Honeywell Smoke Alarm XL 800 SERIES User Manual

XL 800 Series  
FOR SMOKE CONTROL  
HONEYWELL EXCEL 5000 OPEN SYSTEM  
INSTALLATION AND COMMISSIONING INSTRUCTIONS  
CONTENTS  
Connecting HMIs or Laptops........................................ 17  
Connecting the XI582 Operator Interface............... 17  
Connecting Laptops (XL-Online/CARE) ................. 18  
XCL8010AU Terminals........................................... 18  
Features.......................................................................18  
LONWORKS Interface and Terminals ....................... 18  
LONWORKS Service LED and Button....................... 18  
C-Bus Tx LED and Rx LED .................................... 19  
Reset Button........................................................... 19  
HMI Interface.......................................................... 19  
Alarm and Power LEDs .......................................... 20  
Watchdog Status .................................................... 20  
Modem Interface..................................................... 20  
I/O Bus Switch S2................................................... 20  
C-Bus Termination Switch S1................................. 21  
Memory .................................................................. 21  
General............................................................................... 3  
Before Installation............................................................. 3  
Installation ......................................................................... 3  
Wiring ................................................................................. 4  
XL800 Series Power Consumption................................ 5  
I/O Modules ................................................................... 5  
Description of the XCL8010AU Controller Module ......... 7  
Overview........................................................................ 7  
Interfaces and Bus Connections.................................. 10  
Technical Data............................................................. 10  
System Data........................................................... 10  
Operational Environment ....................................... 10  
Smoke Control Configuration....................................... 10  
Data File Set-Up .......................................................... 11  
Panel Reset ................................................................. 11  
Typical Power Limited Circuit for XL800...................... 11  
Connecting Single Bus Controller Systems ................. 11  
XCL8010AU, I/O Modules on Single Rail............... 12  
Multiple Rails in Single Cabinet.............................. 12  
LonWorks Bus I/O Modules in Separate Rooms.... 12  
How to Connect Panel Bus and LONWORKS Bus Mixed  
Controller Systems ...................................................... 12  
Connecting I/O Modules......................................... 12  
Connecting I/O Modules to the XCL8010AU.......... 12  
Setting Address of Panel Bus I/O Modules.................. 13  
Setting the I/O Bus Switch ........................................... 14  
LONWORKS Bus Topologies.......................................... 14  
C-Bus Topologies ........................................................ 14  
Description of the I/O Modules....................................... 21  
Common Features ....................................................... 21  
Analog Input Modules .................................................. 22  
Types of Analog Input Modules .............................. 22  
Features ................................................................. 22  
Terminals................................................................ 22  
XFL821AU Connection Examples .......................... 23  
Analog Output Modules................................................ 24  
Types of Analog Output Modules ........................... 24  
Features ................................................................. 24  
Terminals................................................................ 24  
Technical Data........................................................ 24  
Modules with Manual Overrides ............................. 25  
XFL822AU Connection Example............................ 25  
Synchronization Behavior of Analog Output Module  
Configured as Floating Output................................ 25  
Binary Input Modules ................................................... 26  
Types of Binary Input Modules ............................... 26  
Features ................................................................. 26  
Terminals................................................................ 26  
Technical Data........................................................ 26  
Status LEDs............................................................ 27  
XF823AU Connection Examples ............................ 27  
Relay Output Modules.................................................. 28  
Types of Relay Output Modules ............................. 28  
Features ................................................................. 28  
Terminals................................................................ 28  
Permissible Loads .................................................. 29  
Status LEDs with Manual Overrides....................... 29  
Connection Examples............................................. 30  
Mounting/Dismounting Modules.................................... 14  
Mounting/Dismounting Controller/Sockets................... 15  
Mounting Sockets................................................... 15  
Connecting Sockets ............................................... 15  
Dismounting Sockets ............................................. 16  
Mounting/Dismounting Electronic Modules.................. 16  
Mounting Electronic Modules ................................. 16  
Dismounting Electronic Modules............................ 17  
Connecting via C-Bus.................................................. 17  
Connecting to the Controller................................... 17  
Setting the C-Bus Termination Switch.................... 17  
Shielding ................................................................ 17  
Copyright © 2008 Honeywell GmbH All Rights Reserved  
EN1B-0410GE51 R0908A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Excel 800  
Installation  
WARNING  
Mount controller subpanel in cabinet so all labeling is visible.  
Secure full-size subpanel in place with six no. 10 x ½-inch  
(13 mm) sheet metal screws (not supplied). Secure smaller  
subpanel with four no. 10 x ½-inch (13 mm) sheet metal  
screws (not supplied).  
This equipment generates, uses, and can radiate radio  
frequency energy, and if not installed and used in accordance  
with the instructions manual, may cause interference to radio  
communications. It has been tested and found to comply with  
the limits for a Class A computing device pursuant to Subpart  
J of Part 15 of FCC Rules, which are designed to provide  
reasonable protection against such interference when  
operated in a commercial environment. Operation of this  
equipment in a residential area is likely to cause interference,  
in which case the user, at his own expense, will be required to  
take whatever measures may be required to correct the  
interference. Any unauthorized modification of this equipment  
may result in the revocation of the owner’s authority to  
continue its operation.  
NOTE:  
Subpanel must mount flat and should not bulge or  
recess anywhere.  
FULL-SIZE  
CABINET  
General  
The XL800 Series is designed to provide heating, ventilating  
and air-conditioning control. They can operate either  
standalone, or networked to Honeywell central workstations  
such as EBI. These controllers can also be used for smoke  
control system monitoring and control, for monitor and control  
of fire (UL864), and general purpose signaling (UL2017). In  
UL 2017 applications, the product can be used as a type NM  
(Non-Monitored) system. It is also approved for UL916  
(Energy Management Equipment.)  
The XL800 Series can be used for smoke control applications  
when used in conjunction with a UL listed fire alarm control  
panel (FACP) and UL listed fire fighters’ smoke control station  
(FSCS).  
Before Installation  
SIX NO. 10 x ½-INCH (13 mm)  
SHEET METAL SCREWS  
1. Unpack door and remove the XL800 from carton. Check  
equipment and report any damage to a Honeywell  
representative.  
2. Verify cabinet is installed correctly.  
Fig. 1. Mounting controller subpanel in cabinet (full-size  
subpanel cabinet shown)  
3. Securely mount the XL800 to a rigid structural surface  
using at least four sets of 1/4 in. (6 mm) mounting  
hardware (supplied locally).  
NOTE:  
Anchoring materials must be suitable for the  
mounting surface (wood, concrete, steel).  
Mounting must comply with all local codes.  
4. Obtain correct number and type of sheet metal screws for  
subpanel. Installation of a full-size subpanel requires six  
no. 10 x ½-inch (13 mm) sheet metal screws (not  
supplied). Installation of a smaller subpanel requires four  
no. 10 x ½-inch (13 mm) sheet metal screws (not  
supplied).  
5. Obtain 14505159-001 Tamper Switch per job  
requirements. Installation of Tamper Switch is optional.  
3
EN1B-0410GE51 R0908A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring  
Excel 800  
Wiring  
WARNING  
All wiring to the XL800 controller is unsupervised, except as  
noted.  
Risk of electric shock or equipment damage!  
All circuits are power limited, except for AC power circuits,  
relay contacts and other circuits as noted.  
Subpanel and Controller power must remain OFF until  
Controller is checked.  
All field wiring terminals accept 24 AWG to 14 AWG  
(0.25 mm2 to 2 mm2) conductors except as noted.  
4. Install optional Tamper Switch on cabinet per instructions  
in the cabinet installation instructions. Wire Tamper  
Switch per job drawings.  
All wiring must conform to local codes, ordinances, and  
regulations. Refer to job drawings for details.  
Verify that the voltage difference between any conductor and  
earth ground does NOT exceed 150 Vac.  
5. Mount cabinet door.  
1. Connect input/output device wiring, C-Bus transmission  
wiring (minimum 18 gage [0.8012 sq mm]), LON Bus  
transmission wiring, and 14507063 Power Cable to  
Controller per job drawings. Fig. 2 and Fig. 3 show typical  
controller wiring. Four Power Module models are available  
(see Table 2).  
CAUTION  
Risk of electric equipment damage! Excessive static can  
burn out equipment.  
2. Connect line voltage to Terminals H and N of the  
14507287 Power Module. Connect a good earth ground to  
Terminal G of the Power Module. Fig. 5 through Fig. 7  
show typical power wiring.  
Observe proper anti-static material handling practices  
when installing or servicing PC parts and related  
components.  
Observe proper equipment and body grounding practices.  
Discharge static electricity from your body before handling  
parts.  
3. For Power Modules -001 through -007, leave power to  
Power Supply and Controller OFF. Connect 14507063  
Power Cable from Controller to Power Module.  
Table 1. Connector terminal specifications  
connector terminal pin signal type  
input /  
output  
voltage  
type  
max.  
voltage  
max. current  
max.  
max. line  
frequency impedance  
analog input  
AI  
input  
SIGNAL ±12 V  
SIGNAL ±10 V  
SIGNAL ±10 V  
±20 mA  
±20 mA  
±20 mA  
9600 baud  
8K ohms  
15K ohms  
8K ohms  
10K ohms  
digital input  
DI  
input  
output(1  
output(2  
input  
--  
--  
analog output  
digital output  
AO  
DO  
TI  
9600 baud  
AC/DC  
±24 VAC/DC ±50 mA  
--  
totalizer output  
signal ground  
J1 RS-485 (C-BUS) (3  
SIGNAL ±12 V  
±12 mA  
--  
100 Hz  
--  
GND  
+A  
-A  
--  
--  
--  
1
2
input / output SIGNAL ±5 V  
input / output SIGNAL ±5 V  
1 mA / 180 mA 9600 baud  
1 mA / 180 mA 9600 baud  
100 ohms  
100 ohms  
--  
3S Shield A  
--  
--  
--  
--  
--  
(1 special application; (2 regulated; (3 supervised  
Table 2. Power module models  
transformer max. input  
model  
(48 VA) controller  
VAC output  
accessory output  
convenience outlet  
Vac  
current draw  
Hz  
14507287-001 120  
0.5 A  
60  
24  
120 Vac, 10A  
120 Vac, 10A  
120 Vac, 10A  
--  
14507287-002 120  
14507287-003 120  
14507287-007 120  
1.7 A  
60  
60  
60  
24  
24  
24  
24 Vac, 100 VA, 24 Vac, 40 VA  
1.7 A  
24 Vac, 100 VA, 24 Vdc, 600 mA  
--  
120 A  
EN1B-0410GE51 R0908A  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Excel 800  
Wiring  
XL800 Series Power Consumption  
I/O Modules  
When selecting the appropriate power supply, the power  
consumption of the XL800 modules must be taken into  
account.  
Variants of I/O Modules  
There are two variants of I/O modules:  
Panel Bus I/O modules with communication via Panel Bus  
(light-gray housings)  
Modules are automatically commissioned (with firmware  
download) by the XCL8010AU  
Table 3. XL800 power consumption  
max. power consumption  
model  
24 Vac, 60 Hz  
24 Vdc  
LONWORKS Bus I/O modules (dark-gray housings) with  
communication via LONWORKS (FTT10-A, link power  
compatible) for easy integration and use with 3rd-party  
controllers  
XCL8010AU with  
watchdog load  
690 mA  
640 mA  
XCL8010AU without  
watchdog load  
190 mA  
140 mA  
Terminal Sockets  
XF821AU, XFL821AU  
130 mA  
160 mA  
80 mA  
90 mA  
I/O modules are mounted on the appropriate terminal  
sockets. Panel Bus I/O modules and LONWORKS Bus I/O  
modules use the same terminal sockets.  
XF822AU, XFR822AU,  
XFL822AU, XFLR822AU  
XF823AU, XFL823AU  
180 mA  
140 mA  
130 mA  
90 mA  
XF824AU, XFR824AU,  
XFL824AU, XFLR824AU  
Color Coding  
To distinguish modules and components, the following color  
coding is used:  
XFR825AU  
140 mA  
90 mA  
Table 4. Color coding of Excel 800 Modules  
color  
part  
red  
All of the user-accessible adjustable  
mechanical parts (i.e., bridge connectors and  
locking mechanism) and operating controls  
(manual overrides, etc.)  
light-gray  
dark-gray  
Panel Bus I/O modules  
LONWORKS Bus I/O modules  
5
EN1B-0410GE51 R0908A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring  
Excel 800  
ANALOG  
INPUT  
ANALOG  
OUTPUT  
BINARY  
INPUT  
RELAY  
OUTPUT  
FLOATING  
OUTPUT  
LonWorks  
BUS  
MODULES  
XFLR822AU  
XFL822AU  
XFLR824AU  
XFL824AU  
XFL821AU  
XFL823AU  
PANEL  
BUS  
MODULES  
XFR822AU  
XF822AU  
XFR824AU  
XF824AU  
XFR825AU  
XF821AU  
XF823AU  
XS821-22  
XS823  
XS824-25  
XCL8010AU  
CONTROLLER MODULE  
LonWorks or Panel Bus  
Fig. 2. Overview of I/O modules and terminal sockets  
EN1B-0410GE51 R0908A  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Excel 800  
Description of the XCL8010AU Controller Module  
Description of the XCL8010AU Controller Module  
Overview  
PC or HMI  
EXCELON  
I/O MODULES  
NO CONNECTION  
LonWorks BUS  
C-BUS  
Fig. 3. Connections to the XCL8010AU Controller  
Legend  
1
2
3
4
5
6
7
8
9
Power supply for I/O modules  
I/O Bus communication terminals  
LONWORKS interface  
LONWORKS service button  
LONWORKS service LED  
C-Bus Tx LED  
C-Bus Rx LED  
Reset button  
HMI interface (for field use, only)  
10 Alarm LED  
11 Power LED  
12 Power supply terminals  
13 Alarm/watchdog outputs  
14 NO CONNECTION  
15 S2 I/O Bus switch  
16 S1 C-Bus termination switch  
17 C-Bus terminals  
Fig. 4. XCL8010AU Controller Module front details  
18 LONWORKS terminals  
7
EN1B-0410GE51 R0908A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Description of the XCL8010AU Controller Module  
Excel 800  
24 VAC CONTROLLER  
POWER SWITCH  
120 VAC, 60 HZ  
LINE INPUT  
FUSE F1 (2 AMPS) PART NUMBERS ARE AS FOLLOWS:  
2 AMP  
F1  
–HONEYWELL PART NO. 14000485-007  
(AVAILABLE FROM HONEYWELL BRANCH LOCATIONS, ONLY)  
–BUSSMAN PART NO. AGC-2  
CONTROLLER  
POWER  
*
ON  
H
N
G
–LITTLEFUSE PART NO. 312002  
OFF  
MAIN LINE VOLTAGE  
120 VAC, 60 HZ  
TERMINAL  
CONNECTED TO A GOOD  
EARTH GROUND.  
G
MUST BE  
CONTROLLER  
SUPPLY  
24VAC  
48VA  
~
MUST BE WIRED  
TO EARTH GROUND  
G
14507063-002 POWER CABLE  
(incl. with 14507287 power modules  
14507287-001 through -003, only.)  
G
MUST BE  
UNSWITCHED  
UNFILTERED  
120 VAC  
WIRED TO EARTH GROUND  
BRN  
GRN  
CONNECTOR TO  
XL800 CONTROLLER  
J5  
BLK  
CONNECTORS ARE KEYED TO  
PREVENT MISALIGNMENT.  
* 14507287-001 POWER TERMINALS LABELED H-N-G.  
CONVENIENCE OUTLET  
(UNFILTERED, UNSWITCHED)  
-001 = 120 VAC, 10 AMP  
Fig. 5. Typical 14507287-001 Power Module wiring  
24 VAC CONTROLLER  
POWER SWITCH  
120 VAC, 60 HZ  
LINE INPUT  
120 VAC, 60 HZ  
LINE INPUT  
24VAC ACCESSORY  
POWER -002 AND -003  
MODELS (4 AMP MAX.)  
2 AMP  
5 AMP  
F2  
CONTROLLER  
F1  
POWER  
*
ON  
ON  
H
N
G
OFF  
OFF  
~
MAIN LINE VOLTAGE  
120 VAC, 60 HZ  
2 AMP  
F3  
TERMINAL  
G  
MUST BE  
CONTROLLER  
SUPPLY  
24VAC  
CONNECTED TO A GOOD  
EARTH GROUND.  
MUST BE WIRED  
TO EARTH GROUND  
48VA  
~
G
14507063-002 POWER CABLE  
(incl. with 14507287 power modules  
14507287-001 through -003, only.)  
24 VAC ACCESSORY POWER  
-002 MODEL, ONLY. 2 AMP MAX.  
G
MUST BE  
WIRED TO EARTH GROUND  
FOR 14507287-003 (24VDC)  
FOR 14507287-002 (24VAC)  
BRN  
GRN  
BRN GRY BRN GRY  
RED BRN GRY GRY  
CONNECTOR TO  
XL800 CONTROLLER  
J5  
BLK  
UNSWITCHED  
UNFILTERED 120 VAC  
CONNECTORS ARE KEYED TO  
PREVENT MISALIGNMENT.  
* 14507287-001 POWER TERMINALS LABELED H-N-G.  
CONVENIENCE OUTLET  
(UNFILTERED, UNSWITCHED)  
-002 AND -003 = 10 AMP  
FUSE NO. FUSE RATING  
HONEYWELL PART NO.  
BUSSMAN PART NO.  
LITTLEFUSE PART NO.  
POWER MODULE  
14507287-001 THROUGH -003  
14507287-002 AND -003  
14507287-002 AND -003  
F1  
F2  
F3  
2 AMPS  
5 AMPS  
2 AMPS  
14000485-007  
14507374-001  
14000485-007  
AGC-2  
312002  
GMA 5AMP  
AGC-2  
235005  
312002  
Fig. 6. Typical 14507287-002, -003 Power Module wiring  
EN1B-0410GE51 R0908A  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Excel 800  
Description of the XCL8010AU Controller Module  
CONTROLLER TRANSFORMER  
GRN  
G 70  
CONTROLLER  
SUPPLY 24 VAC  
48 VA  
BRN  
~
71  
72  
BLK  
1
3
4
BLK  
24 V 50 VA  
H
N
G
14507351-001  
429P156A  
E1A 1052 XXXX  
WHT  
GRN  
COM 120 V  
1
2
MAIN LINE (120 VAC, 60 Hz)  
TERMINAL “G” MUST BE  
CONNECTED TO A GOOD  
EARTH GROUND.  
1
MECHANICALLY SECURED TO SUBPANEL WITH MOUNTING SCREW  
1
Fig. 7. Typical 14507287-007 Power Module wiring  
I/O Module Overview  
Table 5. Overview of I/O modules  
description inputs outputs manual controls  
Panel Bus  
module  
LONWORKS  
LEDs 1)  
Bus module  
XFL821AU  
XFL822AU  
XF821AU  
XF822AU  
Analog Input Module  
Analog Output Module  
8
8
8 status LEDs  
XFR822AU XFLR822AU Analog Output Module  
8
8 manual overrides 8 status LEDs  
XF823AU  
XF824AU  
XFL823AU  
XFL824AU  
Binary Input Module  
Relay Output Module  
12  
12 status LEDs  
6 status LEDs  
6 2)  
6 2)  
3
XFR824AU XFLR824AU Relay Output Module  
XFR825AU Floating Output Module  
6 manual overrides 6 status LEDs  
3 manual overrides 3 pairs of status LEDs  
1) In addition to the power LED and service LED  
2) Changeover outputs  
9
EN1B-0410GE51 R0908A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Description of the XCL8010AU Controller Module  
Excel 800  
Corresponding Terminal Sockets  
Technical Data  
Table 6. I/O modules and corresponding terminal sockets  
System Data  
I/O module  
socket  
scope of delivery  
1 terminal socket,  
1 bridge connector  
1 swivel label holder  
Table 7. System data  
XF821AU,  
XFL821AU  
Operating voltage  
24 VAC/DC, 60 Hz  
Max. 3.57 A  
(1 XCL8010AU Controller  
+ 16 I/O modules)  
XF822AU,  
XS821-22  
Power consumption  
XFL822AU,  
XFLR822AU,  
XFR822AU  
1 terminal socket,  
1 bridge connector  
1 swivel label holder  
XF823AU,  
XFL823AU  
Operational Environment  
XS823  
Table 8. Operational environment  
XF824AU,  
1 terminal socket,  
ambient operating  
temperature  
0 49 °C (32 122 °F)  
XFL824AU,  
XFLR824AU,  
XFR824AU  
1 bridge connector  
1 swivel label holder  
1 long cross connector  
XS824-25  
ambient operating  
humidity  
5 93 % rel. humidity  
(non-condensing)  
XFR825AU  
ambient storage  
temperature  
–20 +70 °C (–4 +158 °F)  
Interfaces and Bus Connections  
ambient storage  
humidity  
5 95 % rel. humidity  
(non-condensing)  
The Excel 800 System can be connected to the following  
devices and systems:  
Smoke Control Configuration  
Panel Bus  
SMOKE CONTROL CONFIGURATION  
For communication with up to 16 Panel Bus I/O modules  
Polarity-insensitive  
9
XL800  
AO  
SUPPLY  
FAN  
4
LonWorks Bus  
AIRFLOW SENSOR  
UL-LISTED  
FIRE ALARM  
CONTROL UNIT  
11  
For communication with other LONWORKS Bus devices  
8
AO  
EXHAUST  
FAN  
within the building  
5
12  
FTT10, link power compatible  
Polarity-insensitive  
AO  
FIREFIGHTERS’  
SMOKE CONTROL  
PANEL (FSCS)  
DAMPER  
2
3
VERIFICATION  
14505068  
AUDIBLE  
ANNUNCIATOR  
C-Bus  
1
For communication with other controllers  
STATUS CONTROL  
10  
6
7
HMI  
Fig. 8. Typical smoke control configuration  
NOTES:  
For connecting an operator interface, e.g., XI582 or a  
laptop, e.g., for CARE  
1
Locate and configure per NFPA 92A, Section 3-4.3.4.  
UL-listed annunciator / FSCS panel switches have a  
minimum rating of 24 V, 1/10 Amp, and lamps / LEDs  
have a rating of 24 V, limited to 50 mA.  
Modem  
NO CONNECTION  
2
3
Locate so as to minimize control wiring and piping.  
Avoid running wires or piping through areas that have  
a high fire risk.  
Locate per UL 555S.  
EN1B-0410GE51 R0908A  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Excel 800  
Description of the XCL8010AU Controller Module  
4
Locate separate from and below all building exhaust  
fans and upstream of any prevailing winds.  
CAUTION  
Risk of electric equipment damage!  
5
6
7
Exhaust to outside of building.  
Locate airflow differential switch.  
Failure to use listed/approved replacement parts can  
damage product, degrade operation and result in loss of  
safety function.  
This product must be installed and operated within its  
environmental, mechanical, and electrical specifications as  
contained in this document.  
Locate UL-listed damper pressure / position indicator  
per damper installation instructions.  
8
Smoke control must be initiated by a listed fire alarm  
control unit or in zone automatic alarm devices and not  
devices located outside of the smoke control zone.  
Interconnecting wiring must be within 20 ft. (6 meters)  
and in conduit.  
When servicing, use only listed/approved replacement  
parts ordered directly from the manufacturer.  
Typical Power Limited Circuit for XL800  
9
Refer to NFPA 92A.  
POWER  
LIMITED  
POWER  
LIMITED  
10  
Verify that the AC voltage source connected to the  
inside of the main line voltage terminal block is from a  
UL-1481 listed uninterruptible power supply. The main  
line voltage terminal block maximum current draw is  
0.5 A. For 220/240 VAC (60 Hz) applications, verify  
that no potential between any conductor and the earth  
ground exceeds 150 VAC.  
NON-POWER  
LIMITED  
2
ANALOG INPUT  
MODULE  
ANALOG OUTPUT  
MODULE  
DIGITAL INPUT  
MODULE  
DIGITAL OUTPUT  
MODULE  
CPU  
POWER LIMITED  
24VAC  
CONTROL  
24VAC  
ACCESSORY  
24VAC  
NON-POWER  
LIMITED  
2
3
2
11  
12  
All external LONWORKS bus field wiring must be limited  
to 4000 ft. (1200 meters) and be terminated to  
14506944-001 transient protector (35 V, 290 mA max.)  
except C-Bus field wiring communicating at 1 MHZ,  
which uses 14502412-014 transient protector (19 V,  
500 mA).  
1
1
NON-POWER  
LIMITED  
NON-POWER  
LIMITED  
Fig. 9. Typical power-limited circuit for XL800  
Panel Bus wiring must be in the same enclosure or  
less than 20 ft. to adjacent enclosure. No protection is  
required.  
1
2
14507287-001 through -003 power module accessory  
24 VAC output (rated 2A) must be wired in accordance  
with NFPA 70, Article 725 when routed within the  
cabinet or adjacent cabinets and also for external field  
wiring.  
Data File Set-Up  
Generate the engineering data file for the XL800 Series  
Controllers. This data file has a mix of hardware points for the  
necessary inputs and outputs to control fans, dampers, and  
other equipment. In addition to the inputs and outputs, a  
custom control program is written to control the outputs per  
the sequence. The XL800 controllers can reset the program  
once the data from the operator interface indicates a normal  
condition for the dedicated smoke control equipment. Wire  
conditions must be programmed to provide annunciation of  
trouble conditions.  
14507287-001, -002, -003, and -007 control power  
module 24 VAC output is inherently power-limited.  
Thus, all sourced power from the XL800 controller is  
power-limited. All field wiring from these controllers  
meet NFPA 70, Article 725 power limited Class II  
requirements.  
3
4
If a separate auxiliary power-limited 24 VAC power  
source is required, use a control power module  
(14507287-001 or -007 control supply).  
Also required for a dedicated application for the XL800, is a  
weekly time program to test control points, fans, and dampers  
by exercising the equipment and verifying feedback  
automatically during low building activity periods.  
Devices must be installed in areas as shown. All cable  
must be routed as shown. All internal power-limited  
wiring must be separated by ¼ inch (6 mm) or barrier  
from non-power-limited wire. Excess wiring must be  
cut, trimmed, and dressed properly to ensure that  
proper clearances are maintained.  
Panel Reset  
When in Smoke Control Mode, panel reset is accomplished  
by resetting the initiating panel contact circuit or by the  
separate initiating/reset switch on the FSCS panel.  
Connecting Single Bus Controller Systems  
This section describes how to connect a controller system  
which uses Panel Bus I/O modules, only or LONWORKS Bus  
I/O modules, only.  
11  
EN1B-0410GE51 R0908A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Description of the XCL8010AU Controller Module  
Excel 800  
XCL8010AU, I/O Modules on Single Rail  
Connect XCL8010AU Controller Module and I/O modules  
ROOM 1  
using the bridge connectors.  
75  
76  
77  
78  
This provides power supply and communication connection.  
No further wiring is necessary.  
LonWorks  
I/O MODULE  
LonWorks  
I/O MODULE  
XCL8010AU  
1 2  
Multiple Rails in Single Cabinet  
The multiple rails of a controller system are connected in  
series.  
Connect the rail ends as follows:  
Power supply  
via power supply terminals 73, 74 or 77, 78  
ROOM 2  
Communication  
75  
76  
77  
78  
via communication terminals 71, 72 or 75, 76  
LonWorks  
I/O MODULE  
LonWorks  
I/O MODULE  
LonWorks  
I/O MODULE  
73  
74  
71  
72  
I/O MODULE  
73  
74  
71  
72  
73  
74  
75  
76  
77  
78  
Fig. 11. Wiring the LONWORKS Bus I/O modules in  
separate rooms  
I/O MODULE I/O MODULE I/O MODULE  
71  
72  
73  
74  
75  
76  
77  
78  
Maximum Cable Length  
I/O MODULE XCL8010AU I/O MODULE  
1 2  
Max. cable length: 1200 meters (4000 ft), supervised.  
71  
72  
73  
74  
I/O MODULE  
How to Connect Panel Bus and LONWORKS  
Bus Mixed Controller Systems  
Connecting I/O Modules  
For connecting the I/O modules with each other, proceed as  
described for single-bus controller systems.  
Connecting I/O Modules to the XCL8010AU  
Panel Bus I/O Modules  
Fig. 10. Wiring the power supply and the communication  
lines to the I/O modules  
Connect communication terminals 71 74 or 75 78 of  
Panel Bus I/O modules to communication terminals 71 ─  
74 or 75 78 of the XCL8010AU Controller Module using  
either  
LonWorks Bus I/O Modules in Separate Rooms  
In this scenario, only communication lines must be connected  
between the rooms.  
– Bridge connectors  
for flush mounting on a single DIN rail or  
Connect the last module of room 1 to the first module of  
– Cables  
room 2:  
for separate mounting, e.g., on multiple rails, separate  
cabinets, etc.  
– via communication terminals 71, 72 or 75, 76  
LONWORKS Bus I/O Modules  
Connect communication terminals 71 74 or 75 78 of  
LONWORKS Bus I/O modules to LONWORKS terminals 11 ─  
14 of the XCL8010AU using cables.  
EN1B-0410GE51 R0908A  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Excel 800  
Description of the XCL8010AU Controller Module  
Panel Bus modules  
Panel Bus modules  
71  
72  
73  
74  
75  
76  
77  
78  
71  
72  
73  
74  
75  
76  
77  
78  
71  
72  
73  
74  
75  
76  
77  
78  
XCL8010AU  
11  
12  
13  
14  
1
2
3
4
LonWorks Bus modules  
71  
72  
73  
74  
75  
76  
77  
78  
Fig. 12. Mixed bus system – correct wiring  
Panel Bus modules  
LonWorks Bus modules  
71  
72  
73  
74  
78  
71  
72  
73  
74  
75  
76  
77  
78  
4  
75  
76  
77  
78  
XCL8010AU  
11  
12  
13  
1
2
3
Fig. 13. Mixed bus system – incorrect wiring  
Use the rotary HEX switch to set the address to the one  
Setting Address of Panel Bus I/O Modules  
already defined during engineering.  
Each Panel Bus I/O module is assigned its own unique  
address. For the sake of clarity for maintenance personnel, it  
is recommended that you address the Panel Bus I/O modules  
in ascending order 0 through F.  
Table 9. HEX switch settings and addresses  
HEX switch  
address  
0
1
2
3
4
5
6
7
01 02 03 04 05 06 07 08  
HEX switch  
address  
8
9
A
B
C
D
E
F
09 10 11 12 13 14 15 16  
13  
EN1B-0410GE51 R0908A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mounting/Dismounting Modules  
Excel 800  
LONWORKS Bus Topologies  
The LONWORKS Bus is a 78-kilobit serial link that uses  
transformer isolation so that the bus wiring does not have a  
polarity. I.e. it is not important which of the two LONWORKS  
Bus terminals are connected to each wire of the twisted pair.  
4
LOCK  
The LONWORKS Bus does not need to be shielded on the  
controller module side.  
The LONWORKS Bus can be wired in daisy chain, star, loop or  
any combination thereof as long as the maximum wire length  
requirements are met.  
Configuration  
The recommended configuration is a daisy chain with two bus  
terminations. This layout allows for max. LONWORKS Bus  
lengths, and its simple structure presents the least number of  
possible problems, particularly when adding on to an existing  
bus.  
Fig. 14. HEX switch location  
NOTE:  
If the HEX switch setting is changed, the Panel  
Bus I/O module will revert to its default  
configuration. With LONWORKS Bus I/O modules,  
the HEX switch is without function.  
C-Bus Topologies  
Via the C-Bus up to 30 C-Bus devices (e.g., controllers, etc.)  
can communicate with one another and a PC central. The C-  
Bus must be connected via the individual controllers (open  
ring).  
Setting the I/O Bus Switch  
Set the I/O Bus switch S2 of the XCL8010AU Controller  
Module depending on the modules connected to terminals  
71 78 and the desired communication as follows:  
NOTE:  
Star connection is not allowed because  
uncontrollable line reflections may occur.  
Table 10. I/O Bus switch settings  
communication  
S2 setting  
terminals  
Mounting/Dismounting Modules  
LONWORKS Bus  
only  
LON  
71 74 LONWORKS Bus  
75 78 LONWORKS Bus  
11 14 LONWORKS Bus  
WARNING  
Risk of electric shock or equipment damage!  
Panel Bus and  
LONWORKS Bus  
Panel  
71 74 Panel Bus  
75 78 Panel Bus  
11 14 LONWORKS Bus  
Do not touch any live parts in the cabinet.  
Disconnect the power supply before you start to install the  
Excel 800 System.  
More than one disconnect switch may be required to de-  
energize the system.  
Do not reconnect the power supply until you have  
completed the installation.  
NOTE:  
The terminal socket of each I/O module can be  
mounted and wired before inserting and locking  
the corresponding electronic module.  
Fig. 15. S2 I/O Bus switch  
EN1B-0410GE51 R0908A  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Excel 800  
Mounting/Dismounting Modules  
Mounting/Dismounting Controller/Sockets  
Mounting Sockets  
NOTE:  
When using both Panel Bus and LONWORKS Bus  
I/O modules in an Excel 800 System, group both  
Panel Bus modules (light-gray) and LONWORKS  
Bus I/O modules (dark-gray), e.g., on different  
rails. Up to 10 Panel Bus I/O modules can be  
mounted to one side of the XCL8010AU. In total,  
up to 16 Panel Bus I/O modules can be mounted  
to one controller. The XCL8010AU Controller  
Module is mounted on the DIN rail in the same way  
as a terminal socket.  
Panel  
Panel  
Panel  
Panel  
XCL8010AU  
BUS I/O BUS I/O  
BUS I/O BUS I/O  
max. 10  
max. 10  
max. 16  
Fig. 18. Mounting terminal sockets  
NOTE:  
Take care to not bend the Omega clamp, which  
serves to establish the electrical contact with the  
DIN rail and which located on the back of the  
terminal socket.  
Fig. 16. Max. number of Panel Bus I/O modules  
LonWorks LonWorks  
BUS I/O BUS I/O  
LonWorks LonWorks  
XCL8010AU  
Connecting Sockets  
BUS I/O BUS I/O  
Controller and terminal sockets on the same DIN rail can be  
connected mechanically and electrically with bridge  
connectors.  
max. 10  
max. 10  
max. 20  
NOTE: MAX. OF 16 DIGITAL INPUT MODULES MAY BE USED.  
Controller and terminal sockets on different DIN rails must be  
connected using cables.  
Fig. 17. Max. number of LONWORKS Bus I/O modules with  
power supply via XCL8010AU  
NOTICE  
Angle the terminal socket at the upper edge of the DIN rail  
until it snaps in.  
Risk of malfunction!  
Swing the terminal socket down and apply gentle force  
Wire Panel Bus I/O modules and LONWORKS Bus  
until it snaps into position with an audible "click".  
I/O modules separately.  
Position XCL8010AU Controller Module and terminal  
When using both Panel Bus and LONWORKS Bus  
I/O modules in an Excel 800 System, LONWORKS Bus  
I/O modules must be connected to the XCL8010AU  
Controller Module via LON terminals 11 14.  
sockets flush with one another along the rail.  
If desired, mount stoppers at the ends of the rail to prevent  
sliding.  
Position the bridge connector on terminals 71 74 of the  
right hand terminal socket or XCL8010AU Controller Module  
and on terminals 75 78 of the left hand terminal socket or  
XCL8010AU Controller Module. Then press the bridge  
connector down.  
15  
EN1B-0410GE51 R0908A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mounting/Dismounting Modules  
Excel 800  
Fig. 21. Releasing latch  
Fig. 19. Connecting terminal sockets with bridge  
connector  
Mounting/Dismounting Electronic Modules  
NOTE:  
Bridge connectors transmit both communication  
signals and power supply between modules.  
Removing bridge connectors will interrupt the  
transmission of both communication signals and  
power supply between the modules.  
Mounting Electronic Modules  
NOTE:  
Electronic modules can be removed from the  
socket or inserted into the sockets without  
switching off the power supply. The behavior of  
connected field devices must be taken into  
consideration.  
Dismounting Sockets  
Disconnecting Sockets  
Make sure that terminal socket und I/O module match.  
Release all bridge connectors before removing the  
XCL8010AU Controller Module and/or the terminal sockets  
from the DIN rail.  
Make sure that the red locking mechanism is in the open,  
i.e., left, position.  
Gently push the electronic module onto the terminal socket  
until snug.  
Press down at the same time both the gray side wings next  
to the red button and then pull the bridge connector out of  
the module.  
Fig. 22. Inserting the electronic module  
Fig. 20. Releasing bridge connectors  
Lock the red locking mechanism by sliding it to the right.  
Dismounting Controller/Terminal Sockets  
Insert a screwdriver into the latch on the underside of the  
module and lever the red latch 2–3 mm downwards. The  
module can then be swung away from the rail.  
EN1B-0410GE51 R0908A  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Excel 800  
Mounting/Dismounting Modules  
Setting the C-Bus Termination Switch  
Set the C-Bus termination switch S1 appropriately.  
Fig. 23. Locking the electronic module  
Fig. 25. C-Bus termination switch S1  
NOTE:  
The red locking mechanism will not close if the  
electronic module is not properly mounted.  
Table 11. XCL8010AU C-Bus termination switch settings  
Dismounting Electronic Modules  
switch setting  
baud rate  
S1  
NOTE:  
Electronic modules can be removed from the  
socket or inserted into the sockets without  
switching off the power supply. The behavior of  
connected field devices must be taken into  
consideration.  
9.6k all  
76k mid  
76k end  
Up to 9600 baud (default setting)  
Up to 76800 baud without bus termination  
Up to 76800 baud with bus termination  
Open the red locking mechanism by sliding it to the left  
and then gently pull the electronic module out of the  
terminal socket.  
Shielding  
In principle, data transmitting cables should be shielded in  
case of RFI.  
On the controller side, connect the shield to terminals 7  
and 10.  
On the side of the device, connect the shield to the  
respective terminals.  
Do not connect it to the cabinet ground or any other  
ground points.  
Connecting HMIs or Laptops  
Laptops or HMIs, e.g., XI582, can either be connected via the  
HMI interface of the XCL8010AU Controller Module or via the  
LONWORKS interface.  
Fig. 24. Dismounting the electronic module  
Connecting via C-Bus  
Connecting the XI582 Operator Interface  
Via C-Bus, an XCL8010AU Controller Module can be  
connected to other controller systems to form a network.  
Connect the XI582AH Operator Interface to the HMI  
interface or LONWORKS interface of the XCL8010AU  
Controller Module by means of  
– the XW882 cable or  
Connecting to the Controller  
Connect the C-Bus to the XCL8010AU Controller Module  
– the XW582 cable connected with an XW586 cable.  
as follows:  
– Input to C-Bus terminals 8 and 9  
– Output to C-Bus terminals 5 and 6  
– Do not connect the C-Bus to the cabinet earth or any  
other earth ground points  
17  
EN1B-0410GE51 R0908A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mounting/Dismounting Modules  
Excel 800  
Connecting Laptops (XL-Online/CARE)  
Connect a laptop (on which e.g., XL-Online or CARE has  
been installed) to the HMI interface or LONWORKS interface  
of the XCL8010AU Controller Module by means of  
Features  
LONWORKS Interface and Terminals  
The XCL8010AU Controller Module features  
– the XW885 cable or  
An RJ45 socket serving as an interface  
– the XW585 cable connected with an XW586 Cable.  
to connect laptops or HMIs to the LONWORKS Bus  
LONWORKS terminals 11, 12, 13, and 14  
to connect LONWORKS Bus I/O modules or other  
LONWORKS devices to the XCL8010AU Controller or other  
LONWORKS controllers.  
XCL8010AU Terminals  
71 COM  
75  
76  
77  
78  
COM  
A
A
72 COM  
COM  
B
24  
V~  
24  
V~0  
B
24  
73  
74  
V~  
24  
V~0  
87 65 4 3 21  
11 LON  
1
2
3
4
24  
V~  
24  
V~0  
24  
V~0  
1
12 LON  
8
9
C+  
5
6
7
C+  
2
LON  
13  
14  
C-  
C-  
1
LON  
2
SHIELD  
SHIELD  
NC  
10  
*
*Watch Dog  
Relay  
Fig. 27. LONWORKS interface and LONWORKS terminals  
Fig. 26. Terminal assignment and internal connections of  
the XCL8010AU Controller Module  
LONWORKS Interface Signals on RJ45 Socket  
Table 13. Signals of LONWORKS interface  
Table 12. Description of XCL8010AU terminals  
ter-  
pin  
signal type  
Connection to LONWORKS Bus  
Connection to LONWORKS Bus  
Not used  
1
signal  
comment  
minal  
2
2-wire communication bus  
(LON/Panel Bus)  
71, 75 COM a  
72, 76 COM b  
3 8  
2-wire communication bus  
(LON/Panel Bus)  
LONWORKS Service LED and Button  
The XCL8010AU Controller Module is equipped with a  
LONWORKS service button and corresponding LONWORKS  
Service LED (status: yellow/OFF).  
73, 77 24 V~ Power supply for I/O modules  
74, 78 24 V~0 Power supply for I/O modules  
1
2
24 V~ Power supply from transformer  
24 V~0 Power supply from transformer  
24 V~0 Alarm/watchdog output  
3
LON  
4
NC  
C+  
C-  
Alarm/watchdog output  
5, 8  
6, 9  
7, 10  
11, 12  
13, 14  
C-Bus  
C-Bus  
Shield C-Bus shield  
LON  
LON  
LONWORKS IN  
1 2  
LONWORKS OUT  
Fig. 28. LONWORKS service button (1) and service LED (2)  
See also section "Troubleshooting" on page 31.  
EN1B-0410GE51 R0908A  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Excel 800  
Mounting/Dismounting Modules  
C-Bus Tx LED and Rx LED  
HMI Interface  
The XCL8010AU Controller Module is equipped with a Tx  
LED (status: yellow/OFF) and an Rx LED (status:  
yellow/OFF).  
The XCL8010AU Controller Module is equipped with an HMI  
Interface for the connection of HMIs, e.g., XI582 Operator  
Interface or a laptop (with XL-Online/CARE).  
C-Bus  
1
2
Fig. 29. C-Bus Tx LED (1) and Rx LED (2)  
Fig. 31. HMI interface, Tx LED (1) and Rx LED (2)  
C-Bus LEDs  
HMI interface LEDs on RJ45 socket  
Table 15. HMI interface LEDs  
Table 14. Controller C-Bus LEDs  
Tx (1)  
flickering  
The controller is sending data onto the  
C-Bus  
Tx (1)  
flickering  
The controller is transmitting data to the HMI  
The controller is receiving data from the HMI  
Rx (2)  
flickering  
The controller is receiving data from the  
C-Bus  
Rx (2)  
flickering  
Reset Button  
The XCL8010AU Controller Module is equipped with a reset  
button.  
HMI interface Signals on RJ45 socket  
Table 16. Signals of the HMI interface  
pin  
signal type  
1
2
3
4
5
6
7
8
-
RESET  
Receive  
Transmit  
-
Signal ground  
-
1
5 V  
-
Fig. 30. Reset button (1)  
NOTICE  
Pushing the reset button (1), e.g. using a paperclip, will cause  
the XCL8010AU Controller Module to reset.  
Equipment damage!  
NOTE:  
In the event of a reset, all non-volatile memory  
contents are permanently deleted, though the  
clock will not be set to zero. In order to avoid  
problems, we therefore recommend that you  
always save your application changes (e.g., time  
program changes) to FLASH memory.  
If earth grounding is required, make sure that only terminal  
2 is connected to earth ground. Terminal 1 must not be  
connected to earth ground. See also Appendix 1.  
19  
EN1B-0410GE51 R0908A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mounting/Dismounting Modules  
Excel 800  
Alarm and Power LEDs  
Watchdog Status  
The XCL8010AU Controller Module is equipped with an alarm  
LED and a power LED.  
Table 19. Watchdog status (terminal 4)  
status  
Failure (= alarm)  
Normal operation  
signal on terminal 4  
24 V  
0 V  
Modem Interface  
NO CONNECTION.  
I/O Bus Switch S2  
The XCL8010AU Controller Module features a 2-position I/O  
Bus switch S2.  
I/O Bus switch S2 must be set in accordance with the kind of  
I/O modules connected to communication terminals 71, 72  
and 75, 76 of the XCL8010AU Controller Module.  
Fig. 32. Alarm LED (1) and power LED (2)  
Terminals 71, 72 and 75, 76 must be all connected either to  
Panel Bus I/O modules or to LONWORKS Bus I/O modules.  
Alarm LED (1, red)  
The default setting is Panel.  
Table 17. Controller alarm LED  
Off  
On  
Normal operation  
Watchdog alarm output is powered  
The controller has encountered a hardware  
problem  
The application has a fault  
The controller has been powered up without  
an application or the operator has manually  
stopped the application.  
In this case, the LED will light up 13 minutes  
after power-up without application  
Flashing  
The watchdog alarm output has not yet been  
powered, although the controller has  
encountered a problem.  
Fig. 33. I/O Bus switch S2  
The controller performs a warm start.  
Table 20. I/O Bus switch settings  
If problem persists, the LED will become lit  
constantly, see above.  
communication  
LONWORKS Bus only  
S2 setting  
LON  
Panel  
See section "Troubleshooting" on page 31.  
Panel Bus and LONWORKS Bus  
Power LED (2, green)  
Table 18. Controller power LED  
LONWORKS BUS modules connected to  
terminals 11 14 of the XCL8010AU  
Controller Module  
On  
Normal operation  
Panel Bus connected to terminals 71, 72 or Panel  
75, 76 of the XCL8010AU Controller  
Module  
Flashing  
One or more of the internal voltage supplies  
are outside of the permissible ranges.  
The controller stops operation.  
Check wiring or see section  
"Troubleshooting" on page 31.  
Goes out  
briefly  
The operator has activated the reset  
button  
The controller is performing a warm start  
EN1B-0410GE51 R0908A  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Excel 800  
Description of the I/O Modules  
C-Bus Termination Switch S1  
The XCL8010AU Controller Module features a 3-position C-  
Bus termination switch S1.  
Description of the I/O Modules  
Common Features  
This switch must be set in accordance with the given C-Bus  
configuration.  
Switches Located on the Terminal Socket  
Table 23. Terminal socket switches  
feature  
function  
Service button  
S1  
LED test, see section "Troubleshooting"  
on page 31  
LONWORKS service button functionality  
for LONWORKS Bus I/O modules  
Hex switch S2  
Module addressing for Panel Bus  
I/O modules  
LEDs Located on the I/O Module  
Table 24. LEDs on I/O module  
Fig. 34. C-Bus termination switch  
feature  
function  
Table 21. XCL8010AU C-Bus termination switch S1  
settings  
Service LED  
(yellow)  
Service information, see section  
"Troubleshooting" on page 31  
switch setting  
baud rate  
S1  
Power LED  
(green)  
Information on power supply, see section  
"Troubleshooting" on page 31  
9.6k all  
Up to 9600 baud (default setting)  
76k mid  
Up to 76800 baud without bus termination  
For the location of these elements, see figures of the  
respective modules.  
Up to 76800 baud with bus termination  
controller at the end of the C-Bus  
76k end  
Memory  
Table 22. XCL8010AU memory  
memory  
size  
usage  
SRAM  
512 KB For controller application,  
modem trend and firmware  
RACL application: 128 KB  
Total application: 192 KB  
Flash  
2 MB  
Firmware (1 MB) and application  
(1 MB) storage  
EPROM  
128 KB For bootstrap loader  
NOTE:  
The XCL8010AU Controller Module does not  
contain a battery. RAM (data and realtime  
clocktime) is buffered for 3 days by a super  
capacitor.  
21  
EN1B-0410GE51 R0908A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Description of the I/O Modules  
Excel 800  
Terminals  
Analog Input Modules  
COM  
75  
A
COM  
76  
B
71 COM  
A
Types of Analog Input Modules  
72 COM  
B
24  
24  
77  
V~  
24  
78  
V~0  
73  
Table 25. Excel 800 Analog Input Modules  
V~  
24  
V~0  
74  
type  
XF821  
XFL821  
description  
housing  
Panel Bus Analog Input Module light-gray  
VAUX VAUX  
AI1 AI2 AI3 AI4 AI5 AI6 AI7 AI8  
LONWORKS Bus Analog Input  
Module  
dark-gray  
light-gray  
21 22  
1
2
3
4
5
6
7
8
XS821-822 terminal socket  
GNDGND  
GNDGNDGNDGND GND GND GND GND  
9
10  
11 12 13 14 15 16 17 18  
25 26  
Features  
8 analog inputs  
Fig. 36. Terminal assignment and internal connections of  
Analog Input Modules  
Sensor-break and short-circuit detection, see section  
"Troubleshooting" on page 31.  
Table 26. Description of Analog Input Module terminals  
ter-  
signal  
comment  
minal  
2-wire communication bus  
(LON/Panel Bus)  
71, 75  
COM a  
COM b  
2-wire communication bus  
(LON/Panel Bus)  
72, 76  
73, 77  
74, 78  
1 8  
24 V~  
Power supply  
Power supply  
24 V~0  
AI1 AI8 Analog inputs 1 8  
Ground. All grounds are connected  
9 18  
GND  
internally to each other  
Auxiliary voltage signal (used e.g. for  
10 VDC / supplying setpoint potentiometers).  
21, 22  
5 mA  
Connections to these terminals  
must be made in the same room.  
Fig. 35. XF821AU Analog Input Module with terminal  
socket  
Shield connection (functional earth),  
internally connected to the DIN rail  
25, 26  
Legend  
NOTE:  
Shield connection to be used for shielded I/O  
cables only. It is not allowed to connect a  
LONWORKS shield.  
1
2
3
4
Service button S1  
Hex switch S2  
Service LED  
Power LED  
Functionality of service LED and power LED: see Table 42  
and following.  
EN1B-0410GE51 R0908A  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Excel 800  
Description of the I/O Modules  
XFL821AU Connection Examples  
400 OHM  
1
18 25  
2
1
12 25  
SHIELD  
SHIELD  
1
2
2
0(4) to 20 mA  
0 to 10 V  
0(4) to 20 mA (VIA EXTERNAL  
500 OHM RESISTOR).  
0 TO 10 VDC  
5
14 22 25  
3
1
13 25  
SHIELD  
SHIELD  
10 11 12  
2
VMP  
Pt1000 NTC20kW  
Fig. 37. XFL821AU Analog Input Module  
23  
EN1B-0410GE51 R0908A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Description of the I/O Modules  
Excel 800  
Terminals  
Analog Output Modules  
Types of Analog Output Modules  
Table 27. Excel 800 Analog Output Modules  
type  
XF822  
description  
housing  
Panel Bus Analog Output  
Module  
light-gray  
XFR822  
XFL822  
Panel Bus Analog Output  
Module with manual overrides  
light-gray  
dark-gray  
dark-gray  
light-gray  
LONWORKS Bus Analog Output  
Module  
XFLR822  
XS821-22  
LONWORKS Bus Analog Output  
Module with manual overrides  
Fig. 39. Terminal assignment and internal connections of  
the Analog Output Modules  
terminal socket  
Table 28. Description of the Analog Output Module  
terminals  
Features  
8 analog outputs;  
ter-  
can also be configured per output as binary outputs  
signal  
comment  
minal  
(0 10 V, 2 10 V, ON/OFF, or floating)  
Corresponding output status LEDs (red)  
2-wire communication bus  
(LON/Panel Bus)  
71, 75  
COM a  
COM b  
XFR822AU/XFLR822AU: 8 manual overrides, see figure  
2-wire communication bus  
(LON/Panel Bus)  
below  
72, 76  
73, 77  
74, 78  
24 V~  
Power supply  
Power supply  
24 V~0  
1 8 AO1 AO8 Analog outputs 1 8  
Ground. All grounds are connected  
internally to each other  
9 18  
21, 22  
25, 26  
GND  
N.C.  
Do not use!  
Shield connection (functional earth),  
internally connected to the DIN rail  
NOTE:  
Shield connection to be used for shielded I/O  
cables only. It is not allowed to connect a  
LONWORKS shield.  
Technical Data  
Output status LEDs behavior  
Fig. 38. XF822AU Analog Output Module with terminal  
socket  
Table 29. Analog Output Module status LED behavior  
automatic mode  
override mode  
brightness follows the  
commanded output signal  
Legend  
1
2
3
4
5
6
Service button S1  
Hex switch S2  
Manual overrides  
Output LEDs  
flashes  
Service LED  
Power LED  
Functionality of service LED and power LED: see Table 42  
and following.  
EN1B-0410GE51 R0908A  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Excel 800  
Description of the I/O Modules  
This updating (synchronization) is performed:  
Modules with Manual Overrides  
The XFR822AU/XFLR822AU Analog Output Modules are  
equipped with manual overrides: one rotary knob for each  
analog output.  
If the calculated position of the actuator  
< lower synchronization threshold (2 %)  
= synchronization towards 0 %  
If the calculated position of the actuator  
> upper synchronization threshold (98 %)  
= synchronization towards 100 %  
The manual overrides can be set manually to either "auto" or  
"0 110%".  
Following any power-up or any reset  
NOTICE  
Damage to the electronic module!  
Do not use a tool to adjust the rotary knobs.  
Do not use excessive force. Adjust only by hand.  
XFL822AU Connection Example  
L
N
24V  
14507287  
POWER  
MODULE  
~
XFL822AU  
XSL511  
8
11  
1
73  
Umax = 11 VDC  
Imax = 1 mA, -1 mA  
GND SIGNAL 24VAC  
M
Fig. 40. XFL822AU Analog Output Module  
Synchronization Behavior of Analog Output Module  
Configured as Floating Output  
In order to regularly update the real actuator position with the  
calculated position and thus ensure that the actuator  
definitely reaches its end position, a synchronization process  
is performed by the Analog Output Module.  
During the synchronization process, the Analog Output  
Module will continue running for the configured runtime once  
it reaches the calculated end position.  
25  
EN1B-0410GE51 R0908A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Description of the I/O Modules  
Excel 800  
Terminals  
Binary Input Modules  
COM  
75  
A
COM  
76  
B
71 COM  
A
Types of Binary Input Modules  
72 COM  
B
24  
24  
77  
V~  
24  
78  
V~0  
73  
Table 30. Excel 800 Binary Input Modules  
V~  
24  
V~0  
74  
type  
XF823  
description  
housing  
light-gray  
dark-gray  
Panel Bus Binary Input Module  
BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12  
XFL823  
LONWORKS Bus Binary Input  
Module  
1
2
3
4
5
6
7
8
9
10 11 12  
XS823  
terminal socket  
light-gray  
GNDGNDGNDGNDGND GNDGNDGND GNDGNDGNDGND  
13 14 15 16 17 18 19 20 21 22 23 24  
25 26  
Features  
12 binary inputs  
Fig. 42. Terminal assignment and internal connections of  
Binary Input Modules  
12 configurable status LEDs (green/red, yellow/OFF)  
Binary inputs can be used as  
– Static digital inputs as dry-contacts  
Table 31. Description of Binary Input Module terminals  
ter-  
signal  
comment  
minal  
2-wire communication bus (LON/Panel  
Bus)  
71, 75  
COM a  
COM b  
2-wire communication bus (LON/Panel  
Bus)  
72, 76  
73, 77  
74, 78  
24 V~  
Power supply  
Power supply  
24 V~0  
1 12 BI1 BI12 Binary inputs 1 12  
13 ─  
24  
Ground. All grounds are connected  
internally to each other.  
GND  
Shield connection (functional earth),  
internally connected to the DIN rail.  
25, 26  
NOTE:  
Shield connection to be used for shielded I/O  
cables only. It is not allowed to connect a  
LONWORKS shield.  
Fig. 41. XF823AU Binary Input Module with terminal  
socket  
Technical Data  
Legend  
Table 32. Technical data for of Binary Input Modules  
1
2
3
4
5
Service button S1  
Hex switch S2  
Input LEDs  
input type  
dry-contact  
2 mA  
current rating (closed  
input)  
Service LED  
Power LED  
open contact voltage  
16 22 VDC  
Functionality of service LED and power LED: see Table 42  
and following.  
EN1B-0410GE51 R0908A  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Excel 800  
Description of the I/O Modules  
Status LEDs  
The status LEDs can be configured individually for use as  
either alarm LEDs (red/green) or as status LEDs (yellow/OFF  
[default]).  
Given a state of "logical ON," the LED will be lit (yellow or  
red).  
XF823AU Connection Examples  
1
1
13 25  
2
14  
SHIELD  
2
5 TO 24V  
2
1
MIN.  
MIN.  
25 MS 25 MS  
CONTACT SUITABLE FOR  
LOW VOLTAGE (GOLD).  
1
2
PROTECTED SWITCHING  
UP TO 40 VDC / 24 VAC.  
3
15  
5 TO 24  
VDC  
~ 120V  
PT1000 NTC20kW  
1
Fig. 43. XFL823AU Binary Input Module  
27  
EN1B-0410GE51 R0908A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Description of the I/O Modules  
Excel 800  
Terminals  
Relay Output Modules  
71 COM  
COM 75  
A
A
Types of Relay Output Modules  
72 COM  
COM 76  
B
B
24  
V~  
24  
77  
V~  
24  
78  
V~0  
73  
Table 33. Excel 800 Relay Output Modules  
24  
V~0  
74  
type  
XF824  
description  
housing  
Relay block 1  
Relay block 2  
Panel Bus Relay Output Module light-gray  
NO  
NC  
NO  
NO  
NC  
NO  
NC  
NO  
NO  
NC  
21  
11  
12  
13  
14  
31  
32  
33  
34  
41  
42  
43  
44  
51  
61  
XFR824  
Panel Bus Relay Output Module light-gray  
with manual overrides  
NC 22  
NC  
52  
53  
54  
62  
63  
64  
COM  
CON  
COM 23  
COM  
CON  
COM  
CON  
COM  
CON  
COM  
CON  
CON  
XFL824  
LONWORKS Bus Relay Output  
Module  
dark-gray  
dark-gray  
light-gray  
24  
25  
XFLR824  
XS824-25  
LONWORKS Bus Relay Output  
Module with manual overrides  
Cross connector (can be removed, as desired)  
Fig. 45. Terminal assignment and internal connections of  
Relay Output Modules  
terminal socket; can be fitted  
with long (red) cross connector  
(incl. in scope of the delivery)  
Features  
6 relays (changeover contacts), arranged in two blocks  
XFLR824AU, XFR824AU: 6 manual overrides  
Low and line voltage allowed, see WARNING.  
Fig. 44. XF824AU Relay Output Module with terminal  
socket  
Legend  
1
2
3
4
5
6
Service button S1  
Hex switch S2  
Manual overrides  
Status LEDs  
Service LED  
Power LED  
Functionality of service LED and power LED: see Table 42  
and following.  
EN1B-0410GE51 R0908A  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Excel 800  
Description of the I/O Modules  
Table 34. Description of Relay Output Module terminals  
Permissible Loads  
terminal  
signal  
COM a  
comment  
Table 35. Permissible loads of Relay Output Modules  
2-wire communication bus  
(LON/Panel Bus)  
71, 75  
max. load  
2-wire communication bus  
(LON/Panel Bus)  
per relay output  
module (total)  
(common)  
24 VAC, 60 Hz  
COM b  
72, 76  
12 A  
24 V~  
73, 77  
74, 78  
11  
Power supply  
24 VDC  
12 A resistive, 12 A, 0.6 PF  
24 V~0  
Power supply  
REL1 N.O.  
REL1 N.C.  
R1 COM  
Relay 1 N.O. contact  
Relay 1 N.C. contact  
relay 1 common contact  
per normally open 24 VAC, 60 Hz  
12  
contact (common)  
13  
4 A  
For connection of relay 1 common via  
cross connector*  
24 VDC  
4 A resistive, 4 A, 0.6 PF  
R1 COM  
14  
REL2 N.O.  
REL2 N.C.  
R2 COM  
21  
22  
23  
Relay 2 N.O. contact  
Relay 2 N.C. contact  
Relay 2 common contact  
per normally  
closed contact  
(common)  
24 VAC, 2 A, 60 Hz  
24 VDC  
4 A resistive, 4 A, 0.6 PF  
For connection of relay 2 common via  
cross connector*  
R2 COM  
24  
REL3 N.O.  
REL3 N.C.  
R3 COM  
31  
32  
33  
Relay 3 N.O. contact  
Relay 3 N.C. contact  
Relay 3 common contact  
Status LEDs with Manual Overrides  
Honeywell  
1
2
4
5
6
3
For connection of relay 3 common via  
cross connector*  
R3 COM  
34  
--1  
--0  
--AUTO  
REL4 N.O.  
REL4 N.C.  
R4 COM  
41  
42  
43  
Relay 4 N.O. contact  
Relay 4 N.C. contact  
Relay 4 common contact  
For connection of relay 4 common via  
cross connector*  
!
R4 COM  
44  
REL5 N.O.  
REL5 N.C.  
R5 COM  
51  
52  
53  
Relay 5 N.O. contact  
Relay 5 N.C. contact  
Relay 5 common contact  
Fig. 46. Manual overrides (toggle switches)  
The XFR824AU and XFLR824AU Relay Output Modules are  
equipped with six manual overrides: one for each relay  
output. These toggle switches can manually be set to either  
"auto" or "0" or "1".  
For connection of relay 5 common via  
cross connector*  
R5 COM  
54  
REL6 N.O.  
REL6 N.C.  
R6 COM  
61  
62  
63  
Relay 6 N.O. contact  
Relay 6 N.C. contact  
Relay 6 common contact  
Table 36. Relay Output Module status LED behavior  
For connection of relay 6 common via  
cross connector*  
R6 COM  
64  
25  
N.O.*  
(direct) (reverse)  
N.C.*  
mode  
LED  
ON  
Shield connection (functional earth),  
internally connected to the DIN rail  
automatic mode, state  
“logical ON”  
ON  
OFF  
ON  
* Do not connect by wire!  
automatic mode, state  
“logical OFF”  
OFF  
OFF  
override mode (setting “0”)  
override mode (setting “1”)  
flashes OFF  
flashes ON  
ON  
OFF  
*As configured during engineering.  
29  
EN1B-0410GE51 R0908A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Description of the I/O Modules  
Excel 800  
Connection Examples  
71 COM  
COM 75  
71 COM  
A
A
A
72 COM  
COM 76  
72 COM  
B
B
B
24  
24  
24  
73  
77  
73  
V
~
V
~
V
~
24  
24  
24  
V~0  
74  
78  
74  
V
~
0
V
~
0
NO  
NC  
NO  
NC  
NO  
NC  
NO  
NC  
NO  
NC  
NO  
NC  
21  
22  
23  
24  
11  
12  
13  
14  
31  
32  
33  
34  
41  
42  
43  
44  
51  
52  
53  
54  
61  
62  
63  
64  
COM  
CON  
COM  
CON  
COM  
CON  
COM  
CON  
COM  
CON  
COM  
CON  
25  
1
2
14507287 SERIES  
POWER MODULE  
Fig. 47. XF824AU connection example  
71 COM  
COM 75  
71 COM  
A
A
A
72 COM  
COM 76  
72 COM  
B
B
B
24  
24  
24  
73  
77  
73  
V
~
V
~
V
~
24  
24  
24  
V~0  
74  
78  
74  
V
~
0
V
~
0
NO  
NC  
NO  
NC  
NO  
NC  
NO  
NC  
NO  
NC  
NO  
NC  
21  
22  
23  
24  
11  
12  
13  
14  
31  
32  
33  
34  
41  
42  
43  
44  
51  
52  
53  
54  
61  
62  
63  
64  
COM  
CON  
COM  
CON  
COM  
CON  
COM  
CON  
COM  
CON  
COM  
CON  
25  
3
2
1
14507287 SERIES  
POWER MODULE  
Fig. 48. XFR825AU connection example  
EN1B-0410GE51 R0908A  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Excel 800  
Troubleshooting  
Troubleshooting  
Testing Wiring Connections  
The push-in terminals feature small holes (1 mm in diameter)  
which can be used to measure the signals.  
Insert a probe (1) as shown on the right.  
Fig. 49. Testing wiring connections  
Troubleshooting on the XCL8010AU Controller  
The following LEDs of the XCL8010AU Controller can be used for troubleshooting purposes:  
Power LED (green)  
Alarm LED (red)  
LONWORKS service LED  
C-Bus Tx and Rx LEDs  
HMI Tx and Rx LEDs  
Power LED (green)  
Table 37. XCL8010AU power LED  
meaning  
case  
power LED  
remedy  
No action necessary  
1
ON  
Normal operation  
One or more of the internal voltage supplies  
are outside of the permissible ranges. The  
controller stops operation.  
2
Flashing  
Check power  
Check wiring  
If problem persists, replace hardware  
3
Goes out briefly  
No action necessary  
The operator has activated the reset button  
The controller is performing a warm start  
31  
EN1B-0410GE51 R0908A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Excel 800  
Alarm LED (red)  
Table 38. XCL8010AU alarm LED  
meaning  
case  
alarm LED  
remedy  
No action necessary  
Try powering down and then  
1
OFF  
ON  
Normal operation  
Watchdog alarm output is powered  
2
– The controller has encountered a  
powering up the XCL8010AU.  
hardware problem  
- or -  
If problem persists, check and – if  
necessary – reload the application.  
– The application has a fault  
- or -  
If problem still persists, replace  
hardware  
– The controller has been powered up  
without an application or the operator  
has manually stopped the application,  
e.g., using XL-Online.  
In this case, the LED will light up  
13 minutes after power-up without  
application  
3
Flashing  
Although the controller has encountered a  
problem, the watchdog alarm output has not  
yet been powered.  
If it happens only once, the controller  
has performed a restart  
If, however, it happens multiple times,  
then there is an application or hardware  
problem (see case #2)  
If problem persists, the LED will become lit  
constantly, see case #2.  
The controller performs a warm start.  
LONWORKS Service LED  
Fig. 50. Flashing pattern of the LONWORKS service LED  
The LONWORKS service LED of the XCL8010AU Controller Module displays the following flashing patterns indicating possible  
failure modes:  
EN1B-0410GE51 R0908A  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Excel 800  
Troubleshooting  
Table 39. XCL8010AU LONWORKS service LED  
meaning  
case  
When can it occur?  
Anytime  
remedy  
No action necessary  
Node is configured and running normally  
Bad node hardware  
1
2
3
4
Power up of controller  
Power up of controller  
Power up / reset  
Replace hardware  
Replace hardware  
Bad node hardware  
Node lacks application.  
May be caused by neuron chip firmware when  
a mismatch occurs on application checksum  
Using EXCELON, set module to  
“configured online”  
If problem persists, the MIP software  
on LW interface has been erased due  
to wrong setting performed using  
ECHELON tool:  
Replace hardware  
Watchdog timer resets occurring.  
Possible corrupt EEPROM and bootstrap  
mode  
5
6
Anytime  
Anytime  
Download firmware  
Node is unconfigured but has an application  
Proceed with commissioning  
C-Bus Tx and Rx LEDs  
Table 40. XCL8010AU C-Bus Tx and Rx LEDs  
meaning  
case  
C-Bus LEDs  
remedy  
If the C-bus is functioning properly, then the  
XCL8010AU is functioning properly  
1
Both LEDs are flashing  
No action necessary  
If the C-bus is not functioning properly, then  
the termination can be wrong  
Check C-bus termination switch S1  
(location: see Fig. 4 on page 7)  
No C-bus communication  
No C-bus communication  
2
3
Both LEDs are OFF  
Check C-bus settings  
Check C-bus wiring  
Both LEDs are flashing  
synchronously  
HMI Tx and Rx LEDs  
Table 41. XCL8010AU HMI Tx and Rx LEDs  
meaning  
case  
HMI LEDs  
remedy  
If the HMI Interface is functioning properly,  
then the XCL8010AU is functioning properly  
1
Both LEDs are flashing  
Both LEDs are OFF  
No action necessary  
No HMI Interface communication  
2
Check HMI Interface connection and  
proper earthing of connected  
hardware  
33  
EN1B-0410GE51 R0908A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Excel 800  
I/O Modules Troubleshooting  
Check if the power supply voltage level is OK and that there is no high voltage (> 24 VAC or > 40 VDC) connected to the  
inputs/outputs of the XF821AU, XFL821AU, XF822AU, XFL822AU, XFR822AU, XFLR822AU, XF823AU, and XFL823AU I/O  
modules.  
Replace the problem I/O module with another module of the same kind.  
– If the problem persists, this is an indication that the problem is caused by the application or incorrect wiring.  
– If the problem is solved, this is an indication that the I/O module was defective.  
For troubleshooting purposes on all I/O modules the following features can be used:  
Power LED  
Service LED  
Service button  
In addition, a module-specific troubleshooting may be necessary.  
Power LED of I/O Modules  
Table 42. Power LED of I/O modules  
case  
power LED  
meaning  
I/O module is powered  
remedy  
No action necessary  
1
ON  
No power  
2
3
OFF  
Check power supply  
If the I/O module’s service LED is likewise  
flashing, the I/O module is in the boot mode  
Flashing continuously  
Wait until rebooting (firmware  
download) has been completed  
EN1B-0410GE51 R0908A  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Excel 800  
Troubleshooting  
Service LED of I/O Modules  
Table 43. Service LED of I/O modules  
meaning  
case  
Service LED  
remedy  
If the power LED is also OFF, then  
Replace hardware  
LED remains OFF after  
power-up  
1
Defective device hardware  
Possible power supply problems, clock  
problems, defective processor  
LONWORKS Bus I/O modules:  
Replace hardware  
LED is lit continuously after  
first power-up  
LONWORKS Bus I/O modules:  
Defective hardware  
Panel Bus I/O modules:  
2
Panel Bus I/O modules:  
Set the hex address to the position configured  
I/O module has not yet been configured  
by XCL8010AU  
with CARE  
Ensure that I/O Bus switch S2 of XCL8010AU is  
Boot loader is active  
set to position "Panel"  
Failure during last firmware download  
Checksum error  
Check the Panel Bus wiring:  
-
-
-
Check for cable breaks  
Check for cable short-circuits  
If using separate transformers: Check ground  
connection  
Eliminate any mixture of Panel Bus I/Os and  
LonWorks I/Os on same wire  
Allow XCL8010AU to configure I/O module  
Unplug and replug the module  
If problem persists, replace hardware  
Panel Bus I/O modules, only:  
Download error or application checksum error.  
Boot loader is running  
Alternating flash between  
service LED and power LED  
3
4
5
Panel Bus I/O modules, only:  
Wait until rebooting (firmware download) has  
been completed  
LONWORKS Bus I/O modules, only:  
LONWORKS Bus I/O module lacks application  
LED flashes at power up,  
goes OFF, and then is lit  
continuously  
Download application  
Set module to configured mode  
No action necessary  
LONWORKS Bus I/O modules, only:  
LONWORKS Bus I/O module is unconfigured, but  
has an application  
LED repeatedly blinks  
ON for 1 sec and  
OFF for 1 sec  
I/O module is configured and running normally  
LED remains OFF after a  
short ON duration  
6
7
Sensor failure of Analog Input Module  
(in case of LONWORKS Bus I/O modules, this  
behavior can occur only if the appropriate NV  
has been bound)  
Check sensor or connection  
Check sensor configuration  
LED flashes continuously in  
following pattern:  
4 x ON/OFF followed by  
pause  
LONWORKS Bus I/O modules, only: LONWORKS  
I/O Bus module has received the wink  
command from network, physical outputs are  
unaffected  
LED flashes continuously in  
following pattern:  
5 x ON/OFF followed by  
pause  
8
No action necessary  
Replace hardware  
Check bus wiring  
Boot loader problem or hardware defect  
LED flashes continuously in  
following pattern:  
6 x ON/OFF followed by  
pause  
9
Communications failure  
LED flashes continuously in  
following pattern:  
7 x ON/OFF followed by  
pause  
10  
Ensure that I/O Bus switch S2 of XCL8010AU is  
set to correct position  
Ensure that LONWORKS Bus I/O modules and  
Panel Bus I/O modules are not sharing same  
bus  
In case of Panel Bus I/O modules, only:  
Check for incorrect HEX addresses (2 Panel Bus  
I/O modules using same HEX address)  
In case of LONWORKS Bus I/O modules, only:  
Check heartbeat  
35  
EN1B-0410GE51 R0908A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Excel 800  
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative:  
Automation and Control Solutions  
Honeywell GmbH  
Böblinger Strasse 17  
71101 Schönaich / Germany  
Phone: (49) 7031 63701  
Fax:  
(49) 7031 637493  
Subject to change without notice. Printed in Germany  
EN1B-0410GE51 R0908A  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Grizzly Drill G7945 User Manual
Haier Microwave Oven HMC1120BEBB User Manual
Haier Refrigerator UN FZBU110 User Manual
Hamilton Beach Kitchen Grill 840058500 User Manual
Hasbro Games Giggle Game User Manual
Hearth and Home Technologies Universal Remote 6000C LP User Manual
Honeywell Home Security System K5305 1V5 User Manual
Hotpoint Clothes Dryer NLL113EYWO User Manual
Hunter Fan Universal Remote 81002 User Manual
IBM Projector IL1210 User Manual