Honeywell Air Cleaner F35F User Manual

F35F Media Air Cleaner  
WITH EXPANDAPAC™ MEDIA FILTER  
PRODUCT DATA  
FEATURES  
High efficiency Expandapac media filter with Ultra-  
Web® technology captures particles as small as  
1.0 micron.  
Strong media will not tear when installing combs.  
Combs are located down stream from filter so they  
stay clean.  
Efficiency and arrestance ratings based on the  
American Society of Heating, Refrigerating and Air  
Conditioning Engineers (ASHRAE) Standard 52.1-92.  
—Initial Atmospheric Dust Spot Efficiency: 25.8%  
—Average Atmospheric Dust Spot Efficiency: 32.0%  
—Average Synthetic Dust Weight Arrestance: 92.0%  
—ASHRAE Dust Holding Capacity: 55g  
APPLICATION  
The F35F Expandapac Media Air Cleaner captures a  
significant amount of the airborne particles, 1.0 microns and  
larger from the air circulated through the unit.  
The above data is for a 16 x 25 in. filter.  
Contents  
Application...........................................................................  
Features ..............................................................................  
Ordering Information ...........................................................  
Specifications ......................................................................  
Planning the Installation ......................................................  
Installation and Checkout ....................................................  
Future Option ......................................................................  
Replacement Parts..............................................................  
1
1
2
3
4
7
9
9
Expandapac™ and Ultra-Web® are Trademarks of Donaldson Company, Inc.  
Copyright © 1998 Honeywell Inc.  
All Rights Reserved  
68-0178-2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F35F Expandapac™ MEDIA AIR CLEANER  
Filter Media:  
Expandapac.  
SPECIFICATIONS  
IMPORTANT  
Temperature Rating:  
-40°F to +125°F (-40°C to +52°C).  
The specifications in this publication do not include  
normal manufacturing tolerances; therefore, an  
individual unit may not exactly match the listed  
specifications. This product is tested and calibrated  
under closely controlled conditions, and some minor  
differences in performance can be expected if those  
conditions are changed.  
Capacity and Pressure Drop:  
F35 FILTER PRESSURE DROP VS AIR FLOW RATE  
0.30  
1
0.25  
0.20  
0.15  
0.10  
0.05  
0.00  
Model:  
F35F Expandapac Media Air Cleaner includes cabinet,  
access door, Expandapac media filter, filter frame, and  
combs.  
Application:  
Use with gas, oil, and electric forced warm air furnaces and  
with compressor cooling. Can be used with heat pumps if  
filter is changed regularly to prevent excessive pressure drop.  
400  
600  
800  
1000  
AIRFLOW (cfm)  
1200  
1400  
2
1600  
1800 2000  
20" X 25"  
Arrestance Efficiency:  
16" X 25"  
AND 20" X 20"  
Efficiency ratings are based on National Bureau of Standards  
Dust Spot Method using atmospheric dust and American  
Society of Heating, Refrigerating and Air-Conditioning  
Engineers Standard 52.1-92.  
1
2
WHEN FIRST INSTALLED. PRESSURE DORP INCREASES AS  
FILTER BECOMES LOADED. FILTER SHOULD BE REPLACED  
WHEN PRESSURE DROP REACHES 0.5 IN. WC (0.1 kPa).  
—Initial Atmospheric Dust Spot Efficiency: 25.8%  
—Average Atmospheric Dust Spot Efficiency: 32.0%  
—Average Synthetic Dust Weight Arrestance: 92.0%  
—ASHRAE Dust Holding Capacity: 55g  
MAXIMUM CAPACITY BASED ON 500 fpm FACE VELOCITY.  
M12002-A  
Fig. 2. Capacity pressure drop of  
F35 Expandapac Media Filter.  
The above data is for a 16 x 25 in. filter.  
The F35F removes particles as small as 1.0 microns.  
Dimensions:  
1-1/8 (29)  
DIM B  
(SEE TABLE)  
DIM A  
(SEE TABLE)  
7/8 (22)  
6-3/4 (171)  
DIM C (SEE TABLE)  
DIM D (SEE TABLE)  
7/8 (22)  
5/8  
(16)  
F35 SIZE  
DIM A  
DIM D  
DIM B  
DIM C  
IN.  
IN.  
MM  
IN.  
MM  
MM  
IN.  
MM  
IN.  
MM  
406 X 635  
508 X 635  
508 X 508  
16 X 25  
20 X 25  
20 X 20  
14 7/16  
18 7/16  
18 7/16  
367  
468  
468  
16 3/16  
20 3/16  
20 3/16  
411  
513  
513  
23 1/4  
23 1/4  
18 1/4  
591  
591  
457  
25 1/2  
25 1/2  
20 1/2  
648  
648  
521  
M6931  
Fig. 1. Installation dimensions in in. (mm) of air cleaner.  
68-0178—2  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
F35F Expandapac™ MEDIA AIR CLEANER  
Mounting:  
Applications with a Humidifier  
Mounts in any position in the return air duct next to the  
furnace blower compartment. Airflow must be in the direction  
of the arrow on the filter. Cabinet is sturdy enough to support  
weight of a residential furnace and evaporator coil.  
The media air filter is compatible with humidifiers. Avoid  
applications where water mist can reach the media. If an  
atomizing humidifier is used, the filter media will require  
replacement more often because of minerals in the water.  
Underwriters Laboratories, Inc.:  
UL 900, Class 2 listed.  
Choose Mounting Position  
The media air cleaner can be mounted in any position, but the  
arrow on the cartridge must point in the same direction as the  
airflow. See Fig. 3-10 for proper location of the media air  
cleaner for a variety of furnace installations. Note that the  
media air filter cabinet is sturdy enough to easily support the  
weight of the furnace and evaporator coil. See Fig. 4.  
Upgrade Path:  
The F35 uses the same cabinet as the F50 Electronic Air  
Cleaner. Upgrade requires installing the cell key, electronic  
cells, protective screens, and power box installation and wiring.  
Accessory:  
S830A Clogged Filter Indicator.  
Replacement Parts:  
Replace Expandapac media filter annually or more often if  
reduced airflow results in lower heating/cooling equipment  
performance. See Replacement Parts section for Media Filter  
and Frame/Comb replacement part numbers.  
PLANNING THE INSTALLATION  
Location  
Install the media air cleaner where all the air passing through  
the system is circulated through it. The best location is in the  
return air duct next to the blower compartment so the media air  
filter can help to keep the blower motor and evaporator coils  
clean. Do not mount in the supply air duct.  
For most efficient air cleaning, spread airflow evenly across  
the face of the media. If the duct is a different size than the  
media air cleaner cabinet, gradual transitions are required. If  
the duct turns sharply just before the air filter, turning vanes  
are required (Fig.12).  
M939A  
Fig. 3. Highboy furnace, with side installation.  
Media air cleaner is mounted vertically  
where return enters side inlet of furnace.  
Choose a location that is readily accessible for checking and  
replacing the filter. Allow at least 26 in. (660 mm) clearance in  
front of the unit for removal of the filter.  
Install the media air cleaner where the temperature will not  
exceed the ratings in the Specifications section.  
Applications with Air Conditioning  
Mount the media air filter upstream of the evaporator coil in a  
cooling system. The filter will help to keep the coil clean and  
reduce maintenance.  
Applications with a Charcoal Filter  
Add an activated charcoal filter to the air handling system to  
remove gaseous (nonparticulate) contaminants from the  
circulated air. A common residential application is to remove  
odors that cannot be removed by mechanical air filters. The  
activated charcoal filter, if used, should be installed  
downstream from the media air cleaner to protect the  
charcoal filter from lint and other particles.  
M940A  
Fig. 4 Highboy furnace, with installation  
beneath furnace. Media air cleaner is mounted  
horizontally where return enters from below.  
68-0178—2  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
F35F Expandapac™ MEDIA AIR CLEANER  
M6932-A  
Fig. 5. Highboy furnace, with closet installation.  
Media air cleaner is mounted vertically on  
furnace between furnace and louvered  
return air opening in closet door.  
M943A  
Fig. 7. Counterflow furnace, with media  
air cleaner mounted horizontally in return  
duct or plenum just above furnace.  
M942A  
Fig. 6. Lowboy furnace, with media air cleaner  
mounted horizontally in return plenum just  
above furnace and opposite heating plenum.  
M944A  
Fig. 8. Central fan installation, with media air cleaner  
mounted horizontally in central return duct.  
68-0178—2  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
F35F Expandapac™ MEDIA AIR CLEANER  
Turning Vanes  
If the media air cleaner is installed next to an elbow or angle  
fitting, add turning vanes inside the angle to distribute airflow  
more evenly across the face of the media. See Fig 12.  
Offsets  
If the duct connection to the furnace in a side installation  
allows less than 7 in. (178 mm) for mounting media air  
cleaner cabinet, attach an offset to the elbow. See Fig. 13.  
M945A  
DUCT SIZE CHANGED GRADUALLY TO PREVENT TURBULENCE.  
20 DEGREE EXPANSION PER SIDE PER  
FITTING (4 IN. PER RUNNING FOOT  
[100 MM PER 300 LINEAR MM])  
Fig. 9. Horizontal furnace, with media air cleaner mounted  
vertically in return duct near furnace.  
RETURN AIR  
DUCT  
TRANSITION FITTING  
M947A  
MEDIA AIR FILTER CABINET  
Fig. 11. Duct size changed gradually  
to prevent turbulence.  
M946A  
TURNING  
VANES  
Fig. 10.Two or more media air cleaners  
used in a high capacity system.  
Determining Sheet Metal Requirements  
The media air cleaner is adaptable to all new or existing  
forced air heating and cooling systems used in residential  
applications. Transitions or turning vanes may be required in  
some applications for effective media air cleaner operation.  
Transitions  
Transitions are needed when the duct is a different size than  
the media air filter cabinet. Follow these guidelines when  
fabricating:  
1. Use gradual transitions to reduce air turbulence and  
increase efficiency. See Fig. 11.  
M5651  
2. Use no more than 20 degrees (about 4 in. per running ft  
[100 mm per 300 linear mm]) of expansion on each side  
of a transition fitting.  
Fig. 12.Turning vanes installed in bend help  
distribute airflow evenly over face of media.  
68-0178—2  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
F35F Expandapac™ MEDIA AIR CLEANER  
Make sure that shop-fabricated sheet metal components,  
such as turning vanes, are available.  
Fasten the Cabinet to the Furnace  
Align the cabinet with the return air opening. Place blocks under  
the cabinet, as necessary, to make sure the unit is seated  
securely. Create an opening in the furnace to match the cabinet  
opening. Attach the cabinet securely to the furnace. Attach the  
unit directly or fit a starting collar in the furnace opening. Either  
drill holes and fasten with sheet metal screws or rivets, or use  
slip joints. If you are drilling holes, use a locking pliers to help  
hold the unit in place during drilling.  
OFFSET  
LESS  
THAN  
7 in.  
(178 mm)  
AT LEAST  
7 in.  
(178 mm)  
1
Install Turning Vanes  
Install turning vanes to help distribute air equally over the full  
surface of the upstream side of the media. Install the vanes  
whenever an abrupt 90 degree elbow is installed directly  
against the media air cleaner cabinet.  
1
REQUIRED TURNING VANES HELP DISTRIBUTE AIRFLOW EVENLY.  
M948A  
Fig. 13.Typical use of duct offset to  
make room for media air cleaner.  
Fasten Cabinet to Ductwork  
Fasten the side of the cabinet to the ductwork using sheet  
metal screws, rivets, or slip joints, as appropriate.  
INSTALLATION AND CHECKOUT  
Connect Ductwork  
When Installing this Product…  
Connect the vertical duct section to the elbow. If the vertical  
drop of the duct is less than 7 in. (178 mm) from the side of  
the furnace, shorten the horizontal trunk or attach an offset  
fitting to the elbow. See Fig. 13. When ductwork is properly  
aligned, connect the vertical duct to the horizontal trunk.  
1. Read these instructions carefully. Failure to follow them  
could damage the media air cleaner or cause a  
hazardous condition.  
2. Check the ratings given in the instructions and on the  
media air cleaner to make sure the product is suitable  
for your application.  
3. Installer must be a trained, experienced service  
technician.  
Seal Joints  
Seal all joints in the return air system between the media air  
cleaner and the furnace to prevent dust from entering the  
clean airstream.  
Remove Furnace Filter and  
Clean Blower Compartment  
Assemble Expandapac Media Filter  
1. Open the new media filter; expand it and set it upright  
Before starting the installation, remove and discard the existing  
furnace filter (if used). Thoroughly clean the blower  
compartment. If possible, power vacuum the ductwork to  
remove accumulated dust in an occupied home or remove  
construction dirt in a new home. The media air filter cannot  
remove dirt that has settled in the blower compartment and  
distribution ducts.  
on a flat surface.  
2. Insert one end panel tab into the retainers on the frame.  
Fold in the end panel flanges and push the tab  
completely in, making sure the end panel flanges are  
inside the frame flanges. See Fig. 14.  
3. Repeat step 2 on the opposite corner.  
Install the Cabinet  
The following procedure describes a typical side installation  
on an existing highboy furnace. Alternate procedures are  
noted as appropriate. Other changes in installation  
4. Flip over the assembly and repeat steps 2 and 3 on the  
remaining two corners.  
procedures may be necessary to complete your installation.  
5. Lay the filter assembly down flat so the arrows point up.  
Insert the combs as shown in Fig.15, aligning them with  
the notches in the end panel flanges. Make sure the  
combs are inserted completely.  
Review the Installation Plan  
Temporarily place the cabinet on the floor, oriented as it will  
be when installed. Measure to make sure the plan allows  
adequate clearance (at least 26 in. [660 mm]) for easy  
removal and replacement of the filter.  
68-0178—2  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
F35F Expandapac™ MEDIA AIR CLEANER  
END PANEL  
TAB  
FRAME PANEL  
RETAINER  
Checkout  
Visually check the installation. Make sure:  
Airflow is in the direction of the arrow on the  
Expandapac media air filter.  
Turning vanes and transitions, if used, are properly  
installed.  
Joints in sheet metal between media air cleaner and  
furnace are sealed.  
All sheet metal connections are complete.  
Original furnace filter was removed and blower  
compartment was cleaned.  
Replace any access doors removed during the Installation or  
Checkout.  
FRAME  
FLANGE  
Run the furnace or cooling system through one complete  
cycle to make sure the system operates as desired.  
END PANEL  
FLANGE  
FRAME  
PANEL  
Maintenance  
Replace the media filter when pressure drop across the  
media filter reaches 0.5 in. wc (0.1 kPa) or at least annually. If  
the media air filter is installed downstream from an atomizing  
humidifier or if the installation includes both heating and  
cooling, more frequent replacement may be necessary.  
Clogged media filter must be replaced promptly to avoid  
restricting airflow and reducing efficiency of the heating-  
cooling system. Record the replacement date in the space  
provided on the replacement media filter.  
Replace the Expandapac Media Filter as follows:  
1. Remove the cabinet door and pull out the dirty filter  
assembly.  
FRAME  
PANEL  
M6934  
2. Remove all the combs and two frame panels. Set them  
aside. Dispose of the dirty filter.  
Fig. 14. Assemble Expandapac media filter in frame.  
3. Open the new media filter; expand it and set it upright  
on a flat surface.  
Install Expandapac Media Filter  
4. Insert one end panel tab into the retainers on the frame.  
Fold in the end panel flanges and push the tab  
completely in, making sure the end panel flanges are  
inside the frame flanges. See Fig. 15.  
Slide the assembled Expandapac media filter into the cabinet,  
making sure the arrow on the cartridge points in the direction  
of the airflow.  
Replace the access door. Insert the tab on the bottom of the  
door into the slot in the cabinet. Swing the door closed and  
press it into place.  
5. Repeat step 4 on the opposite corner.  
6. Flip over the assembly and repeat steps 4 and 5 on the  
remaining two corners.  
COMBS (3 OR 4,  
DEPENDING ON  
FILTER SIZE)  
7. Lay the filter assembly down flat so the arrows point up.  
Insert the combs as shown in Fig.16, aligning them with  
the notches in the end panel flanges. Make sure the  
combs are inserted completely.  
8. Insert the new filter assembly into the cabinet and close  
the door.  
See Replacement Parts in the Specifications section. If desired,  
install the S830A Clogged Filter Indicator to allow visual  
indication of when the media needs replacing. Install and adjust  
the S830A by following the instructions provided with the unit.  
M6935  
Fig.15. Insert combs in media filter.  
68-0178—2  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
F35F Expandapac™ MEDIA AIR CLEANER  
FUTURE OPTION  
The F35F Expandapac Media Air Cleaner cabinet and filter  
are designed to be easily upgraded to an F50 Electronic Air  
Cleaner. An electronic air cleaner has the features to increase  
the comfort and enjoyment of your home:  
Captures up to 95% of airborne particles, 0.5 microns  
and larger that pass through the unit.  
Can save 10 to 15 percent in operating costs over the  
life of your equipment. Honeywell offers an exclusive  
10-year Clean Coil Guarantee.  
Protects your expensive HVAC equipment.  
No on-going filter replacements necessary because  
cells can be washed and restored to top efficiency.  
Increases home comfort.  
Easy to maintain.  
And it’s by Honeywell, a leader in indoor air quality  
products for over 30 years.  
High Efficiency Cleaning F50 Electronic Air Cleaner.  
REPLACEMENT PARTS  
3
1
2
M11200  
F35F part numbers are keyed to parts list.  
F35F Replacement Parts List  
No. Description  
16 x 25 in.  
20 x 25 in.  
203305AG (1)  
FC35A1027  
20 x 20 in.  
203305AG (1)  
FC35A1019  
1
2
Access Door  
203306AB (1)  
Expandapac Media Air Filter. Must be ordered in  
multiples of 6.  
FC35A1001  
3
Frame and Combs. Must be ordered in multiples of 6.  
FC35B1018  
FC35B1026  
FC35B1000  
68-0178—2  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
F35F Expandapac™ MEDIA AIR CLEANER  
68-0178—2  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
68-0178—2  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Home and Building Control  
Honeywell Inc.  
Honeywell Plaza  
P.O. Box 524  
Minneapolis MN 55408-0524  
Home and Building Control  
Honeywell Limited-Honeywell Limitée  
155 Gordon Baker Road  
North York, Ontario  
Honeywell Asia Pacific Inc.  
Room 3213-3225  
Sun Hung Kai Centre  
No. 30 Harbour Road  
Wanchai  
M2H 3N7  
Hong Kong  
Honeywell Europe S.A.  
3 Avenue du Bourget  
1140 Brussels  
Honeywell Latin American Region  
480 Sawgrass Corporate Parkway  
Suite 200  
Belgium  
Sunrise FL 33325  
Printed in U.S.A. on recycled  
paper containing at least 10%  
68-0178—2 L.C. Rev. 2-98  
post-consumer paper fibers.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Gravely Lawn Mower 205E+05 User Manual
Grizzly Biscuit Joiner G0612 User Manual
Guardian Technologies Portable Generator 02010 2 User Manual
Halfords Cyclometer 151640 User Manual
Hasselblad Digital Camera 503CW CFV User Manual
Hayter Mowers Trimmer 407F User Manual
Healthrider Home Gym HRT07920 User Manual
Honeywell Network Router Q7751A User Manual
Hoshizaki Ice Maker KM 1601MRH User Manual
HP Hewlett Packard All in One Printer Mopier 240 User Manual