7800 SERIES
EC7810A, EC7820A Relay Modules
SPECIFICATION DATA
FEATURES
•
Safety features:
— Interlock check.
— Dynamic AMPLI-CHECK™
— Closed loop logic test.
— Dynamic input check.
— Dynamic safety relay test.
— Dynamic self-check logic.
— Expanded safe-start check.
— Internal hardware status monitoring.
— Low Fire Start Switch test.
— Tamper resistant timing and logic.
Ignition attempts: 1 or 5. Selectable by model number.
Access for external electrical voltage checks.
Application flexibility.
Dependable, long-term operation provided by microcomputer
technology.
•
•
•
•
•
First-out annunciation and system diagnostics provided by a
2 row by 20 column vacuum fluorescent display (VFD)
located on the KDM (optional).
•
Five sequence information light emitting diodes (LED) with
symbols for Power, Pilot, Flame, Main and Alarm (see Fig. 1).
Interchangeable plug-in flame amplifiers.
Nonvolatile memory; EC7810/EC7820 retain history files and
sequencing status after loss of power.
Remote reset (subject to application approval; optional).
Remote mounting of KDM (subject to application approval).
Burner control data available on the optional KDM:
— Flame signal strength.
•
•
•
•
•
GENERAL
The Honeywell EC7810/EC7820A Relay Module is a
microprocessor-based integrated burner control for
automatically fired gas, oil or combination fuel single burner
atmospheric (EC7810A) or atmospheric with fan (EC7820A)
applications. The EC7810A/EC7820A system consists of the
relay module, wiring subbase, amplifier and purge card. The
optional keyboard display module (KDM) can be mounted on
the relay module or on the face of a panel door. The KDM can
also be mounted remotely from the panel if this is approved
for the application.
— Hold status.
— Lockout/alarm status.
— Sequence status.
— Sequence time.
— Total cycles of operation.
— Total hours of operation.
— Fault history providing the six most recent faults:
•
•
•
•
•
Cycles of operation at the time of the fault.
Fault message and code.
Hours of operation at the time of the fault.
Sequence status at the time of the fault.
Sequence time at the time of the fault.
The EC7810/EC7820 is programmed to provide a level of
safety, functional capability and features beyond the capacity
of conventional controls.
— Diagnostic information:
•
•
•
•
•
•
•
Device type.
Flame amplifier type.
Flame failure response time (FFRT).
Manufacturing code.
On/off status of all digital inputs and outputs.
Selected prepurge time.
The basic functions of the EC7810/EC7820A include
automatic burner sequencing, flame supervision, system
status indication, system or self-diagnostics and
troubleshooting.
Software revision and version of relay module and
optional KDM.
•
•
Status of configuration jumper.
Status of Run/Test Switch.
® U.S. Registered Trademark
66-2040
Copyright © 1998 Honeywell Inc.
•
All Rights Reserved
Download from Www.Somanuals.com. All Manuals Search And Download.
7800 SERIES EC7810A, EC7820A RELAY MODULES
Table 1B. EC7820A Terminal Ratings.
Terminal No.
Abbreviation
Description
Ratings
a
G
Flame Sensor Ground
a
Earth G
Earth Ground
N
Line Voltage Common (Neutral)
Alarm (Normally Open)
Burner/Blower Motor
Line Voltage Supply (L1)
Limits and Burner Control
Airflow Switch Input
Pilot Valve 1 (interrupted)
Main Fuel Valve
3
AL
FAN
L1
220/230/240 Vac, 1A, 10A inrush for 5000 cycles.
220/230/240 Vac, 4A at P.F. = 0.5, 20A inrush.
4
b
5
220-240 Vac (+10%/-15%), 50/60 Hz (±10%).
6
RT
220/230/240 Vac, 5A (maximum).
220/230/240 Vac, 1 mA.
7
LD2
PV1
MV
IGN
c
8
220/230/240 Vac, 4A at P.F. = 0.5, 20A inrush.
c
9
220/230/240 Vac, 4A at P.F. = 0.5, 20A inrush.
c
10
Ignition
220/230/240 Vac, 4A at P.F. = 0.2.
F(11)
Flame Signal
135 to 220 Vac, current limited.
d
13
COM
MOD
Firing Rate Common
Firing Rate Modulate
Control Voltage
220/230/240 Vac, 4A at P.F. = 0.5.
d
14
220/230/240 Vac, 4A at P.F. = 0.5.
16
220-240 Vac (+10%/-15%).
220/230/240 Vac, 1 mA.
220/230/240 Vac, 1 mA.
220/230/240 Vac, 1 mA.
17
ES2
ES1
Preignition Interlock Input
Low Fire Switch Input
Lockout Input
18
20
LOS
PV2
c
21
22
Pilot Valve 2 (Intermittent)
Shutter
220/230/240 Vac, 4A at P.F.= 0.5, 20A inrush.
e
SHTR
220-240 Vac, 0.25A.
a
b
c
d
e
See Table 2.
2000 VA maximum connected load to 7800 SERIES Relay Module Assembly.
Total load current, excluding burner/boiler motor and firing rate outputs cannot exceed 5A, 25A inrush.
Can also be 24 Vac, 3A at PF = 0.5.
220-240 Vac to 120 Vac, 10 VA (minimum) stepdown transformer (not provided) required to drive shutter.
Table 2. Recommended grounding practices.
Ground type
Recommended Practice
Earth ground (subbase and relay module). 1. Use to provide a connection between the subbase and the control panel of
the equipment. Earth ground must be capable of conducting enough current
to blow the 20A fuse (or breaker) in the event of an internal short circuit.
2. Use wide straps or brackets to provide minimum length, maximum surface
area ground conductors. If a leadwire must be used, use 14 AWG copper
wire.
3. Make sure that mechanically-tightened joints along the ground path are free
of nonconductive coatings and protected against corrosion on mating
surfaces.
Signal ground (KDM, Data ControlBus
Module™, Communications Interface
ControlBus™ Module).
Use the shield of the signal wire to ground the device to the signal ground
terminal 3(c) of each device. Connect the shield at both ends of the daisy chain
to earth ground.
3
66-2040
Download from Www.Somanuals.com. All Manuals Search And Download.
7800 SERIES EC7810A, EC7820A RELAY MODULES
Table 3. Sequence Timing for Normal Operation.
First
Safety
Time
Main
Trial
Time***
Purge or
Pilot
Stab.
Main
Ignition
Device
Initiate Standby Waiting Preignition
Stab. Run Attempts
EC7810A1027 2 sec
EC7810A1035 2 sec
EC7820A1026 2 sec
EC7820A1034 2 sec
*
*
*
*
**
**
**
**
3 sec
3 sec
3 sec
3 sec
5 or 10 sec 5 sec 5 or 8 sec 5 sec
5 or 10 sec 5 sec 5 or 8 sec 5 sec
5 or 10 sec 5 sec 5 or 8 sec 5 sec
5 or 10 sec 5 sec 5 or 8 sec 5 sec
*
*
*
*
1
5
1
5
* Standby and Run can be an infinite period.
** Waiting Time is determined by the ST7800A Purge Card selected.
*** Second Safety Time is Main Trial Time plus Flame Failure Response Time.
Electrical Ratings (See Tables 1A and 1B):
Voltage and Frequency: 220 to 240 Vac (+10%/-15%),
50/60 Hz (±10%).
Oil Approvals:
EC7810A1027: DIN-5F104/96.
EC7820A1026: DIN-5F105/96.
EN298: “Automatic gas burner systems for gas burners
and gas burning appliances with or without fans.”
Keyboard Display Module (Optional): 13 Vdc peak
fullwave rectified (+20%/-15%).
Power Dissipation:
Relay Module: 10W maximum.
KDM: 3W maximum.
Maximum Total Connected Load: 2000 VA.
Fusing (Total Connected Load): 20A, type FRN or
equivalent.
Please note the following to comply with EN60730 for remote
mounting of the KDM and/or remote reset. It is necessary to
provide electrical separation using insulation at least
equivalent to double or reinforced insulation. Accomplish this
by either:
•
Optically isolating the communication and/or remote
reset lines from the control cabinet or
Providing physical separation from the communication
and/or remote reset lines using electrical conduit and a
remote display cover assembly (part no. 204718A) or
other suitable enclosure that meets IP40 class of
protection.
Environmental Ratings:
Ambient Temperatures:
Operating: -40°C to 60°C (-40°F to 140°F).
Storage: -40°C to 66°C. (-40°F to 150°F).
Humidity: 85% RH continuous, noncondensing.
Vibration: 0.5G environment.
•
Dimensions:
Mounting:
See Fig. 1 and 2.
Q7800A Wiring Subbase for Panel Mount: To meet EN60730
requirements, mount the relay module in a secured panel
which meets IP40 class of protection.
Weight:
Relay Module: 0,730 kg unpacked.
KDM: 0,113 kg unpacked.
Required Components:
Plug-in Flame Signal Amplifier: See Table 2.
ST7800A Plug-in Purge Timer Cards: Selectable from two
seconds to 30 minutes.
IMPORTANT
Flame Detection System available for use with
EC7810/EC7820. Select your plug-in Flame Signal
Amplifier and applicable Flame Detector from Table 4.
Q7800A Wiring Subbase.
Accessories:
Keyboard Display Modules (KDM) (Optional):
S7800A1001 English language.
S7800A1035 French language.
S7800A1043 German language.
S7800A1050 Italian language.
S7800A1068 Spanish language.
S7800A1118 Katakana (Japanese) language.
S7800A1126 Portuguese language.
S7800B1009 Chinese language.
Approvals:
This product complies with the following European directives:
Gas Appliance Directive (90/269/EEG).
Low Voltage Directive (73/23/EEG).
EMC Directive (89/336/EEG).
GASTEC (CE-63AP3070/1).
Factory Mutual: J.I.0Y0A9.AF.
66-2040
4
Download from Www.Somanuals.com. All Manuals Search And Download.
7800 SERIES EC7810A, EC7820A RELAY MODULES
Miscellaneous:
Communications:
S7820A1007 Remote Reset Module.
Q7700B1004 Network Interface Unit with universal 100 to
250 Vac, 50/60 Hz external power supply, external
modem required.
QS7800A1001 ControlBus Module, standard.
QS7800B1000 ControlBus Module, multidrop.
QS7800C1009 ControlBus Module, data acquisition
modules.
QS7800D1008 ControlBus Module, Armstrong.
QS7800E1007 ControlBus Module, Pulsafeeder.
QS7850A1006 ControlBus Module, General Purpose
Interface.
ZM7850A1001 Combustion System Manager™ Software.
ZM7850B1000 SYSNet™ Facilities Integration Software.
S7810A1009 Data ControlBus™ Module (if no KDM is
used).
203541 Data ControlBus Connector, 5-wire.
203765 Remote Display Mounting Bracket.
221729 Relay Module Dust Cover.
204718A Keyboard Display Module Cover, NEMA 4, clear.
204718B Keyboard Display Module Cover, NEMA 1, clear.
204718C Keyboard Display Module Cover, NEMA 4, clear
with reset button.
205321B Flush Display Mounting Kit.
221818A Extension Cable, display, (1524 mm).
221818C Extension Cable, display, (3048 mm).
123514A Rectification Flame Simulator.
203659 Ultraviolet Flame Simulator.
203968A Remote Display Power Supply, 13 Vdc, plug-in.
S7810B1007 Data ControlBus™ Module, Multi-Drop
Switch Module.
Table 4. Flame Detection System
Plug-in Flame Signal Amplifiers
Applicable Flame Detectors
Flame Failure
Response
Time
Type
Color Self-Checking
Model
Fuel
Type
Models
Rectification Green
No
R7847A
1 or 2 sec
maximum.
Gas
Rectifying
C7004, C7007, C7011.
Complete Assemblies:
C7008, C7009, Q179.
Flame Rod
a
Holders
No
R7847A
R7847B
1 or 2 sec
maximum.
Oil
Rectifying
Photocell
C7003, C7010, C7013,
C7014.
b
Dynamic
Ampli-Check™
1 or 2 sec
maximum.
Gas
Rectifying
C7004, C7007, C7011.
Complete Assemblies:
C7008, C7009, Q179.
Flame Rod
a
Holders
Dynamic
Ampli-Check™
R7847B
R7849A
R7849B
R7861A
R7886A
1 or 2 sec
maximum.
Oil
Rectifying
Photocell
C7003, C7010, C7013,
C7014.
d
b
c
d
Ultraviolet
Purple
Blue
No
1 or 2 sec
maximum.
Gas, oil
Gas, oil
Gas, oil
Ultraviolet
(Minipeeper)
C7027,C7035, C7044 .
d
Dynamic
Ampli-Check™
1 or 2 sec
maximum.
Ultraviolet
(Minipeeper)
C7027,C7035, C7044 .
g
c,f
c,f
Dynamic
Self-Check
1 or 2 sec
maximum.
Ultraviolet
C7061.
g
Dynamic
2 sec
Gas, oil, Ultraviolet
C7076.
Self-Check
maximum.
coal
(Adjustable
Sensitivity)
a
b
c
Order flame rod separately; see holder instructions.
Use only Honeywell Photocell part number 38316.
Dynamic Self-Check ultraviolet amplifiers should be used only on burners that cycle on-off at least once every 24 hours.
Appliances with burners that remain on continuously for 24 hours or longer should use C7061A Flame Detector with R7861A
Amplifier.
C7027, C7035 and C7044 Flame Detectors should be used only on burners that cycle on-off at least once every 24 hours.
Appliances with burners that remain on continuously for 24 hours or longer should use C7061A Flame Detector with R7861A
Amplifier as ultraviolet flame detection system.
Circuitry tests the flame signal amplifier at least 12 times a minute during burner operation and shuts down the boiler if the
amplifier fails.
Circuitry tests all electronic components in the flame detection system (amplifier and detector) 12 times a minute during
burner operation and shuts down the burner if the detection system fails.
d
e
f
g
A 220/240 Vac to 120 Vac 10 VA step-down transformer (not provided) must be used to drive the shutter.
5
66-2040
Download from Www.Somanuals.com. All Manuals Search And Download.
66-2040
6
Download from Www.Somanuals.com. All Manuals Search And Download.
7
66-2040
Download from Www.Somanuals.com. All Manuals Search And Download.
Home and Building Control
Honeywell Inc.
Honeywell Plaza
P.O. Box 524
Minneapolis MN 55408-0524
Home and Building Control
Honeywell Asia Pacific Inc.
Room 3213-3225
Sun Hung Kai Centre
No. 30 Harbour Road
Wanchai
Honeywell Limited-Honeywell Limitée
155 Gordon Baker Road
North York, Ontario
M2H 3N7
Hong Kong
Honeywell Latin American Region
480 Sawgrass Corporate Parkway
Suite 200
Honeywell Europe S.A.
3 Avenue du Bourget
1140 Brussels
Sunrise FL 33325
Belgium
Printed in U.S.A. on recycled
paper containing at least 10%
post-consumer paper fibers.
66-2040 G.R. 3-98
Download from Www.Somanuals.com. All Manuals Search And Download.
|