Honeywell Air Cleaner F116 User Manual

F116A Self-Contained Ductable  
Commercial Air Cleaner  
SPECIFICATION DATA  
FEATURES  
Variety of filter configurations available to customize the air  
cleaner for any application.  
CPZ™(Charcoal Potassium Permanganate and Zeolite) disposable  
modules can be used for odor control.  
Three-speed, direct-drive, forward curve blower/motor circulates  
up to 2500 cfm (72 cu m/min) for large areas.  
Negative and positive pressure rooms can be created with the  
F116.  
APPLICATION  
The F116 Self-Contained Ductable Commercial Air Cleaner is  
designed for use in any application that requires the removal of  
airborne contaminants from an enclosed area. The air going to the  
unit and the discharged air can be transported in a network of  
ducting and plenums, or the unit can be used independently.  
SPECIFICATIONS  
Models:  
Static Pressure:  
F116A Self-Contained Ductable Commercial Air Cleaners are  
available in two cabinet sizes:  
Shorter cabinet: Uses a prefilter with one primary filter  
Longer cabinet: Uses a prefilter with two primary filters.  
Minimum: 1.2 in. W.G.  
Maximum: 1.85 in. W.G.  
Dimensions:  
See Fig. 1.  
Material:  
0.0508 in. 16 GA unpainted aluminum.  
Blower/Motor:  
Three-speed, direct-drive, forward curve.  
1070 rpm nominal speed.  
Thermal circuit breaker.  
Electrical Ratings:  
Voltage: 120 Vac, 60 Hz; 1 PHS, 14A.  
220 Vac, 50/60 Hz; 1PHS, 7A.  
Connections: Hard-wired.  
Running Load (All Three Fan Speeds): Must not exceed 14A at  
120V or 220V at 7A.  
Lubrication:  
Oil annually.  
Maximum Starting Loads:  
Filter Options:  
High Speed: 23A at 120V.  
High Efficiency Particulate Arrestance (HEPA) Filter (99.97%  
Efficiency).  
DOP (Di-Octyl Phthalate) Filter (95% Efficiency).  
ASHRAE Dust Spot Filter (95% Efficiency).  
ASHRAE Dust Spot Filter (65% Efficiency).  
CPZ™ Sorbent Modules (for odor control).  
11.5A at 220V.  
Medium and Low Speeds: 15A at 120V.  
7.5A at 220V.  
Air Volume, Internal Static Pressure and Installation Weight:  
All vary with air cleaner filter configuration.  
Approvals:  
Underwriters Laboratories Inc. Listing Pending.  
Canadian Underwriters Laboratories Inc.Certification Pending.  
The Honeywell Trademark is used under license from Honeywell  
Intellectual Properties, Inc. by Air-Pure Systems.  
Honeywell International Inc. makes no representations or warranties  
with respect to this product.  
68-3028-2 Revised 11-07  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graco Heat Pump 312877C User Manual
Graham Field Blood Pressure Monitor V223 User Manual
Groupe SEB USA T FAL Baby Monitor 912471 User Manual
Harbor Freight Tools Automobile Parts 41005 User Manual
Harbor Freight Tools Impact Driver 95310 User Manual
Harman Kardon Stereo Receiver AVR 7550HD User Manual
Hotpoint Washer AVTL 83 User Manual
HP Hewlett Packard Tablet Accessory 651176 002 User Manual
Husqvarna Pole Saw FS 413 User Manual
IBM Laptop 2082BKU User Manual