ML6131
Direct Coupled Actuator
PRODUCT DATA
FEATURES
•
•
•
Mounts directly on damper shaft.
6 lb-in. torque.
Selectable 45°, 60°, and 90° stroke in either clockwise
(cw) or counterclockwise (ccw) directions.
•
•
15 second timing model suitable for use with pressure
independent VAV systems.
Magnetic coupling typically provides a maximum of
18 lb-in. stall torque eliminating the need for
mechanical stops or limit switch adjustments.
•
•
•
Two field-addable auxiliary switches.
Field-addable auxiliary feedback potentiometer.
Models available with 0° to 30° minimum position
adjustment in cw or ccw directions.
•
•
•
Compatible for use with Honeywell W7620 Terminal
Unit Controller.
Can be used with the Commercial Zone Damper in the
W7600 Commercial Zone System.
APPLICATION
Manual declutch on some models.
The ML6131 Direct Coupled Actuator (DCA) is used to control
dampers in applications such as variable air volume (VAV)
terminal units. It is suitable for use with single pole double
throw (spdt) floating thermostats or two-position control
systems.
Contents
®
® U.S. Registered Trademark
Copyright © 2000 Honeywell Inc. • All Rights Reserved
63- 2498- 2
Download from Www.Somanuals.com. All Manuals Search And Download.
ML6131 DIRECT COUPLED ACTUATOR
2-7/8 (73)
1-11/16
CAUTION
Actuator Damage Hazard.
(42)
Deteriorating vapors and acid fumes can damage
the actuator metal parts.
Install actuator in areas free of acid fumes and
deteriorating vapors.
1 (25)
1/8
(3)
OPTIONAL
AUXILIARY
SWITCH
Location
4-7/8
(123)
Choose a location for the actuator that allows enough
clearance for mounting accessories and for servicing.
CW
COM
CCW
4-1/4
(108)
Mounting
These actuators are designed to open a damper or valve by
driving the shaft in either the clockwise (cw)
or
counterclockwise (ccw) direction. The actuator has a
mounting tab on the bottom that secures it to a damper box or
valve linkage. When mounted correctly, this tab allows the
actuator to float without rotating relative to the shaft. The tab is
sized for 1/4 in. self-tapping sheet metal screws (not
included).
11/16
(18)
7/8
(22)
1-5/16
(33)
3-3/8 (86)
2-1/2 (64)
M18016
CAUTION
Tightly securing mounting tab to damper housing
can damage actuator.
Fig. 1. Approximate dimensions of ML6131
Direct Coupled Actuator in in. (mm).
Equipment Damage Hazard.
Once mounted, the actuator must be allowed to float;
do not fully tighten the screw.
INSTALLATION
These actuators are shipped in the fully clockwise 90° position
as viewed from the end of the damper shaft.
When Installing this Product...
1.
Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous
condition.
CAUTION
2.
Check the ratings given in the instructions and on the
product to make sure the product is suitable for your
application.
Equipment Damage Hazard.
Mounting actuator unevenly with damper housing
can damage actuator.
Mount actuator flush with damper housing or add
spacer between mounting tab and damper box
3.
4.
Installer must be a trained, experienced service
technician.
After installation is complete, check out product
operation as provided in these instructions.
IMPORTANT
All wiring must agree with applicable codes,
DAMPER
SHAFT
ADD SPACER BETWEEN
DAMPER BOX AND TAB
ordinances and regulations.
ML6131
WARNING
Explosion Hazard.
A spark from the actuator or attached accessories
can result in serious injury or death.
Install the actuator in areas free of escaping gas and
other explosive vapors.
VAV BOX HOUSING
M4449
CAUTION
Fig. 2. Mounting actuator to VAV box when
actuator is not flush with box.
Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment
circuitry.
Disconnect all power supplies before installation.
Actuators with auxiliary switches can have more than
one disconnect.
3
63-2498—2
Download from Www.Somanuals.com. All Manuals Search And Download.
ML6131 DIRECT COUPLED ACTUATOR
Preparation
Before mounting the actuator onto the shaft, determine the
following:
1.
2.
Size of the shaft (3/8 in. to 1/2 in.).
Direction the shaft rotates to open the device (cw or
ccw). See Fig. 3.
3.
Degrees of actuator stroke for opening device (45°, 60°,
or 90°).
DIRMECLT6C1O3U1PLED ACTUATOR
If the shaft is 3/8 in. round or square, use part number 201391
Shaft Adapter provided inside the bag assembly shipped with
the actuator. Place the adapter opposite the setscrews
(see Fig. 4).
MANUAL
DECLUTCH
LEVER
ML6131
M17611
TYPE A DAMPER
Fig. 5. Location of manual declutch lever.
COOLING
AIR FLOW
Installation
After determining the direction of the shaft rotation (cw or
ccw), install the device. For valve linkage mounting, refer to
the instructions shipped with the linkage. For damper
mounting, proceed as follows:
CW TO OPEN, CCW TO CLOSE
TYPE B DAMPER
1.
Place the actuator onto the damper shaft.
COOLING
AIR FLOW
CAUTION
Equipment Damage Hazard.
Improper range stop selection can damage
light-duty dampers.
CCW TO OPEN, CW TO CLOSE
M2067A
Fig. 3. Determining direction damper
shaft rotates when opening.
Be sure to select the proper range stop.
2.
If the angle of the damper opening is either 45° or 60°,
close the actuator using the manual declutch:
a. Disengage the hub using the declutch lever; see
Manual Operation (Declutch) section.
SHAFT ADAPTER
b. Rotate the hub until the actuator gear train passes
the proper 45° or 60° setting. (Do not insert the pin
until after the actuator passes this point.)
c. Release the declutch lever.
NOTE: Dampers with 90° stroke do not require the
range stop pin.
M2064
3.
Insert the range stop pin into the appropriate (cw or
ccw) 45° or 60° slot. The range stop pin is clipped into
its final position only after the pin passes through both
snap into position and not be removable manually
Fig. 4. Using shaft adapter for 3/8 in. shafts.
Manual Operation (Declutch)
IMPORTANT
Do not fully tighten the mounting screw; the actuator
CAUTION
must be allowed to float.
Personal Injury and Product Damage Hazard.
Do not use manual declutch without supporting
the load.
4.
5.
With the actuator placed in its final position, secure the
mounting tab to the damper box with a sheet metal
screw.
Position the damper in the open position and securely
tighten the Allen screws into the damper shaft.
Support load independent of actuator immediately
prior to and while using manual declutch lever.
Manual declutch capability is available on some actuators.
Use the manual declutch lever to manually adjust the actuator
To operate, push the lever in the direction of the arrow on the
lever cover.
63-2498—2
4
Download from Www.Somanuals.com. All Manuals Search And Download.
ML6131 DIRECT COUPLED ACTUATOR
1.
2.
Determine the direction of the desired closing rotation.
Move the actuator to the position fully opposite the
desired closing rotation (if cw closing rotation is desired,
move the actuator to the full ccw position).
RANGE STOP PIN
3.
Determine the correct hole for the setscrew using Fig. 8
and the results of step 1.
ACTUATOR PLATES
THIS SETSCREW
CORRESPONDS WITH
CLOSING IN THE
CW DIRECTION
THIS SETSCREW
CORRESPONDS WITH
CLOSING IN THE
CCW DIRECTION
60
60
45
60
45
CW
60
45
COM
CCW
45
M10247
Fig. 8. Setscrew location for ML6131.
CAUTION
Equipment Damage Hazard.
Improper hub positioning or hole selection can
permanently damage the device.
Avoid backdriving the actuator with the setscrew.
M10246A
Fig. 6. Range stop pin properly inserted.
4.
Remove the red cap from the desired hole. Leave the
other cap in position. The caps ensure that dust and
other impurities do not enter the gear train through
unused holes.
SCREWDRIVER
5.
6.
Thread the locknut fully onto the 1/4 in. setscrew.
Insert the setscrew into the desired hole, turning
clockwise until resistance is encountered or the locknut
contacts the housing.
7.
8.
If resistance is met before the setscrew is fully inserted,
stop and review the initial setup procedures as detailed
in steps 1 through 3.
Determine the angle of minimum position required for
the application. With the setscrew fully inserted, the
minimum position is 30°. With the setscrew fully out, the
minimum position is 0°.
M2065
Fig. 7. Lifting a range stop pin out of its slot.
9.
Using the conversion of approximately 1.7 angular
degrees of shaft rotation per turn of the setscrew, back
the screw out of the housing and stop slightly short of
the calculated position. This allows the setscrew to be
set accurately while taking air flow measurements.
Minimum Position Setscrew
Certain ML6131 models are equipped with two tapped holes
located in the plastic housing at the top of the actuator. These
holes can be used with the minimum position setscrew and
setscrew provides for a 0° to 30° minimum position
adjustment.
IMPORTANT
After initiating step 10, the setscrew cannot be
turned into the housing without returning the actuator
to the fully open position (as determined in step 1).
The actuator follows the setscrew without damaging
the housing only when backed out of the housing
(turned ccw).
NOTE: Before starting operation, note that the 1/4 in.
minimum position setscrew limits closing motion,
while the range stop pin limits opening motion.
5
63-2498—2
Download from Www.Somanuals.com. All Manuals Search And Download.
ML6131 DIRECT COUPLED ACTUATOR
10.
11.
Rotate the actuator to minimum position using the
manual declutch; see Manual Operation (Declutch)
section.
With the actuator at minimum position, adjust the
position more accurately using air flow measurements.
The 201052A, B and C Auxiliary Switches are field-addable.
For mounting instructions, see form 63-2218, provided with
the device.
IMPORTANT
When operating an ML6131 from a two-position
controller, a 201052B Auxiliary Switch is required for
proper operation. See Fig. 10.
IMPORTANT
— After each adjustment, ensure the actuator is
completely stopped before proceeding with the next
adjustment.
NOTE: See Fig. 11 for the 201052B Auxiliary Switch wiring.
— To reduce the minimum position, turn out the
setscrew (ccw). The actuator then drives toward the
closed position.
— Turning the setscrew in (cw) damages the actuator
housing.
2
ML6131
EXTERNAL
SWITCH
R8222
RED COM
BLUE CW
— If the device is too far closed, return to step 1.
12.
When proper air flow is achieved, loosen the locknut
from the setscrew until it contacts the actuator housing,
then turn it an additional 1/8 turn to lock the setscrew in
place.
WHITE CCW
T87F
1
L1
(HOT)
W
Y
L2
R
IMPORTANT
Run an entire check of the operation after completing
this procedure.
1
2
POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
AUXILIARY SWITCHES ARE REQUIRED TO TURN
OFF THE MOTOR AT EACH END OF THE STROKE.
Wiring
M17613
Fig. 9. ML6131 used with T87F in heating-only
or cooling-only application.
CAUTION
Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment
circuitry.
ML6131
L1
201052B
(HOT)
RED COM
BLUE CW
Disconnect all power supplies before installation.
Actuators with auxiliary switches can have more than
one disconnect.
SPDT
CONTROL
L2
2
1
ON/OFF
CONTROL
WHITE CCW
3
4
All wiring must comply with local electrical codes, ordinances
and regulations. Voltage and frequency of the transformer
used with the actuator must correspond with the
characteristics of both the power supply and the actuator.
typical wiring.
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2
3
SET SWITCH TO CLOSE WHEN STROKE REACHES FULL CW POSITION.
SET SWITCH TO CLOSE WHEN STROKE REACHES FULL CCW POSITION.
ON-OFF CONTROL REQUIRES AN R8222 SPDT RELAY IN PLACE OF THE
4
Auxiliary Switches
SPDT CONTROL.
M17612
The 201052A, B or C Auxiliary Switch is used in conjunction
with the actuator. It allows for control of equipment external to
the actuator (for example, electric reheat coils and fan) at an
adjustable point in the stroke (0° to 90°) of the actuator.
Fig. 10. 201052B Auxiliary Switch wiring.
63-2498—2
6
Download from Www.Somanuals.com. All Manuals Search And Download.
ML6131 DIRECT COUPLED ACTUATOR
Auxiliary Potentiometers
AUXILIARY POTENTIOMETER
The 200976 Auxiliary Potentiometer mounts on the face of
potentiometer shaft has a slipping collar, which means that if
one of the two limits of the potentiometer is exceeded, the
collar will continue to rotate, causing no damage to the
potentiometer itself. To mount the potentiometer on the
actuator:
MOTOR
RB
RW
POSITION
RESISTANCE
RESISTANCE
FULLY CW
24V (COM-CW)
500 OR
2000 OHMS
0 OHMS
500 OR
2000 OHMS
FULLY CCW
24V (COM-CCW)
0 OHMS
1.
2.
3.
Turn the potentiometer to align the shaft key with the
slot in the potentiometer drive.
AUXILIARY POTENTIOMETER LEADS
MOTOR
Tilt the potentiometer slightly so the key faces down
toward the slot.
Insert the potentiometer into the slot, and push down so
the potentiometer is flush with the actuator body and the
bracket is aligned over the screw hole.
Insert the screw provided into the hole and fasten
securely.
ROTATION
RW OHMS
INCREASE
DECREASE
RB OHMS
DECREASE
INCREASE
CCW
CW
4.
IMPORTANT
Failure to follow the calibration procedures can result
in improper resistance values at desired stroke.
60
To Calibrate the 200976A,C:
60
45
IMPORTANT
Remove the range stop pins and minimum position
45
setscrews prior to calibration.
CW
1.
2.
3.
Drive the actuator fully closed (0°) to fully open (90°)
and back again to the fully closed position. This must be
done to receive the correct resistance readings at the
appropriate degree of stroke.
Check the resistance values of the potentiometer with
an ohmmeter at intervals in the stroke while referring to
in the Specifications section.
COM
CCW
R
B
W
Replace the range stop pins and/or the minimum
position setscrews using the appropriate procedures.
FIELD-ADDABLE AUXILIARY POTENTIOMETER
M10251B
Fig. 11. ML6131 with field-addable potentiometer.
7
63-2498—2
Download from Www.Somanuals.com. All Manuals Search And Download.
ML6131 DIRECT COUPLED ACTUATOR
OPERATION
CHECKOUT
To check out the ML6131, determine the direction the damper
shaft moves to open the damper (cw or ccw). See Fig. 3:
VAV Systems
1.
2.
3.
VAV systems control the temperature within a space by
varying the volume of supply air. Air is delivered to the space
at a fixed temperature. The volume of supply air is controlled
by the space thermostat modulating the supply air damper.
When full heating and cooling flexibility is required in a zone, it
is handled by temperature air system, or with reheat capability
in the air terminal units. As individual zones shut down, the
total air flow in the system is regulated by a central duct static
pressure controller. The fan system is sized to handle an
average peak load, not the sum of the individual peaks. As
each zone peaks at a different time of day, extra air is
Place 24 Vac across the appropriate COM and CW or
COM and CCW terminals to energize the actuator. The
ML6131 should begin to open the damper.
If the actuator does not run, switch the 24 Vac across
the opposite COM and CW or COM and CCW terminals
to determine if the damper will begin to close.
If the actuator does not run in either direction, replace
the ML6131.
In the event the ML6131 is used with a spdt floating wall
thermostat (pressure dependent systems):
1.
2.
borrowed from the off-peak zones. This transfer of air from
low-load to high-load zones occurs only in true VAV systems.
Adjust the setpoint of the thermostat to call for cooling.
Observe the operation of the actuator; if the device is
closed, it should begin to open.
3.
4.
5.
In pressure independent systems, individual zone airflow
sensors are used to maintain the zone air flow rate regardless
of fluctuation in the total system pressure.
If not, adjust the setpoint of the thermostat higher to
determine if the wiring is correct.
If no movement is observed, check for the presence of
24 volts.
If using the T641 Thermostat, check that 24 volts are
present between terminals C and Y during a call for
cooling. With proper wiring and 24 volts present, the
actuator should operate correctly.
Pressure independent systems, when used with controllers
such as the W7620, can react faster to changes in air flow
demand. Therefore, these systems can use the faster
15 second ML6131 models.
6.
If not, replace the actuator.
Parallel Actuators
NOTE: When the ML6131 is used with electronic
control systems such as the W7620, override
the control system by programming the
controller to open/close the zone damper as
appropriate.
IMPORTANT
Over time, parallel-driving actuators can become out
of sync with each other. Normally, driving all
actuators to the fully-open or fully-closed position
puts them back in sync.
certain the total connected load does not exceed the current
capacity of the controller or thermostat.
Home and Building Control
Honeywell Inc.
Honeywell Plaza
Home and Building Control
Honeywell Limited-Honeywell Limitée
155 Gordon Baker Road
North York, Ontario
P.O. Box 524
Minneapolis, MN 55408-0524
M2H 3N7
Printed in U.S.A. on recycled
paper containing at least 10%
post-consumer paper fibers.
63-2498—2 B.B. Rev. 6-00
Download from Www.Somanuals.com. All Manuals Search And Download.
|