Honeywell Automobile Parts ML4105 User Manual

ML4105, ML4115, ML8105, ML8115  
Fast-Acting, Two-Position Actuators  
FOR FIRE/SMOKE CONTROL APPLICATIONS  
PRODUCT DATA  
FEATURES  
30 lb-in. (3.4 N•m) or 50 lb-in. (5.7 N•m) minimum  
driving torque at 350°F (176°C).  
Integral spring return ensures level of return torque.  
Fifteen-second spring return timing.  
No special cycling required during long-term holding.  
No audible noise during holding.  
Patent pending design eliminates need for limit  
switches to reduce power consumption.  
Models available for 24, 120, and 230 Vac.  
Ninety-five degree angle of rotation.  
Actuator holds rated torque at reduced power level.  
Die-cast aluminum housing.  
Housing design allows flush mounting to damper.  
Integral junction box with three conduit openings  
eliminates need for separate wiring box.  
High-temperature indicator included.  
APPLICATION  
APPLICABLE LITERATURE  
The ML4105, ML4115, ML8105, and ML8115 Fast-Acting,  
Two-Position Actuators are spring return direct coupled  
actuators (DCA) with an integral junction box for on/off  
damper control. The actuator accepts an on/off signal from a  
single-pole, single-throw (spst) controller. Models are  
available with clockwise (cw) or counterclockwise (ccw) spring  
return and are designed to operate reliably in smoke control  
systems requiring Underwriter’s Laboratories Inc. UL555S  
ratings up to 350°F.  
— Motor/Actuator Selection Guide  
for Damper Applications  
— Engineering Manual of Automatic Control  
(also called The Gray Manual)  
— Direct Coupled Actuator  
63-8419  
77-1100  
Quick Selection Guide  
— Damper Torque Calculator  
63-8553  
63-8437  
Contents  
Ordering Information ........................................................  
2
® U.S. Registered Trademark  
Copyright © 2003 Honeywell International Inc.  
N314  
All Rights Reserved  
63-2540-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
ML4105, ML4115, ML8105, ML8115 FAST-ACTING, TWO-POSITION ACTUATORS  
Timing (At Rated Torque and Voltage):  
Drive Open:  
ML4105, ML8105: 15 sec maximum, 14 sec typical.  
ML4115: 25 sec maximum, 18 sec typical.  
ML8115: 25 sec maximum, 22 sec typical.  
Spring Close: 15 seconds.  
Table 3. Environmental Ratings.  
ML4105C1016  
ML4105C1008  
ML4105D1007  
ML4105D1015  
ML4115C,D  
All Devices  
NEMA1  
IP40  
IP54  
Cycling Requirements:  
2 (51)  
1 (25)  
Prolonged holding-period (1 year) testing of these actuators  
has been performed with no spring return failures. The  
actuator and the internal spring are designed to require no  
special cycling during long-term holding.  
5/8  
(17)  
1
Honeywell recommends following all local, state and national  
codes for periodic testing of the entire smoke control  
system. Refer to National Fire Protection Association (NFPA)  
National Fire Codes®: NFPA90A, NFPA92A and NFPA92B  
for your application.  
6 3/8  
(161)  
NFPA recommends periodic examination of each fire/smoke  
damper (semi-annually or annually) to ensure proper  
performance.  
7 1/2  
(192)  
Design Life (at Rated Voltage): 60,000 full stroke cycles.  
Approvals: See Table 2.  
Environmental Protection Ratings: See Table 3.  
2 (51)  
3 5/16 (84)  
Accessories:  
4 (102)  
1/16 (2)  
201391 Shaft Adapter for 3/8 in. shafts (not supplied with  
actuator).  
7/8 (22)  
205649 Mounting Bracket (not supplied with actuator).  
Table 2. Approvals.  
1
ML4115/ML8115 HAVE SMALLER  
HUB WITH TWO SET SCREWS.  
ML4105/ML8105 HAVE LONGER  
HUB WITH FOUR SET SCREWS.  
ML4105  
ML4115C,D  
ML8105,  
C1008, C1016,  
A,B  
D1007 D1015 ML4115A,B ML8115  
5 1/8 (129)  
M13053A  
UL/cUL  
X
X
X
X
X
X
X
X
Fig. 1. ML4105/ML4115/ML8105/ML8115  
dimensional drawing in in. (mm).  
UL873 Plenum  
Rating, File No.  
E4436; Guide  
No. XAPX.  
X
CE  
X
X
X
X
X
X
C-TICK  
3
63-2540—9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ML4105, ML4115, ML8105, ML8115 FAST-ACTING, TWO-POSITION ACTUATORS  
INSTALLATION  
When Installing this Product...  
1. Read these instructions carefully. Failure to follow  
them could damage the product or cause a hazardous  
condition.  
2. Check the ratings given in the instructions and on the  
product to make sure the product is suitable for your  
application.  
3. Installer must be a trained, experienced service  
technician.  
4. After installation is complete, check out product  
operation as provided in these instructions.  
1
IMPORTANT  
All wiring must agree with applicable codes,  
ordinances and regulations.  
WARNING  
Electrical Power Hazard.  
Line voltage can cause death or serious injury  
and short equipment circuitry.  
2
Disconnect power supply before installation.  
1
2
ENSURE THAT MOUNTING ASSEMBLY PREVENTS ACTUATOR  
ROTATION AND ALLOWS ACTUATOR TO FLOAT ALONG  
INDICATED AXIS. WHEN TOO TIGHT, THE RESULTING BINDING  
CAN DAMAGE THE ACTUATOR OR REDUCE TORQUE OUTPUT.  
CAUTION  
Electrical Shock or Equipment Damage Hazard.  
Low voltage can shock individuals or short  
equipment circuitry.  
ACCESSORY MOUNTING BRACKET IS NOT SUPPLIED WITH  
THE ACTUATOR.  
M13054A  
Disconnect power supply before installation.  
Fig. 2. Mounting actuator to damper housing.  
Location and Mounting  
The ML4105, ML4115, ML8105 and ML8115 DCA are  
designed to open a damper by driving the damper shaft in  
Preparation  
either clockwise  
or counterclockwise  
direction.  
Before mounting the actuator onto the damper shaft,  
determine the damper shaft size (3/8 in. to 1/2 in.  
[10 mm to 13 mm]).  
The actuator housing has two slots on the bottom that, with a  
205649 Mounting Bracket, secure it flush to a damper box  
(see Fig. 2). When mounted correctly, these slots allow the  
actuator to float without rotating relative to the damper shaft.  
If damper shaft is 3/8 in. (10 mm) round or square, use part  
number 201391 Shaft Adapter (not supplied with actuator).  
Place adapter opposite set screws (see Fig. 3).  
CAUTION  
Tightly securing actuator to damper housing can  
damage actuator.  
NOTE: The damper shaft adapter centers a 3/8 in. (10 mm)  
damper shaft in the hub. Failure to use adapter can  
cause mounting screws to loosen. A 1/2 in. (13 mm)  
damper shaft does not require an adapter.  
Equipment Damage Hazard.  
Mount actuator to allow it to float along its vertical axis.  
NOTE: ML4105, ML4115, ML8105, and ML8115 Actuators  
are shipped in the fully closed position.  
SHAFT ADAPTER  
M2064  
Fig. 3. Using damper shaft adapter for  
3/8 in. (10 mm) damper shafts.  
63-2540—9  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ML4105, ML4115, ML8105, ML8115 FAST-ACTING, TWO-POSITION ACTUATORS  
Installation  
(
(
)
)
L1  
L2  
RED  
CAUTION  
Improper set screw tightening causes device  
malfunction.  
24 VAC  
BLACK  
Device Malfunction Hazard.  
Tighten set screws with proper torque to prevent  
damper shaft slippage.  
M17585A  
Fig. 4. Typical 24 Vac wiring.  
CAUTION  
Actuator Damage Hazard.  
Using actuator as shaft bearing causes device  
damage.  
Use actuator only to supply rotational torque. Avoid  
(
)
L1  
L2  
BLACK  
120 VAC  
WHITE  
any side loads to actuator output coupling bearings.  
(
)
To install actuator, proceed as follows:  
1. Place actuator over damper shaft; and hold mounting  
bracket in place. See Fig. 2.  
M17589A  
2. Mark screw holes on damper housing.  
3. Remove actuator and mounting bracket.  
4. Drill or center-punch holes for mounting screws (or use  
no.10 self-tapping sheet metal screws).  
Fig. 5. Typical 120 Vac wiring.  
5. Turn damper blades to desired normal (closed) position.  
6. Place actuator and mounting bracket back into position  
and secure bracket to damper box with sheet metal  
screws.  
7. Tighten set screws securely into damper shaft using  
minimum 30 lb-in., maximum 60 lb-in. torque. Use  
1/8 in. or 3 mm Allen wrench (see Specifications for  
details) to tighten set screws.  
(
)
L1  
L2  
BROWN  
BLUE  
230 VAC  
(
)
M17588A  
Wiring  
Fig. 6. Typical 230 Vac wiring.  
See Fig. 4 through 8 for typical wiring diagrams.  
WARNING  
Line voltage can cause death or serious injury and  
short equipment circuitry.  
Electrical Power Hazard.  
(
)
L2  
L1  
3
2
1
230 VAC  
)
L1  
Disconnect power supply before installation.  
(
M17586A  
CAUTION  
Electrical Shock or Equipment Damage Hazard.  
Low voltage can shock individuals or short  
equipment circuitry.  
Fig. 7. 230 Vac terminal-strip wiring.  
Disconnect power supply before installation.  
200 F  
93 C  
IMPORTANT  
(
)
L1  
L2  
1. All wiring must comply with local electrical codes,  
2
1
3
ordinances and regulations.  
230 VAC  
2. Voltage and frequency of transformer used with  
ML8105 and ML8115 must correspond with the  
characteristics of power supply and actuator.  
3. Use wires rated for at least 75°C (167°F).  
(
)
L1  
M17587A  
Fig. 8. 230 Vac terminal-strip wiring with a thermal fuse.  
NOTE: Terminal strip included with ML4105C1008 and  
ML4105D1007.  
5
63-2540—9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ML4105, ML4115, ML8105, ML8115 FAST-ACTING, TWO-POSITION ACTUATORS  
OPERATION  
CHECKOUT  
The ML4105, ML4115, ML8105, and ML8115 DCA are  
designed for use in Smoke Control Systems. If power fails, the  
actuator spring returns to the 0° position. The actuator mounts  
flush with the damper box. The actuator drives from 0° to 95°  
and spring returns back to 0°.  
ML4105A,B and ML4115A,B (120 Vac model)  
1. Verify that the indicator has not turned black (see  
Temperature Indicator section).  
2. Check damper position.  
3. Connect 120 Vac to the black and white leadwires to  
drive the damper to the open position. The actuator  
should drive the damper.  
4. If the actuator does not run, remove power for at least  
two seconds.  
5. If the actuator spring returns, allow it to close entirely,  
then return to step 3.  
IMPORTANT  
A break in power of less than two seconds can cause  
the actuator to spring-return 5 degrees or less and  
remain in place until a break in power of longer  
duration.  
The actuators are operated by an spst two-position controller.  
When using an spst two-position controller, the actuator drives  
to the damper fully open position when controller contact  
makes and spring returns to the damper fully closed position  
when controller contact breaks. The actuator drops to holding  
power level on detection of stall, independent of hub position.  
6. If the actuator does not spring return, verify that the  
actuator is properly installed. See Installation section.  
7. If the actuator is correctly installed but neither runs nor  
spring returns, replace the actuator.  
ML4105C,D and ML4115C,D (230 Vac model)  
1. Verify that the indicator has not turned black (see  
Temperature Indicator section).  
Cycling  
The actuator and the internal spring are designed so that no  
special cycling during long-term holding is required.  
Honeywell recommends following all local, state, and national  
codes for periodic testing of the entire smoke control system.  
Refer to National Fire Protection Association (NFPA) National  
Fire Codes®: NFPA90A, NFPA92A, and NFPA92B for your  
application.  
2. Check damper position.  
3. Connect 230 Vac to the blue and brown leadwires to  
drive the damper to the open position. The actuator  
should drive the damper.  
4. If the actuator does not run, remove power for at least  
two seconds.  
5. If the actuator spring returns, allow it to close entirely,  
then return to step 3.  
6. If the actuator does not spring return, verify that the  
actuator is properly installed. See Installation section.  
7. If the actuator is correctly installed but neither runs nor  
spring returns, replace the actuator.  
Temperature Indicator  
The temperature indicator, located on the cover of the  
actuator, provides evidence that the ambient temperature has  
exceeded 200°F (93°C). This is an indication that something  
in the building has caused temperatures to rise well above the  
long-term actuator operation temperature. While the actuator  
is capable of operating at 350°F (176°C) for extended periods  
of time, this indicator provides a visual signal that the actuator  
has been exposed to high temperatures for an undetermined  
period of time. The indicator provides a visual indication to fire  
authorities regarding the extent of damage after an event in  
the building.  
ML8105 and ML8115 (24 Vac model)  
1. Verify that the indicator has not turned black (see  
Temperature Indicator section).  
2. Check damper position.  
3. Connect 24 Vac to the red and black leadwires to drive  
the damper to the open position. The actuator should  
drive the damper.  
4. If the actuator does not run, remove power for at least  
IMPORTANT  
two seconds.  
If the indicator turns black, replace the actuator.  
5. If the actuator spring returns, allow it to close entirely,  
then return to step 3.  
NOTE: The actuator is designed to operate for 30 minutes  
during a one-time excursion to 350°F (176°C).  
6. If the actuator does not spring return, verify that the  
actuator is properly installed. See Installation section.  
7. If the actuator is correctly installed but neither runs nor  
spring returns, replace the actuator.  
63-2540—9  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
ML4105, ML4115, ML8105, ML8115 FAST-ACTING, TWO-POSITION ACTUATORS  
D
F
I
Montageanweisung  
Instructions d’Installation  
Istruzioni per I’Installazione  
NL Installatievoorschrift  
DK Installasjonsinstruks  
N
Installationsinstrukioner  
SF Asennusohje  
S
E
Installations Instrukioner  
Instrucciones de montage  
A
A1, A4  
A2  
24 VAC  
120 VAC  
!
d
ASSEMBLY  
EINBAU  
MONTAGE  
MONTAGGIO  
a
D
F
I
NL MONTAGE  
DK MONTERE  
N
MONTERING  
FIN ASENTAMINEN  
a
S
E
MONTERA  
MONTAJE  
b
M11874  
M11875  
b
c
M11876  
A3  
A5  
A6  
MIN: 45 lb-in. (5.1 Nm)  
MAX: 60lb-in. (6.8 Nm)  
b
HEX  
4mm  
c
a
a
b
b
a
M12030  
M11881  
M11882  
7
63-2540—9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ML4105, ML4115, ML8105, ML8115 FAST-ACTING, TWO-POSITION ACTUATORS  
B
B1  
B2  
B4  
24 VAC  
120 VAC  
!
a
b
M11887  
DISASSEMBLY  
AUSBAU  
DÉMONTAGE  
SMONTAGGIO  
D
F
I
M11886  
NL DEMONTAGE  
DK AFMONTERE  
DEMONTERE  
FIN PURKAMINEN  
N
B3  
S
E
NEDMONTERA  
DESMONTAJE  
M11884  
a
HEX  
b 4mm  
M11885  
M11888  
National Fire Codes® is a registered trademark of the National Fire Protection Association (NFPA).  
Automation and Control Solutions  
Honeywell International  
Honeywell Europe S.A. Honeywell Latin American  
Honeywell International Inc. Honeywell Limited-Honeywell Limitée Control Products  
3 Avenue du Bourget  
1140 Brussels  
Belgium  
Region  
1985 Douglas Drive North  
Golden Valley, MN 55422  
35 Dynamic Drive  
Scarborough, Ontario  
M1V 4Z9  
Honeywell Building  
17 Changi Business Park Central 1  
Singapore 486073  
480 Sawgrass Corporate Parkway  
Suite 200  
Sunrise FL 33325  
63-2540—9 B.B. Rev. 5-03  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Greenway Home Products Indoor Fireplace MM256BRG User Manual
Harman Kardon Home Theater System AVR65 User Manual
Honeywell Door RCWL2200A User Manual
Hughes Kettner Stereo Amplifier Mark II 100W Head User Manual
Hyundai Cassette Player H 2204 User Manual
IBM Garage Door Opener 38 User Manual
IBM Printer 1725 SLS User Manual
IBM Projector 520Q User Manual
IKEA TV Video Accessories AA 189267 3 User Manual
Impex Home Gym WM 357 User Manual