Honeywell Burner M9481 User Manual

Honeywell  
M9484 AND M9494 MODUTROL MOTORS ARE LOW  
VOLTAGE, REVERSING PROPORTIONAL CONTROL  
ACTUATORS FOR VALVES, DAMPERS AND AUXIL-  
IARY EQUIPMENT. THEY ARE ESPECIALLY DE-  
SIGNED  
GAS BURNER CONTROL SYSTEMS.  
•i Replace M941 motors.  
Oil immersed motor and gear train for reliable per-  
formance and long life.  
Wiring box provides NEMA 3 weather protection.  
Actuator motor and circuitry operate from 24 volts  
AC. Models available with factory installed transformer,  
or internal transformer can be field added.  
Quick-connect terminals standard screw terminal  
adapter available.  
Cl Adapter bracket for matching shaft height of older  
motors is standard with replacement motors.  
Field adjustable stroke  
able.  
to  
models avail-  
q
Nominal timing of 30 seconds for  
and 60 sec-  
onds for  
available.  
stroke is standard. Other timings are  
Die-cast magnesium housing.  
q
Available accessories include valve and damper  
linkages, explosion proof housing, and auxiliary  
switches.  
,
Field addable interface modules can be mounted in  
wiring box to upgrade actuator to Series 70 (electronic)  
control.  
•i  
Models available with tapped output shaft.  
M9484 rated for 150 lb.-in. torque at stan-  
dard timings.  
M9494 rated for 300 lb.-in. torque at 2 or 4  
minute timings for  
stroke.  
Form Number 63-2195-l  
S.M.  
Rev. 11-90  
@Honeywell Inc. 1990  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STANDARD MODELS  
ELECTRICAL RATINGS:  
VOLTAGE  
POWER  
CURRENT  
DRAW (A)  
94 is Series 90  
D: is adjustable stroke  
to 1  
18  
23  
24  
0.8  
Without  
No auxiliary switches  
E: is adjustable stroke  
to 1  
1 auxiliary switch  
F: is adjustable stroke  
to 1  
Transformer  
Power Rating  
is high torque  
150 lb.-in. at  
standard timing  
9 is high torque  
300  
120  
0.24  
With internal  
Transformer  
23  
23  
208  
240  
0.14  
0.12  
2 or 4 min timing  
2 auxiliary switches  
Output Drive  
4 is dual-ended shaft,  
non-spring return  
1 is single-ended shaft,  
non-spring return  
STROKE: Field adjustable from  
to  
Start position  
of shaft changes with adjustment of stroke. (Midpoint of  
stroke remains fixed as stroke is adjusted, as shown in  
Fig. 2.) Stroke is adjusted by means of cams located in  
wiring compartment. (See Stroke Setting Procedure.)  
Motors are shipped with stroke set at  
NOTE: Some motors furnished to equipment manufactur-  
ers will have no adapter bracket, a single-ended shaft  
and/or no wiring box.  
DEAD WEIGHT LOAD ON SHAFT:  
Power or Auxiliary End-200 lb.  
Maximum Combined Load-300 lb.  
AMBIENT TEMPERATURE RATINGS:  
kg] maximum.  
kg].  
CONTROLLER TYPE: Series 90 Control Circuit-135  
ohm series 90 proportioning controller. Series 90 high  
or low limit controller with manual minimum position po-  
tentiometer (with a combined total resistance of up to  
500 ohms) may also be used in the control circuit.  
F
C]  
25% duty cycle.  
C].  
square  
Minimum-minus  
CRANKSHAFT:  
F
inch  
M9484, M9494 have double-ended shaft.  
M9481, M9491 have single-ended shaft.  
MOTOR ROTATION: Normally  
The closed posi-  
tion is the limit of counterclockwise rotation as viewed  
from the power end of the motor. See Fig 2.  
clockwise (as viewed from the power end). Motors are  
shipped in the closed position.  
normal position is the position the motor will assume  
with controller disconnected.  
WHEN PURCHASING REPLACEMENT AND MODERNIZATION PRODUCTS FROM YOUR AUTHORIZED  
DISTRIBUTOR, REFER TO THE TRADELINE CATALOG OR PRICE SHEETS FOR COMPLETE ORDERING  
NUMBER.  
IF YOU HAVE ADDITIONAL QUESTIONS, NEED FURTHER INFORMATION, OR WOULD LIKE TO COMMENT  
ON OUR PRODUCTS OR SERVICES, PLEASE WRITE OR PHONE:  
1. YOUR LOCAL HONEYWELL RESIDENTIAL AND BUILDING CONTROLS SALES OFFICE (CHECK WHITE  
PAGES OF PHONE DIRECTORY).  
2.  
AND BUILDING CONTROLS CUSTOMER SERVICE  
HONEYWELL INC., 1885 DOUGLAS DRIVE NORTH  
MINNEAPOLIS, MINNESOTA 55422-4386  
(IN CANADA-HONEYWELL LIMITED/HONEYWELL LIMITEE, 740 ELLESMERE ROAD, SCARBOROUGH,  
ONTARIO Ml P  
WORLD.  
SALES AND SERVICE OFFICES IN ALL PRINCIPAL CITIES OF THE  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
AUXILIARY SWITCH RATINGS (amperes):  
has 1 spdt switch.  
terfly valve. Requires adapter bracket packed with  
motor.  
Potentiometer-Limits minimum position of  
motor.  
has 2 spdt switches.  
ONE CONTACT  
Full Load  
120v  
7.2  
240v  
3.6  
Q68 Dual Control Potentiometer-Controls 1 through 9  
additional motors.  
Q181 Auxiliary Potentiometer-Controls 1 or 2 addi-  
tional motors.  
Locked Rotor  
43.2  
21.6  
Motor Crank Arm-Infinitely adjustable crank  
arm. Approximately 0.75 inches shorter than the  
4074ELY crank arm, can rotate through downward  
position and clear base of motor without requiring  
use of adapter bracket.  
VA pilot duty, 1201240  
on opposite contact.  
DIMENSIONS: See Fig. 1.  
UNDERWRITERS LABORATORIES INC. LISTED  
File No. E4436; Guide No. XAPX.  
CANADIAN STANDARDS ASSOCIATION CERTIFIED:  
General Listing File No.  
220741A Screw Terminal Adapter-converts the stan-  
dard quick-connect terminals to screws terminals.  
Transformers-mounted internally, provide 24  
power to motor  
Hz (for electrical iso-  
lation).  
Hz.  
Hz.  
STROKE STROKE RUNNING  
Hz.  
Module with selectable voltage  
ranges (4-7 Vdc, 6-9 Vdc, and 10.5-13.5 Vdc).  
Adapts motor to M71 XX function.  
Module, selectable voltage or cur-  
rent control, with adjustable null and span. Adapts  
function; 4 to 20  
Module, for W936 economizer ap-  
plications. Adapts motor to function.  
15  
30  
75  
150  
300  
30  
1 min  
150  
1.2 min  
300 134.01 600 168.01  
motor to  
or 2 to 10 Vdc.  
torque is the maximum torque available to  
overcome occasional large loads such as a seized  
damper or valve. MOTOR MUST NOT BE USED  
CONTINUOUSLY AT THIS RATING.  
Module, 3-wire 14-17 Vdc control  
with minimum position capability. Adapts motor to  
function.  
of  
min motor will damage motor.  
up to 6  
motors in unison  
from one Series 90 controller.  
2 or 3  
XX motors from a W973  
Single-zone Logic Panel or  
Discharge Air  
motor from a 4-20  
XX motors from a 4-20  
ACCESSORIES:  
Controller.  
ES6501 17 Explosion-proof Housing-Encloses motor  
for use in explosive atmospheres. Not for use with  
one  
Controller.  
Q618, and  
Linkages. Order from Nel-  
up to 4  
Controller.  
son Electric Co. Requires Honeywell  
pling.  
Q607 External Auxiliary Switch-Controls auxiliary  
equipment as a function of motor position.  
Q605 Damper Linkage-Connects motor to damper.  
INCLUDES MOTOR CRANK ARM.  
0618 Linkage-Connects Modutrol motor to water or  
steam valve.  
Q601 Bracket and Linkage Assembly-Connects  
Modutrol motor to water or steam valve.  
Linkage-Connects Modutrol motor to  
Cou-  
Resistor Board-Plugs onto quick-connects  
in wiring box of  
of  
motor. Can be used in place  
EAU, EDC, or EED resistor kits (func-  
tions described above).  
7616ADW Motor Crank Arm-Approximately 0.75  
inches shorter than the 7616BR crank arm, can  
rotate through the downward position and clear  
base of motor without requiring use of adapter  
bracket.  
WHEN INSTALLING THIS PRODUCT...  
1. Read these instructions carefully. Failure to follow  
them could damage the product or cause a hazardous  
condition.  
Disconnect power supply before beginning  
stallation to prevent  
ment damage.  
Never turn the motor shaft by hand or with a  
wrench-this will damage the motor.  
Always conduct a thorough checkout when in-  
stallation is complete.  
1.  
shock and equip-  
2.  
ratings given in the instructions  
the  
product to make sure the product is suitable for your  
application.  
2.  
3.  
3. Installer must be a trained, experienced service  
technician.  
4. After installation is complete, check out product  
operation as provided in these instructions.  
63-2195-l  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
5.37  
ADAPTER  
BRACKET  
FIG.  
IN  
NOTE: M9481, M9491 do not have auxiliary shaft. All other dimensions are the same.  
LOCATION  
connectors with wiring box to provide NEMA 3  
weather protection.  
install the Modutrol motor in any location except where  
acid fumes or other deteriorating vapors might attack the  
metal parts, or in atmospheres of escaping gas or the  
Always install motors with the crankshaft horizontal.  
Mounting flanges extending from the bottom of the  
explosive  
excessive salt environments, mount-  
ing base and screws should be zincorcadmium plated, not  
motor housing are drilled for  
screws or bolts.  
inch  
machine  
stainless steel or brass: Use the  
for mounting on these surfaces.  
adapter bracket  
Motors are shipped from the factory in closed position  
(at the limit of counterclockwise rotation as viewed from the  
power end of the motor, as shown in Fig. 2) with the stroke  
set at  
Allow enough clearance for installing accessories and  
servicing the motor when selecting a location. See Fig. 1.  
located outdoors, mount upright and use liquid-tight  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
ADAPTER BRACKET  
Adaptor Bracket, positioned between the  
motor and the equipment, raises the shaft height  
M9484 motor by 0.75 inch to match that of the M941 motor.  
This is required on all valve linkage applications,  
External Auxiliary Switch applications, and on some  
damper linkage applications (either to provide clearance  
for the crank arm to rotate through the downward position,  
or to allow the damper linkage to reach the shaft).  
To mount the motor with the bracket:  
1. Mount the bracket to the equipment with existing or  
standard bolts.  
2. Mount the motor to the bracket using the bolts pro-  
vided into the threaded holes of the bracket (see Fig. 3).  
For valve linkage applications, the bracket should first  
be mounted to the linkage (see Fig. 4). The bracket then  
provides a convenient base on which the motor can be  
positioned. After the motor shaft is aligned to the linkage,  
it can then be attached to the bracket with the 4 bolts  
provided. These bolts go through the inner set of holes in  
NON SPRING RETURN MOTORS  
FIG. 2-LIMITS OF MOTOR ROTATION.  
the motor  
and into the threaded holes of the bracket.  
BOLTS  
PROVIDED (4)  
1
OR  
ZINC PLATED MACHINE SCREWS OR BOLTS  
FIG.  
MOTOR WITH 220738A ADAPTER BRACKET. The bracket is first mounted to the  
with standard bolts. The motor is then mounted to the bracket using the bolts provided with the  
which thread into the threaded bracket holes.  
DAMPER LINKAGES  
linkage. In general, however, check the following points of  
operation when installing a motor and linkage.  
1. Linkages for valves and louver type dampers should  
be adjusted so that the damper or valve moves through  
only the maximum required distance when the motor  
moves through its full stroke.  
A 220738A Adapter Bracket is packed with replace-  
ment motors. Use of this bracket is optional for many  
damper applications but may be needed in damper appli-  
cations requiring the crank arm to rotate through the  
bottom plane of the actuator. If the bracket is not used in a  
replacement application, the damper linkage will have to  
be adjusted to the new shaft position.  
The motor comes without a crank arm. The crank arm  
is included in the Q605 linkage or may be ordered sepa-  
rately (see Accessories).  
For detailed instructions on the assembly of specific  
linkages, refer to the instruction sheet packed with each  
2. With modulating control, maximum damper opening  
should be no more than  
provided beyond this point.  
Little additional airflow is  
3. The motor must be stopped at the end of its stroke  
by the limit switch and must not be stalled by the damper  
or valve. The motor will be damaged if it is not permitted to  
complete its full stroke.  
63-2195-l  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
BOLTS PROVIDED (4)  
WIRING BOX  
MOTOR  
MACHINE SCREWS OR BOLTS.  
LTS SECURING BRACKET TO LINKAGE.  
TIGHTEN AFTER SECURING MOTOR TO THE BRACKET USING FOUR BOLTS PROVIDED.  
ON VALVE LINKAGE,.  
MOUNTING  
FIG.  
Figs. 5 and 6 show internal schematics.  
The motor terminals are quick-connects located on top  
of theprintedcircuit boardshown in  
4. Do not exceed the motor ratings in any installation.  
5. Do not turn motor shaft manually or with a  
this will damage the motor.  
adapter is standard on all Trade models and also may be  
added to all models. Access to the wiring compartment is  
VALVE LINKAGES  
gained  
and lifting off the cover.  
inthetoppf the wiring box  
The 220738A Mounting Bracket must be used with the  
00, Q601 and Q618 linkages in all valve applications.  
WIRING BOX  
WIRING  
When used with liquid-tight conduit connectors, the wiring  
box provides NEMA 3 weather protection for the motor.  
The box also provides knockouts for wiring conduits and  
encloses terminals. The wiring box, standard with replace-  
ment motors, is required for housing an internal trans-  
former, internal auxiliary switches or Series 70 Interface  
Modules.  
Disconnect power supply before wiring to prevent electri-  
cal shock or equipment damage. All wiring must agree with  
applicable codes, ordinances, and regulations.  
A transformer is required to supply 24  
power to the  
motor. Make sure that the power requirements stamped on  
the motor correspond to the characteristics of the power  
supply.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
YELLOW LEAD  
BLUE LEAD  
I
CLOSE  
1
1
WIRING SHOULD BE NEC CLASS 1 UNLESS POWER SUPPLY  
MEETS CLASS  
2
REQUIREMENTS. TAPE UNUSED LEADS. MAKE  
CERTAIN THE CURRENT DRAW OF THE EXTERNAL CIRCUIT IS  
LESS THAN CONTACT RATING OF SWITCH.  
2
ON TWO-SWITCH MOTORS SECOND SWITCH HAS BLACK  
LEADS WITH BLUE, YELLOW. AND RED TRACERS.  
254  
DIR ECTION OF MOTOR TRAVEL AS VIEWED FROM POWER E ND.  
CONNECT 24V POWER TO TERMINALS ONLY. DO NOT CONNECT  
POWER SUPPLY TO CONTROLLER TERMINALS. PROVIDE DISCONNECT  
MEANS AND OVERLOAD PROTECTION AS REQUIRED.  
3
TURN  
POT FULL  
STROKE, FULL  
STROKE.  
FIG.  
WIRING OF  
MODUTROL  
FIG.  
SWITCH INTERNAL WIRING.  
MOTORS.  
STROKE  
CAMS (YELLOW)  
MINIMUM  
INNER AUXILIARY  
INNER AUXILIARY  
SWITCH CAM (BLUE)  
OUTER AUXILIARY  
SWITCH CAM (RED)  
OUTER AUXILIARY  
STROKE POT  
NOTE: FEATURES AVAILABLE ON SOME MODELS ONLY.  
FIG. 7-TERMINALS AND ADJUSTMENTS.  
63-2195-l  
Download from Www.Somanuals.com. All Manuals Search And Download.  
AUXILIARY SWITCH CONNECTIONS  
The  
has 2 internal auxiliary switches which  
may be used to prove low fire and high fire positions.  
1. To prove low fire use red (common) and yellow wires  
connected to outer (left) switch. This switch makes red to  
yellow and breaks red to blue as motor closes.  
2. Wires connected to the inner (right) switch are black  
with colored tracers. To prove high fire, use red tracer  
(common) and blue tracer wires. The right switch makes  
red tracer to blue tracer and breaks red tracer to yellow  
tracer as motor opens.  
supplies to de-energize the  
The  
has 1 internal auxiliary switch. The switch  
wires are color-coded as follows: solid yellow-normally  
closed (N.C.); solid red-common (COM.); solid  
blue-normally open (N.O.).  
Color coding and switching action are tabulated below  
to aid the installer.  
SWITCH/CAM COLOR-CODING:  
TABLE 1  
CAM  
ASSEMBLY  
SWITCH  
CAM  
SWITCH  
DESIGNATION  
COLOR  
COLOR CODE  
Normally Closed (N.C.)  
Common (COM.)  
Solid Yellow  
Solid Red  
Red  
Left  
Outer  
Normally Open (N.O.)  
Solid Blue  
Normally Closed (N.C.)  
Common (COM.)  
Normally Open (N.O.)  
Yellow Tracer  
Red Tracer  
Blue Tracer  
Inner  
Blue  
Right  
from power end of motor.  
Fig. 6.  
SWITCHING ACTION:  
TABLE 2  
MOTOR  
POSITION  
CAM  
NORMAL  
FUNCTION  
SWITCH  
BREAKES  
MAKES  
Closing  
High portion of cam  
not in Contact  
with Cam follower.  
Red  
to  
Blue  
Proves  
Low Fire  
Position  
Red  
to  
Yellow  
Left  
Opening  
High portion of cam  
in Contact  
with Cam follower.  
Red Tracer  
to  
Blue Tracer  
Red Tracer  
to  
Yellow Tracer  
Proves  
High Fire  
Position  
Right  
from power end of motor.  
Fig. 9  
BEFORE SETTING STROKE:  
1. Remove top cover from motor.  
STROKE  
On  
motors, stroke is field adjustable and  
to 160”. Motors are shipped in  
can be set from  
position. In order to set stroke, both mechanical and elec-  
trical adjustments are required. The mechanical adjust-  
ments (cams) establish the full open (clockwise,  
viewed from the power end) and full closed (counterclock-  
wise positions of the motor shaft. The electrical  
2. Disconnect controller from motor.  
3. Connect  
terminals on 135 ohm potentiome-  
ter (Q209 or S963) to matching terminals on motor.  
as  
adjustment (trim pot) provides sufficient total stroke angle  
to ensure that cams will actuate both limit switches.  
SETTING  
STROKE (Fig. 8):  
1. Turn stroke pot fully clockwise  
2. Drive motor to mid-position using 135 ohm pot  
STROKE SETTING PROCEDURE  
See Fig. 8.  
(Q209 or  
or by jumpering B-R-W.  
3. Insert  
in. screwdriver blade into slot on inner  
yellow cam and MOVE TOP OF SCREWDRIVER as far as  
possible counterclockwise (viewed from power  
end). Repeat in successive cam slots until inner cam is  
against counterclockwise stop.  
Detach linkage from motor before adjusting stroke.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
MOVE SCREWDRIVER AT TOP  
ONLY TO ADJUST CAM:  
IN. STRAIGHT BLADE  
SCREWDRIVER  
OUTER STROKE  
ADJUST CAMS  
OUTER CAM  
RY SWITCH CAMS  
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND  
OVERLOAD PROTECTION AS REQUIRED.  
A
A
NOTE: CAMS ARE OFFSET  
2
TRANSFORMER MAY BE EXTERNAL OR INTERNAL.  
PROVIDE BETTER VIEW OF BACK CAM.  
FIG.  
ADJUSTMENT SETUP.  
IN. STRAIGHT-BLADE  
SCREWDRIVER  
STROKE ADJUST  
CAMS (YELLOW)  
RIGHT/INNER  
INNER AUXILIARY CAM (BLUE)  
OUTER AUXILIARY CAM (RED)  
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND  
OVERLOAD PROTECTION AS REOUIRED.  
A
2
TRANSFORMER MAY BE EXTERNAL OR INTERNAL.  
A
OTOR CLOSE  
POWER END  
NOTE: CAMS ARE OFFSET VERTICALLY TO  
PROVIDE BETTER VIEW OF BACK CAM.  
FIG. O-AUXILIARY SWITCH ADJUSTMENT SETUP.  
63-2195-l  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Switching action and color coding are shown in Tables  
1 and 2 on page 8.  
Motors with factory added auxiliary switches are  
shipped in the closed position (counterclockwise  
as viewed from power end) with auxiliary cams set to  
IMPORTANT  
Set cams by moving top of screwdriver only. Press-  
ing screwdriver against sides of cam slots could  
cause damage to motor end switches.  
actuate switches  
from the closed position, and to  
4. Insert  
yellow cam and MOVE TOP OF SCREWDRIVER as far as  
possible clockwise Repeat in successive cam slots  
until outer cam is against clockwise stop.  
in. screwdriver blade into slot on outer  
provide  
clockwise  
differential. Wiih motor in closed (full counter-  
position, auxiliary switch breaks R-B.  
IMPORTANT  
Do not turn motor shaft by hand or with a wrench as  
damage to the gear train and circuit board stroke  
limit contacts will result.  
NOTE: Excessive force will damage cam stop on hub.  
5. Check motor stroke before connecting linkage.  
6. Disconnect 135 ohm pot, reconnect controller, re-  
place top cover on motor.  
PROCEDURE (Fig. 9)  
1. Removetopcoverfrom  
terminals and cam adjustments.  
gain access to motor  
7. Attach linkage to motor.  
2. Disconnect controller from motor and connect 135  
ohm manual potentiometer with R-W-B terminals on pot  
connected to corresponding terminals on motor (Fig. 9).  
3. Adjust 135 ohm pot so that motor shaft turns to  
position where auxiliary equipment is to be switched.  
SETTING  
STROKE (Fig. 8):  
1. Turn stroke pot fully counterclockwise  
2. Drive motor to mid-position, using 135 ohm pot  
(Q209 or  
3. Insert  
cam and MOVE TOP OF SCREWDRIVER as far as  
possible clockwise (viewed from power end). Re-  
peat in successive cam slots until inner cam is against  
clockwise stop.  
or by jumpering B-R-W.  
in. screwdriver into slot on inner yellow  
4. Insert a  
in., straight-blade screwdriver into slot on  
cam associated with selected auxiliary switch. The inner  
(blue) cam actuates the inner (right) switch, the outer (red)  
cam actuates the outer (left) switch. MOVE TOP OF  
SCREWDRIVER to set cams.  
5. For switch differential of 1 check continuity of aux-  
iliary switch R-B contacts and rotate cam as follows:  
NOTE: Excessive force will damage cam stop on hub.  
a.  
contacts are open, rotate cam clockwise  
R-B contacts close.  
until  
4. Insert  
yellow cam and MOVE TOP OF SCREWDRIVER  
possible counterclockwise Repeat in successive  
in. screwdriver blade into slot on outer  
far as  
b. contacts are closed, rotate cam counterclockwise  
until R-B contacts open.  
6. For switch differential of  
cam slots until outer cam is against counterclockwise stop.  
check continuity of  
auxiliary switch R-B contacts and rotate cam as follows:  
a. contacts are open, rotate cam counterclockwise  
until R-B contacts close.  
NOTE: Excessive force will damage cam stop on hub.  
5. Check motor stroke before connecting linkage.  
6. Disconnect 135 ohm pot, reconnect controller, re-  
place top cover on motor.  
b. contacts are closed, rotate cam clockwise  
until R-B contacts open.  
c. Final adjustment in the proper direction should be  
made to obtain contact make or break at the desired  
position.  
7. Attach linkage to motor.  
AUXILIARY SWITCHES  
7. Check for proper differential and switching of  
iaryequipmentby runningmotorthroughfullstroke  
directions), using 135 ohm pot. Repeat adjustment if  
necessary.  
8. Disconnect 135 ohm pot, reconnect controller, re-  
place top cover on motor.  
The auxiliary switches in  
motors are actu-  
ated by adjustable cams. The cams are mounted on the  
motor shaft at the power end of the motor. The settings of  
the cams determine the point in motor shaft rotation at  
which the auxiliary equipment will be switched on or off.  
These cams can be set to actuate switches at any angle  
within the stroke of the motor. Also each cam provides a  
fast rise portion for switching (1 differential) and a slow  
NOTE: If differential is changed from to  
ing action is reversed, thus: switch contacts R-B make  
and R-W acounterclockwise (closed) rotation.  
the switch-  
rise portion for slow switching  
differential).  
CONNECTION DIAGRAMS (Figs. 10-13)  
SERIES 90 CIRCUIT  
These motors are designed for use in series 90 propor-  
tioning control circuits employing a 135 ohm series 90  
controller. Series 90 high or low limit controls or manual  
minimum position potentiometers may also be used in the  
control circuit.  
The potentiometers, one in the controller and one in the  
motor, along with resistor network, form a bridge circuit. As  
long as the value of the controlled medium remains at the  
controller set point, the circuit is balanced, and the motor  
does not run.  
When the value of the controlled medium changes, the  
potentiometer wiper in the controller is moved, which  
unbalances the bridge circuit. This unbalance is amplified,  
The M9484 can also be used with some electronic  
controllers which provide a 4-20  
control output. is  
necessary to use a resistor kii (4074EED for controlling up  
to 6 motors) or Q7230 Interface Module to interface to the  
and energizes  
switching to run the motor in the  
4-20  
source.  
direction necessary to correct the change in temperature  
or pressure. The motor turns the feedback potentiometer  
to rebalance the circuit and stop the motor.  
The standard series 90 controller has  
W, and B  
terminals. As the controller reduces Rto W resistance, the  
motor will drive closed (CCW as viewed from the power  
end).  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERIES 99  
CONTROLLER  
MOTOR  
OPTIONAL CONNECTIONS  
WITH  
OHM POTENTIOMETERS IN SERIES.  
SERIES 90  
CONTROLLER  
MOTOR  
SERIES 90 HIGH  
LIMIT CONTROL  
SUPPLY.  
PROTECTION AS REQUIRED.  
DISCONNECT MEANS AND OVERLOAD  
TRANSFORMER  
2
TRANSFORMER MAY BE INTERNAL OR EXTERNAL TO MOTOR.  
1
POWER SUPPLY.  
PROTECTION AS REQUIRED.  
DISCONNECT MEANS AN,, OVERLOAD  
2
TRANSFORMER MAY BE INTERNAL OR EXTERNALTO MOTOR.  
IG. 1 l-MOTOR USED  
LER AND A SERIES 90 LOW OR HIGH  
CONTROL.  
SPDT SWITCH  
OR SERIES 60  
CONTROLLER  
USED AS A  
SOURCE  
SINGLE MOTOR  
SLAVE MOTOR(S)  
TRANSFORMER  
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD  
PROTECTION AS REOUIRED.  
USE SOLID LINE CONNECTION FOR POSITIVE CLOSING TO  
2
3
MINIMUM  
SUBSTITUTE DOTTED LINE CONNECTION  
FOR POSITIVE FULL CLOSURE.  
TO  
4
ADDITIONAL SLAVE MOTORS (6 TOTAL,  
TRANSFORMER MAY BE INTERNAL OR EXTERNAL TO MOTOR.  
RESISTOR (A) DEPENDS ON NUMBER OF SLAVES. SEE RESISTOR SELECT-  
ION CHART IN TEXT.  
2
SEE MOTOR SPECIFICATIONS FOR  
L
FOR MOTOR, SERIES 90  
CONTROLLER, MINIMUM POSITION PO-  
TENTIOMETER (ETC.).  
FOR MOTOR USED WITH 4  
CONTROL.  
FIG.  
TO 20  
63-2195-I  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RESISTOR SELECTION CHART FOR  
4-20  
CHECKOUT  
After installation and linkage adjustment, check the entire  
motor and control hookup to ensure that-  
OUTPUT  
*
The motor operates the damper or valve properly.  
The motor responds properly to the controller.  
VOLTAGE  
REQUIRED  
l
RESISTOR (A)  
Inspect the motor, linkage, and valve or damper to see  
that all mechanical connections are correct and secure. In  
damper installations, the  
than a few inches past the ball joints. Check to see that  
there is adequate clearance for the linkage to move  
through its stroke without binding or striking other objects.  
Check to see that cams operate the auxiliary switches,  
if used, at the desired point of motor rotation.  
MOTORS  
(Ohms)  
237  
150  
Part No.  
802139BFAA  
802139BBDA  
1
2
1.7  
2.0  
should not extend more  
124 113  
5
6
23.3.20.7  
3.3  
97.6”  
Not part of this  
These values represent the controller output voltage  
required to drive the motors.  
obtain separately.  
NOTE: Motors are shipped in the fully closed position (the  
limit of counterclockwise rotation as viewed from the  
power end of the motor) with the stroke set at  
SERIES 90 MOTORS OPERATION CHECK WITH MODUTROL MOTOR DISCONNECTED FROM CONTROLLER  
IF NO OR LIMITED RESPONSE  
RESPONSE  
STEP  
ACTION  
1.  
2.  
3.  
4.  
Apply 24  
None.  
Open terminal B and short W to R.  
Open terminal W and short B to R.  
Connect terminals to B to W.  
Motor drives closed.  
Motor drives open.  
Motor must drive to  
position.  
Proceed to Step 6.  
Proceed to Step 6.  
Proceed to Step 6.  
No voltage or out of range. Proceed  
to Step 7.  
5.  
Remove jumpers from  
Check voltage between B and R,  
and W and R.  
B, and W. 17 to 20 Vdc.  
Replace motor.  
Replace motor.  
Motor is defective.  
Motor printed wiring board  
is defective.  
6.  
7.  
Motor does not drive.  
Voltage out of range.  
Spring mechanism defective  
-replace motor.  
Spring return motors return  
to their normal mechanical  
position.  
8.  
Disconnect 24  
NOTES:  
Ensure motor transformer is sized properly. If a common transformer is used to power multiple motors, ensure power  
input is in phase with all motors.  
Motors may operate in Series 90 or two-position control applications. However, checking voltage between terminals  
to B and R to W is necessary to confirm proper operation in electronic (W973, 4 to 20  
etc.) applications.  
bracket is needed,  
the Adapter Bracket  
DAMPER APPLICATION  
sections and see Fig. 3 as well as the INSTALLATION,  
SETTINGS &ADJUSTMENTS, and  
of these instructions.  
5. Use old mounting bolts to mount the new actuator.  
6. Mountthedampercrankarmandlinkagetotheshaft  
of the new actuator.  
8. Use the CHECKOUT procedures to test the proper  
adjustment of the crank arm and linkage.  
1. Turn off power and remove wiring from the old  
actuator.  
2. Remove crank arm from shaft of old actuator and  
remove the old actuator.  
3.  
see whether or not the mounting bracket is  
needed. the linkage can reach the lowershaft position of  
the new actuator and if the crank arm has clearance for the  
needed rotation, then the bracket is not needed. Use  
220738A Adapter Bracket or 221455A crank arm if crank  
arm must rotate through the bottom plane of the motor (for  
damper applications).  
VALVE APPLICATION  
When installing a M9484, M9494 motor in a valve ap-  
plication which has a  
necessary to use the 220738A Adapter Bracket provided  
to motorshafttothesame height asthatof  
motor. Ensure motor stroke is to operate Honeywell  
two-way or three-way valves.  
Q601 or  
it will be  
the bracket is not needed, mount the new actuator  
directly to the equipment and refer to the INSTALLATION,  
SETTlNGS&ADJUSTMENTS,andCHECKOUTsections  
of these instructions as needed.  
Honeywell Inc.  
International Sates Offices in all principal cities of the world. Manufacturing in  
Australia, Canada, Finland, Franc%, Germany, Japan, Mexico, Netherlands,  
Spain, Taiwan, United Kingdom, U.S.A.  
U.S.A.: 1885 Douglas Drive N.  
Golden Valley, MN 55422-4386  
CANADA: 740 Ellesmere Road  
QUALITY  
KEY  
PRINTED IN U.S.A.  
Scarborough, Ontario  
P
Download from Www.Somanuals.com. All Manuals Search And Download.  

Greenheck Fan Ventilation Hood WD 400 Series User Manual
Groupe SEB USA T FAL Iron Virtuose User Manual
HannsG Car Video System HA191 User Manual
HANNspree Car Video System HF289 User Manual
Harbor Freight Tools Smoker 92388 User Manual
Hotpoint Double Oven OS897D P HP S User Manual
HP Hewlett Packard Laptop Docking Station 367055 002 User Manual
HP Hewlett Packard Printer Transcend Traffix Manager User Manual
Huawei Network Router Aolynk DR811 User Manual
IBM Home Theater Server ibm User Manual