can greatly reduce heating capability.  
7. System operating conditions  
For heat pump systems, heating and cooling design loads  
must both be checked.  
Operating limits:  
OUTDOOR UNITS  
When selecting equipment which has outdoor air intro-  
duced into the unit, determine the mix conditions of room air  
and outdoor air at design conditions. The cooling capacity  
tables in this literature are based on 80 F edb. Adjust for ac-  
tual dry-bulb and wet-bulb conditions with the required out-  
door air to select the proper equipment.  
CONDITION  
009,012 018,024,048  
Maximum Cooling Ambient (F)  
125  
125  
Minimum Cooling Ambient (F) (without  
accessory low-ambient kit)  
55  
55  
Minimum Cooling Ambient (F) (with  
accessory low-ambient kit)  
–20  
–20  
Minimum Cooling Return-Air Temperature (F)  
Maximum Cooling Return-Air Temperature (F)  
Maximum Heating Return-Air Temperature (F)*  
Minimum Heating Return-Air Temperature (F)*  
Maximum Heating Ambient Temperature (F)*  
Minimum Heating Ambient Temperature (F)  
55  
95  
55  
95  
2. Unit combinations and coil mixed matches  
The 538A, 538C, 538D, and 538S units are the only units  
approved for use with the 619E duct-free split systems.  
These outdoor units may also be used with other fan coil  
units.  
80/71†  
55  
80/71†  
55  
0
−20  
80  
80  
Saturated Suction Temperature Range  
Minimum (F)  
3. Unit mounting (outdoor)  
–15  
55  
–15  
55  
Maximum (F)  
a. Unit leveling — For reliable operation, units should be  
level in all planes.  
Saturated Condensing Temperature Range  
Minimum (F)  
Maximum (F)  
85  
150  
80  
150  
b. Clearance — Adequate clearance must be provided for  
airflow. See dimensional drawings for proper clear-  
ances. The outdoor units are designed for free-blow ap-  
plication. Air inlets and outlets should not be restricted.  
Outdoor fan external static pressure available is less  
than 0.1 in. wg.  
Maximum Compressor Discharge  
Temperature (F)  
275  
60  
275  
60  
Minimum Discharge Superheat (F)  
*Heat pump units only.  
†Dry bulb/wet bulb.  
c. Unit location — Cooling units may be stacked 2 high.  
Units may be wall mounted, pad mounted at ground  
level, roof mounted, mounted on or under a deck, or  
mounted on a patio. Be sure water drainage from roof  
will not drain directly onto the unit.  
FAN COIL UNITS  
ALL  
CONDITION  
UNITS  
Maximum Room  
Temperature (F)  
84  
NOTE: If stacking units is desired (538A, 538C, 538S only),  
field-fabricated and installed hardware is required. Contact  
your local representative for details.  
Minimum Room  
Temperature (F)  
64  
Maximum Return Air (F)  
Dry-Bulb  
Wet-Bulb  
85  
72  
If 018, 024, 048 units are being mounted near a wall, the  
outdoor-air section should discharge toward the wall. This  
will provide inherent coil protection and the best possible  
sound and airflow performance. The 009, 012 units should  
be mounted with fan discharge pointing away from the wall.  
Maximum Saturated  
Suction Temperature (F)  
55  
27  
Minimum Saturated  
Suction Temperature (F)  
8. Low-ambient operation  
4. Unit mounting (indoor)  
Units can operate in cooling down to 55 F (538A, 538C,  
538D) under all conditions without a low-ambient or winter  
start kit.  
a. Unit leveling — For reliable operation, units should be  
level in all planes.  
b. Clearance — Provide adequate clearance for airflow.  
The unit return and discharge should not be obstructed  
by furniture, curtains, or anything which may cause unit  
short cycling or air recirculation. See base unit dimen-  
sional drawings on pages 13 and 14 for required  
clearances.  
c. Unit location — When selecting unit location, select a  
location which will provide the best air circulation for the  
room.  
Units equipped with accessory low-ambient or winter start  
kits should also be equipped with field-fabricated wind  
baffle, field supplied crankcase heater (scroll units only)  
and field-supplied isolation relay.  
a. Winter start (538C and 538S) — The use of a winter  
start control may extend the unit operation range (below  
40 F) without addition of the low-ambient kit. Winter start  
bypasses the low-pressure switch for 3 minutes.  
b. Crankcase heater — Scroll compressor units with low-  
ambient control or winter start should be equipped with  
crankcase heaters to prevent refrigerant migration dur-  
ing compressor off cycle.  
Position units as high as possible on the wall for best air  
circulation. Allow adequate clearances above the unit for  
servicing (removing unit covers). Place the unit in the  
middle (horizontally) of the wall selected (if possible).  
Select an outside wall if available to make piping easier,  
and place the unit so it faces the normal location of room  
occupants.  
c. Freezestat (heat pump systems only) — Freeze up  
protection is provided on all fan coil units.  
19  
APPLICATION DATA (cont)  
9. Metering devices  
method. Since all refrigerant lines are on the low side  
of the system, it is not normally necessary to add or  
remove charge.  
a. 009, 012 units — The 009 and 012 units have capillary  
tubes for refrigerant metering located in the outdoor con-  
densing unit.  
b. 018, 024 units — The 018, 024 units use a piston-type  
metering device located in the indoor unit.  
2) These units have mixed-phase refrigerant flow in the  
liquid line. DO NOT install a filter drier in the liquid  
line. The liquid line must be insulated.  
3) No line size changes should be made on 009, 012  
units.  
NOTE: All 538A, 538C, 538D (018, 024) duct-free split sys-  
tems use Chattleff style AccuRaterpistons. DO NOT mix  
piston types. All 538D009, 012 systems use Aeroquip type  
pistons. See Long-Lines Applications section on page 20  
for changes in piston sizes due to long lines.  
c. 538A,D018, 024 units  
1) These units are shipped with a charge of R-22 refrig-  
erant. See System Piston Guide and Refrigerant  
Charges tables on page 21 for system charges. Add  
additional charge by weight as necessary and check  
the charge with a superheat calculator.  
2) For these units, install the filter drier provided with  
the unit in the liquid line. Use of a field-supplied mois-  
ture indicator is also recommended.  
10. Drain connections  
Install drains to meet local sanitation codes. If adequate  
gravity drainage cannot be provided, unit should be  
equipped with accessory condensate pump. High wall fan  
coil unit condensate pumps have a 10 ft lift capability above  
the condensate pan level.  
d. 538S units  
See base unit dimensional drawings on pages 13 and 14  
for fan coil unit drain locations and sizes.  
1) Outdoor units are shipped with the charges listed in  
the Specifications — 538S Condensing Units table  
on page 8. To determine if additional charge is re-  
quired, add all charges listed in fan coil unit specifi-  
cations table(s) in the Product Data literature for your  
system (per circuit). The sum of the charges listed is  
the system circuit charge required based on 25 ft of  
line.  
NOTE: High wall fan coil units have internal condensate  
traps.  
Drain connections may be routed through alternate loca-  
tions on most fan coils. See base unit dimensional drawings  
on pages 13 and 14 for possible alternate locations.  
11. Refrigerant lines  
2) For the 538S units, filter driers are provided in the  
unit.  
3) Vapor supply lines on all 538S units should be 8 in.  
a. General refrigerant line sizing:  
5
1) All charges, line sizing, and capacities are based on  
runs of 25 ft. For runs over 25 ft, consult long-lines  
section on page 20 for proper line sizing, charge, and  
AccuRater refrigerant metering device sizing.  
only. DO NOT resize vapor supply lines for additional  
length.  
4) When sizing vapor return line, determine line length  
by finding equivalent ft of tubing. Equivalent line  
lengths equal the linear length (measured length) of  
the interconnecting vapor return tubing plus losses  
due to elbows (see Fitting Loss in Equivalent Ft For  
Elbows table on page 21). If the number of elbows is  
not yet known, assume 50% additional length for  
equivalent length. In determining line size, be sure oil  
can be properly returned to the compressor. Contact  
your local representative for oil return recommenda-  
tions as necessary. For line lengths from 25 to 50 ft,  
no special tubing requirements are normally re-  
quired. Adjust charge to required amount by adding  
charge per subcooling method. Refer to 538S base  
unit installation instructions for charging details.  
e. Long-lines applications, 538A,D018,024 units:  
NOTE: For runs less than 25 ft, some of the charge may  
need to be removed to obtain the correct system super-  
heat. The minimum line length should be 8 ft.  
MAXIMUM LINE LENGTHS  
MAXIMUM LIFT MAXIMUM LIFT—  
MAXIMUM  
EQUIVALENT  
FT  
FAN COIL  
BELOW  
FAN COIL  
ABOVE  
UNIT  
CONDENSING  
UNIT  
CONDENSING  
UNIT  
538A, 538D018,024  
538D, 538D009  
538C, 538D012  
538S  
200  
35  
150  
35  
65  
16  
49  
35  
16*  
30†  
50  
30†  
1) Liquid lines on all 538A,D018,024 units should be  
3
8
in. only. DO NOT resize liquid lines for additional  
*This changes to 25 ft with addition of accessory crankcase heater.  
†Maximum distance permitted is 30 ft from lowest system component to  
highest system component.  
length.  
2) When sizing vapor line, determine line length by find-  
ing equivalent ft of pipe. Equivalent line lengths  
equal the linear length (measured length) of the in-  
terconnecting vapor tubing plus losses due to elbows  
(see Fitting Loss in Equivalent Ft For Elbows table  
on page 21). If the number of elbows is not yet  
known, assume 50% additional length for equivalent  
length. In determining line size, be sure oil can be  
properly returned to the compressor. Consult your lo-  
cal representative for proper oil return recommenda-  
tions as necessary. For line lengths from 15 to 49 ft,  
no special piping requirements are normally  
required. Adjust charge to required amount by add-  
ing charge per Step l) on page 23 and checking  
superheat.  
2) Refrigerant lines should not be buried in the ground.  
If it is necessary to bury the lines, not more than  
36 in. should be buried. Provide a minimum 6-in. ver-  
tical rise to the service valves to prevent refrigerant  
migration.  
3) The vapor line must be insulated. Use a minimum of  
1
2-in. thick insulation. Closed-cell insulation is rec-  
ommended in all long-line (over 25 ft) applications.  
4) Special consideration should be given to isolating  
interconnecting tubing from the building structure.  
Isolate the tubing so that vibration or noise is not  
transmitted into the structure.  
b. 538C,D009,012 units  
1) These units are shipped with a charge of R-22 refrig-  
erant. Check the charge using the superheat  
20  
APPLICATION DATA (cont)  
3) For line lengths over 50 ft (018,024 only):  
FITTING LOSS IN EQUIVALENT FT FOR ELBOWS  
a) A crankcase heater should be added to scroll  
compressor units (all non-scroll compressor units  
have crankcase heaters as standard). Crankcase  
heaters help prevent refrigerant migration to the  
compressor during the off cycle.  
90-DEGREE  
SHORT  
RADIUS  
90-DEGREE  
LONG  
RADIUS  
45-DEGREE  
SHORT  
RADIUS  
TUBE SIZE  
O.D. (in.)  
5
8
4
1.6  
1.8  
1.0  
1.2  
0.8  
0.9  
3
b) Any time the equivalent line length is over 100 ft,  
a liquid line solenoid must be used. A liquid line  
solenoid may also be required for vertical lift ap-  
plications over 25 ft. See Step h) on page 22.  
c) The accessory wind baffle is recommended.  
d) The Effective Capacity Loss table on this page  
provides the estimated percentage of nominal  
cooling capacity losses based on the standard re-  
quired vapor line size versus what is selected for  
long-line applications.  
CHATTLEFF COMMON PISTON SIZES  
PISTON SIZE  
PISTON SIZE  
PISTON SIZE  
32  
33  
35  
36  
37  
38  
39  
40  
41  
42  
43  
45  
47  
49  
51  
52  
53  
55  
57  
59  
61  
62  
63  
65  
67  
68  
70  
71  
73  
74  
76  
78  
80  
81  
82  
84  
86  
88  
89  
90  
92  
93  
96  
98  
101  
104  
Select the desired vapor line size from the Effec-  
tive Capacity Loss table based on equivalent ft  
and desired vapor line size.  
Subtract the nominal percentage loss from the  
unit cooling capacities for the given indoor and  
outdoor combination.  
COOLING ONLY SYSTEM PISTON GUIDE AND REFRIGERANT CHARGES  
INDOOR  
UNIT  
619E  
OUTDOOR  
PISTON REQUIRED  
CHARGE  
(Lb)*  
UNIT  
(Size)  
538  
009  
012  
018  
024  
C
C
A
A
009  
012  
018  
024  
None  
None  
49  
1.5  
1.8  
4.6  
5.3  
57  
NOTES:  
*Charge based on 25 ft of interconnecting tubing. Charge may need to be added  
for longer tubing runs or when used with certain fan coils. Check unit nameplate  
for required charge.  
1. All 018,024 pistons are Chattleff type.  
2. All cooling units have a full factory charge.  
3. Service valves are front-seating type.  
HEAT PUMP SYSTEM PISTON GUIDE AND REFRIGERANT CHARGES  
UNIT  
COOLING  
PISTON  
SIZE  
HEATING  
PISTON  
SIZE  
REQUIRED  
SYSTEM  
CHARGE (Lb)*  
Indoor  
619E  
Outdoor  
538D  
009  
012  
018  
024  
009  
012  
018  
024  
30  
42  
51  
49  
32  
42  
47  
52  
1.5  
2.0  
5.0  
5.1  
*Charge based on 25 ft of interconnecting tubing. Charge may need to be added  
for longer tubing runs or when used with certain fan coils. Check unit nameplate  
for required charge.  
NOTES:  
1. All 009,012 pistons are Aeroquip type. All 018,024 pistons are Chattleff type.  
2. The 538D heat pumps have a holding charge only as shipped from the  
factory.  
EFFECTIVE CAPACITY LOSS  
PERCENT COOLING CAPACITY LOSS  
NOMINAL  
UNIT SIZE*  
STANDARD  
VAPOR LINE (in.)  
LONG-LINE  
VAPOR LINE (in.)†  
50 ft  
75 ft  
100 ft  
125 ft  
150 ft  
175 ft  
200 ft  
5
5
8
8
8
8
8  
4  
8  
4  
1
0
2
0
3
0
5
0
4
1
8
1
5
1
7
2
9
2
10  
3
18,000  
24,000  
5
5
5
3
5
3
10  
2
13  
3
**  
4
**  
5
*Nominal cooling capacity of the unit being specified.  
NOTE: Long-line applications (50 ft and longer) are not permitted on 009, 012  
systems.  
†The vapor line diameter that may be selected for long-line application. If smaller  
vapor lines than are specified in the table are selected, a larger capacity loss will  
occur. If larger vapor lines are selected, refrigerant oil return will be impaired due  
to velocity loss.  
**Not recommended due to excessive loss of capacity.  
21  
APPLICATION DATA (cont)  
e) Changes in piston size — The metering device for a  
long-line application must be adjusted to compen-  
sate for the frictional losses due to the long refriger-  
ant lines, refrigerant lines accessories, and indoor  
coil above or below the outdoor unit. The  
AccuRaterrefrigerant metering device piston may  
need to be changed to provide this adjustment. The  
AccuRater piston should be changed for the indoor  
unit depending upon system configuration and line  
length. Use the Change in Indoor Unit Piston Size El-  
evation table on next page to determine correct  
AccuRater piston size. The standard piston size is  
shown in the System Piston Guide and Refrigerant  
Charges tables on page 21.  
LEGEND  
FCU  
OU  
Fan Coil Unit  
Outdoor Unit  
*009,012 systems.  
†538A,538D018,024 systems.  
Horizontal Configuration  
f) Horizontal configuration — If the total equivalent  
horizontal length is 100 ft or longer, the indoor piston  
must be increased one full piston size, in addition to  
the charge change in Step l), page 23. If exact size is  
not available, use next smaller size per Chattleff  
Common Piston Sizes table.  
g) Elevated configuration — After finding the appropri-  
ate change in piston size, add or subtract the  
change from the original piston size number. If the  
piston size is decreased, round down to the next  
common piston size. If the piston size is increased,  
round the new piston size up to the next common  
piston size.  
*009,012 systems.  
†538A,538D018,024 systems.  
h) Liquid line solenoid and tubing configuration — The  
solenoid has a flow arrow stamped on the valve  
body. When the valve is closed (not energized), the  
pressure is applied in the direction of the flow arrow,  
complete shut off will occur. If pressure is applied  
against the direction of the arrow, leakage through  
the valve will occur. When determining the proper lo-  
cation for a solenoid in a system liquid line, consider  
both flow direction and location of the valve in the  
system. See the diagram below for proper location,  
and install per sections i), j), and k) below.  
i) Horizontal configuration (see figure below) — Install a  
biflow (538D only or standard) liquid line solenoid  
valve within 2 ft of the fan coil with the flow arrow  
pointing toward the indoor unit if equivalent ft of pip-  
ing is 100 ft or more.  
LEGEND  
Fan Coil Unit  
Outdoor Unit  
FCU  
OU  
Liquid Line  
Solenoid Valve  
(if used)  
Lowered Configuration — Indoor Unit  
Installed Below the Outdoor Unit  
Slope the vapor line toward the indoor unit to provide  
for refrigerant migration protection during the off cycle  
due to temperature differences caused by slight el-  
evation changes between indoor and outdoor units.  
NOTE: When installing a liquid line solenoid, a low-  
voltage transformer may be required.  
*009,012 systems.  
†538A,538D018,024 systems.  
CHANGE IN INDOOR UNIT PISTON SIZE  
FOR ELEVATION  
OUTDOOR UNIT ABOVE INDOOR UNIT  
Ft  
Piston Change  
0- 25  
0
-3  
26- 50  
51- 75  
76-100  
101-125  
126-150  
-5  
-7  
LEGEND  
-9  
FCU  
OU  
Fan Coil Unit  
-10  
Outdoor Unit  
INDOOR UNIT ABOVE OUTDOOR UNIT  
Liquid Line  
Ft  
Piston Change  
Solenoid Valve  
(Required over 25 ft)  
0-25  
26-65  
0
+4  
Elevated Configuration — Indoor Unit  
Installed Above the Outdoor Unit  
22  
APPLICATION DATA (cont)  
j) Elevated configuration — Indoor unit installed above  
and thermistor cable assemblies should not touch each  
other, and cable runs may be extended up to 200 ft.  
the outdoor unit (see figure at right):  
• If there is over 25 ft of lift, a biflow (538D only) or  
standard solenoid valve is required in the liquid line.  
• The maximum elevation difference is 65 ft, and the  
maximum equivalent ft of piping is 200.  
• Install an inverted trap in the vapor line. The top of  
the trap must be above the top of the fan coil. This  
prevents the refrigerant from collecting in the vapor  
line.  
14. Wiring  
Use only copper wires from the disconnect to the unit ter-  
minal block. Aluminum and copper-clad aluminum wires are  
not acceptable.  
All duct-free split systems (except the 009,012 outdoor  
units) provide 24-v power for the outdoor unit in the duct-  
free fan coil. The 009,012 outdoor units systems use high-  
voltage controls.  
The 009,012 outdoor units system fan coil units must have  
power wires run from the outdoor condensing unit to the in-  
door unit to prevent out-of-phase wiring.  
k) Lowered configuration — Indoor unit installed below  
the outdoor unit (see figure at right):  
• For lines shorter than 100 ft, no solenoid valve is  
required in the liquid line. For lines over 100 ft, in-  
stall a biflow (538D only) or standard solenoid  
valve in the liquid line.  
15. Air throw  
Refer to Air Throw Data table below for system air throw  
• The maximum elevation difference is 150 ft, and  
the maximum equivalent ft is 200.  
capabilities.  
AIR THROW DATA*  
l) Additional charge — The unit should be charged by  
weighing in the appropriate charge. Add charge  
based on the actual length of line which is over 25 ft  
of liquid line. Add .58 oz of refrigerant per 1 ft in-  
crease over the 25 ft line to the charge listed in Sys-  
tem Piston Guide and Refrigerant Charges table on  
page 21.  
FAN COIL  
SIZE  
HIGH SPEED  
CFM  
APPROXIMATE  
AIR THROW (FT)  
009  
012  
018  
024  
215/252*  
302  
16  
24  
30  
35  
480/455*  
550/525*  
*Cooling only unit/Heat pump unit.  
NOTE: Air throw is with unit mounted with typical clearances in a 10-ft high room.  
NOTE: This only applies to systems where the piston is located  
at the indoor unit (538A018,024 and 538D018,024).  
16. Sound data  
12. Group control  
CONDENSING UNIT SOUND RATINGS  
The 619E fan coil units may be group controlled from a  
single timeclock or energy management system by inter-  
rupting the 24-v power to the control board.  
UNIT SIZE  
009  
SOUND RATING (Decibels)  
FREE FIELD dBA*  
66  
66  
68  
68  
55.7  
55.7  
57.7  
57.7  
012  
13. Thermistors (Heat Pump Systems Only)  
018  
Thermistors are used on both indoor and outdoor units to  
determine operating conditions. Proper thermistor location  
is critical to unit operation. All thermistors have identical re-  
sistance values. See Thermistor Equivalence charts on  
typical system wiring schematics (pages 24-27).  
Thermistor cable assemblies are provided with fan coil  
units to run between indoor and outdoor units. High-voltage  
024  
LEGEND  
Decibels  
dBA  
Sound levels  
Decibels on the A Scale  
*Free field is a rating with no reflective surfaces near the unit. Data sound pressure is  
measured at 3.2 ft (1 m) from the unit. See Sound Power Data Octave Bands table for  
more information.  
SOUND POWER DATA OCTAVE BANDS — A WEIGHTED (Fan Coil Units Only)  
OCTAVE BAND DATA (dBA)  
UNIT  
FAN SPEED  
125  
36.5  
32.8  
31.7  
38.2  
31.7  
29.2  
36.7  
33.6  
33.5  
35.1  
31.7  
29.1  
40.8  
38.0  
37.3  
37.0  
39.8  
43.2  
44.9  
43.7  
40.7  
43.8  
41.4  
38.9  
250  
40.3  
37.9  
36.6  
41.1  
39.8  
38.4  
43.5  
42.5  
41.6  
43.8  
43.3  
42.2  
49.1  
46.7  
44.4  
44.4  
46.9  
49.1  
51.9  
50.5  
47.7  
51.5  
49.5  
47.3  
500  
45.2  
43.6  
41.6  
46.2  
45.0  
43.9  
50.2  
47.1  
43.8  
50.3  
46.3  
42.9  
53.7  
50.6  
47.5  
49.3  
52.2  
54.0  
59.1  
57.2  
55.1  
58.5  
56.5  
54.4  
1000  
48.2  
44.9  
41.6  
47.9  
45.3  
41.9  
51.1  
48.8  
45.6  
51.1  
48.6  
45.6  
55.2  
51.7  
48.6  
50.4  
53.7  
56.0  
59.5  
57.0  
54.7  
58.8  
56.2  
53.7  
2000  
42.3  
39.1  
35.4  
43.0  
42.0  
38.6  
46.5  
43.4  
39.8  
46.4  
42.9  
39.1  
49.1  
44.9  
40.4  
43.4  
47.4  
50.7  
54.8  
51.8  
49.0  
53.5  
50.4  
47.4  
4000  
33.2  
29.8  
27.7  
33.6  
36.8  
28.1  
38.6  
36.2  
33.0  
38.0  
34.2  
30.3  
41.3  
35.8  
32.0  
35.6  
40.1  
44.0  
48.0  
44.4  
40.5  
46.2  
42.5  
39.0  
8000  
31.2  
31.2  
31.2  
31.2  
36.8  
31.2  
31.7  
33.4  
32.7  
31.2  
31.2  
31.2  
32.3  
31.6  
31.6  
31.9  
32.7  
34.0  
36.7  
33.6  
32.2  
36.0  
36.0  
36.0  
High  
Medium  
Low  
619F 009  
Cooling  
Only  
High  
619F 009  
Heat  
Pump  
Medium  
Low  
High  
619F 012  
Cooling  
Only  
Medium  
Low  
High  
619F 012  
Heat  
Pump  
Medium  
Low  
High  
619F 018  
Cooling  
Only  
Medium  
Low  
High  
619F 018  
Heat  
Pump  
Medium  
Low  
High  
619F 024  
Cooling  
Only  
Medium  
Low  
High  
619F 024  
Heat  
Pump  
Medium  
Low  
LEGEND  
NOTES:  
1. Outdoor sound levels are tone corrected values taken in accordance with ARI Sound  
ARI  
dBA  
Air Conditioning & Refrigeration Institute  
Decibels on the A scale  
Standard 270.  
2. Indoor sound levels are tone corrected values taken in accordance with ARI Sound  
Standard 350.  
23  
(See Legend and Notes, page 28.)  
24  
(See Legend and Notes, page 28.)  
25  
(See Legend and Notes, page 28.)  
26  
(See Legend and Notes, page 28.)  
27  
LEGEND AND NOTES FOR TYPICAL WIRING SCHEMATICS  
LEGEND  
AGING  
For Burn-In Test  
(short terminals)  
Assembly  
OFR  
OL  
Outdoor-Fan Relay  
Overload  
Printed Circuit Board  
Start Thermistor  
Return-Air Thermistor  
Resistor Capacitor  
Receiver  
PCB  
PTC  
RA TH  
RC  
AS  
C
Contactor  
CAP  
CH  
Capacitor  
Crankcase Heater  
Compressor Lockout  
Connector  
RCV  
RVS  
SC  
CLO  
CN  
Reversing Valve Solenoid  
Start Capacitor  
Start Relay  
COMP  
CT CLO  
DFB  
DFT  
EMI  
Compressor  
SR  
Current Sensing Loop (Lockout)  
Defrost Board  
STM  
TB  
Step Motor  
Terminal Block  
Thermal Protector  
Transformer  
Defrost Thermostat  
Electromagnetic Interference  
Fan Motor Capacitor  
Fuse  
TP  
TRAN  
FMC  
FU  
GND  
HA  
HPS  
IDC TH  
IDFM  
JEM-A  
Terminal (Marked)  
Ground  
Home Automation  
High-Pressure Switch  
Indoor-Coil Thermistor  
Indoor-Fan Motor  
Japan Electric Manufacturing  
Industry Association  
Relay  
Terminal (Unmarked)  
Splice  
Terminal Block  
K
LLPS  
LPS  
ODA TH  
ODC TH  
OFM  
Factory Wiring  
Liquid Low Pressure Switch  
Low-Pressure Switch  
Outdoor-Air Thermistor  
Outdoor-Coil Thermistor  
Outdoor-Fan Motor  
Field Control Wiring  
Field Power Wiring  
Accessory or Optional Wiring  
NOTES:  
1. If any of the original wire furnished must be replaced, it must be replaced  
with type 90 C wire or its equivalent.  
2. Wire in accordance with National Electrical Code (NEC) and local codes.  
3. The CLO locks out the compressor to prevent short cycling on compressor  
overloads and safety devices. Before replacing CLO, check these other de-  
vices. A minimum 1 amp turn is required to hold contacts closed.  
4. A thermistor wiring cable is provided with the fan coil unit.  
5. Compressor and fan motors are protected by internal thermal overloads.  
6. Transformer has an internal 2 amp thermal fuse on the primary side.  
OPERATING SEQUENCE  
619E CONTROL SYSTEM — The 619E unit is equipped with a  
microprocessor control which operates the system. This control  
is located in the control box of the fan coil unit, with thermistors  
located in the fan coil inlet and on the indoor coil. The 619E heat  
pump fan coil units also have thermistors located on the outdoor  
coil and in the outdoor air inlet. These thermistors monitor sys-  
tem operation and control the operating mode. To change set-  
tings or modes of operation, use the factory-supplied infrared  
wireless remote controller. This controller allows the fan coil unit  
to be operated from within the same room without any wire con-  
nections to the unit.  
system does not start again, the green ‘‘UNIT ON’’ light will flash  
an error code.  
MICROPROCESSOR CONTROL OPERATION — This system  
is controlled by a microprocessor designed to give optimum lev-  
els of comfort and operating efficiency. The control is located in  
the 619E unit. To operate the unit, the factory-supplied remote  
controller is required.  
There are 8 (619E cooling-only systems) or 10 (619E heat  
pump systems) operating modes (including the off mode) for the  
unit. Each mode operates as follows:  
• Off Mode — When the unit is in the off mode, all functions  
(compressor, outdoor fan, indoor fan, and air sweep) are off,  
except the reversing valve (619E heat pump units only),  
which will stay energized if the unit was last operated in the  
cooling mode.  
The remote controller includes a wall-mounted bracket. To in-  
stall the bracket, attach bracket to the wall using factory-  
supplied, double-sided tape. Install factory-supplied batteries  
into the remote controller, and place the controller into the  
bracket so that it will be ready for use.  
• Air Circulation Mode (Fan Operation Only) — When air circu-  
lation mode is selected, the indoor fan will operate continu-  
ously in the selected speed (high, medium, low, or auto.). If  
the auto. mode is selected, the indoor fan will operate at low  
speed. The compressor and outdoor fan are off. The reversing  
valve (619E heat pump units only) will remain in the last  
operating mode.  
OPERATING MODE MEMORY — After the system is turned off  
or after a power failure, the system remains in the last operating  
mode selected. When the system is turned back on, or when  
power is automatically restored, operation continues in the  
same operating mode as when power shut down.  
AUTOMATIC OPERATION (AUTO.) MODE — If auto. mode is  
selected, the system automatically switches the operating mode  
from heating (heat pump system only) to cooling, or from cool-  
ing to heating (heat pump system only) depending on the se-  
lected temperature.  
• Cooling Mode — When the cooling mode is selected, the in-  
door fan will operate continuously at the selected speed if the  
speed is high, medium, or low. If the indoor fan is in auto.  
mode, the fan will change operating speeds depending on the  
difference between the room temperature and the set point.  
The reversing valve (619E heat pump units only) will be on.  
The compressor cannot run for 3 minutes from the time the  
system starts up or for 3 minutes from the time the compres-  
sor last operated. When the temperature of the room is equal  
to or greater than the selected temperature, the compressor  
and outdoor fan will operate until the room temperature is  
2° F below the set point, and then shut off. When the room  
temperature is less than the selected temperature, the com-  
pressor and outdoor fan remain off.  
NOTE: Between the cooling cycle and the heating cycle there is  
a neutral zone of approximately 2° F above and 2° F below the  
selected temperature when only the fan is operating.  
OPERATING FAULT DIAGNOSIS — The system includes an  
automatic diagnosis feature which is activated under difficult or  
unacceptable operating conditions. If such conditions occur, the  
system stops automatically, the operating fault signal appears  
(green ‘‘UNIT ON’’ light on the front of the fan coil unit flashes),  
and an analysis of the system operating conditions is initiated.  
The system will then be restarted automatically, as soon as nor-  
mal conditions have been restored, or it will remain off. If the  
28  
OPERATING SEQUENCE (cont)  
• Maximum Dehumidification Mode — When the dehumidifica-  
change operating speeds depending on the difference be-  
tween the room temperature, the set point, and the coil tem-  
perature. The reversing valve will be off. The compressor  
cannot run for 3 minutes from the time the system starts up or  
for 3 minutes from the time it last operated. When the tem-  
perature of the room is 8° F below the selected temperature,  
the unit will operate in heat pump mode until the temperature  
is 6° F above the selected temperature, or the compressor  
runs for 40 minutes (whichever comes first). If the tempera-  
ture of the room is less than 7° F below or equal to the se-  
lected temperature, the unit operates in heat pump mode until  
the selected set point temperature plus 2° F is reached.  
tion mode is selected, the indoor fan will operate continuously  
at the selected speed if the speed is high, medium, or low. If  
the indoor fan is in auto. mode, the fan will change operating  
speeds depending on the room temperature. If the room tem-  
perature is below the set point, the indoor fan will run at ultra-  
low speed, and the compressor could run for up to 4 minutes.  
(Ultra-low speed is a control-driven speed [not user config-  
urable] used to sample the space when the fan would nor-  
mally be off.) The reversing valve (619E heat pump units only)  
will be on. The compressor cannot run for 3 minutes from the  
time the system starts up or for 3 minutes from the time the  
compressor last operated.  
• Demand Defrost Mode (Heat Pump Systems Only) — This  
unit uses a demand defrost system to remove frost from the  
outdoor coil during heating operation. The indoor and outdoor  
fans are shut off during defrost mode. See Electronic Control  
Defrost Regions map on page 30 for defrost region details.  
Initial Operation — When the mode is first selected, one of the  
following occurs:  
1. If the room temperature is above or equal to the selected  
temperature, the unit will operate for 16 minutes, and the  
compressor and outdoor fan will operate. The indoor fan will  
operate as in the cooling mode. After 16 minutes of operation  
(or when the room reaches 2° F below set point), the unit  
switches to normal dehumidification operation.  
• Sleep Mode — The sleep mode timer will turn the unit off  
when the timer reaches zero minutes. During the first  
112 hours from the time the sleep mode timer starts, the room  
temperature is set back from the selected tempera-  
ture a total of 4° F in cooling and 6° F in heating (538D only).  
2. If the room temperature is below the selected temperature,  
the unit will operate for 8 minutes as follows: the compressor  
and outdoor fan will operate for 3 minutes. The indoor fan will  
operate in low speed, and 30 seconds after the compressor  
stops, the indoor fan stops. The unit remains off for 1 minute,  
and then the indoor fan starts in ultra-low speed for 30 sec-  
onds. The unit then switches to normal dehumidification  
operation.  
• Awake Mode — The awake timer will turn the unit on when the  
timer reaches zero minutes. The unit will start in the same  
mode and at the same selected temperature as when the sys-  
tem shut off.  
• Automatic Operation Mode for Cooling Only Systems — The  
unit samples the air in the room. Based on the room tempera-  
ture, the unit selects one of the following modes:  
Normal Operation — One of the following will take place:  
1. Cooling Mode — If the room temperature is more than  
82.4 F with a preset temperature of 78.8 F.  
1. When the temperature of the room is equal to or greater than  
the selected temperature (by not more than 3° F), the unit  
will operate for 8 minutes as follows: the compressor and  
outdoor fan will operate for 3 minutes. The indoor fan will op-  
erate in low speed, and 30 seconds after the compressor  
stops, the indoor fan stops. The unit remains off for 1 minute,  
and then the indoor fan starts in ultra-low speed for 30 sec-  
onds. The normal dehumidification operation is repeated for  
the newly sensed room temperature.  
2. Dry Mode — If the room temperature is more than 75.2 F  
and less than 82.4 F with a preset temperature of 77 F.  
3. Fan Only Mode — If the room temperature is less than  
75.2 F.  
The preset temperature can be changed by ±4 F using the re-  
mote control.  
• Automatic Operation Mode for Heat Pump Systems (538B) —  
The operation mode will be determined after 20 seconds of  
room monitoring (to determine the room temperature and the  
outdoor air temperature).  
2. If the room temperature is equal to or greater than the se-  
lected temperature, but not by more than between 4° F and  
F, the compressor and outdoor fan operate for 4 minutes.  
The indoor fan will run at ultra-low speed and will stop  
30 seconds after the compressor stops. After 3 minutes, the  
indoor fan runs at ultra-low speed for 30 seconds. The nor-  
mal dehumidification operation is repeated for the newly  
sensed room temperature.  
Test Mode — The test mode can be selected by setting the  
slide switch on the fan coil unit to TEST position. The slide  
switch is located on the front of the unit. The fan coil unit will  
start immediately (there is no compressor time delay when us-  
ing test mode) in cooling mode with an infinitely low set point.  
The indoor fan speed will be at the high setting, and the swing  
louvers will be on (moving up and down).  
3. When the room temperature is equal to or greater than 4° F  
below the selected temperature, the system operates as fol-  
lows: The compressor and outdoor fan operate for 3 min-  
utes. The indoor fan will operate at ultra-low speed and will  
stop 30 seconds after the compressor stops. After 4 or 5 min-  
utes, the indoor fan starts in ultra-low speed for 30 seconds.  
The normal dehumidification operation is repeated for the  
newly sensed room temperature. If the room temperature is  
still 4° F below the selected temperature, the compressor,  
outdoor fan, and indoor fan remain off. After 712 minutes, the  
indoor fan operates at ultra-low speed for 30 seconds. The  
normal dehumidification operation is repeated for the newly  
sensed room temperature.  
NOTE: The unit cannot be controlled by the remote controller  
until the slide switch is returned to the REMOTE position.  
• Emergency Mode — This mode is only to be used if the re-  
mote controller is lost, damaged, or the batteries are dis-  
charged. To initiate emergency mode, manually move the  
slide switch on the fan coil unit to the EMER position. The unit  
is automatically operated in cooling or heating (538D units  
only) mode according to room temperature. Emergency op-  
eration settings are as follows:  
1. Operation mode: AUTO.  
2. Fan Speed: AUTO.  
3. Cooling set point: 77 F  
4. Timer mode: Continuous  
• Heat Pump Heating Mode (Heat Pump Systems Only) —  
When the heat pump mode is selected, the indoor fan will op-  
erate at the selected speed if the speed is high, medium, or  
low, unless overridden by the coil temperature (to prevent  
cold drafts). If the indoor fan is in auto. mode, the fan will  
NOTE: The unit cannot be controlled by the remote controller  
until the slide switch is returned to the REMOTE position.  
29  
*Minimum unit run time starts when outdoor coil temperature drops below 34 F, then accumulates run  
time regardless of coil temperature.  
Electronic Control Defrost Regions Map  
30  
ENGINEER’S SPECIFICATION GUIDE — OUTDOOR UNITS (Models 538A, 538C, 538D, and 538S )  
GENERAL: Furnish and install a Model 538A, 538C, 538D, or  
538S air-to-air outdoor unit in combination with a fan coil unit in  
the location and manner shown on the plan drawings. The unit  
shall be designed and tested for use with Refrigerant R-22 and  
shall be equipped with refrigerant line fittings which permit  
sweat or flare connections.  
Outdoor unit shall contain a fully hermetic compressor with a  
crankcase heater (non-scroll units), oil system, operating oil  
charge, internal motor protection, and spring isolation. Outdoor  
fans shall be direct-drive propeller type, shall discharge air hori-  
zontally, shall be totally enclosed, and shall have permanently  
lubricated sleeve bearings.  
Nominal system electrical characteristics shall be  
single phase, 60 Hz. Each unit shall be capable of satisfactory  
operation within voltage range of v to v.  
MAXIMUM DIMENSIONS: Outdoor unit — width  
depth in., height inches.  
COOLING CAPACITY: Total system cooling capacity shall not  
v,  
CONTROL CIRCUIT: Controls and protective devices shall in-  
clude time-delay restart, automatic restart on power failure,  
3-pole contactors (3 phase units), safety lockout if any safety is  
open, high-pressure and loss-of-pressure switches, automatic  
outdoor-fan motor protection, start capacitor and relay (single-  
phase units without scroll compressors), system diagnostics  
and high condensing temperature protection , compressor mo-  
tor current and temperature overload protection, high pressure  
relief, and outdoor fan failure protection. A 24-v transformer  
shall be factory installed and wired on outdoor units for external  
control circuit (size 018 and 024 only).  
in.,  
be less than  
cfm at  
Btuh with indoor air quantity of  
F wet bulb temperature of air entering  
outdoor unit. Sensible heat capacity shall not be less than  
Btuh with  
sor power input shall be  
F dry bulb temperature. Compres-  
v or less at these conditions.  
APPROVALS: Unit shall be constructed in accordance with  
ASHRAE 15 (latest revision), NEC, and CSA. Unit shall carry  
the UL listing label.  
HEATING CAPACITY (Heat Pump Systems Only): Total heating  
capacity shall be  
when rated at  
Btuh or greater (integrated rating)  
F dry-bulb outdoor ambient with cfm  
FIELD-INSTALLED ACCESSORIES: Low-ambient kit (538A,  
538C, 538D), liquid solenoid valve, wall mount kit, crankcase  
heater (reciprocating-compressor units only) and winter start kit  
(538C, 538S).  
and  
have a minimum HSPF of  
F entering (heating) coil. The equipment must  
. Compressor shall be ca-  
pable of operation in heating duty down to −20 F outdoor am-  
bient air temperature (with accessory low-ambient kit). Unit shall  
be capable of simultaneous heating duty and defrost cycle  
operation.  
OUTDOOR SECTION: The coil shall be constructed of alumi-  
num plate fins mechanically bonded to copper tubing with all  
joints brazed. Coil shall be  
rows deep with a nominal  
fin spacing of  
not less than  
fins per in., and shall have a face area of  
square ft.  
31  
ENGINEER’S SPECIFICATION GUIDE — HIGH WALL FAN COIL UNITS (Model 619E)  
GENERAL: Furnish and install indoor, wall-mounted, draw-thru,  
COIL SECTION: Coil shall be copper tube with aluminum fins  
and galvanized steel tube sheets. Fins shall be bonded to the  
tubes by mechanical expansion. A drip pan under the coil shall  
have a drain connection for hose attachment to remove conden-  
sate. Condensate pan shall have internal trap and auxiliary drip  
pan under coil header.  
direct expansion, indoor cooling only or heat pump fan coil unit  
to be used without ductwork. Unit shall consist of tangential,  
direct-drive fan, fan motor, cooling coil, piping connectors, elec-  
trical controls, microprocessor control system, and integral tem-  
perature sensing. Unit shall be capable of being used in a  
refrigerant circuit with a matching air-cooled outdoor condens-  
ing unit.  
NOTE: The 009 and 012 units use capillary tubes in the OUT-  
DOOR unit for refrigerant control, and the 018,024 units use the  
accessory AccuRaterpiston refrigerant metering device in the  
INDOOR unit except systems using 538S outdoor units. These  
systems have a thermostatic expansion valve in the outdoor  
unit.  
Nominal unit electrical characteristics shall be  
phase, 60 Hz. The unit shall be capable of satisfactory operation  
within voltage limits of v to v.  
v, single  
Unit shall be capable of providing a constant volume of air at a  
specified external static pressure within the unit nominal oper-  
ating range.  
CONTROLS: Controls shall consist of a microprocessor-based  
control system which shall provide the following functions as a  
minimum: automatic restart, a timer function, temperature-  
sensing controls, evaporator coil freeze protection, wireless in-  
frared remote control, auto. stop features, automatic airsweep  
control, dehumidification mode, fan-only operation, diagnostics,  
a 25-ft indoor-to-outdoor thermistor connection cable, user-  
selectable fan speed control, compressor restart time delay, and  
condenser high-temperature protection.  
MAXIMUM DIMENSIONS: Indoor unit — width  
depth in., height inches.  
in.,  
CABINET: Cabinet discharge and inlet grilles shall be attrac-  
tively styled, high-impact polystyrene. Cabinet shall be fully in-  
sulated for improved thermal and acoustic performance.  
FAN SECTION: Fan shall be tangential direct-drive blower type  
with air intake at the upper front face of the unit and discharge  
at the bottom front. Automatic, motor-driven horizontal air  
sweep shall be provided standard.  
ACCESSORIES: Condensate pump.  
Air sweep operation shall be user selectable. Vertical direction  
may be manually adjusted and horizontal air sweep may be  
manually set.  
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE  
Bryant  
Day & Night  
Payne  
UNIT MUST BE INSTALLED IN ACCORDANCE  
WITH INSTALLATION INSTRUCTIONS  
Air Conditioning  
Copyright 1996 Carrier Corporation  
Printed in U.S.A.  
6/96  
CATALOG NO. BDP-3261-900  

Adesso Barcode Reader 3000 User Manual
Brother DCP 8045D User Manual
Bryant Air Handling Units 524J User Manual
Bryant LEGACY 569J User Manual
Epson Printer LQ 590 User Manual
GE General Electric Air Conditioner ABV10 User Manual
GE Zoneline 3900 User Manual
Haier Air Conditioner AC18CS1ERA User Manual
Haier Air Conditioner HW 24LMA13T3 User Manual
Honda Automobiles GXV50 User Manual