Honeywell Home Security System GEC User Manual

DN-6872 • J-114B  
December 19, 2002  
Gentex Commander² GE Series  
Low-Frequency Evacuation Signals  
GEC, GEH, GES Models  
Section: Audio/Visual Devices  
GENERAL  
The Gentex Commander² GE Series features low-profile  
strobes, horns or horn/strobe combinations that offer de-  
pendable audible and audible/visual alarms and the low-  
est current available.  
California  
State Fire  
Marshal  
7135-0569:122  
(GEC, GEH models)  
7125-0569:123  
Commander² GE Series horns allow selection of high or  
low dBA, of synchronizable chime or whoop tones, as well  
as selection of a 2400 Hz (remote signaling) or a low-fre-  
quency broadband 1500-3000 Hz mechanical sounding  
(evacuation) tone where doors must be considered.  
(GES models)  
S3406  
(GEC, GEH models)  
S5405 (GES models)  
MEA  
285-91-E Vol. XV  
Commander² GE Series models are easily field-change-  
able from temporal 3 to continuous tone by simply remov-  
ing a jumper. GEC models are shipped from the factory on  
the temporal lower-frequency mode and come standard with  
a rugged cast-metal mounting plate.  
City of  
Chicago  
ADA  
Approved  
The Commander² GE Series appliances have a minimal  
operation current and a minimum flash rate of 1 Hz regard-  
less of input voltage. The Super Slide™ feature tests su-  
pervision. A locking mechanism is included, which secures  
the product to the bracket without screws showing.  
Commander² GE Series appliances are UL-  
Listed for use with fire protective systems  
per UL 464, UL 1971, and UL 1638. The  
appliances are warranted for three years  
from the date of purchase.  
FEATURES  
• Installers can prewire the entire system,  
then install the signaling devices.  
• Super Slide™ feature for easier supervi-  
sion testing. When mounting Super  
Slide™, die-cast metal mounting plate  
mounts to single-gang boxes, double-  
gang boxes, 4" (101.6 mm) square boxes,  
or Gentex GSB box.  
• Lower installation and operating costs.  
• Input terminals utilize 12 AWG (3.25 mm²) to 18 AWG  
(0.75 mm²).  
• True evacuation tone. Switch selection for:  
• Synchronize strobe and/or horn with Gentex AVS44 con-  
trol module.  
High or low dBA.  
High or low frequency (1500 to 3000 Hz).  
Temporal 3 signaling, chime or whoop tones.  
• Widest range of candela available. 15/75, 75 and 110  
candela strobes meets or exceeds ADA 4.28.3 require-  
ments.  
Tamperproof reentrant grille.  
• Wide voltage range of 16 – 33 VDC or FWR.  
• Rugged die-cast metal mounting bracket. Surface-mount  
with Gentex GSB box.  
• Dimensions: 5" (127 mm) high x 4.5" (114.3 mm) wide x  
2.5" (63.5 mm) deep.  
• Separate horn and strobe functions. Horn can be silenced  
while strobes remain flashing.  
• Models available in red or off-white.  
Super Slide™ is a trademark of Gentex Corporation.  
NOTIFIER® is a  
company.  
This document is not intended to be used for installation purposes. We try to keep our  
product information up-to-date and accurate. We cannot cover all specific applications or  
anticipate all requirements. All specifications are subject to change without notice.  
For more information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118  
12 Clintonville Road, Northford, Connecticut 06472  
DN-6872 • 12/19/02 — Page 1 of 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GEC Models  
Conventional  
Wiring  
GEH/GES Models  
Conventional  
Wiring  
GE Series Wiring with AVS44 Sync Module  
6872horn.tbl  
Horn Ratings over Input Voltage Range of 16 – 33 V  
dBA @ 10' (3.048 m) dBA @ 10' (3.048 m)  
DC (mA)  
FWR (mA)  
per UL 464  
per UL 464  
Horn Mode  
HIGH dB  
LOW dB  
16 V 24 V 33 V 16 V 24 V 33 V 16 V 24 V 33 V 16 V 24 V 33 V  
Temporal 3 2400 Hz  
Temporal 3 Mechanical  
Temporal 3 Chime  
Continuous 2400 Hz  
Continuous Mechanical  
Continuous Chime  
Whoop  
78  
76  
70*  
81  
80  
70*  
82  
83  
81  
71*  
86  
84  
71*  
83  
84  
82  
71*  
87  
85  
73*  
83  
71*  
70*  
66*  
74*  
72*  
66*  
69*  
75  
77  
13  
11  
9
19  
16  
12  
21  
18  
12  
51  
24  
22  
15  
28  
25  
15  
56  
27  
23  
19  
21  
27  
19  
51  
37  
33  
24  
42  
37  
24  
58  
43  
40  
29  
48  
44  
30  
62  
73*  
68*  
78  
76  
70*  
80  
14  
13  
10  
43  
76  
78  
68*  
72*  
70*  
75  
TABLE NOTES: 1) *Operating the horn in this mode at this voltage will not meet the minimum UL reverberant sound level  
required for public mode fire protective service. These settings are acceptable only for private mode fire alarm use. Use the high  
dBA setting for public mode application (not applicable when using the chime tone — the chime tone is always private mode).  
2) The sound output for the temporal 3 tone is rated lower, as the time the horn is off is averaged into the sound output rating.  
While the horn is producing a tone in the temporal 3 mode, its sound pressure is the same as when in continuous mode.  
DN-6872 • 12/19/02 — Page 3 of 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Grundig CRT Television MF 72 6510 8 User Manual
GSW Water Heater Electric Water Heate User Manual
Haier Microwave Oven HDN 3090EGB User Manual
Hamilton Beach Blender 59780R User Manual
Hamilton Beach Blender 840111200 User Manual
Hotpoint Dishwasher FDFSM 31011 FUTURA User Manual
Hotpoint Washer Dryer WD72 User Manual
HP Hewlett Packard Flat Panel Television L1710 User Manual
Ice O Matic Ice Maker EMF 1106 Series User Manual
iHome Headphones i815 User Manual