Honeywell Smoke Alarm ADT HRSI User Manual

ADT-HRSI  
Intelligent Heat Detector  
S
Y
S
T
E
M
SPECIFICATION DATA  
FEATURES  
·
70ft (21.3 meter) spacing  
·
9°C (15°F) per minute rate-of-rise and 57°C (135°F)  
fixed temperature alarm threshold  
·
·
·
·
·
·
·
·
Intelligent detector with integral microprocessor  
Non-volatile memory  
Automatic device mapping  
Electronic addressing  
Identification of defective detectors  
Twin status LEDs  
Standard, relay, and fault isolator mounting bases  
Designed and manufactured to ISO 9001 standards  
DESCRIPTION  
- Original detector sensitivity values upon manufacturing  
- Number of recorded alarms and troubles  
- Time and date of last alarm  
- Analog signal patterns just before the last alarm  
- Up to 32 possible trouble codes which may be used to  
diagnose faults.  
Honeywell's Signature Series Model ADT-HRSI Intelligent  
Heat Detectors gather analog information from their fixed  
temperature and/or rate-of-rise heat sensing elements and  
converts it into digital signals. The detector's on-board  
microprocessor measures and analyzes these signals. It  
compares the information to historical readings and time  
patterns to make an alarm decision. Digital filters remove  
signal patterns that are not typical of fires. Unwanted alarms  
are nearly eliminated.  
In the unlikely event that an unwanted alarm does take place,  
the history file can be called up to help isolate the problem  
and prevent it from happening again.  
The microprocessor in each detector provides four additional  
benefits; self-diagnostics and history log, automatic device  
mapping, stand-alone operation and fast, stable  
communication.  
Automatic Device Mapping:  
The loop controller learns where each device's serial number  
address is installed relative to other devices on the circuit.  
This "mapping" feature provides supervision of each device's  
installed location to prevent a detector from being reinstalled  
(after cleaning etc.) in a different location from where it was  
originally. The history log for the detector at its original  
location remains relevant and intact.  
Self-diagnostics and History Log:  
Each Signature Series detector constantly runs self-checks  
to provide important maintenance information. The results  
of the self-check are automatically updated and permanently  
stored in the detector's non-volatile memory. This information  
is accessible for review any time at the control panel, PC, or  
by using the SIGA-PRO Signature Program/Service Tool.  
The information stored in the detector's memory includes:  
The Signature Series Data Entry Program also uses the  
mapping feature. With interactive menus and graphic  
support, the wired circuits between each device can be  
examined. Layout or "as-built" drawing information showing  
wire branches (T-taps), device types and their address are  
stored on disk for printing hard copy. This takes the "mystery"  
out of the installation. The preparation of "as-built" drawings  
is fast and efficient.  
- Detector serial number, address, and type  
- Date of manufacture, hours of operation, and last  
maintenance date  
- Current detector sensitivity values and the extent of  
environmental compensation  
74- 3346  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ADT-HRSI INTELLIGENT HEAT DETECTOR  
Isolator Base ADT-IB, ADT-IBS:  
Accessories:  
This base includes a built-in line fault isolator. A detector  
must be installed for it to operate. The integral isolator relay  
is controlled by the detector or the loop controller. A  
maximum of 96 isolator bases can be installed on one  
circuit. The isolator base does not support the SIGA-LED  
Remote LED.  
All detector mounting bases have wiring terminals that are  
accessible from the "room-side" after mounting the base to  
the electrical box. The bases mount to North American 1-  
gang boxes and to 3-1/2 in or 4 in octagon boxes, 1-1/2 in  
(38 mm) deep. They also mount to European BESA and  
1-gang boxes with 60.3 mm fixing centers.  
The isolator operates as follows: a short on the line causes  
all isolators to open within 23 msec. at 10 msec intervals,  
beginning nearest the loop controller, the isolators close to  
provide the next isolator down the line with power. When the  
isolator next to the short closes, it reopens within 10 msec.  
In Class A operation, the process repeats beginning on the  
other side of the loop controller.  
Removing a detector from its base (except isolator base)  
does not affect other devices operating on the same circuit.  
Standard Base SIGA-SB:  
This is the basic mounting base for Honeywell Signature  
Series detectors. The SIGA-LED Remote LED is supported  
by the Standard Base.  
Remote LED SIGA-LED:  
Relay Base ADT-RB:  
The remote LED connects to the SIGA-SB Standard Base  
only. It features a North American size 1-gang plastic  
faceplate with a white finish and red alarm LED.  
This base includes a relay. Normally open or closed  
operation is selected during installation. The dry contact is  
rated for 1 amp (pilot duty) at 30 Vdc. The relay's position is  
supervised to avoid accidentally jarring it out of position. The  
relay base does not support the SIGA-LED Remote LED.  
The relay is controlled by the detector and operates as  
follows: at system power-up or reset, the relay is de-  
energized.  
SIGA-TS Trim Skirt:  
Supplied with 4 in bases, it can also be ordered separately to  
use with the other bases to help hide surface  
imperfections not covered by the smaller bases.  
When a detector is installed in the base with the power on,  
the relay energizes for 4 seconds, then de-energizes. when a  
detector is removed from a base with the power on, the relay  
is de-energized. When the detector enters the alarm state,  
the relay is energized.  
Application:  
Table 1 below shows six standard test fires used to rate the  
sensitivity of smoke and heat detectors. The table indicates  
that no single sensing element is suited for all test fires.  
Table 1. Test Fires.  
Test Fire  
Type of Sensor  
ADT-ISI  
Ion  
ADT-PSI  
Photo  
ADT-HRSI  
Rate-of Rise/  
Fixed Temp.  
ADT-PHSI  
Photo/ Heat  
3D  
ADT-IPHSI  
Ion/ Photo/ Heat  
4D  
Open Wood  
Optimum  
Suitable  
Unsuitable  
Optimum  
Optimum  
Unsuitable  
Unsuitable  
Suitable  
Very Suitable  
Optimum  
Optimum  
Optimum  
Optimum  
Optimum  
Optimum  
Very Suitable  
Wood Pyrolysis  
Smoldering Cotton  
Polyurethane Foam  
n-Heptane  
Very Suitable  
Very Suitable  
Optimum  
Optimum  
Optimum  
Very Suitable  
Very Suitable  
Unsuitable  
Very Suitable  
Optimum  
Very Suitable  
Optimum  
Liquid Fire without Smoke  
Unsuitable  
Very Suitable  
3
74-3346  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ADT-HRSI INTELLIGENT HEAT DETECTOR  
SPECIFICATIONS  
Compatible Mounting Bases:  
SIGA-SB standard base  
Heat Sensor:  
Combination fixed temperature and rate of rise, alarms at  
57°C (135°F) ambient or temp. increases greater than  
9°C (15°F) per min.  
ADT-RB relay base  
ADT-IB and ADT-IBS isolator base  
LED Operation:  
Detector Spacing:  
On-board green LED: Flashes when polled  
On-board red LED: Flashes when in alarm  
Both LEDs: On steady when in alarm (stand-alone)  
70ft (21.3m) center to center  
Environmental Limits:  
Temperature: 32° to 100°F (0° to 38°C)  
Humidity: 0 to 93% rh, non-condensing  
Compatible remote red LED:  
Flashes when in alarm  
Voltage:  
Compatibility:  
15.2 to 19.95 Vdc (19 Vdc nominal)  
Signature loop controller  
Operating Current:  
Address Requirements:  
Stand-by: 45mA at 19V  
Alarm: 45mA at 19V  
Emergency stand-alone alarm mode: 18mA  
Pulse current: 100mA (100 msec)  
During communication: 9 mA max.  
1 device address  
Accessories:  
SIGA-SB: Detector mounting base  
ADT-RB:  
ADT-IB:  
Detector mounting base with relay  
Detector mounting base with fault isolator  
Construction:  
ADT-IBS: Same as above, with loop continuity switch  
SIGA-LED: Remote alarm LED  
High impact engineering polymer  
SIGA-TS: Trim skirt (supplied with 4in bases)  
Finish:  
White  
Home and Building Control  
Honeywell Inc.  
Honeywell Plaza  
P.O. Box 524  
Minneapolis MN 55408-0524  
Home & Building Control  
European Centre of Excellence  
Fire Solutions  
Lovelace Road, Southern Industrial Area  
Bracknell, Berkshire, RG12 8WD  
United Kingdom  
Honeywell GmbH  
Honeywellstrasse  
63477 Maintal 1  
Germany  
74-3346 J.S. 12-99  
EN0C-0746E 0599R0-OB  
Printed in U.S.A.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Grizzly Paint Sprayer H6330 User Manual
Groupe SEB USA T FAL Fryer Fryer User Manual
Haan Carpet Cleaner SI 60 User Manual
Hakuba Projector Accessories PMD1 User Manual
Harbor Freight Tools Water Pump 69774 User Manual
Heatiator Indoor Fireplace CH76 User Manual
Hotpoint Washer Dryer HE7L 292 User Manual
Husqvarna Cordless Saw FS 700 EX User Manual
IDEAL INDUSTRIES Boiler CXSi 110 User Manual
Igloo Water Dispenser MWC496B User Manual