| 	
		 K5942V2 7/04   
					5894PI   
					PASSIVE INFRARED MOTION DETECTOR/TRANSMITTER   
					INSTALLATION INSTRUCTIONS   
					GENERAL INFORMATION   
					The 5894PI Passive Infrared   
					Detector/Transmitter is 10-year battery-   
					operated wireless device intended for use as   
					part of a 5800 series wireless alarm system.   
					SPECIFICATIONS   
					Pet Immune Lens:   
					35 ft x 45 ft (10.6m x 13.7m).   
					28 zones (8 over, 8 long range, 8 intermediate,   
					4 short-range).   
					BATTERY ACTIVATION/INSTALLATION   
					Motion   
					1. Remove front cover by pressing the front   
					cover latch and lifting the cover off. See   
					Figure 2.   
					a 
					Designed for use in commercial and residential   
					installations, the 5894PI is a wall-mounted unit   
					with a standard lens that provides wide-angle   
					protection up to a range of 35 ft (10.6m). For   
					best coverage, mount the detector so that the   
					likely direction of intruder motion is across the   
					pattern.   
					When installed per the guidelines, the Tier-   
					Balanced Optics technology in the 5894PI   
					provides false alarm protection against pets   
					and other animals up to 80 lbs.   
					This document provides installation instructions   
					for the 5894PI, but the installer must be familiar   
					with the installation instructions for the 5800   
					Wireless Alarm System with which the 5894PI   
					is intended to be used.   
					Pulse Processing:   
					Intermediate, Standard, or Harsh, Installer-   
					selectable. Note: For pet immune applica-   
					tions, see Special Instructions for   
					Installations with Pets on page 3.   
					Detectable Walk Rate:   
					0.5–10 ft/Sec (0.15–3m/Sec).   
					Mounting Height:   
					7.0 ft (2.1m)   
					Walk Test Indicator:   
					Red LED with enable/disable link.   
					Batteries:   
					Three 3-volt Lithium batteries. Use only   
					ADEMCO No. 466, Duracell DL123A,   
					Panasonic CR123A, Sanyo CR123A, or Varta   
					CR123A.   
					0perating Temperature:   
					32°F – 122°F (0°C - 50°C).   
					FEATURES   
					• Tier-Balanced Optics provides pet immunity   
					against animals up to 80 lbs.   
					Operating Humidity:   
					Up to 95% RH (max.), non-condensing.   
					• Wireless operation for fast installation.   
					Dimensions:   
					3.0"W 5.0"H x 1.7"D   
					(76.3mm x 127.0mm x 42.6mm).   
					• Dual-element pyroelectric sensor provides   
					positive protection while minimizing false   
					alarms.   
					• Selectable PIR sensitivity.   
					• Provision to turn LED on while Walk Testing   
					(LED is turned off after testing).   
					Figure 2. Remove the Front Cover   
					Approvals/Listings:   
					FCC, IC, cULus, C-Tick   
					2. To activate the installed batteries, remove   
					the battery pull-tab. (See Figure 3.) Make   
					sure the batteries remain firmly seated in   
					the battery holders.   
					TOP VIEW   
					22.5'   
					• 
					Tamper-protected cover and wall; detector   
					transmits message if cover or detector is   
					removed.   
					• 
					• 
					• 
					Wall or corner mounting options.   
					Patented Black Bug Guard.   
					Temperature compensation.   
					SYSTEM DESCRIPTION   
					Optical System   
					0 
					The 5894PI uses efficiently designed Fresnel   
					lenses with Tier-Balanced Optics.   
					Radio Transmitter   
					. 
					The built-in transmitter serves only as the   
					communication link to the alarm system's   
					Receiver/Control, and can send alarm, tamper,   
					supervisory, and battery status messages to   
					the system's receiver/control. The transmitter is   
					not used for detection purposes. Each detector   
					has a unique ID code permanently assigned at   
					the factory. You must enroll this ID into the   
					control system at the time of installation. This   
					allows each detector used in the system to be   
					uniquely identified. You must program the   
					control to enroll the 5894PI as an "RF" type unit   
					(i.e., supervised RF).   
					Figure 3. Remove Pull Tab to   
					activate batteries   
					22.5'   
					10'   
					20'   
					30' 35'   
					3. To replace the batteries, remove the old   
					batteries from the holder. Then, observing   
					correct polarity, install three new Lithium   
					batteries into the battery holders, as shown   
					in Figure 4. Make sure the batteries are   
					firmly seated.   
					ALTERNATE   
					COUNT POLARITY   
					EACH ZONE CONSISTS   
					OF 2 FIELDS   
					4. Replace the cover (snap fit).   
					SIDE VIEW   
					Battery Caution   
					To conserve battery life during normal   
					operation, no more than one transmission   
					sequence will occur within a 3-minute period.   
					There is no such time restriction in Test mode   
					(refer to the Walk Test section).   
					7'   
					0 
					Risk of fire, explosion, and burns. Do not   
					recharge, disassemble, heat above 100°C, or   
					incinerate. Dispose of used batteries promptly.   
					Keep away from children.   
					10'   
					20'   
					30' 35'   
					0 
					Figure 1. Protection Pattern   
					Page 1   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Note: Each time you remove and replace the   
					front cover, or remove and replace the sensor   
					in the mounting plate, the sensor will transmit   
					every alarm signal for 64 alarm events.   
					1. Remove front cover, and set the pulse   
					count jumper as required in the installation   
					(INT, STD or HARSH),   
					2. Enable the LED by placing the jumper link   
					in the TEST position (see Figure 4 for   
					jumper location).   
					TEST PROCEDURES   
					MAINTAINING PROPER OPERATION   
					In order to maintain the detector in proper   
					working condition, it is important that the user   
					observes the following:   
					Important: Testing should be conducted with   
					the protected area cleared of all people. Place   
					the protective system's control in the Test   
					mode for the Walk Test procedure. When the   
					PIR senses movement, the system's console   
					1. Replace all three batteries within seven (7)   
					days after a "low battery" message has   
					appeared in the system's display.   
					2. Detectors should never be re-aimed or   
					relocated without the advice or assistance   
					of the alarm service company.   
					3. The physical surroundings of the protected   
					area should not be changed. If furniture or   
					stock is moved, or air conditioning or   
					additional heating is installed, the PIR may   
					have to be readjusted.   
					4. Walk Tests should be conducted frequently   
					(at least weekly) to confirm continued   
					proper coverage.   
					emits   
					a 
					beep, verifying that the PIR's   
					transmitter signal has reached the control's   
					wireless receiver.   
					The absolute range of all PIR units is subject to   
					variation because of different types of clothing,   
					backgrounds, and ambient temperature. For   
					this reason, ensure that the most likely intruder   
					routes are well within the PIR's protective   
					zones and that Walk Testing is carried out   
					along these routes.   
					Note:   
					Removing the front cover, or   
					removing the sensor from the mounting   
					plate, will also enable the LED.   
					3. Replace front cover and walk through   
					protective zones, observing that the   
					detector's LED lights whenever motion is   
					detected (the LED serves as a Walk Test   
					indicator during this procedure).   
					WALK TEST   
					Test mode is initiated by removing and   
					replacing the detector’s front cover, or by   
					removing and replacing the sensor from the   
					mounting plate.   
					4. After the Walk Test is completed, disable   
					the LED by placing the LED jumper link   
					in the Normal position. Failing to do so   
					will reduce the battery life. (see Figure 4.)   
					SPECIAL INSTRUCTIONS FOR INSTALLATION WITH PETS   
					To take full advantage of the pet immunity in the 5894PI, the guidelines below should be followed:   
					• 
					• 
					• 
					Mount the center of the detector 7.0 feet high.   
					Set the Pulse Count to Standard or Harsh.   
					Mount where animals/rodents cannot come within six feet of the detector by climbing on   
					furniture, boxes, or other objects.   
					• 
					Do not aim the detector at stairways or furniture / objects that can be climbed by an animal.   
					Note: This unit will provide immunity to false alarms for an individual animal or a group of animals   
					whose total weight is equal to or less than 80 pounds when the room temperature is above 50° F.   
					TROUBLESHOOTING   
					Trouble 1: INTERMITTENT ALARM   
					Trouble 4: SUPERVISION FAILURE   
					Probable Causes:   
					Probable Causes:   
					A. Rapid temperature change. Check for electric or gas heaters,   
					open flames, electric arcs, etc.   
					A. When enrolling the detector, a tamper signal was used to transmit   
					the detector serial number, and the panel enrolled the detector with a   
					loop type “4”, or the wrong device was learned.   
					Remedy: Locate source and re-position detector.   
					B. Drafts causing drapes, light fixtures, display material to move.   
					Remedy: Eliminate source of motion.   
					Remedy: Ensure the serial number and loop types are correct for   
					each detector; if the detector loop type is programmed as “4”,   
					manually change it to “1” at the panel. If the wrong device was   
					learned, enroll the detector again (see Programming on page 2).   
					Trouble 2: LED INOPERATIVE DURING WALK TEST   
					Probable Causes:   
					B. The detector was placed in a location where the RF signal is not   
					strong enough.   
					A. LED control jumper set to NORMAL position.   
					Remedy: Re-position jumper to TEST position (see Figure 4).   
					B. LED malfunction. Check for broken/shorted leads.   
					Remedy: Return unit for service.   
					Remedy: Repeat the directions to verify the transmission path (see   
					the Radio Transmission Path Check section on page 2). If   
					necessary, move the detector to a new location.   
					Trouble 5: UNIT DOES NOT APPEAR TO BE OPERATING   
					Probable Cause:   
					A. Unit is not receiving power.   
					Trouble 3: LED OPERATIVE WITH LED JUMPER LINK SET   
					TO NORMAL (OFF) POSITION   
					Remedy: Check for appropriate battery voltage. Install new batteries   
					if necessary. Be sure to change all batteries.   
					Probable Causes:   
					A. The sensor is not mounted squarely on the wall, (the wall   
					tamper switch is not depressed.)   
					Trouble 6: UNIT IS ALWAYS IN TEST MODE   
					Probable Cause:   
					Remedy: Re-position the sensor to make sure the wall   
					tamper switch is fully depressed.   
					B. The sensor’s front cover is not installed.   
					Remedy: Replace the sensor’s front cover.   
					A. The sensor front cover was removed and replaced, or the sensor   
					was removed and replace in the mounting plate, so the sensor is   
					transmitting every alarm signal for 64 alarm events.   
					Remedy: Wait for the sensor to transmit 64 alarm events.   
					Page 3   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				LIMITATIONS OF THE PIR MOTION DETECTOR   
					LIMITED WARRANTY   
					While the Intrusion Detector is a highly reliable intrusion detection   
					device, it does not offer guaranteed protection against burglary. Any   
					Intrusion Detection device is subject to compromise or failure to warn   
					for a variety of reasons:   
					Honeywell International Inc. (“Seller”), 165 Eileen Way, Syosset, New   
					York 11791, warrants its product(s) to be in conformance with its own   
					plans and specifications and to be free from defects in materials and   
					workmanship under normal use and service for 24 months from the   
					date stamp control on the product(s) or, for product(s) not having an   
					Honeywell date stamp, for 12 months from date of original purchase   
					unless the installation instructions or catalog sets forth a shorter   
					period, in which case the shorter period shall apply. Seller's obligation   
					shall be limited to repairing or replacing, at its option, free of charge for   
					materials or labor, any product(s) which is proved not in compliance   
					with Seller's specifications or proves defective in materials or   
					workmanship under normal use and service. Seller shall have no   
					obligation under this Limited Warranty or otherwise if the product(s) is   
					altered or improperly repaired or serviced by anyone other than   
					Honeywell factory service. For warranty service, return product(s)   
					transportation prepaid, to Honeywell Factory Service, 165 Eileen Way,   
					Syosset, New York 11791.   
					THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, OF   
					MERCHANTABILITY, OR FITNESS FOR A PARTICULAR PURPOSE   
					OR OTHERWISE, WHICH EXTEND BEYOND THE DESCRIPTION   
					ON THE FACE HEREOF. IN NO CASE SHALL SELLER BE LIABLE   
					TO ANYONE FOR ANY CONSEQUENTIAL OR INCIDENTAL   
					DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY,   
					EXPRESS OR IMPLIED, OR UPON ANY OTHER BASIS OF   
					LIABILITY WHATSOEVER, EVEN IF THE LOSS OR DAMAGE IS   
					CAUSED BY THE SELLER'S OWN NEGLIGENCE OR FAULT.   
					• Passive Infrared Motion Detectors can detect intrusion only within the   
					designed ranges as diagrammed in this installation manual.   
					• Passive Infrared Motion Detectors do not provide volumetric area   
					protection. They do create multiple beams of protection, and intrusion   
					can be detected only in unobstructed areas covered by those beams.   
					• Passive Infrared Detectors cannot detect motion or intrusion that   
					takes place behind walls, ceilings, floors, closed doors, glass   
					partitions, glass doors, or windows.   
					• Mechanical tampering, masking, painting, or spraying of any material   
					on the lenses, windows or any part of the optical system can reduce   
					the detection ability of the Passive Infrared Motion Detector.   
					• Passive Infrared Detectors sense changes in temperature; however,   
					as the ambient temperature of the protected area approaches the   
					temperature range of 90° to 105°F (32° to 40°C), the detection   
					performance can decrease.   
					• This Passive Infrared Detector will not operate without the   
					appropriate battery installed, or if the battery is weak or improperly   
					connected (i.e., reversed polarity).   
					• Passive Infrared Detectors, like other electrical devices, are subject   
					to component failure. Even though this equipment is designed to last   
					as long as 10 years, the electronic components in it could fail at any   
					time.   
					We have cited some of the most common reasons that a Passive   
					Infrared Motion Detector can fail to catch intrusion. However, this does   
					not imply that these are the only reasons, and therefore it is   
					recommended that weekly testing of this type of unit, in conjunction with   
					weekly testing of the entire alarm system, be performed to ensure that   
					the detectors are working properly.   
					Installing an alarm system may make the owner eligible for a lower   
					insurance rate, but an alarm system is not a substitute for insurance.   
					Homeowners, property owners and renters should continue to act   
					prudently in protecting themselves and continue to insure their lives and   
					property.   
					We continue to develop new and improved protection devices. Users of   
					alarm systems owe it to themselves and their loved ones to learn about   
					these developments.   
					Seller does not represent that the product(s) it sells may not be   
					compromised or circumvented; that the product(s) will prevent any   
					personal injury or property loss by burglary, robbery, fire or otherwise;   
					or that the product(s) will in all cases provide adequate warning or   
					protection. Customer understands that   
					a 
					properly installed and   
					maintained alarm system may only reduce the risk of a burglary,   
					robbery, fire, or other events occurring without providing an alarm, but   
					it is not insurance or a guarantee that such will not occur or that there   
					will be no personal injury or property loss as   
					a 
					result.   
					CONSEQUENTLY, SELLER SHALL HAVE NO LIABILITY FOR ANY   
					PERSONAL INJURY, PROPERTY DAMAGE OR OTHER LOSS   
					BASED ON A CLAIM THAT THE PRODUCT(S) FAILED TO GIVE   
					WARNING. HOWEVER, IF SELLER IS HELD LIABLE, WHETHER   
					DIRECTLY OR INDIRECTLY, FOR ANY LOSS OR DAMAGE   
					ARISING UNDER THIS LIMITED WARRANTY OR OTHERWISE,   
					REGARDLESS OF CAUSE OR ORIGIN, SELLER'S MAXIMUM   
					LIABILITY SHALL NOT IN ANY CASE EXCEED THE PURCHASE   
					PRICE OF THE PRODUCT(S), WHICH SHALL BE THE COMPLETE   
					AND EXCLUSIVE REMEDY AGAINST SELLER.   
					This warranty replaces any previous warranties and is the only   
					warranty made by Seller on this product(s). No increase or alteration,   
					written or verbal, of the obligations of this Limited Warranty is   
					authorized.   
					FCC Notice: This equipment has been tested and found to comply with the limits for   
					a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are   
					designed to provide reasonable protection against harmful interference in a   
					residential installation. This equipment generates, uses and can radiate radio   
					frequency energy, and if not installed and used in accordance with the instructions   
					may cause harmful interference to radio communications. However, there is no   
					guarantee that interference will not occur in a particular installation.   
					If this equipment does cause harmful interference to radio or television reception,   
					which can be determined by turning the equipment off and on, the user is   
					encouraged to try to correct the interference by one or more of the following   
					measures:   
					1) Reorient or relocate the receiving antenna,   
					2) Increase the separation between the equipment and receiver,   
					3) Connect the equipment into an outlet on a circuit different from that to which the   
					receiver is connected.   
					4) Consult the dealer or an experienced radio/television technician for help.   
					Changes or modifications to this equipment not expressly approved by Honeywell   
					may void the user’s authority to operate this equipment.   
					165 Eileen Way, Syosset, New York 11791   
					Copyright © 2004 Honeywell International Inc.   
					ÊK5942V2\Š   
					K5942V2   
					7/04   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				 |