Honeywell Cell Phone 805595 User Manual

Bedienungs- und Installationsanleitung  
Operation and Installation Instruction  
IQ8Wireless Funkkoppler für Wandmontage  
IQ8Wireless transponder for wall mounting  
(Art.-Nr. / Part No. 805595)  
D
GB  
798941  
10.2006  
Technische Änderungen vorbehalten!  
Technical changes reserved!  
G 205113  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless Funkkoppler für Wandmontage  
Inhaltsverzeichnis Seite  
2
3
4
Projektierungshinweise.........................................................................................................................5  
Montage .................................................................................................................................................8  
Installation.............................................................................................................................................10  
4.1  
4.2  
4.3  
Anschluss der Spannungsversorgung....................................................................................10  
Betrieb als Teilnehmer Analog-Ringleitung.............................................................................11  
Betrieb an Standard Meldergruppe(n).....................................................................................12  
Betrieb an zwei getrennten Standard Meldergruppen........................................13  
Stand-alone Betrieb ..................................................................................................................14  
Relaisausgänge ........................................................................................................................15  
Eingänge....................................................................................................................................16  
R-Eingang ..........................................................................................................16  
P-Klemme...........................................................................................................16  
Schnittstelle........................................................................................................16  
Eing ....................................................................................................................16  
UB .......................................................................................................................16  
4.3.1  
4.4  
4.5  
4.6  
4.6.1  
4.6.2  
4.6.3  
4.6.4  
4.6.5  
5
6
Inbetriebnahme....................................................................................................................................17  
5.1  
5.2  
5.3  
Analog-Ringleitung....................................................................................................................18  
Standard-Meldergruppeneingang............................................................................................19  
Wichtige Hinweise zum Umgang mit Batterien ......................................................................20  
Technische Daten................................................................................................................................22  
Das Gerät “IQ8Wireless Funkkoppler für Wandmontage (Art.-Nr. 805595)“  
entspricht bei bestimmungsgemäßer Anwendung den grundlegenden  
Anforderungen und den übrigen, einschlägigen Bestimmungen der R&TTE-  
Richtlinie 1999/5/EG.  
Ergänzende und aktuelle Informationen  
Die in dieser Dokumentation beschriebenen Leistungsmerkmale, Daten und  
Produktangaben entsprechen dem Stand der Drucklegung dieses Dokumentes  
(Datum siehe Deckblatt) und können durch Produktänderungen und/oder  
geänderte Normen und Richtlinien bei der Projektierung, Installation und  
Inbetriebnahme ggf. von den hier genannten Informationen abweichen.  
Aktualisierte Dokumentationen und Informationen stehen zum Abgleich auf der  
Auflagen der EU-Wirtschaftsgemeinschaft  
Dieses Gerät wurde gemäß den gültigen Richtlinien und Anforderungen der  
Europäischen Union (EU) für den Betrieb innerhalb der EU-Mitgliedstaaten  
entwickelt, produziert und gekennzeichnet. Sollte dieses Gerät außerhalb dieses  
Gültigkeitsbereiches bzw. in Italien (I), Norwegen (N), Zypern (CY), Polen (PL),  
Slowakische Republik (SK), Kroatien (HR) oder Rumänien (RO) installiert werden,  
so sind vorher die nationalen Richtlinien und Auflagen des entsprechenden  
Landes zu beachten.  
Eine Inbetriebnahme ist nur in Übereinstimmung und Erfüllung der jeweiligen  
nationalen und lokalen Anforderungen zulässig.  
FB 798941 / 10.06  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless Funkkoppler für Wandmontage  
1
Allgemein  
Der IQ8Wireless Funkkoppler ermöglicht in Verbindung mit dem zugehörigen IQ8Wireless  
Funksockel und IQ8Wireless Funkinterface die kabellose Anschaltung von Brandmeldern und  
kann wahlweise als Teilnehmer der Analog-Ringleitung des Brandmeldesystems IQ8Control  
oder als eigenständige Funk-Steuereinrichtung in Brandmeldesystemen mit konventionellen  
Meldergruppen eingesetzt werden.  
Das IQ8Wireless Funksystem gewährleistet den ausreichenden Schutz gegen störende  
elektromagnetische Einflüsse unter normalen Umgebungsbedingungen. Diese Baugruppe  
erzeugt und nutzt elektromagnetische Strahlung und kann bei unsachgemäßem Gebrauch  
oder bei Nichtbeachtung der Installationsanleitung eine andere Funkübertragung stören. Die  
elektromagnetische Beeinflussung von Geräten kann grundsätzlich nicht für alle Installationen  
ausgeschlossen werden. Wenn durch diese Baugruppe elektromagnetische Störungen auf  
Rundfunk- oder Fernsehgeräte übertragen werden, die nicht durch das Ein-/Ausschalten des  
Gerätes zu beheben sind, können folgende Maßnahmen zur Beseitigung durchgeführt werden:  
Verändern Sie die Lage der Funkkomponenten  
Vergrößern Sie den Abstand zwischen der gestörten Baugruppe und den Funk-  
komponenten  
Systemanforderungen  
Programmiersoftware tools 8000 ab Version V1.09  
Wird der IQ8Wireless Funkkoppler als Busteilnehmer der Analog-Ringleitung der  
Brandmelderzentrale IQ8Control betrieben, so ist für die Brandmelderzentrale die  
Systemsoftware ab Version V3.04 R001 erforderlich.  
Zubehör  
Art.-Nr.  
Bezeichnung  
805593  
IQ8Wireless Funksockel für automatische Brandmelder Serie IQ8Quad  
(ohne integrierten Alarmgeber)  
805594  
805597  
805601  
805602  
805603  
805604  
805605  
IQ8Wireless Funkgateway für automatische Brandmelder Serie IQ8Quad  
4 Lithium Batterien (Typ AA / 3,6V) zur Spannungsversorgung  
IQ8Wireless universelles Funkinterface (rot), ohne Abdeckplatte  
IQ8Wireless universelles Funkinterface (weiß), ohne Abdeckplatte  
IQ8Wireless Montagerahmen für Alarmgeber IQ8Alarm (rot + weiß)  
IQ8Wireless Montagerahmen für automatische Brandmelder IQ8Quad (weiß)  
IQ8Wireless Abdeckplatte für Funkinterface 805601 und 805602 (rot + weiß)  
Für den Einsatz der automatischen Brandmelder Serie IQ8Quad mit integriertem  
Alarmgeber sind die Art.-Nr. 805602 und 805604 erforderlich.  
Bei Schäden die durch Nichtbeachtung der Betriebsanleitung verursacht werden,  
erlischt der Garantieanspruch. Für Folgeschäden, die daraus resultieren,  
übernimmt der Hersteller keine Haftung. Diese Installationsanleitung ist vor der  
Montage des Funkkopplers genau durchzulesen.  
4
FB 798941 / 10.06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless Funkkoppler für Wandmontage  
2
Projektierungshinweise  
Bei der Projektierung und Ausführung von Brandmeldeanlagen in der Bundesrepublik  
Deutschland müssen unter anderem folgende Normen und Richtlinien beachtet werden:  
DIN VDE 0100  
DIN 14675  
DIN VDE 0833  
DIN EN54  
VdS-Richtlinien (VdS Schadenverhütung GmbH, Köln)  
Lokale Bauauflagen  
Grundsätzlich sollten diese Anforderungen und Vorgaben auch bei der Projektierung von  
Brandmeldeanlagen außerhalb des Gültigkeitsbereiches dieser Normen und Richtlinien  
eingehalten werden. Abhängig von dem tatsächlichen Einsatzgebiet sind zusätzlich nationale  
Auflagen und Bestimmungen einzuhalten.  
Eckdaten für den IQ8Wireless Funkkoppler:  
Max. 32 Funksockel (inkl. Brandmelder IQ8Quad) pro Funkkoppler oder  
Maximal 10 IQ8Handfeuermelder (mit IQ8Wireless Funkinterface) pro Funkkoppler  
Beim Anschluss des IQ8Wireless Funkkopplers an eine Standard Meldergruppe bilden  
alle zugeordneten IQ8Wireless Funkteilnehmer eine gemeinsame Meldergruppe  
(siehe VdS-Hinweis)  
Eckdaten für die Analog-Ringleitung (Brandmeldesystem IQ8Control)  
Ein IQ8Wireless Funkkoppler ist ein Teilnehmer der Analog-Ringleitung und belegt  
1 Adresse  
Ein zugeordneter IQ8Wireless Funksockel (inkl. Brandmelder IQ8Quad) belegt 1 Adresse  
Ein IQ8Handfeuermelder (inkl. erforderlichem IQ8Wireless Funkinterface) belegt  
1 Adresse  
Max. 127 Teilnehmer (Adressen) pro Analog-Ringleitung  
Max. 10 IQ8Wireless Funkkoppler pro Analog-Ringleitung  
max. 20 IQ8Wireless Funkkoppler pro Brandmelderzentrale IQ8Control C  
max. 50 IQ8Wireless Funkkoppler pro Brandmelderzentrale IQ8Control M  
Jeder automatische Brandmelder IQ8Quad (mit IQ8Wireless Funksockel) oder  
IQ8Handfeuermelder (mit IQ8Wireless Funkinterface) kann als eigene Meldergruppe  
konfiguriert werden  
Automatische Brandmelder und Handfeuermelder dürfen nicht an einem  
gemeinsamen IQ8Wireless Funkkoppler betrieben werden.  
FB 798941 / 10.06  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless Funkkoppler für Wandmontage  
Der Montageort des Funkkopplers sollte so gewählt werden, dass die kürzeste  
Übertragungsstrecke (Funkweg) zu den Funksockeln realisiert werden kann und möglichst  
keine störende elektromagnetische Beeinflussung zu erwarten ist. Durch Störquellen oder  
einen ungeeigneten Montageort kann die Funktion des Funkkopplers erheblich beeinträchtigt  
und die Reichweite reduziert werden:  
Elektrische Störquellen  
Energie- / Starkstromkabel  
Starke Funksender im nahen Umfeld  
Getaktete elektronische Schaltungen  
Computer bzw. EDV-Anlagen  
Mechanische Störquellen  
Metallgitter und Metalltore  
Metallschränke (Schrankwände)  
Betondecken und Betonwände  
Ungünstige Anordnung (Winkel) von Funkkoppler und Funksockel  
Der Funkkoppler arbeitet mit 25 Kanälen in dem Frequenzband 433 MHz bzw.  
868 MHz. Beachten Sie auch Störquellen, die nur zeitweilig auftreten, wie z.B.  
Mobiltelefone oder Computer!  
Anforderung an die Umgebung  
Die Qualität der Funkübertragung ist stark abhängig von der Umgebungstemperatur. Eine  
Temperatursenkung in den überwachten Räumen, z.B. in der Nacht, kann die im  
Tagbetrieb erreichte Funkqualität negativ beeinflussen.  
Tagsüber betriebsbedingt offenstehende Schiebetore oder Türen, wie auch z.B.  
Deckenkräne, können im geschlossenen Zustand oder veränderter Position die  
Funkstrecke stören.  
Zur Projektierung des Funksystems steht in der Programmiersoftware tools 8000  
eine Feldstärkemessung zur Verfügung. Mit dieser Option kann die Qualität der  
Funkverbindung (Feldstärke) zwischen dem Funkkoppler und dem  
Funkteilnehmer überprüft werden.  
Das Gerät “IQ8Wireless Funkkoppler für Wandmontage (Art.-Nr. 805595)“  
entspricht bei bestimmungsgemäßer Anwendung den grundlegenden  
Anforderungen und den übrigen, einschlägigen Bestimmungen der R&TTE-  
Richtlinie 1999/5/EG.  
6
FB 798941 / 10.06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless Funkkoppler für Wandmontage  
Abschwächung des Funksignals  
max. 300m*  
0% bis -10%  
Holz, Gips, Leichtbauwände  
-5% bis -35%  
Backstein (oder Trennwände mit Isolierfüllung)  
-30% bis -90%  
armierte Betonwand  
-90% bis -100%  
Metall, Metallgitter Alukaschierung  
Abb. 1: Abschwächung des Funksignals bei mechanischen Hindernissen (in Prozent)  
*
Maximale Reichweite bei Sichtkontakt zwischen Funksockel und Funkkoppler sowie  
optimalen technischen Rahmenbedingungen.  
FB 798941 / 10.06  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless Funkkoppler für Wandmontage  
3
Montage  
Der Funkkoppler ist mit geeignetem Befestigungsmaterial (wie z.B. Dübel + Schrauben)  
lagerichtig auf einer stabilen Wandfläche ohne mechanische Verspannung des Gehäuses zu  
montieren.Der Montageort sollte so gewählt sein, dass eine gute Funkverbindung (Feldstärke)  
zwischen dem Funkkoppler und den zugehörigen Funksockeln gewährleistet werden kann.  
Die Qualität der Funkverbindung kann mit der Programmiersoftware tools 8000 ab V1.09  
überprüft werden.  
172  
39  
Oben  
Abb. 2: Befestigungspunkte der Gehäuserückwand (Maße in mm)  
Auf der Vorderseite des Gehäuses befinden sich die 4 LED-Zustandsanzeigen mit jeweils  
eigenem Beschriftungsfeld sowie die Gehäuseschraube.  
Oben  
LED 1  
LED 2  
LED 3  
LED 4  
1
A
rot grün  
B
rot grün  
200  
Abb. 3: IQ8Wireless Funkkoppler im Gehäuse mit Anzeige-LED und Antennen (Maße in mm)  
Beachten Sie, dass der Funkkoppler nicht auf Wänden montiert wird,  
die z.B. ein Metallgitter enthalten oder mit Aluminiumfolie isolierter Glaswolle  
gefüllt sind und somit den Funkweg ggf. stark beeinträchtigen können.  
8
FB 798941 / 10.06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless Funkkoppler für Wandmontage  
LED 1 Betrieb (grün) leuchtet im Normalbetrieb  
LED 2 Sammelfeuer (rot)  
leuchtet, wenn die Feuermeldung eines zugeordneten Funkteilnehmers erkannt  
wurde. Das Relais >Sammelfeuer< wird angesteuert.  
LED 3 Sammelstörung (gelb), Anzeige nicht speichernd  
leuchtet, wenn eine Störungsmeldung des Funkkopplers oder eines zugeordneten  
Funkteilnehmers erkannt wurde. Die Ansteuerung des Relais >Sammelstörung< wird  
unterbrochen und der Relaiskontakt wechselt den Schaltzustand.  
LED 4 Initialisierung (gelb)  
Leuchtet während des Einschalt-/Einlernvorgangs bei der Erkennung der  
Funkteilnehmer.  
Gehäuseschraube zum Öffnen/Schließen des Kopplergehäuses.  
c
LED-Anzeigen auf der Platine  
Anzeige der esserbus® Kommunikation  
Die beiden LED (rot und grün) flackern bei einer Kommunikation auf der  
A
angeschlossenen Analog-Ringleitung der Brandmelderzentrale IQ8Control.  
B
LED-Anzeige für den Funk-Status  
rot  
grün  
blinkt  
Normalbetrieb  
Alle zugeordneten Funkteilnehmer befinden sich  
ordnungsgemäß im Frequenzhopping-Betrieb  
Aus  
(2Hz)  
Normalbetrieb mit Funkstörung  
Mindestens 1 Funkteilnehmer ist nicht mehr im  
Frequenzhopping-Betrieb und wird im Basiskanal  
gesucht. Nach ca.40-60s wird die Störung an der  
BMZ angezeigt. Wenn der Funkteilnehmer vor Ablauf  
dieser Zeit wieder automatisch gefunden wird,  
erlischt die rote LED.  
blinkt  
(2Hz)  
An  
Installationsmodus (eingeschränkter Betrieb)  
z.B. während der Messung der Signalstärke, der  
Koppler- oder Melderdatenvergabe oder bei der  
Suche nach einem Funkteilnehmer.  
Blinken abwechselnd  
(2Hz)  
Blinken gleichzeitig  
(2Hz)  
Defekt - Funkbetrieb aus  
Kein Funkbetrieb möglich Î Koppler ist defekt  
Abschaltung – Funkbetrieb aus  
Der Funkbetrieb wurde automatisch abgeschaltet  
weil kein Funkteilnehmer zugeordnet ist, bzw. alle  
zugeordneten Funkteilnehmer nicht gefunden  
werden.  
Blinken gleichzeitig  
alle 7 Sekunden  
FB 798941 / 10.06  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless Funkkoppler für Wandmontage  
4
Installation  
4.1  
Anschluss der Spannungsversorgung  
Die Spannungsversorgung kann von der Brandmelderzentrale oder einem externen Netzteil  
erfolgen. Zur Spannungsversorgung des Funkkopplers ist eine eigene, separat abgesicherte,  
Versorgungsleitung zu installieren. Das Anschlusskabel muss den Richtlinien zum  
Funktionserhalt in Brandmeldesystemen entsprechen. Werden mehrere Funkkoppler an eine  
gemeinsame Spannungsversorgung angeschlossen, so ist jede Versorgungsleitung einzeln  
und rückwirkungsfrei, z.B. mit der 8-Sicherungskarte (Art.-Nr. 382040), abzusichern.  
Überwachung der Spannungsversorgung  
Die externe Spannungsversorgung wird von dem Funkkoppler überwacht. Wird der  
Funkkoppler als Teilnehmer der Analog-Ringleitung des Brandmeldesystems IQ8Control  
installiert, so wird eine Störung über die Ringleitung an die Brandmelderzentrale übertragen  
und dort angezeigt.  
Beim Anschluss des Funkkopplers an eine Standard Meldergruppe kann der Relaisausgang  
>Sammelstörung< zur Meldung einer Störung genutzt werden.  
UB  
-
+
Externes Netzteil  
UBext.  
GND  
Störmelde-  
kontakt  
oder  
-
9 V.....30 V DC  
Brandmelderzentrale  
+
UBext.  
GND  
Abb. 4: Anschluss der Spannungsversorgung  
Zur Spannungsversorgung des Funkkopplers muss ein VdS-zugelassenes  
Netzteil gemäß EN 54-4 angeschlossen werden, z.B. Externes 12 V DC-Netzteil  
mit Akkustellplatz (Art.-Nr. 785653) oder 24 V DC-Ausführung (Art.-Nr. 785655).  
10  
FB 798941 / 10.06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless Funkkoppler für Wandmontage  
4.2  
Betrieb als Teilnehmer Analog-Ringleitung  
Der Funkkoppler wird direkt an die Analog-Ringleitung des Brandmeldesystems IQ8Control  
angeschlossen.  
Alle Meldungen des Funkkopplers werden über die Analog-Ringleitung zur Brandmelder-  
zentrale IQ8Control übertragen. Die zugeordneten Funkteilnehmer können in einzelne  
Meldergruppen aufgeteilt werden. Bei einer Meldung eines Funksockels wird dann die  
Meldergruppe und Meldernummer des Funksockels (inkl. Brandmelder IQ8Quad) oder des  
IQ8Handfeuermelders angezeigt.  
Zusätzlich können die beiden Relaisausgänge des Funkkopplers für Steuerfunktionen genutzt  
werden. Für den Betrieb des Funkkopplers ist eine externe Spannungsversorgung erforderlich.  
Jumper J1 + J2 nicht gesteckt  
J2  
J2  
J1  
J1  
UB  
UB  
IN OUT  
+ + - -  
IN OUT  
+ + - -  
PE PE  
PE PE  
+ -  
+ -  
-
-
9 V.....30 V DC  
9 V.....30 V DC  
+
+
A+  
B+  
A-  
B-  
Abb. 5: Anschluss des Funkkopplers an die Analog-Ringleitung (Prinzipdarstellung)  
Systemvoraussetzungen  
Brandmelderzentrale IQ8Control C/M ab Softwarestand V3.04 R001  
Analog-Ring-Modul (Art.-Nr. 804382 / 784382)  
Programmiersoftware tools 8000 ab V1.09  
Anschlussdaten  
Externe Spannungsversorgung 9 V DC bis 30 V DC  
Jumper J1 und J2 nicht gesteckt (werkseitige Einstellung)  
FB 798941 / 10.06  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless Funkkoppler für Wandmontage  
4.3  
Betrieb an Standard Meldergruppe(n)  
Über die Relais kann der Funkkoppler an den Standard-Meldergruppeneingang eines  
Brandmeldesystems angeschlossen werden. Alle Funkteilnehmer bilden eine gemeinsame  
Meldergruppe an diesem Funkkoppler. Eine Aufteilung in mehrere, unterschiedliche  
Meldergruppen ist nicht möglich. Der Meldergruppeneingang wird mit dem Widerstand (R1) an  
dem invers betriebenen, im Ruhebetrieb angesteuerten, Sammelstörungsrelais  
angeschlossen. Im Alarmfall wird über das Sammelfeuerrelais der Alarmwiderstand (R2)  
parallel zu R1 geschaltet und die Meldergruppe ausgelöst.  
Rücksetzen  
Der Funkkoppler wird in den meldebereiten Normalzustand zurückgesetzt, indem die  
Spannung der Meldergruppe für die Zeit von mindestens 60ms unter den Spannungswert 5 V  
absinkt, z.B. durch Ein-/Ausschalten oder Rücksetzen der betreffenden Meldergruppe).  
Das Rücksetzen kann optional auch über einen externen Reset-Taster (siehe c) oder einen  
Relaiskontakt realisiert werden. Hierzu muss für mindestens 1 Sekunde eine Spannung von  
9 bis 30 V DC an den Eingang (Eing +/-) des Funkkopplers geschaltet werden.  
Jumper J1 + J2  
gesteckt  
J2  
J1  
Sa-Feuer  
Sa-Stör  
C
C
UB  
Eing  
+
PE  
NC NO  
R
P
NO NC  
-
-
+
R2  
R1  
-
Meldergruppe 1  
+
-
1
Reset  
9 V bis 30 V DC  
+
Abb. 6: Anschluss an einen Standard Meldergruppeneingang  
Anschlussdaten  
Externe Spannungsversorgung 9 V DC bis 30 V DC  
Meldergruppenspannung 9 V DC bis 30 V DC  
R1 Ruhewiderstand (z.B. 10Kfür Standard Meldergruppen System 8000/IQ8Control)  
R2 Alarmwiderstand (z.B. 1Kfür Standard Meldergruppen System 8000/IQ8Control)  
Jumper J1 und J2 gesteckt (Jumper sind im Beipack enthalten)  
Reset-Zeit = 0,2 bis 3 Sekunden  
Abhängig von dem Meldergruppeneingang kann bei dieser Anschaltung die  
Störung eines einzelnen Funkteilnehmers zur Störung der gesamten  
Meldergruppe führen und die Meldebereitschaft beeinträchtigen. In diesem Fall  
kann die Störungsmeldung auf einen separaten Meldergruppeneingang gelegt  
werden, so dass nicht gestörte Teilnehmer weiterhin meldebereit bleiben.  
12  
FB 798941 / 10.06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless Funkkoppler für Wandmontage  
4.3.1  
Betrieb an zwei getrennten Standard Meldergruppen  
Mit dieser getrennten Anschaltung zur Feuer- und Störungsmeldung kann nach einer  
Störungsmeldung (z.B. die Batterie eines Funksockels ist zu schwach) noch zusätzlich eine  
Feuermeldung übertragen werden. Die Störungsmeldung ist nicht speichernd und setzt sich  
nach Beseitigung der Meldungsursache automatisch zurück.  
Rücksetzen  
Der Funkkoppler wird in den meldebereiten Normalzustand zurückgesetzt, indem die  
Spannung der Meldergruppe “Feuer“ (hier im Beispiel Nr. 1) für die Zeit von mindestens 60ms  
unter den Spannungswert 5 V absinkt, z.B. durch Ein-/Ausschalten der Meldergruppe. Das  
Rücksetzen kann optional auch über einen externen Reset-Taster (siehe c) oder einen  
Relaiskontakt realisiert werden. Hierzu muss für mindestens 1 Sekunde eine Spannung von  
9 bis 30 V DC an den Eingang (Eing +/-) des Funkkopplers geschaltet werden.  
Jumper J1 + J2  
gesteckt  
J2  
J1  
Sa-Feuer  
Sa-Stör  
C
C
UB  
Eing  
+
NC NO  
R
P
NO NC  
-
-
BMZ  
+
R1  
R2  
R3  
-
Meldergruppe  
"Feuer"  
+
Meldergruppe  
"Störung"  
-
+
-
1
Reset  
9 V bis 30 V DC  
+
Abb. 7: Anschluss an zwei getrennten Standard Meldergruppen (Feuer / Störung)  
Anschlussdaten  
Externe Spannungsversorgung 9 V DC bis 30 V DC  
Meldergruppenspannung 9 V DC bis 30 V DC  
R1 Ruhewiderstand (z.B. 10Kfür Standard Meldergruppen System 8000/IQ8Control)  
R2 Alarmwiderstand (z.B. 1Kfür Standard Meldergruppen System 8000/IQ8Control)  
R3 Ruhewiderstand für die Störungsmeldung (z.B. 10Kfür Standard Meldergruppen  
System 8000/IQ8Control)  
Jumper J1 und J2 gesteckt (Jumper sind im Beipack enthalten)  
Reset-Zeit = 0,2 bis 3 Sekunden  
FB 798941 / 10.06  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless Funkkoppler für Wandmontage  
4.4  
Stand-alone Betrieb  
Im Stand-alone Betrieb kann der Funkkoppler, ohne weitere Anschaltung an eine  
Brandmelderzentrale, als eigenständiges Gerät betrieben werden. Zum Anschluss von lokalen  
Signalgebern für die Feuer- und Störungsmeldung stehen die beiden Relaisausgänge  
>Sammelfeuer< (Sa-Feu) und >Sammelstörung< (Sa-Stör) zur Verfügung.  
Über das Relais Sammelstörung kann auch eine Meldung, z.B. an ein übergeordnetes  
Gefahrenmeldesystem oder eingewiesene Personen abgesetzt werden.  
Rücksetzen  
Das Rücksetzen wird über einen externen Reset-Taster (siehe c) oder optional mit einem  
externen Relaiskontakt realisiert. Hierzu muss für mindestens 1 Sekunde eine Spannung von  
9 bis 30 V DC an den Eingang (Eing +/-) des Funkkopplers geschaltet werden.  
Jumper J1 + J2  
nicht gesteckt  
J2  
J1  
Sa-Feuer  
Sa-Stör  
UB  
C
C
IN OUT  
Eing  
+
NC NO  
R
P
NO NC  
-
-
-
-
+
+
+
-
1
Reset  
9 V DC bis 30 V DC  
+
Abb. 8: Anschluss eines einzelnen Funkkopplers im Stand-alone Betrieb  
Anschlussdaten  
Externe Spannungsversorgung 9 V DC bis 30 V DC  
Jumper J1 und J2 offen  
Reset-Zeit = 0,2 bis 3 Sekunden  
14  
FB 798941 / 10.06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless Funkkoppler für Wandmontage  
4.5  
Relaisausgänge  
Der Funkkoppler verfügt über die zwei Relaisausgänge >Sammelfeuer< und  
>Sammelstörung<. Die Schaltfunktion der beiden Relais kann nicht verändert werden.  
Beim Anschluss des Funkkopplers an eine Standard-Meldergruppe werden beide Relais  
beschaltet und stehen somit nicht mehr für die Schaltfunktion >Sammelfeuer< bzw.  
>Sammelstörung< zur Verfügung.  
Sa-Feuer  
Sa-Stör  
C
C
NC NO  
R
P
NO NC  
externe Geräte  
externe Geräte  
Abb. 9: Relaiskontakte (Ruhelage)  
2 potentialfreie Wechslerkontakte  
Kontaktbelastung 30 V DC / 1A  
Sa-Feuer (Sammelfeuer)  
Der Relaisausgang >Sammelfeuer< wird angesteuert, wenn mindestens ein zugeordneter  
Funksockel oder IQ8Handfeuermelder eine Alarm-/ Feuermeldung zu diesem Funkkoppler  
überträgt.  
Sa-Stör (Sammelstörung)  
Das Relais >Sa-Stör < ist im störungsfreien Normalbetrieb dauerhaft angesteuert. Somit kann  
bei einem Ausfall der Versorgungsspannung über den Zustandswechsel dieses Relais noch  
eine Störungsmeldung abgesetzt werden.  
Der Relaisausgang >Sammelstörung< wird angesteuert, wenn mindestens ein zugeordneter  
Funksockel oder IQ8Handfeuermelder eine Störungsmeldung zu diesem Funkkoppler  
überträgt oder der Funkkoppler selbst eine Störung (z.B. Energieversorgung) erkennt.  
Die Ansteuerung des Relais ist der Störungsmeldung folgend (nicht speichernd).  
FB 798941 / 10.06  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless Funkkoppler für Wandmontage  
4.6  
Eingänge  
UB  
Schnittstelle  
Eing  
+
-
-
R
P
1
2
3
4
5
6
+
Abb. 10: Lage der Anschlussklemmen  
4.6.1  
R-Eingang  
Eingang für den Anschluss des Funkkopplers an eine Standard-Meldergruppe. Dieser Eingang  
wird für die Rücksetzfunktion benötigt. Beim Anschluss des Funkkopplers an die Analog-  
Ringleitung des Brandmeldesystems IQ8Control darf der Eingang nicht beschaltet werden.  
4.6.2  
P-Klemme  
Freie Stützpunktklemme  
4.6.3  
Schnittstelle  
Ohne Funktion – Klemmen nicht beschalten.  
Diese Schnittstelle ist für die zukünftige Erweiterung des Leistungsumfanges vorgesehen  
(z.B. direkter Anschluss des Service-PC).  
4.6.4  
Eing  
Rücksetzeingang für ein externes RESET-Signal.  
Durch Anlegen einer Spannung im Bereich von 9V DC bis 30V DC für die Dauer von  
mindestens 1 Sekunde wird der Funkkoppler zurückgesetzt.  
4.6.5  
UB  
Eingang für die Versorgungsspannung 9 V DC bis 30 V DC.  
16  
FB 798941 / 10.06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless Funkkoppler für Wandmontage  
5
Inbetriebnahme  
Zur Inbetriebnahme des Funkkopplers ist die Programmiersoftware tools 8000 ab Version  
V1.09 sowie das Zentraleninterface (Art.-Nr. 789862) und ein Service-PC erforderlich. Die  
Inbetriebnahme unterscheidet sich abhängig davon, ob der Funkkoppler als Teilnehmer der  
Analog-Ringleitung installiert ist oder an einen Standard-Meldergruppeneingang  
angeschlossen wurde.  
Beispiel:  
Von Funkkoppler 1 werden alle im Kreis befindlichen und dunkel dargestellten Funksockel mit  
ausreichender Feldstärke erkannt. Mit der Programmiersoftware tools 8000 werden die  
gewünschten (im Beispiel dunklen) Funksockel dem Funkkoppler 1 zugeordnet.  
1
1
2
2
Abb. 11: Erkannte und zugeordnete Funksockel von Funkkoppler 1  
Die dem Funkkoppler zugeordneten Funksockel sind bei der Inbetriebnahme des  
1
Funkkopplers 2 für diesen nicht mehr erkennbar, weil sie bereits zum Funkkoppler 1  
zugeordnet wurden. Alle vom Funkkoppler 2 erkannten Funksockel (helle Darstellung) können  
dem Funkkoppler  
2
zugeordnet werden. Die Zuordnung zwischen Funksockel und  
Funkkoppler kann in der Programmierung mit der Programmiersoftware tools 8000 beliebig  
geändert werden. Berücksichtigen Sie bei der Zuordnung die Qualität der Funkverbindung  
(Feldstärke) und die Verteilung der Funksockel innerhalb der überwachten Räume.  
Wird ein Funkkoppler während der Inbetriebnahme abgeschaltet oder verliert er  
die Kommunikation zu seinem zugeordneten Funkteilnehmer, so sind diese  
wieder für alle anderen - in entsprechender Reichweite montierten -Funkkoppler  
sichtbar. Die Funkteilnehmer können bei der Zuordnung durch die individuelle  
Seriennummer identifiziert werden. Diese Seriennummer wird bei jedem  
erkannten Funkteilnehmer in der Programmiersoftware tools 8000 angezeigt.  
Bei einer Zuordnung eines Funkteilnehmers zu mehreren Funkkopplern ist der  
ordnungsgemäße Betrieb nicht gewährleistet.  
Zur schnellen Hilfe bei Problemen während der Inbetriebnahme können auf dem  
Display der Brandmelderzentrale IQ8Control dreistellige Störungscode angezeigt  
werden. Die Bedeutung des Codes ist in der Installationsanleitung der BMZ  
IQ8Control beschrieben.  
Detaillierte Informationen zur Programmierung des Funkkopplers finden Sie in  
der Online-Hilfe der Programmiersoftware tools 8000.  
FB 798941 / 10.06  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless Funkkoppler für Wandmontage  
5.1  
Analog-Ringleitung  
1. Schließen Sie den Funkkoppler - wie im Abschnitt „Installation“ beschrieben - an die  
Analog-Ringleitung  
des  
Brandmeldesystems  
IQ8Control  
und  
die  
externe  
Spannungsversorgung an.  
2. Schalten Sie die Brandmelderzentrale bzw. die Analog-Ringleitung ein, an der der  
Funkkoppler angeschaltet ist. Beim Anschluss mehrerer Funkkoppler sollten diese einzeln  
und nacheinander in Betrieb genommen werden, um eine mehrfache Zuordnung eines  
Funkteilnehmers zu vermeiden.  
3. Führen Sie mit dem Service-PC und der Programmiersoftware tools 8000 eine  
Verdrahtungserkennung der Ringleitung durch. Alle Teilnehmer der Analog-Ringleitung  
werden angezeigt.  
4. Klicken Sie auf den gewünschten Funkkoppler dieser Analog-Ringleitung, um den Dialog  
für die Programmierung des Funkkopplers zu öffnen.  
5. Überprüfen Sie in dem Menüpunkt „Signalstärke messen“, ob die Funkübertragung  
zwischen dem Funkkoppler und dem Funksockel über eine ausreichende Qualität verfügt.  
6. In dem Menüpunkt „Funkteilnehmer zuordnen“ werden alle von diesem Funkkoppler  
erkannten Funksockel angezeigt. Sind mehrere Funkkoppler vorhanden, so werden  
bereits anderen Funkkopplern zugeordnete Funksockel nicht mehr angezeigt.  
7. Ordnen Sie die in dem Menüpunkt „Funkteilnehmer zuordnen“ alle gewünschten  
Funksockel einzeln dem Funkkoppler zu. Die Funkteilnehmer können individuell in  
einzelne Meldergruppen eingeordnet werden.  
8. Für diesen Funkkoppler ist die Inbetriebnahme beendet. Lassen Sie den Funkkoppler  
eingeschaltet und nehmen Sie, falls vorhanden, weitere Funkkoppler in Betrieb.  
805595  
Service-PC  
Zentralen-  
Interface  
789862  
esserbus®-PLus  
Abb. 12: IQ8Wireless Funkkoppler als Teilnehmer der Analog-Ringleitung  
18  
FB 798941 / 10.06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless Funkkoppler für Wandmontage  
5.2  
Standard-Meldergruppeneingang  
1. Schließen Sie die externe Spannungsversorgung an den Funkkoppler, wie im  
Kapitel „Installation“ beschrieben, an.  
2. Schließen Sie den Service-PC über das Zentraleninterface (Art.-Nr. 789862) an die  
Anschlussklemmen für die Analog-Ringleitung des Funkkopplers an und starten Sie die  
Programmiersoftware tools 8000.  
3. Führen Sie mit dem Service-PC und der Programmiersoftware tools 8000 eine  
Verdrahtungserkennung durch.  
4. Klicken Sie auf den gewünschten Funkkoppler, um den Dialog für die Programmierung zu  
öffnen.  
5. Überprüfen Sie in dem Menüpunkt „Signalstärke messen“, ob die Funkübertragung  
zwischen dem Funkkoppler und dem Funksockel über eine ausreichende Qualität verfügt.  
6. In dem Menüpunkt „Funkteilnehmer zuordnen“ werden alle von diesem Funkkoppler  
erkannten Funksockel angezeigt. Sind mehrere Funkkoppler vorhanden, so werden  
bereits anderen Funkkopplern zugeordnete Funksockel nicht mehr angezeigt.  
7. Ordnen Sie die in dem Menüpunkt „Funkteilnehmer zuordnen“ alle gewünschten  
Funksockel bis einschließlich dem Menüpunkt „Melder einlesen“ dem Funkkoppler einzeln  
zu.  
8. Entfernen Sie die Verbindung an den Anschlussklemmen der Analog-Ringleitung des  
Funkkopplers und schalten Sie den Koppler für ca. 5 Sekunden spannungsfrei.  
9. Schließen Sie den Funkkoppler, wie im Kapitel „Installation“ beschrieben, an den  
Standard-Meldergruppeneingang des Brandmeldesystems an.  
10. Für diesen Funkkoppler ist die Inbetriebnahme beendet.  
4G/2R  
esserbus®-  
805595  
Koppler  
IN OUT  
+ + - -  
esserbus®  
Zentralen-  
Interface  
789862  
Service-PC  
Standard  
Meldergruppe  
Abb. 13: IQ8Wireless Funkkoppler an einem Standard-Meldergruppeneingang  
FB 798941 / 10.06  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless Funkkoppler für Wandmontage  
5.3  
Wichtige Hinweise zum Umgang mit Batterien  
Hinweise zum Stromverbrauch und zum Umgang mit den Batterien (Art.-Nr. 805597) für den  
Einsatz in IQ8Wireless Funkkomponenten:  
Batterien erst kurz vor der Inbetriebnahme (Zuordnung zu den Funkkopplern) in die  
Funkteilnehmer einsetzen! Nicht zugeordnete Funkteilnehmer haben einen ca. 4-mal  
höheren Stromverbrauch.  
Ausreichende Restfeldstärke beachten!  
Der Betrieb mit geringerer Feldstärke verursacht einen etwas höheren Stromverbrauch.  
Zeitgleich in Betrieb genommene, gleiche Funkteilnehmer können somit später nach  
unterschiedlicher Laufzeit eine Batterieunterspannung (Batt. < 30) an der BMZ melden. Die  
Wahrscheinlichkeit von Funkstörungen (z.B. durch Elektro-Smog oder Feldänderungen)  
steigt sehr stark mit geringerer Restfeldstärke. Wenn der Funkkontakt unterbrochen wird  
und die Funkteilnehmer das Frequenzhopping verlassen müssen, um in den Basiskanälen  
wieder vom zugeordneten Funkkoppler in das Frequenzhopping gebracht zu werden,  
verursacht dieses einen ca. 4-mal höheren Stromverbrauch.  
Wie häufig ein Funkkoppler nach einem seiner zugeordneten Funkteilnehmer im  
Basiskanal suchen muss, erkennt man über den Service-PC an dem Zähler >Vorstörung<  
in der Programmiersoftware tools 8000.  
Beim Ausfall der 12/24  
V
DC-Spannungsversorgung eines Funkkopplers wird der  
Funkbetrieb des Kopplers beendet und alle zugeordneten Funkteilnehmer suchen im  
Basiskanal nach diesem Funkkoppler. Hierdurch ca. 4-mal höherer Stromverbrauch der  
Funkteilnehmer.  
Im Alarmfall verursachen die Melder in Funkteilnehmern einen etwas höheren  
Stromverbrauch.  
Die zugelassenen Batterien (Art.-Nr. 805597) sind im unbelasteten Zustand mit einer sehr  
geringen Selbstentladung (1% jährlich @ 25°C ± 10°C) behaftet. Die Lagerung außerhalb  
dieses Temperaturbereiches verursacht eine höhere Selbstentladung. Die nominelle  
Kapazität der Batterien nimmt z.B. bei niedrigen Temperaturen ab und ist bei einem Betrieb  
in der Nähe des Gefrierpunktes bis zu 20-30% geringer.  
Aufgrund der „Passivierungseffekte“ sollten Batterien, die älter als drei Jahre sind, nicht  
mehr verwendet werden. Daher sind die Batterien entsprechend gekennzeichnet.  
Z.B.: F.02.277.E  
F
= Frankreich  
02  
277  
E
= im Jahr 2002  
= produziert am 277sten Tag  
= Charge  
Zur Inbetriebnahme werden die Batterien automatisch nach dem Einlegen kurzzeitig mit  
einem sehr hohen Strom belastet. In seltenen Fällen kann hierdurch sofort eine  
Batterieunterspannung  
(Batt.  
<
30)  
an  
der  
BMZ  
angezeigt  
werden.  
Abhilfe: Funkteilnehmer über die BMZ noch einmal einschalten.  
Die Batteriespannung wird bei betriebsbereiten Teilnehmern ca. alle 12 Stunden  
automatisch und ca. 2 Minuten nach dem Einlegen der Batterien bzw. nach Einschalten  
(Meldergruppe/Melder) eines Funkteilnehmers geprüft.  
20  
FB 798941 / 10.06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless Funkkoppler für Wandmontage  
Batteriepole und -kontakte der Funkteilnehmer nicht mit bloßen Fingern berühren ! Durch  
einen Fettfilm wird ein Übergangswiderstand zwischen den Batterien und Kontakten  
gebildet. Dieser Übergangswiderstand kann zu einer verfrühten bzw. falschen Anzeige zur  
Batterieunterspannung (Batt. < 30) an der BMZ führen.  
Unsachgemäße Lagerung der Funkteilnehmer und Batterien können solche  
Übergangswiderstände (z.B. durch Korrosion) verursachen. Kontakte ggf. vor dem  
Einsetzen der Batterien(z.B. mit einer Isopropanol-Lösung) reinigen.  
Die Batterien ausschließlich im Set (4 Stück) tauschen, um eine gleichmäßige Entladung  
zu gewährleisten. Die gemeldete Batterieunterspannung (Batt. < 30) an der BMZ bezieht  
sich immer auf die Batterie mit der kleinsten Kapazität.  
Bei Funkteilnehmern die nach langer Betriebszeit eine Batterieunterspannung melden,  
kann bei der Überprüfung durch die Bewegung der eingesetzten Batterien ggf. für kurze  
Zeit (wenige Stunden) die Störung behoben sein. Nach dem Einschalten des  
Funkteilnehmers erfolgt daher keine Meldung „Batterieunterspannung“. Batteriesatz der  
entsprechenden Funkteilnehmer vollständig austauschen !  
FB 798941 / 10.06  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless Funkkoppler für Wandmontage  
6
Technische Daten  
Betriebsspannungsbereich  
:
:
:
:
:
:
:
9 V DC bis 30 V DC  
Betriebsspannung  
Kontaktbelastung  
Ruhestrom  
12 V DC oder 24 V DC  
max. 30 V DC / 1A  
ca. 17 mA @ 12 V DC  
ca. 18 mA @ 12 V DC  
433 / 868 MHz  
Alarmstrom  
Frequenzband  
Reichweite  
bis max. 300m  
(abhängig von Montageort und Umgebungsbedingungen)  
Anwendungstemperatur  
Lagertemperatur  
Schutzart  
:
:
:
:
:
:
:
:
-5 °C bis +55 °C  
-10 °C bis +60 °C  
IP 42  
Gehäuse  
PC/ASA Kunststoff  
weiß, ähnlich RAL 9010  
ca. 250g  
Farbe  
Gewicht  
Maße (mm)  
200 x 280 x 39 (mm) - inkl. Antennen  
G 205113  
VdS-Anerkennung  
22  
FB 798941 / 10.06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation and Installation Instruction  
IQ8Wireless transponder for wall mounting  
(Part No. 805595)  
798941  
GB  
G 205113  
Technical changes reserved!  
10.2006  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless transponder for wall mounting  
Intended purpose  
This product must only be used for the applications outlined in the catalogue and the  
technical description and in combination with external components and systems which  
have been approved or recommended by the manufacture.  
Warning  
In order to ensure correct and safe operation of the product, all guidelines concerning its  
transport, storage, installation, and mounting must be observed. This includes the  
necessary care in operating the product.  
Safety-relevant user information  
This manual includes all information required for the proper use of the products described.  
The term 'qualified personnel' in the context of the safety information included in this  
manual or on the product itself designates:  
project engineers who are familiar with the safety guidelines concerning fire alarm and  
extinguishing systems.  
trained service engineers who are familiar with the components of fire alarm and  
extinguishing systems and the information on their operation as included in this manual.  
trained installation or service personnel with the necessary qualification for carrying out  
repairs on fire alarm and extinguishing systems or who are authorised to operate, ground  
and label electrical circuits and/or safety equipment/systems.  
Safety warnings  
The following information is given in the interest of your personal safety and to prevent  
damage to the product described in this manual and all equipment connected to it.  
Safety information and warnings for the prevention of dangers putting at risk the life and  
health of user and maintenance personnel as well as causing damage to the equipment  
itself are marked by the following pictograms. Within the context of this manual, these  
pictograms have the following meanings:  
Designates risks for man and/or machine. Non-compliance will create risks  
to man and/or machine. The level of risk is indicated by the word of warning:  
Important information on a topic or a procedure and other important  
information!  
This is an important guideline issued by VdS Schadenverhütung GmbH,  
Cologne. If the hazard alarm system is programmed in compliance with VdS,  
this section must be read very carefully and all instructions must be adhered to.  
Disassembling  
In accordance with the regulations 2002/96/EG (WEEE), after being  
disassembled, electrical and electronic equipment is taken back by the  
manufacturer for a proper disposal.  
24  
FB 798941 / 10.06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless transponder for wall mounting  
Table of contents Page  
7
General.................................................................................................................................................26  
System design information .................................................................................................................27  
Assembly..............................................................................................................................................30  
Installation .......................................................................................................................................32  
8
9
10  
10.1  
10.2  
10.3  
Connecting the power supply..............................................................................................32  
Operation as a device on the analog loop .........................................................................33  
Operation on a conventional detector zone.......................................................................34  
Connection of two detector zones for individual fire and fault alarm .............35  
Stand-alone operation .........................................................................................................36  
Relay outputs........................................................................................................................37  
Inputs.....................................................................................................................................38  
R - input .........................................................................................................38  
P - terminal.....................................................................................................38  
Interface (Schnittstelle)..................................................................................38  
Input (Eing) ....................................................................................................38  
UB...................................................................................................................38  
10.3.1  
10.4  
10.5  
10.6  
10.6.1  
10.6.2  
10.6.3  
10.6.4  
10.6.5  
11  
12  
Commissioning...............................................................................................................................39  
Analog loop...........................................................................................................................40  
Conventional detector zone input.......................................................................................41  
Important battery information ..............................................................................................42  
11.1  
11.2  
11.3  
Specifications..................................................................................................................................44  
If used properly, the “IQ8Wireless transponder (Part No. 805595)“ complies with  
the basic directives and corresponding requirements in according to the R&TTE  
Directive 1999/5/EC.  
Additional and updated Informations  
The described features, specifications and product related informations in this  
manual correspond to the date of issue (refer to date on the front page) and may  
differ due to modifications and/or amended Standards and Regulations of the  
System design, Installation and Commissioning.  
Updated documentations and informations are available for comparison on the  
EU-Community requirements  
This RF-device has been developed, manufactured and labeled in accordance to  
the requirements of the European Union (EU). If this device should be installed  
outside this EU directives and respectively in Italy (I), Norway (N), Cyprus (CY),  
Poland (PL), Slovakia (SK), Croatia (HR) or Romania (RO), the valid standards  
and requirements of the appropriate country must be observed and satisfied.  
Commissioning of this device is only permitted in accordance to the national and  
local standards and requirements.  
FB 798941 / 10.06  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless transponder for wall mounting  
7
General  
The IQ8Wireless transponder, in combination with the associated IQ8Wireless detector bases  
(Part No. 805593) and IQ8Wireless interfaces enables the wireless connection of IQ8Quad  
series fire detectors and may be used as a device on the analog loop of the IQ8Control fire  
alarm system or as a stand-alone wireless control device in fire alarm systems with  
conventional detector zones.  
The IQ8Wireless system guarantees adequate protection against electro-magnetic  
interference under normal ambient conditions. This module generates and uses electro-  
magnetic radiation and may disturb other wireless transmissions if it is not used as intended or  
not installed as described in the instructions. In principle, electro-magnetic influence of  
equipment cannot be excluded for all installations. If this module causes electro-magnetic  
interference on radios or televisions that cannot be rectified by switching the device on and off,  
the following measures can be carried out to rectify the interference:  
Change the position of the wireless components  
Create a greater gap between the module which is exhibiting signs of interference and the  
wireless components  
System requirements  
Programming software tools 8000 from Version V1.09  
To operate the IQ8Wireless transponder as a loop device of the Fire Alarm Control  
System IQ8Control, the IQ8Control operating system software Version V3.04 R001 is  
required.  
Accessories  
Part No.  
Description  
805593  
IQ8Wireless detector base for automatic Fire detectors series IQ8Quad  
(without integrated alarm device)  
805594  
805597  
805601  
805602  
805603  
805604  
805605  
IQ8Wireless Gateway automatic Fire detectors IQ8Quad  
4 Lithium batteries (type AA / 3,6V) for power supply  
IQ8Wireless universal Interface (red), without cover  
IQ8Wireless universal Interface (white), without cover  
IQ8Wireless Mounting frame for Alarm device IQ8Alarm (red + white)  
IQ8Wireless Mounting frame for automatic Fire detectors IQ8Quad (white)  
Cover for IQ8Wireless Interface 805601 und 805602 (red + white)  
For the operation of the intelligent Fire alarm detectors series IQ8Quad with  
integrated alarm device use Part No. 805602 and 805604.  
Warranty claims will not be accepted in case of damage caused by  
non-compliance with the operating instructions. The manufacturer is not liable for  
subsequent damage resulting from the above. Please study the installation  
instruction of the IQ8Wireless transponder carefully before installing.  
26  
FB 798941 / 10.06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless transponder for wall mounting  
8
System design information  
When fire alarm systems are planned and installed in the Federal Republic of Germany,  
they must comply with certain standards and guidelines, including the following:  
DIN VDE 0100  
DIN 14675  
DIN VDE 0833  
DIN EN54  
VdS Guidelines (VdS Schadenverhütung GmbH, Cologne)  
Local building authority conditions  
In principle, these requirements and specifications should also be complied with in the  
planning of fire alarm systems outside the area of validity of these standards and guidelines.  
Depending on the actual area in which the system will be used, additional national conditions  
and regulations may have to be complied with.  
Key data for the IQ8Wireless transponder:  
Max. 32 IQ8Wireless detector bases (incl. IQ8Quad fire detector) per transponder or  
Maximum 10 IQ8Wireless MCPs (incl. IQ8Wireless Interface) per transponder.  
If the IQ8Wireless transponder is connected to a conventional detector zone, all assigned  
IQ8Wireless devices form one common detector zone (refer to VdS Guidelines)  
Key data for the analog loop (fire alarm system IQ8Control)  
An IQ8Wireless transponder is a device on the analog loop and requires 1 address  
An assigned IQ8Wireless detector base (incl. IQ8Quad fire detector) requires 1 address  
An IQ8Wireless MCP (incl. IQ8Wireless Interface) requires 1 address  
Max. 127 devices (addresses) per analog loop  
Max. 10 IQ8Wireless transponders per analog loop  
Max. 20 IQ8Wireless transponders per fire alarm control panel IQ8Control C  
Max. 50 IQ8Wireless transponders per fire alarm control panel IQ8Control M  
Every automatic IQ8Quad fire detector (with IQ8Wireless detector base) or IQ8Wireless  
MCP (incl. IQ8Wireless Interface) can be configured as a separate detector zone  
Automatic fire detectors and MCPs may not be operated on one and the same  
IQ8Wireless transponder.  
FB 798941 / 10.06  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless transponder for wall mounting  
The installation location of the IQ8Wireless transponder should be chosen so that the shortest  
transmission path (wireless path) to the wireless bases can be implemented and that no  
electro-magnetic interference is to be expected. The function of the IQ8Wireless transponder  
may be seriously affected and its range reduced by interference sources or an unsuitable  
installation location:  
Electrical interference sources  
Energy/power cables  
Powerful wireless transmitters in the vicinity  
Switched-mode electronic circuits  
Computer and IT systems  
Mechanical interference sources  
Metal grating and metal gates  
Metal cabinets (cabinet units)  
Concrete ceilings and concrete walls  
Unfavourable arrangements (angles) of IQ8Wireless transponders and IQ8Wireless  
detector bases  
The IQ8Wireless transponder operates with a range up to 25 channels within the  
frequency band of 433 MHz and 868 MHz.  
Also consider temporary interference sources such as mobile phones or  
computers!  
Requirements for the environment  
The quality of the wireless transmission depends very much on the ambient temperature.  
A reduction in temperature in the monitored rooms, for example at night may have a  
negative effect on the wireless quality achieved during the day.  
Sliding gates or doors which are open during the day for operational reasons as well as  
overhead cranes may disrupt the wireless path when they are closed or in a different  
position respectively.  
To plan the wireless system the tools 8000 software contains a field strength  
measurement tool. This can be used to check the quality of the wireless link  
(field strength) between the IQ8Wireless transponder and the IQ8Wireless  
devices.  
If used properly, the “IQ8Wireless transponder (Part No. 805595)“ complies with  
the basic directives and corresponding requirements in according to the  
R&TTE Directive 1999/5/EC.  
28  
FB 798941 / 10.06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless transponder for wall mounting  
Weakening of the wireless signal  
max. 300m*  
0% to -10%  
Timber, plasterboard, leight-weight partition walls  
-5% to -35%  
Brick (or insulated partition walls)  
-30% to -90%  
Reinforced concrete wall  
-90% to -100%  
Metal, metal grating, aluminium lining  
Fig. 14: Weakening of the wireless signal in case of mechanical obstructions  
(as a percentage)  
*
Maximum range with line of sight between the IQ8Wireless detector base and the  
IQ8Wireless transponder as well as optimum technical conditions.  
FB 798941 / 10.06  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless transponder for wall mounting  
9
Assembly  
The IQ8Wireless transponder should be installed with suitable fixing material (such as wall  
plugs and screws) in the proper position on a stable wall surface with no mechanical stress of  
the housing. The mounting place location of the IQ8Wireless transponder should be chosen so  
that a good wireless link (field strength) between the transponder and the assigned  
IQ8Wireless detector bases is guaranteed. The transmission quality can be checked with the  
programming software tools 8000 version V1.09 or higher.  
172  
39  
Top  
Fig. 15: Fixing points on the back of the housing (sizes in mm)  
On the front side of the housing there are 4 LED status indicators, each with its own inscription  
field, as well as the housing screw.  
Top  
LED 1  
LED 2  
LED 3  
LED 4  
1
A
red green  
B
red green  
200  
Fig. 16:IQ8Wireless transponder in housing with display LED and aerials (sizes in mm)  
Observe that the IQ8Wireless transponder must not be installed on walls with  
metal grating or which are filled with aluminium foil-insulated glass wool and  
which could thus seriously affect the wireless communication.  
30  
FB 798941 / 10.06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless transponder for wall mounting  
Operation (green)  
LED 1  
LED 2  
Lits in normal operation  
Common fire alarm (red)  
Lits when the fire alarm of an assigned wireless device has been detected.  
The relay >common fire alarm< is activated.  
Common trouble (yellow), display not latched  
Lits when a fault message from the IQ8Wireless transponder or an assigned  
wireless device has been detected. Activation of the >common fault< relay is  
interrupted and the relay contact changes position.  
LED 3  
Initialisation (yellow)  
LED 4  
Lits during the switch-on/learning process of the IQ8Wireless transponder while the  
wireless devices are being recognised.  
Housing screw to open/close the transponder housing  
c
LED-indicators on the board  
Status indication of the Analog loop communication  
Both LED (red and green) twinkle while the data communication on the connected  
loop of the FACP IQ8Control is active.  
A
B
LED-incicator for the wireless operation mode  
red  
green  
flashes  
Normal operation mode  
All assigned wireless devices operates as required in  
the frequenzy-hopping mode.  
Off  
(2Hz)  
Normal operation with a communication fault  
At least one wireless device is out of the frequenzy-  
hopping mode and is automatically searched in the  
base channel. This fault is indicated at the FACP  
after approx. 40-60s. If the wireless device could be  
automatically found within this time the red LED goes  
out.  
ON  
flashes  
(2Hz)  
Installation mode (restricted operation)  
e.g. during field strength measurement, transponder  
or detector data assignment or while searching a  
wireless device.  
Flashes alternately  
(2Hz)  
Malfunction – Wireless mode disabled  
Wireless communication not possible Î transponder  
is defect (return to factory)  
Flashes common  
(2Hz)  
Disablement – wireless mode off  
The wireless operation mode is automatically  
disabled due to no wireless is assigned or present.  
Flashes common  
each 7 seconds  
FB 798941 / 10.06  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless transponder for wall mounting  
10  
10.1  
Installation  
Connecting the power supply  
The power supply can come from the fire alarm control panel or from an external power unit.  
To supply power to the IQ8Wireless transponder you must install a separate, protected supply  
line. The connection cable must comply with the guidelines relating to the functions of fire  
alarm systems. If several IQ8Wireless transponders are connected to a shared power supply,  
each power line must be protected individually and non-reactively, for example with the 8-fuse  
card (Part No. 382040).  
Monitoring the power supply  
The external power supply is monitored by the wireless transponder. If the IQ8Wireless  
transponder is installed as a device on the analog loop of the IQ8Control fire alarm system,  
a fault is transmitted via the loop to the fire alarm control panel where it is displayed.  
If you connect the IQ8Wireless transponder to a standard detector zone, the >Common fault  
relay< (SaS-Stör) output may be used to report faults.  
UB  
-
+
External Power supply  
UBext.  
GND  
Fault  
contact  
or  
FACP  
-
9 V.....30 V DC  
+
UBext.  
GND  
Fig. 17: Power supply connection  
A VdS-approved power unit according to EN54-4 must be connected to supply  
power to the IQ8Wireless transponder, e.g. external 12 V DC power unit with  
battery compartment (Part No. 785653) or 24 V DC design (Part No. 785655).  
32  
FB 798941 / 10.06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless transponder for wall mounting  
10.2  
Operation as a device on the analog loop  
The IQ8Wireless transponder is connected directly to the analog loop of the IQ8Control fire  
alarm control system.  
All reports from the transponder are transmitted via the analog loop to the IQ8Control fire  
alarm control panel. The assigned wireless devices can be split into individual detector zones.  
If a report is sent from a IQ8Wireless base, the detector zone and detector number of the  
IQ8Wireless base (incl. fire detector IQ8Quad) or the wireless manual call point IQ8MCP are  
displayed.  
The two relay outputs of the transponder can also be used for control functions. An external  
power supply is required to operate the transponder.  
Jumper J1 + J2 removed  
J2  
J2  
J1  
J1  
UB  
UB  
IN OUT  
+ + - -  
IN OUT  
+ + - -  
PE PE  
PE PE  
+ -  
+ -  
-
-
9 V.....30 V DC  
9 V.....30 V DC  
+
+
A+  
B+  
A-  
B-  
Fig. 18: Connecting the IQ8Wireless transponder to the analog loop (schematic diagram)  
System requirements:  
Fire alarm control panel IQ8Control C/M with appropriate software version V3.04 R001  
Analog loop module (Part No. 804382 / 784382)  
Programming software tools 8000 version V1.09 or higher  
Connection data  
External power supply 9 V DC to 30 V DC  
Jumpers J1 and J2 removed (factory setting)  
Reset time = 0.2 to 3 seconds  
FB 798941 / 10.06  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless transponder for wall mounting  
10.3  
Operation on a conventional detector zone  
The IQ8Wireless transponder can be connected to the conventional detector zone input of a  
fire alarm system via the relays. All IQ8Wireless devices form a common detector zone on this  
IQ8Wireless transponder. You cannot split these into several, different detector zones. The  
detector zone input is connected with resistor (R1) to the inversely operated >common fault<  
relay (Common fault) which is activated in quiescent mode. In case of an alarm the alarm  
resistor (R2) is switched parallel to R1 and the detector zone is triggered via the  
>common fire alarm< relay (Common fire).  
Reset  
The IQ8Wireless transponder is reset to the functional, normal status when the voltage of the  
detector zone drops below 5V for at least 60ms (e.g. by switching the respective detector zone  
e.g. no. 1 on/off). The detector zone can also be reset via an external reset button (refer to c)  
or a relay contact. In this case a voltage of 9 to 30 V DC must be switched for at least  
1 second at the input (input +/-) of the IQ8Wireless transponder.  
Jumper J1 + J2  
inserted  
J2  
Common fire  
Sa-Feuer  
Common fault  
Sa-Stör  
J1  
UB  
C
C
Eing  
+
PE  
NC NO  
R
P
NO NC  
-
-
+
R2  
R1  
-
Detector zone 1  
+
-
1
Reset  
9 V - 30 V DC  
+
Fig. 19: Connection to a conventional detector zone input (Example)  
Connection data  
External power supply 9 V DC to 30 V DC  
Detector zone voltage 9 V DC to 30 V DC  
R1 quiescent resistor (e.g. 10Kfor conventional detector zones System 8000/IQ8Control)  
R2 alarm resistor (e.g. 1Kfor conventional detector zones System 8000/IQ8Control)  
Jumpers J1 and J2 inserted (supplied with package)  
Reset time = 0.2 to 3 seconds  
Depending on the detector zone input, with this connection a fault in a single  
wireless device can lead to a fault in the entire detector zone and affect the  
detector function. In this case the fault message can be moved to a separate  
detector zone input, so that devices that are not defective remain functional.  
34  
FB 798941 / 10.06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless transponder for wall mounting  
10.3.1  
Connection of two detector zones for individual fire and fault alarm  
The application provides the separate transmission of a fault alarm (e.g. battery low message)  
and an additional fire alarm message. The fault message is non-latching and is resetted  
automatically after the cause of the fault alarm is not present anymore.  
Reset  
The IQ8Wireless transponder is reset to the functional, normal status when the voltage of the  
detector zone “Fire” drops below 5V for at least 60ms (e.g. by switching the fire zone on/off).  
The detector zone can also be reset via an external reset button (refer to c) or a relay contact.  
In this case a voltage of 9 to 30 V DC must be switched for at least 1 second at the input  
(input +/-) of the IQ8Wireless transponder.  
Jumper J1 + J2  
inserted  
J2  
Common fire  
Sa-Feuer  
Common fault  
Sa-Stör  
J1  
UB  
C
C
Eing  
+
FACP  
-
-
NC NO  
R
P
NO NC  
+
R1  
R2  
R3  
-
Detector zone  
"Fire"  
+
-
Detector zone  
"Fault"  
+
-
1
Reset  
9 V - 30 V DC  
+
Fig. 20: Wiring of two individual detector zones for fire alarm and fault (Example)  
Connection data  
External power supply 9 V DC to 30 V DC  
Detector zone voltage 9 V DC to 30 V DC  
R1 quiescent resistor (e.g. 10Kfor conventional detector zones System 8000/IQ8Control)  
R2 alarm resistor (e.g. 1Kfor conventional detector zones System 8000/IQ8Control)  
R3 fault resistor (e.g. 10Kfor conventional detector zones System 8000/IQ8Control)  
Jumpers J1 and J2 inserted (supplied with package)  
Reset time = 0.2 to 3 seconds  
FB 798941 / 10.06  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless transponder for wall mounting  
10.4  
Stand-alone operation  
In the stand-alone mode the transponder operates with no need of any further connections to  
a fire alarm system. To connect local arm devices the relay common fire (Sa-Feu) and/or  
common fault (Sa-Stör) may be used.  
A fault message may be transmitted via the common fault relay to, e.g. a supervising system  
or an authorized person.  
Reset  
To reset the transponder connect an external reset button (refer to c) or a relay contact. In  
this case a voltage of 9 to 30 V DC must be switched for at least 1 second at the input (input +/-)  
of the IQ8Wireless transponder.  
Jumper J1 + J2  
removed  
J2  
Common fire  
Sa-Feuer  
Common fault  
Sa-Stör  
J1  
UB  
C
C
IN OUT  
Eing  
+
NC NO  
R
P
NO NC  
-
-
-
-
+
+
+
-
1
Reset  
9 V DC - 30 V DC  
+
Fig. 21: Required wiring for the stand–alone operation  
Connection data  
External power supply 9 V DC to 30 V DC  
Jumper J1 and J2 removed  
Reset time = 0.2 to 3 seconds  
36  
FB 798941 / 10.06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless transponder for wall mounting  
10.5  
Relay outputs  
The transponder provides two relay outputs >common fire alarm< and >common fault<. The  
operation of the two relays cannot be changed.  
If the transponder is connected to a conventional detector zone, the two relays are connected  
and are thus no longer available for the >common fire alarm< or >common fault< switch  
functions.  
Sa-Feuer  
Sa-Stör  
C
C
NC NO  
R
P
NO NC  
external devices  
external devices  
Fig. 22: Relay contacts (quiescent mode)  
2 dry changeover contacts  
Maximum contact rating 30 V DC/1A  
Common fire alarm (Sa-Feuer)  
The relay output >Common Fire alarm< is activated when at least one assigned IQ8Wireless  
base or IQ8Wireless MCP transmits a alarm or fire alarm to this transponder.  
Common fault (Sa-Stör)  
The >common fault relay< is always activated in normal mode without fault condition. In this  
way, if the power supply fails, this relay can still send a fault alarm via the status change of the  
relay.  
The relay output >Common fault< is activated when at least one assigned IQ8Wireless base  
or IQ8Wireless MCP transmits a fault alarm to this transponder or the transponder itself  
detects a fault (e.g. power supply).  
The relay activation follows the fault alarm (not latched).  
FB 798941 / 10.06  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless transponder for wall mounting  
10.6  
Inputs  
UB  
Schnittstelle  
Eing  
+
-
-
R
P
1
2
3
4
5
6
+
Fig. 23: Position of the terminals  
10.6.1  
R - input  
Input for connecting the transponder to a standard detector zone. This input is required for the  
reset function. If the transponder is connected to the analog loop of the IQ8Control fire alarm  
system, the input must not be connected.  
10.6.2  
P - terminal  
Free terminal point  
10.6.3  
Interface (Schnittstelle)  
No function – do not connect terminals.  
This interface is for future feature extensions (e.g. direct connection of the service PC).  
10.6.4  
Input (Eing)  
Reset input for an external RESET signal. The transponder is reset by applying voltage of  
9V DC to 30V DC for at least 1 second.  
10.6.5  
UB  
Input for power supply 9 V DC to 30 V DC.  
38  
FB 798941 / 10.06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless transponder for wall mounting  
11  
Commissioning  
To start the IQ8Wireless transponder you will need the tools 8000 programming software from  
version V1.09 or higher and the panel interface (Part No. 789862) as well as a service PC.  
Start-up differs depending on whether the transponder is connected as a device on the analog  
loop or to a standard detector zone input.  
Example:  
IQ8Wireless transponder 1 recognises all the wireless bases with adequate field strength  
(coloured dark here). The tools 8000 software is used to assign the required (dark coloured)  
wireless bases to the transponder 1.  
1
1
2
2
Fig. 24: Recognised and assigned wireless bases of IQ8Wireless transponder 1  
The IQ8Wireless detector bases that are assigned to transponder 1 can no longer be  
recognised by transponder 2 when it is started up because they are already assigned to  
transponder 1. All IQ8Wireless detector bases recognised by transponder 2 (light coloured)  
can be assigned to wireless base 2.  
The assignment of the IQ8Wireless detector bases and transponders may be changed to suit  
your requirements with the tools 8000 software. When assigning, consider the quality of the  
wireless link (field strength) and the distribution of the IQ8Wireless detector bases within the  
monitored areas.  
If an IQ8Wireless transponder is switched off or looses communication to its  
assigned wireless devices during start-up, it can again be recognised by all other  
IQ8Wireless transponders – within a suitable range. During assignment the  
wireless devices can be identified by the individual serial numbers. These serial  
numbers are displayed in the tools 8000 software for each wireless device that is  
recognised. If  
a
wireless device is assigned to several IQ8Wireless  
transponders, no guarantee can be given that the system will work properly.  
To ease the commissioning procedure some helpful 3-digit trouble codes may be  
displayed at the Fire alarm control panel IQ8Control. For additional information  
and description of the trouble code refer to the manual of the FACP IQ8Control.  
For further information about programming the IQ8Wireless transponder refer to  
tools 8000 Online manual.  
FB 798941 / 10.06  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless transponder for wall mounting  
11.1  
Analog loop  
1. Connect the IQ8Wireless transponder to the analog loop of the IQ8Control fire alarm  
system and the external power supply as described in "Installation".  
2. Switch on the fire alarm control panel or the analog loop to which the IQ8Wireless  
transponder is connected. If several IQ8Wireless transponders are connected, start these  
up one after the other to prevent multiple assignment of one wireless device.  
3. Conduct a wiring recognition of the loop with the service PC and the tools 8000  
programming software. All devices on the analog loop are displayed.  
4. Click the required IQ8Wireless transponder on this analog loop to open the dialog for  
programming the wireless transponder.  
5. In the menu item “Measure signal strength” check if the quality of the wireless  
transmission between the transponder and the base is adequate.  
6. All the wireless bases that this IQ8Wireless transponder has recognised are displayed in  
menu item "Assign wireless devices“. If several IQ8Wireless transponders exist, wireless  
bases that are already assigned to other IQ8Wireless transponders are not shown.  
7. In the menu item “Assign wireless devices”, assign all required wireless bases to the  
IQ8Wireless transponder individually. The wireless devices can be assigned individually in  
individual detector zones.  
8. Start-up is complete for this wireless transponder. Leave the IQ8Wireless transponder  
switched on and start up any other IQ8Wireless transponders that you have.  
805595  
Service PC  
Panel  
Interface  
789862  
esserbus®-PLus  
Fig. 25: Commissioning Î Analog loop connection  
40  
FB 798941 / 10.06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless transponder for wall mounting  
11.2  
Conventional detector zone input  
1. Connect the external power supply to the IQ8Wireless transponder as described in  
"Installation".  
2. Connect the service PC to the terminals for the analog loop of the IQ8Wireless  
transponder via the panel interface (Part No. 789862) and start the tools 8000  
programming software.  
3. Conduct a wiring recognition with the service PC and tools 8000.  
4. Click the required IQ8Wireless transponder to open the programming dialog.  
5. In the menu item “Measure signal strength” check if the quality of the wireless  
transmission between the transponder and the base is adequate.  
6. All the IQ8Wireless bases that this IQ8Wireless transponder has recognised are displayed  
in menu item "Assign wireless devices“. If several IQ8Wireless transponders exist,  
IQ8Wireless bases that are already assigned to other IQ8Wireless transponders are not  
shown.  
7. In the menu item “Assign wireless devices“, assign all required IQ8Wireless bases to the  
IQ8Wireless transponder individually incl. menu option “Read detectors”.  
8. Remove the connection on the terminals on the analog loop of the IQ8Wireless  
transponder and disconnect the transponder for approx 5 seconds from power supply.  
9. Connect the IQ8Wireless transponder to the conventional detector zone input of the fire  
alarm system as described in “Installation”.  
10. Start-up is complete for this IQ8Wireless transponder.  
4Z/2R  
esserbus®-  
805595  
transponder  
IN OUT  
esserbus®  
+ + - -  
Panel  
Interface  
789862  
Service PC  
Conventional  
detector zone  
Fig. 26: Commissioning Î Conventional zone input  
FB 798941 / 10.06  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless transponder for wall mounting  
11.3  
Important battery information  
Battery information relating to power consumption and batteries (Art. No. 805597) for use in  
IQ8Wireless RF components  
Insert batteries into the RF devices shortly before initial operation (assigned to the RF  
transponders)! Unassigned RF devices consume approx. 4 times more power.  
Bear in mind the sufficient remaining field strength!  
Operation with low field strength causes the power consumption to be somewhat higher.  
Similar RF devices which were put into operation at the same time may subsequently  
register low battery voltage (batt. < 30) on the FACP after different running times.  
The probability of interferences (e.g. caused by electromagnetic pollution or alternating  
field strength) rises very high relating to the reduced field strength. If the wireless  
transmission is interrupted and a wireless devices must leave the frequency hopping  
mode, it is operated in the basic channels until the assigned transponder is able to take  
this device into the frequency hopping mode again. In this mode the current consumption  
may increase up to 4 times higher.  
How often a RF transponder has to search for one of its RF devices in the base channel  
can be determined using the Service PC on the >disturbance< counter in the programming  
software tools 8000.  
If the 12/24 V DC power supply to a RF transponder should malfunction, the radio  
operation of the transponder terminates and all the assigned RF devices search in the  
base channel for this RF transponder. This causes the RF devices’ power consumption to  
be up to approx. 4 times higher.  
In the case of an alarm, the detectors in the RF devices consume somewhat more power.  
In an uncharged state, the approved batteries (Art. No. 805597) have a very low self-  
discharge rate (1 % annually @ 25 °C ± 10 °C). Storage outside this temperature range  
causes the self-discharge rate to increase. The nominal capacity of the batteries  
decreases, for example, at low temperatures and is 20-30 % lower during operation near to  
the freezing point.  
Due to “passivation effects” batteries which are more than 3 years old should no longer be  
used. Batteries are labelled accordingly. e.g. F.02.277.E  
F
= France  
02  
277  
E
= in the year 2002  
= produced on the 277th day  
= charge  
For initial operation, the batteries are inserted and then charged automatically for a short  
time and with a very high current. In rare cases, this may cause low battery voltage  
(batt. < 30) to be immediately displayed on the FACP.  
Remedy: Activate the RF devices once more using the FACP.  
For functioning devices, the battery voltage is checked approx. every 12 hours  
automatically and approx. 2 minutes after insertion of the batteries/after activation (detector  
zone/detector) of a RF device.  
42  
FB 798941 / 10.06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless transponder for wall mounting  
Do not touch the battery poles or contacts of the RF devices with bare fingers! A layer of  
grease causes transfer resistance to build up between the batteries and contacts. This  
transfer resistance may lead to the FACP prematurely or incorrectly displaying low battery  
voltage (batt. < 30).  
Improper storage of the RF devices and batteries may be the cause of such transfer  
resistance (e.g. due to corrosion). If necessary, clean contacts before inserting the  
batteries (e.g. with isopropanol solution).  
Only change the batteries as a set (4 items) in order to ensure an equal charge. The  
registered low battery voltage (batt. < 30) on the FACP always relates to the battery with  
the smallest capacity.  
For RF devices which register low battery voltage after a long operating time, the  
malfunction may be repaired during inspection by agitating the batteries used for a short  
amount of time (a few hours). When the RF device is activated, no “low battery voltage“  
message appears. Completely replace the set of batteries for the corresponding RF device!  
FB 798941 / 10.06  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless transponder for wall mounting  
12  
Specifications  
Power supply range  
:
:
:
:
:
:
:
9V DC to 30 V DC  
Operating voltage  
Contact rating  
12 V DC or 24 V DC  
max. 30V DC / 1 A  
Quiescent current  
Alarm current  
approx. 17 mA @ 12 V DC  
approx. 18 mA @ 12 V DC  
433/868 MHz  
Frequency band  
Range of transmission path  
up to max. 300m  
(dependent on mounting location and ambient conditions)  
Ambient temperature  
Storage temperature  
Protection rating  
Housing  
:
:
:
:
:
:
:
:
-5 °C to +55 °C  
-10 °C to +60 °C  
IP 42  
PC/ASA plastic  
Colour  
white, similar RAL 9010  
approx. 250g  
Weight  
Dimension  
200 x 280 x 39 (mm) - including aerial  
G 205113  
VdS approval  
44  
FB 798941 / 10.06  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IQ8Wireless transponder for wall mounting  
Notes  
FB 798941 / 10.06  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Novar GmbH a Honeywell Company  
Dieselstraße 2, D-41469 Neuss  
Internet: www.novar.de  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Grizzly Lathe G9730 User Manual
Haier Air Conditioner 0010552537 User Manual
Hamilton Beach Hot Beverage Maker 40996 User Manual
Hayter Mowers Lawn Mower CODE131B User Manual
Hearth and Home Technologies Indoor Fireplace 36EBU User Manual
HP Hewlett Packard Laptop Docking Station XB4000 User Manual
HP Hewlett Packard Network Cables LH4r User Manual
HP Hewlett Packard Switch 331404 008 User Manual
Huawei Switch M866 User Manual
Husqvarna Lawn Mower 14 Pro User Manual