Honeywell Burner R8182D User Manual

R8182D,E,F,H,J Combination  
Protectorelay™ and Hydronic  
Heating Controls  
PRODUCT DATA  
FEATURES  
Depending on model, these single unit devices provide  
combinations of high limit, low limit, and circulator  
control.  
All models use a 24V thermostat and C554A Cadmium  
Sulfide Flame Detector.  
R8182D,E,H and J have auxiliary terminals ZC and ZR  
for circulator zone control. Additional zones require a  
separate 24V thermostat and R845 Relay.  
All models have capability for zone control with zone  
valves. Each additional zone requires a separate 24V  
thermostat and a V8043 or V8044 Zone Valve.  
Ideal for packaged boiler systems requiring compact,  
multipurpose controls.  
R8182D,E,F mode  
R8182H,J models mount on a 4 x 4 inch junction box,  
and have a 5 ft (1.5m) armored capillary for remote  
sensor location.  
Aquastat® Controller section is field replaceable.  
Oil burner circuit includes an improved safety shutoff  
in the event the burner fails to start.  
Flame failure during the running cycle results in a  
45 second attempt to restart. If unsuccessful, safety  
shutoff occurs, requiring manual reset before burner  
can be restarted.  
GENERAL  
The R8182 is a combination Protectorelay™ intermittent  
ignition oil burner primary and immersion type Aquastat®  
controller for oil-fired, hydronic heating systems.  
Contents  
Ordering Information ........................................................  
2
® U.S. Registered Trademark  
Copyright © 2002 Honeywell • All Rights Reserved  
68- 0105- 2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
R8182D,E,F,H,J COMBINATION PROTECTORELAY™ AND HYDRONIC HEATING CONTROLS  
KNOCKOUTS  
FOR 1/2 IN.  
(13 MM)  
CONDUIT (5)  
KNOCKOUTS  
FOR 1/2 IN. (13 MM)  
CONDUIT (5)  
2-7/16  
(62)  
1-5/16  
(33)  
3-3/8 (86)  
1/2 (13)  
1
1
7/8  
(22)  
VERTICAL  
MOUNT  
ONLY  
7-1/8  
(181)  
3-7/16  
(87)  
7-1/8  
(181)  
HORIZONTIAL  
MOUNT ONLY  
3-9/16  
(91)  
3-1/4 (83)  
M4517  
3/16  
(5)  
5-1/4 (133)  
VERTICAL MOUNT SHOWN.  
3-7/16 (87)  
5-1/4 (133)  
1
1
SIDE MOUNTED HINGE SHOWN.  
M4518  
Fig. 1. R8182D,E,F installation dimensions in in. (mm).  
Fig. 2. R8182H,J installation dimensions in in. (mm).  
Thermostat Anticipator Setting: 0.2A for R8182, 0.4A for  
each R845A Switching Relay used.  
Maximum Ambient Temperature (at Element): 250°F  
R8182D,E,F  
(121°C).  
FITS BOILER TAPPED HOLE  
CONTROL MOUNT  
1/2 OR 3/4 NPT  
Maximum Pressure Rating:  
200 psi (1379 kPa) on immersion well.  
100 psi (689.5 kPa) direct immersion.  
Internal Views: Refer to Fig. 4 through 8.  
Well Insertion Length: 3-3/8 in. (86 mm).  
INSERTION LENGTH  
3-3/8 IN. (86 MM)  
INSULATION LENGTH  
1-1/2 OR 3 IN.  
(38 OR 76 MM)  
Immersion Well Dimensions (Order Well Separately):  
Refer to Fig. 3.  
R8182H,J  
FITS BOILER TAPPED HOLE  
1/2 OR 3/4 NPT  
SETSCREW  
Aquastat® Assembly Repair Parts: 125026AAE Aquastat®  
Assembly: Replaces R8182D,F Sensing Bulb.  
Replacement Well Assemblies: Refer to form 68-0040,  
Wells and Fittings for Temperature Controllers, for part  
numbers and descriptions.  
INSERTION LENGTH  
3-3/8 IN. (86 MM)  
INSULATION LENGTH  
1-1/2 IN. (38 MM)  
M4530  
Fig. 3. Approximate immersion well dimensions.  
Device  
R8182D  
Description  
Part Number  
1-1/2 in. (38 mm) insulation, horizontal or vertical; 3 in. (76 mm) insulation horizontal.  
125026AAD  
1250266AAE  
123726AV  
3 in. (76 mm) insulation, vertical.  
R8182E  
1-1/2 in. (38 mm) insulation, horizontal or vertical; 3 in. (76 mm) insulation horizontal.  
3 in. (76 mm) insulation, vertical.  
123726AW  
3
68-0105—2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R8182D,E,F,H,J COMBINATION PROTECTORELAY™ AND HYDRONIC HEATING CONTROLS  
Device  
R8182F  
Description  
1-1/2 in. (38 mm) insulation, horizontal or vertical; 3 in. (76 mm) insulation horizontal.  
3 in. (76 mm) insulation, vertical.  
Part Number  
125017AAB  
125017AAC  
125026AAJ  
123726AT  
R8182H  
R8182J  
1-1/2 in. (38 mm) insulation.  
Dial Stop: For restricting range, part no. 4074BRR for  
R8182D,F,H.  
SAFETY SWITCH  
RESET BUTTON  
GROUNDING SCREW  
Optional Specifications:  
R8182D,E,F: Case with long dimension horizontal.  
R8182H,J: End mounted hinge.  
TRANSFORMER  
FOR THERMOSTAT  
CIRCUIT  
AQUASTAT SWITCH  
SAFETY SWITCH  
RESET BUTTON  
GROUNDING SCREW  
TRANSFORMER  
FOR THERMOSTAT  
CIRCUIT  
CIRCULATOR  
RELAY (1K)  
DIFFERENTIAL  
SETTING  
BURNER MOTOR  
AND IGNITION  
RELAY (2K)  
CIRCULATOR  
RELAY (1K)  
BURNER MOTOR  
AND IGNITION  
RELAY (2K)  
VOLTAGE BARRIER  
LOW LIMIT  
SETTING  
TRANSFORMER FOR  
CAD CELL CIRCUIT  
HIGH LIMIT  
SETTING  
M4532  
VOLTAGE BARRIER  
Fig. 5. Internal view of R8182E.  
HIGH LIMIT  
SETTING  
TRANSFORMER FOR  
CAD CELL CIRCUIT  
GROUNDING SCREW  
M4525  
SAFETY SWITCH  
RESET BUTTON  
Fig. 4. Internal view of R8182D.  
HIGH LIMIT  
SETTING  
BURNER MOTOR  
AND IGNITION  
RELAY (2K)  
LOW LIMIT  
SETTING  
TRANSFORMER FOR  
CAD CELL CIRCUIT  
VOLTAGE BARRIER  
M4515  
Fig. 6. Internal view of R8182F.  
68-0105—2  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
R8182D,E,F,H,J COMBINATION PROTECTORELAY™ AND HYDRONIC HEATING CONTROLS  
INSTALLATION  
SAFETY SWITCH  
RESET BUTTON  
TRANSFORMER  
FOR THERMOSTAT  
WARNING  
CIRCUIT  
Explosion Hazard.  
Can cause severe injury, death or property  
damage.  
This product is intended for use only in systems with a  
DIFFERENTIAL  
SETTING  
pressure relief valve.  
CIRCULATOR  
RELAY (1K)  
When Installing this Product…  
1. Read these instructions carefully. Failure to follow them  
could damage the product or cause a hazardous  
BURNER MOTOR  
condition.  
AND IGNITION  
RELAY (2K)  
2. Check the ratings given in these instructions and on the  
LOW LIMIT  
SETTING  
product to be sure the product is suitable for your  
application.  
3. The installer must be a trained, experienced service  
VOLTAGE BARRIER  
technician.  
4. After completing installation, use these instructions to  
check product operation.  
TRANSFORMER FOR  
CAD CELL CIRCUIT  
HIGH LIMIT  
SETTING  
CAD CELL  
M4524  
LEADS (YELLOW)  
WARNING  
Explosion or Electrical Shock Hazard.  
Can cause severe injury, death or property  
damage.  
Fig. 7. Internal view of R8182H.  
1. Disconnect the power supply before beginning  
installation to prevent electrical shock or equipment  
damage.  
SAFETY SWITCH  
RESET BUTTON  
TRANSFORMER  
FOR THERMOSTAT  
CIRCUIT  
2. Be sure that combustion chamber is clear of oil or  
oil vapor before starting burner.  
3. Be sure that the ambient temperature at the  
element will not exceed 250°F (121°C).  
AQUASTAT SWITCH  
IMPORTANT  
2K RELAY  
1K RELAY  
Be sure that the sensing bulb fits snugly inside the  
immersion well and that the sensing bulb rests  
against the bottom of the immersion well. Refer to  
Fig. 9.  
VOLTAGE BARRIER  
TRANSFORMER  
FOR CAD CELL  
CIRCUIT  
Mounting the R8182  
1. Disconnect the power supply.  
2. Drain all water from the boiler.  
3. Generally, boilers are equipped with a tapping that  
allows horizontal mounting of the immersion well where  
average temperature boiler water circulates freely. If no  
tapping is provided, prepare one.  
HIGH LIMIT  
SETTING  
4. Install the immersion well or compression fitting  
(ordered separately) by threading the immersion well  
into the tapped hole.  
CAD CELL LEADS (YELLOW)  
M4531  
5. For R8182D,E,F models:  
Fig. 8. Internal view of R8182J.  
a. Loosen the immersion well clamp screw on the side  
of the R8182 case.  
b. Insert the bulb into the immersion well until it  
bottoms.  
c. If necessary, bend the capillary tube to hold the bulb  
against the bottom of the immersion well.  
5
68-0105—2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
R8182D,E,F,H,J COMBINATION PROTECTORELAY™ AND HYDRONIC HEATING CONTROLS  
NOTE: Do not make sharp bends in the tubing. A sharp  
bend can break the tubing and cause a loss of fill. In  
models with an adjustable tubing length, pull the  
extra tubing out of the controller case.  
NOTE: Do not make sharp turns while bending the capillary  
tubing. In models with an adjustable tubing length,  
pull the extra tubing out of the controller case.  
7. Apply the heat-conductive compound into the  
immersion well (if necessary).  
d. Fit the controller case onto the immersion well so  
that the immersion well clamp slides over the flange  
of the immersion well.  
a. Fold the plastic bag of heat-conductive compound  
lengthwise and twist it gently.  
e. Securely tighten the immersion well clamp screw.  
6. For R8182H,J models:  
b. Cut off the end of the plastic bag and work the open  
end of the bag all the way into the immersion well.  
c. Slowly pull the bag out of the immersion well while  
squeezing it firmly to evenly distribute the  
heat-conductive compound.  
a. Loosen the screw holding the hinged backplate to  
the controller case and swing the backplate away  
from the controller case.  
b. Screw the backplate to a 4 by 4 inch junction box.  
c. Insert the bulb into the immersion well until it  
bottoms.  
8. Wipe off any excess grease and tighten the set screw  
against the adapter.  
If the existing immersion well is not usable, remove the  
existing immersion well and order a new one using form  
68-0040, Wells and Fittings for Temperature Controllers.  
d. If necessary, bend the capillary tube to hold the bulb  
against the bottom of the immersion well.  
NOTE: Do not make sharp bends in the tubing. A sharp  
bend can break the tubing and cause a loss of fill. In  
models with an adjustable tubing length, pull the  
extra tubing out of the controller case.  
1. Disconnect the power supply.  
2. Drain all water from the boiler.  
3. Install the new immersion well by threading it into the  
threaded hole.  
4. Loosen the immersion well clamp screw. See Fig. 9.  
5. Insert the sensing bulb into the immersion well and  
bend the capillary tubing, if necessary, to hold the  
sensing bulb against the bottom of the immersion well.  
e. Tighten the immersion well screw over the brass  
collar.  
f. After wiring, swing control against the backplate and  
refasten with the screw.  
7. Refill the boiler and check for water leakage.  
NOTE: Do not make sharp turns while bending the capillary  
tubing. In models with an adjustable tubing length,  
pull the extra tubing out of the controller case.  
Mounting the R8182D TRADELINE®  
If the existing immersion well does not fit the R8182D  
immersion well clamp, use a 1249094 immersion well adapter  
(order separately; see form 68-0040, Wells and Fittings for  
Temperature Controllers).  
6. Apply heat-conductive compound into the immersion  
well (if necessary).  
a. Fold the plastic bag of heat-conductive compound  
lengthwise and twist it gently.  
b. Cut off the end of the plastic bag and work the open  
end of the bag all the way into the immersion well.  
c. Slowly pull the bag out of the immersion well while  
squeezing it firmly to evenly distribute the  
heat-conductive compound.  
1. Disconnect the power supply.  
2. Drain all water from the boiler.  
3. Fasten the R8182D immersion well clamp to the flange  
on the immersion well adapter. Refer to Fig. 9.  
4. Place the adapter on the capillary tube.  
5. Put the adapter end into the hole in the controller case  
and tighten the clamp screw.  
6. Insert the sensing bulb into the immersion well and  
bend the capillary tubing, if necessary, to hold the  
sensing bulb against the bottom of the immersion well.  
7. Be sure the immersion well fits the hole in the controller  
case.  
8. Position the immersion well clamp snugly over the  
immersion well flange. Securely tighten the clamp  
screw.  
9. Refill the boiler and check for water leakage.  
68-0105—2  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
R8182D,E,F,H,J COMBINATION PROTECTORELAY™ AND HYDRONIC HEATING CONTROLS  
BACK OF  
CONTROLLER  
CASE  
IMMERSION  
WELL CLAMP  
CONTROLLER  
CASE  
BOILER  
IMMERSION  
WELL CLAMP  
1
IMMERSION  
WELL SPUD  
ADAPTER  
IMMERSION  
ADAPTER  
WELL CLAMP  
SCREW  
OLD IMMERSION  
WELL ASSEMBLY  
SENSING  
BULB  
(A)  
(D)  
(C)  
(B)  
2
HEAT-CONDUCTIVE COMPOUND  
1
2
BEND THE CAPILLARY TUBE TO HOLD THE SENSING BULB IN GOOD  
THERMAL CONTACT WITH THE IMMERSION WELL AT POINTS (A) AND (B).  
CAPILLARY  
TUBE  
ASSURE THAT CAPILLARY TUBE FITS FREELY IN THE ADAPTER SO THE  
TENSION OF THE CAPILLARY TUBE AT POINT (C) HOLDS THE SENSING  
BULB IN GOOD THERMAL CONTACT WITH THE IMMERSION WELL AT POINT (D).  
M8830  
SETSCREW  
SHORT TUBE  
FITS IN CENTRAL  
RECESS OF ADAPTER  
IMMERSION  
WELL CLAMP SCREW  
Fig. 9. Positioning the sensing bulb in the immersion well.  
Method 1  
WIRING  
1. Strip 7/16 in. of insulation from the wire end.  
2. Wrap the wire 3/4 of the distance around the screw as  
IMPORTANT  
shown in method 1.  
Use Underwriters Laboratories Inc. listed connectors  
when making external circuit connections to the  
orange and white line voltage burner and ignition  
leadwires of the R8182H,J.  
3. Using a standard, flat-headed screwdriver, tighten the  
screw until the wipe is snugly in contact with the screw  
and contact plate.  
4. Tighten the screw pin an additional one-half turn.  
WARNING  
Can cause severe injury, death or property  
damage.  
Disconnect power supply before wiring to prevent  
electrical shock or equipment damage.  
Method 2  
Electrical Shock Hazard.  
1. Strip 5/16 in. of insulation from the wire end.  
2. Insert wire beneath the screw as shown in method 2.  
3. Using a standard, flat-heat screwdriver, tighten the  
screw until the wire is snugly in contact with the screw  
and contact plate.  
4. Tighten the screw an additional one-half turn.  
All wiring must comply with local codes, regulations, and  
ordinances.  
NOTE: Do not use a push-type ratchet screwdriver.  
IMPORTANT  
The TRADELINE® R8182D,H can be converted to replace an  
R8182B,C,E,F or a White Rodgers 6C92-2 or 6C92-3. When  
replacing a White Rodgers model, the immersion well must  
also be replaced. Refer to Fig. 10 for Aquastat® limit  
connections necessary for each R8182D conversion.  
Terminals on the R8182 are approved for copper  
wire only.  
Follow the wiring instructions furnished by the appliance  
manufacturer, if available, or refer to Fig. 11 through 17. For  
wiring multiple zoning systems, refer to Fig. 16 and 17.  
To release the wires from the R8182, insert a screwdriver into  
the rectangular hole adjacent to the wire, push inward to  
release the locking-grip on the wire, and pull the wire out of  
the terminal hole.  
The R8182 is equipped with special wiring terminals. Wires  
can be wrapped around the terminal screw or inserted from  
the side.  
To reinsert the wire into a new terminal hole, simply push the  
wire into the new slot.  
7
68-0105—2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
R8182D,E,F,H,J COMBINATION PROTECTORELAY™ AND HYDRONIC HEATING CONTROLS  
USING THE TRADELINE® R8182D  
TO REPLACE R8182F:  
USING THE TRADELINE® R8182D  
TO REPLACE R8182B,E OR  
WHITE RODGERS 6C92:  
1. REMOVE BLUE WIRE FROM  
THIS TERMINAL AND INSULATE  
END TO PREVENT CONTACT.  
1. REMOVE WHITE ABD BLACK  
LEADS FROM THEIR TERMINAL  
AND CONNECT WITH A  
2. REMOVE OTHER BLUE WIRE  
FROM THIS TERMINAL AND  
CONNECT AS SHOWN BELOW.  
SODDERLESS CONNECTOR.  
TO USE TRADELINE® R8182H  
TO REPLACE R8182J:  
3. CONNECT CIRCULATOR TO  
ZC AND C2.  
1. REMOVE RED AND WHITE  
LEADS FROM THEIR TERMINALS  
AND CONNECT WITH A  
BLUE  
WHITE  
SOLDERLESS CONNECTOR.  
BLUE  
BLUE  
COMPLETED  
WIRING TO  
REPLACE  
R8182C,F  
COMPLETED WIRING  
TO REPLACE  
R8182B,E AND  
L
O
H
I
WHITE RODGERS 6C92  
L
O
H
I
BLACK  
BLACK  
YELLOW  
OR RED  
M4526  
YELLOW  
Fig. 10. Converting TRADELINE® R8182D,H to replace other controls.  
68-0105—2  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
R8182D,E,F,H,J COMBINATION PROTECTORELAY™ AND HYDRONIC HEATING CONTROLS  
1
1
L1  
(HOT)  
L1  
L2  
L2  
2
(HOT)  
R8182D  
BLUE  
R8182E  
2K2  
2
4
1
G
HIGH LIMIT  
R
1
2
G
3
1K2  
TO OIL  
BURNER  
AND  
ZR  
ZR  
B
B1  
HIGH LIMIT  
R
1K2  
2K1  
BLUE  
3
TO OIL  
BURNER  
AND  
IGNITION  
B
B1  
B2  
4
C2  
B
R
TO WATER  
IGNITION  
LOW  
CIRCULATOR  
B2  
C2  
C1  
ZC  
LIMIT  
TO WATER  
CIRCULATOR  
1K1  
WHITE  
2
W
C1  
ZC  
1K1  
S.SW  
CONTACTS  
CIRCULATOR  
2K1  
2K  
SAFETY  
SWITCH  
HEATER  
S.SW  
CONTACTS  
2K2  
TRIAC  
1K  
R1  
BILATERAL  
SWITCH  
2K  
SAFETY  
SWITCH  
HEATER  
R2  
C1  
TRIAC  
T
T
F
F
1K  
R1  
BILATERAL  
SWITCH  
R2  
24 VOLT  
THERMOSTAT  
C1  
C554A  
T
T
F
F
120 VAC POWER SUPPLY. PROVIDE DISCONNECT MEANS AND  
OVERLOAD PROTECTION AS REQUIRED.  
1
2
CONTROL CASE MUST BE CONNECTED TO EARTH GROUND.  
24 VOLT  
THERMOSTAT  
USE GROUNDING SCREW PROVIDED.  
C554A  
M4527  
120 VAC POWER SUPPLY. PROVIDE DISCONNECT MEANS AND  
OVERLOAD PROTECTION AS REQUIRED.  
1
2
Fig. 12. R8182E internal schematic and wiring diagram.  
WHEN THE BLACK AND WHITE WIRES ON THE TRADELINE® R8182D  
AQUASTAT® CONTROLLER ASSEMBLY ARE DISCONNECTED FROM  
THE CIRCULATOR SWITCH AND ARE INTERCONNECTED, LOW LIMIT  
AND CIRCULATOR CONTROL ARE BYPASSED. CIRCULATOR  
OPERATES WITHY THEROMSTAT ONLY.  
3
4
TO REPLACE R8182C,F, REMOVE BLUE WIRE AND INSULATE END.  
DISCONNECT THE THE OTHER BLUE WIRE AT 4 AND WIRE TO B  
AT 3. WHEN CIRCULATOR IS CONNECTED BETWEEN ZC AND C2,  
LOW LIMIT FUNCTION IS REMOVED AND CIRCULATOR OPERATES  
WITH CIRCULATOR CONTROL (R TO W) ONLY.  
CONTROL CASE MUST BE CONNECTED TO EARTH GROUND.  
USE GROUNDING SCREW PROVIDED.  
M4519  
Fig. 11. R8182D internal schematic and wiring diagram.  
9
68-0105—2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R8182D,E,F,H,J COMBINATION PROTECTORELAY™ AND HYDRONIC HEATING CONTROLS  
1
1
L1  
L1  
L2  
2
L2  
(HOT)  
(HOT)  
R8182H  
R8182F  
2
1
1
2
G
ZR  
HIGH LIMIT  
R
1K2  
2K1  
ORANGE  
TO OIL  
BURNER  
AND  
JUMPER  
B
R
B
R
W
C1  
B1  
TO WATER  
CIRCULATOR  
B
R
WHITE  
IGNITION  
HIGH  
LIMIT  
LOW  
LIMIT  
CIRCULATOR  
CONTROL  
C2  
B2  
TO  
BURNER  
AND  
1K1  
W
C1  
C2  
ZC  
TO WATER  
CIRCULATOR  
IGNITION  
CIRCULATOR  
2K2  
SAFETY  
SWITCH  
CONTACTS  
S.SW  
CONTACTS  
2K1  
SAFETY  
T
SWITCH  
HEATER  
2K2  
TRIAC  
2K  
T
24 VOLT  
THERMOSTAT  
2K  
SAFETY  
SWITCH  
HEATER  
BILATERAL  
SWITCH  
R1  
TRIAC  
1K  
R1  
R2  
C1  
BILATERAL  
SWITCH  
F
F
T
T
R2  
C1  
C554A  
120 VAC POWER SUPPLY. PROVIDE DISCONNECT MEANS AND  
OVERLOAD PROTECTION AS REQUIRED.  
1
2
C554A  
24 VOLT  
THERMOSTAT  
CONTROL CASE MUST BE CONNECTED TO EARTH GROUND.  
USE GROUNDING SCREW PROVIDED.  
M4528  
120 VAC POWER SUPPLY. PROVIDE DISCONNECT MEANS AND  
1
OVERLOAD PROTECTION AS REQUIRED.  
M4520  
Fig. 13. R8182F internal schematic and wiring diagram.  
Fig. 14. R8182H internal schematic and wiring diagram.  
68-0105—2  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R8182D,E,F,H,J COMBINATION PROTECTORELAY™ AND HYDRONIC HEATING CONTROLS  
24 VOLT  
24 VOLT  
24 VOLT  
1
THERMOSTAT THERMOSTAT THERMOSTAT  
L1  
(HOT)  
L2  
2
R8182J  
4
1
L1  
HIGH LIMIT  
(HOT)  
TO OIL  
BURNER  
AND  
ORANGE  
L2  
1
ZR  
ZC  
B
R
1K2  
2K2  
WHITE  
IGNITION  
C1  
C2  
TO WATER  
CIRCULATOR  
5
3
5
5
3
1K1  
L1  
L2  
3
S.SW  
CONTACTS  
T
T
B1  
TO OIL  
BURNER  
AND  
IGNITION  
B2  
C2  
2K1  
2
C1  
2K  
SAFETY  
SWITCH  
HEATER  
TRIAC  
1K  
R1  
BILATERAL  
SWITCH  
CIRCULATOR  
1
2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD  
PROTECTION AS REQUIRED.  
R2  
C1  
T
T
F
F
R8182H AND J HAVE WHITE AND ORANGE LEADWIRES FOR OIL  
BURNER AND IGNITION CONNECTIONS.  
3
4
RED LEADWIRES PROVIDED ONLY ON MODLES WITH END SWITCH.  
CHOOSE AT72, AT87, OR AT88 TRANSFORMER TO MATCH  
MAXIMUM SYSTEM LOAD.  
5
USE V8043 OR V8044 ZONE VALVES WITH AUXILIARY END  
SWITCH ONLY.  
24 VOLT  
THERMOSTAT  
M4522  
C554A  
120 VAC POWER SUPPLY. PROVIDE DISCONNECT MEANS  
1
Fig. 16. R8182D,E,F,H and J in a typical zoning  
application using zone valves.  
AND OVERLOAD PROTECTION AS REQUIRED.  
M4529  
Fig. 15. R8182J internal schematic and wiring diagram.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
68-0105—2  
R8182D,E,F,H,J COMBINATION PROTECTORELAY™ AND HYDRONIC HEATING CONTROLS  
L1  
L2  
(HOT)  
6
1
ZONE 2  
THERMOSTAT  
R845A  
SWITCHING  
RELAY ZONE 2  
R8182D  
1
2
G
BLUE  
1K  
3
ZR  
HIGH LIMIT  
R
5
3
T
1K2  
2K1  
4
TO OIL  
BURNER  
AND  
B
B1  
B
R
1K1  
T
1K2  
IGNITION  
LOW  
LIMIT  
B2  
C2  
TO WATER  
CIRCULATOR  
W
C1  
ZC  
1K1  
CIRCULATOR  
5
2
6
4
1
S.SW  
CONTACTS  
ZONE 2  
CIRCULATOR  
2K2  
2K  
SAFETY  
SWITCH  
HEATER  
TO ADDITIONAL  
ZONES 3, 4, ETC.  
120 VAC POWER SUPPLY. PROVIDE DISCONNECT  
MEANS AND OVERLOAD PROTECTION AS REQUIRED.  
1
TRIAC  
1K  
R1  
2
3
4
THERMOSTAT HEAT ANTICIPATOR SETTING, 0.2 AMP FOR R8182D.  
THERMOSTAT HEAT ANTICIPATOR SETTING, 0.4 AMP FOR R845A.  
BILATERAL  
SWITCH  
CONTROL CASE MUST BE CONNECTED TO EARTH  
GROUND. USE GROUNDING SCREW PROVIDED.  
R2  
C1  
T
T
F
F
R8182E,H,J CONNECTIONS FROM ZC AND ZR ARE IDENTICAL  
FOR MULTIPLE CIRULATOR ZONING APPLICAITON.  
5
6
2
24 VOLT  
THERMOSTAT  
EACH ADDITIONAL ZONE REQUIRES A SEPARATE,  
FIELD-ADDED 24V THERMOSTAT AND R845 RELAY.  
C554A  
M4521  
Fig. 17. R8182D and R845A in a typical multiple circulator zoning application.  
R8182F  
OPERATION  
The thermostat call for heat pulls in relay 2K to turn on the  
burner. When the cadmium sulfide the flame detector sees  
flame, safety switch the heater circuit is bypassed. The  
circulator is independent of the thermostat circuit, being  
controlled only by the Aquastat¨ limit switch. See Fig. 13, 17  
and 20.  
R8182D  
A call for heat by the thermostat pulls in relay 1K, which  
energizes the safety switch circuit and relay 2K to turn on the  
burner. Safety switch starts to heat. If burner ignites within  
safety switch timing, the cadmium sulfide flame detector sees  
flame and the safety switch heater circuit is bypassed. The  
burner operates until the call for heat is satisfied. The  
circulator operates when relay 1K pulls in only if R to W is  
made in the Aquastat¨ limit.  
R8182H  
A call for heat by the thermostat pulls in relay 1K, which  
energizes the safety switch circuit and relay 2K to turn on the  
burner. The safety switch starts to heat. If the burner ignites  
within the safety switch timing, the cadmium sulfide flame  
detector sees the flame and the safety switch heater circuit is  
bypassed. The burner shuts Off when a call for heat is  
satisfied. The circulator operates when relay 1K pulls in only if  
R to W in the Aquastat¨ limit is made.  
When R to B (low limit) is made by a drop in water  
temperature, it acts as a call for heat, pulling in relay 2K to  
turn on the burner. The circulator cannot operate. See Fig. 11,  
16, 17 and 19.  
R8182E  
When R to B (low limit) is made by a drop in water  
temperature, it acts as a call for heat, pulling in relay 2K to  
turn on the burner. The circulator cannot operate. See Fig. 14,  
16, 17 and 18.  
The burner and circulator operate whenever the thermostat  
calls for heat. Relay 2K pulls in. When the cadmium sulfide  
flame detector sees flame, the safety switch heater circuit is  
bypassed, and 2K is held in through 2K1. If temperature rises  
to a high limit setpoint, R to B breaks, shutting off the burner.  
The circulator continues operation under the thermostat  
direction. See Fig. 12, 16, 17 and 20.  
68-0105—2  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
R8182D,E,F,H,J COMBINATION PROTECTORELAY™ AND HYDRONIC HEATING CONTROLS  
R8182J  
The burner and circulator operate whenever the thermostat  
calls for heat. Relay 2K pulls in. When the cadmium sulfide  
flame detector sees flame, the safety switch heater circuit is  
bypassed, and 2K is held in through 2K1. If temperature rises  
to a high limit setpoint, R to B breaks, shutting off the burner.  
The circulator continues operation under direction of the  
thermostat. See Fig. 15, 16, 17 and 19.  
SWITCH BREAKS ON  
TEMPERATURE RISE.  
BURNER TURNS OFF.  
CIRCULATOR OPERATES  
ON A CALL FOR HEAT.  
HIGH LIMIT  
SETTING  
SWITCH MAKES ON  
TEMPERATURE FALL.  
BURNER OPERATES ON A  
CALL FOR HEAT.  
Multizone Control  
SWITCH MAKES R-W  
AND BREAKS R-B ON  
TEMPERATURE RISE.  
In all multizone applications, a call for heat in any zone  
energizes the safety switch circuit and relay 2K pulls in. If the  
burner ignites within the safety switch timing, the cadmium  
sulfide flame detector sees flame and the safety switch heater  
is bypassed.  
LOW LIMIT  
AND  
CIRCULATOR  
SETTING  
1
SWITCH MAKES R-W  
AND BREAKS R-B ON  
TEMPERATURE RISE.  
SWITCH MAKES R-B AND  
BREAKS R-W ON  
TEMPERATURE FALL.  
BURNER IS ON TO  
MAINTAIN MINIMUM  
WATER TEMPERATURE.  
CIRCULATOR IS OFF.  
In all multizone applications with R8182D and H, the low limit  
control in the Aquastat® limit acts independently to turn on the  
main burner on a drop in water temperature. When R to B (low  
limit) is made, relay 2K pulls in to turn on the main burner, the  
same as for single-zone application.  
1
WHEN WATER REACHES PROPER TEMPERATURE, THE BURNER  
SHUTS OFF OR THE CIRCULATOR PUMP STARTS (WHEN CALLING  
Zone Circulator Control with R8182D,H  
FOR HEAT).  
M1523  
The relay for each zone is connected to the Aquastat® limit  
through terminals ZC and ZR. The R845 Relay and  
thermostat for each zone can energize the zone circulator  
through ZC only if R to W in the Aquastat® limit is made. If  
R to B (high limit) is made, the zone thermostat energizes the  
burner through ZR.  
Fig. 18. R8182D,H Aquastat® limit switching.  
240°F (116°C)  
R-B BREAKS ON  
TEMPERATURE RISE.  
BURNER TURNS OFF.  
CIRCULATOR OPERATES  
ON A CALL FOR HEAT.  
Zone Circulator Control with R8182E,J  
HIGH LIMIT  
SETTING  
The relay for each zone is connected to the Aquastat® limit  
through terminals ZC and ZR. The R845A Relay and  
thermostat in each zone can energize the zone circulator  
through ZC on a call for heat. If R to B (high limit) is made, the  
zone thermostat energizes the burner through ZR.  
15°F (8°C)  
DIFFERENTIAL  
R-B MAKES ON  
TEMPERATURE FALL.  
BURNER AND  
CIRCULATOR OPERATE  
ON A CALL FOR HEAT.  
Zone Valve Control with R8182  
The valve for each zone is connected to the Aquastat® limit  
by wiring end switches on the zone valve to T-T on the R8182.  
On a call for heat from any zone, the R8182 operates the  
same as for single zone applications.  
M1510  
180°F (82°C)  
Fig. 19. R8182E,J Aquastat® limit switching.  
13  
68-0105—2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R8182D,E,F,H,J COMBINATION PROTECTORELAY™ AND HYDRONIC HEATING CONTROLS  
Low Limit/Circulator Setting—D And H  
240°F (116°C)  
Models  
On a temperature rise, with the adjustable differential at the  
minimum setting of 10°F (6°C), the burner circuit (R-B) breaks  
and the circulator circuit (R-W) makes at the low limit setpoint.  
See Fig. 19. On a temperature drop of 10°F (6°C) below the  
setpoint, the R-B circuit makes and the R-W circuit breaks.  
HIGH LIMIT  
SETTING  
R-B BREAKS ON  
TEMPERATURE RISE.  
BURNER TURNS OFF.  
10°F (6°C)  
DIFFERENTIAL  
R-B MAKES ON  
At any differential setting greater than 10°F (6°C), the R-B  
make temperature and R-W break temperature remains the  
same— setting minus 10°F (6°C). The R-B break and R-W  
make temperature are the setpoint temperature plus the  
difference between the differential setting and 10°F (6°C).  
TEMPERATURE FALL.  
BURNER OPERATES  
ON CALL FOR HEAT.  
CIRCULATOR  
SETTING  
R-W MAKES ON  
TEMPERATURE RISE.  
CIRCULATOR TURNS ON.  
EXAMPLE: Setpoint of 140°F (60°C); differential set at 25°F  
(14°C). On a temperature rise, R-B breaks and R-W makes at  
155°F (68°C). On a temperature fall, R-B makes and R-W  
breaks at 130°F (54°C).  
10°F (6°C)  
DIFFERENTIAL  
R-B BREAKS ON  
TEMPERATURE FALL.  
CIRCULATOR TURNS OFF.  
Set the low limit indicator at the minimum temperature  
recommended for domestic hot water supply. This setting  
must be at least 20°F (11°C) below the high limit setting to  
prevent one switch from locking out the other.  
M1509  
110°F (43°C)  
Fig. 20. R8182F Aquastat® limit switching.  
Set the differential the desired number of degrees.  
Circulator Setting—F Models  
STARTUP AND CHECKOUT  
Set the circulator indicator at the minimum water temperature  
recommended for hydronic heating comfort.  
WARNING  
Can cause severe injury, death or property  
damage.  
This product is intended for use only in systems with a  
pressure relief valve.  
Setting Stops (R8182D,H TRADELINE®)  
Explosion Hazard.  
Part no. 126580 Setting Stops can be installed on the low and  
high limit adjusting knobs to prevent turning the knobs beyond  
a predetermined point. To install the setting stops, proceed as  
follows:  
Because heating systems differ, the correct temperature  
setting for one system may not be correct for another. Follow  
the boiler manufacturers recommendations for proper  
selection of settings.  
IMPORTANT  
Once the setting stops are in place, they cannot be  
replaced. If they must be removed, cut off with  
cutters—do not twist off.  
1. On low limit knob, turn the knob to the setting that is to  
be established as the limit.  
High Limit Setting—All Models  
The high limit opens and turns off the burner when the water  
temperature reaches the setpoint. The high limit automatically  
resets after the water temperature drops past the setpoint and  
through the 10°F (6°C) [15°F (8°C) with R8182E,J] differential.  
2. Place the setting stop over the knob so that the arm of  
the setting stop (after the stop is pressed into place)  
strikes projection A and prevents turning the knob  
beyond the chosen limit setting. See Fig. 21.  
3. Press the setting stop tightly onto the knob so its inner  
teeth securely engage the knob.  
Set the indicator at the desired shutoff temperature.  
4. Turn knob back and forth several times to make sure  
stop functions properly.  
5. Repeat steps 1 to 4 for the high limit knob.  
After settings are made, replace the cover.  
68-0105—2  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
R8182D,E,F,H,J COMBINATION PROTECTORELAY™ AND HYDRONIC HEATING CONTROLS  
Make certain the system operates as described in the  
OPERATION section. Use the following procedure to verify  
that the Protectorelay™ burner sequencing relay is controlling  
properly.  
1
STOP ARM  
SETTING  
Flame Failure Check  
Shut off the oil supply hand valve while the burner is on. After  
45 seconds, the safety switch locks out, the motor stops, and  
PROJECTION "A"  
the oil valve closes. Allow five minutes for the burner to cool,  
then manually reset the safety switch.  
SETTING STOP  
Ignition Failure Check  
Test by closing the oil supply while the burner is off. Run  
through the starting procedure but do not open the oil supply  
line hand valve. The safety switch locks out as in flame failure.  
Then turn the oil back on, and reset the safety switch.  
KNOB SET AT 140°F (60°C)  
M4523  
1
SCALE MARKINGS IN FAHRENHEIT ONLY.  
Power Failure Check  
Turn off the power supply while the burner is on. When the  
burner goes out, restore power and the burner will restart.  
Fig. 21. Setting stop in position to restrict low limit setting  
to 180°F (82°C) or lower.  
NOTE: If operation is not as described, see cover insert for  
additional information and check wiring.  
Startup  
Aquastat® Controller Replacement  
The Aquastat® limit section of the Protectorelay™ control is  
field replaceable. When ordering a replacement assembly,  
specify the complete model number of the R8182.  
WARNING  
Explosion Hazard.  
Can cause severe injury, death or property  
damage.  
Be sure combustion chamber is free of oil or vapor.  
Replace the Aquastat® Limit  
1. Disconnect power supply.  
2. On all models—Note the position of the connecting  
wires.  
3. Remove fastening screws and wires.  
4. Remove Aquastat® limit and install the new assembly.  
1. Push red reset button and release.  
2. Open hand valve on oil supply line.  
3. Set thermostat to call for heat.  
4. Close line switch; burner will start.  
5. Under normal conditions, burner operates until  
thermostat is satisfied or line switch is opened.  
MATERIAL SAFETY DATA SHEET (MSDS)  
Manufacturer: Honeywell Inc., 1985 Douglas Drive North,  
Minneapolis, MN 55422.  
SECTION 1. PRODUCT AND COMPANY  
IDENTIFICATION.  
Date Released: October 8, 1999.  
Emergency Telephone Information: 1-888-809-3787.  
NFPA Ratings:  
Product Name: Heat conductive compound.  
MSDS ID: DS9021.  
Synonyms: MS1699.  
Health 0; Flammability 1; Reactivity 0; Personal Protection  
B.  
Product Use: Heat conductive material used to enhance  
contact and heat transfer in temperature sensor applications.  
15  
68-0105—2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R8182D,E,F,H,J COMBINATION PROTECTORELAY™ AND HYDRONIC HEATING CONTROLS  
Section 2. Composition, Information on  
Ingredients (Table 3).  
a
Table 2. Ingredients of Heat Conductive Compound .  
Ingredients  
No. 2 Lithium Complex Grease (70%):  
Mineral Oil  
CAS Number  
Percent  
PEL  
TLV  
3
3
64742-65-0  
64742-62-7  
35-50  
5 mg/m  
5 mg/m  
3
3
Mineral Oil  
20-25  
5 mg/m  
5 mg/m  
Lithium Hydrostearate/Sebacate Complex  
Zinc Alkyldithiophosphate  
Aluminum Paste (30%):  
68815-49-6  
68649-42-3  
4-9  
0-2  
3
3
Aluminum, as Al  
7429-90-5  
8052-41-3  
20-25  
10-15  
15 mg/m  
10 mg/m  
3
3
Aliphatic Petroleum Distillates  
2900 mg/m 525 mg/m  
Stearic Acid  
57-11-4  
1-2  
1-2  
3
3
Aromatic Petroleum Distillates  
64742-95-6  
5 mg/m  
5 mg/m  
a
Additional Information: Part No. 120650 (0.5 oz. tube); Part No. 107408 (4 oz. can); Part number 197007 (5 gallon container).  
May also contain minute amounts of lithium and molybdenum lubricant compounds.  
Skin Contact:  
Section 3. Hazard Identification  
Remove excess with cloth or paper. Wash thoroughly with  
mild soap and water. Obtain medical attention if irritation  
develops and persists.  
Acute Health Effects:  
Skin—Excessive contact can cause skin irritation and  
dermatitis.  
Ingestion:  
Contact physician or local poison control center immediately.  
Eye—Direct contact with eye will cause irritation.  
Inhalation—No adverse effects are expected.  
Inhalation:  
Remove patient to fresh air and obtain medical attention if  
symptoms develop.  
Ingestion—Ingestion of product may cause nausea, vomiting  
and diarrhea.  
Section 5. Fire Fighting Measures  
Chronic Health Effects:  
Existing skin rash or dermatitis may be aggravated by  
repeated contact.  
Flash Point:  
>383°F (195°C). Will burn if exposed to flame.  
OSHA Hazard Classifications:  
None.  
Extinguishing Media:  
Carbon dioxide, dry chemical or foam.  
Carcinogenicity:  
Not considered to be a carcinogen by either OSHA, NTP,  
IARC, or ACGIH.  
Special Fire Fighting Procedures:  
None.  
Target Organs:  
Explosion Hazards:  
None. Aluminum powder can react with water to release  
flammable hydrogen gas. In the form of this product, this  
reaction is not expected.  
None known.  
Section 4. First Aid Measures  
Section 6. Accidental Release Measures  
Eye Contact:  
Flush eyes with water for 15 minutes. Remove any contact  
lenses and continue to flush. Obtain medical attention if  
irritation develops and persists.  
Scrape up and dispose as solid waste in accordance with  
state and federal regulations.  
Section 7. Handling and Storage  
Store in dry place. Keep container closed when not in use.  
68-0105—2  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R8182D,E,F,H,J COMBINATION PROTECTORELAY™ AND HYDRONIC HEATING CONTROLS  
Incompatibilities:  
Strong oxidizing agents and halogens.  
Section 8. Exposure Controls and Personal  
Protection  
Hazardous Decomposition Products:  
Carbon dioxide, carbon monoxide.  
Ventilation:  
No special ventilation is required when working with this  
product.  
Section 11. Toxicology Information  
No data available.  
Respiratory Protection:  
None required.  
Section 12. Ecological Information  
Eye Protection:  
Not normally required. However, use chemical safety goggles  
or faceshield if potential for eye contact exists, especially if  
material is heated.  
Chemical Fate Information:  
Hydrocarbon components will biodegrade in soil; relatively  
persistent in water.  
Hand/Clothing Protection:  
Not normally required. Protective gloves and clothing are  
recommended, as material is difficult to remove from skin and  
clothing.  
Section 13. Disposal Consideration  
Dispose of as solid waste in accordance with Local, State and  
Federal regulations.  
Other Protective Equipment:  
None required.  
Section 14. Transportation Information  
DOT Classification:  
Not classified as hazardous.  
Section 9. Physical and Chemical Properties  
Appearance/Odor:  
Aluminum color, semi-solid material, pleasant odor.  
Section 15. Regulatory Information  
SARA Title III Supplier Notification:  
Solubility in Water:  
Include in Section 311/312 inventory reports if amounts  
exceed 10,000 pounds. Aluminum compounds are subject to  
the reporting requirements under Section 313 of Emergency  
Planning and Community Right-to-Know Act of 1986 (40 CFR  
372). Ingredients listed in TSCA Inventory.  
Negligible.  
Specific Gravity:  
0.86.  
Section 16. Other Information  
Section 10. Stability and Reactivity  
This information is furnished without warranty, expressed or  
implied, except that it is accurate to the best of our knowledge.  
Stability:  
Stable.  
Prepared By:  
PROSAR, 1295 Bandana Boulevard, Suite 335, St. Paul, MN  
55108 (651-917-6100).  
Reactivity:  
Hazardous polymerization will not occur.  
17  
68-0105—2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
68-0105—2  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
19  
68-0105—2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Automation and Control Solutions  
Honeywell  
Honeywell Limited-Honeywell Limitée  
1985 Douglas Drive North  
Golden Valley, MN 55422  
35 Dynamic Drive  
Scarborough, Ontario  
M1V 4Z9  
Printed in U.S.A. on recycled  
paper containing at least 10%  
post-consumer paper fibers.  
68-0105—2 G.R. Rev. 1-02  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graham Field Blood Pressure Monitor 222 User Manual
GSW Water Heater POWER VENTED GAS FIRED WATER HEATER User Manual
Haier Saw HRF 498FR A1 User Manual
Harbor Freight Tools Automobile Parts 212cc User Manual
Harbor Freight Tools Grinder 53177 User Manual
Hayter Mowers Lawn Mower CODE144S User Manual
Honeywell Satellite Radio 5817 User Manual
Honeywell Security Camera HD3MDIP User Manual
HP Hewlett Packard Stereo Equalizer HP 7550 A User Manual
Hunter Fan Fan 23838 User Manual