Hubbell Switch LXi 2300 User Manual

Hubbell Industrial Controls, Inc.  
Electric Fire Pump Controllers  
Specifications for LXi 2300 Controllers * Auto-transformer Starting With Transfer Switch * July 2002  
The fire pump controller shall be factory assembled, wired, and tested as a unit assembly, shall conform to the requirements of the latest  
editions of NFPA-20 and NFPA-70, and shall be Listed/Approved by and bear the label of UL/FM. The controller shall be Hubbell-  
Lexington LXi 2300 equipped with LXi logic.  
The controller shall be of the combined manual/automatic type and be furnished in a floor mounted drip-proof steel Type 2 enclosure with  
lifting eyes. The enclosure shall be red with a non-glare surface. The controller shall be for auto-transformer starting and designed, tested,  
and marked for the rated horsepower and 3-phase voltage and frequency in a 40 degree C. ambient. Taps on the transformer shall allow  
voltages of 50, 65, or 80% to be applied for reduced current, closed-transition starting.  
All electrical components shall be accessible from the front for maintenance and service. No components or component wiring shall be  
permitted on the door of the enclosure. The controller shall have a common operating handle for both the line isolating switch and the  
controller circuit breaker mounted in the enclosure flange. The minimum withstand rating for the fire pump controller shall be 150,000  
amps RMS symmetrical at 200-600volts. The unit shall be Listed/Approved with UL/FM as “Suitable For Use As Service Equipment”.  
The controller shall have separate and independent pressure settings with minimum run timing capable of a setting of 10 minutes.  
Settings of the pressures shall be established at the time of the field acceptance test. Provisions shall be included to allow manual or  
automatic shut-down in the field.  
The controller shall have two sets of Form “C” contacts for Pump Running, Phase Reversal, Power/Phase Failure, and one set of Form  
“C” contacts for Trouble. The Trouble contacts shall be activated by the following conditions: Invalid Configuration Memory,  
Emergency Manual Start, Pump Running, Phase Failure, Phase Reversal, Overload, Locked Rotor, Fail-to-Start, and Lockout.  
The controller shall be equipped with LXi intelligent fire pump control system logic. All firmware shall be non-volatile flash based CPLD  
( complex-programmable logic device). The boot-up time for the logic shall be 3 seconds or less. Controllers that do not boot-up and  
allow the pump to be started in 3 seconds or less are not acceptable. An RS232 serial port shall be supplied for downloading event history  
to a PC for analysis and printing.  
The digital pressure readings and settings shall be displayed on the LXi LCD mounted on the enclosure flange. The LCD screen shall be 4  
x 20 (4 lines of 20 characters) per screen, and the screens may be scrolled to give a total of 320 characters. The real time display shall give  
simultaneous 3-phase digital amps and volts for the pump power, and digital display for the system pressure. Controllers that do not  
simultaneously display digital 3-phase amps, line-to-line volt readings, and system pressure, are not acceptable.  
The event alarm caches shall be compartmentalized, and no compartment shall over-ride any other compartment. The compartments  
allow for analysis of four types of information events without having to look through all events including those not related to a problem.  
Events shall be shown with Date and Time for each event occurrence:  
1.  
2.  
3.  
4.  
Events that have occurred during a pump idle period  
Events that occurred during the last start period  
Events that occurred during the last run period  
Events that occurred during the last stop period.  
The LED displays shall be mounted on the enclosure flange and have an LED for the following, with provisions for three spare LED’s to  
be available and programmable for other options or event displays.  
Power Available  
Phase Reversal  
Pump Running  
Pressure Switch Start  
Local Manual Stop  
Fail to Start  
Run Timer On  
Locked Rotor  
Local Manual Start  
Start Timer/Accelerate  
Lockout On  
Pump Start Delay On  
Overload  
Low Suction  
Shorted SCR  
Overtemp SCR  
Emergency Manual Start  
Remote Start  
The LED displays shall be mounted on the enclosure flange and have an LED for the following:  
Programming of the LXi logic shall be from the touch pad mounted on the enclosure flange. Programming shall be password protected so  
that only authorized personnel can change the logic functions. The fire pump controller shall be Model LXi 2300 equipped with LXi Logic  
as manufactured by Hubbell Industrial Controls, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Haier Clothes Dryer HDM80 61 User Manual
Haier Flat Panel Television LS42T3 User Manual
Harbor Freight Tools Stereo System 97563 User Manual
Hotpoint Washer Dryer AQXXF 149 PI User Manual
HP Hewlett Packard Computer Hardware sx2000 User Manual
HP Hewlett Packard Laptop 1100 User Manual
Hubbell Work Light S 21 User Manual
Husqvarna Snow Blower 125B User Manual
Hypertec Carrying Case 3101 User Manual
iHome Clock Radio iH12 User Manual