Hubbell Switch LXi 2100 User Manual

Hubbell Industrial Controls, Inc.  
Electric Fire Pump Controllers  
Specifications for LXi 2100 Controllers * Solid State Soft-Start/Stop With Transfer Switch * July 2002  
The fire pump controller shall be factory assembled, wired, and tested as a unit assembly, shall conform to the requirements of the latest  
editions of NFPA-20 and NFPA-70, and shall be Listed/Approved by and bear the label of UL/FM. The controller shall be Hubbell-  
Lexington LXi 2100 equipped with LXi logic.  
The controller shall be of the combined manual/automatic type and be furnished in a floor mounted drip-proof steel Type 2 enclosure with  
lifting eyes. The enclosure shall be red with a non-glare surface. The controller shall be for solid state soft start/stop and designed, tested,  
and marked for the rated horsepower and 3-phase voltage and frequency in a 40 degree C. ambient.  
The soft-start controller shall include a full-wave three-phase controlled, open loop starting assembly consisting of control logic and a  
separate three-phase full-wave (anti-parallel) SCR thermistor assembly. The control logic shall be conformal coated and carry a 5 year  
warranty. Circuit adjustments and LED indicators shall be in the front of the control logic for accessibility and indicating.  
The SCR controller shall be designed and rated to carry locked rotor current (600% of FLA) for 20 seconds as required by NFPA 20.  
SCR’s rated for 500% for 10 seconds shall not be acceptable. The SCR’s utilized in the thermistor assembly shall have a minimum 1200  
volt PIV rating and Dv/Dt protection including 100 joule minimum MOV’s per phase.  
The solid-state starter shall supply a reduced voltage which will increase to full voltage along an acceleration ramp, adjustable between  
0.5 and 10 seconds. The controller shall include a motor contactor bypass for the SCR unit when full-voltage has been reached, or in the  
event of overheating of the SCR unit.  
For normal stopping situations the controller shall initiate a stop sequence through the solid-state unit. The starter shall decrease the  
voltage applied to the motor via an adjustable deceleration ramp (between 0.5 and 10 seconds) to a preset adjustable voltage level. The  
starter shall hold at this voltage level for an adjustable time period between 3 and 60 seconds to monitor for another starting cause. The  
deceleration/minimum speed hold feature of the controller shall provide reduced hydro-mechanical stress in the system piping. If no new  
starting cause occurs during the deceleration/minimum speed period the controller will decelerate the fire pump to a full stop. The “Soft  
Stop” pushbutton shall cause the controller to initiate the same stop sequence through the solid-state starter. The “Emergency Stop” push  
button shall cause the controller to bypass the solid-state starter deceleration and stop immediately.  
The soft-start module shall be provided with the following indicating diagnostics :  
Power Available  
Acceleration  
Deceleration  
Green LED  
Yellow LED  
Yellow LED  
Blue LED  
Controller Initiate  
Run  
Minimum Speed  
Shorted SCR  
Blue LED  
Yellow LED  
Yellow LED  
Red LED  
Emergency Stop  
All electrical components shall be accessible from the front for maintenance and service. No components or component wiring shall be  
permitted on the door of the enclosure. The controller shall have a common operating handle for both the line isolating switch and the  
controller circuit breaker mounted in the enclosure flange. The minimum withstand rating for the fire pump controller shall be 150,000  
amps RMS symmetrical at 200-600volts. The unit shall be Listed/Approved with UL/FM as “Suitable For Use As Service Equipment”.  
The controller shall have separate and independent pressure settings with minimum run timing capable of a setting of 10 minutes.  
Settings of the pressures shall be established at the time of the field acceptance test. Provisions shall be included to allow manual or  
automatic shut-down in the field.  
The controller shall have two sets of Form “C” contacts for Pump Running, Phase Reversal, Power/Phase Failure, and one set of Form  
“C” contacts for Trouble. The Trouble contacts shall be activated by the following conditions: Invalid Configuration Memory,  
Emergency Manual Start, Pump Running, Phase Failure, Phase Reversal, Overload, Locked Rotor, Fail-to-Start, and Lockout.  
The controller shall be equipped with LXi intelligent fire pump control system logic. All firmware shall be non-volatile flash based CPLD  
( complex-programmable logic device). The boot-up time for the logic shall be 3 seconds or less. Controllers that do not boot-up and  
allow the pump to be started in 3 seconds or less are not acceptable. An RS232 serial port shall be supplied for downloading event history  
to a PC for analysis and printing.  
The digital pressure readings and settings shall be displayed on the LXi LCD mounted on the enclosure flange. The LCD screen shall be 4  
x 20 (4 lines of 20 characters) per screen, and the screens may be scrolled to give a total of 320 characters. The real time display shall give  
simultaneous 3-phase digital amps and volts for the pump power, and digital display for the system pressure. Controllers that do not  
simultaneously display digital 3-phase amps, line-to-line volt readings, and system pressure, are not acceptable.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graco Crib Toy 1857155 User Manual
Grandstream Networks Network Card HandyTone 496 User Manual
Grundig Flat Panel Television 32 VLD 8130 SL User Manual
Hamilton Beach Humidifier 840117800 User Manual
Harbor Freight Tools Automobile Accessories 95409 User Manual
Harbor Freight Tools Utility Trailer 2575 User Manual
Havis Shields Automobile Accessories KK ST FLIP User Manual
Hearth and Home Technologies Outdoor Fireplace Montana 36 User Manual
Hypertec Carrying Case TANCD2HY User Manual
IBM Computer Monitor 6736 HB0 User Manual