Honeywell Home Security System 2 Partitioned Security System User Manual |
ꢀ
ꢀ
$'(0&2ꢀ9,67$ꢁꢂꢃꢀ
ꢀꢁ3DUWLWLRQHGꢂ6HFXULW\ꢂ6\VWHPꢂ
ꢂ
ꢂ
3URJUDPPLQJ *XLGH
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
N7001PRV5 5/04 Rev A
Download from Www.Somanuals.com. All Manuals Search And Download.
Recommended Programming Procedure
The following is a step-by-step procedure recommended for programming your VISTA-40 system.
1. Set the keypads (and other peripheral devices) to the appropriate addresses.
2. Set factory defaults by pressing ✱97.
This will automatically enable keypad addresses 00-01, so be sure at least one keypad is set to one of these
addresses.
3. Program system-wide (global) data fields.
Using the programming form as a guide, enter program mode and program all system-wide programming
fields. These options affect the entire system, regardless of partitions. They include control options,
downloader and dialer options, RF options, event logging options, etc. Refer to the Program Field Index for a
listing of the program fields and their function.
Note that field 2✱00 (number of partitions) must be programmed before continuing.
4. Program partition-specific fields.
When the system-wide fields have been programmed, program all partition-specific programming fields by
first pressing ✱91 to select a partition (while still in data field program mode). Then enter the first partition-
specific field number ✱09. When you are finished, the next partition-specific field is automatically displayed.
Partition-specific fields can have different values for each partition. To program the fields for the next partition,
press ✱91, enter the desired partition number, then enter field ✱09. Refer to the MECHANICS OF
PROGRAMMING section in the ADEMCO VISTA-40 Installation and Setup Guide for detailed instructions.
5. Use #93 Menu Mode for device programming.
Refer to Device Programming in this guide to assign keypad ID numbers and default partitions for each
keypad, and to selectively suppress certain keypad sounding options. Also use this mode to assign RF
receivers, relay modules, and the VIP module.
6. Use #93 Menu Mode for zone programming.
Refer to Zone Programming in this guide to program zone response types, assign right loop zones and
wireless zones, assign zones to partitions, and to program alarm report codes.
7. Use #93 Menu Mode for programming relays.
Refer to Relay Programming in this guide to program desired relay operation.
8. Program Communication options.
Refer to System Communication section in the ADEMCO VISTA-40 Installation and Setup Guide for detailed
instructions. Then use #93 menu mode to program report codes.
9. Use #93 Menu Mode for programming alpha descriptors.
Refer to Alpha Programming in this guide to enter zone and partition descriptors and a custom installer’s
message.
10. Use #93 Menu Mode for relay voice descriptors and custom word substitutes.
Refer to Relay Voice Descriptors in this guide for further instructions for programming relay descriptors to be
annunciated by the VIP module, as well as the Custom Index section for custom word substitutes.
11. Define user access codes.
Refer to User Access Codes in the ADEMCO VISTA-40 Installation and Setup Guide to program authority
level, O/C reporting option, partition assignments, and RF key assignments for each user.
12. Exit Programming Mode.
Exit programming mode by pressing either ✱98 or ✱99. Additional entries of ✱99 are required if the exit is
being done from fields 1✱00 and above.
To prevent re-access to programming mode using the Installer’s code, use ✱98. The only way to re-access
programming mode is by depressing both the [✱] and [#] keys at the same time within 30 seconds of power-
up.
Exiting by using ✱99 always allows reentry into programming mode using the Installer code. Either way of
exiting allows access via downloading. Note that if local programming lockout is set via downloading,
programming mode cannot be entered at the keypad.
– 3 –
Download from Www.Somanuals.com. All Manuals Search And Download.
Program Field Index
On the following pages, the programming fields have been arranged in numerical order. Use this index to cross-reference the
fields on the programming form.
Field
Group
Field Group
Communications
Field Group
# 93 Menu Mode
*00
*02
*03
*04
*05
*09
*10
*11
*12
*13
*14
*15
*16
*17
*19
*20
*21
*22
*23
*24
*25
*26
*27
*28
*29
*30
*31
*32
*33
*34
*35
*36
*37
*38
*39
*40
*41
*42
*43
*44
*45
*46
*47
*48
System-Wide
*49
*50
*51
*52
*53
*54
*55
*56
*57
*58
*59
*60
*61
*62
*63
*64
*65
*66
*67
*68
*69
*70
*71
*72
*73
*74
*75
*76
*77
*78
*79
*80
*81
*82
*83
*84
*85
*86
*87
*88
*89
*90
1*01
1*02
1*03
1*04
1*05
1*06
1*07
1*08
1*09
1*28
1*29
1*30
1*31
1*32
1*33
1*34
1*40
1*41
1*43
1*44
1*45
1*46
1*47
1*48
1*49
1*52
1*53
1*57
1*58
1*60
1*66
1*70
1*71
1*74
1*75
1*76
2*00
2*01
2*02
2*17
2*18
2*19
2*20
2*21
# 93 Menu Mode
# 93 Menu Mode
# 93 Menu Mode
# 93 Menu Mode
Partition-Specific
Partition-Specific
Partition-Specific
Partition-Specific
Partition-Specific
System-Wide
System-Wide
Partition-Specific
System-Wide
System-Wide
System-Wide
System-Wide
Partition-Specific
Partition-Specific
System-Wide
Communications
Communications
Communications
Communications
Communications
Communications
Communications
Communications
Communications
Communications
Communications
Communications
Communications
Communications
Communications
Communications
Communications
Communications
Communications
Communications
Communications
Communications
Communications
Communications
Communications
Communications
Communications
Communications
Communications
Communications
Communications
Communications
Communications
Communications
Partition-Specific
Partition-Specific
System-Wide
# 93 Menu Mode
# 93 Menu Mode
# 93 Menu Mode
# 93 Menu Mode
# 93 Menu Mode
# 93 Menu Mode
System-Wide
System-Wide
System-Wide
System-Wide
System-Wide
Communications
Communications
Communications
Communications
Partition-Specific
System-Wide
Partition-Specific
System-Wide
Partition-Specific
System-Wide
System-Wide
Partition-Specific
System-Wide
System-Wide
System-Wide
System-Wide
System-Wide
System-Wide
System-Wide
System-Wide
System-Wide
Partition-Specific
System-Wide
System-Wide
System-Wide
System-Wide
Partition-Specific
System-Wide
Partition-Specific
System-Wide
System-Wide
Communications
Communications
System-Wide
Partition-Specific
Communications
Communications
Partition-Specific
Communications
Communications
System-Wide
System-Wide
System-Wide
Partition-Specific
Partition-Specific
Communications
System-Wide
Communications
Communications
Communications
Communications
Communications
Communications
Communications
Partition-Specific
Partition-Specific
Communications
Partition-Specific
# 93 Menu Mode
# 93 Menu Mode
– 4 –
Download from Www.Somanuals.com. All Manuals Search And Download.
VISTA-40 Programming Form
Some fields are programmed for each partition (shown as shaded fields). If you are programming a multiple-partition system,
see the Partition-Specific Fields section for programming these fields. Standard default (*97) values are shown in brackets.
*00 INSTALLER CODE
| | |
*25 BURG.TRIGGER FOR RESPONSE TYPE 8 [1]
Enter 4 digits, 0-9 [4140]
1=enable; 0=disable
*02 *05 RESPONSE TYPES FOR ZONES
*26 INTELLIGENT TEST REPORTING
[0]
Skip these fields. Use #93 Menu Mode, Zone
Programming to program the response types.
1=yes (no report sent if any other report was recently sent);
0=no (send report at programmed interval, field *27)
Must be 0 for UL installations.
*09 ENTRY DELAY #1
[02]
[03]
[06]
|
|
|
00, 02-15 times 15 seconds
Maximum "03" for UL.
*27 TEST REPORT INTERVAL
[024]
| |
Enter interval in hours, 001-199; 000=no report;
Max. 024 for UL installations.
*10 EXIT DELAY #1
00, 03-15 times 15 seconds
Maximum "04" for UL installations.
*28 POWER UP IN PREVIOUS STATE
[1]
[1]
[0]
1=yes; 0=no; "1" for UL installations.
*11 ENTRY DELAY #2
*29 QUICK ARM
00, 02-15 times 15 seconds (must be longer than Entry Delay
#1). Maximum "03" for UL installations.
1=yes; 0=no
*30 TOUCHTONE OR ROTARY DIAL
*12 EXIT DELAY #2
[08]
|
1=TouchTone; 0=rotary
00, 03-15 times 15 seconds (must be longer than Exit Delay
#1). Maximum "04" for UL installations.
*31 PABX ACCESS CODE
|
|
|
|
|
|
|
|
*13 ALARM SOUNDER DURATION
[04]
|
00-09; B-F (11-15)
01-15 times 2 minutes. Must be minimum 16 minutes for UL
installations.
*32 PRIM. SUBS. ACCT #
Enter 00-09; B-F (11-15) [15 15 15 15]
*14 ZONE 9 RESPONSE TIME
[0]
*33 PRIMARY PHONE NUMBER
Enter 1 for fast response time 10ms
Enter 0 for normal response time 350ms.
Must be 0 for UL installations.
*15 KEYSWITCH ASSIGNMENT
[0]
[0]
Enter 0-9 for each digit. Enter #11 for *, #12 for #,
#13 for 2 second pause
Enter partition in which keyswitch used,
1-2; 0=disable
*34 SECONDARY PHONE NUMBER
*16 CONFIRMATION OF ARMING DING
1=enable; 0=disable.
Must be "1" for UL Installations.
*17 AC LOSS KEYPAD SOUNDING
[0]
[0]
Enter 0-9 for each digit. Enter #11 for *, #12 for #,
#13 for 2 second pause
1=yes; 0=no
*35 DOWNLOAD PHONE NO.
*19 RANDOMIZE AC LOSS REPORT
1=10-40 min; 0=normal report (about 2 min. after AC loss).
*20 VIP MODULE PHONE CODE
|
|
Enter 0-9 for each digit. Enter #11 for *, #12 for #,
#13 for 2 second pause
Enter 01 - 09 for the first digit; enter
11 for “*” or 12 for “#” for the second digit.
Must be set to "0" for UL installations.
[00],
[11]
*36 DOWNLOAD ID NO.
|
|
|
|
|
|
|
|
*21 PREVENT FIRE TIMEOUT
[0]
Enter 00-09; A-F (10-15) [15 15 15 15 15 15 15 15]
1=No timeout; 0=Timeout.
*37 DOWNLOAD COMMAND ENABLES
*22 KEYPAD PANIC ENABLES
[001]
0
1=enable; 0=disable
995 996 999
Dlr ShtdwnSys ShtdwnNot UsedRmt BypRmt DisarmRmt ArmUpld PgmDwnld Pgm
See field 1*53 for Callback disable option; [1=enable];
0=disable. For UL installations, all entries must be "0."
*23 MULTIPLE ALARMS
[1]
1=yes; 0=no
*38 PREVENT ZONE XX BYPASS
[00]
|
*24 IGNORE EXPANSION ZONE TAMPER
[0]
01-64; 00 if all zones can be bypassed
1=Ignore; 0=Enable tamper for RF and RPMs.
Must be "0" for UL installations if using these devices.
– 5 –
Download from Www.Somanuals.com. All Manuals Search And Download.
*58 SUPERVISORY AND RESTORE CODES FOR ZONES
*39 ENABLE OPEN/CLOSE REPORT FOR
[0]
01-16. Enter 00-09; B-F (11-15). Default = [00 00 00 00 00]
INSTALLER CODE 1=enable; 0=disable
|
|
Trbl
|
|
Byp
|
*40 OPEN/CLOSE REPORT FOR KEYSWITCH [0]
Alarm Rst
Trbl Rst
Byp Rst
1=enable; 0=disable
*59 *62 ALARM REPORT CODES & ID DIGITS FOR
ZONES 17-32.
*41 NORMALLY CLOSED or EOLR (Zones 2-8) [0]
Skip these fields. Use #93 Menu Mode, Zone
Programming to program the report codes.
1=N.C.loops; 0=EOLR supervision.
Must be "0" for UL installations.
*63 SUPERVISORY AND RESTORE CODES FOR ZONES
17-32. Enter 00-09; B-F (11-15). Default = [00 00 00 00 00]
*42 DIAL TONE PAUSE
[0]
[1]
|
|
|
|
|
0=5 seconds; 1=11 seconds; 2=30 seconds.
Must be "0" UL Installations.
Alarm Rst
Trbl
Trbl Rst
Byp
Byp Rst
*43 DIAL TONE DETECTION
*64 *67 ALARM REPORT CODES & ID DIGITS FOR
ZONES 33-48.
1=wait for true dial tone; 0=pause, then dial
Skip these fields. Use #93 Menu Mode, Zone
Programming to program the report codes.
*44 RING DETECTION COUNT
[00]
|
*68 SUPERVISORY AND RESTORE CODES FOR ZONES
01-14; 15=answering machine; 00=no detection.
Must be "00" for UL Burglary.
33-48. Enter 00-09; B-F (11-15). Default = [00 00 00 00 00]
|
|
|
|
|
*45 PRIMARY FORMAT
[1]
Alarm Rst
Trbl
Trbl Rst
Byp
Byp Rst
0=Low Speed; 1=Contact ID; 2=ADEMCO High Speed;
3= ADEMCO Express
*69 *72 ALARM REPORT CODES & ID DIGITS FOR
ZONES 49-64.
*46 LOW SPEED FORMAT (Primary)
[0]
Skip these fields. Use #93 Menu Mode, Zone
Programming to program the report codes.
0= ADEMCO Low Speed; 1=Sescoa/Radionics
*73 SUPERVISORY AND RESTORE CODES FOR ZONES
*47 SECONDARY FORMAT
[1]
49-64. Enter 00-09; B-F (11-15). Default = [00 00 00 00 00]
0=Low Speed; 1=Contact ID; 2= ADEMCO High Speed;
3= ADEMCO Express
|
|
|
|
|
Alarm Rst
Trbl
Trbl Rst
Byp
Byp Rst
*48 LOW SPEED FORMAT (Sec.)
[0]
*74 *77 ALARM REPORT CODES & ID DIGITS FOR
0= ADEMCO Low Speed; 1=Sescoa/Radionics
ZONES 87-99.
Skip these fields. Use #93 Menu Mode, Zone
Programming to program the report codes.
*49 CHECKSUM VERIFICATION
[0] [0]
1=yes; 0=no
Prim
Sec
*78 SUPERVISORY AND RESTORE CODES FOR ZONES
87-99. Enter 00-09; B-F (11-15). Default = [00 00 00 00 00]
*50 SESCOA/RADIONICS SELECT
[0]
[0]
1=Sescoa; 0=Radionics
|
|
|
|
|
Alarm Rst
Trbl
Trbl Rst
Byp
Byp Rst
*51 DUAL REPORTING
1=yes; 0=no If used with Spilt Reporting "1" option (1*34),
alarms and alarm restores go to both primary & secondary
numbers, while all other reports go to secondary only. If used
with Split Reporting "2" option, alarms and alarm restores go to
both, open/close and test messages go to secondary only,
while all other reports go to primary.
ZONE TYPE RESTORE ENABLES
*79 FOR ZONE TYPES 1-8
1
2
3
4
5
6
7
8
*52 STANDARD/EXPANDED REPORT FOR PRIMARY
1=enable; [0=disable]
*80 FOR TYPES 9, 10
[0 0 0 0 0 0]
Alarm Rstr Byp Trbl O/C LoBat
0=standard; 1=expanded;
9
10
1=enable; [0=disable]
Note: Expanded overrides 4+2 format.
*53 STANDARD/EXPANDED REPORT FOR SECONDARY
[0 0 0 0 0 0]
Alarm Rstr Byp Trbl O/C LoBat
0=standard; 1=expanded;
Note: Expanded overrides 4+2 format.
*54 *57 ALARM REPORT CODES & ID DIGITS FOR
ZONES 01-16.
Skip these fields. Use #93 Menu Mode, Zone
Programming to program the report codes.
– 6 –
Download from Www.Somanuals.com. All Manuals Search And Download.
*80 *81
SYSTEM NON-ALARM CODES
Enter 00-09; B-F (11-15).
1*30 RF RCVR CHECK-IN INTERVAL
[06]
[12]
|
|
Default = 00 for all reports
02-15 times 2 hours; 00 disables supervision
*80 1st Digit
*81 2nd Digit
1*31 RF XMITTER CHECK-IN INTERVAL
|
|
|
|
|
|
|
|
|
|
|
Close
02-15 times 2 hours; 00 disables transmitter supervision
|
|
|
|
|
|
|
|
|
1*33 TOUCHTONE W/ROTARY BACKUP
[0]
Open
1=enable; 0=disable
Low Battery
1*34 COMM. SPLIT REPORTING
[0]
Low Battery Restore
AC Loss
0=no; 1=alarms and alarm restores primary, others secondary;
2=open/close, test secondary, others primary. See 51 for
comments if using with dual reporting.
1*40 1*41 NON-ALARM DIALER CODES
Enter 00-09; B-F (11-15).
AC Restore
Test
Default = 00 for all reports
1*40 1st Digit
1*41 2nd Digit
|
|
Armed STAY
Power Up
|
|
Time/Date Set or Event Log Reset
Cancel
1*43 PERM. KEYPAD BACKLIGHT
[0]
Program Tamper
1=enable; 0=disable When disabled, display lights when any
key is pressed, and turns off after period of keypad inactivity.
*83 FIRST TEST REPORT TIME
|
|
|
1*44 WIRELESS KEYPAD TAMPER
[0]
[Day 00; hour 12; min 00] Days 01-07 Hours 00-23 Min 00-
59; 00 in all boxes = instant (Day 01= Monday)
DETECTION
1=enable; 0=disable.
Must be "0" for UL installations.
*84 SWINGER SUPPRESSION
[03]
|
01-15 alarms
Must be "00" (disabled) for UL.
*85 ENABLE DIALER REPORTS FOR PANICS & DURESS
1*45 EXIT DELAY SOUNDING
[0]
1=enable; 0=disable. Produces quick beeping during exit
delay if enabled.
NOTE: See page 32, “SOUND OPTION”, prompt for
disabling the entry/exit beeps on individual keypads.
1=enable; [0=disable]
995 996 999 Duress
1*46 AUXILIARY OUTPUT MODE
[0]
*87 ENTRY WARNING
[1]
Enter 0 for ground start output.
Enter 1 for open/close trigger.
Enter 2 for keypad-like sounding.
Enter 3 if AAV module is being used.
NOTE: Only one of the above options may be active within
the system.
1=continuous; 0=3 beeps
*86 4208 MODULE ZONE ASSIGMENT
[0]
1 = allows 8 zones on one module (10-17), but prevents any
other polling loop expansion. 0 = all other setups.
*88 BURG. ALARM COMM. DELAY
[0]
1*47 CHIME ON EXTERNAL SIREN
[0]
1=16 seconds; 0=no delay
Must be "0" for UL installations.
1=enable; 0=disable
1*48 WIRELESS KEYPAD ASSIGNMENT
[0]
*89 RESTORE REPORT TIMING
[0]
0=disable; enter partition in which RF keypad used, 1-2.
Must be "0" for UL installations.
0=Instant; 1=At bell timeout if zone is restored; 2=when
system is disarmed. Must be "0" for UL installations.
1*49 SUPPRESS TX SUPERVISION SOUND
[1]
*90 SEC. SUBS. ACCT #
|
|
|
|
1=disable; 0=enable.
Must be "0" for UL installations.
Enter 00-09; B-F (11-15) [15 15 15 15]
2nd Page Programming Fields (press *94)
1*52 SEND CANCEL IF ALARM + OFF
[0]
[0]
[0]
1*01 1*09 ASSIGN RESPONSE TYPE FOR ZONES.
1=no restriction; 0=within bell timeout period only
Skip these fields. Use #93 Menu Mode, Zone
Programming to program the response types.
1*53 DOWNLOAD CALLBACK
MISCELLANEOUS WIRELESS OPTIONS
1=callback not required; 0=callback required.
Fields 1*28 - 1*31 are not applicable for UL installations.
1*57 5800 RF BUTTON GLOBAL ARM
1*28 RF TX LOW BATTERY SOUND
[0]
1=enable; 0=disable
1=immediate; 0=when disarmed
1*29 RF TX LOW BATTERY REPORTING
[0]
1=enable; 0=disable
– 7 –
Download from Www.Somanuals.com. All Manuals Search And Download.
1*58 5800 RF BUTTON FORCE ARM
[0]
2*02 DAYLIGHT SAVING TIME
[1, 5]
|
Enter "1" to enable. If a zone is faulted after pressing button,
keypad will beep once. Pressing the button again within 4
sec. bypasses the zone. Enter "0" to disable.
Must be "0" for UL installations.
START/END WEEKEND
Enter 1-7. 1=first; 2=second; 3=third; 4=fourth; 5=last;
6=next to last; 7=3rd from last [1,5]
Start | End
2*17 NUMBER OF CODES PER PARTITION
1*60 ZONE 5 AUDIO ALARM VERIFICATION
[0]
[0]
|
|
Enter 1 If 2-way audio (AAV) is being used; Enter 0 if it is
not.
Enter 01-69 for each partition. The total must not exceed 70.
Must be "0" for UL installations.
2*18 ENABLE GOTO FOR THIS PARTITION
[0]
[0]
1=Allow log-on from other partition; 0=disable
1*66 SILENCE BELLS DURING AAV
[0]
Enter 1 to alarm sounders during AAV session.
Enter 0 to have alarm sounders continue to sound during
AAV session. Must be 0 for UL installations.
2*19 USE PARTITION DESCRIPTORS
0=disable; 1=enable
1*70 EVENT LOG TYPES
2*20 ENABLE J7 TRIGGERS FOR PARTITION [1]
0=disable for displayed partition; 1=enable for displayed
partition
[1 0 0 0 1]
Alarm Chk Byp O/C Syst
2*21 ENABLE SUPERVISION PULSES FOR LRR
1=enable; 0=disable
TRIGGER OUTPUTS
[000]
| |
1*71 12/24 HOUR TIME STAMP FORMAT
[0]
Used for supervised connection to 7920SE.
F
B
P
0=12 hour; 1=24 hour
Enter 0 to disable or 1 to enable the listed outputs.
F= Fire; B= Burglary; P= Silent Panic/Duress.
Must be 1 for UL. Installations.
1*74 RELAY TIMEOUT XXX MINUTES [000]
| |
Enter the relay timeout, 000-127 in multiples of 2 minutes,
desired for #93 Menu Mode Relay Programming output
command "56."
SUMMARY OF PROGRAMMING COMMANDS
To enter program mode, enter installer code + [8] + [0] +
[0]
1*75 RELAY TIMEOUT YYY SECONDS [000]
| |
•
Enter the relay timeout, 000-127 seconds for #93 Menu
Mode Relay Programming command "57."
•
•
•
To set standard defaults, press *97
To change to next page of program fields, press *94
To return to previous set of fields, press *99
To erase account and phone number field entries,
press [*] + field number + [*]
To assign zone descriptors, press #93 + follow menu
prompts
To add custom words, press #93 + follow menu prompts
To enter Installer's Message, press #93 + follow menu
prompts
1*76 ACCESS CONTROL RELAY
[00]
|
Relay will be pulsed for 2 seconds whenever code + [0] is
pressed. Enter 00-08; 00=none.
Must be "00" for UL.
•
•
3rd Page Programming Fields (press *94)
•
•
2*00 NUMBER OF PARTITIONS
[1]
Enter 1-2
•
To exit program mode, enter *99 OR *98: *99 allows re-
access to programming mode by installer code. *98
prevents re-access to programming mode by installer
code.
2*01 DAYLIGHT SAVING TIME [04, 10]
|
|
START/END MONTH
00-12; if no daylight saving time, enter 00,00
Start End
– 8 –
Download from Www.Somanuals.com. All Manuals Search And Download.
Partition-Specific Fields
(Duplicate this page for each partition in the installation.)
To program these fields,
1. Press *91 to select a partition.
2. Enter a partition-specific field number (ex. *09).
3. Make the required entry.
4. Repeat steps 1-3 for the other partition in the system.
PARTITION #____ PROGRAM FIELDS
1st Page Fields
*88 BURG. ALARM COMM. DELAY
[0]
*09 ENTRY DELAY #1
[02]
[04]
[06]
[08]
[04]
|
|
|
|
|
1=16 seconds; 0=no delay. Must be "0" for UL installations.
00, 02-15 times 15 seconds.
Maximum 03 for UL Listed installations.
*90 SEC. SUBS. ACCT #
|
|
|
|
Enter 00-09; B-F (11-15) [15 15 15 15]
2nd Page Fields
*10 EXIT DELAY #1
00, 03-15 times 15 seconds.
Maximum 04 for UL Listed installations.
1*43 PERM. KEYPAD BACKLIGHT
[0]
1=enable; 0=disable When disabled, display lights when
any key is pressed, and turns off after period of keypad
inactivity.
*11 ENTRY DELAY #2
00, 02-15 times 15 seconds.
Maximum 03 for UL installations.
1*45 EXIT DELAY SOUNDING
[0]
*12 EXIT DELAY #2
1=enable; 0=disable. Produces quick beeping during exit
delay if enabled.
00, 03-15 times 15 seconds.
Maximum 04 for UL installations.
1*47 CHIME ON BELL 1
[0]
*13 ALARM SOUNDER DURATION
1=enable; 0=disable
01-15 times 2 minutes.
Must be minimum 16 minutes for UL installations.
1*52 SEND CANCEL IF ALARM + OFF
[0]
*16 CONFIRMATION OF ARMING DING
[0]
1=no restriction; 0=within Bell Timeout period only
1=enable; 0=disable.
Must be "1" for UL installations.
1*76 ACCESS CONTROL RELAY FOR PART.[00]
|
Relay will be pulsed for 2 seconds whenever code + [0] is
pressed. Enter 00-08; 00=none. Must be "00" for UL installs.
3rd Page Fields
*22 KEYPAD PANIC ENABLES
[001]
1=enable; 0=disable
995 996 999
[1]
2*18 ENABLE GOTO FOR THIS PARTITION
[0]
*23 MULTIPLE ALARMS
1=Allow log-on from other partitions; 0=disable
1=yes; 0=no. Must be 1 for UL installations.
2*20 ENABLE J7 TRIGGERS BY PARTITION
[1]
*29 QUICK ARM
[1]
0=disable; 1=enable for
1=yes; 0=no
*32 PRIM. SUBS. ACCT #
|
|
|
|
SUMMARY OF PROGRAMMING COMMANDS
Enter 00-09; B-F (11-15) [15 15 15 15]
•
To enter program mode, enter installer code + [8] + [0] +
[0]
*38 PREVENT ZONE XX BYPASS
[00]
|
|
•
•
•
•
To set standard defaults, press *97
To change to next page of program fields, press *94
To return to previous set of fields, press *99
To erase account and phone number field entries,
press [*] + field number + [*]
To assign zone descriptors, press #93 + follow menu
prompts
To add custom words, press #93 + follow menu prompts
To enter Installer's Message, press #93 + follow menu
prompts
001-64; 000 if all zones can be bypassed
*39 ENABLE OPEN/CLOSE REPORT
[1]
FOR INSTALLER CODE
1=enable; 0=disable
•
*84 SWINGER SUPPRESSION
[03]
01-15 alarms; Must be "00" (disabled) for UL installations.
•
•
*85 ENABLE DIALER REPORTS FOR PANICS & DURESS
1=enable; [0=disable]
995 996 999 Duress
•
To exit program mode, enter *99 OR *98: *99 allows re-
access to programming mode by installer code. *98
prevents re-access to programming mode by installer
code.
*87 ENTRY WARNING
[1]
1=continuous; 0=3 beeps
– 9 –
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming With #93 Menu Mode
NOTE: The following field should be preset before beginning: 2*00 Number of Partitions. In addition, receivers should
be programmed via Device programming.
After programming all system related programming fields in the usual way, press #93 while still in programming mode to
display the first choice of the menu driven programming functions. Press 0 (NO) or 1 (YES) in response to the displayed menu
selection. Pressing 0 will display the next choice in sequence.
For UL installations, verify that the audio alarm verification feature is disabled.
U
L
#93 MENU MODE KEY COMMANDS
The following is a list of commands used while in the menu mode.
#93
[4]
[#]
Enters Menu mode
Serves as ENTER key. Press to have keypad accept entry.
Backs up to previous screen.
0
Press to answer NO
1
Press to answer YES
01-09
00
All data entries are either 1-digit or 2-digit entries.
Exits menu mode, back into field programming mode, when entered at the first question for each category.
Menu selections are as follows:
PROMPT
EXPLANATION
For programming the following:
ZONE PROG?
1 = YES 0 = NO
•
•
•
•
•
•
Zone Number
Zone Response Type
Partition Number for Zone
Dialer report code for zone
Input Device Type for zone (whether RF, polling loop, etc.)
Enrolling serial numbers of 5800 Series transmitters & serial polling loop devices into the system.
0
Same as Zone Programming except:
EXPERT MODE?
1 = YES 0 = NO
•
•
Done with a minimum number of keystrokes.
0
0
Can program wireless keys using pre-defined templates.
For entering alpha descriptors for the following:
ALPHA PROG?
1 = YES 0 = NO
•
•
•
•
•
Zone Descriptors
Installer's Message
Custom Words
Partition Descriptors
Relay Descriptors
For defining the following device characteristics for addressable devices, including keypads, RF receivers
(5881), output relay modules (4204), and 4285/4286 VIP Module:
DEVICE PROG?
1 = YES 0 = NO
0
•
•
•
•
Device Address
Device Type
Keypad Options (incl. partition assignment)
RF House ID
For defining relay functions.
RELAY PROG?
1 = YES 0 = NO
0
0
0
For entering voice descriptors for relays to be used with the 4285/4286 VIP Module.
For creating custom word substitutes for VIP Module annunciation.
RLY VOICE DESCR?
1 = YES 0 = NO
CUSTOM INDEX ?
1 = YES 0 = NO
– 10 –
Download from Www.Somanuals.com. All Manuals Search And Download.
Zone Programming
If using 5800 Series transmitters, do not the install batteries until you are ready to enroll them. After enrolling
the transmitter, the battery need not be removed. This is to prevent enrolling the wrong serial number.
PROMPT
EXPLANATION
Press 1 to enter ZONE PROGRAMMING mode. The following screens appear. Press [✱] to display the next
screen. Press # to display a previous screen.
ZONE PROG?
1 = YES 0 = NO
0
0
This prompt appears once upon entering Zone Programming Mode.
If “Yes,” Confirmation prompts will be displayed after the device’s Serial and Loop numbers have been
entered later.
SET TO CONFIRM?
1 = YES 0 = NO
Enter the 2-digit zone number to be programmed, as follows:
Protection Zones = 01–64
ENTER ZONE NO.
00 = QUIT
10
System Supervisory Zones = 88, 89, 90, 91, 92 (duress), 97
Keypad Panic Zones = 95, 96, 99
↑
Zone 10 entered
Press [✱] to continue.
This display appears, showing a summary of the zone's current programming. ZT = Zone Type, P =
Partition, RC = Report Code, In = the input type of device, and L = the device's loop number to which the
sensor is connected.
10 ZT
00
P
RC In L
10 00 1
1
Some devices can support more than one zone by means of individual loops (for example, 5801, 5804,
5816, 5817, etc.). If the zone is not programmed, the display appears as shown here. If you are checking a
zone's programming, and it is programmed satisfactorily, press [#] to back up one step and enter another
zone number, if desired.
Press [✱] to continue.
Each zone must be assigned a zone type, which defines the way in which the system responds to faults in
that zone. Refer to the Zone Type Definitions section in the ADEMCO VISTA-40 Installation and Setup
Guide for detailed definitions of each zone type. Enter the zone type desired (or change it, if necessary).
Available zone types are listed below.
10 ZONE TYPE
PERIMETER
03
Zone number 10 and Zone
Type 03 entry shown
00 = Assign for Unused Zones
01 = Entry/Exit #1, Burglary
02 = Entry/Exit #2, Burglary
03 = Perimeter, Burglary
04 = Interior Follower, Burglary
05 = Trouble Day/Alarm Night
06 = 24 Hr. Silent Alarm
08 = 24 Hr. Auxiliary
09 = Fire Without Verification
10 = Interior Delay, Burglary
20 = Arm–STAY†
21 = Arm AWAY†
22 = Disarm†
†
These are special zone
types used with 5800
Series Wireless
Pushbutton Units that
result in arming the system
in the STAY or AWAY
mode, or disarming the
system, depending on the
selection made.
23 = No Alarm Response
(e.g., relay activation)
07 = 24 Hr. Audible Alarm
Press [✱] to continue.
Enter the partition number (1–2) you are assigning this zone to.
Press [✱] to continue.
10 Partition
1
Enter the report code. The report code consists of 2 hexadecimal digits, each in turn consisting of 2
numerical digits. For example, for a report code of "3C," enter 03 for "3" and 12 for "C."
(Refer to the System Communication section in the Installation and Setup Guide for more information about
10 REPORT CODE
1st 03 2nd 12
3C
report codes and reporting formats.)
Press [✱] to continue.
– 11 –
Download from Www.Somanuals.com. All Manuals Search And Download.
PROMPT
EXPLANATION
Enter the input device type as follows:
00 = not used
10 INPUT TYPE
RF Xmitter
3
01 = hardwired
Input types 4 & 5 are
valid for certain 5800
Series transmitters only
(e.g., 5801, 5802, 5802CP
& 5803).
03 = supervised RF transmitter (RF type)
04 = unsupervised RF transmitter (UR type)
05 = RF button-type transmitter (BR type)
06 = serial number polling loop device (SL type)
07 = DIP switch-type polling loop device
08 = right loop of DIP switch type device
Right loops refer to the use of the right loop on a 4190WH Zone Expander Module and/or 4278 PIR, which
allow hardwired devices to be monitored by the polling loop.
If you are programming hardwired or DIP switch polling loop devices, the summary display appears after
completing this entry.
Press [✱] to continue.
For Serial Number entry and Loop Number entry, do one of the following:
a. Transmit two open and close (or close and open) sequences. For a button-type transmitter, press and
release the button, wait approximately 4 seconds, then press and release the button a second time.
10 INPUT S/N:
AXXX-XXXX
L
1
OR
b. Manually enter the 7-digit serial number printed on a label on the transmitter, using the Alpha keypad.
Then press the [✱] key, the cursor moves to the “L” position. You can edit the loop number, if necessary.
When the loop number is acceptable, press [✱].
OR
c. Press key [C] to copy the last serial number enrolled (used when programming a transmitter with several
input loops).
Press [✱] to accept.
The cursor will then move to the Loop column (L) with the previously entered/transmitted serial number
displayed.
Enter the loop number (refer to 5800 Series Transmitters Loop Designations below).
10 INPUT S/N:
A022-4064
L
1
To Delete an Existing Serial Number, enter 0 in the loop number field. The serial number will change to
“0”s.
If 0 was entered in error, simply re-enter the loop number or press [#], and the serial number will return to the
display.
Press [✱] to accept.
The system will then check for a duplicate serial/loop number combination.
If a duplicate serial/loop number combination is found, the keypad will emit a single long beep, and display
the serial number along with a “?” for the loop number, allowing you to re-enter the correct loop number.
If the serial/loop number combination is not a duplicate in the system, a display appears showing the serial
number and loop number entry.
10 INPUT S/N:
A022-4064
L
1
Press [✱] to continue.
– 12 –
Download from Www.Somanuals.com. All Manuals Search And Download.
5800 Series Transmitters Loop Designations
LOOP 3
LOOP 2
(REED)
LOOP 1
(PRIMARY)
LOOP 2
LOOP 1
LOOP 2
(AUX. CENTER)
LOOP 1
(TERMINALS)
LOOP
1
LOOP 3
LOOP 4
(AUX. RIGHT)
ALTERNATE
POSITION
FOR LOOP 2
YOU MUST
ENROLL THIS
BUTTON
5817
ENROLL AS "RF"
5816MN
ENROLL AS "RF"
5801
5802MN
ENROLL AS "UR" OR "RF"
ENROLL AS "UR" OR "RF"
LOOP 3
LOOP 2
(REED)
YOU MUST
ENROLL THIS
BUTTON
LOOP
LOOP 1
(TERMINALS)
LOOP 2
LOOP 1
2
LOOP 4
(REED)
LOOP 2
LOOP 1
LOOP 3
(TERMINALS)
(INTERNAL
SHOCK
YOU MUST
ENROLL THIS
BUTTON
SENSOR)
LOOP 3
(TERMINALS)
LOOP 4
5819S (WHS & BRS)
ENROLL AS "RF"
5819
ENROLL AS "RF"
LOOP 1
LOOP 3
5804
ENROLL
AS "BR"
•
•
•
•
•
• •
•
•
•
SET
HOUSE
CODE
• •
•
5827
SET HOUSE CODE
• •
5827BD
SET HOUSE CODE
•
•
•
•
5804BD
ENROLL AS "BR"
LOOP
1
5809
ENROLL AS "RF"
LOOP 2
(REED)
LOOP 1
(MOTION)
LOOP
1
(Green)
(Red)
(Yellow)
LOOP 1
(TERMINALS)
5808
ENROLL AS "RF"
5816
ENROLL AS "RF"
5850 (GBD)
ENROLL AS "RF"
5890
ENROLL AS "RF"
5800_trans_loop-V0
Note: For information on any transmitter not shown above, refer to the instructions accompanying that transmitter for
details regarding loop numbers, etc.
The 5802MN, 5802MN2, 5804, 5804BD, 5814, 5816TEMP, 5819, 5819WHS & BRS, 5827BD,
and 5850 transmitters are not intended for use in UL installations.
U
L
PROMPT
EXPLANATION
Confirmation Option: This prompt only appears if you answered “Yes” at the first prompt. The system
enters a confirmation mode so that the operation of the actual programmed input can be confirmed. Activate
the loop input or button that corresponds to this zone. At any time during this step, you may press the [✱] key
on the keypad to save the serial and loop number combination without confirming.
XMIT TO CONFIRM
PRESS ✱TO SKIP
If the serial number transmitted does not match the serial number entered, a display similar to the one
at the left appears. If the loop number does not match, it is also displayed.
Entd
Rcvd
A022-4063
A022-4064
1
If so, activate the loop input or button on the transmitter once again. If a match is not obtained (i.e., summary
display does not appear), press the [#] key twice and then enter or transmit the correct serial number.
If the serial number transmitted does match the serial number entered, the system beeps 3 times and a
summary display appears, showing that zone’s programming. Note that an “s” indicates that a transmitter’s
serial number has been enrolled.
10 ZT P RC In
03 3C RF 1s
L
1
Press [✱] to accept the zone information.
– 13 –
Download from Www.Somanuals.com. All Manuals Search And Download.
PROMPT
EXPLANATION
The system now returns to the “ENTER ZONE NO.” prompt for the next zone.
When all zones have been programmed, enter 00 to quit.
ENTER ZONE NO.
00 = QUIT
11
After you have enrolled each wireless device, remove ONE of the serial number labels from that device and affix it in
the appropriate column on the worksheets provided later in this Programming Guide; then enter the other information
(zone number, zone type, etc.) relevant to that device.
When you have finished programming all zones, test each using the system’s Test Mode. Do not use the
Transmitter ID Sniffer Mode. The system checks only for transmission of one zone on a particular
transmitter, NOT the zones assigned to each additional loop, and also does not verify polling loop type
zones.
Expert Mode Zone Programming
Expert mode allows you to program zones using the minimum number of screens and keystrokes.
Enter the Programming mode with [Installer Code] + [8] [0] [0]
Before programming your zones, do the following:
1. Program field 2✱00: Number of Partitions.
2. Enable your RF Receiver in Device Programming menu mode.
To program your zones, press ✱93 to display the "ZONE PROG?" prompt. Enter 0 (NO) to each prompt until the “EXPERT
MODE?” prompt appears.
PROMPT
EXPLANATION
Press 1 to enter Expert mode.
EXPERT MODE?
1 = YES 0 = NO
0
This prompt appears once upon entering Expert Mode.
If you select “Yes,” Confirmation prompts will be displayed after the device’s Serial and Loop numbers have
been entered later.
SET TO CONFIRM?
0 = NO 1 = YES
0
A summary display appears, showing zone 1’s current programming or default values.
Zn ZT P RC In
L
01 03
1
10 HW
-
Enter the desired 2-digit zone number and press [✱].
Note: If you want to exit the Expert mode, enter 00 + [✱].
If an “s” appears after the loop number, it indicates that the transmitter’s serial number has been enrolled.
Use the [D] key to enter and duplicate wireless keys (see “Entering Wireless Keys” later)
Zn ZT
10 03
P
RC In
L
1
10 RF 1s
Enter all zone information except for Loop number, or press [C] to copy the zone information on this screen
from the last saved zone (including Loop).
Zn ZT
10 03
P
RC In
L
-
1
10 RF
ZT = Zone Type
P
= Partition
RC = Report Code
In = Input Device Type
L
= Loop number to which the sensor is connected.
NOTE: Pressing the [C] copies the zone information from the last saved zone, which includes the
input type. Verify this information is correct for this zone.
On this screen:
•
•
Use the [A] key to move to the right.
Use the [B] key to move to left and to back up to “ZT” field.
Press [✱] to accept the existing or newly entered zone information.
– 14 –
Download from Www.Somanuals.com. All Manuals Search And Download.
PROMPT
EXPLANATION
If you entered RF, BR, UR or SL for the Input Type, this screen displays. Otherwise the summary screen for
the next zone displays.
Enter the 7-digit serial number, using one of the following methods:
a. Transmit two open and close (or close and open) sequences. For a button-type transmitter, press and
release the button, wait approximately 4 seconds, then press and release the button a second time.
OR
10 INPUT S/N:
A XXX-XXXX
L
-
b. Manually enter the 7-digit serial number printed on a label on the transmitter, using the alpha keypad.
Then press the [✱] key, the cursor will move to the “L” position. You can edit the loop number, if
necessary. When the loop number is acceptable, press [✱].
OR
c. Press key [C] to copy the last serial number enrolled (used when programming a transmitter with several
input loops).
Remember, you can use the [A] key to move to the right or the [B] key to move to the left.
You can also use the [#] key to back up without saving.
Press [✱] to accept the serial number and advance to the “L” position (if method “a” or “c” was used), then
enter the loop number.
If necessary, press the [#] key to back up without saving, and re-enter or edit the serial number before
pressing [✱] to save
10 INPUT S/N:
A022-4064
L
1
The system checks for a duplicate. If a duplicate serial/loop number combination is found, the keypad will
emit a single long beep, and display the serial number along with a “?” for the loop number, allowing you to
re-enter the correct loop number.
To Delete an Existing Serial Number, enter 0 in the loop number field. The serial number will change to
“0”s.
If 0 was entered in error, simply re-enter the loop number or press [#], and the serial number will return to the
display.
10 INPUT S/N:
A000-0000
L
1
The prompt to confirm appears. This prompt only appears if you answered “Yes” at the “SET TO
CONFIRM?” prompt.
XMIT TO CONFIRM
PRESS ✱TO SKIP
The system enters a confirmation mode so that the operation of the actual programmed input can be
confirmed. Activate the loop input or button that corresponds to this zone. At any time during this step, you
may press the [✱] key on the keypad to save the serial and loop number combination without confirming.
If the serial number transmitted does not match the serial number entered, a display similar to the one
at the left appears. If the loop number does not match, it also is displayed.
Entd
Rcvd
A022-4063
A022-4064
1
L
If so, activate the loop input or button on the transmitter once again. If a match is not obtained (i.e., summary
display for the next zone does not appear), press the [#] key twice and then enter or transmit the correct
serial number.
Activate the button on the wireless key again after re-entering the serial number.
If the serial number transmitted matches the serial number entered, the system beeps 3 times and
advances to the summary display for the next zone's programming.
Zn
11
ZT
00
P
1
RC In
10
00 1
After all the zones have been programmed, enter 00 for the zone number to quit.
After you have enrolled each wireless device, remove ONE of the serial number labels from that device and affix it in
the appropriate column on the worksheets provided later in this Programming Guide; then enter the other information
(zone number, zone type, etc.) relevant to that device.
Entering Wireless Keys
If you pressed the D key previously to enter defaults for 5804 and/or 5804BD wireless keys, the following screens appear:
PROMPT
EXPLANATION
Enter template number (1–6).
FROM TEMPLATE
1–3 = 5804 templates; 4–6 = 5804BD templates. See the defaults provided for each template in the chart
that follows these procedures.
1–6
1
Select from templates. Press [✱] to display template (template 1 shown selected).
Note: If necessary, press [#] to back up and re-enter template number.
Press [#] if you want to return to zone attributes screen.
When you press [✱], the selected template is displayed.
Top line of display represents loop numbers; bottom line represents zone type.
Press [✱] to accept template.
L
01 02 03 04
ZT 23 22 21 23
1
– 15 –
Download from Www.Somanuals.com. All Manuals Search And Download.
PROMPT
EXPLANATION
Enter partition number for wireless key.
Press [✱] to continue.
PARTITION
1
The system searches for the highest available, consecutive 4-zone group (the four zones required for the
5804 and 5804BD), and displays the lowest zone number of the group.
If you want to start at a different zone number, enter the zone desired and press [✱].
If that zone number is displayed, the system has the required number of consecutive zones available,
beginning with the zone you entered. If not, the system again displays a suggested zone that can be used.
If the required number of consecutive zones is not available at all, the system will display “00.”
Press [✱] to accept.
ENTER ZONE NO
00 = QUIT
24
L
Example of zone number
suggested by the system.
This indicates that zones
24, 25, 26, and 27 are
available.
To enter the serial number:
Press and release a button on the wireless key.
OR
24 INPUT S/N
AXXX-XXXX
L
1
Manually enter the 7-digit serial number printed on the device’s label.
Press [✱] to accept serial number. The system checks for a duplicate.
If a duplicate exists, a long error beep will sound and the serial number reverts back to all “X”s allowing
you to re-enter the serial number.
Use the [A] key to move forward within the screen, and the [B] key to back up.
If you entered YES previously at the SET TO CONFIRM prompt (see first prompt following entry into the
Expert Programming Mode), the display on the left appears.
To confirm, activate the button on the wireless key that corresponds to this zone.
XMIT TO CONFIRM
PRESS ✱TO SKIP
If the serial number transmitted does not match the serial number entered, a display similar to the one
at the left appears.
If so, activate the loop input or button on the transmitter once again. If a match is not obtained (i.e., summary
display does not appear), press the [#] key and then enter the correct serial number.
Entd
Rcvd
A022-4063
A022-4064
Activate the button on the wireless key again after re-entering the serial number.
If the serial number transmitted matches the serial number entered, the system will beep 3 times and
revert to the "Start Zone No." prompt and will show the lowest numbered zone of the next available 4-zone
group (4 consecutive zones) that is available for programming.
ENTER ZONE NO
00 = QUIT
28
After all the wireless keys have been entered, enter 00 for the zone number to quit.
After you have enrolled each wireless device, remove ONE of the serial number labels from that device and affix it in
the appropriate column on the worksheets provided later in this Programming Guide; then enter the other information
(zone number, zone type, etc.) relevant to that device.
Wireless Key Default Templates
5804
5804BD
Template 1
Loop Function
Zone Type Template 4
Loop
Function
Zone Type
1
2
3
4
No Response
23
1
No Response
No Response
Arm AWAY
Disarming
23
Disarming
22
2
23
Arm AWAY
No Response
21
3
21
23
4
22
Template 2
Template 3
Loop Function
Zone Type Template 5
Loop
Function
Zone Type
1
2
3
4
No Response
23
1
No Response
Arm STAY
Arm AWAY
Disarming
23
Disarming
Arm AWAY
Arm STAY
22
2
20
21
3
21
20
4
22
Loop Function
Zone Type Template 6
Loop
Function
Zone Type
1
2
3
4
24-Hour Panic
07
22
21
20
1
2
3
4
24-Hour Panic
Arm STAY
Arm AWAY
Disarming
07
20
21
22
Disarming
Arm AWAY
Arm STAY
– 16 –
Download from Www.Somanuals.com. All Manuals Search And Download.
Alpha Descriptors Programming
You can program a user-friendly English language description/location for all protection zones, relays, keypad panics, polling
loop short, and RF receiver supervision troubles.
Each description can be composed of a combination of words (up to 3) that are selected from a vocabulary of 244 words
stored in memory, and any word can have an "s" or " ’s " added to it. In addition, up to 20 installer-defined words can be added
to those already in memory. Thus, when an alarm or trouble occurs in a zone, an appropriate description for the location of
that zone will be displayed at the keypad.
NOTE: Due to the use of 2-digit zone numbers, the first word of the descriptor is limited to 7 characters if you want it to fit on
the top line of the display.
A custom installer’s message can be programmed for each partition, which is displayed when the system is "Ready" (e.g., THE
PETERSONS’).
1. To program alpha descriptors, enter Programming mode, then press [#]93 to display "ZONE PROG?"
2. Press 0 (NO) twice to display "ALPHA PROG?".
3. Press 1 to enter Alpha Programming.
There are 5 submenu selections that will be displayed one at a time.
Press 1 to select the mode desired. Press 0 to display the next mode available. The alpha menu selections are:
ZONE DESCRIP?
DEFAULT SCREEN?
CUSTOM WORD?
PART DESCRIP?
EXIT EDIT MODE?
For entering zone descriptors.
For creating custom message; displayed when system is ready.
For creating custom words for use in descriptors.
For creating 4-character partition names.
Press 1 to exit back to #93 Menu Mode.
4. Refer to the sections that follow for procedures for adding alpha descriptors.
Zone Descriptors
1. Select ZONE DESCRIPTOR mode.
The keypad keys perform the following functions:
[3] Scrolls both alphabet and actual words in ascending alphabetical order.
[1] Scrolls both alphabet and actual words in descending alphabetical order.
[2] Adds or removes an "s" or " 's " to a vocabulary word.
[6] Switches between alphabet and actual word list; used to accept entries.
[8] Saves the zone description in the system's memory.
[#] [#] plus zone number displays the description for that zone.
2. Enter the zone number to which you want to assign a descriptor.
For example, key [✱] 01 to begin entering the description for Zone 1, (key [✱] 02 for Zone 2, [✱] 03 for Zone 3, etc.). The
following is displayed: ✱ ZN 01 A.
Note that the first letter of the alphabet appears after the zone number, and that the zone number is automatically
included with the description.
3. Enter the descriptor for that zone.
Use one of two methods as follows:
(Assume, for example, that the desired description for Zone 1 is BACK DOOR.)
a) Press [#] followed by the 3-digit number of the first word from the fixed dictionary shown later in this section (e.g.,
[0][1][3] for BACK).
Press 6 in order to accept the word and proceed, or press 8 to store the complete descriptor and exit;
or
b) Select the first letter of the desired description (note that "A" is already displayed). Use the 3 key to advance through
the alphabet and the 1 key to go backward.
Press 3 key repeatedly until "B" appears (press 1 to go backwards if you happen to pass it), then press 6 to display
the first available word beginning with “B”.
Press 3 repeatedly to advance through the available words until the word “BACK” is displayed.
To add an "s" or " 's" if you need to, press 2. The first depression adds an "s," the second depression adds
an " 's, " the third depression displays no character (erases the " 's"), the fourth depression adds an "s," etc.
– 17 –
Download from Www.Somanuals.com. All Manuals Search And Download.
4. Accept the word.
To accept the word, press 6, which switches back to the alphabet list for the next word, or press 8 to store the complete
descriptor and then exit.
5. Select the next word.
For selection of the next word (DOOR), repeat step 3a (word #057) or 3b, but selecting the word "DOOR.”
To accept the word, press 6, which again switches back to alphabet list.
6. Store the descriptor.
When all desired words have been entered, press 8 to store the description in memory.
To review the zone descriptors, key [#] plus zone number (e.g., #01).
To edit zone descriptors, key [✱] plus zone number (e.g., ✱01)
7. Exit Zone Description Mode: enter 00.
Default Screen (Custom Message Display)
Normally, when the system is in the disarmed state, the following display is present on the keypad.
****DISARMED****
READY TO ARM
Part or all of the above message can be modified to create a custom installer message for each partition. For example,
“****DISARMED****” on the first line or “READY TO ARM” on the second line could be replaced by the installation company
name or phone number for service.
Note: There are only 16 character spaces on each of the two lines.
To create a custom display message, proceed as follows:
1. Select Default Screen mode.
The keypad asks for the partition number for this message.
Enter the partition number. Press [✱] to accept entry.
The following display appears:
****DISARMED****
READY TO ARM
A cursor is present at the extreme left of the first line (over the first "star"). Press 6 to move the cursor to the right and 4 to
move the cursor to the left. Press 7 to insert spaces or erase existing characters.
2. Create the message.
For example, to replace “READY TO ARM” with the message “SERVICE 424-0177,” proceed as follows:
Press 6 to move the cursor to the right, and continue until the cursor is positioned over the first location on the second
line.
Press 3 to advance through the alphabet to the first desired character (in this case, "S"). Press 1 to go backward, when
necessary. When the desired character is reached, press 6.
The cursor then moves to the next position, ready for entry of the next character (in this example, "E"). When the cursor
reaches a position over an existing character, press 3 or 1 to advance or back up from that character in the alphabet.
Proceed in this manner until all characters in the message have been entered.
3. Save the message.
Store the new display message in memory by pressing 8.
4. The system asks for a new partition number.
Enter 0 to quit or 1-2 for a new partition number.
Custom Words
Up to 20 installer-defined words can be added to the built-in vocabulary. Each of the 20 "words" can actually consist of several
words, but bear in mind that a maximum of 10 characters can be used for each word string.
1. Select CUSTOM WORD Mode.
The keys perform the following functions:
[3] Advances through alphabet in ascending order.
[1] Advances through alphabet in descending order.
[6] Selects desired letter; moves the cursor 1 space to the right.
[4] Moves the cursor one space to the left.
[7] Inserts a space at the cursor location, erasing any character at that location.
[8] Saves the new word in the system's memory.
[✱] Returns to Description Entry Mode.
– 18 –
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Enter the custom word number (01-20) you want to create.
For example, if you are creating the first word (or word string), enter 01; when creating the second word, enter 02, and so
on. A cursor now appears at the beginning of the second line.
3. Type the word using one of two methods as follows:
a) Press [#], followed by the 2-digit entry for the first letter you would like to display (e.g., 65 for "A").
When the desired character appears, press 6 to select it. The cursor will then move to the right, in position for the
next character. Press [#] plus the 2-digit entry for the next letter of the word.
or
b) Press 3 to advance through the list of symbols, numbers, and letters.
Press 1 to move back through the list.
When you have reached the desired character, press 6 to select it. The cursor then moves to the right, in position for
the next character.
4. Repeat step 3 to create the desired custom word (or words).
Press 4 to move the cursor to the left if necessary.
Press 7 to enter a blank (or to erase an existing character).
Each word or word string cannot exceed 10 characters.
5. Save the word by pressing 8.
This returns you to the “CUSTOM WORD?” display. The custom word (or string of words) is automatically added to the
built-in vocabulary at the end of the group of words beginning with the same letter.
Custom words are retrieved as word numbers 250 to 269 for words 1 to 20, respectively, when using method 3a to enter
alpha descriptors.
When using method 3b to enter alpha descriptors, each word appears at the end of the group of words that begin with the
same letter as it does.
6. Repeat steps 2 through 6 to create up to a maximum of 20 custom words (or word strings).
7. Exit Custom Word Mode by entering 00 at the “CUSTOM WORD” prompt.
Partition Descriptors
1. Select "Part DESCRIPT." Mode.
The system asks for the partition number desired. Enter the number as a single-key entry 1-2.
2. Follow the same procedure as for custom words.
Note: The partition descriptors are limited to 4 characters (e.g., WHSE for warehouse).
– 19 –
Download from Www.Somanuals.com. All Manuals Search And Download.
Alpha Descriptor Vocabulary
(For entering alpha descriptors. To select a word, press [#] followed by the word’s 3-digit number.)
NOTE: This vocabulary is not to be used for relay voice descriptors. See the Relay Voice Descriptors section when
programming relay voice descriptors.
000 (Word Space)
001 AIR
002 ALARM
003 ALCOVE
004 ALLEY
005 AMBUSH
006 AREA
007 APARTMENT
008 ART
•
•
052 DETECTOR
053 DINING
054 DISCRIMINATOR
055 DISPLAY
056 DOCK
057 DOOR
058 DORMER
059 DOWN
060 DOWNSTAIRS
061 DRAWER
062 DRIVEWAY
063 DRUG
102 INTERIOR
103 INTRUSION
151 POLICE
152 POOL
153 POWER
202 TRANSMITTER
203 TRAP
•
•
•
•
104 JEWELRY
105 KITCHEN
204 ULTRA
205 UP
•
154 QUAD
•
•
•
•
•
206 UPPER
207 UPSTAIRS
208 UTILITY
209 VALVE
210 VAULT
211 VIBRATION
212 VOLTAGE
•
•
•
•
106 LAUNDRY
107 LEFT
108 LEVEL
109 LIBRARY
110 LIGHT
111 LINE
112 LIQUOR
113 LIVING
114 LOADING
115 LOCK
155 RADIO
156 REAR
157 RECREATION
158 REFRIG
159 REFRIGERATION
160 RF
161 RIGHT
162 ROOM
163 ROOF
•
•
•
009 ATTIC
010 AUDIO
011 AUXILIARY
•
•
•
•
•
064 DUCT
•
•
•
•
•
012 BABY
013 BACK
014 BAR
015 BARN
016 BASEMENT
017 BATHROOM
018 BED
019 BEDROOM
020 BELL
021 BLOWER
022 BOILER
023 BOTTOM
024 BOX
025 BREAK
026 BUILDING
027 BURNER
•
•
213 WALL
214 WAREHOUSE
215 WASH
216 WEST
217 WINDOW
218 WINE
219 WING
220 WIRELESS
221 WORK
065 EAST
066 ELECTRIC
067 EMERGENCY
068 ENTRY
069 EQUIPMENT
070 EXECUTIVE
071 EXIT
116 LOOP
117 LOW
118 LOWER
164 SAFE
•
•
•
•
•
•
165 SCREEN
166 SENSOR
167 SERVICE
168 SHED
169 SHOCK
170 SHOP
171 SHORT
172 SHOW
173 SIDE
174 SKYLIGHT
175 SLIDING
176 SMOKE
177 SONIC
•
•
•
•
•
•
•
119 MACHINE
120 MAGNETIC
121 MAIDS
122 MAIN
123 MASTER
072 EXTERIOR
•
•
•
•
•
•
073 FACTORY
074 FAILURE
075 FAMILY
076 FATHERS
077 FENCE
078 FILE
079 FIRE
080 FLOOR
081 FLOW
222 XMITTER
223 YARD
•
•
124 MAT
•
•
125 MEDICAL
126 MEDICINE
127 MICROWAVE
128 MONEY
129 MONITOR
130 MOTHERS
131 MOTION
132 MOTOR
133 MUD
•
•
224 ZONE (No.)
225 ZONE
•
•
•
028 CABINET
029 CALL
030 CAMERA
031 CAR
032 CASE
033 CASH
•
•
178 SONS
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
226
227
0
1
•
•
179 SOUTH
180 SPRINKLER
181 STAMP
182 STATION
183 STEREO
184 STORE
185 STORAGE
186 STORY
187 STRESS
188 STRIKE
189 SUMP
082 FOIL
228 1ST
229
230 2ND
231
232 3RD
233
234 4TH
235
236 5TH
237
238 6TH
239
240 7TH
241
242 8TH
243
•
•
083 FOYER
084 FREEZER
085 FRONT
086 FUR
2
•
•
3
034 CCTV
•
134 NORTH
135 NURSERY
035 CEILING
036 CELLAR
037 CENTRAL
038 CIRCUIT
039 CLIP
040 CLOSED
041 COIN
087 FURNACE
4
•
•
088 GALLERY
089 GARAGE
090 GAS
•
•
•
136 OFFICE
137 OIL
138 OPEN
139 OPENING
140 OUTSIDE
141 OVERFLOW
142 OVERHEAD
5
•
•
6
091 GATE
190 SUPERVISED
191 SUPERVISION
192 SWIMMING
193 SWITCH
•
092 GLASS
093 GUEST
094 GUN
7
042 COLD
043 COATROOM
044 COLLECTION
045 COMBUSTION
046 COMPUTER
047 CONTACT
8
•
•
095 HALL
096 HEAT
097 HIGH
098 HOLDUP
099 HOUSE
143 PAINTING
144 PANIC
145 PASSIVE
146 PATIO
147 PERIMETER
148 PHONE
149 PHOTO
150 POINT
194 TAMPER
195 TAPE
196 TELCO
197 TELEPHONE
198 TELLER
199 TEMPERATURE
200 THERMOSTAT
201 TOOL
9
•
•
•
•
244 9TH
250 Custom Word 1
to
•
•
048 DAUGHTERS
049 DELAYED
050 DEN
269 Custom Word 20
•
•
100 INFRARED
101 INSIDE
051 DESK
•
CHARACTER (ASCII) CHART
(For Adding Custom Words)
32
33
34
35
36
37
38
39
40
41
(space)
!
"
#
$
%
&
’
(
)
42
43
44
45
46
47
48
49
50
51
*
+
,
-
.
52
53
54
55
56
57
58
59
60
61
4
5
6
7
8
9
:
;
<
=
62
63
64
65
66
67
68
69
70
71
>
?
72
73
74
75
76
77
78
79
80
81
H
I
J
K
L
M
N
O
P
Q
82
83
84
85
86
87
88
89
90
R
S
T
U
V
W
X
Y
Z
@
A
B
C
D
E
F
/
0
1
2
3
G
Notes: This factory-provided vocabulary of words is subject to change.
Bulleted words in bold face type are those that are also available for use by the 4285/4286 VIP Module. If you are
using a VIP Module, and words other than these are selected for alpha descriptors, the Voice Module will not provide
annunciation of those words.
– 20 –
Download from Www.Somanuals.com. All Manuals Search And Download.
Device Programming
This menu is used to program keypads, receivers, and relay modules, etc.
Device Address 00 is always set as an alpha keypad assigned to Partition 1 with no sounder suppression
options, and these settings cannot be changed.
From Data Field Programming mode, press [#]93 to display "ZONE PROG?" Press 0 repeatedly to display "DEVICE PROG?"
PROMPT
EXPLANATION
Press 1 to enter Device Programming.
DEVICE PROG?
1=YES 0=NO
0
The device address identifies the device to the control. Enter the 2-digit device address number to match
the device’s physical address setting (01-15).
NOTE: If using the 4285/4286 Voice Module, it must be used at Device Address 04.
DEVICE ADDRESS
01-15, 00=QUIT
01
Select the type of addressable device as follows:
DEVICE TYPE
0 = device not used
3 = RF receiver (5881)
0
1 = alpha keypad (6139/6160)
2 = fixed keypad (6137/6150)
Press [✱] to accept entry.
4 = output relay module (4204)
5 = voice (VIP) Module (4285/4286)
Alpha Keypad
PROMPT
EXPLANATION
If you selected device type 1 (alpha keypad) or 2 (fixed keypad), this prompt appears. Enter the addressable
device’s default partition number (1 to maximum number of partitions programmed for system in field 2*00).
This is the primary partition for the device.
01 CONSOLE PART.
1
Press [✱] to accept entry.
Keypads can be individually programmed to suppress arm/disarm beeps, entry/exit beeps and chime mode
beeps. This helps prevent unwanted sounds from disturbing users in other areas of the premises.
01 SOUND OPTION
00
Enter a number 00-03 for the keypad sounding suppression options desired for the keypad as follows:
00 = no suppression
01 = suppress arm/disarm & entry/exit beeps
02 = suppress chime mode beeps only
03 = suppress arm/disarm, entry/exit and chime mode beeps
Press [✱] to accept entry.
RF Expander
PROMPT
EXPLANATION
If you selected device type 3 (RF receiver), this prompt appears. Enter the 2-digit House ID (00-31). This is
required if you are using a wireless keypad (5827/5827BD).
01 RF EXPANDER
HOUSE ID
00
Press [✱] to accept entry.
VIP Module
PROMPT
EXPLANATION
If you selected device type 5 (VIP Module), this prompt appears. Enter the partition number 1-2 in which the
module is located.
Press [✱] to accept entry.
01 MODULE PART.
1
Press 00 + [✱] to exit Menu mode.
Press ✱99 to exit Program mode.
– 21 –
Download from Www.Somanuals.com. All Manuals Search And Download.
Relay Programming
The system supports up to 8 relay outputs. Relays can be used to perform many different functions and actions. Each relay
must be programmed to begin one of three types of ACTIONS at a designated START event, and end that ACTION at a
designated STOP event. The options and prompts used to start and stop these devices are described below
The letter(s) in parentheses after each function described below, such as (A) after ACTION, are those that appear in the
various summary displays of programmed data during programming.
ACTION (A)
The "ACTION" of the device is how the device will respond when it is activated by the "START"
programming. You may want the device to activate momentarily, to pulse on and off continuously, or to
remain activated until some other event occurs to stop it. There are five different action choices:
•
•
•
•
ACTIVATE for 2 SECONDS and then reset.
ACTIVATE and REMAIN ACTIVATED until stopped by some other event.
PULSE ON and OFF until stopped by some other event.
NO RESPONSE when the device is not used.
START (STT)
The "START" programming determines when and under what conditions the device is activated. The
following START options are available:
1) EVENT (EV) is the condition (alarm, fault, trouble) that must occur to a zone or group of zones (zone
list) in order to activate the device. These conditions apply only when a zone list is used. The different
choices for "EVENT" are listed below and in “Programming Relays” later in this section.
•
•
•
•
ALARM
Action begins upon any alarm in an assigned zone in the zone list.
Action begins upon any opening of an assigned zone in the zone list.
Action begins upon any trouble condition in an assigned zone in the zone list.
Action is not dependent upon one of the above events.
FAULT
TROUBLE
NOT USED
ZONE LIST (ZL) is a group of zones to which the “EVENT” applies in order to activate a particular
device. Note that there are a total of 4 zone lists that can be programmed; when the selected EVENT
(alarm, fault or trouble) occurs in any zone in the selected “Start” ZONE LIST (1-4), activation of the
selected device will START.
3) ZONE TYPE/SYSTEM OPERATION (ZT). If all zones to be used to start the device have the same
response type, and there are no other zones of this type that are not to activate this device, then
“ZONE TYPE” may be used instead of a "ZONE LIST" and "EVENT” to activate the device.
If a system operation, such as “DISARMING” or “ANY FIRE ALARM,” is to activate the device, enter
the appropriate choice under the “ZONE TYPE” option.
The “ZONE TYPE/SYSTEM OPERATION” option functions independently of the “EVENT/ZONE
LIST” combination.
If a specific "ZONE TYPE" is chosen, any zone of that response type going into alarm, trouble, or fault
will cause the device to activate as selected in "ACTION.” If the same “ZONE TYPE” is also chosen for
the STOP programming, any zone of that type that restores will de-activate the device.
If a "SYSTEM OPERATION" is chosen, that operation will cause the device to activate as selected in
"ACTION.” The different choices for "ZONE TYPE" and "SYSTEM OPERATION" are listed in
“Programming Relays” later in this section, and on the Programming Form.
4) PARTITION NO. (P). The device's "Start" ZONE TYPE/SYSTEM OPERATION may be limited to an
occurrence on one partition (1-2), or any partition (0).
STOP (STP):
The "STOP" programming determines when and under what conditions the device is de-activated. The
following options are available:
1). RESTORE ZONE LIST (ZL). If a "ZONE LIST" is used as the “Stop” event, the device de-activates
when all the zones in that list restore from a previous fault, trouble, or alarm condition. This occurs
regardless of what is programmed to "START" the device; therefore, a "RESTORE ZONE LIST" is
normally only used when a "ZONE LIST" is used to start the device.
2). ZONE TYPE/SYSTEM OPERATION (ZT). Instead of using a "RESTORE ZONE LIST," you can select
a specific zone (response) type or system operation action to de-activate the device.
If you choose a specific "ZONE TYPE," any zone of that response type that restores from a previous
alarm, trouble, or fault condition will cause the device to de-activate.
If you choose a "SYSTEM OPERATION," that operation causes the device to de-activate. The
different choices for "ZONE TYPE" and "SYSTEM OPERATION" are listed in “Programming Relays”
later in this section, and in the Programming Form.
3) PARTITION NO. (P). The device's "Stop" Zone Type/System Operation may be limited to an
occurrence on one partition (1-2), or on any partition (0).
The “ZONE TYPE/SYSTEM OPERATION” option functions independently of the
“RESTORE/ZONE LIST” combination.
– 22 –
Download from Www.Somanuals.com. All Manuals Search And Download.
Relay Output Devices Programming
From Data Field Programming Mode, press #93 to display the "ZONE PROG?" prompt. Press [0] (NO) to each menu option
until the "RELAY PROG?" prompt appears. Press [1] (YES).
While in this mode, press [✱] to advance to next screen. Press [#] to back up to the previous screen.
PROMPT
EXPLANATION
Enter the relay (output device) identification number 01-08. This is a reference number only, used for
identification purposes. The actual module address and relay number on the module are programmed in the
last two prompts.
ENTER RELAY #
(00=QUIT)
01
Press [✱] to continue.
Press [✱] to continue.
02 A EV ZL P
STT 0 0 00
0
The keypad displays a summary STOP screen.
Press [✱] to continue.
02
A
0
ZL ZT
00 00
P
STOP
0
The Relay Action is the way in which the relay will respond when activated by the "start" event. Enter the
desired action for this relay as follows:
02 RELAY ACTION
NO RESPONSE
0
0
0=not used; 1=close for 2 secs.; 2=stay closed; 3=pulse on/off
A relay may be activated by an Event/Zone List combination, and/or by a Zone Type/System Operation. For
an Event/Zone List combination, enter the event code as follows:
02 START EVENT
NOT USED
0=not used; 1=alarm; 2=fault; 3=trouble
If you are not using a Zone List to activate the relay, enter 0.
Press [✱] to continue.
A zone list is a set of zones that can be used to initiate the start or stop relay action. If a zone list is being
used to start this relay action, enter the zone list number, 1-4. If a zone list is not being used, enter 0.
Press [✱] to continue.
02 START: ZN LIST
0
A Zone Type/System Operation can be used instead of or in addition to an Event/Zone List combination or
a specific zone to start the relay action. If a Zone Type/System Operation is being used, enter the 2-digit
code as listed in the table that follows.
02 START: ZN TYPE
NO RESPONSE
00
Press [✱] to continue.
Choices for Start/Stop Zone Types and System Operations:
00 = No Response (Not Used)
01 = Entry/Exit #1
02 = Entry/exit #2
03 = Perimeter
04 = Interior Follower
05 = Trouble Day/Alarm Night
06 = 24-Hr. Silent
23 = No Alarm Response
31 = End of Exit Time
32 = Start of Entry Time
33 = Any Burglary Alarm
34 = Code + [#] + 71 Key Entry
35 = Code + [#] + 72 Key Entry
36 = At Bell Timeout **
37 = 2 Times Bell Timeout **
38 = Chime
39 = Fire Alarm
40 = Bypassing
31 = End of Exit Time
41 = AC Power Fail
42 = System Battery Low
43 = Communication failure
44 = RF Low Battery
45 = Polling Loop Failure
51 = RF Receiver Failure
52 = Kissoff
54 = Fire Zone Reset
55 = Disarm + 1 Minute
56 = XX Minutes (enter XX in field 1*74) *
57 = YY Seconds (enter YY in field 1*75) *
58 = Duress
60 = Audio Alarm Verification (must be
selected for both START and STOP
operation)
07 = 24-Hr. Audible
08 = 24-Hr. Auxiliary
09 = Fire Alarm or Trouble
10 = Interior w/Delay
20 = Arming-STAY
21 = Arming-AWAY
22 = Disarming (Code + Off)
Stop condition only
*
** Or at disarming, whichever occurs earlier
If you are using options 56 and/or 57 (usually as the STOP Zone Type), you must program data fields 1*74
and 1*75 for the respective relay timeouts for minutes and seconds.
– 23 –
Download from Www.Somanuals.com. All Manuals Search And Download.
PROMPT
EXPLANATION
If the starting event will be limited to occurring on a specific partition, enter the partition number (1-2) in
which the start event will occur. Enter 0 for any partition.
Press [✱] to continue.
02 START: PARTN
ANY PARTITION
0
Do not use a zone programmed with an RF Button (Input Type BR) to STOP a relay. The system will not de-
activate the relay.
PROMPT
EXPLANATION
If a zone list is being used to stop this relay action, enter the zone list number, 1-4. The restore of a zone
on the zone list stops the relay. If a zone list is not being used, enter 0.
Press [✱] to continue.
02 STOP: ZN LIST
00
If a Zone Type/System Operation is being used to stop the relay action, enter the 2-digit code listed in the
Choices for Start/Stop System Operation chart.
Press [✱] to continue.
02 STOP: ZN TYPE
NO RESPONSE
00
0
This is the partition to which the stop condition will be limited. Enter 0 for any partition. Enter 1-2 for specific
partition number.
Press [✱] to continue.
02 STOP: PARTN
ANY PARTITION
The system may have some devices that are not intended to be under end user control, such as relays
activating fire doors or machinery. Enter 1 if the end user will be restricted from accessing this relay.
Press [✱] to continue.
02 RESTRICTION
1=YES 0=NO
0
Enter 1 for (ECP) relay modules (4204). Enter 2 for X-10 devices.
Press [✱] to continue.
02 RELAY TYPE
V-PLEX
0
If you selected 1 (4204), enter the actual module’s address (01-15) as set by its DIP switches. Up to 2
modules can be installed in a system.
Press [✱] to continue.
02 ECP ADDRESS
00
For 4204 Relay Outputs, enter the specific relay number on that module (1-4).
Press [✱] to continue.
02 MODULE RELAY#
0
The keypad will display the Start and Stop summary screens again.
Press [✱] to continue.
If you selected 2 for X-10 devices, enter the numerical equivalent of the House Code of the device, as
follows:
02 HOUSE CODE
A
00
A=00
B=01
C=02
D=03
E=04
F=05
G=06
H=07
I=08
J=09
K=10
L=11
M=12
N=13
O=14
P=15
Enter the numerical unit code of the X-10 device (00-15).
Press [✱] to continue.
02 UNIT CODE
00
The keypad displays the Start and Stop summary screens again.
Press [✱] to continue.
When all relays have been programmed, enter 00 at the "ENTER RELAY NO." prompt.
If you are defining a zone list, continue to the next section. If not, enter 00 + [✱] at the next two prompts. You will then be
asked "Quit Menu Mode?" Enter 1 for "Yes," 0 for "No." Then enter [✱]99 to exit programming completely.
Zone List Programming
After all relays have been programmed, upon entering 00 at the "ENTER RELAY NO." prompt, you are asked to enter a zone
list. If a zone list number was used to start or stop a relay, you must define the zones belonging to that list as follows:
PROMPT
EXPLANATION
Enter the zone list number 01-04. Enter 00 to quit.
ENTER Zn LIST ?
00=QUIT
00
– 24 –
Download from Www.Somanuals.com. All Manuals Search And Download.
PROMPT
EXPLANATION
Using 2-digit entries, enter each zone to be included in this zone list. Press [✱] after you enter each zone
number.
01 ADD ZONE #
00=QUIT
00
When you have entered all zones, enter 00.
Press [✱] to continue.
Enter 0 to save this zone list. Enter 1 to delete it.
01 Del Zn LIST ?
1=YES 0=NO
0
0
Enter 1 to delete one or more zones in that zone list. Enter 0 if no changes are necessary. If you enter 1,
the following screen appears; otherwise, the "Enter Zone LIST" prompt reappears.
01 DEL ZONES ?
1=YES 0=NO
Enter each zone number to be deleted from the zone list, pressing [✱] after each number.
01 Zn to DELETE ?
00=QUIT
00
00
This display appears if you pressed 00 at the “Enter Zone LIST” prompt. Enter the zone list number that you
wish to view.
Press [✱] to continue.
VIEW Zn LIST ?
00=QUIT
Press [✱] to scroll through all zones in that list. Enter 00 +[✱] to quit.
Press 1 to exit Menu Mode.
01 ASSIGNED ZONE
00=QUIT
00
Press [✱]99 to exit Program Mode.
Relay Voice Descriptors
If you are using the 4285/4286 VIP Module, you can program voice descriptors for each relay output. The descriptors are
announced by the voice module when you access the relays via the # 70 Relay Access Mode over the telephone.
Each voice descriptor can consist of up to 3 words selected from the Relay Voice Descriptors and Custom Word Substitutes
Vocabulary list (later in this section).
The index numbers from this vocabulary list are to be used for relay voice descriptors only. For normal
system voice annunciation (e.g., alarms, troubles, status), use the highlighted words in the alpha vocabulary
list in the Alpha Programming part of this guide.
To enter relay voice descriptors, do the following:
1. From Data Field Programming mode, press #93 to display the "ZONE PROG?" prompt.
2. Press 0 (NO) to each menu option until the "RLY VOICE DESCR?" prompt is displayed. Follow the instructions below.
While in this mode, press [✱] to advance to next screen. Press [#] to back up to previous screen.
PROMPT
EXPLANATION
Press 1 to program voice descriptors for relays.
RLY VOICE DESCR?
1=YES 0=NO
0
Enter the 2-digit relay number (01-08) for the relay desired, or enter 00 to quit Relay Voice Descriptor
Programming Mode.
Press [✱]
ENTER RELAY NO.
00=QUIT
01
From the Relay Voice Descriptors and Custom Word Substitutes Vocabulary list, enter the 3-digit index
number for the first word of the relay descriptor phrase.
Press [✱] to accept entry.
01 ENTER DESC d1
01 ENTER DESC d2
01 ENTER DESC d3
From the Relay Voice Descriptors and Custom Word Substitutes Vocabulary list, enter the 3-digit index
number for the second word of the relay descriptor phrase. If second word is not desired, press 000.
Press [✱] to accept entry.
From the Relay Voice Descriptors and Custom Word Substitutes Vocabulary list, enter the 3-digit index
number for the third word of the relay descriptor phrase. If third word is not desired, press 000.
Press [✱] to accept entry. The “ENTER RELAY NO.” prompt appears. Enter the next relay number to be
programmed. When you have programmed all relay devices, enter 00 to quit.
Enter [✱]99 to exit Program Mode.
– 25 –
Download from Www.Somanuals.com. All Manuals Search And Download.
Relay Voice Descriptors and Custom Word Substitutes Vocabulary
Word
Index Word
Index
Daughter’s................208
Den ..........................052
Detector....................128
Device......................060
Dim...........................163
Dining.......................031
Door .........................016
Down........................008
Downstairs ...............184
Driveway ..................130
Duct..........................131
Word
Index
Word
Index
Word
Index
Air ............................ 116
Alarm ....................... 255
And .......................... 067
Apartment ................ 117
Appliances ............... 161
Area ......................... 118
Attic.......................... 119
Front.........................087
No.............................165
North.........................146
Not............................012
Side .........................153
Six ...........................075
Sixth.........................219
Smoke .....................024
Son’s........................223
South.......................155
Stairs .......................006
Station .....................156
Storage....................157
Sun..........................154
System.....................062
Garage .....................023
Gas...........................138
Glass........................139
Off ............................011
Office........................147
On ............................058
One...........................070
Open.........................148
Outside.....................210
Hall...........................050
Heat..........................010
Baby......................... 120
Back......................... 121
Bar ........................... 122
Basement................. 021
Bathroom ................. 051
Battery...................... 053
Bed .......................... 092
Bedroom .................. 015
Blower...................... 123
Boiler........................ 124
Bright ....................... 162
Building.................... 125
Burglary.................... 039
Inside........................209
Kitchen .....................022
Panic ........................013
Partition ....................090
Patio.........................149
Phone.......................061
Power .......................063
Pump........................166
East..........................132
Eight.........................077
Eighth.......................221
Equipment................133
Exit...........................004
Temperature ............158
Third ........................159
Three .......................072
Tool .........................213
Two..........................071
Laundry ....................140
Left ...........................027
Library ......................141
Light .........................019
Living........................030
Loading.....................142
Lower .......................094
Factory.....................134
Father’s ....................211
Fence.......................135
Fifth..........................218
Fire...........................040
First .........................136
Five..........................074
Floor.........................029
Four..........................073
Fourth.......................217
Foyer........................137
Rear .........................088
Right.........................028
Room........................018
Up............................025
Upper.......................187
Upstairs ...................183
Utility........................185
Machine....................143
Master ......................144
Medical.....................014
Mother’s....................212
Motion ......................145
Call........................... 009
Central ..................... 089
Chime ...................... 054
Closed...................... 126
Computer ................. 127
Console.................... 066
’s...............................007
Second .....................056
Service .....................150
Seven .......................076
Seventh ....................220
Shed.........................151
Shop.........................152
West ........................215
Window....................017
Wing ........................216
Nine..........................078
Ninth.........................222
Zero.........................069
Zone ........................002
Custom Word Substitutes for VIP Module Annunciation
A substitute word can be programmed for each of the 20 custom words used in your alpha zone descriptions. The VIP Module
announces this substitute word in place of the custom word that is displayed on the alpha keypad. For example, a zone
display of "John’s Bedroom" could be announced as "Son’s Bedroom," as there is no annunciation for the custom word "John."
Note that if a substitute word is not assigned, the VIP Module will not annunciate the zone descriptor at all, but will only
annunciate the zone number.
To enter custom word substitutes, do the following:
1. From Data Field Programming Mode, press #93 to display the "ZONE PROG?" prompt.
2. Press [0] (NO) to each menu option until the "CUSTOM INDEX ?" prompt is displayed.
PROMPT
EXPLANATION
Enter 1 at this prompt.
CUSTOM INDEX ?
1=YES 0=NO
0
Enter the custom word number (01-20) for which a voice substitute is desired. Enter 00 to quit this
Programming Mode.
CUSTOM WORD NO.
00=QUIT
Press [✱] to accept entry.
Enter the 3-digit substitute word index number from the Relay Voice Descriptors and Custom Word
Substitutes Vocabulary list in the Relay Voice Descriptors part of this section.
01 ENTER INDEX #
Press [✱] to accept entry.
The "CUSTOM WORD NO." prompt is displayed. Enter the next custom word number to be substituted, or
enter 00 to quit.
– 26 –
Download from Www.Somanuals.com. All Manuals Search And Download.
System Layout Worksheets
Before programming any security system, you should first define the installation. To help you lay out a partitioned
system, use the following worksheets. This will further simplify the programming process.
PARTITIONS
Descriptor
(4-char max)
Prim.
Sub. #
Sec.
Sub. #
Alpha Default Message
(32-character maximum)
Partition #
Partition 1
Partition 2
Keyswitch Arming Partition Assignment (1-2):
Wireless Keypad Partition Assignment (1-2):
Voice Module Partition Assignment (1-2):
Use Partition Descriptor (yes/no)?
COMMUNICATION OPTIONS BY PARTITION
Part. 1
Option
Part. 2
Swinger Suppression Count 00-15; 00=no suppression
Cancel Report After Disarm
Dialer Reports for Panic (* + 1)
Dialer Reports for Panic (# + 3)
Dialer Reports for Panic (* + #)
Dialer Reports for Duress
Burglary Alarm Communications Delay (16 sec.)
SYSTEM DEFINITIONS BY PARTITION (enter values or yes/no)
Part. 1 Part. 2
Option
Entry Delay #1 (00, 30-225 seconds):
Exit Delay #1 (00, 45-225 seconds):
Entry Delay #2 (00, 30-225 seconds):
Exit Delay #2 (00, 45-225 seconds):
Quick Arming
Multiple Alarms per Arming
Console Panic for Zone 95 (* + 1)
Console Panic for Zone 96 (# + 3)
Console Panic for Zone 99 (* + #)
Allow Sign-on (GOTO function)
Non-Bypassable Zone*
Sounder Timeout Duration for Bell (2 min. increments)
Console Annunciation During Entry**
Console Annunciation During Exit
Confirmation of Arming Ding for Bell
Chime on Bell
Access Control Relay (field 1*76)
*Can be any zone 01-64.
**no = 3 beeps; yes = continuous
PRINTER OPTIONS
12- or 24-hour Time format
EVENT LOG TYPES
Option
Alarm
No
Yes
Trouble
Bypass
Open/Close
System
– 27 –
Download from Www.Somanuals.com. All Manuals Search And Download.
DEVICES (keypads, 4204, rf receivers, vip module, lrr)
Sound
Opt
House
ID
Device Types:
Addr
Type
Part
00 = Device Not Used
01 = Alpha Console
02 = Fixed-Word Console
03 = RF Receiver
04 = Relay Module
05 = Voice Module
NOTES:
00.
01.
02.
03.
04.
05.
06.
07.
08.
09.
10.
11.
12.
13.
14.
15.
Address 04 must be used for the Voice Module,
if used.
Console Sounder Options:
0 = No Suppression
1 = Suppress Arm/Disarm and Entry/Exit Beeps
2 = Suppress Chime Mode Beeps Only
3 = Suppress Arm/Disarm, Entry/Exit and Chime
Mode Beeps
Defaults:
Addresses 00 = Alpha Keypad; No Suppression
Addresses 01 = Alpha Keypad; No Suppression
Addresses 02 = Alpha Keypad; No Suppression
Addresses 03 = Alpha Keypad; No Suppression
ACCESS CODES & USER DEFINITIONS FOR PARTITIONS 1 & 2
4-digit
Security
Code
Partition 1
Partition 2
2-Digit
User #
Auth.
Level
Open/
Close
RF Key
2-Digit
User #
Auth.
Level
Open/
Close
RF Key
Authority Levels: 1=Master (arm, disarm, bypass, and/or modify lower level users)
2=Manager (arm, disarm, bypass, and/or modify lower level users)
3=Operator A (arm, disarm, bypass)
4=Operator B (arm, disarm)
5=Operator C (arm, disarm only if system was armed with this code)
6=Duress code (arm, disarm, triggers silent panic alarm)
– 28 –
Download from Www.Somanuals.com. All Manuals Search And Download.
– 29 –
Download from Www.Somanuals.com. All Manuals Search And Download.
– 30 –
Download from Www.Somanuals.com. All Manuals Search And Download.
– 31 –
Download from Www.Somanuals.com. All Manuals Search And Download.
ZONE DEFINITIONS FOR KEYPAD PANIC ZONES 95, 96, & 99
Enter yes/no for each
partition (field *22)
Zone
No.
Zone
Type
Report
Code
Zone Information (part numbers) &
Alpha Descriptor (3 words max.)
1
2
95
96
99
ZONE DEFINITIONS FOR SYSTEM ZONES; 70, 88; 89, 90, 91 & 97
Zone Information (part numbers)
Zone
No.
Zone Report
Type Code
&
Alpha Descriptor (3 words max.)
70
88
89
90
91
97
Zone Types:
00=zone not used
01=entry/exit 1
02=entry/exit 2
03=perimeter
05=day/night burglary
06=24-hour silent
07=24-hour audible
08=24-hour auxiliary
09=supervised fire
10=interior (w/delay)
20=arm stay
21=arm away
22=disarm
23=no alarm response
04=interior (follower)
Input Types:
00=not used
05=RF button transmitter
01=hardwired
03=supervised RF transmitter
04=unsupervised RF transmitter
06=serial number polling loop
07=Dip switch-type polling loop
08=right loop dip switch polling loop
– 32 –
Download from Www.Somanuals.com. All Manuals Search And Download.
Relay Outputs Worksheets
Applicable only if relays (4204) or X-10 devices are used.
ꢀ
Programmed in the #93 Menu Mode in the Relay Programming Section. Fill in the worksheet below and follow the
procedure in the installation instructions as you enter the data during the displays and prompts that appear in sequence.
Notes: 1. For 4204 the Device Programming section must be programmed for the device address. Set the DIP
switches on the device for that address.
2. For X-10 devices, use the 1361X10 transformer in place of the transformer that comes in the box with the
control panel.
Dev Add 4204
or House Code
for X-10
Relay # for 4204
or
Unit Code for X-10
1=4204
2=X-10
RELAY
DEV #
S T A R T
EV/ZL ZT / P
S T O P
ZL ZT / P
Restrict
A
1.
2.
3.
4.
5.
6.
7.
8.
A =
EV = EVENT
ZL = ZONE LIST
DEVICE ACTION
0 = No Response; 1 = Close for 2 sec; 2 = Close and stay closed; 3 = Pulse on and off
0 = Not used; 1 = Alarm; 2 = Fault; 3 = Trouble; 4 = Restore
1-4, 0 = Not Used
NOTES: "START" ZONE LIST: Upon alarm, fault, trouble or restore of ANY zone in this list, device action starts.
"STOP" ZONE LIST: Upon restore of ALL zones in this list, device action stops. It need not be same list as used for START.
ZT = ZONE TYPE/SYSTEM OPERATION
Choices for Zone Types are:
00=zone not used
01=entry/exit 1
02=entry/exit 2
03=perimeter
05=day/night burglary
06=24-hour silent
07=24-hour audible
08=24-hour auxiliary
09=supervised fire
10=interior (delay)
20=arm stay
21=arm away
22=disarm
23=no alarm response
04=interior (follower)
NOTE: Any zone in "ZT" for Start, going into alarm, fault, or trouble will activate the relay.
Any zone in "ZT" for Stop, that restores will stop the relay action.
Choices for System Operation are:
00 = No Response (Not Used)
01 = Entry/Exit #1
02 = Entry/exit #2
23 = No Alarm Response
31 = End of Exit Time
32 = Start of Entry Time
33 = Any Burglary Alarm
34 = Code + [#] + 71 Key Entry
35 = Code + [#] + 72 Key Entry
36 = At Bell Timeout **
37 = 2 Times Bell Timeout **
38 = Chime
39 = Fire Alarm
40 = Bypassing
31 = End of Exit Time
41 = AC Power Fail
43 = Communication failure
44 = RF Low Battery
45 = Polling Loop Failure
51 = RF Receiver Failure
52 = Kissoff
03 = Perimeter
04 = Interior Follower
05 = Trouble Day/Alarm Night
06 = 24-Hr. Silent
54 = Fire Zone Reset
55 = Disarm + 1 Minute
56 = XX Minutes (enter XX in field 1*74) *
57 = YY Seconds (enter YY in field 1*75) *
58 = Duress
60 = Audio Alarm Verification (must be
selected for both START and STOP
operation)
07 = 24-Hr. Audible
08 = 24-Hr. Auxiliary
09 = Fire Alarm or Trouble
10 = Interior W/Delay
20 = Arming-STAY
21 = Arming-AWAY
22 = Disarming (Code + Off)
42 = System Battery Low
*
Stop condition only
** Or at disarming, whichever occurs earlier
P =
PARTITION No. 1-2, 0 = Any
– 33 –
Download from Www.Somanuals.com. All Manuals Search And Download.
ZONE LISTS FOR RELAY DEVICES – Programmed in the #93 Menu Mode in the Relay Programming Section. Fill in the
required data on the worksheet below and follow the procedure shown earlier in this Programming Guide as you enter the
data during the displays and prompts that appear in sequence. Up to 4 zone lists may be created
Note: Record desired zone numbers below. More or fewer boxes than shown may be needed, as any list may include any or
all of system's zone numbers.
Zone List 1: Started or stopped by zone numbers (enter 00 to end entries).
Zone List 2: Started or stopped by zone numbers (enter 000 to end entries).
Zone List 3: Started or stopped by zone numbers (enter 000 to end entries).
Zone List 4: Started or stopped by zone numbers (enter 000 to end entries).
– 34 –
Download from Www.Somanuals.com. All Manuals Search And Download.
VISTA-40 Summary of Connections Diagram
P O L L I N G L O O P
( F a s t / N o r m a l ) L o o p
P r o g r a m m a b l e R e s p o n s e
B R E A K D E T E C T O R L O O P
L A T C H I N G T Y P E G L A S S
( A l s o s u p p o r t s N O / N C B u r g c o n t a c t s )
D E T E C T O R L O O P
2 - W I R E S M O K E
D a t a o u t
D a t a i n
N O C O N N E C T I O N
R E D ( + )
B L K ( - )
– 35 –
Download from Www.Somanuals.com. All Manuals Search And Download.
165 Eileen Way, Syosset, New York 11791
Copyright © 2004 Honeywell International, Inc.
¬1ꢀꢁꢁꢂ359ꢃꢄlꢅ
N7001PRV5 5/04 Rev A
Download from Www.Somanuals.com. All Manuals Search And Download.
|