ADTRAN Battery Backup Unit L4 User Manual

JOBAID  
PRICING AND AVAILABILITY 800.827.0887  
TECHNICAL SUPPORT 888.4ADTRAN  
RETURN FOR REPAIR 256.963.8722  
BATTERY BACKUP UNIT (L4)  
61175044L4-22A  
Wallmount instructions (cont’d)  
4. Remove the two closure screws on the battery box and open the cover.  
5. Use a long shaft screwdriver to tighten the three support screws.  
6. Make the connections to your ADTRAN product. (Refer to the documentation provided  
with your ADTRAN system for detailed instructions on making the connections.)  
BATTERY BACKUP  
UNIT  
CAUTION  
This equipment MUST only be installed in a DC-C bonding and  
grounding environment per Telcordia GR-1089-CORE, Issue 3. It  
may not be utilized in a DC-I (isolated) bonding and grounding  
environment.  
ckup  
Battery Ba  
1175044L4  
GROUNDING  
SAFETY INFORMATION  
18 AWG or larger ground wire is recommended to connect an additional ground conductor  
to “ground bus” in the customer equipment room.  
When using your telephone equipment, please follow these basic safety  
precautions to reduce the risk of fire, electrical shock, or personal injury:  
WARRANTY  
1. Do not use this product near water, such as a bathtub, wash bowl, kitchen  
sink, laundry tub, in a wet basement, or near a swimming pool.  
2. Avoid using a telephone (other than a cordless-type) during an electrical  
storm. There is a remote risk of shock from lightning.  
3. Do not use the telephone to report a gas leak in the vicinity of the leak.  
4. Use only the power cord, power supply, and/or batteries indicated in the  
manual. Do not dispose of batteries in a fire; they may explode. Check with  
local codes for special disposal instructions.  
Warranty for Carrier Network products manufactured by ADTRAN and supplied under Buyer's  
order for use in the U.S. is ten (10) years except batteries which carry a manufacturer’s warranty  
of one year. For a complete copy of ADTRAN's U.S. Carrier Networks Equipment Warranty, dial  
(877) 457-5007 and request Document 414.  
COMPLIANCE CODES  
Code  
PC  
Input  
Output  
F
X
E
C
X
TC  
MOUNTING INSTRUCTIONS  
IC  
CAUTION  
Electronic equipment can be damaged by static electrical discharge.  
Before handling equipment, wear an antistatic discharge wrist strap  
to prevent damage to electronic components. Place equipment in  
antistatic packing material when transporting or storing. When  
working on equipment, always place them on an approved antistatic  
mat that is electronically grounded.  
MAINTENANCE  
Life expectancy: 3-5 years of standby use.  
Battery performance is adversely affected by extreme temperatures.  
Old batteries should be recycled. Reference ADTRAN document 60000120-36A for more  
information.  
BATTERY SPECIFICATIONS  
Unpack the Backup system and inspect for damage. If damage is apparent, refer  
to your carrier or supplier for remedy. It is not necessary to remove the batteries  
during installation.  
1
2
Part Number: 311212V02  
Suppliers: YUASA and PANASONIC  
Batteries: 7 Amp/ hr  
Battery type: Lead acid  
DC Output: -54 VDC, 60 W (average), 100 W  
Backup Time: Up to 8 hours  
Battery Charging: 16 hr nominal, 24 hr maximum  
Wire Gauge: 18 AWG  
Preferred Temperature: 68º F (20º C)  
CAUTION  
Fully loaded Battery Box weighs 30 lbs.  
Wall mount the battery box with the following minimum clearances:  
Top - 9”  
Left Side - 1”  
Right Side - 5”  
Bottom - 3”  
The device complies with Part 15 of the FCC rules. Operation is subject to the following  
two conditions: (1) This device may not cause harmful interference, and (2) this device  
must accept any interference received, including interference that may cause undesired  
operation.  
1. Using the template provided (61175044L4-19), mark and drill three pilot  
holes using a size I (0.228” diameter) drill bit.  
2. Insert 1/4” x 3/4” flat-head wood screws (supplied) into the three pilot holes,  
leaving 1/8” to 3/16” space between the screw head and the backboard.  
3. With an assistant, mount the battery box on the three support screws on the  
backboard.  
C A U T I O N !  
SUBJECT TO ELECTROSTATIC DAMAGE  
OR DECREASE IN RELIABILITY.  
Changes or modifications not expressly approved by ADTRAN could void the user's  
authority to operate this equipment.  
HANDLING PRECAUTIONS REQUIRED.  
JOBAid, 61175044L4-22A, January 2004  
Technical Support 1-888-4ADTRAN (1-888-423-8726)  
2004 ADTRAN, All Rights Reserved  

Briggs Stratton AIR CLEANER 286700 User Manual
Canon Wireless Photo All In One 8333B002 User Manual
Cornelius QUANTUM SERIES User Manual
Delfield Shelleymatic NDF User Manual
Epson Printer CX11N User Manual
Ford TSB 05 4 12 User Manual
Friedrich PE12K__B User Manual
GE General Electric Air Conditioner AS_14 User Manual
Haier HSU 119M07 User Manual
Harbor Freight Tools HaulMaster 1 Ton CHAIN HOIST 996 User Manual