Heatcraft Refrigeration Products Refrigerator H IM 82B User Manual

Refrigeration  
System Installation  
H-IM-82B  
July 2008  
Part No. 25001901  
Replaces H-IM-82A (6/06)  
Refrigeration System  
For Outdoor Applications  
Table of Contents  
1. Owner's Installation Instructions  
Performance/Electrical Data  
Specifications....................................................................................2  
Dimensional Diagrams..................................................................3  
Space and Location Requirements  
Recommended Unit Placement.................................................4  
Rigging  
Mounting  
Inspection  
General Safety Information..........................................................5  
Standard Installation Procedure ................................................6  
Outdoor Unit Installation Instructions.....................................7  
2. Freezers  
Service Information  
Maintenance  
Sequence of Operation  
Freezer System Pre-Setpoints  
Electric Defrost Sequence of Operation  
Programming Electric Defrost Controls ........................... 8-10  
3. Coolers  
Installation and  
Operation Guide  
Defrost Controls  
Sequence of Operation  
Maintenance .................................................................................. 11  
4. Service Information  
System Troubleshooting Chart................................................ 12  
Replacement Parts....................................................................... 13  
5. Wiring Information  
Electrical Wiring Diagrams..................................................14-19  
6. Warranty Information ....................................................... 20  
© 2008 Heatcraft Refrigeration Products LLC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional Diagrams  
Figure A. Medium Cabinet Dimensions without weather hood  
Models PTT 021, 031, 044, 047, 063, 072  
*
25" x 25" panel opening required for evaporator section of medium cabinet sizes.  
* 21.5" with weather hood.  
Figure B. Large Cabinet without weather hood  
Models PTT 052, 069, 099, 128  
*
25" x 381/2" panel opening required for evaporator section of large cabinet sizes.  
* 23.5" with weather hood.  
Figure C. Medium Cabinet with weather hood  
Models PTT 021, 031, 044, 047, 063 and 072  
Figure D. Large Cabinet with weather hood  
Models PTT 052, 069, 099 and 128  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Recommended Unit Placement For PTT Models  
Some general rules for the evaporator section placement which  
must be followed are:  
1.  
Ensure that the structural integrity of the box can  
withstand the weight of the top mounted equipment.  
2.  
3.  
The air pattern must cover the entire room.  
NOTE: Always avoid placement of  
units directly above doors  
and door openings.  
NEVER locate the evaporator section over doors.  
4.  
5.  
Location of aisles, racks, etc. must be known.  
Never remove or unlock any panel cam-locks to install  
top mounted equipment.  
The size and shape of the storage will generally determine the type  
and number of units to be used and their location.  
Evaporator  
Section  
Compressor  
Section  
Top View  
One System  
Evaporator  
Airflow  
Evaporator  
Section  
Evaporator  
Section  
Compressor  
Section  
2 x Width  
Min.  
W
Min.  
Compressor  
Section  
W
Min.  
Top View  
Systems  
Evaporator  
Airflow  
Evaporator  
Airflow  
Two  
Multiple units must be spaced  
properly to provide adequate air  
circulation.  
W = Unit Width  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Rigging  
Mounting  
Rigging holes are provided on all models. Caution should be  
exercised when moving these units. To prevent damage to  
the unit housing during rigging, cables or chains used must  
The system requires an opening in the ceiling to the  
dimensions stated on page 3. Mounting rails are located  
at both ends of the chassis. Mounting rails may be used to  
be held apart by spacer bars. The mounting platform or base attach unit to ceiling. Through-bolts should be insulated or  
should be level and located so as to permit free access of  
supply air. The unit weather hood may be removed for the  
non-conductive to prevent sweating. The chassis is weather  
stripped around the air grille and will seal to the box roof.  
rigging process. The condensing unit cover (wrapper) should The trim ring (shipped loose), when provided, should be  
be left in place.  
installed around the air diffuser when secured with the  
hardware provided. Be sure to adhere to your local standard  
construction codes.  
Access Requirements  
Provide adequate space at the compressor end of the unit for  
servicing. Provide two (2) feet of space above unit for service.  
Trim Pieces (4)  
Overlap as Shown  
Trim Ring  
Installation  
Detail  
Ceiling of Walk-in.  
Evaporator Grill  
Self Drilling Screw  
Inspection  
General Safety Information  
1. Each shipment should be carefully checked against the  
bill of lading.  
1. Installation and maintenance to be performed only by  
licensed contractor.  
2. The shipping receipt should not be signed until all items  
listed on the bill of lading have been accounted for.  
2. Ensure that the structural integrity of the box can  
withstand the weight of the  
unit weights).  
(See page 2, Table 3 for  
3. Check packaging for signs of damage.  
4. Any shortage or damages should be immediately  
reported to the delivering carrier.  
3. Avoid contact with sharp edges and coil surfaces.  
They are a potential injury hazard. Wear gloves during  
moving and rigging.  
5. Damaged material becomes the delivering carrier’s  
responsibility, and should not be returned to the  
manufacturer unless prior approval is given to do so.  
4. Make sure all power sources are disconnected before  
any service work is done on units.  
6. When unpacking the system, care should be taken to  
prevent damage.  
7. Avoid removing the shipping base until the unit has been  
moved to the final destination.  
8. Complete warranty return card for each unit and mail to  
Heatcraft Refrigeration Products.  
Table 4. Control Factory Default Settings  
PTT  
Temperature  
Set Points  
Defrost  
Start Times  
Defrost Duration  
(Maximum)  
Drip  
Time  
Fan  
Delay  
Defrost Termination  
Set Point  
Models  
Cooler Models  
All cabinet sizes  
Every 3 hours of  
compressor run time  
35˚F  
60 min.  
40 min.  
38˚F  
65˚F  
Freezer Models  
Med. & Lg. cabinet  
-10˚F  
4 / day  
2 min.  
2 min.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
The Outdoor  
comes standard with the  
following additional components:  
Crankcase Heater  
Drain Line Heater  
Weather Hood  
Fan Cycling  
(Pressure on 1 fan models, Pressure and Ambient  
on 2 fan models).  
Standard Installation Procedure  
PTT Models  
For outdoor use  
Condensate Drain  
Outlet Location  
1. Provide a 25" X 25" (medium cabinet) or  
25" X 38.5" (large cabinet) opening in the  
roof of walk-in cooler or as specified by the  
panel manufacturer.  
8. Remove compressor compartment cover for  
access to electrical box.  
9. Connect power wiring in accordance with all  
applicable building and electrical codes.  
2. Apply silicone caulk around the perimeter of roof  
opening. Place the curb on roof of cooler. It is  
recommended that the curb be fastened to  
the roof panels using non-conductive bolts or  
insulating the bolt heads. Bolt heads should be  
countersunk or low profile to prevent contact with  
10. Reinstall condensing unit cover(s).  
11. Reinstall the protective weather hood.  
(See Figure 4, page 7)  
the  
system. (See Figure 1, page 7) Check the  
units require  
top of the curb with a level.  
12. Apply power and check for proper operation.  
a surface that is within 1° of level or better and no  
more than a 5/8" drop per 3 feet  
(17mm drop per meter).  
Drain Line  
3. Install the membrane onto the roof of the box and  
over the curb. Fasten to roof per panel  
A condensate drain outlet is located on the side of the  
compressor compartment. Field piping may be connected  
to the outlet provided it is adequately sloped and heated  
for freezing weather conditions. There is a drain line "P" trap  
located in the PTT unit.  
manufacturer's instructions. The membrane  
material should be slit over the evaporator grill  
opening the flaps allowed to drape into the hole  
2" - 4". (See Figure 2, page 7) Care should be taken  
during the membrane installation to prevent  
bunching or folding which could affect the gasket-  
to-curb sealing or trap rainwater adjacent to the  
curb.  
General Safety information:  
Do NOT lift the  
by the weather hood.  
4. Remove the weather hood from the  
system.  
This product is not designed to be transported while  
installed or operating.  
The compressor compartment cover(s) should be  
left in place during lifting/rigging.  
5. Place  
system onto curbing and center over  
opening in roof box. (See Figure 3, page 7)  
6. It is recommended that the  
system be  
secured to the curb with wood screws. Seal  
the screw heads as necessary to prevent  
moisture from entering beneath the membrane.  
Additional caulk may be applied around the  
perimeter of the evaporator box gasket. The  
compressor compartment should not be caulked.  
7. Install trim pieces (if used) around the ceiling  
opening in cooler.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
PTT Models  
Example Outdoor Curb Installation  
(Curb supplied by others)  
This area of  
curb may be solid.  
Figure 1. Curb placed on roof of walk-in cooler.  
Figure 2. Roof membrane placed over curb.  
Note: Do not caulk  
around the base of com-  
pressor compartment.  
Figure 3. PTT unit placed on roof of walk-in color.  
(see rigging instructions).  
Figure 4. Weather hood installed after electrical service  
connection.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Medium and Large Cabinet Freezers  
3. The temperature/defrost control energizes the  
Service Information  
compressor contactor, starting the compressor and  
condenser fan(s).  
All  
units are designed for maximum durability, reliability and  
simplicity.  
comes to you ready for operation, fully charged and  
4. Freezer evaporator fans will be energized by the  
temperature/defrost control when the coil temperature  
reaches 35°F or fan delay time has elapsed.  
with all controls preset at the factory. The following information is  
provided as an aid in the event that service is required.  
Maintenance  
The evaporator section of a  
system should be checked at  
Freezer Defrost Control -  
Medium & Large Cabinet  
freezer units come factory equipped with an electronic  
temperature/defrost control. There are 2 different models of  
electronic control used and it is important to determine which  
one is present on your unit before altering any factory settings.  
Please refer to the picture of the controller display on this page  
to determine the model used. Instructions for any necessary  
reprogramming are included in this manual on pages 8-10.  
least once for proper defrosting because the amount and pattern  
of frosting can vary greatly. The frost build-up is dependent on  
the temperature of the room, the type of product being stored,  
how often new product is brought into the room and percentage  
of time the door to the room is open. It may be necessary to  
periodically change the number of defrost cycles or adjust the  
duration of defrost.  
System Standard Maintenance Guidelines  
After first year of operation and under normal usage, maintenance  
should cover the following items at least once every six months:  
1. Check and tighten ALL electrical connections.  
2. Check all wiring and insulators.  
3. Check contactors for proper operation and for worn  
contact points.  
Dixell Electronic Controller  
The Dixell XR-60CX and the Dixell XR-60C are fully  
configurable electronic refrigeration controllers. All  
parameter values are reprogrammable and are stored in the  
non-volatile memory.  
4. Check all fan motors. Tighten motor mount bolts/ nuts  
and tighten fan set screws.  
5. Clean the condenser coil surface.  
6. Check the operation of the control system. Make certain  
all safety controls are operating properly.  
7. Check that all defrost controls are functioning properly.  
8. Clean the evaporator coil surface.  
The controllers use two levels of programming that can be  
accessed through the keypad. The first level is the user level.  
It gives access to six settings; temp. differential, defrost cycle  
intervals, defrost termination temperature, draining time,  
defrost fan delay, and fan stop temperature.  
9. Clean the drain pan and check the drain pan and drain line  
for proper drainage.  
The second level is the service level. It allows access to all  
other parameters. It is recommended that changes in this  
level be made only by a qualified technician.  
Refrigeration Sequence of Operation  
1. Power is provided to the temperature control, compressor  
contactor and cooler evaporator fans.  
Front Panel Commands  
2. The temperature controller closes and energizes the  
compressor contactor, starting the compressor,  
evaporator and condenser fan(s).  
3. When the system reaches the desired box temperature,  
the temperature control will de-energize the compressor  
contactor. Evaporator fans will continue to operate at  
this point.  
XR-60CX Controller  
XR-60C Controller  
4. When the fixture temperature rises above the set point  
and minimum off-time has elapsed, the temperature  
control will close and re-energize the compressor contactor.  
USE OF LEDS  
Each LED function is described in the following table.  
LED  
LED MODE  
FUNCTION  
Electric Defrost Sequence of Operation  
for Freezers  
1. During normal operation, at the preset time intervals,  
the temperature/defrost control will de-energize the  
compressor contactor and evaporator fans and energize  
the defrost heaters. These functions are controlled  
through relays on the controller.  
ON  
Compressor enabled  
-Programming Phase (flashing with )  
- Anti-short cycle delay enabled  
Flashing  
ON  
Defrost enabled  
- Programming Phase (flashing with )  
- Drip time in progress  
Flashing  
ON  
2. When the coil has defrosted fully and has reached the  
preset coil temperature (as sensed by the coil  
Fans enabled  
temperature sensor) the defrost heater de-energizes  
and the fan delay and drip sequences begin.  
Fans delay after defrost in progress  
(60CX only)  
A temperature alarm occurred  
Flashing  
ON  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
MAIN FUNCTIONS  
NOW YOU ARE IN THE HIDDEN MENU.  
3. Select the required parameter.  
HOW TO SEE THE SETPOINT  
4. Press the “SETkey to display its value (Now only the LED  
is blinking).  
1. Push and immediately release the SET key:  
the display will show the Set point value.  
5. Use UP or DOWN to change its value.  
6. Press “SETto store the new value and move to the  
following parameter.  
HOW TO CHANGE THE SETPOINT  
1. Push the SET key for more than 2 seconds to change the  
Set point value;  
To exit: Press SET + UP or wait 15s without pressing a key.  
NOTE: the set value is stored even when the procedure is  
exited by waiting the time-out to expire.  
2. The value of the set point will be displayed and the LED  
starts blinking;  
3. To change the Set value push the UP or DOWN arrows  
within 10s.  
HOW TO SEE THE ALARM DURATION AND MAX (MIN)  
TEMPERATURE  
4. To memorise the new set point value push the SET key  
again or wait 10s.  
If the alarm LED is on, an alarm has taken place.  
To see the kind of alarm, the max (min) reached temperature  
and alarm duration do as follows:v  
HOW TO START A MANUAL DEFROST  
1. Push the Up or Down key.  
Push the DEF key for more than 2 seconds  
2. On the display the following message is shown::  
HALfor high temperature alarm (“LALfor the  
minimum allarm), followed by the Maximum  
(minimum) temperature.  
and a manual defrost will start.  
HOW TO CHANGE A PARAMETER VALUE  
To change the parameter’s value operate as follows:  
1. Use “UPor “DOWNto change its value.  
2. Press “SETto store the new value and move to the  
following parameter.  
To exit: Press SET + UP or wait 15s without pressing a key.  
NOTE: the set value is stored even when the procedure is  
exited by waiting the time-out to expire.  
Then the “tiM(tiMe) message is displayed, followed by  
the “Durationin h.mm.  
3. Then the instrument displays the temperature once  
again.  
NOTE1: if an alarm is still occurring the “timshows the  
partial duration.  
NOTE2: the alarm is recorded when the temperature come  
THE HIDDEN MENU  
The hidden menu Includes all the parameters of the instrument. back to normal values  
HOW TO ENTER THE HIDDEN MENU  
HOW TO RESET A RECORDED ALARM OR ONE THAT IS  
STILL OCCURRING  
1. Enter the Programming mode by  
pressing the Set + DOWN key for 3s  
(LED 1 and start blinking).  
2. When a parameter is displayed keep  
pressed the Set + DOWN for more than 7s.  
The Pr2 label will be displayed immediately  
followed from the HY parameter.  
1. Hold the SET key pressed for more than 3s, while the  
recorded alarm is displayed. (the rSt message will be  
displayed)  
2. To confirm the operation, the “rStmessage starts  
blinking and the normal temperature will be displayed  
DEFAULT PARAMETER SETTINGS  
DEFAULT SETTINGS  
Menu/User  
Level  
Possible  
Settings  
Label Characteristic  
Description  
Low  
Medium  
Temp.  
High  
Temp.  
Temp.  
REGULATION  
SEt Set Point  
LS ~ US  
1~ 45  
-10  
3
34  
3
38  
3
(0,1 ÷ 25,5°C / 1÷255 °F) Intervention  
differential for set point. Compressor  
Cut IN is Set Point + differential (Hy).  
Compressor Cut OUT is when the  
temperature reaches the set point  
Hy  
Differential  
Pr1  
(- 50°C÷SET/-58°F÷SET): Sets the minimum  
value for the set point..  
(SET÷110°C/ SET÷230°F). Set the maximum  
value for set point.  
LS Minimum set point  
US Maximum set point  
Pr2  
Pr2  
Pr2  
-67 ~ SET  
SET ~ 302F  
-21~21  
-23  
37  
0
25  
40  
0
33  
45  
0
Thermostat probe (-12.0÷12.0°C; -120÷120°F) allows to adjust  
Ot  
OdS  
AC  
calibration  
possible offset of the thermostat probe  
(0÷255min) This function is enabled at  
Outputs activation the initial start up of the instrument and  
0 ~ 255  
minutes  
Pr2  
Pr2  
Pr2  
0
4
6
0
4
6
0
4
6
delay at start up  
inhibits any output activation for the period  
of time set in the parameter  
(0÷50 min) minimum interval between the  
compressor stop and the following restart  
(0÷255 min) time during which the  
compressor is OFF in case of faulty  
thermostat probe. With COF=0  
compressor is always active  
Anti-short cycle  
delay  
0 ~ 50  
minutes  
Compressor OFF  
COF time with faulty  
probe  
0 ~ 255  
minutes  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
DISPLAY  
°C=Celsius; °F=Fahrenheit. WARNING: When  
the measurement unit is changed the SET  
point and the values of the parameters Hy,  
LS, US, Ot, ALU and ALL have to be checked  
and modified if necessary  
°C = Celsius  
Temperature  
measurement unit  
CF  
Pr2  
Pr2  
°F  
°F  
°F  
°F  
=Fahrenheit  
DEFROST  
EL = electric  
defrost / in  
= hot gas  
defrost  
tdF Defrost type  
EL = electrical heater; in = hot gas  
EL  
EL  
EL  
(-50÷50 °C/ -58÷122°F) (Enabled only when  
Defrost termination EdF=Pb) sets the temperature measured by  
dtE  
IdF  
Pr1  
Pr1  
-58~122  
65  
6
65  
6
38  
6
temperature  
the evaporator probe, which causes the end  
of defrost  
Interval between  
defrost cycles  
(0÷120h) Determines the time interval  
between the beginning of two defrost cycles  
0 ~ 120  
hours  
(0÷255min) When P2P = n, (not evaporator  
probe: timed defrost) it sets the defrost  
duration, when P2P = y (defrost end based  
on temperature) it sets the maximum  
length for defrost  
(0÷120 min) time interval between reaching  
defrost termination temperature and the  
restoring of the control’s normal operation.  
This time allows the evaporator to eliminate  
water drops that might have formed due  
to defrost  
(Maximum) length  
for defrost  
0 ~ 255  
MdF  
Pr2  
Pr1  
40  
2
40  
2
60  
0
minutes  
0 ~ 255  
minutes  
Fdt Drip time  
FANS (XR60CX ONLY)  
Fans delay after  
(0÷255min) Interval between end of defrost  
and evaporator fans start  
0 ~ 255  
Not  
Fnd  
Pr1  
Pr2  
2
2
defrost  
minutes  
Applicable  
(0÷59°C; Fct=0 function disabled). If the  
difference of temperature between the  
evaporator and the room probes is more  
than the value of the Fct parameter, the  
fans are switched on  
Temperature  
differential  
Not  
Applicable  
Fct  
0~90  
10  
10  
avoiding short  
cycles of fans  
(-50÷50°C/122°F) setting of temperature,  
detected by evaporator probe, above  
which fans are always OFF  
Fans stop  
FSt  
Not  
Pr1  
Pr2  
-58~122  
35  
35  
temperature  
Applicable  
ALARMS  
(Ab; rE) Ab= absolute temperature: alarm  
temperature is given by the ALL or ALU  
Temperature alarms values. rE = temperature alarms are  
rE = relative  
to set point  
Ab =  
ALC  
Ab  
Ab  
Ab  
configuration  
referred to the set point. Temperature alarm  
is enabled when the temperature exceeds  
the “SET+ALUor “SET-ALLvalues  
absolute  
(SET÷110°C; SET÷230°F) when this  
temperature is reached the alarm is  
enabled, after the “ALddelay time  
-50.0 ÷ SET°C; -58÷230°F when this  
temperature is reached the alarm is  
enabled, after the “ALddelay time  
MAXIMUM  
ALU  
ALL  
Pr2  
Pr2  
ALL~ 302  
-58~ ALu  
38  
50  
15  
50  
30  
temperature alarm  
Minimum  
temperature alarm  
-25  
ALARM SIGNALS  
Message  
Cause  
Outputs  
Message  
Cause  
Outputs  
Compressor output  
according to par. “Conand  
“COF”  
Minimum  
temperature alarm  
Room probe  
failure  
“LA”  
Outputs unchanged.  
“P1”  
“P2”  
“HA”  
Compressor and fans  
restarts  
“dA”  
“EA”  
Door open  
Evaporator probe  
failure  
Defrost end is timed  
Outputs unchanged.  
External alarm  
Output unchanged.  
Maximum  
temperature alarm  
Reprinted with permission from Dixell.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All Cooler Models  
Cooler Defrost Control  
Maintenance  
Cooler units utilize an electronic temperature control.  
The temperature may be adjusted by setting the dial. This  
control is preset to provide 3 hours of compressor run time  
The evaporator section of a  
at least once for proper defrosting because the amount  
and pattern of frosting can vary greatly. The frost build-up  
system should be checked  
between defrost cycles. Defrosts are temperature terminated is dependent on the temperature of the room, the type of  
and cannot be reprogrammed. The temperature control  
is programmed for minimum on cycle of one minute and  
minimum off cycle of four minutes.  
product being stored, how often new product is brought  
into the room and percentage of time the door to the room  
is open.  
Air Defrost Sequence of Operation  
for Coolers  
System Standard Maintenance Guidelines  
After first year of operation and under normal usage,  
maintenance should cover the following items at least once  
every six months:  
Air defrost units are preprogrammed for 3 hours of  
compressor run time between defrosts. These periods are  
not reprogrammable. After 3 hours, the temperature control  
will turn the compressor off. When the coil temperature  
reaches 38°F, the control will terminate the defrost cycle.  
1. Check and Tighten ALL electrical connections.  
2. Check all wiring and insulators.  
3. Check contactors for proper operation and for worn  
contact points.  
Room Thermostat Settings:  
• Approximate dial settings of control  
0 = Unit off (not an electrical disconnect)  
1 = 52°F (11°C)  
4. Check all fan motors. Tighten motor mount bolts/nuts  
and tighten fan set screws.  
5. Clean the condenser coil surface.  
2 = 49°F (9°C)  
3 = 45°F (7°C)  
4 = 41°F (5°C)  
5 = 38°F (3°C)  
6. Check the operation of the control system. Make  
certain all safety controls are operating properly.  
7. Check that all defrost controls are functioning properly.  
8. Clean the evaporator coil surface.  
6 = 34°F (1°C)  
9. Clean the drain pan and check the drain pan and  
drain line for proper drainage.  
NOTE: If power is interrupted to the unit during the  
refrigeration off-cycle (system at temperature setpoint,  
compressor o), the thermostat will initiate an extra defrost  
period approximately one hour after power is restored.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 5.  
System Troubleshooting Chart  
PROBLEM  
Compressor  
POSSIBLE CAUSES  
1. Main switch open.  
POSSIBLE CORRECTIVE STEPS  
1. Close switch.  
will not run  
2. Fuse blown.  
2. Check electrical circuits and motor winding for shorts or grounds.  
Investigate for possible overloading. Replace fuse after fault is corrected.  
3. Overloads are automatically reset. Check unit closely when unit comes  
back on line.  
3. Thermal overloads tripped.  
4. Defective contactor or coil.  
4. Repair or replace.  
5. System shut down by safety devices.  
5. Determine type and cause of shutdown and correct it before resetting  
safety switch.  
6. No cooling required.  
7. Motor electrical trouble.  
8. Loose wiring.  
6. None. Wait until calls for cooling.  
7. Check motor for open windings, short circuit or burn out.  
8. Check all wire junctions. Tighten all terminal screws.  
Compressor  
1. Flooding of refrigerant into crankcase.  
2. Worn compressor.  
1. Check setting of expansion valves.  
2. Replace.  
noisy or vibrating  
High  
1. Non-condensables in system.  
2. Fan not running.  
1. Remove the non-condensables.  
2. Check electrical circuit. Replace if motor fails.  
3. Clean.  
discharge  
pressure  
3. Dirty condenser coil.  
4. System overcharged with refrigerant.  
4. Reclaim refrigerant and recharge proper amount.  
Low discharge  
pressure  
1. Insufficient refrigerant in system.  
2. Low suction pressure.  
1. Check for leaks. Repair and add charge.  
2. See corrective steps for low suction pressure.  
High suction  
pressure  
1. Excessive load.  
1. Reduce load or add additional equipment.  
2. Check remote bulb. Regulate superheat.  
2. Expansion valve overfeeding.  
Low  
1. Lack of refrigerant.  
1. Check for leaks. Repair and add charge (see refrigerant charge chart).  
2. Clean.  
suction  
pressure  
2. Evaporator dirty or iced.  
3. Expansion valve malfunctioning.  
4. Condensing temperature too low.  
3. Check and reset for proper superheat.  
4. Check ambient temp, 50°F to 100°F.  
Compressor  
1. Operating beyond design conditions.  
2. Dirty condenser coil.  
1. Add equipment so that conditions are within allowable limits.  
2. Clean coil.  
thermal protector  
switch open  
3. Overcharged system.  
3. Reduce charge (see refrigerant charge).  
Fan(s) will  
1. Main switch open.  
1. Close switch.  
not operate  
2. Blown fuses.  
2. Replace fuses. Check for short circuits or overload conditions.  
3. Replace motor.  
3. Defective motor.  
4. Defective defrost control.  
5. Unit in defrost cycle.  
4. Replace defective component.  
5. Wait for completion of cycle.  
6. Coil does not get cold enough to reset thermostat  
6. Adjust fan delay setting of control. See Defrost Section page 8.  
Room  
1. Control cut out set too high.  
2. Superheat too high.  
3. System low on refrigerant.  
4. Coil iced-up.  
1. Adjust control.  
temperature  
too high  
2. Adjust thermal expansion valve.  
3. Add refrigerant. See refrigerant charge chart.  
4. Manually defrost coil. Check defrost controls for malfunction.  
Ice accumulating  
on ceiling around  
evaporator and/or  
on fan guards'  
1. Defrost duration is too long.  
1. Adjust defrost termination temp on control. See page 8.  
2. Adjust fan delay setting or replace bad sensor.  
3. Replace defective control or sensor. See page 10 error codes.  
4. Adjust number of defrosts.  
2. Fan delay not delaying fans after defrost period.  
3. Defective defrost control or sensor.  
4. Too many defrosts.  
venturi or blades  
Coil not clearing  
of frost during  
defrost cycle.  
1. Coil temperature not getting above freezing  
point during defrost.  
1. Check heater operation.  
2. Not enough defrost cycles per day.  
3. Defrost cycle too short.  
2. Adjust control for more defrost cycles.  
3. Adjust defrost control, defrost duration setting.  
4. Replace defective component. See page 10 error codes.  
4. Defective defrost control or sensor.  
Ice accumulating  
in drain pan  
1. Defective heater.  
1. Replace heater.  
2. Unit not installed properly (out of level)  
3. Drain line plugged.  
2. Check and adjust if necessary. See pages 7, 8.  
3. Clean drain line.  
4. Defective control.  
4. Replace defective component.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Replacement Parts by  
Commercial Refrigeration Parts  
Right source. Right parts. Right now.  
InterLink™ is your link to a complete line of dependable and certified commercial refrigeration  
parts, accessories and innovative electronic controls for all Heatcraft Refrigeration Products (HRP)  
equipment. At InterLink, we provide our wholesalers with a comprehensive selection of product  
solutions and innovative technologies for the installed customer base. And every product is built  
to ensure the same high performance standards with which all HRP brands are built — backed by  
a dedicated team to serve every customer need, delivering at the best lead times in the industry.  
Dependable. Versatile. Courteous.  
Finally, one simple source for all your replacement needs from a name you can trust.  
Coolers  
Freezers  
Part Description  
Fan Blades  
Part Number  
Evaporator  
Condenser  
22901901  
22900701  
1
1
2
1
2
1
3
2
3
2
3
2
3
2
1
1
2
1
2
3
2
3
3
2
3
2
1
2
Fan Motors  
208/230V Evaporator  
208/230V Condenser  
Evap. Fan Motor Bracket  
Cond. Fan Motor Bracket  
25307801**  
25307801  
4000104  
1
1
1
1
2
1
2
1
2
1
2
1
3
2
3
2
3
2
3
2
3
2
3
2
3
2
3
2
1
1
1
1
2
1
2
1
2
1
2
1
3
2
3
2
3
2
3
2
3
2
3
2
3
2
3
2
23103301  
Contactors  
25A, 208-240V  
20A, 230V  
2259996  
1
1
1
1
034915200  
1
1
1
1
1
1
1
1
1
1
1
1
1
3
1
1
1
3
1
1
1
3
1
1
1
1
1
1
Temperature Control  
Freezer Defrost/Temp Control Kit 208/230V*  
Temp Control Cooler 208/240V Kit*  
Heater Limit Thermostat  
Defrost Heaters  
89814701  
89814601  
5708L  
1
1
1
1
1
1
230V Defrost Heaters  
4312F  
4313F  
230V Defrost Heaters  
3
3
3
3
Outdoor Parts  
Fan Pressure Control  
28917301  
5521R  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Fan Temperature Control  
Drain Line Heater  
24753401  
28917401  
50047901  
50047801  
1
1
1
1
1
1
1
1
1
Drain Line Heater T'stat  
Weather Hood Medium  
Weather Hood Large  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
*Kits include control, sensors, mounting hardware and instructions.  
**PSC motor option (H designation on end of model name): part 25307801 = 25308601, part 25307701 = 25308501,  
part 25303201 = 25399201, part 25300101 = 25308501. Contact InterLink Parts at 800-686-7278.  
Whenever possible, replacement parts are to be obtained from one of our local authorized wholesalers. Replacement parts which are  
covered under the terms of the warranty statement on the back cover of this manual, will be reimbursed for total part cost only. The  
original invoice from the parts supplier must accompany all warranty claims for replacement part reimbursement. Heatcraft Refrigeration  
Products reserves the right to adjust the compensation amount paid on any parts submitted for warranty reimbursement when a parts  
supplier's original invoice is not provided with a claim.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Medium and Large Cabinet Models Wiring. 208-230/1/60 voltages.  
Cooler - Air Defrost Systems - Single Phase  
Diagram 1. Wiring Diagram for  
System, Air Defrost 208-230/1/60 (B): Models PTT047H2B, PTT063H2B,  
PTT072H2B, PTT099H2B, and PTT128H2B.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Medium and Large Cabinet Models Wiring. 208-230/1/60 voltages  
Indoor and Outdoor Models with Dixell XR-60C Controller  
Freezer - Electric Defrost Systems - Single Phase  
Diagram 2. Wiring Diagram for  
System, Electric Defrost 208-230/1/60 (B): Models PTT021L6B, PTT031L6B,  
PTT044L6B, PTT052L6B, and PTT069L6B.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Medium and Large Cabinet Models Wiring. 208-230/1/60 voltages  
Indoor and Outdoor Models with Paragon Controller  
Diagram 3. Wiring Diagram for  
System, Electric Defrost 208-230/1/60 (B): Models PTT021L6B, PTT031L6B,  
PTT044L6B, PTT052L6B and PTT069L6B.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Large Cabinet Models Wiring. 208-230/3/60 voltage.  
Cooler - Air Defrost Systems - Three Phase  
Diagram 4. Wiring Diagram for  
System, Air Defrost 208-230/3/60 (C): Models PTT099H2C and PTT128H2C.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Large Cabinet Models Wiring. 208-230/3/60 voltage  
Indoor and Outdoor Models with Dixell XR-60C Controller  
Freezer - Electric Defrost Systems - Three Phase  
Diagram 5. Wiring Diagram for  
only.  
System, Electric Defrost 208-230/3/60 (C): Models PTT052L6C and PTT069L6C  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Large Cabinet Models Wiring. 208-230/3/60 voltage  
Indoor and Outdoor Models with Paragon Controller  
Freezer - Electric Defrost Systems - Three Phase  
Diagram 6. Wiring Diagram for  
only.  
System, Electric Defrost 208-230/3/60 (C): Models PTT052L6C and PTT069L6C  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Warranty Statement  
The following conditions should be adhered to when installing this  
unit to maintain the manufacturers warranty:  
HeatcraftRefrigerationProductsLLCwarrantstoitsdirectpurchasers  
thatthe  
product,exceptServiceParts,manufacturedbyHeatcraft  
RefrigerationProductsLLCshallbeofamerchantablequality, freeof  
defects in material or workmanship, under normal use and service  
for a period of two (2) years from date of original installation, or  
thirty (30) months from date of shipment by Heatcraft Refrigeration  
Products LLC, whichever first occurs. Service Parts, for product out  
of original warranty, should be so warranted for a period of twelve  
(12) months from date of shipment. Any product covered by this  
order found to Heatcraft Refrigeration Products LLC's satisfaction to  
be defective upon examination at Heatcraft Refrigeration Products  
LLC's factory will, at Heatcraft Refrigeration Products LLC's option,  
be repaired or replaced and returned to Buyer via lowest common  
carrier,orHeatcraftRefrigerationProductsLLCmayatitsoptiongrant  
Buyer a credit for the purchase price of the defective article. Upon  
return of a defective product to Heatcraft Refrigeration Products  
LLC's plant, freight prepaid, by Buyer, correction of such defect by  
repair or replacement, and return freight via lowest common carrier,  
shallconstitutefullperformancebyHeatcraftRefrigerationProducts  
LLC of its obligations hereunder.  
(a)  
The power supply to the unit must meet the  
following conditions:  
A. Three phase voltages must  
be +/- 10% of nameplate  
ratings. Single phase must be  
within +10% or -5% of  
nameplate ratings.  
B. Phase imbalance cannot  
exceed 2%.  
(b)  
(c)  
All control and safety switch circuits must be  
properly connected according to the wiring  
diagram.  
The factory installed wiring must not be  
changed without written factory approval.  
HermeticcompressorsfurnishedbyHeatcraftRefrigerationProducts  
LLC are subject to the standard warranty terms set forth above,  
except that motor compressor replacements or exchanges shall  
be made through the nearest authorized wholesaler of the motor  
compressor manufacturer (not at Heatcraft Refrigeration Products  
LLC's factory) and no freight shall be allowed for transportation of  
the motor compressor to and from the wholesaler.The replacement  
motor compressor shall be identical to the model of the motor  
compressor being replaced. Additional charges which may be  
incurred throughout the substitution of other than identical  
replacements are not covered by this warranty.  
The foregoing is in lieu of all other warranties, express or implied,  
notwithstandingtheprovisionsoftheuniformcommercialcode,the  
Magnuson-MossWarranty-FederalTradeCommissionImprovement  
Act, or any other statutory or common law, federal or state.  
Optional Three-Year Extended Compressor  
Warranty  
TheEquipmentDealermaypurchasefortheOwneratthetimeofthe  
originalinvoiceoftheequipmentaThree-YearLimitedReplacement  
Compressor Warranty. This entitles the owner to be reimbursed for  
thecostofareplacementcompressor, duringthethirdthroughfth  
year of the life of the compressor.  
Heatcraft Refrigeration Products LLC makes no warranty expressed  
or implied, of fitness for any particular purpose, or of any other  
nature whatsoever, with respect to products manufactured or  
sold by Heatcraft Refrigeration Products LLC hereunder, except as  
specifically set forth above and on the face hereof. It is expressly  
understood and agreed that Heatcraft Refrigeration Products LLC  
shall not be liable to buyer, or any customer of Buyer, for direct or  
indirect, special, incidental, consequential or penal damages, or for  
any expenses incurred by reason of the use or misuse by Buyer or  
third parties of said products. To the extent said products may be  
considered "Consumer Products,' as defined in Section 101 of the  
Magnuson-Mosswarranty-FederalTradeCommissionImprovement  
Act, Heatcraft Refrigeration Products LLC makes no warranty of any  
kind, express or implied, to "Consumers," except as specifically set  
forth above and on the face hereof.  
The warranty program functions similarly to the standard warranty  
offered.Whenacompressorfailureoccursandtheunitisexchanged  
"over the counter" at the authorized wholesaler outlet a salvage  
credit is issued along with the invoice for the new compressor.  
ReturncopiesofboththecreditandinvoicetotheEquipmentDealer  
along with the model and serial number of the condensing unit.  
TheEquipmentDealerwillprocessthisclaimwiththeManufacturer  
and subsequently reimburse the Owner for the cost of the new  
compressor.  
This warranty covers the actual compressor only and does not  
extend to any labor, trip charges, crane rental, taxes or additional  
parts, refrigerant or processing/handling charges required to make  
the unit operational.  
This equipment is designed to operate properly and produce the  
rated capacity when installed in accordance with good refrigeration  
industry practices.  
Since product improvement is a continuing effort,  
we reserve the right to make changes in specifications without notice.  
2175 West Park Place Blvd. • Stone Mountain, GA 30087  
H-IM-82B-0708  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graco Heat Pump 3A0096B User Manual
Grandstream Networks Security Camera GXV3504 User Manual
Haier Washer Dryer HWM70 0588 User Manual
Hasbro Robotics 81327 User Manual
Heat Controller Heat Pump VMH 09 User Manual
HP Hewlett Packard PDAs Smartphones h2200 Series User Manual
Hypertec Carrying Case N6608AHY User Manual
Hyundai Car Video System H CMD4008 User Manual
IBM Laptop 27P2076 User Manual
IBM Ricoh Printer 1612 User Manual