Honeywell Universal Remote PUB1012S User Manual

Spyder® BACnet®  
Programmable Controllers  
PRODUCT DATA  
The Spyder BACnet controllers require the Spyder BACnet  
Programmable Feature to be licensed in the WEBpro  
workbench tool and the WEBS AX JACE Controller for  
programming and downloading. The Spyder BACnet Models  
are also available as Individually Licensed Controllers (ILC).  
The ILC versions are identical in design and capability in every  
detail except for the licensing. The Individual Licensing of the  
Spyder ILCs (the License is built in) allows them to be  
programmed and downloaded with any brand of the Niagara  
Workbench or JACE controller. The Spyder ILCs are identified  
with a suffix on the Part Number of -ILC. Example:  
PUB6438S-ILC follows all the same Installation Instructions  
information as the PUB6438S.  
These controllers are for use in VAV (Variable Air Volume),  
Unitary and advanced HVAC control applications. Each  
controller has flexible, universal inputs for external sensors,  
digital inputs, and a combination of analog and digital Triac  
outputs. All the models are described in Table 1. The photo to  
the left is the model PVB6436AS, which includes the actuator.  
PRODUCT DESCRIPTION  
The PUB and PVB controllers are part of the Spyder family.  
These controllers are BACnet MS/TP network devices  
designed to control HVAC equipment. These controllers  
provide many options and advanced system features that  
allow state-of-the-art commercial building control. Each  
controller is programmable and configurable through software.  
Table 1. Controller configurations.  
Velocity  
Pressure  
Universal  
Inputs  
(UI)  
Digital  
Inputs  
(DI)  
Analog  
Outputs  
(AO)  
Digital  
Outputs  
(DO)  
Series 60  
Floating  
Actuator  
Controller  
Model  
Programmable  
Type  
Sensor  
(Microbridge)  
PUB1012S  
PUB4024S  
PUB6438S  
PVB0000AS  
PVB4022AS  
PVB4024NS  
PVB6436AS  
PVB6438NS  
Unitary  
Unitary  
Unitary  
VAV  
1
4
6
0
4
4
6
6
0
0
4
0
0
0
4
4
1
2
3
0
2
2
3
3
2
4
8
0
2
4
6
8
NO  
NO  
NO  
NO  
NO  
NO  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
NO  
VAV  
VAV  
VAV  
YES  
NO  
VAV  
Each controller communicates via an EIA-485 BACnet MS/TP communications network, capable of baud rates between 9.6 and  
115.2 kbits/s.  
Controllers are field-mountable to either a panel or a DIN rail.  
63-2689-05  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS  
For the PVB6436AS model, the actuator is mounted first and  
then the controller is mounted. For the other models, go to  
“Mount Controller” on page 5 to begin the installation.  
Input  
Type  
Sensor  
Type  
Operating  
Range  
TR23  
Setpoint  
Potentiometer 10,500 Ohm  
500 Ohm  
to  
-4° DDC to +4° DDC  
(-8° DDF to +7° DDF)  
or  
50 F to 90 F  
(10 C to 32 C)  
Mount Actuator onto Damper Shaft  
(PVB0000AS, PVB4022AS and  
PVB6436AS)  
PVB0000AS, PVB4022AS and PVB6436AS controllers include  
the direct-coupled actuator with Declutch mechanism, which is  
shipped hard-wired to the controller.  
Resistive Input Generic  
100 Ohms to 100K Ohms  
0–10 Vdc  
Voltage  
Input  
Transducer,  
Controller  
Discrete Input Dry Contact  
closure  
Open Circuit > 3000 Ohms  
Closed Circuit < 3000 Ohms  
The actuator mounts directly onto the VAV box damper shaft  
and has up to 44 lb-in. (5 Nm) torque, 90-degree stroke, and 90  
second timing at 60 Hz. The actuator is suitable for mounting  
onto a 3/8 to 1/2 in. (10 to 13 mm) square or round VAV box  
damper shaft. The minimum VAV box damper shaft length is 1-  
9/16 in. (40 mm).  
a
C7031G and C7041F are recommended for use with these  
controllers, due to improved resolution and accuracy when  
compared to the PT1000.  
The two mechanical end-limit set screws control the amount of  
rotation from 12° to 95°. These set screws must be securely  
fastened in place. To ensure tight closing of the damper, the  
shaft adapter has a total rotation stroke of 95° (see Fig. 1).  
BEFORE INSTALLATION  
The controller is available in three models (see Table 1).  
Review the power, input, and output specifications on page 2  
before installing the controller.  
— Hardware driven by Triac outputs must have a minimum  
current draw, when energized, of 25 mA and a maximum  
current draw of 500 mA.  
— Hardware driven by the analog current outputs must have a  
maximum resistance of 550 Ohms, resulting in a maximum  
voltage of 11 volts when driven at 20 mA.  
NOTES:  
1.  
The actuator is shipped with the mechanical end-  
limit set screws set to 95 degrees of rotation.  
Adjust the two set screws closer together to  
reduce the rotation travel. Each “hash mark” indi-  
cator on the bracket represents approximately 6.5°  
of rotation per side.  
2.  
The Declutch button, when pressed, allows you to  
rotate the universal shaft adapter (see Fig. 1).  
If resistance exceeds 550 Ohms, voltages up to 18 Vdc are  
possible at the analog output terminal.  
IMPORTANT  
Determine the damper rotation and opening angle  
WARNING  
prior to installation. See Fig. 2 below and Fig. 3 on  
page 4 for examples.  
Electrical Shock Hazard.  
Can cause severe injury, death or property damage.  
Disconnect power supply before beginning wiring or  
making wiring connections to prevent electrical shock  
or equipment damage.  
UNIVERSAL SHAFT  
CLAMPING BOLTS (2)  
UNIVERSAL  
SHAFT ADAPTER  
INSTALLATION  
The controller must be mounted in a position that allows  
clearance for wiring, servicing, removal, connection of the  
BACnet MS/TP Molex connector and access to the MS/TP  
MAC address DIP switches (see Fig. 15 on page 12).  
MECHANICAL  
END LIMIT SET  
SCREWS (2)  
The controller may be mounted in any orientation.  
DECLUTCH  
BUTTON  
IMPORTANT  
Avoid mounting in areas where acid fumes or other  
deteriorating vapors can attack the metal parts of the  
controller, or in areas where escaping gas or other  
explosive vapors are present. Fig. 6–Fig. 7 on page 5  
for mounting dimensions.  
M23568  
Fig. 1. Series 60 Floating Actuator.  
3
63-2689—05  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS  
Mounting Actuator Onto Damper Shaft  
(PVB0000AS, PVB4022AS and PVB6436AS)  
DAMPER  
The unit is shipped with the actuator set to rotate open in the  
clockwise (CW) direction to a full 95 degrees. The extra 5  
degrees ensures a full opening range for a 90 degree damper.  
The installation procedure varies depending on the damper  
opening direction and angle:  
1. If the damper rotates clockwise (CW) to open, and the  
angle of the damper open-to-closed is 90 degrees:  
a. Manually open the damper fully (rotate clockwise).  
b. Using the Declutch button, rotate the universal shaft  
adapter fully clockwise.  
c. Mount the actuator to the VAV damper box and shaft.  
d. Tighten the two bolts on the centering clamp  
(8 mm wrench; 70.8–88.5 lb-in. [8–10 Nm] torque).  
When the actuator closes, the damper rotates CCW  
90 degrees to fully close.  
DAMPER SHAFT  
ROTATES  
CLOCKWISE  
TO OPEN  
M23569  
2. If the damper rotates clockwise (CW) to open, and the  
angle of the damper open-to-closed is 45 or 60 degrees:  
a. Manually open the damper fully (rotate clockwise).  
b. The actuator is shipped with the mechanical  
end-limits set at 95 degrees. Adjust the two  
mechanical end-limit set screws to provide the  
desired amount of rotation. Adjust the two set screws  
closer together to reduce the rotation travel.  
c. Tighten the two mechanical end-limit screws (Phillips  
#2 screwdriver; (26.5–31 lb-in. [3.0–3.5 Nm] torque).  
d. Using the Declutch button, rotate the universal shaft  
adapter fully clockwise.  
Fig. 2. Damper with 90 degree CW rotation to open.  
IMPORTANT  
Mount actuator flush with damper housing or add a  
spacer between the actuator mounting surface and  
damper box housing.  
Before Mounting Actuator onto Damper  
Shaft (PVB0000AS, PVB4022AS and  
PVB6436AS)  
e. Mount the actuator to the VAV damper box and shaft.  
f. Tighten the two bolts on the centering clamp  
(8 mm wrench; 70.8–88.5 lb-in. [8–10 Nm] torque).  
g. When the actuator closes, the damper rotates CCW  
either 45 or 60 degrees to fully close.  
Tools required:  
— Phillips #2 screwdriver - end-limit set screw adjustment  
— 8 mm wrench - centering clamp  
3. If the damper rotates counterclockwise (CCW) to open, and  
the angle of the damper open-to-closed is 90 degrees:  
a. Manually open the damper fully (rotate counterclock-  
wise).  
Before mounting the actuator onto the VAV box damper shaft,  
determine the following:  
1. Determine the damper shaft diameter. It must be  
between 3/8 in. to 1/2 in. (10 to 13 mm).  
2. Determine the length of the damper shaft. If the length of  
the VAV box damper shaft is less than 1-9/16 in.  
(40 mm), the actuator cannot be used.  
3. Determine the direction the damper shaft rotates to open  
the damper (CW or CCW) (see Fig. 3). Typically, there is  
an etched line on the end of the damper shaft that indi-  
cates the position of the damper. In Fig. 2, the indicator  
shows the damper open in a CW direction.  
b. Using the Declutch button, rotate the universal shaft  
adapter fully counterclockwise.  
c. Mount the actuator to the damper box and shaft.  
d. Tighten the two bolts on the centering clamp (8 mm  
wrench; 70.8–88.5 lb-in. [8–10 Nm] torque). When  
the actuator closes, the damper rotates CW  
90 degrees to fully close.  
4. If the damper rotates counterclockwise to open, and the  
angle of the damper open-to-closed is 45 or 60 degrees:  
a. Manually open the damper fully (rotate counterclock-  
wise).  
4. Determine the damper full opening angle (45, 60, or 90  
degrees). In Fig. 2, the damper is open to its full open  
position of 90 degrees.  
b. The actuator is shipped with the mechanical  
end-limits set at 95 degrees. Adjust the two  
mechanical end-limit set screws to provide the  
desired amount of rotation. Adjust the two set screws  
closer together to reduce the rotation travel.  
c. Tighten the two mechanical end-limit screws  
(Phillips #2 screwdriver; (26.5–31 lb-in. [3.0–3.5 Nm]  
torque).  
TYPE A DAMPER  
AIR  
FLOW  
CW TO OPEN, CCW TO CLOSE  
d. Using the Declutch button, rotate the universal shaft  
adapter fully counter-clockwise.  
TYPE B DAMPER  
e. Mount the actuator to the VAV damper box and shaft.  
f. Tighten the two bolts on the centering clamp  
(8 mm wrench; 70.8–88.5 lb-in. [8–10 Nm] torque).  
g. When the actuator closes, the damper rotates CW  
either 45 or 60 degrees to fully close.  
AIR  
FLOW  
CCW TO OPEN, CW TO CLOSE  
M2067B  
Fig. 3. Determining the rotation direction (CW or CCW)  
for damper opening.  
63-2689—05  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS  
IMPORTANT  
Special precautions must be taken for dampers that  
8-9/32  
(211)  
1-15/16  
(49)  
open in a CCW direction. The actuator is shipped with  
its rotation direction set to CW to Open, which applies  
to the damper direction in steps 1 and 2 above. If the  
damper shaft rotates in the CCW direction to open, the  
controller software must be programmed to change  
the rotation to “Reverse to Open,which applies to the  
damper direction in steps 3 and 4 above.  
4-1/8  
(105)  
27/32  
(21)  
13 14 15 16 17 18 19 20 21 22 23 24  
6-1/4  
(159)  
6-9/32  
(159)  
5-7/8  
(149)  
IMPORTANT  
It is advisable to leave the dampers in an open  
position after installation to avoid the possibility of  
over-pressurizing the duct work on fan startup. Use  
the Declutch button (see Fig. 1 on page 3) to open the  
box damper on controllers that are powered down, to  
prevent over-pressurization in the duct work on fan  
startup. To Declutch, press and hold the button to  
disengage the motor. Turn the damper shaft until the  
damper is open and release the button. When power  
is restored to the controller, the controller  
1
2
3
4
5
6
7
8
9
10 11 12  
DEPTH IS  
2-1/4 (57)  
3/16 (4.5) PANEL  
MOUNTING HOLE (4X)  
NOTE: CONTROLLER CAN BE MOUNTED IN ANY ORIENTATION.  
M31532  
Fig. 5. Panel mounting - controller and actuator  
dimensions in inches (mm) for PVB0000AS and  
PVB4022AS only (PVB4022AS shown).  
synchronizes the damper actuator, so that the damper  
is in the correct position upon startup.  
Mount Controller  
NOTE: The controller may be wired before mounting to a  
panel or DIN rail.  
10-5/16 (262)  
8-5/16 (211)  
1-55/64  
(47)  
6-29/64 (164)  
Terminal blocks are used to make all wiring connections to the  
controller. Attach all wiring to the appropriate terminal blocks  
2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 4  
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0  
5-3/4  
(146)  
7/16  
(11)  
DEPTH IS 2-1/4 (57)  
4-13/16 (122)  
4-1/8 (105)  
4-13/16 (122)  
4-1/8 (105)  
6-17/64  
(159)  
5-3/64  
(128)  
13 14 15 16 17 18 19 20 21 22 23 24  
13 14 15 16 17 18 19 20 21 22 23 24  
1 1 1 1 1 1 1 1  
1 2 3 4 5 6 7 8  
9 0 1 2 3 4 5 6 7  
6-1/4  
(159)  
6-1/4  
(159)  
PANEL MOUNTING HOLE  
(4X) 3/16 IN. (4.5)  
DEPTH IS  
2-1/4 (57)  
5-7/8  
(149)  
5-7/8  
(149)  
NOTE: CONTROLLER CAN BE MOUNTED IN ANY ORIENTATION.  
M29329  
Fig. 6. Panel mounting - controller and actuator  
dimensions in inches (mm) for PVB6436AS.  
1
2
3
4
5
6
7
8
9
10 11 12  
1
2
3
4
5
6
7
8
9
10 11 12  
3/16 (4.5) PANEL MOUNTING HOLE (4X)  
NOTE: CONTROLLER CAN BE MOUNTED IN ANY ORIENTATION.  
M31531  
Fig. 4. Panel mounting - controller dimensions in inches  
(mm) for PUB1012S, PUB4024S and PVB4024NS only  
(PUB4024S and PVB4024NS shown).  
PANEL MOUNTING HOLE  
(4X) 29/64 IN. (12)  
PVB6438NS  
PUB6438S  
2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 4  
2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 4  
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0  
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0  
5-3/4  
(146)  
5-3/64  
(128)  
5-3/64  
(128)  
5-29/64  
(139)  
5-29/64  
(139)  
1 1 1 1 1 1 1 1 1 1 2  
9 0 1 2 3 4 5 6 7 8 9 0  
1 1 1 1 1 1 1 1 1 1 2  
9 0 1 2 3 4 5 6 7 8 9 0  
1 2 3 4 5 6 7 8  
1 2 3 4 5 6 7 8  
6-29/64 (164)  
6-27/32 (174)  
6-29/64 (164)  
6-27/32 (174)  
DEPTH IS  
2-1/4 (57)  
M29330  
NOTE: CONTROLLER CAN BE MOUNTED IN ANY ORIENTATION.  
Fig. 7. Panel mounting - controller dimensions in inches (mm) for models PUB6438S and PVB6438NS.  
5
63-2689—05  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS  
NOTES:  
Panel Mounting  
The controller enclosure is constructed of a plastic base plate  
and a plastic factory-snap-on cover.  
Use 1/4 inch (6 mm) outside diameter, with a 0.040  
in. (1 mm) wall thickness, plenum-rated 1219 FR  
(94V-2) tubing.  
Always use a fresh cut on the end of the tubing  
that connects to the air flow pickups and the  
restrictor ports on the controller.  
NOTE: The controller is designed so that the cover does  
not need to be removed from the base plate for  
either mounting or wiring.  
Connect the high pressure or upstream tube to the plastic  
restrictor port labeled (+), and the low pressure or downstream  
tube to the restrictor port labeled (-). See labeling in Fig. 9.  
When twin tubing is used from the pickup, split the pickup  
tubing a short length to accommodate the connections.  
The controller mounts using four screws inserted through the  
corners of the base plate. Fasten securely with four No. 6 or  
No. 8 machine or sheet metal screws.  
The controller can be mounted in any orientation. Ventilation  
openings are designed into the cover to allow proper heat  
dissipation, regardless of the mounting orientation.  
NOTES:  
If controllers are mounted in unusually dusty or dirty  
environments, an inline, 5-micron disposable air  
filter (use 5-micron filters compatible with  
pneumatic controls) is recommended for the high  
pressure line (marked as +) connected to the air  
flow pickup.  
DIN Rail Mounting (PUB1012S, PUB4024S,  
PUB6438S, PVB4024NS and PVB6438NS)  
To mount the PUB1012S, PUB4024S, PUB6438S,  
PVB4024NS and PVB6438NS controllers on a DIN rail  
[standard EN50022; 1-3/8 in. x 9/32 in. (7.5 mm x 35 mm)],  
refer to Fig. 8 and perform the following steps:  
1. Holding the controller with its top tilted in towards the DIN  
rail, hook the two top tabs on the back of the controller  
onto the top of the DIN rail.  
The tubing from the air flow pickup to the controller  
should not exceed three feet (0.914 m). Any length  
greater than this will degrade the flow sensing  
accuracy.  
Use caution when removing tubing from a connec-  
tor. Always pull straight away from the connector or  
use diagonal cutters to cut the edge of the tubing  
attached to the connector. Never remove by pulling  
at an angle.  
2. Push down and in to snap the two bottom flex connectors  
of the controller onto the DIN rail.  
IMPORTANT  
To remove the controller from the DIN rail, perform the  
following:  
1. Push straight up from the bottom to release the top  
tabs.  
AIR FLOW  
PICKUP  
CONNECTOR  
TUBING  
2. Rotate the top of the controller out towards you and  
pull the controller down and away from the DIN rail to  
release the bottom flex connectors.  
RESTRICTOR  
PORT  
RESTRICTOR  
PORT  
ΔP  
2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 4  
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0  
TOP TABS  
DIN RAIL  
1 1 1 1 1 1 1 1 1 1 2  
9 0 1 2 3 4 5 6 7 8 9 0  
1 2 3 4 5 6 7 8  
M23556A  
Fig. 9. Air flow pickup connections (PVB0000AS,  
PVB4022AS, PVB4024NS, PVB6436AS and PVB6438NS).  
Power  
BOTTOM FLEX  
CONNECTORS  
M16815  
Before wiring the controller, determine the input and output  
device requirements for each controller used in the system.  
Select input and output devices compatible with the controller  
and the application. Consider the operating range, wiring  
requirements, and the environment conditions when selecting  
input/output devices. When selecting actuators for modulating  
applications consider using floating control. In direct digital  
control applications, floating actuators will generally provide  
control action equal to or better than an analog input actuator  
for lower cost.  
Fig. 8. Controller DIN rail mounting (models PUB1012S,  
PUB4024S, PUB6438S, PVB4024NS and PVB6438NS).  
Piping (PVB0000AS, PVB4022AS,  
PVB4024NS, PVB6436AS and  
PVB6438NS)  
Air flow Pickup  
For PVB0000AS, PVB4022AS, PVB4024NS, PVB6436AS and  
PVB6438NS, connect the air flow pickup to the two restrictor  
ports on the controller (see Fig. 9).  
Determine the location of controllers, sensors, actuators and  
other input/output devices and create wiring diagrams. Refer to  
Fig. 17–Fig. 23 beginning on page 14 for illustrations of typical  
controller wiring for various configurations.  
63-2689—05  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS  
The application engineer must review the control job  
is less than 33 VA, this same transformer could be used to  
power three of these controllers and meet NEC Class 2  
restrictions (no greater than 100 VA).  
requirements. This includes the sequences of operation for the  
controller, and for the system as a whole. Usually, there are  
variables that must be passed between the controller and other  
Spyder BACnet controller(s) that are required for optimum  
system wide operation. Typical examples are the TOD, Occ/  
Unocc signal, the outdoor air temperature, the demand limit  
control signal, and the smoke control mode signal.  
See Fig. 11–Fig. 12 beginning on page 9 for illustrations of  
controller power wiring. See Table 4 for VA ratings of various  
devices.  
Table 4. VA ratings for transformer sizing.  
It is important to understand these interrelationships early in  
the job engineering process, to ensure proper implementation  
when configuring the controllers. Refer to the controller  
Application Guides.  
Device  
Description  
VA  
PVB6436AS  
Controller and Actuator  
9.0  
controllers and  
Series 60 Floating  
Damper Actuator  
Power Budget  
PUB6438S or  
PVB6438NS  
Controller  
5.0  
A power budget must be calculated for each device to  
determine the required transformer size for proper operation. A  
power budget is simply the summing of the maximum power  
draw ratings (in VA) of all the devices to be controlled. This  
includes the controller itself and any devices powered from the  
controller, such as equipment actuators (ML6161 or other  
motors) and various contactors and transducers.  
ML684  
Versadrive Valve Actuator  
Damper Actuator, 35 lb-in.  
Damper Actuator SR 50 lb-in  
Damper Actuator, 66 lb-in.  
Damper Actuator, 132 lb-in.  
Valve Actuator  
12.0  
2.2  
ML6161  
ML6185  
ML6464  
ML6474  
R6410A  
R8242A  
12.0  
3.0  
3.0  
IMPORTANT  
When multiple controllers operate from a single  
transformer, connect the same side of the transformer  
secondary to the same power input terminal in each  
device. The earth ground terminal (terminal 3) must  
be connected to a verified earth ground for each  
controller in the group (see Fig. 12 on page 9).  
Half-wave devices and full-wave devices must not use  
the same AC transformer. If a Spyder controller will  
share its power supply with another device, make  
sure the other device utilizes a half-wave rectifier and  
that the polarity of the wiring is maintained.  
0.7  
Contactor  
21.0  
For contactors and similar devices, the in-rush power ratings  
should be used as the worst case values when performing  
power budget calculations. Also, the application engineer must  
consider the possible combinations of simultaneously  
energized outputs and calculate the VA ratings accordingly.  
The worst case, which uses the largest possible VA load,  
should be determined when sizing the transformer.  
Each controller requires 24 Vac power from an energy-limited  
Class II power source. To conform to Class II restrictions (U.S.  
only), transformers must not be larger than 100 VA. A single  
transformer can power more than one controller.  
POWER BUDGET CALCULATION EXAMPLE  
Table 3 is an example of a power budget calculation for a  
typical PVB6436AS controller. While the example is shown for  
only this model, the process is applicable for all controller  
models.  
GUIDELINES FOR POWER WIRING ARE AS FOLLOWS:  
For multiple controllers operating from a single  
transformer, the same side of the transformer  
secondary must be connected to the same power input  
terminal in each device. The earth ground terminal  
must be connected to a verified earth ground for each  
controller in the group (see Fig. 12 on page 9).  
Controller configurations are not necessarily limited to  
three devices, but the total power draw, including  
accessories, cannot exceed 100 VA when powered by  
the same transformer (U.S. only).  
Table 3. Power budget calculation example.  
VA  
Device  
Obtained From  
Information  
PVB6436AS  
9.0  
controllers (include  
Series 60 Floating  
Damper Actuator)  
®
R8242A Contactor  
fan rating  
21.0  
0.0  
TRADELINE Catalog  
inrush rating  
See Fig. 11 on page 9 for controller power wiring used  
in UL 1995 equipment (U.S. only).  
Many controllers require all loads to be powered by the  
same transformer that powers the controller.  
Keep the earth ground connection wire run as short as  
possible (refer to Fig. 11–Fig. 12 beginning on page 9).  
Do not connect earth ground to the controller’s digital or  
analog ground terminals (refer to Fig. 11 and Fig. 12).  
Unswitched 24 Vac power wiring can be run in the  
same conduit as the LONWORKS® Bus cable.  
D/X Stages  
For example, assume  
cooling stage outputs are  
wired into a compressor  
control circuit and have no  
impact on the budget.  
®
M6410A Steam  
Heating Coil Valve  
0.7  
TRADELINE Catalog,  
0.32A 24 Vac  
TOTAL  
30.7  
Line-Loss  
The system example above requires 30.7 VA of peak power.  
Therefore, a 100 VA AT92A transformer could be used to  
power one controller of this type. Because the total peak power  
Controllers must receive a minimum supply voltage of 20 Vac.  
If long power or output wire runs are required, a voltage drop  
due to Ohms Law (I x R) line-loss must be considered. This  
line-loss can result in a significant increase in total power  
7
63-2689—05  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS  
required and thereby affect transformer sizing. The following  
example is an I x R line-loss calculation for a 200 ft. (61m) run  
from the transformer to a controller drawing 37 VA and using  
two 18 AWG (1.0 sq mm) wires.  
With 100 percent load, the transformer secondary must supply  
between 23 and 25 volts to meet the NEMA standard. When a  
purchased transformer meets the NEMA standard DC20-1986,  
the transformer voltage regulating ability can be considered  
reliable. Compliance with the NEMA standard is voluntary.  
The formula is:  
Loss = [length of round-trip wire run (ft.)] x [resistance in  
wire (ohms per ft.)] x [current in wire (amperes)]  
27  
26  
25  
24  
23  
22  
From specification data:  
18 AWG twisted pair wire has a resistance of 6.52 ohms per  
1000 feet.  
Loss = [(400 ft.) x (6.52/1000 ohms per ft.)] x [(37 VA)/(24V)]  
= 4.02 volts  
21  
20  
19  
18  
17  
16  
15  
14  
This means that four volts are going to be lost between the  
transformer and the controller. To assure the controller  
receives at least 20 volts, the transformer must output more  
than 24 volts. Because all transformer output voltage levels  
depend on the size of the connected load, a larger transformer  
outputs a higher voltage than a smaller one for a given load.  
Fig. 10 shows this voltage load dependence.  
200  
0
50  
100  
150  
% OF LOAD  
In the preceding I x R loss example, even though the controller  
load is only 37 VA, a standard 40 VA transformer is not  
sufficient due to the line-loss. Looking at Fig. 10, a 40 VA  
transformer is just under 100 percent loaded (for the 37 VA  
controller) and has a secondary voltage of 22.9 volts. (Use the  
lower edge of the shaded zone in Fig. 10 that represents the  
worst case conditions.) When the I x R loss of four volts is  
subtracted, only 18.9 volts reaches the controller. This is not  
enough voltage for proper operation.  
M993  
Fig. 10. NEMA Class 2 transformer voltage output limits.  
The Honeywell transformers listed in Table 5 meet the NEMA  
standard DC20-1986.  
Table 5. Honeywell transformers that meet  
NEMA standard DC20-1986.  
Transformer Type  
AT40A  
VA Rating  
In this situation, the engineer has three alternatives:  
1. Use a larger transformer. For example, if an 80 VA model  
is used, an output of 24.4 volts, minus the four volt line-  
loss, supplies 20.4V to the controller (see Fig. 10).  
Although acceptable, the four-volt line-loss in this exam-  
ple is higher than recommended.  
40  
40  
AT72D  
AT87A  
50  
AK3310 Assembly  
100  
NOTE: The AT88A and AT92A transformers do not meet  
the voluntary NEMA standard DC20-1986.  
IMPORTANT  
No installation should be designed where the line-loss  
is greater than two volts. This allows for nominal oper-  
ation if the primary voltage drops to 102 Vac (120 Vac  
minus 15 percent).  
Wiring  
All wiring must comply with applicable electrical codes and  
ordinances, or as specified on installation wiring diagrams.  
Controller wiring is terminated to the screw terminal blocks  
located on the top and the bottom of the device.  
2. Use heavier gauge wire for the power run. 14 AWG  
(2.0 sq mm) wire has a resistance of 2.57 ohms per  
1,000 ft. Using the preceding formula results in a line-  
loss of only 1.58 volts (compared with 4.02 volts). This  
would allow a 40 VA transformer to be used. 14 AWG  
(2.0 sq mm) wire is the recommended wire size for 24  
Vac wiring.  
WARNING  
Electrical Shock Hazard.  
3. Locate the transformer closer to the controller. This  
reduces the length of the wire run, and the line-loss.  
Can cause severe injury, death or property damage.  
Disconnect power supply before beginning wiring or  
making wiring connections, to prevent electrical shock  
or equipment damage.  
The issue of line-loss is also important in the case of the output  
wiring connected to the Triac digital outputs. The same formula  
and method are used. Keep all power and output wire runs as  
short as practical. When necessary, use heavier gauge wire, a  
bigger transformer, or install the transformer closer to the  
controller.  
NOTES:  
For multiple controllers operating from a single  
transformer, the same side of the transformer  
secondary must be connected to the same power  
input terminal in each controller. Controller  
configurations will not necessarily be limited to  
three devices, but the total power draw, including  
accessories, cannot exceed 100 VA when  
To meet the National Electrical Manufacturers Association  
(NEMA) standards, a transformer must stay within the NEMA  
limits. The chart in Fig. 10 shows the required limits at various  
loads.  
powered by the same transformer (U.S. only). For  
power and wiring recommendations, See “Power”  
63-2689—05  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS  
on page 6. The earth ground terminal (terminal 3)  
must be connected to a verified earth ground for  
each controller in the group (see Fig. 12 on  
page 9).  
All loads on the controller must be powered by the  
same transformer that powers the controller itself.  
A controller can use separate transformers for  
controller power and output power.  
IMPORTANT  
Connect terminal 2, (the 24 Vac common [24 VAC  
COM] terminal) to earth ground (see Fig. 11).  
NOTE: Unswitched 24 Vac power wiring can be run in the  
same conduit as the LONWORKS® cable.  
Keep the earth ground connection (terminal 3) wire  
run as short as possible.  
Do not connect the universal input COM terminals,  
analog output COM terminals or the digital input/  
output COM terminals to earth ground. Refer to  
Fig. 16–Fig. 21 beginning on page 13 for wiring  
examples.  
ΔP  
22222222233333333334  
12345678901234567890  
CONNECT POWER TO  
TERMINALS 1 AND 2  
11111111112  
12345678  
901234567890  
The 24 Vac power from an energy limited Class II power  
source must be provided to the controller. To conform to Class  
II restrictions (U.S. only), the transformer must not be larger  
than 100 VA.  
TRANSFORMER  
COM  
24 VAC  
Fig. 11 depicts a single controller using one transformer.  
LINE VOLTAGE  
GREATER  
THAN 150 VAC  
1
OUTPUT  
IMPORTANT  
DEVICE  
POWER  
EARTH  
GROUND  
Power must be off prior to connecting to or removing  
connections from the 24 Vac power (24 Vac/24 Vac  
COM), earth ground (EGND), and 20 Vdc power (20  
Vdc) terminals.  
1
WHEN CONNECTIONG POWER TO THE SPYDER BACnet  
CONTROLLER, CONNECT THE COM LEG OF THE VAC SECONDARY  
CIRCUIT TO A KNOWN EARTH GROUND.  
M29684A  
IMPORTANT  
Fig. 11. Power wiring details for one controller per  
transformer.  
Use the heaviest gauge wire available, up to 14 AWG  
(2.0 sq mm), with a minimum of 18 AWG (1.0 sq mm),  
for all power and earth ground wiring.  
More than one controller can be powered by a single  
transformer. Fig. 12 shows power wiring details for multiple  
controllers.  
Screw-type terminal blocks are designed to accept up  
to one 14 AWG (2.0 sq mm) conductor or up to two 18  
AWG (1.0 sq mm) conductors. More than two wires  
that are 18 AWG (2.0 sq mm) can be connected with  
a wire nut. Include a pigtail with this wire group and  
attach the pigtail to the terminal block.  
NOTE: Controller configurations are not necessarily lim-  
ited to three devices, but the total power draw,  
including accessories, cannot exceed 100 VA  
when powered by the same transformer (U.S.  
only). For power wiring recommendations, see  
ΔP  
ΔP  
ΔP  
22222222233333333334  
22222222233333333334  
12345678901234567890  
22222222233333333334  
12345678901234567890  
12345678901234567890  
CONNECT POWER TO  
TERMINALS 1 AND 2  
11111111112  
901234567890  
11111111112  
901234567890  
11111111112  
901234567890  
12345678  
12345678  
12345678  
COM  
24 VAC  
120/240  
VAC  
TRANSFORMER  
OUTPUT  
DEVICE  
POWER  
EARTH  
GROUND  
M29685A  
Fig. 12. Power wiring details for two or more controllers per transformer.  
76.8 or 115.2 kilobits per second (configured at global  
Communications  
controller). The Spyder BACnet controllers are master devices  
on the MS/TP network. Each Spyder BACnet controller uses a  
high-quality EIA-485 transceiver and exerts 1/4 unit load on the  
MS/TP network.  
Each controller uses a BACnet MS/TP communications port.  
The controller’s data is presented to other controllers over a  
twisted-pair MS/TP network, which uses the EIA-485 signaling  
standard capable of the following baud rates: 9.6, 19.2, 38.4,  
9
63-2689—05  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS  
Cabling should be selected that meets or exceeds the BACnet  
Standard which specifies the following: An MS/TP EIA-485  
network shall use shielded, twisted-pair cable with  
BACnet device from other devices during installation. The  
Spyder BACnet Controllers Device Instance Number is  
automatically set when it is added to a WEBStation-AX project.  
The Device Instance Number can be changed by the user,  
which may be necessary when integrating with a third party or  
when attempting to replace an existing controller and it is  
desired to maintain the existing Device Instance Number.  
characteristic impedance between 100 and 130 ohms.  
Distributed capacitance between conductors shall be less than  
100 pF per meter (30 pF per foot). Distributed capacitance  
between conductors and shield shall be less that 200 pF per  
meter (60 pF per foot). Foil or braided shields are acceptable.  
The Honeywell tested and recommended MS/TP cable is  
Honeywell Cable 3322 (18 AWG, 1-Pair, Shielded, Plenum  
cable), alternatively Honeywell Cable 3251 (22 AWG, 1-Pair,  
Shielded, Plenum cable) is available and meets the BACnet  
Standard requirements (www.honeywellcable.com).  
To edit the Device Instance Number using WEBs AX:  
1. Identify an unused Device Instance Number on the BAC-  
net Network, in the range of 0 - 4194302.  
2. Open the Spyder Bacnet Device Mgr View  
a. Double click on the BacnetNetwork located in the  
Nav tree.  
The maximum BACnet MS/TP network Bus segment length is  
4,000 ft. (1,219 m) using recommended wire. Repeaters must  
be used when making runs longer than 4,000 ft. (1,219 m). A  
maximum of three repeaters can be used between any two  
devices.  
b. Select the Spyder Controller to be modified.  
c. Click on the Edit button.  
d. Enter an unused value in the Device Id field.  
e. Select OK  
3. Right Click on the Spyder Controller and select Actions >  
Write Device Instance to complete the update  
Setting the MS/TP MAC address  
Termination Resistors  
The MS/TP MAC address for each device must be set to a  
unique value in the range of 0-127 on an MS/TP network  
segment (address 0, 1, 2, & 3 should be avoided as they are  
commonly used for the router, diagnostic tools, and as spare  
addresses). DIP switches on the Spyder BACnet controller are  
used to set the controller's MAC address.  
Matched terminating resistors are required at each end of a  
segment bus wired across (+) and (-). Use matched precision  
resistors rated 1/4W ±1% / 80 - 130 Ohms. Ideally, the value of  
the terminating resistors should match the rated characteristic  
impedance of the installed cable. For example, if the installed  
MS/TP cable has a a listed characteristic impedance of 120  
Ohm, install 120 Ohm matched precision resistors.  
To set the MS/TP MAC address of a Spyder BACnet controller:  
1. Find an unused MAC address on the MS/TP network to  
which the Spyder BACnet controller connects.  
2. Locate the DIP switch bank on the Spyder BACnet for  
addressing. This is labeled MAC Address  
3. With the Spyder BACnet Controller powered down, set  
the DIP switches for the MAC Address you want. Add the  
value of DIP switches set to ON to determine the MAC  
address. See Table 6. Example, if only DIP switches 1, 3,  
5, and 7 are enabled the MAC address would be 85 (1 +  
4 + 16 + 64 = 85).  
NOTE: The controller does not provide any network bias-  
ing.  
Shield Terminating  
Following proper MS/TP cabling shield grounding procedures  
is important to minimize the risk of communication problems  
and equipment damage caused by capacitive coupling.  
Capacitive coupling is caused by placing MS/TP cabling close  
to lines carrying higher voltage. The shield should be grounded  
on only one end of the MS/TP segment (typically the router  
end). Tie the shield through using the SHLD (terminal 4) on the  
Spyder BACnet Controller.  
NOTE: See Fig. 15 on page 12 for DIP switch orienta-  
tion and arrangement.  
Sylk™ Bus  
Table 6. DIP Switch Values For MS/TP MAC Address.  
Sylk is a two wire, polarity insensitive bus that provides both 18  
VDC power and communications between a Sylk-enabled  
sensor and a Sylk-enabled controller. Using Sylk-enabled  
sensors saves I/O on the controller and is faster and cheaper  
to install since only two wires are needed and the bus is  
polarity insensitive. Sylk sensors are configured using the  
latest release of the Spyder Tool for WEBPro and WEBStation.  
DIP  
7
6
5
4
8
3
4
2
2
1
1
VALUE 64  
32  
16  
Setting the Device Instance Number  
The Device Instance Number must be unique across the entire  
BACnet system network because it is used to uniquely identify  
the BACnet devices. It may be used to conveniently identify the  
63-2689—05  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS  
NOTE: ALL BACnet MS/TP CONNECTIONS ARE MADE TO:  
BAC–  
BAC+  
SHLD  
2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 4  
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0  
2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 4  
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0  
2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 4  
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0  
1 1 1 1 1 1 1 1 1 1 2  
9 0 1 2 3 4 5 6 7 8 9 0  
1 1 1 1 1 1 1 1 1 1 2  
9 0 1 2 3 4 5 6 7 8 9 0  
1 1 1 1 1 1 1 1 1 1 2  
9 0 1 2 3 4 5 6 7 8 9 0  
1 2 3 4 5 6 7 8  
1 2 3 4 5 6 7 8  
1 2 3 4 5 6 7 8  
BACnet MS/TP–  
BACnet MS/TP+  
SHIELD  
BACnet MS/TP–  
BACnet MS/TP+  
SHIELD  
ADD APPROPRIATE TERMINATION  
RESISTOR BETWEEN THE BAC+  
AND THE BAC– TERMINALS.  
M29331  
Fig. 13. Termination modules.  
Wiring Method  
1.STRIP 1/2 IN. (13 MM)  
FROM WIRES TO  
BE ATTACHED AT  
ONE TERMINAL.  
1/2  
(13)  
WARNING  
Electrical Shock Hazard.  
Can cause severe injury, death or property damage.  
Disconnect power supply before beginning wiring, or  
making wiring connections, to prevent electrical shock  
or equipment damage.  
2. TWIST WIRES  
TOGETHER WITH  
PLIERS (A MINIMUM  
OF THREE TURNS).  
NOTE: When attaching two or more wires to the same  
terminal, other than 14 AWG (2.0 sq mm), be sure  
to twist them together. Deviation from this rule  
can result in improper electrical contact (see Fig.  
14).  
Each terminal can accommodate the following gauges of wire:  
— Single wire: from 22 AWG to 14 AWG solid or stranded  
— Multiple wires: up to two 18 AWG stranded, with 1/4 watt  
wire-wound resistor  
3. CUT TWISTED END OF WIRES TO 3/16 IN. (5 MM)  
BEFORE INSERTING INTO TERMINAL AND  
TIGHTENING SCREW. THEN PULL ON EACH  
WIRE IN ALL TERMINALS TO CHECK FOR  
Prepare wiring for the terminal blocks, as follows:  
1. Strip 1/2 in. (13 mm) insulation from the conductor.  
2. Cut a single wire to 3/16 in. (5 mm). Insert the wire in the  
required terminal location and tighten the screw.  
3. If two or more wires are being inserted into one terminal  
location, twist the wires together a minimum of three  
turns before inserting them (see Fig. 14).  
GOOD MECHANICAL CONNECTION.  
M17207  
Fig. 14. Attaching two or more wires at terminal blocks.  
Wiring Details  
Each controller is shipped with the digital outputs, which switch  
the 24 Vac to the load (High Side).  
4. Cut the twisted end of the wires to 3/16 in. (5 mm) before  
inserting them into the terminal and tightening the screw.  
5. Pull on each wire in all terminals to check for good  
mechanical connection.  
The three analog outputs (AO) are used to control modulating  
heating, cooling and economizer equipment. Any AO may be  
used as a digital output, as follows:  
— False (0%) produces 0 Vdc, (0 mA)  
True (100%) produces the maximum 11 Vdc (22 mA)  
The wiring connection terminals described in Table 7 are  
11  
63-2689—05  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS  
Table 7. Description of wiring terminal connections for  
PUB6438S, PVB6436AS, and PVB6438NS.  
IMPORTANT  
If the controller is not connected to a good earth  
ground, the controller's internal transient protection  
circuitry is compromised and the function of protect-  
ing the controller from noise and power line spikes  
cannot be fulfilled. This could result in a damaged cir-  
cuit board and require replacement of the controller.  
Refer to installation diagrams for specific wiring.  
Terminal  
Label  
Connection  
INPUT POWER & GROUND  
1
24 Vac  
24 Vac Power  
24 Vac Power  
Earth Ground  
MS/TP Shield  
Sylk  
2
3
4
5
6
24 Vac COM  
EGND  
SHLD  
All controllers have the terminal arrangements similar to the  
examples shown in Fig. 15 as described in Table Table 7 on  
page 12.  
SBUS 1  
SBUS 2  
Sylk  
NETWORK CONNECTIONS  
LONWORKS® communications  
MS/TP MAC ADDRESS DIP SWITCHES  
7
8
BAC +  
BAC -  
The MS/TP MAC address DIP switches are used to set the  
unit's MAC address. Each Spyder BACnet on an MS/TP  
network must have a unique MAC address in the range of 0-  
127 (address 0 should be avoided as it is the Honeywell factory  
default MAC address for all MS/TP devices).  
LONWORKS® communications  
a
DIGITAL OUTPUTS  
9
DO-1  
DO-2  
COM  
DO-3  
DO-4  
COM  
DO-5  
DO-6  
COM  
DO-7  
DO-8  
COM  
Digital Output  
Digital Output  
Common  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
MS/TP SERVICE CONNECTOR PINS  
Digital Output  
Digital Output  
Common  
Local device MS/TP network connection is provided via the  
molex connector pins (0.100-in. molex connector—part  
number: 22-01-2035).  
Digital Output  
Digital Output  
Common  
TERMINALS 21-40  
Digital Output  
Digital Output  
Common  
2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 4  
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0  
b
ANALOG OUTPUTS  
21  
22  
23  
24  
25  
AO-1  
COM  
AO-2  
AO-3  
COM  
Analog Output  
Common  
Analog Output  
Analog Output  
Common  
c
DIGITAL INPUTS  
26  
27  
28  
29  
30  
DI-1  
DI-2  
COM  
DI-3  
DI-4  
Digital Input  
Digital Input  
1 1 1 1 1 1 1 1 1 1 2  
1 2 3 4 5 6 7 8  
9 0 1 2 3 4 5 6 7 8 9 0  
Common  
TERMINALS 9-20  
TERMINALS 1-8  
BACnet MS/TP MAC  
ADDRESS DIP SWITCHES  
LOCAL BACnet MS/TP  
MOLEX CONNECTOR PINS  
Digital Input  
Digital Input  
M29332  
ATTACHED DEVICE(S) POWER  
20 Vdc Power  
UNIVERSAL INPUTS  
Universal Input  
Common  
31  
20 Vdc  
Fig. 15. Controller Terminal Connections, MS/TP MAC  
address DIP switches, MS/TP service connector pins, and  
BACnet Status LED for the PUB's and PVB's (PVB6438NS  
shown).  
32  
33  
34  
35  
36  
37  
38  
39  
UI-1  
COM  
UI-2  
UI-3  
COM  
UI-4  
UI-5  
COM  
UI-6  
Universal Input  
Universal Input  
Common  
Wiring Applications (Examples)  
Fig. 16–Fig. 22, beginning on page 13, illustrate controller  
wiring for the following configurations.  
Universal Input  
Universal Input  
Common  
Typical controller wiring for VAV application using the TR23  
Wall Module and a C7770A Air Temperature Sensor (see  
Fig. 16 on page 13).  
Typical controller wiring for VAV application with staged  
reheat (see Fig. 17 on page 14).  
Typical controller wiring for PWM reheat and PWM  
peripheral heat valve actuator (see Fig. 18 on page 15).  
Typical controller wiring for AHU application (see Fig. 19 on  
page 16).  
Typical controller wiring for 4 to 20 mA enthalpy sensors and  
digital inputs (see Fig. 20 on page 17).  
40  
Universal Input  
a
For the PVB6436AS controller ONLY, terminals 18, 19, and 20 (DO7,  
DO8, & COM) are not present. The actuator is internally hardwired to  
these terminals.  
b
c
Analog outputs may be configured as digital outputs and operate as fol-  
lows:  
– False (0%) produces 0 Vdc, (0 mA)  
True (100%) produces the maximum 11 Vdc (22 mA)  
Digital inputs: Open circuit = False; Closed circuit = True  
63-2689—05  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS  
Typical controller wiring for 4 to 20 mA heating, cooling, and  
model ML6161 floating motor control (see Fig. 21 on  
page 18).  
Typical controller wiring for a pneumatic transducer, model  
RP7517B (see Fig. 22 on page 19).  
WINDOWS CONTACTS  
(CONTACTS CLOSED  
EQUALS WINDOW CLOSED)  
OCCUPANCY SENSOR  
(CONTACTS CLOSED  
EQUALS OCCUPIED)  
AIR FLOW  
PICKUP  
C7770A  
AIR  
TEMPERATURE  
SENSOR  
2
3
3
COM  
COM  
DI-3  
DI-2  
ΔP  
UI-4  
DI-1  
UI-1  
UI-2  
UI-3  
COM  
AO-1  
22222222233333333334  
12345678901234567890  
11111111112  
901234567890  
12345678  
24 VAC  
COM  
DO-6  
DO-5  
+
2
-
24 VAC  
COM  
BACnet MS/TP–  
COM  
DO-4  
DO-3  
COM  
DO-2  
DO-1  
BACnet MS/TP+  
SHIELD  
REHEAT STAGE 3  
REHEAT STAGE 2 (OR CLOSE)  
REHEAT STAGE 1 (OR OPEN)  
DAMPER CLOSE  
DAMPER OPEN  
12 11 10  
9
8
7
6
5
4
3
2
1
DIP SWITCH  
DIP SWITCH S2  
ON  
S1  
1
ON  
DO NOT CHANGE THIS  
SWITCH POSITION.  
SW1 SW2  
ON  
SW1 SW2  
TR23-H ONLY  
DIP SWITCH S3  
(TR23 AND TR24 ONLY.)  
SW1 SW2 SW3  
1
DIP SWITCH S1 FOR HUMIDITY MODELS ONLY. SEE TR23 INSTALLATION INSTRUCTIONS, FORM NO. 62-0267,  
FOR CONFIGURATION DETAILS.  
2
3
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED TOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.  
CONTACTS MUST BE SUITABLE FOR DRY SWITCHING, 5V AT 10 mA. USE SEALED TYPE, GOLD FLASHED OR PIMPLED CONTACTS.  
M31169C  
Fig. 16. Controller wiring diagram (model PVB6438NS shown) for typical VAV application, using the TR23 wall module and  
a C7770A air temperature sensor. (For note 2, refer to Fig. 14.)  
13  
63-2689—05  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS  
WINDOWS CONTACTS  
(CONTACTS CLOSED  
EQUALS WINDOW CLOSED)  
OCCUPANCY SENSOR  
(CONTACTS CLOSED  
EQUALS OCCUPIED)  
AIR FLOW  
PICKUP  
3
2
3
COM  
DI-2  
DI-3  
UI-1  
ΔP  
COM  
UI-3  
DI-1  
UI-2  
AO-1  
22222222233333333334  
12345678901234567890  
11111111112  
901234567890  
12345678  
24 VAC  
+
2
STAGE 3  
STAGE 2  
COM  
-
24 VAC  
COM  
BACnet MS/TP–  
DO-3  
BACnet MS/TP+  
SHIELD  
DO-2  
DO-1  
STAGE 1  
DIP SWITCH  
S1  
DIP SWITCH S2  
1
LINE  
POWER  
12 11 10  
9
8
7
6
5
4
3
2
1
ON  
ON  
DO NOT CHANGE THIS  
SWITCH POSITION.  
SW1 SW2  
SW1 SW2  
ON  
DIP SWITCH S3  
(TR23 AND TR24 ONLY.)  
SW1 SW2 SW3  
TR23-H ONLY  
1
DIP SWITCH S1 FOR HUMIDITY MODELS ONLY. SEE TR23 INSTALLATION INSTRUCTIONS, FORM NO. 62-0267, FOR CONFIGURATION DETAILS.  
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED TOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.  
CONTACTS MUST BE SUITABLE FOR DRY SWITCHING, 5V AT 10 mA. USE SEALED TYPE, GOLD FLASHED OR PIMPLED CONTACTS.  
2
3
M31172C  
Fig. 17. Controller wiring diagram (model PVB6436AS shown) for typical VAV application with staged reheat.  
(For note 2, refer to Fig. 14.)  
63-2689—05  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS  
22222222233333333334  
12345678901234567890  
11111111112  
901234567890  
12345678  
24 VAC  
REHEAT  
+
-
ML7984B  
VALVE ACTUATOR  
24 VAC  
COM  
PWM VALVE ACTUATOR  
3
T6 T5  
C
B
W
R
1
DO-3  
PERIPHERAL HEAT  
VALVE ACTUATOR  
1
2
3
4
ON  
PWM VALVE ACTUATOR  
OFF  
2
3
ML7984B  
CONFIGURATION  
DIP SWITCHES  
(LOCATED ADJACENT  
TO THE INPUT  
T6 T5  
C
B
W
R
TERMINAL BLOCK)  
1
1
DO-2  
DO-1  
3
24 VAC  
24 VAC COM  
1
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED TOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.  
2
3
TURN POWER OFF BEFORE SETTING THE DIP SWITCHES.  
MAKE SURE ALL TRANSFORMER/POWER WIRING IS AS SHOWN: REVERSING TERMINATIONS WILL RESULT IN EQUIPMENT  
MALFUNCTION.  
M29335C  
Fig. 18. Controller wiring diagram (model PUB6438S shown) for typical PWM reheat and PWM peripheral heat valve  
actuator. (For note 2, refer to Fig. 14.)  
NOTE: Make sure to set the Configuration DIP Switch as  
shown in Fig. 18. Switches 1 through 3 set the tim-  
ing of the ML7984B valve actuator to match the  
controller outputs (0.1 second minimum with a  
maximum time of 25.6 seconds). Switch 4 deter-  
mines the action of the actuator (Off = Direct Act-  
ing, On = Reverse Acting).  
15  
63-2689—05  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS  
20 VDC  
OUTDOOR  
ENTHALPY  
UI-3  
3
COM  
20 VDC  
COM  
RETURN  
ENTHALPY  
UI-4  
UI-5  
DI-1  
2
AO-1  
UI-1  
COM  
UI-2  
UI-6  
22222222233333333334  
12345678901234567890  
DISCHARGE  
AIR TEMP  
FAN  
11111111112  
901234567890  
12345678  
24 VAC  
COM  
DO-8  
+
2
-
BACnet MS/TP–  
24 VAC  
COM  
COM  
DO-4  
HEAT 1  
HEAT 2  
BACnet MS/TP+  
SHIELD  
DO-3  
COM  
COMP 1  
COMP2  
DO-2  
DIP SWITCH  
DIP SWITCH S2  
ON  
DO-1  
S1  
1
12 11 10  
9
8
7
6
5
4
3
2
1
ON  
DO NOT CHANGE THIS  
SWITCH POSITION.  
SW1 SW2  
SW1 SW2  
ON  
DIP SWITCH S3  
(TR23 AND TR24 ONLY.)  
SW1 SW2 SW3  
TR23-H ONLY  
1
DIP SWITCH S1 FOR HUMIDITY MODELS ONLY. SEE TR23 INSTALLATION INSTRUCTIONS, FORM NO. 62-0267,  
FOR CONFIGURATION DETAILS.  
2
3
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED TOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.  
CONTACTS MUST BE SUITABLE FOR DRY SWITCHING, 5V AT 10 mA. USE SEALED TYPE, GOLD FLASHED OR PIMPLED CONTACTS.  
M31176B  
Fig. 19. Controller wiring diagram (model PUB6438S shown) for typical AHU application.  
(For note 2, refer to Fig. 14.)  
63-2689—05  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS  
DI-3  
COM  
20 VDC  
OCCUPANCY SENSOR  
(CONTACTS CLOSED  
EQUALS OCCUPIED)  
OUTDOOR  
ENTHALPY  
UI-3  
3
4
WINDOWS CONTACTS  
(CONTACTS CLOSED  
EQUALS WINDOW CLOSED)  
COM  
DI-2  
20 VDC  
COM  
RETURN  
ENTHALPY  
UI-4  
UI-5  
DI-1  
2
COM  
UI-6  
AO-1  
UI-1  
UI-2  
22222222233333333334  
12345678901234567890  
DISCHARGE  
AIR TEMP  
FAN  
11111111112  
901234567890  
12345678  
24 VAC  
COM  
DO-8  
3
+
-
COM  
DO-4  
24 VAC  
COM  
HEAT 1  
HEAT 2  
2
BACnet MS/TP–  
DO-3  
COM  
BACnet MS/TP+  
SHIELD  
COMP 1  
COMP2  
DO-2  
DIP SWITCH  
DIP SWITCH S2  
ON  
DO-1  
S1  
1
12 11 10  
9
8
7
6
5
4
3
2
1
ON  
DO NOT CHANGE THIS  
SWITCH POSITION.  
SW1 SW2  
SW1 SW2  
ON  
DIP SWITCH S3  
(TR23 AND TR24 ONLY.)  
SW1 SW2 SW3  
TR23-H ONLY  
1
DIP SWITCH S1 FOR HUMIDITY MODELS ONLY. SEE TR23 INSTALLATION INSTRUCTIONS, FORM NO. 62-0267, FOR CONFIGURATION DETAILS.  
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED TOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.  
2
3
CONTACTS MUST BE SUITABLE FOR DRY SWITCHING, 5V AT 10 mA. USE SEALED TYPE, GOLD FLASHED OR PIMPLED CONTACTS.  
M31177B  
Fig. 20. Controller wiring diagram (model PUB6438S shown) with 4 to 20 mA enthalpy sensors and digital inputs.  
(For note 2, refer to Fig. 14.)  
17  
63-2689—05  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS  
TWO - OR  
THREE-WAY  
HOT WATER/  
STEAM VALVE  
TWO - OR  
THREE-WAY  
CHILLER  
WATER VALVE  
SERIES 70  
VALVE  
SERIES 70  
VALVE  
ACTUATOR  
ACTUATOR  
24  
IN-  
24  
IN-  
VAC COM PUT  
VAC COM PUT  
AO-3  
COM  
UI-6  
AO-2  
AO-1  
UI-3  
COM  
DI-1  
UI-1  
DISCHARGE  
AIR TEMP  
UI-2  
22222222233333333334  
12345678901234567890  
11111111112  
901234567890  
12345678  
3
24 VAC  
FAN  
+
-
24 VAC  
COM  
BACnet MS/TP–  
BACnet MS/TP+  
SHIELD  
COM  
DIP SWITCH  
DIP SWITCH S2  
DO4  
S1  
1
ON  
ON  
COM  
DO NOT  
DAMPER CLOSED  
CHANGE THIS  
SW1 SW2  
SW1 SW2  
SWITCH  
POSITION.  
ON  
DIP SWITCH S3  
(TR23 AND  
DAMPER OPEN  
TR24 ONLY.)  
SW1 SW2 SW3  
12 11 10  
9
8
7
6
5
4
3
2
1
TR23-H ONLY  
1
2
DIP SWITCH S1 FOR HUMIDITY MODELS ONLY. SEE TR23 INSTALLATION INSTRUCTIONS, FORM NO. 62-0267, FOR CONFIGURATION DETAILS.  
EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM. USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM2) WITH  
A MINIMUM OF 18 AWG (1.O MM2), FOR EARTH GROUND WIRE.  
3
4
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED TOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.  
CONTACTS MUST BE SUITABLE FOR DRY SWITCHING, 5V AT 10 mA. USE SEALED TYPE, GOLD FLASHED OR PIMPLED CONTACTS.  
M31178A  
Fig. 21. Controller wiring diagram (model PUB6438S shown) with 4 to 20 mA heating, cooling, and model ML6161 damper  
actuator. (For note 2, refer to Fig. 14.)  
63-2689—05  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS  
if one controller is connected improperly (see Fig. 13 on  
page 11).  
AO1  
2
— Verify that Triac wiring of the digital outputs to external  
devices uses the proper load power and 24 Vac common  
terminal (digital output common terminals) for High-Side  
switching.  
22222222233333333334  
12345678901234567890  
NOTE: All wiring must comply with applicable electrical  
codes and ordinances or as specified on installa-  
tion wiring diagrams.  
For guidelines for wiring run lengths and power budget, see  
VERIFY END-OF-LINE TERMINATION RESISTOR  
PLACEMENT  
11111111112  
901234567890  
12345678  
The installation wiring diagrams should indicate the locations  
for placement of the end of line termination resistors. See  
Fig. 13 on page 11.  
24 VAC  
+
PNEUMATIC  
VALVE  
ACTUATOR  
24 VAC  
COM  
2B  
-
1
RP7517B  
1M  
Correct placement of the end-of-line termination resistors is  
required for proper LONWORKS® Bus communications.  
M
BROWN  
BLACK  
BLUE  
Step 2. Startup  
Refer to Fig. 23 and the following text for startup information.  
HOST  
STATUS LED  
1
USE 1/4 IN (6 MM) PNEUMATIC TUBING. MINIMUM BRANCH LINE  
MUST BE 6 FT. (1.8M) OR LONGER.  
TERMINALS 21-40  
2
TERMINALS 21, 23, AND 24 ARE ANALOG OUTPUTS.  
M29339B  
2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 4  
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0  
Fig. 22. Controller wiring diagram (model PUB6438S  
shown) for RP7517B pneumatic transducer.  
CHECKOUT  
Step 1. Check Installation and Wiring  
Inspect all wiring connections at the controller terminals, and  
verify compliance with installation wiring diagrams. If any wiring  
changes are required, first be sure to remove power from the  
controller before starting work. Pay particular attention to:  
— 24 Vac power connections. Verify that multiple controllers  
being powered by the same transformer are wired with the  
transformer secondary connected to the same input  
terminal numbers on each controller. Use a meter to  
measure 24 Vac at the appropriate terminals (see Fig. 12  
on page 9). Controller configurations are not necessarily  
limited to three devices, but the total power draw, including  
accessories, cannot exceed 100 VA when powered by the  
same transformer (U.S. only).  
— Be sure that each controller has terminal 3 wired to a  
verified earth ground, using a wire run as short as possible  
with the heaviest gauge wire available, up to 14 AWG (2.0  
sq mm) with a minimum of 18 AWG (1.0 sq mm) for each  
controller in the group (see Fig. 12 on page 9).  
— Check that the MS/TP network polarity has been connected  
properly on each controller. BACnet MS/TP is polarity  
sensitive; communication will be lost for the entire segment  
1 1 1 1 1 1 1 1 1 1 2  
9 0 1 2 3 4 5 6 7 8 9 0  
1 2 3 4 5 6 7 8  
TERMINALS 9-20  
LOCAL BACnet MS/TP  
MOLEX CONNECTOR PINS  
TERMINALS 1-8  
BACnet  
STATUS LED  
BACnet MS/TP MAC  
ADDRESS DIP SWITCHES  
M29340A  
Fig. 23. LED, service, and network connection locations.  
SET THE MS/TP MAC ADDRESS  
The MS/TP MAC address DIP switches are used to set the  
unit's MAC address. Each Spyder BACnet on an MS/TP  
network must have a unique MAC address in the range of 0-  
127 (address 0 should be avoided as it is the Honeywell factory  
default MAC address for all MS/TP devices).  
CONTROLLER STATUS LED:  
The LED on the front of the controller provides a visual  
indication of the status of the device. When the controller  
receives power, the LED appears in one of the following  
allowable states, as described in Table 8.  
19  
63-2689—05  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS  
Table 8. Status LED States.  
CONTROLLER REPLACEMENT  
LED State  
OFF  
Blink Rate  
Status or Condition  
There are no serviceable or repairable parts inside the  
controller.  
Not applicable  
No power to processor,  
LED damaged, low  
voltage to board, first  
second of power up or  
loader damaged.  
WARNING  
Fire, Explosion, or Electrical Shock Hazard.  
Can cause severe injury, death or property damage.  
Do not attempt to modify the physical or electrical  
characteristics of this device in any way. Replace the  
controller if troubleshooting indicates a malfunction.  
ON  
ON steady;  
not blinking  
Processor not operating.  
Application Program CRC  
being checked. This takes  
1-2 seconds and occurs  
on each restart (power  
up, reset and reflash, and  
following configuration file  
download).  
WARNING  
Electrical Shock Hazard.  
Very Slow Blink 1 second ON,  
(continuous)  
Controller is operating  
normally.  
Can cause severe injury, death or property damage.  
Disconnect power supply before beginning controller  
replacement to prevent electrical shock or equipment  
damage.  
1 second OFF  
Slow Blink  
(continuous)  
0.5 second ON, Controller alarm is active  
0.5 second OFF or controller in process of  
configuration file  
download.  
Terminal Block Removal  
To simplify controller replacement, all terminal blocks are  
designed to be removed with the wiring connections intact and  
then re-installed on the new controller. See Fig. 24 and refer to  
the following procedure:  
Medium Blink 0.3 second ON, Controller is in reflash  
(continuous)  
0.3 second OFF mode or awaiting/  
receiving reflash data via  
the BACnet network.  
BACNET STATUS LED:  
IMPORTANT  
The LED on the front of the controller, between the BACnet  
MS/TP terminals and MAC Address DIP Switches, provides a  
visual indication of the BACnet MS/TP communication status.  
When the controller receives power, the LED appears in one of  
the following allowable states, as described in Table 9.  
To prevent bending or breaking the alignment pins on  
longer terminal blocks, insert the screwdriver at  
several points to evenly and gradually lift up the  
terminal block.  
Insert the screwdriver blade no more than 1/8 in.  
(3 mm) to prevent damage to the terminal block align-  
ment pins on the controller circuit board.  
Table 9. BACnet Status LED States.  
BACnet LED Status  
Status or Condition  
Solid on  
Controller has power, loader is not  
running.  
Solid on, blinking off  
once in 2.5 sec.  
Controller is in reflash mode, no MS/  
TP communication.  
Solid on, blinking off  
twice in 2.5 sec.  
Controller is in reflash mode, MS/TP  
communication present.  
Solid on, blinking off  
thrice in 2.5 sec  
Controller is in reflash mode, MS/TP  
communication data transfer in  
progress.  
Solid off, there is no  
power  
No power to processor, LED  
damaged, low voltage to board, or  
loader damaged.  
SHORT TERMINAL BLOCK  
LONGTERMINAL BLOCK  
M23563  
Solid off, blinking on  
once in 2.5 sec.  
Controller is running, no MS/TP  
communication.  
Fig. 24. Removing Terminal Blocks.  
Solid off, blinking on  
twice in 2.5 sec.  
Controller is running, MS/TP  
communication present.  
1. Use a thin-bladed screwdriver to evenly raise the  
terminal block from its alignment pins:  
a. For short terminal blocks (1 to 5 terminals), insert  
screwdriver blade in the center of the terminal block  
and use a back and forth twisting motion to gently  
raise the terminal block from its alignment pins 1/4 in.  
(6.35 mm).  
b. For long terminal blocks (6 or more terminals), insert  
screwdriver blade on one side of the terminal block  
and gently rotate the blade 1/4 turn. Then, move to  
the other side of the terminal block and do the same.  
Repeat until the terminal block is evenly raised 1/4 in.  
(6.35 mm) from its alignment pins.  
Solid off, blinking on  
thrice in 2.5 sec  
Controller is running, MS/TP  
communication data transfer in  
progress.  
Step 3. Checkout Completion  
At this point the controller is installed and powered. To  
complete the checkout, the NIAGARA FRAMEWORK® application  
(run on a PC) is used to configure the I/O and functions of the  
controller. Refer to the Programming Tool User Guide, form no.  
63-2662, for controller configuration and programming details.  
63-2689—05  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS  
2. Once the terminal block is raised 1/4 in. (6.35 mm) from  
its alignment pins, grasp the terminal block at its center  
(for long terminal blocks grasp it at each end) and pull it  
straight up.  
4. Remove the old controller from its mounting.  
IMPORTANT  
(FOR CONTROLLERS MOUNTED TO A DIN RAIL):  
1. Push straight up from the bottom to release the top  
pins.  
Controller Replacement (PVB0000AS,  
PVB4022AS and PVB6436AS)  
2. Rotate the top of the controller outwards to release  
the bottom flex connectors (see Fig. 8 on page 6).  
For PVB0000AS, PVB4022AS and PVB6436AS controllers,  
which are hard-wired to an actuator, perform the following  
actions to replace the complete assembly (controller and  
actuator):  
1. Remove all power from the controller.  
2. Remove the two air flow pickup connections from the  
pressure sensor.  
3. Remove the terminal blocks (See “Terminal Block  
4. Remove the old controller and actuator assembly from its  
mounting.  
5. Mount the new controller.  
6. Reconnect the two air flow pickup tubes to the pressure  
7. Replace the terminal blocks:  
Insert each terminal block onto its alignment pins.  
Press straight down to firmly seat it.  
Repeat for each terminal block.  
Loosen the two bolts on the actuator clamp to release  
the actuator from the shaft.  
8. Restore power to the controller.  
Remove the controller’s mounting screws.  
Gently pull the controller and actuator assembly  
straight out, until the assembly is clear of the actuator  
shaft.  
Controller Replacement (PUB1012S,  
PUB4024S, and PUB6438S)  
Perform the following to replace the PUB1012S, PUB4024S  
and PUB6438S controllers:  
1. Remove all power from the controller.  
2. Remove the terminal blocks (See “Terminal Block  
5. Mount the new controller and actuator assembly (See  
6. Reconnect the two air flow pickup tubes to the pressure  
3. Remove the old controller from its mounting.  
7. Replace the terminal blocks:  
Insert each terminal block onto its alignment pins.  
Press straight down to firmly seat it.  
Repeat for each terminal block.  
IMPORTANT  
(FOR CONTROLLERS MOUNTED TO A DIN RAIL):  
1. Push straight up from the bottom to release the top  
pins.  
8. Restore power to the controller.  
2. Rotate the top of the controller outwards to release  
the bottom flex connectors (see Fig. 8 on page 6).  
Controller Replacement (PVB4024NS  
and PVB6438NS)  
Perform the following to replace the PVB4024NS and  
PVB6438NS controllers:  
1. Remove all power from the controller.  
2. Remove the two air flow pickup connections from the  
pressure sensor.  
4. Mount the new controller (See “Installation” on page 3.).  
5. Replace the terminal blocks:  
Insert each terminal block onto its alignment pins.  
Press straight down to firmly seat it.  
Repeat for each terminal block.  
6. Restore power to the controller.  
3. Remove the terminal blocks.  
21  
63-2689—05  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS  
63-2689—05  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS  
23  
63-2689—05  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS  
®
BACnet is a registered trademark of ASHRAE.  
®
BTL is a registered trademark of the BACnet International.  
®
NIAGARA FRAMEWORK and the Niagara framework logo are registered trademarks of Tridium, Inc.  
Automation and Control Solutions  
Honeywell International Inc.  
1985 Douglas Drive North  
® U.S. Registered Trademark  
© 2012 Honeywell International Inc.  
63-2689—05 M.S. Rev. 01-12  
Golden Valley, MN 55422  
Printed in United States  
customer.honeywell.com  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graco Automobile Parts 234397 User Manual
Haan Vacuum Cleaner HD 50 User Manual
Haier Microwave Oven MI 2270MG User Manual
Haier Water Dispenser WDNS121SS User Manual
Harbor Freight Tools Telescope 4815 User Manual
Hearth and Home Technologies Stove MTVERNINSAE CSB User Manual
Hotpoint Refrigerator FF187ALG User Manual
HP Hewlett Packard Tablet 2760p User Manual
Ide Line Juicer 753 122 User Manual
Impex Home Gym EVE 1500 User Manual