Bryant DURAPAC 559F User Manual

installation, start-up  
559F  
Sizes 180-300  
15 to 25 Tons  
and service instructions  
SINGLE PACKAGE ROOFTOP  
ELECTRIC HEATING/ELECTRIC COOLING UNITS  
Cancels: II 559F-180-3  
II 559F-180-4  
10/15/98  
CONTENTS  
INSTALLATION  
I. STEP 1 — PROVIDE UNIT SUPPORT  
A. Roof Curb  
Page  
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . 1  
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-15  
I. Step 1 — Provide Unit Support . . . . . . . . . . . . . . . 1  
II. Step 2 — Rig and Place Unit . . . . . . . . . . . . . . . . . 1  
III. Step 3 — Field Fabricate Ductwork . . . . . . . . . . . . 7  
IV. Step 4 — Make Unit Duct Connections . . . . . . . . . 7  
V. Step 5 — Trap Condensate Drain . . . . . . . . . . . . . . 7  
VI. Step 6 — Make Electrical Connections . . . . . . . . . 8  
VII. Step 7 — Make Outdoor-Air Inlet  
Assemble and install accessory roof curb or horizontal adapter  
roof curb in accordance with instructions shipped with the  
curb or horizontal adapter. Accessory roof curb and horizon-  
tal adapter roof curb and information required to field fabri-  
cate a roof curb or horizontal adapter roof curb are shown in  
Fig. 1 and 2. Install insulation, cant strips, roofing, and counter  
flashing as shown. Ductwork can be secured to roof curb be-  
fore unit is set in place.  
Adjustments . . . . . . . . . . . . . . . . . . . . . . 11  
VIII. Step 8 — Install Outdoor-Air Hood . . . . . . . . . . . 12  
IX. Step 9 — Install All Accessories . . . . . . . . . . . . . 13  
IMPORTANT: The gasketing of the unit to the roof curb or  
adapter roof curb is critical for a leak-proof seal. Install gas-  
ket supplied with the roof curb or adapter roof curb as shown  
in Fig. 1. Improperly applied gasket can result in air leaks  
and poor unit performance.  
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-20  
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20-24  
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25  
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . CL-1  
Curb or adapter roof curb should be level. This is necessary  
to permit unit drain to function properly. Unit leveling toler-  
1
ance is Ϯ 16 in. per linear ft in any direction. Refer to Ac-  
cessory Roof Curb or Horizontal Adapter Roof Curb Installa-  
tion Instructions for additional information as required.  
B. Alternate Unit Support  
SAFETY CONSIDERATIONS  
When the curb or adapter cannot be used, support unit with  
sleepers using unit curb or adapter support area. If sleepers  
cannot be used, support long sides of unit with a minimum of  
3 equally spaced 4-in. x 4-in. pads on each side.  
Installation and servicing of air-conditioning equipment can  
be hazardous due to system pressure and electrical compo-  
nents. Only trained and qualified service personnel should  
install, repair, or service air-conditioning equipment.  
Untrained personnel can perform basic maintenance func-  
tions of cleaning coils and filters and replacing filters. All other  
operations should be performed by trained service personnel.  
When working on air-conditioning equipment, observe pre-  
cautions in the literature, tags and labels attached to the unit,  
and other safety precautions that may apply.  
II. STEP 2 — RIG AND PLACE UNIT  
Inspect unit for transportation damage. File any claim with  
transportation agency. Keep unit upright, and do not drop.  
Use spreader bars over unit to prevent sling or cable dam-  
age. Rollers may be used to move unit across a roof. Level by  
using unit frame as  
Ϯ 16 in. per linear ft in any direction. See Fig. 3 for addi-  
a
reference; leveling tolerance is  
1
Follow all safety codes. Wear safety glasses and work gloves.  
Use quenching cloth for unbrazing operations. Have fire ex-  
tinguishers available for all brazing operations.  
tional information. Unit weight is shown in Table 1.  
Four lifting holes are provided in ends of unit base rails as  
shown in Fig. 3. Refer to rigging instructions on unit.  
WARNING: Before performing service or mainte-  
nance operations on unit, turn off main power switch  
to unit. Electrical shock could cause personal injury.  
A. Positioning  
Provide clearance around and above unit for airflow, safety,  
and service access (Fig. 4 and 5).  
Do not install unit in an indoor location. Do not locate air in-  
lets near exhaust vents or other sources of contam-  
inated air.  
IMPORTANT: Units have high ambient operating limits. If  
limits are exceeded, the units will automatically lock the com-  
pressor out of operation. Manual reset will be required to re-  
start the compressor.  
Although unit is weatherproof, guard against water from higher  
level runoff and overhangs.  
B. Roof Mount  
Check building codes for weight distribution requirements.  
NOTES:  
PKG.  
CURB  
1. Roof curb accessory is shipped disassembled.  
DESCRIPTION  
NO. REF.  
HEIGHT  
1
2. Insulated panels:  
3. Dimensions in ( ) are in millimeters.  
2Љ thick neoprene coated 2 lb density.  
1Ј-2Љ  
Standard Curb  
3
3
3
Fig. 1 — Roof Curb Details  
STD UNIT  
WEIGHT  
ECONOMIZER  
WEIGHT  
CORNER  
A
CORNER  
B
CORNER  
C
CORNER  
D
DIM A  
DIM B  
DIM C  
UNIT  
Lb  
Kg  
Lb  
110  
110  
Kg  
50  
50  
Lb  
391 177 365 166 384 174 410 186 3-5 1041 3-6 1067 1-10 559  
399 181 384 174 402 182 439 199 3-4 1016 3-6 1067 1- 508  
Kg  
Lb  
Kg  
Lb  
Kg  
Lb  
Kg ft-in. mm ft-in. mm ft-in. mm  
559F180  
559F216  
1550  
1650  
703  
748  
8
NOTES:  
1. Refer to print for roof curb accessory dimensions.  
2. Dimensions in ( ) are in millimeters.  
3.  
Center of Gravity.  
4.  
Direction of airflow.  
5. Ductwork to be attached to accessory roof curb only.  
6. Minimum clearance:  
Rear: 7Ј-0Љ (2134) for coil removal. This dimension can be reduced to 4Ј-0Љ (1219)  
if conditions permit coil removal from the top.  
Left side: 4Ј-0Љ (1219) for proper condenser coil airflow.  
Front: 4Ј-0Љ (1219) for control box access.  
Right side: 4Ј-0Љ (1219) for proper operation of damper and power exhaust if so  
equipped.  
Top: 6Ј-0Љ (1829) to assure proper condenser fan operation.  
Local codes or jurisdiction may prevail.  
7. With the exception of clearance for the condenser coil and the damper/power ex-  
haust as stated in Note #6,  
clearance.  
a
removable fence or barricade requires no  
POWER EXHAUST/  
BAROMETRIC RELIEF  
(ACCESSORY ONLY)  
8. Dimensions are from outside of corner post. Allow 0Ј-516Љ (8) on each side for top  
cover drip edge.  
Fig. 4 — Base Unit Dimensions, 559F180 and 216  
STD UNIT ECONOMIZER CORNER CORNER CORNER CORNER  
WEIGHT WEIGHT  
DIM A  
DIM B  
DIM C  
A
B
C
D
UNIT  
Lb Kg  
Lb  
Kg  
50  
50  
Lb Kg Lb Kg Lb Kg Lb Kg ft-in. mm ft-in. mm ft-in. mm  
559F240 1700 771  
559F300 1850 839  
110  
110  
419 190 394 179 425 193 463 210 3-4 1016 3-5 1041 1-8 508  
428 194 412 187 511 232 499 226 3-2  
965  
3-7 1092 1-8 508  
NOTES:  
1. Refer to print for roof curb accessory dimensions.  
2. Dimensions in ( ) are in millimeters.  
3.  
Center of Gravity.  
4.  
Direction of airflow.  
5. Ductwork to be attached to accessory roof curb only.  
6. Minimum clearance:  
Rear: 7Ј-0Љ (2134) for coil removal. This dimension can be reduced to 4Ј-0Љ (1219)  
if conditions permit coil removal from the top.  
Left side: 4Ј-0Љ (1219) for proper condenser coil airflow.  
Front: 4Ј-0Љ (1219) for control box access.  
Right side: 4Ј-0Љ (1219) for proper operation of damper and power exhaust if so  
equipped.  
Top: 6Ј-0Љ (1829) to assure proper condenser fan operation.  
Local codes or jurisdiction may prevail.  
7. With the exception of clearance for the condenser coil and the damper/power ex-  
haust as stated in Note #6,  
clearance.  
a
removable fence or barricade requires no  
POWER EXHAUST/  
BAROMETRIC RELIEF  
(ACCESSORY ONLY)  
8. Dimensions are from outside of corner post. Allow 0Ј-516Љ (8) on each side for top  
cover drip edge.  
Fig. 5 — Base Unit Dimensions, 559F240 and 300  
Table 1 — Physical Data  
UNIT 559F  
180  
15  
216  
18  
240  
20  
300  
25  
NOMINAL CAPACITY (tons)  
OPERATING WEIGHT  
COMPRESSOR  
1550  
1650  
1700  
1850  
Scroll, Copeland  
Quantity ... Model (Ckt 1 , Ckt 2)  
1...ZR108KC,  
1...ZR94KC  
2
1...ZR125KC,  
1...ZR108KC  
2
1...ZR16M3,  
1...ZR125KC  
2
2...ZR94KC  
Number of Refrigerant Circuits  
Oil (oz) (Ckt 1 , Ckt 2)  
2
81, 81  
106,81  
106, 106  
136, 106  
REFRIGERANT TYPE  
Expansion Device  
Operating Charge (lb-oz)  
Circuit 1 *  
R-22  
TXV  
10-10  
10-10  
15-5  
12-3  
3
16-0  
13-6  
20-13  
13- 0  
Circuit 2  
CONDENSER COIL  
Cross-Hatched  
8-in. Copper Tubes, Aluminum Lanced,  
Aluminum Pre-Coated, or Copper Plate Fins  
Rows...Fins/in.  
Total Face Area (sq ft)  
2...17  
21.7  
3...15  
21.7  
3...15  
21.7  
4...15  
21.7  
CONDENSER FAN  
Nominal Cfm  
Propeller Type  
10,500  
10,500  
3...22  
2...1050  
1100  
3
14,200  
2...30  
14,200  
2...30  
Quantity...Diameter (in.)  
Motor Hp...Rpm  
3...22  
1
1
2...1050  
1100  
1...1075  
3400  
1...1075  
3400  
Watts Input (Total)  
EVAPORATOR COIL  
Cross-Hatched ⁄8-in. Copper Tubes, Aluminum Lanced or  
Copper Plate Fins, Face Split  
Rows...Fins/in.  
Total Face Area (sq ft)  
2...17  
17.5  
3...15  
17.5  
3...15  
17.5  
4...15  
17.5  
EVAPORATOR FAN  
Quantity...Size (in.)  
Type Drive  
Centrifugal Type  
2...10 x 10  
Belt  
2...12 x 12  
Belt  
2...12 x 12  
Belt  
2...12 x 12  
Belt  
Nominal Cfm  
6000  
7200  
5
8000  
10,000  
10  
Motor Hp  
Motor Nominal Rpm  
Maximum Continuous Bhp  
3.7  
1725  
7.5  
1745  
1745  
1740  
8.7 [208/230 v]  
9.5 [460 v]  
213T  
10.2 [208/230 v]  
11.8 [460 v]  
215T  
4.25  
5.90  
Motor Frame Size  
Nominal Rpm High/Low  
Fan Rpm Range  
56H  
184T  
Low-Medium Static  
High Static  
891-1179  
1227-1550  
Ball  
910-1095  
1069-1287  
Ball  
1002-1225  
1193-1458  
Ball  
1066-1283  
1332-1550  
Ball  
Motor Bearing Type  
Maximum Allowable Rpm  
Motor Pulley Pitch Diameter  
Min/Max (in.)  
1550  
1550  
1550  
1550  
Low-Medium Static  
High Static  
3.1/4.1  
4.9/5.9  
4.9/5.9  
118  
5.4/6.6  
5.4/6.6  
138  
4.9/5.9  
4.9/5.9  
138  
3.7/4.7  
7
Nominal Motor Shaft Diameter (in.)  
Fan Pulley Pitch Diameter (in.)  
8  
Low-Medium Static  
High Static  
6.0  
5.2  
9.4  
9.4  
8.0  
8.0  
7.9  
6.4  
Nominal Fan Shaft Diameter (in.)  
Belt, Quantity...Type...Length (in.)  
1316  
1716  
1716  
1716  
Low-Medium Static  
High Static  
1...BX...42  
1...BX...42  
13.5-15.5  
48  
1...BX...50  
1...BX...48  
13.3-14.8  
37  
1...BX...53  
1...BX...50  
14.6-15.4  
37  
2...BX...50  
2...BX...47  
14.6-15.4  
36  
Pulley Center Line Distance (in.)  
Speed Change per Full Turn of  
Movable Pulley Flange (rpm)  
Movable Pulley Maximum Full Turns  
From Closed Position  
Factory Speed  
Factory Speed Setting (rpm)  
Low-Medium Static  
High Static  
55  
34  
44  
45  
5
5
5
5
3.5  
3.5  
3.5  
3.5  
Low-Medium Static  
High Static  
1035  
1389  
1316  
1002  
1178  
1716  
1120  
1328  
1716  
1182  
1470  
1716  
Fan Shaft Diameter at Pulley (in.)  
HIGH-PRESSURE SWITCH (psig)  
Cutout  
Reset (Auto)  
426  
320  
LOW-PRESSURE SWITCH (psig)  
Cutout  
Reset (Auto)  
27  
44  
FREEZE PROTECTION THERMOSTAT (F)  
Opens  
Closes  
30 ± 5  
45 ± 5  
OUTDOOR-AIR INLET SCREENS  
Quantity...Size (in.)  
Cleanable  
2...20 x 25 x 1  
1...20 x 20 x 1  
RETURN-AIR FILTERS  
Quantity...Size (in.)  
Throwaway**  
4...20 x 20 x 2  
4...16 x 20 x 2  
1
POWER EXHAUST  
LEGEND  
2
Hp, 208/230-460 v Motor Direct Drive, Propeller-Fan (Factory-Wired for 460 v)  
Bhp  
TXV  
Brake Horsepower  
Thermostatic Expansion Valve  
*Circuit 1 uses the lower portion of the condenser coil and lower portion of the evaporator coils; and  
Circuit 2 uses the upper portion of both coils.  
†The 559F300 unit requires 2-in. industrial-grade filters capable of handling face velocities up to 625 ft/min  
(such as American Air Filter no. 5700 or equivalent).  
NOTE: The 559F units have a low-pressure switch (standard) located on the suction side.  
—6—  
III. STEP 3 — FIELD FABRICATE DUCTWORK  
IV. STEP 4 — MAKE UNIT DUCT CONNECTIONS  
Secure all ducts to building structure. Use flexible duct con-  
nectors between unit and ducts as required. Insulate and weath-  
erproof all external ductwork, joints, and roof openings with  
counter flashing and mastic in accordance with applicable codes.  
Unit is shipped for thru-the-bottom duct connections. Duct-  
work openings are shown in Fig. 6. Field-fabricated concen-  
tric ductwork may be connected as shown in Fig. 7 and 8.  
Attach all ductwork to roof curb and roof curb basepans. Re-  
fer to installation instructions shipped with accessory roof curb  
for more information.  
Ducts passing through an unconditioned space must be in-  
sulated and covered with a vapor barrier.  
The 559F units with electric heat require a 1-in. clearance  
for the first 24 in. of ductwork.  
V. STEP 5 — TRAP CONDENSATE DRAIN  
See Fig. 4, 5, and 9 for drain location. Plug is provided in  
drain hole and must be removed when unit is operating. One  
Outlet grilles must not lie directly below unit discharge.  
3
4-in. half coupling is provided inside unit evaporator section  
NOTE: A 90-degree elbow must be provided in the ductwork  
to comply with UL (Underwriters’ Laboratories) codes for use  
with electric heat.  
for condensate drain connection. An 812 in. x 4-in. diameter  
nipple and a 2-in. x 34-in. diameter pipe nipple are coupled to  
standard  
3
3
4-in. diameter elbows to provide a straight path  
WARNING: For vertical supply and return units, tools  
or parts could drop into ductwork and cause an injury.  
Install a 90 degree turn in the return ductwork be-  
tween the unit and the conditioned space. If a 90 de-  
gree elbow cannot be installed, then a grille of sufficient  
strength and density should be installed to prevent ob-  
jects from falling into the conditioned space. Due to elec-  
tric heater, supply duct will require 90 degree elbow.  
down through holes in unit base rails (see Fig. 10). A trap at  
least 4-in. deep must be used.  
Shaded area indicates block-off panels.  
NOTE: Dimension A, AЈ and B, BЈ are obtained from field-supplied ceil-  
ing diffuser.  
Fig. 8 — Concentric Duct Details  
NOTE: Do not drill in this area, as damage to basepan may result in  
water leak.  
Fig. 6 — Air Distribution — Thru-the-Bottom  
(559F216-300 Shown)  
3/4" FPT DRAIN  
CONNECTION  
1-3/8"  
DRAIN HOLES  
Fig. 9 — Condensate Drain Details  
(559F180,216 Shown)  
NOTE: Do not drill in this area, as damage to basepan may result in  
water leak.  
Fig. 7 — Concentric Duct Air Distribution  
(559F216-300 Shown)  
—7—  
This amount of phase imbalance is satisfactory as it is below  
the maximum allowable 2%.  
IMPORTANT: If the supply voltage phase imbalance is  
more than 2%, contact your local electric utility company  
immediately.  
Unit failure as a result of operation on improper line voltage  
or excessive phase imbalance constitutes abuse and may cause  
damage to electrical components.  
B. Field Control Wiring  
Install a Bryant-approved accessory thermostat assembly ac-  
cording to the installation instructions included with the ac-  
cessory. Locate thermostat assembly on a solid wall in the  
conditioned space to sense average temperature.  
Fig. 10 — Condensate Drain Piping Details  
VI. STEP 5 — MAKE ELECTRICAL CONNECTIONS  
Route thermostat cable or equivalent single leads of  
no. 18 AWG (American Wire Gage) colored wire from subbase  
terminals through conduit in unit to low-voltage connections  
as shown on unit label wiring diagram and in Fig. 12.  
A. Field Power Supply  
Unit is factory wired for voltage shown on nameplate.  
When installing units, provide a disconnect, per NEC (Na-  
tional Electrical Code) requirements, of adequate size  
(Table 2).  
NOTE: For wire runs up to 50 ft, use no. 18 AWG insulated  
wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insu-  
lated wire (35 C minimum). For over 75 ft, use no. 14 AWG  
insulated wire (35  
no. 18 AWG cannot be directly connected to the thermostat  
and will require a junction box and splice at the thermostat.  
C
minimum). All wire larger than  
All field wiring must comply with NEC and local  
requirements.  
Route power lines through control box access panel or unit  
basepan (Fig. 4 and 5) to connections as shown on unit wir-  
ing diagram and Fig. 11.  
Set heat anticipator settings as indicated in Table 3. Settings  
may be changed slightly to provide a greater degree of com-  
fort for a particular installation.  
Operating voltage to compressor must be within voltage range  
indicated on unit nameplate. On 3-phase units, voltages be-  
tween phases must be balanced within 2% and the current  
must be balanced within 10%.  
Refer to accessory remote control instructions as  
required.  
CAUTION: The correct power phasing is critical in  
the operation of the scroll compressors. An incorrect phas-  
ing will cause the compressor to rotate in the wrong di-  
rection. This may lead to premature compressor failure.  
Use the following formula to determine the percentage of volt-  
age imbalance.  
Percentage of Voltage Imbalance  
max voltage deviation from average voltage  
= 100 x  
average voltage  
EXAMPLE: Supply voltage is 460-3-60.  
TB1 MAXIMUM WIRE SIZE  
AB = 452 v  
BC = 464 v  
AC = 455 v  
VOLTAGE  
UNIT  
559F  
208/230  
460  
All  
350 kcmil  
2/0  
452 + 464 + 455  
Average Voltage =  
3
LEGEND  
1371  
EQUIP  
Equipment  
Ground  
NEC  
National Electrical  
Code  
Terminal Block  
=
3
GND  
kcmil  
Thousand Circular  
Mils  
TB  
=
457  
Determine maximum deviation from average voltage:  
Fig. 11 — Field Power Wiring Connections  
(AB) 457 − 452 = 5 v  
(BC) 464 − 457 = 7 v  
(AC) 457 − 455 = 2 v  
Maximum deviation is 7 v.  
Determine the percentage of voltage imbalance:  
7
Percentage of Voltage Imbalance = 100 x  
457  
= 1.53%  
UNIT LOW-VOLTAGE CONNECTIONS  
Fig. 12 — Field Control Thermostat Wiring  
—8—  
Table 2 — Electrical Data  
OFM  
COMPRESSOR  
No. 1 No. 2  
VOLTAGE  
RANGE  
POWER  
ELECTRIC  
HEAT*  
POWER  
SUPPLY  
NOMINAL  
VOLTAGE  
IFM  
FLA  
UNIT  
559F  
EXHAUST  
(3 Ph, 60 Hz)  
Min Max RLA LRA RLA LRA Qty Hp FLA (ea) Hp  
FLA LRA kW  
FLA  
MCA  
81/81 100/100  
85/86 110/110  
102/116 110/125  
4.6 18.8 26/34 71/82 108/122 110/125  
42/56 117/135 159/149 175/175  
4.6 18.8 42/56 117/135 165/155 175/175  
56/75 156/180 169/194 200/225  
4.6 18.8 56/75 156/180 175/200 200/225  
MOCP†  
4.6 18.8  
26/34 71/82  
208/230  
187 253 28.8 195 28.8 195  
3
3
3
3
2
2
0.5  
0.5  
0.5  
0.5  
1
1.7  
0.8  
1.7  
0.8  
6.6  
3.3  
3.7 10.5/11.0  
180  
(15 Tons)  
2.3  
6.0  
40  
43  
50  
50  
2.3  
6.0  
32  
32  
39  
39  
55  
58  
60  
60  
460  
414 508 14.7  
95 14.7  
95  
3.7  
4.8  
2.3  
6.0  
55  
55  
66  
66  
72  
75  
80  
80  
2.3  
6.0  
80  
80  
96  
96  
102  
105  
110  
110  
87/87  
92/92  
110/110  
110/110  
4.6 18.8  
26/34 71/82 109/122 110/125  
4.6 18.8 26/34 71/82 114/128 125/150  
208/230  
187 253 30.1 225 28.8 195  
5.0 15.8/15.8  
42/56 117/135 166/155 175/175  
4.8 18.8 42/56 117/135 172/161 175/175  
56/75 156/180 176/200 200/225  
4.6 18.8 56/75 156/180 182/206 200/225  
216  
(18 Tons)  
2.3  
6.0  
44  
47  
50  
60  
2.3  
6.0  
32  
32  
39  
39  
59  
61  
60  
70  
460  
414 508 15.5 114 14.7  
95  
5.0  
7.9  
2.3  
6.0  
55  
55  
66  
66  
76  
79  
90  
90  
2.3  
6.0  
80  
80  
96  
96  
106  
109  
125  
125  
116/116 150/150  
120/120 150/150  
4.6 18.8  
26/34 71/82 120/134 150/150  
4.6 18.8 26/34 71/82 126/140 150/150  
208/230  
187 253 37.8 239 30.1 225  
7.5 25.0/25.0  
42/56 117/135 178/166 200/175  
4.6 18.8 42/56 117/135 183/172 200/175  
56/75 156/180 187/211 200/225  
4.6 18.8 56/75 156/180 193/217 200/225  
240  
(20 Tons)  
2.3  
6.0  
57  
59  
70  
70  
2.3  
6.0  
32  
32  
39  
39  
65  
68  
70  
70  
460  
414 508 17.2 125 15.5 114  
1
7.5  
13.0  
2.3  
6.0  
55  
55  
66  
66  
82  
85  
90  
90  
2.3  
6.0  
80  
80  
96  
96  
112  
115  
125  
125  
—9—  
Table 2 — Electrical Data (cont)  
COMPRESSOR  
No. 1 No. 2  
VOLTAGE  
RANGE  
POWER  
ELECTRIC  
HEAT*  
POWER  
SUPPLY  
NOMINAL  
VOLTAGE  
(3 Ph, 60 Hz)  
OFM  
IFM  
FLA  
UNIT  
559F  
EXHAUST  
Min Max RLA LRA RLA LRA Qty Hp FLA (ea) Hp  
FLA LRA kW  
FLA  
MCA  
MOCP†  
130/130 150/150  
135/135 175/175  
4.6 18.8  
26/34 71/82 130/138 150/150  
4.6 18.8 26/34 71/82 135/143 175/175  
208/230  
187 253 41.0 350 37.8 239  
2
2
1
1
6.6  
2.8  
10.0 28.0/28.0  
42/56 117/135 181/170 200/175  
4.6 18.8 42/56 117/135 187/176 200/200  
56/75 156/180 191/215 200/225  
4.6 18.8 56/75 156/180 197/221 200/225  
300  
(25 Tons)  
2.3  
6.0  
66  
68  
80  
80  
2.3  
6.0  
32  
32  
39  
39  
67  
70  
80  
80  
460  
414 508 21.8 158 17.2 125  
10.0  
14.6  
2.3  
6.0  
55  
55  
66  
66  
84  
87  
90  
100  
2.3  
6.0  
80  
80  
96  
96  
114  
117  
125  
125  
EXAMPLE: Supply voltage is 460-3-60.  
LEGEND  
Full Load Amps  
FLA  
AB = 452 v  
BC = 464 v  
AC = 455 v  
HACR  
IFM  
Heating, Air Conditioning and Refrigeration  
Indoor (Evaporator) Fan Motor  
Locked Rotor Amps  
LRA  
452 + 464 + 455  
Average Voltage =  
MCA  
MOCP  
NEC  
OFM  
RLA  
Minimum Circuit Amps  
3
Maximum Overcurrent Protection  
National Electrical Code  
1371  
=
=
Outdoor (Condenser) Fan Motor  
Rated Load Amps  
3
457  
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v,  
and 480 v. Heaters are rated at 240 v and 480 v. If power distribution  
voltage to unit varies from rated heater voltage, heater kW will vary  
accordingly.  
Determine maximum deviation from average voltage.  
(AB) 457 − 452 = 5 v  
(BC) 464 − 457 = 7 v  
(AC) 457 − 455 = 2 v  
†Fuse or HACR circuit breaker.  
Maximum deviation is 7 v.  
NOTES:  
Determine percent of voltage imbalance.  
1. In compliance with NEC requirements for multimotor and combination load  
equipment (refer to NEC Articles 430 and 440), the overcurrent protective  
device for the unit shall be fuse or HACR breaker. The Canadian units  
may be fuse or circuit breaker.  
7
% Voltage Imbalance = 100 x  
457  
= 1.53%  
2. Unbalanced 3-Phase Supply Voltage  
Never operate a motor where a phase imbalance in supply voltage is greater  
than 2%. Use the following formula to determine the percent of voltage  
imbalance.  
This amount of phase imbalance is satisfactory as it is below the maxi-  
mum allowable 2%.  
IMPORTANTIf the supply voltage phase imbalance is more than 2%, contact  
your local electric utility company immediately.  
% Voltage Imbalance =  
max voltage deviation from average voltage  
3. MCA calculation for units with electric heaters over 50 kW  
= (1.25 x IFM amps) + (1.00 x heater FLA).  
100 x  
average voltage  
—10—  
VII. STEP 7 — MAKE OUTDOOR-AIR INLET ADJUSTMENTS  
A. Manual Outdoor-Air Damper  
Table 3 — Heat Anticipator Settings  
UNIT  
UNIT  
559F  
kW*  
STAGE 1  
STAGE 2  
VOLTAGES  
All units (except those equipped with a factory-installed econo-  
mizer) have a manual outdoor-air damper to provide venti-  
lation air. Damper can be preset to admit up to 25% outdoor  
air into return-air compartment. To adjust, loosen securing  
screws and move damper to desired setting. Then retighten  
screws to secure damper (Fig. 13).  
26/34  
42/56  
56/75  
.40  
.66  
.66  
.66  
.40  
.66  
208/230-3-60  
180-300  
32  
55  
80  
.40  
.40  
.66  
.40  
.66  
.66  
460-3-60  
*Heater kW is based on heater voltage of 208 v, 240 v and 480 v.  
B. Optional Economizer  
Economizer Motor Control Module (Fig. 14-16)  
Set to the D setting (Fig. 15). The control module is located  
on the economizer motor. See Fig. 14 and 16.  
Damper Vent Position Setting  
1. Set fan switch at ON position (continuous fan opera-  
tion) and close night switch if used.  
2. Set system selector switch to OFF position.  
3. Turn adjustment screw slowly until dampers assume de-  
sired vent position. Do not manually operate economizer  
motor since damage to motor will result.  
LEGEND  
LED  
Light-Emitting Diode  
Fig. 15 — Economizer Control Module  
(Part Number W7459A)  
Fig. 13 — 25% Outdoor-air Section Details  
Fig. 16 — Economizer Control Module Location  
Fig. 14 — Economizer Damper Assembly  
— End View  
—11—  
VIII. STEP 8 — INSTALL OUTDOOR-AIR HOOD  
BAFFLE (300 ONLY)  
The same type of factory-installed hood is used on units with  
25% air ventilation and units with an economizer.  
NOTE: The hood top panel, upper and lower filter retainers,  
hood drain pan, baffle (size 300), and filter support bracket  
are secured opposite the condenser end of the unit. The screens,  
hood side panels, remaining section of filter support bracket,  
seal strip, and all other hardware are in a package located  
inside the return-air filter access panel (Fig. 17).  
LOWER FILTER  
RETAINER  
FILTER SUPPORT  
BRACKET  
1. Attach seal strip to upper filter retainer. See Fig. 18.  
2. Assemble hood top panel and side panels, upper filter  
retainer, and hood drain pan (Fig. 19).  
3. Secure lower filter retainer and long section of filter sup-  
port bracket to unit. See Fig. 19. Leave screws loose on  
size 300 units.  
HOOD SIDE  
PANELS (2)  
4. Slide baffle (size 300) unit behind lower filter retainer  
and tighten screws.  
HOOD TOP  
PANEL  
BAFFLE  
(300  
ONLY)  
5. Loosen sheet metal screws for base unit top panel lo-  
cated above outdoor-air inlet opening, and remove screws  
for hood side panels located on the sides of the outdoor-  
air inlet opening.  
6. Match notches in hood top panel to unit top panel screws.  
Insert hood flange between unit top panel flange and unit.  
Tighten screws.  
LOWER  
FILTER  
RETAINER  
FILTER SUPPORT  
BRACKET  
7. Hold hood side panel flanges flat against unit, and in-  
stall screws removed in Step 5.  
8. Insert outdoor-air inlet screens and spacer in channel  
created by lower filter retainer and filter support bracket.  
HOOD DRAIN PAN  
UPPER FILTER RETAINER  
9. Attach remaining short section of filter support bracket.  
NOTE: The outdoor-air hood comes with a baffle which is used on  
size 300 units only; discard baffle for 180-240 units.  
Fig. 19 — Outdoor-Air Hood Details  
A. Enthalpy Control Installation  
NOTE: The accessory outdoor-air enthalpy sensor must be  
installed BEFORE the economizer hoods are installed on the  
unit or hoods will have to be removed.  
1. Remove and discard the factory-installed jumper assem-  
bly containing the 800-ohm resistor on the economizer  
control module (between terminals SR and +). See Fig. 15.  
2. Remove black wire assembly containing the 620-ohm re-  
sistor from between economizer control module termi-  
nal SO and the outdoor-air thermostat (OAT). Place this  
wire assembly (containing the 620-ohm resistor) be-  
tween economizer control module terminals SR and +,  
replacing the jumper removed in Step 1. See Fig. 15.  
3. Disconnect the blue wire from the OAT.  
Fig. 17 — Outdoor-Air Hood Component Location  
4. Remove OAT from the outside of the economizer (see  
Fig. 14).  
5. Mount the enthalpy sensor (Fig. 20) to the economizer  
on the outside of the unit (in the same location from which  
the OAT was removed) using the 2 screws provided. See  
Fig. 14.  
6. Reconnect the blue wire removed in Step 3 to the en-  
thalpy sensor terminal +.  
7. Cut the violet wire provided to desired length and ter-  
minate with quick-connect terminal provided. Route the  
violet wire from the enthalpy sensor terminal S, through  
the snap bushing, and to the economizer control module  
terminal SO. See Fig. 15.  
8. Set changeover set point to the desired location.  
See Fig. 21.  
Fig. 18 — Seal Strip Location (Air Hood Cross-Sectional View)  
—12—  
NOTE: For maximum benefit of outdoor air, set the enthalpy  
control to the ‘A’’ setting. At this setting, when the relative  
humidity is 50% and the outdoor air is below 74 F, the relay  
contacts on the sensor will be closed.  
3. Remove OAT and black wire assembly containing the  
620-ohm resistor from the outside of the economizer  
(see Fig. 14).  
4. Mount the outdoor-air enthalpy sensor (first sensor) to  
the economizer on the outside of the unit (in the same  
location from which the OAT was removed) using the  
2 screws provided. See Fig. 14.  
9. Reinstall economizer hoods if removed.  
IMPORTANT: Be sure all seal strips and RTV sealant are in-  
tact. A watertight seal to inside of unit must be maintained.  
5. Reconnect the blue wire removed in Step 2 to the en-  
thalpy sensor terminal +.  
6. Cut the violet wire provided to desired length and ter-  
minate with quick-connect terminal provided. Route the  
violet wire from the enthalpy sensor terminal S, through  
the snap bushing, and to the economizer control mod-  
ule terminal SO.  
+
7. Mount the second enthalpy sensor in the return-air duct  
(return-air sensor).  
8. Route the blue wire (provided) from terminal + on the  
return-air enthalpy sensor to the economizer control  
module terminal +.  
9. Route the violet wire (provided) from terminal S on the  
return-air enthalpy sensor to the economizer control  
module terminal SR.  
Fig. 20 — Outdoor-Air and Return-Air  
Enthalpy Sensor  
10. Turn changeover set point dial clockwise past the D’  
setting, or the control will not operate on a differen-  
tial. See Fig. 15.  
CONTROL POINT  
CONTROL  
(Approx Deg)  
CURVE  
AT 50% RH  
11. Reinstall economizer hood if removed.  
A
B
C
D
IMPORTANT: Be sure all seal strips and RTV sealant are in-  
tact. A watertight seal to inside of unit must be maintained.  
IX. STEP 9 — INSTALL ALL ACCESSORIES  
After all the factory-installed options have been adjusted, in-  
stall all field-installed accessories. Refer to the accessory in-  
stallation instructions included with each accessory.  
A. MotormasterI Control Installation (559F180 and 216)  
Install Field-Fabricated Wind Baffles  
Wind baffles must be field-fabricated for all units to ensure  
proper cooling cycle operation at low ambient temperatures.  
See Fig. 22 for baffle details. Use 20-gage, galvanized sheet  
metal, or similar corrosion-resistant metal for baffles. Use field-  
supplied screws to attach baffles to unit. Screws should be  
1
5
4-in. diameter and 8-in. long. Drill required screw holes for  
mounting baffles.  
CAUTION: To avoid damage to the refrigerant coils  
and electrical components, use recommended screw sizes  
only. Use care when drilling holes.  
Install MotormasterI Controls  
RH  
Relative Humidity  
Fig. 21 — Psychrometric Chart for Solid-State  
Enthalpy Control  
Only one Motormaster I control is required per unit. The Motor-  
master I control must be used in conjunction with the Acces-  
sory 0° F Low Ambient Kit (purchased separately). The  
Motormaster I device controls outdoor fan no. 1 while out-  
door fans no. 2 and 3 are sequenced off by the Accessory 0° F  
Low Ambient Kit.  
B. Differential Enthalpy Control  
NOTE: The accessory outdoor-air enthalpy sensor must be  
installed BEFORE the economizer hoods are installed on the  
unit or hoods will have to be removed.  
Accessory 0° F Low Ambient Kit — Install the Accessory  
0°  
F
Low Ambient Kit per instruction supplied with  
1. Remove and discard the factory-installed jumper as-  
sembly containing the 800-ohm resistor on the econo-  
mizer control module (between terminals SR and +. See  
Fig. 15.  
accessory.  
Motor Mount — To ensure proper fan height, replace the ex-  
isting motor mount with the new motor mount provided with  
accessory.  
2. Disconnect black wire from economizer control module  
terminal SO and blue wire from the OAT (outdoor-air  
thermostat).  
—13—  
Install Motormaster III Controls  
Only one Motormaster III control is required per unit.  
Sensor — Install the sensor for thermistor input control in  
the location shown in Fig. 24. Connect sensor leads to the  
purple and grey control signal leads on the Motormaster III  
control.  
Signal Selection Switch — Remove the cover of the Motor-  
master III control. Set the switch to accept the thermistor  
sensor input signal. Set the frequency to match the unit power  
supply (60 Hz).  
Motormaster III Control — Recommended mounting location  
is beneath the control box, mounted to the partition that sepa-  
rates the control box section from the indoor section.  
NOTE: If unit power is supplied through the roof curb and  
basepan of the unit, mount the Motormaster III control on  
the corner post adjacent to the conduit running from the base-  
pan to the bottom of the control box.  
NOTE: Dimensions in ( ) are in mm.  
Fig. 22 — Wind Baffle Details  
Transformer (460-v Units Only) — On 460-v units, a trans-  
former is required. The transformer is provided with the ac-  
cessory and must be field-installed.  
Sensor Assembly — Install the sensor assembly in the loca-  
tion shown in Fig. 23.  
SENSOR  
LOCATION  
MotormasterI Control — Recommended mounting location  
is on the inside of the panel to the left of the control box. The  
control should be mounted on the inside of the panel, verti-  
cally, with leads protruding from bottom of extrusion.  
SENSOR  
LOCATION  
B. Motormaster III Control Installation (559F240 and 300)  
Install Field-Fabricated Wind Baffles  
Wind baffles must be field-fabricated for all units to ensure  
proper cooling cycle operation at low ambient temperatures.  
See Fig. 22 for baffle details. Use 20-gage, galvanized sheet  
metal, or similar corrosion-resistant metal for baffles. Use field-  
supplied screws to attach baffles to unit. Screws should be  
1
5
HAIRPIN END  
HAIRPIN END  
4-in. diameter and 8-in. long. Drill required screw holes for  
mounting baffles.  
559F180  
559F216  
NOTE: All sensors are located on the eighth hairpin up from the bottom.  
CAUTION: To avoid damage to the refrigerant coils  
and electrical components, use recommended screw sizes  
only. Use care when drilling holes.  
Fig. 23 — Motormaster I Sensor Locations  
Replace Outdoor Motor  
Replace outdoor fan motor no. 1 with motor included in  
accessory kit. Existing motor is not Motormaster III  
compatible.  
—14—  
addition, Schrader-type valves are located underneath the low-  
pressure switches. Be sure that caps on the ports are tight.  
VII. COMPRESSOR ROTATION  
It is important to be certain the compressors are rotating in  
the proper direction. To determine whether or not compres-  
sors are rotating in the proper direction:  
1. Connect service gages to suction and discharge pres-  
sure fittings.  
2. Energize the compressor.  
3. The suction pressure should drop and the discharge pres-  
sure should rise, as is normal on any start-up.  
If the suction pressure does not drop and the discharge pres-  
sure does not rise to normal levels:  
1. Note that the evaporator fan is probably also rotating  
in the wrong direction.  
2. Turn off power to the unit.  
3. Reverse any two of the incoming power leads.  
4. Turn on power to the compressor.  
SENSOR  
LOCATION  
SENSOR  
LOCATION  
The suction and discharge pressure levels should now move  
to their normal start-up levels.  
NOTE: When compressors are rotating in the wrong direc-  
tion, the unit will have increased noise levels and will not  
provide heating and cooling.  
After a few minutes of reverse operation, the scroll compres-  
sor internal overload protection will open, which will acti-  
vate the units lockout and requires a manual reset. Reset is  
accomplished by turning the thermostat on and off.  
HAIRPIN END  
HAIRPIN END  
VIII. EVAPORATOR FAN  
559F240  
559F300  
Fan belt and variable pulleys are factory installed. Remove  
tape from the fan pulley. See Table 4 for Air Quantity Limits.  
See Tables 5-7 for Fan Performance data. Be sure that fans  
rotate in the proper direction. See Tables 8 and 9 for Static  
Pressure information for accessories and options. See  
Table 10 for fan rpm at various fan motor pulley settings. To  
alter fan performance, see Evaporator-Fan Performance Ad-  
justment section, page 21.  
NOTE: All sensors are located on the eighth hairpin up from the bottom.  
Fig. 24 — MotormasterIII Sensor Locations  
START-UP  
Use the following information and Start-Up Checklist on  
page CL-1 to check out unit PRIOR to start-up.  
I. UNIT PREPARATION  
Check that unit has been installed in accordance with these  
installation instructions and all applicable codes.  
Table 4 — Air Quantity Limits  
UNIT 559F  
MINIMUM CFM  
MAXIMUM CFM  
II. SERVICE VALVES  
180  
216  
240  
300  
4500  
5400  
6000  
7000  
7,500  
9,000  
10,000  
11,250  
Ensure that optional suction, discharge, and standard liquid  
line service valves are open. Damage to the compressor could  
result if they are left closed.  
IX. CONDENSER FANS AND MOTORS  
III. INTERNAL WIRING  
Fans and motors are factory set. Refer to Condenser-Fan Ad-  
justment section (page 22) as required.  
Check all electrical connections in unit control boxes; tighten  
as required.  
X. RETURN-AIR FANS  
IV. CRANKCASE HEATER(S)  
Check that correct filters are installed in filter tracks. See  
Table 1. Do not operate unit without return-air filters.  
Heater(s) is energized as long as there is power to unit and  
compressor is operating.  
XI. OUTDOOR-AIR INLET SCREENS  
IMPORTANT: Unit power must be on for 24 hours prior to  
Outdoor-air inlet screens must be in place before operating  
unit.  
start-up. Otherwise, damage to compressor may result.  
V. COMPRESSOR MOUNTING  
XII. ACCESSORY ECONOMIZER ADJUSTMENT  
Compressors are internally spring mounted. Do not loosen or  
remove compressor holddown bolts.  
Remove filter access panel. Check that outdoor-air damper is  
closed and return-air damper is open.  
VI. REFRIGERANT SERVICE PORTS  
Economizer operation and adjustment is described in Base  
Unit Operation and Economizer Adjustment sections  
(pages 20 and 22), respectively.  
Each refrigerant system has a total of 3 Schrader-type serv-  
ice gage ports. One port is located on the suction line, one on  
the compressor discharge line, and one on the liquid line. In  
—15—  
Table 5 — Fan Performance — 559F180  
Available External Static Pressure (in. wg)  
559F180 (15 TONS)  
Airflow  
0.2  
0.4  
0.6  
0.8  
1.0  
1.2  
(Cfm)  
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts  
4500  
4800  
5100  
5400  
5700  
6000  
6300  
6600  
6900  
7200  
7500  
684 1.28 1102  
715 1.47 1265  
747 1.67 1442  
779 1.90 1635  
812 2.14 1844  
845 2.40 2068  
878 2.68 2309  
912 2.98 2566  
791 1.49 1283  
817 1.68 1451  
844 1.89 1633  
872 2.12 1831  
901 2.37 2044  
887 1.70 1466  
910 1.90 1638  
977 1.92 1652 1061 2.13 1841 1139 2.36 2034  
997 2.12 1828 1078 2.34 2021 1155 2.57 2217  
934 2.12 1825 1018 2.34 2019 1097 2.57 2216 1171 2.80 2416  
959 2.35 2027 1040 2.58 2226 1117 2.81 2426 1189 3.05 2629  
985 2.60 2245 1063 2.84 2448 1138 3.07 2652 1209 3.31 2858  
931 2.64 2273 1011 2.87 2478 1087 3.11 2685 1160 3.35 2893 1229 3.60 3103  
961 2.92 2518 1039 3.16 2728 1112 3.41 2939 1183 3.65 3151 1250 3.90 3365  
992 3.22 2780 1067 3.47 2994 1138 3.72 3209 1207 3.97 3425 1273 4.22 3642  
946 3.29 2841 1023 3.55 3059 1096 3.80 3277 1165 4.05 3496 1232 4.31 3716  
981 3.63 3133 1055 3.89 3355 1125 4.15 3578  
1016 3.99 3443 1087 4.25 3669  
559F180 (15 TONS) (cont)  
Available External Static Pressure (in. wg)  
1.6 1.8 1.9  
Airflow  
1.4  
2.0  
(Cfm)  
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts  
4500  
4800  
5100  
5400  
5700  
6000  
6300  
6600  
6900  
7200  
7500  
1214 2.59 2230 1285 2.82 2430 1353 3.05 2633 1386 3.17 2736 1418 3.29 2839  
1228 2.80 2417 1297 3.04 2619 1364 3.27 2825 1396 3.40 2928 1428 3.52 3033  
1243 3.04 2618 1311 3.27 2823 1376 3.51 3031 1408 3.64 3136 1439 3.76 3242  
1259 3.29 2835 1326 3.53 3043 1390 3.77 3254 1421 3.90 3360 1452 4.02 3467  
1277 3.56 3067 1342 3.80 3278 1405 4.05 3492 1435 4.17 3600 1466 4.30 3708  
1295 3.84 3316 1359 4.09 3530 1421 4.34 3746  
1315 4.15 3580  
——  
LEGEND  
Brake Horsepower  
3. Static pressure losses (i.e., economizer) must be added to external  
static pressure before entering Fan Performance table.  
4. Interpolation is permissible. Do not extrapolate.  
5. Fan performance is based on wet coils, clean filters, and  
casing losses. See Table 8 for accessory/FIOP static pressure  
information.  
6. Extensive motor and drive testing on these units ensures that the full  
horsepower and watts range of the motor can be utilized with confi-  
dence. Using your fan motors up to the watts or bhp rating shown  
will not result in nuisance tripping or premature motor failure. Unit  
warranty will not be affected.  
7. Use of a field-supplied motor may affect wiring size. Contact your  
Bryant representative for details.  
Bhp  
FIOP  
Factory-Installed Option  
Input Watts to Motor  
Watts  
NOTES:  
1. Standard low-medium static drive range is 891 to 1179 rpm. Alter-  
nate high-static drive range is 1227 to 1550. Other rpms require a  
field-supplied drive.  
2. Maximum continuous bhp is 4.25 and the maximum continuous watts  
are 3775. Do not adjust motor rpm such that motor maximum bhp  
and/or watts is exceeded at the maximum operating cfm.  
—16—  
Table 6 — Fan Performance — 559F216 and 240  
Available External Static Pressure (in. wg)  
559F216 and 240 (18 and 20 TONS)  
Airflow  
0.2  
0.4  
0.6  
0.8  
1.0  
1.2  
(Cfm)  
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts  
5,500  
6,000  
6,500  
7,000  
7,500  
8,000  
8,500  
682 1.99 1675  
730 2.38 2005  
778 2.82 2373  
828 3.31 2780  
878 3.84 3227  
928 4.42 3715  
760 2.29 1922  
802 2.68 2257  
846 3.13 2630  
892 3.62 3042  
938 4.15 3494  
832 2.59 2177  
871 2.99 2516  
911 3.44 2893  
901 2.90 2441  
935 3.31 2783  
965 3.22 2712 1027 3.56 2990  
997 3.63 3057 1056 3.97 3337  
972 3.76 3164 1031 4.09 3440 1087 4.43 3722  
953 3.94 3310 1011 4.26 3583 1067 4.59 3863 1121 4.93 4148  
996 4.48 3766 1051 4.81 4043 1105 5.14 4326 1156 5.49 4613  
985 4.74 3986 1040 5.07 4263 1093 5.40 4544 1144 5.74 4830 1194 6.09 5120  
979 5.05 4245 1033 5.38 4521 1085 5.71 4801 1136 6.05 5086 1185 6.39 5375 1232 6.74 5669  
9,000 1030 5.73 4817 1082 6.06 5098 1131 6.40 5382 1180 6.74 5671 1227 7.09 5964 1272 7.44 6260  
9,500 1082 6.46 5433 1131 6.80 5718 1178 7.14 6007 1225 7.49 6299 1270 7.84 6595 1313 8.20 6895  
10,000 1134 7.25 6093 1180 7.59 6382 1226 7.94 6675 1270 8.29 6971 1313 8.65 7271 1356 9.01 7574  
559F216 and 240 (18 and 20 TONS) (cont)  
Available External Static Pressure (in. wg)  
Airflow  
1.4  
1.6  
1.8  
1.9  
2.0  
(Cfm)  
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts  
5,500 1086 3.89 3275 1142 4.24 3567 1197  
6,000 1112 4.31 3623 1167 4.66 3915 1219  
6,500 1142 4.77 4010 1194 5.12 4304 1245  
7,000 1173 5.28 4438 1224 5.63 4733 1273  
7,500 1207 5.83 4906 1255 6.19 5203 1302  
8,000 1242 6.44 5415 1289 6.80 5714 1334  
8,500 1279 7.10 5966 1324 7.45 6268 1368  
9,000 1317 7.80 6561 1360 8.16 6865 1403  
9,500 1356 8.56 7198 1398 8.93 7505 1440  
4.59 3864 1223 4.77 4015 1249 4.96 4167  
5.01 4213 1245 5.19 4364 1270 5.37 4516  
5.47 4602 1270 5.65 4754 1294 5.83 4906  
5.98 5033 1296 6.17 5184 1320 6.35 5337  
6.55 5504 1326 6.73 5657 1348 6.91 5810  
7.16 6018 1357 7.34 6171 1379 7.52 6325  
7.82 6573 1389 8.00 6728 1411 8.18 6883  
8.53 7173 1424 8.71 7328 1445 8.90 7484  
9.29 7815 1460 9.48 7972 1480 9.67 8129  
10,000 1397 9.37 7881 1438 9.74 8190 1477 10.11 8503  
LEGEND  
3. Static pressure losses (i.e., economizer) must be added to external  
static pressure before entering Fan Performance table.  
4. Interpolation is permissible. Do not extrapolate.  
5. Fan performance is based on wet coils, clean filters, and  
casing losses. See Table 9 for accessory/FIOP static pressure  
information.  
Bhp  
FIOP  
Watts  
Brake Horsepower  
Factory-Installed Option  
Input Watts to Motor  
NOTES:  
1. Standard low-medium static drive range for the 216 size is 910 to  
1095 rpm. Standard low-medium static drive range for the 240 size  
is 1002 to 1225 rpm. Alternate high-static drive range for the  
216 size is 1069 to 1287. Alternate high-static drive range for the  
240 size is 1193 to 1458 rpm. Other rpms require a field-supplied  
drive.  
2. Maximum continuous bhp for the 216 size is 5.90. Maximum con-  
tinuous bhp for the 240 size is 8.7 (208/230 v) or 9.5 (460 v). The  
maximum continuous watts for the 216 size is 5180. The maximum  
continuous watts for the 240 size is 7915 (208/230 v) or 8640  
(460 v). Do not adjust motor rpm such that motor maximum bhp and/or  
watts is exceeded at the maximum operating cfm.  
6. Extensive motor and drive testing on these units ensures that the full  
horsepower and watts range of the motor can be utilized with confi-  
dence. Using your fan motors up to the watts or bhp rating shown  
will not result in nuisance tripping or premature motor failure. Unit  
warranty will not be affected.  
7. Use of a field-supplied motor may affect wiring size. Contact your  
Bryant representative for details.  
—17—  
Table 7 — Fan Performance — 559F300  
Available External Static Pressure (in. wg)  
559F300 (25 TONS)  
Airflow  
0.2  
0.4  
0.6  
0.8  
1.0  
1.2  
(Cfm)  
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts  
7,000  
7,500  
8,000  
845 3.26 2693  
896 3.82 3156  
909  
956  
3.60 2979  
969  
3.96 3272 1028  
4.54 3752 1069  
5.17 4278 1112  
5.87 4853 1156  
6.63 5478 1202  
7.44 6155 1248  
8.33 6886 1295  
9.28 7671 1342  
4.32 3574 1083  
4.91 4060 1123  
5.56 4593 1163  
6.26 5175 1205  
7.02 5808 1248  
7.85 6492 1293  
8.74 7229 1338  
4.70 3883 1137  
5.29 4375 1174  
5.94 4915 1213  
6.66 5504 1253  
7.43 6142 1294  
8.26 6833 1336  
9.16 7577 1380  
5.08  
5.68  
6.34  
7.06  
7.84  
8.68  
9.59  
4,200  
4,698  
5,243  
5,838  
6,483  
7,179  
7,929  
8,733  
9,594  
4.17 3450 1014  
4.80 3969 1060  
5.49 4537 1106  
6.23 5155 1154  
7.04 5824 1202  
7.92 6547 1251  
8.86 7325 1300  
948 4.43 3667 1005  
8,500 1001 5.11 4226 1054  
9,000 1053 5.85 4836 1104  
9,500 1106 6.65 5498 1155  
10,000 1159 7.52 6214 1206  
10,500 1213 8.45 6984 1257  
11,000 1266 9.45 7810 1309  
9.70 8020 1384 10.13 8375 1424 10.56  
9.87 8159 1350 10.29 8511 1391 10.73 8868 1431 11.16 9229 1470 11.60  
11,250 1293 9.97 8245 1334 10.40 8597 1375 10.83 8953 1415 11.26 9313 1454 11.70 9677 1493 12.15 10,045  
559F300 (25 TONS) (cont)  
Available External Static Pressure (in. wg)  
Airflow  
1.4  
1.6  
1.8  
(Cfm)  
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts  
7,000 1189 5.47 4,524 1239 5.87 4,854 1288 4.91 5191  
7,500 1224 6.08 5,026 1272 6.48 5,362 1320 5.56 5703  
8,000 1261 6.75 5,577 1307 7.16 5,917 1353 6.26 6263  
8,500 1299 7.47 6,177 1344 7.89 6,523 1388 7.02 6873  
9,000 1338 8.26 6,828 1382 8.68 7,179 1424 7.85 7534  
9,500 1379 9.11 7,530 1421 9.54 7,887 1462 8.74 8247  
10,000 1421 10.02 8,286 1461 10.46 8,648 1501 9.70 9014  
10,500 1464 11.00 9,096 1503 11.45 9,464 1541 10.73 9835  
11,000 1508 12.05 9,963 1546 12.50 10,336  
11,250 1530 12.60 10,417  
LEGEND  
3. Static pressure losses (i.e., economizer) must be added to external  
static pressure before entering Fan Performance table.  
4. Interpolation is permissible. Do not extrapolate.  
5. Fan performance is based on wet coils, clean filters, and  
casing losses. See Table 9 for accessory/FIOP static pressure  
information.  
6. Extensive motor and drive testing on these units ensures that the full  
horsepower and watts range of the motor can be utilized with confi-  
dence. Using your fan motors up to the watts or bhp rating shown  
will not result in nuisance tripping or premature motor failure. Unit  
warranty will not be affected.  
7. Use of a field-supplied motor may affect wiring size. Contact your  
Bryant representative for details.  
Bhp  
Brake Horsepower  
Factory-Installed Option  
Input Watts to Motor  
FIOP  
Watts  
NOTES:  
1. Standard low-medium static drive range is 1066 to 1283 rpm. Alter-  
nate high-static drive range is 1332 to 1550. Other rpms require a  
field-supplied drive.  
2. Maximum continuous bhp is 10.2 (208/230 v) or 11.8 (460 v) and the  
maximum continuous watts are 9510 (208/230 v) or 11,000 (460 v).  
Do not adjust motor rpm such that motor maximum bhp and/or watts  
is exceeded at the maximum operating cfm.  
—18—  
Table 8 — Accessory/FIOP Static Pressure (in. wg) — 559F180  
CFM  
COMPONENT  
4500  
0.04  
0.22  
5000  
0.05  
0.26  
6000  
0.07  
0.35  
7200  
0.09  
0.44  
7500  
0.10  
0.46  
Economizer  
Glycol Coil  
Electric Heat (kW)  
26/34  
32  
0.06  
0.06  
0.07  
0.07  
0.09  
0.09  
0.07  
0.07  
0.08  
0.08  
0.10  
0.10  
0.09  
0.09  
0.12  
0.12  
0.15  
0.15  
0.11  
0.11  
0.16  
0.15  
0.20  
0.20  
0.12  
0.12  
0.17  
0.17  
0.21  
0.21  
42/56  
55  
56/75  
80  
LEGEND  
NOTES:  
1. The static pressure must be added to external static pressure. The  
sum and the evaporator entering-air cfm should then be used in con-  
junction with the Fan Performance tables to determine blower rpm  
and watts.  
FIOP  
Factory-Installed Option  
2. Heaters are rated at 208/240 v and 480 v.  
Table 9 — Accessory/FIOP Static Pressure (in. wg) — 559F216-300  
CFM  
COMPONENT  
5400  
0.06  
0.30  
6000  
0.07  
0.35  
7200  
0.09  
0.44  
9000  
0.11  
0.58  
10,000  
0.12  
11,250  
0.14  
Economizer  
Glycol Coil  
0.66  
0.77  
Electric Heat (kW)  
26/34  
32  
0.08  
0.08  
0.11  
0.11  
0.14  
0.14  
0.09  
0.09  
0.12  
0.12  
0.15  
0.15  
0.11  
0.11  
0.15  
0.15  
0.20  
0.20  
0.15  
0.15  
0.19  
0.19  
0.24  
0.24  
0.17  
0.17  
0.21  
0.21  
0.26  
0.26  
0.20  
0.20  
0.24  
0.24  
0.29  
0.29  
42/56  
55  
56/75  
80  
LEGEND  
NOTES:  
1. The static pressure must be added to external static pressure. The  
sum and the evaporator entering-air cfm should then be used in con-  
junction with the Fan Performance tables to determine blower rpm  
and watts.  
FIOP  
Factory-Installed Option  
2, Heaters are rated at 208/240 v and 480 v.  
Table 10 — Fan Rpm at Motor Pulley Settings*  
MOTOR PULLEY TURNS OPEN  
UNIT  
559F  
1
0
2
1
112  
2
212  
3
312  
4
412  
978  
5
512  
6
180†  
180**  
216†  
216**  
240†  
240**  
300†  
300**  
††  
††  
††  
††  
††  
††  
††  
††  
††  
††  
††  
††  
††  
††  
††  
††  
1179  
1559  
1095  
1287  
1225  
1458  
1283  
1150  
1522  
1077  
1265  
1209  
1434  
1269  
1121  
1488  
1058  
1243  
1187  
1407  
1247  
1551  
1093  
1455  
1040  
1222  
1165  
1381  
1225  
1524  
1064  
1422  
1021  
1200  
1143  
1354  
1203  
1497  
1035  
1389  
1002  
1178  
1120  
1328  
1182  
1470  
1006  
1356  
984  
949  
920  
891  
1323  
965  
1289  
947  
1256  
928  
1227  
910  
1156  
1098  
1301  
1160  
1443  
1134  
1076  
1275  
1138  
1415  
1112  
1053  
1248  
1116  
1388  
1091  
1031  
1222  
1095  
1361  
1069  
1002  
1193  
1066  
1332  
*Approximate fan rpm shown.  
†Indicates standard drive package.  
**Indicates alternate drive package.  
††Due to belt and pulley size, pulley cannot be set to this number of turns open.  
NOTE: For speeds not listed above, field-supplied drives are required.  
—19—  
XIII. BASE UNIT OPERATION  
A. Evaporator Coil  
Clean as required with a commercial coil cleaner.  
A. Cooling, Units Without Economizer  
NOTE: The 559F300 unit has a mist eliminator screen  
attached to the evaporator coil to prevent condensate runoff  
at high wet-bulb conditions. Check periodically and clean as  
necessary.  
When thermostat calls for cooling, terminals G and Y1 are  
energized. The indoor (evaporator) fan contactor (IFC), and  
compressor contactor no. 1 (C1) are energized and evaporator-  
fan motor, compressor no. 1 and condenser fans start. The  
condenser-fan motors run continuously while unit is cooling.  
If the thermostat calls for a second stage of cooling by ener-  
gizing Y2, compressor contactor no. 2 (C2) is energized and  
compressor no. 2 starts.  
B. Condenser Coil  
Clean condenser coil annually and as required by location  
and outdoor-air conditions. Inspect coil monthly — clean as  
required.  
B. Heating, Units Without Economizer (If Accessory or Op-  
tional Heater is Installed)  
C. Condensate Drain  
Check and clean each year at start of cooling season.  
Upon a call for heating through terminal W1, IFC and heater  
contactor no. 1 (HC1) are energized. On units equipped for  
2 stages of heat, when additional heat is needed, HC2 is en-  
ergized through W2.  
D. Filters  
Clean or replace at start of each heating and cooling season,  
or more often if operating conditions require. Refer to  
Table 1 for type and size.  
C. Cooling, Units With Economizer  
NOTE: The 559F300 unit requires industrial grade throw-  
away filters capable of withstanding face velocities up to  
625 fpm. Ensure that replacement filters for the 559F300 units  
are rated for 625 fpm.  
Upon a call for cooling, when outdoor ambient temperature  
is above the outdoor-air temperature control setting, the evapo-  
rator and condenser fans and compressor energize. The econo-  
mizer damper moves to VENT position.  
Upon a first-stage call for cooling, when outdoor ambient  
temperature is below the temperature control setting, the evapo-  
rator fan starts and economizer damper modulates to main-  
tain mixed-air temperature. The compressor(s) remains off.  
E. Outdoor-Air Inlet Screens  
Clean screens with steam or hot water and a mild detergent.  
Do not use throwaway filters in place of screens.  
II. LUBRICATION  
A. Compressors  
Upon a second-stage call for cooling, compressor no. 1 is en-  
ergized and mechanical cooling is integrated with econo-  
mizer cooling. Compressor no. 2 is locked out. If the outdoor-  
air temperature is below 50 F, a cooling lockout switch prevents  
the compressor(s) from running.  
Each compressor is charged with the correct amount of oil at  
the factory. Conventional white oil (Sontext 200LT) is used.  
White oil is compatible with 3GS oil, and 3GS oil may be used  
if the addition of oil is required. See compressor nameplate  
for original oil charge. A complete recharge should be  
four ounces less than the original oil charge. When a com-  
pressor is exchanged in the field it is possible that a major  
portion of the oil from the replaced compressor may still be  
in the system. While this will not affect the reliability of the  
replacement compressor, the extra oil will add rotor drag and  
increase power usage. To remove this excess oil, an access  
valve may be added to the lower portion of the suction line at  
the inlet of the compressor. The compressor should then be  
run for 10 minutes, shut down, and the access valve opened  
until no oil flows. This should be repeated twice to make sure  
the proper oil level has been achieved.  
When supply-air temperature drops below a fixed set point,  
the economizer damper modulates to maintain the tempera-  
ture at the fixed set point.  
D. Freeze Protection Thermostat  
A freeze protection thermostat (FPT) is located on the evapo-  
rator coil. It detects frost build-up and turns off the compres-  
sor, allowing the coil to clear. Once frost has melted, the com-  
pressor can be reenergized by resetting the compressor lockout.  
E. Heating, Units With Economizer (If Accessory or Op-  
tional Heater Is Installed)  
The outdoor air damper stays at VENT position while the evapo-  
rator fan is operating. Upon a call for heating through ter-  
minal W1, the indoor (evaporator) fan contactor (IFC) and  
heater contactor no. 1 (HC1) are energized. On units equipped  
for 2 stages of heat, when additional heat is needed, HC2 is  
energized through W2.  
B. Fan Shaft Bearings  
For size 180 units, bearings are permanently lubricated. No  
field lubrication is required. For size 216-300 units, the bear-  
ings are of the pillow block type and have grease fittings. The  
bearing opposite the motor end has an extended tube line so  
it can be lubricated from the motor side. Lubricate the bear-  
ings twice annually.  
SERVICE  
WARNING: Before performing service or mainte-  
nance operations on unit, turn off main power switch  
to unit. Turn off accessory heater power switch if appli-  
cable. Electrical shock could cause personal injury.  
Typical lubricants are given below:  
MANUFACTURER  
LUBRICANT  
Texaco  
Mobil  
Sunoco  
Texaco  
Regal AFB-2*  
Mobilplex EP No. 1  
Prestige 42  
Multifak 2  
I. CLEANING  
*Preferred lubricant because it contains rust and oxidation inhibitors.  
Inspect unit interior at beginning of each heating and cool-  
ing season and as operating conditions require. Remove unit  
top panel and/or side panels for access to unit interior.  
C. Condenser and Evaporator-Fan Motor Bearings  
The condenser and evaporator-fan motors have permanently-  
sealed bearings, so no field lubrication is necessary.  
—20—  
III. EVAPORATOR FAN PERFORMANCE ADJUSTMENT  
(Fig. 25-27)  
Fan motor pulleys are factory set for speed shown in Table 1.  
To change fan speeds:  
1. Shut off unit power supply.  
2. a. Size 180 Only: Loosen belt by loosening fan motor  
mounting plate nuts.  
b. Size 216-300 Only: Loosen nuts on the 2 carriage bolts  
in the motor mounting base. Install jacking bolt and  
plate under motor base (bolt and plate are shipped  
in installer s packet). See Fig. 25. Using bolt and plate,  
raise motor to top of slide and remove belt. Secure  
motor in this position by tightening the nuts on the  
carriage bolts.  
3. Loosen movable-pulley flange setscrew (see Fig. 25).  
4. Screw movable flange toward fixed flange to increase speed  
and away from fixed flange to decrease speed. Increas-  
ing fan speed increases load on motor. Do not exceed maxi-  
mum speed specified in Table 1.  
See Table 4 for air quantity limits.  
5. Set movable flange at nearest keyway of pulley hub and  
tighten setscrew. (See Table 1 for speed change for each  
full turn of pulley flange.)  
6. Replace and tighten belts. See Belt Tension Adjustment  
section on page 22.  
To align fan and motor pulleys:  
1. Loosen fan pulley setscrews.  
2. Slide fan pulley along fan shaft.  
Fig. 25 — Evaporator-Fan Pulley Alignment  
and Adjustment  
3. Make angular alignment by loosening motor from mount-  
ing plate.  
IV. EVAPORATOR FAN SERVICE AND REPLACEMENT  
A. 559F180 Units (See Fig. 26)  
NOTE: To remove belts only, follow Steps 1-6.  
1. Remove filter and supply-air section panels.  
2. Remove unit top panel.  
3. Loosen carriage nuts A and B holding motor mount as-  
sembly to fan scroll side plates.  
4. Loosen screw C.  
5. Rotate motor mount assembly (with motor attached)  
as far as possible away from evaporator coil.  
6. Remove belt.  
7. Rotate motor mount assembly back past original posi-  
tion toward evaporator coil.  
8. Remove motor mounting nuts D and E (both sides).  
9. Lift motor up through top of unit.  
10. Reverse above procedure to reinstall motor.  
11. Check and adjust belt tension as necessary.  
B. 559F216-300 Units (See Fig. 27)  
The 559F216-300 units use a fan motor mounting system that  
features a slide-out motor mounting plate. To replace or serv-  
ice the motor, slide out the bracket.  
1. Remove the evaporator-fan access panel and the heat-  
ing control access panel.  
2. Remove the center post (located between the evapora-  
tor fan and heating control access panels) and all screws  
securing it.  
Fig. 26 — 559F180 Evaporator-Fan  
Motor Section  
3. Loosen nuts on the two carriage bolts in the motor mount-  
ing base.  
—21—  
4. Using jacking bolt under motor base, raise motor to top  
of slide and remove belt. Secure motor in this position  
by tightening the nuts on the carriage bolts.  
VI. CONDENSER-FAN ADJUSTMENT  
A. 559F180-216 Units (Fig. 28)  
1. Shut off unit power supply.  
5. Remove the belt drive.  
2. Remove access panel(s) closest to the fan to be adjusted.  
3. Loosen fan hub setscrews.  
6. Remove jacking bolt and tapped jacking bolt plate.  
7. Remove the 2 screws that secure the motor mounting  
plate to the motor support channel.  
4. Adjust fan height on shaft using a straightedge placed  
across the fan orifice.  
8. Remove the 3 screws from the end of the motor sup-  
port channel that interfere with the motor slide path.  
5. Tighten setscrews and replace panel(s).  
6. Turn on unit power.  
9. Slide out the motor and motor mounting plate.  
10. Disconnect wiring connections and remove the 4 mount-  
ing bolts.  
B. 559F240,300 Units (Fig. 29)  
1. Shut off unit power supply.  
11. Remove the motor.  
2. Remove fan top-grille assembly and loosen fan hub screws.  
12. To install the new motor, reverse Steps 1-11.  
3. Adjust fan height on unit, using a straightedge placed  
across the fan orifice.  
4. Tighten setscrews and replace rubber hubcap to pre-  
vent hub from rusting to motor shaft.  
5. Fill hub recess with permagum if rubber hubcap is  
missing.  
NOTE: Dimensions are in inches.  
Fig. 28 — Condenser Fan Adjustment, 559F180,216  
NOTE: A 212-in. bolt and threaded plate are included in the installer’s  
packet. They should be added to the motor support channel below the  
motor mounting plate to aid in raising the motor. The plate part number  
3
is 50DP503842. The adjustment bolt is  
8
- 16 x 134-in. LG.  
Fig. 27 — 559F216-300 Evaporator-Fan  
Motor Section  
NOTE: Dimensions are in inches.  
Fig. 29 — Condenser-Fan Adjustment, 559F240,300  
VII. ECONOMIZER ADJUSTMENT  
V. BELT TENSION ADJUSTMENT  
See Tables 11 and 12 for checkout and outdoor-air tempera-  
ture simulation. Make certain the outdoor-air damper is fully  
closed and the return-air damper is fully open before com-  
pleting the following steps.  
To adjust belt tension:  
1. Loosen fan motor bolts.  
2. Adjust belt tension:  
a. Size 180 Units: Move motor mounting plate up or  
down for proper belt tension (12 in. deflection with  
one finger).  
1. Turn on power to the unit.  
2. Turn the thermostat fan switch to the ON position. The  
damper will go to the vent position.  
b. Size 216-300 Units: Turn motor jacking bolt to move  
motor mounting plate up or down for proper belt  
tension (38 in. deflection at midspan with one finger  
[9 lb force]).  
3. Adjust the vent position with the minimum damper po-  
sition adjustment on the module. See Fig. 15.  
4. Set the system selector switch to COOL position  
and set the cooling temperature selector to its lowest  
setting.  
3. Tighten nuts.  
4. Adjust bolts and nut on mounting plate to secure motor  
in fixed position.  
NOTE: The Cooling mode may also be simulated by remov-  
ing the thermostat wires from terminals Y1 and Y2 and in-  
stalling a jumper between terminals R and Y1. Refer to unit  
label diagram for terminal locations.  
—22—  
Table 11 — Economizer Checkout Procedures  
9. Remove the jumper from around the contacts of the OAT  
if installed in Step 6. Remove the jumper from termi-  
nals T and T1 installed in Step 7.  
TEST PROCEDURE  
RESULTS  
A. Disconnect power at TR  
and TR1.  
10. If the Cooling mode was simulated to operate the unit  
in Step 4, remove the jumper and reconnect the ther-  
mostat wires to terminals Y1 and Y2.  
Disconnect jumper  
between P and  
P1. See Fig. 15.  
VIII. POWER FAILURE  
B. Jumper TR to 1.  
C. Jumper T1 to T.  
D. Disconnect outdoor-air  
thermostat connections  
from SO and +.  
Dampers have a spring return. In event of power failure, damp-  
ers will return to fully closed position until power is restored.  
Do not manually operate damper motor.  
Factory-installed  
IX. REFRIGERANT CHARGE  
800 ohm resistor  
should remain connected  
Amount of refrigerant charge is listed on unit nameplate and  
in Table 1. Refer to GTAC II; Module 5; Charging, Recovery,  
Recycling, and Reclamation section for charging methods and  
procedures. Unit panels must be in place when unit is oper-  
ating during charging procedure.  
to SR and +.  
E. Reconnect power to  
terminals TR and TR1.  
1. LED (light-emitting diode)  
should be off.  
2. Motor is in closed position.  
NOTE: Do not use recycled refrigerant as it may contain  
contaminants.  
TEST PROCEDURE  
RESULTS  
A. No Charge  
A. Disconnect  
factory-installed  
resistor from  
Use standard evacuating techniques. After evacuating  
system, weigh in the specified amount of refrigerant (refer to  
Table 1).  
terminals SR and +.  
1. LED (light-emitting diode)  
should be on.  
2. Motor drives toward open.  
B. Low Charge Cooling  
Using cooling charging chart (see Fig. 30), add or remove re-  
frigerant until conditions of the chart are met. Note that charg-  
ing chart is different from those normally used. An accurate  
pressure gage and temperature-sensing device is required.  
Charging is accomplished by ensuring the proper amount of  
liquid sub-cooling. Measure liquid line pressure at the liquid  
line service valve using pressure gage. Connect temperature  
sensing device to the liquid line near the liquid ine service  
valve and insulate it so that outdoor ambient temperature  
does not affect reading.  
Table 12 — High and Low Outdoor-Air  
Temperature Simulation  
TEST PROCEDURE  
RESULTS  
A. Reconnect factory-  
installed 800 ohm resis-  
tor between terminals  
SR and +.  
B. Connect 1200 ohm  
checkout resistor  
between terminals  
SO and +.  
C. To Use the Cooling Charging Chart  
C. Turn set point poten-  
Use the above temperature and pressure readings, and find  
the intersection point on the cooling charging chart. If inter-  
section point on chart is above line, add refrigerant. If inter-  
section point on chart is below line, carefully recover some of  
the charge. Recheck suction pressure as charge is adjusted.  
tiometer to position A.  
Low outdoor-air temperature  
test results:  
1. LED (light-emitting diode)  
should be on.  
2. Motor drives toward open.  
NOTE: Indoor-air CFM must be within normal operating range  
of unit. All outdoor fans must be operating.  
D. Turn set point poten-  
tiometer to position D.  
E. Disconnect 1200 ohm  
checkout resistor.  
The TXV (thermostatic expansion valve) is set to maintain  
between 15 and 20 degrees of superheat at the compressors.  
The valves are factory set and should not require  
re-adjustment.  
High outdoor-air temperature  
test results:  
1. LED should be off.  
2. Motor drives toward closed.  
X. FILTER DRIER  
Replace whenever refrigerant system is exposed to  
atmosphere.  
5. Set the outdoor-air thermostat (OAT) located in the econo-  
mizer section of the unit (see Fig. 14) to 75 F.  
XI. PROTECTIVE DEVICES  
A. Compressor Protection  
6. If the outdoor temperature is below 75 F, the econo-  
mizer will control the mixed air with the mixed-air sen-  
sor. If the outdoor air is above 75 F, place a jumper  
around the contacts of the OAT.  
Overtemperature  
Each compressor has an internal protector to protect it against  
excessively high discharge gas temperatures.  
7. J umper terminal T to terminal T1 on the module (see  
Fig. 15). The economizer will go to the full open posi-  
tion. The outdoor-air damper will go to the full open  
position, and the return-air damper will go to the full  
closed position.  
Overcurrent  
Each compressor has internal line break motor protection,  
except circuit no. 1 on the 559F300 unit. Compressor  
no. 1 on the 559F300 unit uses an electronic module, located  
with the compressor junction box, to provide motor protec-  
tion. This electronic module monitors winding and discharge  
temperatures. If these temperatures reach the trip values,  
the module interrupts the control line and causes the com-  
pressor to switch off.  
8. Adjust mechanical linkage, if necessary, for correct po-  
sitioning. It may be necessary to remove the filters to  
adjust the linkage.  
—23—  
BOTH CIRCUITS  
ALL OUTDOOR FANS MUST BE OPERATING  
B. Evaporator Fan Motor Protection  
A manual reset, calibrated trip, magnetic circuit breaker pro-  
tects against overcurrent. Do not bypass connections or in-  
crease the size of the breaker to correct trouble. Determine  
the cause and correct it before resetting the breaker.  
140  
120  
ADD CHARGE IF ABOVE CURVE  
C. Condenser-Fan Motor Protection  
Each condenser-fan motor is internally protected against  
overtemperature.  
100  
80  
D. High- and Low-Pressure Switches  
If either switch trips, or if the compressor overtemperature  
switch activates, that refrigerant circuit will be automati-  
cally locked out by the CLO. To reset, manually move the ther-  
mostat setting.  
REDUCE CHARGE IF BELOW CURVE  
60  
E. Freeze Protection Thermostat  
An FPT is located on the top and bottom of the evaporator  
coil. It detects frost build-up and turns off the compressor, al-  
lowing the coil to clear. Once the frost has melted, the com-  
pressor can be reenergized by resetting the compressor  
lockout.  
40  
100  
150  
200  
250  
300  
350  
400  
50  
LIQUID PRESSURE AT LIQUID VALVE (PSIG)  
Fig. 30 — Cooling Charging Chart — All Units  
Crankcase Heater  
XII. RELIEF DEVICES  
Only the 559F300 unit is equipped with a 70-watt crankcase  
heater to prevent absorption of liquid refrigerant by oil in the  
crankcase when the compressor is idle. The crankcase heater  
is energized whenever there is a main power to the unit and  
the compressor is not energized.  
All units have relief devices to protect against damage from  
excessive pressures (e.g., fire). These devices protect the high  
and low side.  
XIII. CONTROL CIRCUIT, 24-V  
IMPORTANT: After prolonged shutdown or servicing, ener-  
gize the crankcase heaters for 24 hours before starting the  
compressors.  
This control circuit is protected against overcurrent by a  
3.2-amp circuit breaker. Breaker can be reset. If it trips, de-  
termine cause of trouble before resetting.  
Compressor Lockout  
XIV. REPLACEMENT PARTS  
If any of the safeties (high-pressure, low-pressure, freeze pro-  
tection thermostat, compressor internal thermostat) trip, or  
if there is loss of power to the compressors, the CLO (com-  
pressor lockout) will lock the compressors off. To reset, manu-  
ally move the thermostat setting.  
A complete list of replacement parts may be obtained from  
any Carrier distributor upon request.  
—24—  
TROUBLESHOOTING  
Refer to Table 13 for troubleshooting details.  
Table 13 — Cooling Service Analysis  
CAUSE  
PROBLEM  
REMEDY  
Compressor and  
condenser fan  
will not start.  
Power failure.  
Call power company.  
Fuse blown or circuit breaker tripped.  
Replace fuse or reset circuit breaker.  
Replace component.  
Defective thermostat, contactor, transformer, or control  
relay.  
Insufficient line voltage.  
Determine cause and correct.  
Incorrect or faulty wiring.  
Check wiring diagram and rewire correctly.  
Lower thermostat setting below room temperature.  
Check wiring and repair or replace.  
Thermostat setting too high.  
Compressor will not start  
but condenser fan runs.  
Faulty wiring or loose connections in compressor circuit.  
Compressor motor burned out, seized, or internal  
overload open.  
Determine cause. Replace compressor.  
Defective overload.  
Determine cause and replace.  
Compressor locked out.  
One leg of 3-phase power dead.  
Determine cause for safety trip and reset lockout.  
Replace fuse or reset circuit breaker.  
Determine cause.  
Compressor cycles  
(other than normally  
satisfying thermostat).  
Refrigerant overcharge or undercharge.  
Recover refrigerant, evacuate system, and recharge  
to nameplate.  
Defective compressor.  
Insufficient line voltage.  
Blocked condenser.  
Replace and determine cause.  
Determine cause and correct.  
Determine cause and correct.  
Determine cause and replace.  
Replace thermostat.  
Defective overload.  
Defective thermostat.  
Faulty condenser-fan motor.  
Restriction in refrigerant system.  
Dirty air filter.  
Replace.  
Locate restriction and remove.  
Replace filter.  
Compressor operates  
continuously.  
Unit undersized for load.  
Thermostat set too low.  
Low refrigerant charge.  
Air in system.  
Decrease load or increase unit size.  
Reset thermostat.  
Locate leak, repair, and recharge.  
Recover refrigerant, evacuate system, and recharge.  
Clean coil or remove restriction.  
Replace filter.  
Condenser coil dirty or restricted.  
Dirty air filter.  
Excessive head pressure.  
Dirty condenser coil.  
Refrigerant overcharged.  
Faulty TXV.  
Clean coil.  
Recover excess refrigerant.  
1. Check TXV bulb mounting and secure tightly to  
suction line.  
2. Replace TXV if stuck open or closed.  
Air in system.  
Recover refrigerant, evacuate system, and recharge.  
Determine cause and correct.  
Condenser air restricted or air short-cycling.  
Low refrigerant charge.  
Restriction in liquid tube.  
High heat load.  
Head pressure too low.  
Check for leaks, repair, and recharge.  
Remove restriction.  
Excessive suction  
pressure.  
Check for source and eliminate.  
Faulty TXV.  
1. Check TXV bulb mounting and secure tightly to  
suction line.  
2. Replace TXV if stuck open or closed.  
Refrigerant overcharged.  
Dirty air filter.  
Recover excess refrigerant.  
Replace filter.  
Suction pressure too low.  
Low refrigerant charge.  
Metering device or low side restricted.  
Faulty TXV.  
Check for leaks, repair, and recharge.  
Remove source of restriction.  
1. Check TXV bulb mounting and secure tightly to  
suction line.  
2. Replace TXV if stuck open or closed.  
Insufficient evaporator airflow.  
Increase air quantity. Check filter and replace if  
necessary.  
Temperature too low in conditioned area.  
Field-installed filter drier restricted.  
Unit in economizer mode.  
Reset thermostat.  
Replace.  
Compressor no. 2  
will not run.  
Proper operation; no remedy necessary.  
—25—  
Fig. 31 — Typical Wiring Schematic (559F180, 460-v Shown)  
—26—  
Fig. 31 — Typical Wiring Schematic (559F180, 460-v Shown) (cont)  
LEGEND AND NOTES FOR FIG. 31 AND 32  
AHA  
BKR W/AT  
C
Adjustable Heat Anticipator  
Breaks with Amp Turns  
Contactor, Compressor  
Capacitor  
IFC  
IFCB  
IFM  
IFR  
L
LOR  
LPS  
LS  
Indoor-Fan Contactor  
Indoor-Fan Circuit Breaker  
Indoor-Fan Motor  
Indoor-Fan Relay  
Light  
TH  
TRAN  
Thermostat Heating  
Transformer  
Terminal (Marked)  
CAP  
CB  
Terminal (Unmarked)  
Terminal Block  
Splice  
Circuit Breaker  
CC  
Cooling Compensator  
Compressor Lockout  
Compressor Lockout Switch  
Compressor Motor  
Current Transformer  
Damper Motor  
Dummy Terminal  
Equipment  
Fuse Link  
Freeze Protection Thermostat  
Fuse  
Ground  
Heater Contactor  
High-Pressure Switch  
Heater  
Lockout Relay  
CLO  
CLS  
COMP  
CT  
Low-Pressure Switch  
Limit Switch  
MAT  
OAT  
OFC  
OFM  
OP  
Mixed-Air Thermostat  
Outdoor-Air Thermostat  
Outdoor-Fan Contactor  
Outdoor-Fan Motor  
Overcurrent Protector  
Plug Assembly  
DM  
DU  
Factory Wiring  
Field Wiring  
EQUIP  
FL  
PL  
To Indicate Common  
Potential Only, Not  
To Represent Wiring  
FPT  
FU  
PRI  
QT  
Primary  
Quadruple Terminal  
Solenoid Relay  
GND  
HC  
SR  
SW  
TB  
Switch  
Option/Accessory Wiring  
HPS  
HTR  
Terminal Block  
TC  
Thermostat Cooling  
NOTES:  
1. Compressor and fan motors thermally protected; 3-phase motors protected against  
primary single-phasing conditions.  
2. If any of the original wire furnished must be replaced, it must be replaced with  
type 90 C wire or its equivalent.  
3. Jumpers are omitted when unit is equipped with economizer.  
4. The CLO locks out the compressor to prevent short cycling on compressor over-  
load and safety devices. Before replacing CLO, check these devices.  
5. Number(s) indicates the line location of used contacts. A bracket over (2) num-  
bers signifies a single-pole, double-throw contact. An underlined number sig-  
nifies a normally-closed contact. A plain (no line) number signifies a normally-  
open contact.  
—27—  
Fig. 32 — Typical Component Arrangement (559F180 Shown)  
—28—  
SERVICE TRAINING  
P a ck a ged Ser vice Tr a in in g programs are an excellent way to increase your knowledge of the  
equipment discussed in this manual, including:  
Unit Familiarization  
Installation Overview  
Maintenance  
Operating Sequence  
A large selection of product, theory, and skills programs are available, using popular video-based  
formats and materials. All include video and/or slides, plus companion book.  
Cla ssr oom Ser vice Tr a in in g which includes hands-on experience with the products in our labs  
can mean increased confidence that really pays dividends in faster troubleshooting and fewer call-  
backs. Course descriptions and schedules are in our catalog.  
CALL F OR F REE CATALOG 1-800-962-9212  
[
] Packaged Service Training  
[
] Classroom Service Training  
Copyright 1998 Bryant Heating & Cooling Systems  
CATALOG NO. 5355-900  
START-UP CHECKLIST  
MODEL NO.:  
DATE:  
SERIAL NO.:  
TECHNICIAN:  
I. PRE-START-UP:  
VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT  
VERIFY INSTALLATION OF INDOOR FAN MOTOR ADJ USTMENT BOLT (180 UNITS) OR ADJ USTMENT  
BOLT AND PLATE (216-300 UNITS)  
OPEN ALL SERVICE VALVES (SUCTION, DISCHARGE, AND LIQUID)  
VERIFY INSTALLATION OF ECONOMIZER HOOD  
VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTRUCTIONS  
VERIFY THAT ALL ELECTRICAL CONNECTIONS AND TERMINALS ARE TIGHT  
CHECK THAT INDOOR-AIR FILTER IS CLEAN AND IN PLACE  
VERIFY THAT UNIT IS LEVEL  
CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE, AND VERIFY SET SCREW  
IS TIGHT  
VERIFY THAT FAN SHEAVES ARE ALIGNED AND BELTS ARE PROPERLY TENSIONED  
VERIFY THAT SCROLL COMPRESSOR IS ROTATING IN THE CORRECT DIRECTION  
II. START-UP:  
ELECTRICAL  
SUPPLY VOLTAGE  
L1-L2  
L2-L3  
L3-L1  
COMPRESSOR AMPS — COMPRESSOR NO. 1  
— COMPRESSOR NO. 2  
L1  
L1  
L2  
L2  
L3  
L3  
SUPPLY FAN AMPS  
EXHAUST FAN AMPS  
L1 L2  
ELECTRIC HEAT AMPS (IF SO EQUIPPED)  
L3  
TEMPERATURES  
OUTDOOR-AIR TEMPERATURE  
RETURN-AIR TEMPERATURE  
COOLING SUPPLY AIR  
F
DB (Dry-Bulb)  
DB  
F
F
WB (Wet-Bulb)  
F
ELECTRIC HEAT SUPPLY AIR (IF SO EQUIPPED)  
F
PRESSURES  
REFRIGERANT SUCTION  
CIRCUIT NO. 1  
CIRCUIT NO. 1  
PSIG  
PSIG  
CIRCUIT NO. 2 (216-300 ONLY)  
CIRCUIT NO. 2 (216-300 ONLY)  
PSIG  
PSIG  
REFRIGERANT DISCHARGE  
VERIFY REFRIGERANT CHARGE USING CHARGING CHART ON PAGE 24  
GENERAL  
ECONOMIZER MINIMUM VENT AND CHANGEOVER SETTINGS TO J OB REQUIREMENTS  
VERIFY INSTALLATION OF ALL OPTIONS AND ACCESSORIES  
Copyright 1998 Bryant Heating & Cooling Systems  
CATALOG NO. 5355-900  
CL-1  

Carrier 48EW User Manual
Cornelius Drop In and Free Standing Ice Cooled Dispensers User Manual
Datalogic Scanning GRYPHONTM DX30 User Manual
Epson Printer FX 2190 IN OKIDATAMODE User Manual
Friedrich SL 24 User Manual
Groupe SEB USA T FAL VEILLE BB User Manual
HandHeld Entertainment Barcode Reader 4600RP User Manual
Honda Automobiles 08V03 S9A 101 User Manual
Honeywell HERCULINE 2000 User Manual
HP Hewlett Packard D411 User Manual