rev. 0508
Plumbing
Waste outlet and P-traP
3. Always provide as much down hill slope (“fall”) as
possible; 1/8” per foot is the preferred minimum.
PVC pipe, when used, must be supported to
maintain the 1/8” pitch and to prevent warping.
4. Avoid long runs of condensate drains. Long runs
make it impossible to provide the “fall” necessary for
good drainage.
5. Provide a suitable air break between the flood rim of
the floor drain and outlet of condensate drain. 1” is
ideal.
6. Prevent condensate drains from freezing:
a. Do not install condensate drains in contact with
non-insulated suction lines. Suction lines should
be insulated with a non-absorbent insulation
material such asArmstrong’sArmaflex.
b. Where condensate drains are located in dead
air spaces (between refrigerators or between a
refrigerator and a wall), provide means to prevent
freezing. The water seal should be insulated to
prevent condensation.
The waste outlet is located at the left hand end of these
fixtures allowing drip piping to be run under the fixture
lengthwise.
A1” P-TRAP and threaded adapter are supplied with each
fixture. The P-TRAPmust be installed to prevent air leakage
and insect entrance into the fixture.
installing Condensate drain
Poorly or improperly installed condensate drains can
seriously interfere with the operation of this refrigerator, and
result in costly maintenance and product losses. Please
follow the recommendations listed below when installing
condensate drains to insure a proper installation:
1. Never use pipe for condensate drains smaller
than the nominal diameter of the pipe or P-TRAP
supplied with the case.
ꢀ. When connecting condensate drains, the P-TRAP
must be used as part of the condensate drain
to prevent air leakage or insect entrance. Store
plumbing system floor drains should be at least 14”
off the center of the case to allow use of the P-TRAP
pipe section. Never use two water seals in series in
any one line. Double P-TRAPS in series will cause a
lock and prevent draining.
refrigeration
refrigerant type
Control settings - remote
The standard refrigerant will be R-404 unless otherwise
specified on the customer order. Check the serial plate on
the case for information.
See FMSS-L technical data sheet for the appropriate
settings for your merchandiser. Maintain these parameters
to achieve near constant product temperatures. Product
temperature should be measured first thing in the morning,
after having been refrigerated overnight. Defrost times
should be as directed in the FMSS-L technical data sheet.
The number of defrosts per day should never change.
The duration of the defrost cycle may be adjusted to meet
conditions present at your location.
Piping for more than one case on a condensing unit is run
underground with either common suction and liquid lines
from the machine room or individual suction and liquid lines
joined together in the machine room.
refrigeration lines
Liquid
Suction
Control settings - self Contained
3/8” O.D.
5/8” O.D.
On Self Contained cases all functions, defrost, fans,
temperature are controlled by Pagon ERC-ꢀ controller. See
case specs for proper temperature and defrost settings.
5
8
note: the standard coil is piped at / ” (suction); however,
the store tie-in may vary depending on the number of
coils and the draw the case has. depending on the case
access to tX valves and drain lines
5
7
8
8
setup, the connecting point in the store may be / ”, / ”,
1
Mechanical - Remove product from end of case. Remove
product racks. Remove refrigeration and drain access
panels (labeled). TX valve (mechanical only) and drain are
located under each access panel at end of the case.
8
or 1 / ”. refer to the particular case you are hooking up.
Refrigerant lines should be sized as shown on the
refrigeration legend furnished by the store.
Install P-traPs (oil traps) at the base of all suction line
electronic - The Electronic Expansion valve master and
slave cylinder(s) are located within the electrical access
panel(s).
vertical risers.
Pressure drop can rob the system of capacity. To keep the
pressure drop to a minimum, keep refrigerant line run as
short as possible, using the minimum number of elbows.
Where elbows are required, use long radius elbows only.
electronic expansion valve (optional)
A wide variety of electronic expansion valves and case
controllers can be utilized. Please refer to EEV and
controller manufacturers information sheet. Sensors for
electronic expansion valves will be installed on the coil inlet,
coil outlet, and in the discharge air. (Some supermarkets
require a 4th sensor in the return air). Case controllers will
be located in the electrical raceway or under the case.
for refrigerators with Koolgas defrost, suction, and
liquid lines should not contact each other and should
be insulated for a minimum of 30’from the refrigerator.
additional insulation for the balance of liquid and
suction lines is recommended and required wherever
condensation and dripping would be objectionable.
5
Download from Www.Somanuals.com. All Manuals Search And Download.