HE360 Powered Flow-Through Humidifier  
INSTALLATION INSTRUCTIONS  
READ AND SAVE THESE INSTRUCTIONS  
HUMIDIFIER HOUSING  
WATER FEED TUBE  
COVER  
APPLICATION  
The HE360 Powered Flow-Through Humidifier uses the warm air furnace blower to provide humidification  
for the whole house. The HE360 works with virtually any Honeywell humidity control, but use with the  
Honeywell Perfect Climate Comfort Center™ control for optimal performance.  
INSTALLATION  
WARNING  
Personal Injury or Equipment Damage Can Occur.  
Do not cut or drill into any air conditioning or electrical accessory.  
HUMIDIFIER  
PAD ASSEMBLY  
THUMB SCREW  
M12683  
CAUTION  
Fig. 3. Humidifier components.  
Locate the humidifier where the ambient temperature is between 32°F (0°C) and 160°F (71°C)  
or property damage can occur. Do not install where freezing temperatures could occur.  
Be sure supply plenum static pressure is no greater than 0.4 in. W.C. and water pressure is no  
greater than 125 psi or equipment damage can occur.  
IMPORTANT  
Be sure the black mark on the end of the humidifier pad is facing up for proper operation. Check  
that the water feed tube is placed in the guide slots of the humidifier housing.  
IMPORTANT  
Be sure the template is level before marking to assure optimal product performance.  
8. Reinstall the humidifier pad and PerfectFlowater tray in the humidifier housing.  
9. Hook the top of the cover to the housing and secure with the thumbscrew located at the bottom of  
the cover.  
1. Determine the best location for the humidifier and draw a level line on the plenum. See Fig. 1 and 2.  
IMPORTANT  
Be sure the humidifier will be at least 3 in. (76 mm) above the furnace jacket or there will not be  
enough room for the drain line. Check that there is enough room above the humidifier to remove  
and install the humidifier cover. Do not install on a furnace jacket.  
WIRING  
WARNING  
Serious Personal Injury Hazard.  
RETURN  
Can cause electrical shock and injury from moving parts.  
Disconnect power supply before installation or servicing to prevent electrical shock or equipment  
damage.  
L
A
T
N
O
IZ  
R
O
H
This device contains a moving fan blade. Disconnect power prior to installation or servicing. Do not  
operate the humidifier without the cover securely attached.  
Y
RETRN  
BO  
H
HIG  
All wiring must comply with applicable local codes, ordinances and regulations.  
N
R
U
T
E
R
RETRN  
1. Wire the humidifier solenoid valve, current sensing relay or sail switch, and humidistat. See Fig. 4, 5  
DOWN  
FLO  
and 6. Refer to humidistat installation instructions for mounting and wiring information.  
IMPORTANT  
LOWBOY  
If not using a current sensing relay or sail switch, the 120V humidifier plug must be energized  
during blower motor cycles for proper operation.  
NOTE: Select models of fan centers include humidifier taps so the current sensing relay or sail switch are  
not needed.  
M12687  
TO BLOWER  
MOTOR  
JUNCTION BOX  
Fig. 1.Typical humidifier installation locations.  
1
2
120 VAC  
HUMIDISTAT  
HUMIDIFIER  
YELLOW WIRES  
1
2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND  
OVERLOAD PROTECTION AS REQUIRED.  
24V WIRING.  
M12686  
Fig. 4.Typical hookup diagram for humidifier using the fan control to cycle the blower motor fan  
and humidifier simultaneously.  
M12704  
HUMIDISTAT  
2
Fig. 2. HE360 Humidifier location in relation to AC cooling coils.  
120 VAC  
1
HUMIDIFIER  
2. Tape the template in position and trace around the template.  
3. Remove the template and carefully cut the rectangular opening.  
4. Loosen the thumbscrew on the bottom of the humidifier and remove the cover.  
5. Remove the humidifier pad and PerfectFlowater tray by grasping the tray and pulling it out of the  
housing. See Fig. 3.  
6. Position the humidifier housing in the hole (be sure it is level), so the locking tabs are in place on the  
lower sheet metal edge of the hole.  
YELLOW WIRES  
CURRENT  
SENSING  
RELAY  
1
POWER SUPPLY.  
PROVIDE DISCONNECT  
MEANS AND OVERLOAD  
PROTECTION AS REQUIRED.  
LO  
7. Drill holes and install the two sheet metal screws at the top of the humidifier housing. Secure the  
C
HI  
housing with the eight remaining screws.  
2
24V WIRING.  
M12684  
BLOWER  
MOTOR  
Fig. 5.Typical hookup diagram of the current sensing relay with a humidifier.  
® U.S. Registered Trademark  
69-1107  
Copyright © 1997 Honeywell Inc.  
All Rights Reserved  
TEMPLATE  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Grizzly Drill G0704 User Manual
Haier Air Conditioner 0010530627 User Manual
Haier Drill 15F6B User Manual
Haier TV Receiver 34F9K User Manual
Hans Grohe Plumbing Product 06126XX0 User Manual
Harbor Freight Tools Grinder 47869 User Manual
Harbor Freight Tools Paint Sprayer 91009 User Manual
Hayter Mowers Lawn Mower 005A User Manual
Honeywell Portable Generator Q313A User Manual
HTC Cell Phone NIKI100 User Manual