Heatcraft Refrigeration Products Refrigerator H IM 79E User Manual

Beacon II™  
Refrigeration Systems  
H-IM-79E  
JANUARY 2011  
Part No. 25001401  
Replaces H-IM-79E (09/07)  
Table of Contents  
Installation and  
Operation Manual  
Beacon II™ Board Layout........................................................ 3  
Installation Tips ........................................................................ 4  
Refrigerant Line Brazing........................................................... 5  
Power Supply........................................................................... 5  
Wiring ....................................................................................... 5  
Multiple Evaporator Configuration ........................................... 6  
Box Temperature Control Settings........................................... 7  
Leak Testing ............................................................................. 7  
Refrigerant Charging ............................................................... 7  
Start-Up Operation..............................................................8-11  
Operating Mode Display......................................................... 11  
Programming and Reviewing Settings and Changes .......12-13  
Program Review Button  
Select Button  
Enter Button  
Monitoring Items .................................................................... 14  
Monitor Button  
Force Defrost Button  
Force Service Button  
Reset Time Button  
Clear/Test Button  
Locking The Beacon II Board................................................. 15  
Status Indicator LED .........................................................15-16  
Low Ambient Operation ......................................................... 16  
Pumpdown........................................................................16-17  
Defrost...............................................................................17-18  
Alarms ................................................................................... 18  
Error Indicator......................................................................... 19  
Checking Operation of Expansion Valve...........................20-21  
Power Failures........................................................................ 21  
Spare Sensor Terminals.......................................................... 21  
Checking Sensors .................................................................. 21  
Sensor Resistance/Temperature Table................................... 22  
System Defaults ..................................................................... 22  
InterLink Replacement Parts List ........................................... 23  
Operational Limits .................................................................. 23  
Expansion Valve Capacity...................................................... 24  
Diagnostics........................................................................24-27  
Wiring Diagrams................................................................28-33  
Preventive Maintenance......................................................... 34  
Service Record..................................................................35-36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Beacon II™ Board Layout  
BEACON II™ BOARD  
Defrost  
Heater  
Relay  
Evaporator  
Expansion  
Valve  
Connection  
Fan  
Relay  
LED  
Display  
Selection  
Buttons  
Room  
Sensor  
Defrost  
Sensor  
24V  
Terminal  
Block  
Suction  
Sensor  
Suction  
Pressure  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Installation Tips  
Use a minimum 18 gauge wire for all low  
Some systems may require the crankcase  
voltage connections  
heater be energized 24 hours prior to  
start-up. The Beacon should be de-  
energized for this period by placing it in  
the SERVICE MODE. This is done by  
pressing the FORCE SERVICE button  
twice. To start the system cooling, press the  
CLEAR button.  
The Beacon II board gets its 24 VAC power  
supply from a transformer mounted in the  
electrical end of each evaporator. On  
208-240 volt systems the multi-tap  
transformer is shipped from our factory wired  
for 240 volts. If your supply voltage is 208  
volt you must change to the 208 volt tap on  
the transformer.  
Room sensors must be left connected on  
ALL evaporators.  
NOTE: On multiple evaporators, since a  
transformer is in each evaporator, the  
voltage tap must be set on each  
evaporator.  
A pressure transducer is installed on the  
evaporator. Do not leak test system above  
150 PSI or damage to transducer could  
occur. If leak testing must be greater than  
150 psig, disconnect the transducer from  
he suction header and reconnect after  
testing is complete.  
Refer to wiring schematic shipped on units  
for unit wiring. Schematics in this Installation  
& Operation Manual are typical wiring  
schematics only.  
Condensing Unit  
Program ALL slave evaporators as SLAVES.  
The condensing unit control panel contains the relays,  
contactors, time delay and a terminal block which is  
appropriately marked to match the low voltage wiring  
connections. A sensor for outdoor air temperature  
measurement is installed on the condensing unit.  
Evaporators are shipped from our factory  
with a preset box setpoint temperature of  
35°F for air defrost and -10°F for electric  
defrost. If your box setpoint temperature  
requirements are different this must be set  
using directions outlined under “Room  
Temperature Control”.  
Condensing unit must be installed using proper  
refrigeration practices and codes. Make sure there is  
sufficient clearances around unit for adequate air flow  
and access.  
The suction line temperature sensor MUST  
be removed from the suction line before  
brazing the suction tubing. The sensor  
MUST then be reinstalled on the suction  
line after brazing is completed and the tubing  
has cooled. Insulate when finished.  
Evaporator Unit  
The evaporator contains the Beacon II controller, electric  
expansion valve, pressure transducer, distributor, orifice,  
transformer and three sensors. These components are  
all factory mounted and wired. The three sensors are  
factory mounted and provide input to the controller from  
the following: defrost temp., suction temp., room temp.  
The low pressure switch time delay relay,  
located in the condensing unit, must be set  
to 1 minute.  
Each evaporator unit must be installed using proper  
refrigeration practices and codes. Make sure the  
piping is correctly sized and properly routed. It is highly  
recommended that the liquid and suction lines be  
insulated. There must also be good clearance around  
unit. See Heatcraft Refrigeration Installation & Operation  
Manual for more details.  
If electrical power will be connected prior to  
evacuation and charging of system, unplug  
electric expansion valve from board until  
system is ready to be evacuated, leak tested  
and charged.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brazing  
Refrigerant Line Brazing (Caution)  
The electric expansion valve and the suction temperature  
sensor on the suction line are factory installed.  
Care must be taken when brazing these lines at the  
evaporator.  
Low voltage - 24V Class II control circuit.  
A total of five low voltage leads are required  
to connect the condensing unit to the  
evaporator. (See wiring diagram.) Two of  
these leads are for connecting the outdoor  
temperature sensor. The other three leads  
are for connecting the compressor relay,  
service relay and 24V Common inputs.  
All 24 volt wiring must be run separate  
from the line voltage wiring.  
Too high a temperature may destroy these  
components. Heat absorbing compounds or “wet  
rags” must be used to protect the electric expansion  
valve when brazing the refrigerant line connections.  
The suction line sensor should be removed before  
brazing.  
Low voltage wiring must be 18 gauge  
minimum. For low voltage wiring, maximum  
distances are:  
Power Supply  
The Beacon II board gets its 24 VAC power supply from  
a transformer mounted in the electrical end of each  
evaporator. On 208-240 volt systems the multi-tap  
transformer is shipped from our factory wired for 240  
volts. If your supply voltage is 208 volt you must change  
to the 208 volt tap on the transformer.  
Condensing unit to Master evaporator  
Between evaporators  
Smart Controller to Master evaporator  
500 ft.  
500 ft.  
1000 ft.  
Multiple units – The multi-in and multi-out  
are the communication connections.  
Connection sequence must follow the multi-  
out terminal to the multi-in terminal and  
the multi-out back to the multi-in terminal in  
a daisy chain loop.  
VERY IMPORTANT: If the supply voltage to the  
evaporator is 208 volts, the primary tap of the  
transformer must be moved to the 208 volt tap.  
This must be done for all the evaporators on that  
system.  
Alarm circuit - The onboard alarm is a  
dry set of NC contacts which closes to  
indicate an alarm. The type and wiring for  
the alarm is customer specified. Note that  
the alarm circuit does not distinguish or  
indicate what has caused the alarm.  
If the 24 VAC power supply falls below 18 VAC the  
system may power down and shut off. When the power  
supply is corrected to 24 VAC the system will restart  
after the four minute hold-off period and resume normal  
operation.  
On Beacon II systems the main power for the evaporator  
can be supplied separately from the power supply of the  
condensing unit. All wiring, however, must comply with  
local electrical codes.  
All wiring must comply with all applicable  
codes and ordinances.  
Wiring  
Wiring between the condensing unit and the unit  
cooler(s) will be as follows (see wiring diagrams):  
High voltage - There may be high voltage on  
the defrost heater relay and the fan relay.  
The evaporator may also be connected to a  
separate power supply from the condensing  
unit. See unit cooler spec. plate for ampacity.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Configuration  
Multiple Evaporator Configuration (Master/slave)  
If there are multiple evaporators on a system, the  
factory default as a MASTER evaporator. Place all  
program for each SLAVE evaporator must be changed to boards in the “SERVICE” mode while you program the  
identify it as a SLAVE. To do so, press the “PROGRAM  
REVIEW” button repeatedly until “SLA” appears then  
use the “SELECT” knob to select “YES” then press  
ENTER”. All Beacon II boards are shipped with the  
setpoints to avoid errors and alarms which may cause  
troubles at startup.  
VERY IMPORTANT: This must be done for each slave  
board.  
PROGRAM  
REVIEW  
SELECT  
Up to 4 evaporators can be connected as a  
master/slave configuration. DO NOT remove the room  
sensor from any of the Beacon II boards.  
This also applies when connected to the optional Smart  
Controller.  
S
S
M
S
CU  
M = Master Evaporator  
S = Slave Evaporator  
CU = Condensing Unit  
Each Beacon II board power is supplied by a transformer in the evaporator on which  
it is mounted. Do not run any 24 VAC wires between Beacon II boards on the evaporators.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Box Temp Control Settings  
Leak Testing  
Box Temperature Control Settings  
After all lines are connected, the entire system must be  
leak tested. The complete system should be pressurized  
to not more than 150 psig with refrigerant and dry  
nitrogen. The use of an electronic type leak detector is  
highly recommended because of its greater sensitivity  
to small leaks. As a further check it is recommended  
that this pressure be held for a minimum of 12 hours  
and then rechecked. For a satisfactory installation, the  
system must be leak tight.  
There is an on board room thermostat on  
the Beacon II board which can be adjusted  
to the desired room temperature. The  
temperature differential is 2° F.  
Temperature Differential  
When a system is in the cooling mode and  
the box setpoint is 35°F, the system will  
continue to cool until the box temperature  
gets to 34°F. At this point the compressor  
will pumpdown and shut off. The system will  
restart cooling when the box temperature  
has risen to 36°F.  
Refrigerant Charging  
Beacon II systems are shipped standard with a head  
master valve (scroll compressor models have a 100 PSI  
head master valve. All other models have a 180 PSI head  
master valve). The maximum system refrigerant capacity  
is the receiver capacity as listed in the sales literature  
plus the liquid line capacity. Do not add more refrigerant  
to the system than 90% of the receiver capacity.  
It is important to note that Beacon II has  
a minimum 2 minute “ON” time and a  
minimum 4 minute “OFF” time. This  
means that the system will run in the cooling  
mode a minimum of 2 minutes even  
if the setpoint temperature is met. In  
applications where the system is grossly  
oversized, the box temperature could go  
below the differential temperature before the  
system cycles off.  
In the “OFF” cycle the system will be off for  
a minimum of 4 minutes even if the  
box temperature goes above the differential  
temperature, before cooling will be restarted.  
The on board room thermostat is factory  
set at 35°F for Air Defrost systems and  
-10°F for electric defrost system.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Start-Up Operation  
Start-Up Operation  
Single System With 1 Evaporator  
Check all wiring connections to be sure  
they are correct and tight.  
On the evaporator  
-
-
Use the “PROGRAM REVIEW”  
button to scroll through settings.  
On the condensing unit  
-
-
Check the setting of time delay  
relay. It should be set at 1 minute  
(the second marker).  
Check “rEF” (Refrigerant Type).  
Factory defaults are: Air Defrost  
R-22, Electric Defrost R-404A.  
Change to the refrigerant being used.  
Check the low pressure switch  
setting on freezer units. It must be  
set to 0 psig cut-out, 10 psig cut-in  
to allow positive start and operation,  
especially in cold ambients. This  
can be changed to a higher value in  
warmer climates. On cooler units, the  
low pressure switch has a fixed  
setting and cannot be adjusted.  
-
Check “bot” (Box Temperature).  
Factory defaults are: air defrost  
35°F and electric defrost –10°F.  
Change to the desired temperature.  
-
-
Review and change other setting if  
necessary  
See procedures below on how to  
change settings.  
Turn power on  
CU  
M
M = Master Evaporator  
CU= Condensing unit  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Start-Up Operation  
Single System With Multiple  
Evaporators  
Check all wiring connections to be sure  
they are correct and tight.  
-
-
Check “rEF” (Refrigerant Type).  
Factory defaults are: air defrost  
R-22, electric defrost R-404A.  
Change to the refrigerant being used.  
On the condensing unit  
-
-
Check the setting of time delay  
relay. It should be set at 1 minute  
(the second marker).  
Check “bot” (Box Temperature).  
Factory defaults are: air defrost  
35°F and electric defrost –10°F.  
Change to the desired temperature.  
Check the low pressure switch  
setting on freezer units. It must be  
set to 0 psig cut-out, 10 psig cut-in  
to allow positive start and operation,  
especially in cold ambient. This  
can be changed to a higher value  
in warmer climates. On cooler units,  
the low pressure switch has a fixed  
setting and cannot be adjusted.  
-
-
Review and change other setting if  
necessary.  
See procedures below on how to  
change settings.  
On the SLAVE evaporators. All Beacon II  
boards are shipped with the factory  
default as a “MASTER” evaporator.  
Turn power on.  
-
-
DO NOT REMOVE the Room Sensor  
from any evaporator  
On the MASTER evaporator  
-
-
DO NOT REMOVE the room sensor  
from any evaporator  
Each SLAVE Evaporator must be  
changed to identify it as a SLAVE.  
Use the “PROGRAM REVIEW” button  
to scroll until “SLA” appears, then  
use the “SELECT” knob to select  
“YES” then press “ENTER.”  
Use the “PROGRAM REVIEW” button  
to scroll through settings.  
S
S
M
S
CU  
M = Master Evaporator  
S = Slave Evaporator  
CU = Condensing Unit  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Start-Up Operation  
Multiple Systems With Multiple  
Evaporators (Requires A Smart  
Controller)  
Check all wiring connections to be sure  
they are correct and tight.  
On the MASTER evaporator  
-
DO NOT REMOVE the room sensor  
from any evaporator  
On the condensing units  
-
-
Check setting of time delay relay.  
It should be set at 1 minute  
(the second marker).  
On the SLAVE evaporators. All Beacon II  
boards are shipped with the factory  
default as a “MASTER” evaporator.  
Check the low pressure switch  
-
Each SLAVE evaporator must be  
changed to identify it as a SLAVE.  
Use the “PROGRAM REVIEW”  
button to scroll until “SLA” appears,  
then use the “SELECT” knob to  
select “YES” then press “ENTER.”  
setting on freezer units. It must be set  
to 0 psig cut-out, 10 psig cut-in to  
allow positive start and operation,  
especially in cold ambient. This  
can be changed to a higher value in  
warmer climates. On cooler units,  
the low pressure switch has a fixed  
setting and cannot be adjusted.  
Use the Beacon II Smart Controller to  
set system parameters. See Beacon  
II Smart Controller installation  
Turn power on.  
instructions for more details.  
MULTIPLE SYSTEM CONNECTION  
(See Smart Controller instruction manual for more details)  
SYSTEM 2  
SYSTEM 3  
SYSTEM 1  
S
S
S
S
S
S
S
CU  
S
M
M
S
M
CU  
CU  
M
S
CU  
SMART  
CONTROLLER  
S
S
SYSTEM 4  
CU = Condensing Unit  
M = Master Evaporator  
S = Slave Evaporator  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Start-Up Operation  
Initial Power On  
At the initial application of power to the system, the  
compressor and the evaporator fans will be in a 4 minute  
hold-off cycle and will not start immediately. When there  
is a call for COOLING, the expansion valve (EEV) opens,  
then the compressor is started. The compressor will  
then run for a minimum of 2 minutes in the “hold-on”  
cycle. (This means that the compressor will run for a  
minimum of 2 minutes before shutting off even if the box  
temperature is met).  
When the room sensor detects a rise in temperature of  
approximately 2°F, and the compressor has been off for  
at least 4 minutes, the EEV will open to its last position  
then the compressor will start. The valve is then adjusted  
as necessary to obtain the setpoint superheat setting.  
During this time, the compressor will run for a minimum  
2 minutes “hold-on” cycle.  
The four minute “HOLD-OFF” can be bypassed and the  
system started immediately by pressing the “RESET”  
button on the Beacon II board.  
The LED alternately displays BOX TEMPERATURE  
and MODE of operation. On a call for cooling, dLY will  
show while the expansion valve is opening. After the  
compressor starts the LED will alternately display BOX  
TEMPERATURE and Coo.  
Operating Mode Display  
On multiple evaporator systems the MASTER evaporator  
will display BOX TEMPERATURE and Coo. The SLAVE  
evaporators will display Coo only.  
oFF - Off  
Coo - Cooling  
Pdn - Pumpdown  
dEF - Defrost  
drn - Draining  
dLY - Delay  
tSt - Test  
When the room thermostat setting is satisfied, and if  
the compressor ran for at least 2 minutes, the EEV will  
close and the compressor will pumpdown and shut off.  
The evaporator fans will continue to run. The LED will  
alternately display oFF and BOX TEMPERATURE.  
SEr - Service  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Programming & Reviewing  
Programming And Reviewing Settings / Changes  
“PROGRAM REVIEW” ITEMS  
The PROGRAM REVIEW button is used to program,  
review and change all program settings for the system.  
A-E - Set Defrost type  
Press “PROGRAM REVIEW” button. The Setpoint  
item will appear on the LED. After a few seconds delay  
the Setpoint value will display. Each time the button is  
pressed a different setpoint item is displayed.  
(Air or ELE)  
rEF - Set Refrigerant type  
(R22, R404A or R507)  
bot - Set Box temperature  
(-30°F to +70°F)  
SUP - Set Superheat  
(4°F to 20°F)  
SLA - Set Board as a Slave  
Next, use the “SELECT” knob to change value of  
Setpoint Item.  
(Yes or No)  
dFn - Set Number of defrosts per day  
(1, 2, 3, 4, 5, 6, 8,10 or 12 per day)  
dFF - Set Defrost Fail-safe time  
(10 to 200 minutes)  
dFt - Set Defrost End temperature  
(40°F to 100°F)  
dFS - Set Defrost Delay Start Time  
Next, When the desired value is selected, press the  
“ENTER” button to place it in program memory. If the  
“ENTER” button is not pressed the value will not be  
stored in the memory and thus will not be changed.  
(0.5 Hours to 23.5 Hours)  
ALH - Set Alarm High temperature  
(-40°F to 90°F)  
ALL - Set Alarm Low temperature  
(-40°F to 90°F)  
ALt - Set Alarm time  
(2 to 120 minutes)  
F-C - Set Fahrenheit / Celsius  
temperature units (°F/°C)  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Programming & Reviewing  
Programming And Reviewing Settings / Changes (cont’d.)  
Use the “PROGRAM REVIEW” button to select these items:  
Defrost Type – “A-E ” - Selection is made for air  
defrost or electric defrost coil. This will  
automatically set the system factory defaults for  
air defrost and electric defrost. (See default  
settings.) Please note that the refrigerant type  
default for air defrost is R-22 and for electric  
defrost it is R404A. All units are shipped with  
factory defaults settings.  
selection is made, Defaults: electric defrost 4 per  
day and air defrost 2 per day.  
Defrost fail-safe - “dFF” - This is the maximum  
time allowed for a coil to remain in defrost.  
Defrost will be terminated if the defrost end  
temperature is not attained when this time  
has expired. On multiple evaporator systems this  
is controlled by the Master unit. Each board  
should have the same setting. Defaults: electric  
defrost 30 minutes and air defrost 40 minutes.  
Refrigerant Type - “rEF” - Selection for type of  
refrigerant - R-22, R-404A or R-507. Default:  
Air defrost is R-22 and for electric defrost it is  
R-404A.  
Defrost End Temperature - “dFt” - This is the  
temperature at which the Defrost will be  
terminated. Defaults: electric defrost +60°F and  
air Defrost +45°F.  
Box Temperature - “bot” - Select box  
temperature setpoint. Selection range is -30°F to  
+70° F. Defaults: Electric defrost -10°F and air  
defrost +35°F.  
Defrost Delay Start Time - “dFS” - This allows  
the delay of the start of the first defrost. Defaults:  
0.5 hours to 23.5 hours.  
Superheat - “SUP” - Evaporator superheat is  
controlled by the board on each evaporator.  
Each board measure the evaporator saturation  
suction temperature and the suction pressure to  
determine the superheat. The superheat value  
at the evaporator can be changed to ensure a  
20°F to 30°F superheat at the Compressor.  
Default: 8°F.  
Alarm High Temperature - “ALH” - Temperature  
at which a high box temperature alarm will be  
triggered. This does not apply during defrost.  
Defaults: electric defrost +5°F and air defrost  
+50°F.  
Alarm Low Temperature - “ALL” - Temperature  
at which a Low Box Temperature alarm will be  
triggered. Defaults: Electric Defrost -15°F and Air  
Defrost +30°F.  
Evaporator Board: Slave? - “SLA” - On multiple  
evaporator systems, each evaporator board has  
to be programmed to be a Master or a Slave.  
Each board is shipped from our factory set as  
a Master. You must make this change to each  
Slave evaporator. A selection of “YES” is made  
for this setting.  
Alarm Time - “ALt” - Time which High  
Temperature or Low Temperature condition must  
exceed before alarm is triggered. Default:  
60 minutes.  
The default for each board is a Master, so on  
Single Evaporator systems no change is  
required.  
°F/°C - “F-C” - Select units to display  
temperature. Fahrenheit or Celsius. Default:  
Fahrenheit.  
No. of Defrost per Day - “dFn” - A selection must  
be made for the number of defrosts cycles per  
day – 1,2,3,4,5,6,8,10 or 12 per day. If no  
When °C is selected a red dot will appear in the  
right bottom corner of the LED display of the  
Beacon II board.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Programming & Reviewing  
Use this button to “FORCE DEFROST” To force a  
MONITOR  
defrost , press the “FORCE DEFROST” button. The  
system will pumpdown and shut off the compressor. The  
heaters are then turned on. The display will show “dEF”  
and room temp.  
FORCE  
DEFROST  
Use the “MONITOR”  
button to review these items:  
SUP - Superheat  
(°F/°C)  
ESP - Expansion valve steps  
Use this button to “RESET TIME” Pressing this button  
will reset the time clock in the microprocessor to zero.  
At initial power up, pressing this button will bypass  
the “four minute” hold-off and the system will start  
immediately after the expansion valve opens. This  
display will show “dLy”.  
(0 to 255 steps)  
SCt - Suction temperature  
(°F/°C)  
SSt - Saturated Suction temperature  
(°F/°C)  
RESET  
TIME  
SCP - Suction pressure at Evaporator  
(PSIG/HG)  
Odt - Outdoor temperature  
(°F/°C)  
dFt - Defrost sensor temperature  
Use this button to “FORCE SERVICE”  
(°F/°C)  
Pressing this button TWICE will cause the system to  
pumpdown and the compressor to shut off. The system  
will remain off until the “CLEAR” button is pressed.  
While in the “FORCE SERVICE”, the LED display will  
only show “SEr”.  
dFS - Time left until next defrost  
(hours) (on version 1.8 boards)  
dFE - Last Defrost Elapsed time  
(minutes)  
FORCE  
SERVICE  
AC - Board Voltage  
SPt - Spare Temperature reading  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Programming & Reviewing  
Programming And Reviewing  
Settings/Changes (Cont’d.)  
Locking The Beacon II Board  
The Beacon II board is lockable to prevent programmed  
setting changes by unauthorized personnel. When  
locked, the program setpoints cannot be changed.  
To lock the setting:  
Use this button to “CLEAR/TEST”  
Pressing this button ONCE will return the LED display to  
the default display. With the system in the OFF mode,  
pressing and holding this button will start the “TEST”  
mode. In the “TEST” mode it will cycle through each  
output for 10 seconds. The display will only show “tst”  
during “TEST” mode. Test mode will automatically  
terminate after 3 sequences.  
Press “PROGRAM REVIEW” button.  
Press and hold MONITOR” button.  
While holding MONITOR” button,  
press “ENTER” button.  
The LCD will display Loc.  
This will prevent unauthorized personnel program  
changes. To unlock, repeat steps above. LCD will  
display “UnL”.  
STATUS INDICATOR LED  
A RED, three-digit , alphanumeric LED on the  
Beacon II board indicates status, alarms and  
error codes.  
• OFF  
All Evaporators  
Box Temp / oFF  
Box Temperature/ Mode is displayed  
Box Temperature/ Mode is displayed  
• COOLING  
Single Evaporator-  
Multiple Evaporators  
Master Evap -  
Box Temp /Coo  
Box Temp / Coo  
Box Temperature/ Mode is displayed  
Operating Mode is displayed  
Slave Evaps -  
Coo  
• Pumpdown  
All Evaporators  
Pdn  
dEF  
tSt  
• DEFROST  
All Evaporators  
• TEST  
All Evaporators  
• SERVICE  
All Evaporators  
SEr  
• ALARMS  
A 1  
A 2  
A 3  
High Box Temp  
Low Box temp  
System Start-up failure  
Compressor pumps down and tries  
to restart after 4 minutes.  
Input Fault  
A 4  
Box Temp., Suction Temp., Pressure  
Transducer open or not installed  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Status Indicator LED  
STATUS INDICATOR LED  
ERRORS  
E 1 - Room temperature sensor shorted, open or not installed  
E 2 - Defrost temperature sensor shorted, open or not installed  
E 3 - Suction temperature sensor shorted, open or not installed  
E 4 - Suction pressure transducer shorted, open or not installed  
E 5 - Outdoor temperature sensor shorted  
E 6 - Low superheat during cooling  
E 7 - Compressor shutdown  
(high or low refrigerant pressure or low oil pressure)  
E 9 - Multi-in/Multi-out wiring error  
OTHERS  
Coo - Room Temperature sensor open or not connected  
(Instead of displaying box temperature)  
Loc - Board is locked. Settings cannot be changed  
UnL - Unlock the board settings  
Low Ambient Operation  
All units are shipped standard with Head Master valves.  
(Scroll compressor units have a 100 PSI Head Master  
valve and all other systems have a 180 PSI head master  
valve.) Condensing units with multiple condenser fans  
will have one or more fans cycle on Pressure Fan Cycling  
switch.  
When any of these three conditions occurs the  
compressor will turn off and not restart until there is a  
call for cooling or a periodic pumpdown.  
Periodic Pumpdown  
An adjustable Time Delay relay, factory set at 1 minute,  
is wired across the Low Pressure switch (LPS). In cold  
ambient this allows time for the suction pressure to build  
up and prevent nuisance tripping of the LPS.  
While in the OFF cycle, if there isn’t a call for cooling  
(Box setpoint temperature is met) but:  
The evaporator suction pressure has  
risen to 10 psig  
Pumpdown  
The low pressure switch has closed  
At the end of each cooling cycle, when the box  
temperature is met, the Beacon system will pump down  
and shut off the compressor.  
The system will initiate pumpdown. This periodic  
pumpdown will occur at 4 minute intervals when these  
two conditions are met.  
To pumpdown, the EEV closes and the compressor runs  
until one of the following occurs:  
The low pressure switch opens  
The suction pressure at the evaporator  
is 4 psig  
A total of two minutes has elapsed  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Pumpdown / Defrost  
Service Mode  
Defrost Delay Start Time  
Example: The system is first powered up at 8:00 AM and  
is programmed for 4 defrost per day. The user would like  
the first defrost at 10:00 AM. To accomplish this, use the  
“PROGRAM REVIEW” button to scroll to dFS. Use the  
“SELECTOR” switch to select 2 hours delay start, then  
press “ENTER.” The 1st defrost will now occur at 10:00  
AM and then a defrost will occur every 6 hours thereafter.  
A single pole, single throw switch (SPST) is supplied in  
each condensing unit for shutting off the system. Closing  
the “SERVICE” switch in the condensing unit will cause  
the system to pumpdown and shut off. “Ser” will be  
displayed on the Beacon board LED and “SERVIC”  
is displayed on the Smart Controller LCD display. The  
evaporator fan and heaters will be de-energized in the  
Service Mode.  
Time Remaining Until Next Defrost  
(On Version 1.8 Boards)  
The system will not restart until the SPST switch is  
placed in the “NORMAL” or “OFF” position.  
OR  
To nd out how much time is left until the next defrost is  
scheduled, use the “MONITOR” button to scroll to dFS.  
The time displayed will be how much time until the next  
scheduled defrost.  
A remote “SERVICE” switch can be added to the  
Beacon II board across the “Ser” and “C” connections of  
the terminal block. It will operate in the same manner as  
the switch above.  
Defrost Schedule In Memory  
OR  
Beacon II does not have a real time clock but it keeps  
track of the time that has elapsed in its memory. It also  
keeps in memory the number of defrosts scheduled  
and how much time has elapsed between defrosts. If a  
power failure occurs, when power is restored Beacon  
II remembers how many defrosts are scheduled and  
it remembers how much time was left until the next  
defrost. It will then defrost based on this timing. So, if the  
power failure lasted 15 minutes, the defrost schedule will  
be off by 15 minutes.  
The system can be pumped down by pressing the  
“SERVICE” button twice. To restart the system, press  
the “CLEAR” button.  
OR  
The system can be pumpdown for service by closing  
the liquid line service valve in the condensing unit, then  
closing the suction line service valve when the system  
trips on the low pressure switch.  
In order for air defrost evaporator fan motors to cycle off  
during “SERVICE” mode, the fan motors must be wired  
through the fan relay on the Beacon II board.  
Resetting Defrost Schedule  
When a power interruption causes a severe lag in the  
defrost schedule, the defrost schedule can be reset in  
the following manner. First, press the reset time button  
on the board to zero out the internal counters. Then,  
program the appropriate defrost delay start time for the  
next desired defrost period. The defrost schedule will be  
Defrost  
Defrost Timing  
correct until you have another power outage.  
When power is first applied to the system, its timer  
starts counting time. If 4 defrost are programmed, it will  
initiate a defrost every 6 hours from when power was  
first applied. Beacon II does not have a real time clock.  
Beacon II does provide the ability to delay the starting of  
the first defrost.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Defrost / Alarms  
Electric Defrost Mode  
When a defrost is initiated, the EEV closes, the  
compressor is allowed to pumpdown and shut off. The  
evaporator fans are cycled off and the defrost heaters  
are energized.  
Low Box Temperature - LED Display:  
A 2 - Room temperature has dropped  
below the Alarm Low ALL value for the  
Alarm time ALt, programmed  
On multiple evaporator systems, all controllers must  
terminate their defrost, either on temperature or fail-safe  
time, before the master controller will end the defrost  
cycle.  
There is a 2 minute condensate drain-down period after  
which the compressor is started for a refreeze period.  
The evaporator fan stays off (fan delay). The refreeze  
period will last until the evaporator suction temperature  
is at 28°F or 3 minutes has elapsed. After this sequence,  
the system is back in the refrigerating mode and  
evaporators fans are now running.  
System Start-up failure – LED Display:  
A 3 - Compressor pumps down and tries  
to restart after 4 minutes. After 4  
unsuccessful attempts to restart, the  
alarm code A 3 is displayed. System  
continues trying to restart.  
Input Fault – LED Display: A 4 - Box  
Temp., Suction Temp., Pressure  
Transducer open or not installed.  
Air Defrost Mode  
Power failure – Loss of power to the  
Evaporator  
The sequence is the same as for electric defrost except  
that there are no heaters and the evaporator fans run  
continuously. If the air defrost for motors are wired  
through the fan relay on the board, they will remain  
energized during defrost mode.  
Alarm Codes  
A 1 High Box Temp  
A 2 Low Box temp  
Alarms  
A 3 System Start-up failure  
Compressor pumps down and tries to  
restart after 4 minutes  
A 4 Input Fault  
Beacon provides a set of dry contacts for use in  
signaling an alarm. These contacts can be connected  
to a light, a buzzer, a bell etc., which will be activated  
when an alarm condition occurs. When the Beacon II is  
energized, the alarm contacts are OPENED. When an  
alarm condition is detected, the contacts are CLOSED.  
Box Temp., Suction Temp., Pressure  
Transducer open or not installed  
Conditions under which the alarm contacts will close are:  
Clearing Alarms  
Alarms A1 – High Box Temp. and A2 – Low Box Temp.  
will clear automatically if the Box Temp. decreases  
or increases to below or above the Alarm setpoint  
temperature. Placing the system in the “SERVICE  
MODE” or turning off power will clear the A3 Alarm.  
Replacing the Room Sensor, Suction Sensor or Pressure  
Transducer will clear the A4 Alarm.  
High Box Temperature – LED Display:  
A 1 - Room temperature has exceeded  
the Alarm High ALH value for the Alarm  
time ALt, programmed.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Error Indicator  
Error Indicator Led  
ERROR CODES  
E1 - Room temperature sensor shorted,  
open or not installed  
E2 - Defrost temperature sensor shorted,  
open or not installed  
At initial power up, each Beacon II board checks for  
system errors. The system error check involves checking  
the various temperature sensors to determine whether  
any of these sensors are shorted or open.  
E3 - Suction temperature sensor shorted,  
open or not installed  
E4 - Suction pressure transducer shorted,  
open or not installed  
The system will pumpdown and cycle off and will not  
restart until the fault is cleared or the circuit breaker  
reset, for the following conditions:  
E5 - Outdoor temperature sensor shorted  
E6 - Low superheat  
-
-
-
Suction sensor shorted, open  
or not installed  
E7 - Compressor shut down  
(high or low pressure switch open or  
oil pressure switch open)  
Room temperature sensor shorted  
or not installed  
E9 - Multi-in/multi-out wiring error  
Pressure Transducer open  
or not installed  
The system will pumpdown, cycle off and try to restart  
for these faults. Each try will be after the 4 minutes  
“Hold Off” period, for the following fault conditions:  
Air Defrost fan motors must be wired through the fan  
relay on the Beacon II board for this to be effective on Air  
Defrost systems. The entire system will be shut off and  
remain off until the SPST switch is opened.  
- High pressure or low pressure cutout  
- Oil pressure  
Air Defrost evaporator fans are setup to run constantly.  
If there is a need to shut down the evaporator fans on  
an Air Defrost system, this can be accomplished by  
wiring the evaporator fan motor or evaporator fan motor  
contactor through the fan relay on the Beacon II board.  
When this is done and the Air Defrost system  
After the fourth try, the Alarm contacts will be closed  
and an alarm message displayed on the LED. To clear  
this condition, the system should be cycled through the  
“SERVICE MODE” after the correction is completed.  
is placed in “SERVICE,” the evaporator fans  
will shut off when the system is in pumpdown.  
Evaporator Fans Shut Off  
In some installations, it is desirable to shut off the  
evaporator fans periodically. This is easily accomplished  
on Beacon II by wiring a single pole, single throw switch  
(SPST) between the terminals marked “SERVICE” and  
COM” on the Beacon II board. Closing this switch will  
cause the system to pumpdown and shut off.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Checking Operation of Expansion Valve  
Checking Operation Of Expansion  
Valve (EEV)  
The Expansion valve position can be monitored from  
the LED display pressing the “MONITOR” button and  
scrolling to ESP. This will indicate the number of steps  
the valve is open.  
To check if the expansion valve is closing properly:  
Install a pressure gauge-set to suction line at  
the condensing unit. With the system running,  
close the valve on the liquid line, at the con  
densing unit. The system should pumpdown  
and shut off on the Low Pressure switch (LPS).  
If the system does not pumpdown and trip on  
the LPS then the compressor valves are weak  
and needs to be changed.  
This can also be checked by using the EXV test pins on  
the board. This is indicated by a 0 to 5 Volts DC signal.  
At 0 Volt the valve is closed and at 5 Volts the valve is  
fully open. At values between 0 and 5 Volt, the valve will  
be opened proportionately.  
Use the “MONITOR” button to display “SCP””  
Evaporator Suction Pressure. Record the pressure  
displayed. Start the system and observe the pressure  
displayed. If the pressure does not increase, the  
expansion valve could be defective.  
After the system pumps-down and trip on the  
LPS, put the system in the service mode. This  
will cause the Expansion valve to close. Open  
the valve on the liquid line, at the condensing  
unit. The suction pressure reading on the gauge  
set should not increase. If the suction pressure  
increases then the expansion valve is leaking  
and should be changed.  
If the system is running, use the “MONITOR” button to  
display “SCP” Evaporator Suction Pressure. Record the  
pressure displayed. While the system is running, press  
the “FORCE SERVICE” button. Observe the pressure  
while the system is pumping down. The pressure should  
decrease. If it does not, this indicates a defective valve.  
Expansion Valve Motor Winding Resistance  
If the expansion valve is suspected of not functioning  
properly the motor windings resistance should be  
measured. This is a bipolar motor with two windings.  
Measure the resistance at the pins, on top of the valve,  
between locations A and B  
(Note that the pins are not labeled A, B, C, D. This  
labeling is just for reference. Also, two of the pins, at  
location B and location D, have a wider spacing between  
them than between location A and C)  
or C and D.  
Expansion Valve  
A• •C  
Motor Winding  
Pins  
B
D
For valve size 29320003 and 2930004, the resistance  
measured between pin locations A and B or C and D  
should be approximately 336 Ohms when valve is at  
75ºF.  
For valve size 2930007, 29320008, 29320013 and  
29320014, the resistance measured between pin  
locations A and B or C and D should be approximately  
116 Ohms when the valve is at 75ºF.  
Continues to Page 21  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Power Failures  
Continued from Page 20  
Measuring resistance between locations A and C or B  
and D will always show “Open” because these locations  
are between the motor windings.  
Measuring the DC volt of the EXV TEST pins, on the  
board, will also indicate if the expansion valve is open  
or close. 0 volts DC indicates the valve is closed. 5 volts  
DC indicates the valve is fully open. A value between  
0 and 5 volts indicates how much the valve is open or  
close.  
When the valve is opening or closing, the voltage  
measured between A and B or C and D should be  
between 20 to 22 VAC.  
Power Failures  
Checking Sensors  
In the event of a power failure Beacon II will  
automatically close the expansion valve to prevent  
refrigerant from migrating throughout the system. After  
power returns, with 24 VAC at the board, the system will  
restart in the cooling mode after the four-minute hold off  
period.  
DO NOT REMOVE SENSORS FROM EVAPORATORS  
FOR CHECKING.  
Use the monitor button to display the value  
the sensors are reading on the LED (suction temp. SCt,  
defrost temp. dFt or room temp.). Compare this value to  
the measured value with a thermometer at each of these  
points. If they do not match, change the sensor.  
Spare Sensor Terminals  
Beacon II provides a set of input terminals for customers  
who may want to monitor an additional temperature or  
items such as Product Temperature. This input terminal  
requires a signal from a thermistor which meets the  
temperature/resistance values in Table 1 on page 22.  
OR  
The sensors can be checked for their proper operation  
by placing it in a cup of ice water. Stir the ice water  
and measure the resistance of the sensor. At 32°F the  
resistance should be 32,650 ohms. If it is higher or lower  
by 5,000 ohms approximately, the sensor should be  
replaced.  
If a product temperature simulator is used it must meet  
the resistance/temperature specification listed in Table  
1. The temperature range for this input is –30°F to 140°F.  
Sensors on the Beacon system, as supplied, will not  
simulate product temperature.  
This input can be monitored on the LED display by using  
the “MONITOR” button and scrolling to SPt. The values  
displayed will be the temperature of the spare sensor.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
System Defaults  
Table 1. Resistance/Temperature Specification  
Temperature °F  
Ohms  
5,320  
Temperature °F  
Ohms  
32,650  
42,330  
55,330  
72,950  
97,070  
130,410  
176,960  
104  
86  
77  
68  
59  
50  
41  
32  
23  
14  
5
-4  
-13  
-22  
8,060  
10,000  
12,490  
15,710  
19,900  
25,400  
Table 2. System Defaults  
PARAMETERS  
CODE  
AIR  
ELECTRIC  
Refrigerant  
Box Temperature  
Superheat  
Slave Evaporator  
No. of Defrost per Day  
Defrost Fail-safe time  
Defrost End Temperature  
Defrost Delay Start Time  
Alarm High Temperature  
Alarm Low Temperature  
Alarm Time  
rEF  
bot  
SUP  
SLA  
dFn  
dFF  
dFt  
dFS  
ALH  
ALL  
ALt  
F-C  
R-22  
35°F  
8°F  
No  
2
40 min.  
45°F  
0 hrs.  
50°F  
30°F  
60 min.  
°F  
R-404A  
-10°F  
8°F  
No  
4
30 min.  
60°F  
0 hrs.  
5°F  
-15°F  
60 min.  
°F  
Temperature Units  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
InterLink Replacement Parts List  
Replacement Parts by  
Commercial Refrigeration Parts  
InterLink is your link to a complete line of dependable and certified commercial refrigeration parts, accessories  
and innovative electronic controls for all Heatcraft Refrigeration Products (HRP) brands - including Bohn, Larkin,  
Climate Control and Chandler. At InterLink, we provide our wholesalers with a comprehensive selection of product  
solutions and innovative technologies for the installed customer base. And every product is built to ensure the  
same high performance standards with which all HRP brands are built — backed by a dedicated team to serve  
every customer need, delivering at the best lead times in the industry.  
Table 3. InterLink Replacement Parts List  
PART DESCRIPTION  
Beacon II Control Board  
PART NUMBER  
28910101  
*Temperature Sensor kit – White Leads  
Transformers:  
89904902  
120/24 volt – 40 VA  
240/24 volt – 40 VA  
460/24 volt – 40 VA  
575/24 volt – 40 VA  
22529601  
22529602  
22529603  
22529701  
22511401  
2252440  
Pilot Relay  
Contactor for Compressor 40 amp with 24 volt Coil  
Terminal Block – Condensing Unit  
Low Pressure Switch Time Delay Relay  
Electric Expansion Valve  
2251266  
22536801  
ESB 1 – 3/8” x 3/8” Conn  
ESB 4 – 3/8” x 3/8” Conn  
ESB 10 – 3/8” x 3/8” Conn  
ESB 10 – 1/2” x 1/2” Conn  
ESB 15 – 7/8” x 1 3/8” Conn  
ESB 20 – 7/8” x 1 3/8” Conn  
Expansion Valve Molded Connector  
(Bipolar valves)  
29320003  
29320004  
29320007  
29320008  
29320013  
29320014  
22515201  
Pressure Transducer  
28911201  
22515101  
89704301  
89704101  
89708001  
Pressure Transducer Harness  
Beacon II Smart Controller  
**Smart Controller Software Package  
Beacon II Communications Hub  
*Only the sensor with white leads is shipped as a service replacement part  
**Smart Controller Software package is sold separately  
Table 4. Operational Limits  
OPERATIONAL LIMITS  
Voltage Range  
18 VAC to 30 VAC  
Controlling Box Temp. Range  
Temperature Differential  
Cold Ambient Limits  
-30°F to 70°F  
2°F  
Start & operate to -20°F  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Expansion Valve Capacity  
R-22  
R-404A / R-507  
Evaporator Temperature (°F.)  
+20 -20  
Pressure Drop Across Valve (psi)  
Evaporator Temperature (°F.)  
+20  
-20  
Pressure Drop Across Valve (psi)  
Part Number  
29320003  
29320004  
29320007 - 08 ESVB-10  
29320013  
29320014  
Valve  
ESVB-1  
ESVB-4  
100  
0.68  
3.27  
8.02  
15.14  
22.18  
BTUH  
8160  
39240  
96240  
181680  
266160  
100  
0.64  
3.07  
7.54  
14.25  
20.87  
BTUH  
7680  
36840  
90480  
171000  
250440  
100  
0.48  
2.31  
5.65  
10.69  
15.65  
BTUH  
5760  
27720  
67800  
128280  
187800  
100  
0.42  
2.05  
5.01  
9.47  
13.86  
BTUH  
5040  
24600  
60120  
113640  
166320  
ESVB-15  
ESVB-20  
Diagnostics  
Beacon II Troubleshooting Guide  
PROBLEM  
Step ACTION ITEM  
IF OK  
IF NOT OK  
1.  
2.  
3.  
4.  
5.  
Check Primary Power Supply Disconnect  
Check Voltage to Evaporator Transformer  
Check Transformer Secondary Output Volts next step  
Check Voltage at Control Board (24V and C)  
Replace Control Board  
1. Check fuses and circuit breakers  
2. Check field wiring for breaks  
3. Replace if necessary  
Go to  
LED is not lit.  
4. Check factory wiring and connections  
1.  
2.  
Check Compressor internal overloads  
Check Control Power to Condensing Unit  
(24 Volts across “COMP” and “C” at board)  
Check Compressor Contactor Coil Voltage  
Check Compressor Contactor “pulled in”  
1. Wait for reset  
2. Check transformer voltage (secondary and  
primary) and wiring of 208V power taps.  
3. Check internal condensing unit wiring  
4. Replace as needed  
LED shows Coo, but  
compressor will not run.  
Go to  
next step  
3.  
4.  
ERROR CODES:  
E1 Room Sensor  
Check Sensor and Board Connection  
Check Sensor and Board Connection  
Check Sensor and Board Connection  
Check Transducer and Board Connection  
Check Sensor, wiring and Board Connection  
Replace as needed  
Replace as needed  
Replace as needed  
Replace as needed  
Replace or remove  
E2 Defrost Sensor  
E3 Suction Sensor  
E4 Suction Transducer  
E5 Outdoor Sensor  
1.  
2.  
Check Refrigerant Type  
Check coil for ice  
1. Compare board setpoint and refrigerant  
2. Defrost coil and check defrost cycle  
settings/setpoints, defrost sensor and  
heater amps.  
E6 Low Superheat  
During Cooling  
3.  
4.  
Check Control Board step position from board LED  
3. Replace board if EEV steps not at 2.  
4. Pumpdown system see if LPS opens or if it  
times out (EEV is bad or LPS is set  
incorrectly, if times out) – See Pumpdown.  
5. Check overloads and contactor.  
6. Compare board sensor reading against  
actual suction line temperature.  
Check Electric Expansion Valve Closure  
Go to  
next step  
(0°F for 2 minutes)  
5.  
6.  
Compressor Not Operating  
Check Suction Temperature Sensor  
7.  
Check Suction Pressure Transducer  
7. Compare pressure reading against gauges.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Diagnostics  
Beacon II Troubleshooting Guide (continued)  
PROBLEM  
Step ACTION ITEM  
IF OK  
IF NOT OK  
1.  
2.  
Check wiring connection to the board  
• Correct field wiring to the board  
Low Pressure Safety (LPS) Tripped:  
• Check for correct refrigerant type  
• Check refrigerant charge  
• Change setpoint to match refrigerant  
• Add more refrigerant to proper charge  
• Correct LPS setting  
• Check LPS setting  
• Check LPS wiring  
• Correct LSP wiring  
• Check EEV operation (stuck?)  
• Check coil for icing  
• Check for correct superheat reading  
• Check for correct nozzle selection  
• Check for clogged EEV inlet screen  
• Check line sizing  
• Clean or replace EEV  
• Defrost coil (see E6, step 2)  
• Check/replace sensor or transducer  
• Replace distributor nozzle  
• Replace EEV  
• Correct line sizing  
• Check LPS time delay relay setting  
• Check operation of LPS  
• Reset to 1 minute  
• Replace Low Pressure Safety Switch  
3.  
High Pressure Safety (HPS) Tripped:  
• Check for system overcharge  
• Check for non-condensables  
• Check condenser fan motor and blade  
• Check for dirty condenser coil  
• Check head pressure controls  
• Check fan cycling controls  
• Reclaim/recover excess charge  
• Remove all non-condensables  
• Repair or replace motor and/or blade  
• Clean condenser coil  
• Adjust or replace faulty controls  
• Adjust or replace faulty controls  
• Correct line sizing  
• Check liquid line sizing  
• Check for liquid line restrictions  
• Check operation of HPS  
• Repair line or remove restrictions  
• Replace HPS if necessary  
E7 Compressor  
Shutdown  
4.  
Oil Pressure Safety (OPS) Tripped:  
• Check oil level in compressor  
• Check oil sump screen pickup  
• Check oil pump pressure  
• Check for proper piping practices  
• Check for low superheat (see E6)  
• Check operation of auxiliary relay (R6)  
• Check OPS sensor  
• Add oil to crankcase to minimum level  
• Clean or replace pickup screen  
• Replace compressor oil pump  
• Correct piping to minimize oil logging  
• Correct per steps in E6  
• Replace auxiliary relay  
• Replace faulty OPS sensor  
• Replace faulty OPS  
Go to  
next step  
• Check operation of OPS  
5.  
6.  
Compressor Module Tripped (when supplied):  
• Check module  
• Check superheat at compressor inlet  
• Check compressor for overheating  
• Check suction pressure (too low?)  
• Replace faulty module  
• Reduce superheat (TXV adjust, etc.)  
• Correct overheating problem  
• Consider crankcase pressure regulator  
or other measures  
Phase Loss Monitor (PLM) Tripped:  
• Check presence of all phase legs  
• Check power supply  
• Correct power phase problem  
• Correct power supply problems  
• Replace faulty PLM  
• Check operation of PLM  
7.  
8.  
Demand Cooling (when supplied):  
• Check auxiliary relay  
• Check demand cooling device  
• Replace auxiliary relay  
• Replace faulty demand cooling device  
Check compressor relay on board  
• Replace board if relay is faulty  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Diagnostics  
Beacon II Troubleshooting Guide (continued)  
PROBLEM  
Step ACTION ITEM  
IF OK  
IF NOT OK  
E9 Multi-out to Multi-in  
Communication Wiring  
(only shows after initial  
successful connection)  
1.  
2.  
Check for 24 volts power to the board  
1. If no voltage, see “LED is not lit” above  
for low voltage, see “88888 LED display”  
2. Correct wiring from “Master” unit Multi-out  
to Multi-in of “Slave” unit, etc. to all Slaves  
and return to Master. (See wiring diagrams)  
3. Correct wiring between first Slave with  
error to previous board in the sequence.  
Check for crossed communication wiring  
(multi-out not wired to multi-in terminals)  
Go to  
next step  
3.  
Check for broken communication wiring  
(E9 continued)  
Communication Error  
Occurrence:  
Slave 1  
Master  
Slave 2  
in out  
Slave 3  
in out  
in out  
in out  
3
1
2
Break in the designated  
lines will cause errors  
as follows:  
4
Line #  
Master  
E9  
E9  
E9  
E9  
Slave1  
E9  
no error  
no error  
no error  
Slave 2  
E9  
E9  
no error  
no error  
Slave 3  
E9  
E9  
E9  
no error  
1
2
3
4
Beacon II Smart  
Master  
in out  
Slave 1  
in out  
Slave 2  
in out  
Slave 3  
in out  
Controller  
in out  
3
4
1
2
[With Beacon II Smart Controller]  
5
Line #  
SMART  
+COMM+  
+COMM+  
+COMM+  
+COMM+  
+COMM+  
Master  
E9  
no error  
no error  
no error  
no error  
Slave1  
no error  
E9  
no error  
no error  
no error  
Slave 2  
no error  
E9  
E9  
no error  
no error  
Slave 3  
no error  
E9  
E9  
E9  
1
2
3
4
5
no error  
PROBLEM  
Step ACTION ITEM  
IF OK  
IF NOT OK  
888 LED display  
(power is below 18V and  
appears at initial power)  
1.  
2.  
3.  
4.  
Check Voltage to Evaporator Transformer  
Check Transformer Secondary Output Volts  
Check Voltage at Control Board (24 and C)  
Check Voltage at Beacon II Smart Controller  
1. Check field wiring for breaks or shorts  
2. Replace if necessary  
3. Check factory wiring and connections  
4. Check field wiring from board  
Go to  
next step  
1.  
2.  
3.  
Check for low voltage  
1. Check all steps for “888 LED display”  
Voltage could drop off too fast to show.  
LED displays dLy  
then oFF with no  
displayed errors  
Go to  
Check for short in field wiring from “comp” on next step. 2. Check internal factory wiring to  
board to condensing unit terminal connection  
Replace defective contactor (holding coil)  
compressor contactor.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Diagnostics  
Beacon II Troubleshooting Guide (continued)  
PROBLEM  
Step  
ACTION ITEM  
IF OK  
IF NOT OK  
1. Check system operation: Is it running?  
1. Check power to condensing unit  
Check position of Service Mode switches  
Check compressor overloads and contactor  
2. Add or remove refrigerant to proper charge  
3. Check EEV operation  
2. Check system charge  
3. Check for proper operating superheat  
Check control board EEV signal  
Check suction sensor and transducer  
4. Check EEV inlet screen and restrictions  
Check liquid line sizing  
4. Check for high superheat and EEV wide open  
Check head pressure controls  
5. Check Low Pressure Safety Switch  
6. Compare equipment capacity with requirements  
7. Check box temperature setpoint  
5. Check everything for E7 LPS above  
6. Add or replace with more/larger equipment  
Cannot get to box  
temperature  
Go to  
next step 7. Correct setpoint to proper value  
8. Check compressor application limitations  
Check integrity of compressor operation  
(impaired, worn or damaged components)  
9. Clean condenser coil  
8. Check compressor performance  
9. Check condenser coil for dirt/debris  
10. Check condenser for non-condensables  
11. Check condenser fan operation  
10. Remove all non-condensables  
11. Replace/repair fan blade, motor, cycling  
switch or make corrective adjustments.  
12. Compare board setpoint and refrigerant  
13. Defrost coil and check defrost cycle (see E2)  
settings/setpoints and defrost sensor  
14. Correct defrost setpoints in program  
(frequency and termination of defrosts)  
15. Correct setpoint for more cooling surface  
16. Correct setpoint for proper display values  
12. Check for correct refrigerant type  
13. Check for iced evaporator coil  
14. Check defrost parameters  
15. Check superheat setpoint (too high?)  
16. Check display values (°F or °C)  
Placing system into SERVICE MODE  
(BOARDS ONLY)  
Terminating SERVICE MODE  
(BOARDS ONLY)  
1. Use Remote Service Switch in condensing unit  
2. Pressing “Force Service” button board* twice  
3. Connection between “Ser” and “C” on board*  
(all are wired in parallel; all will activate mode)  
*ONLY Master board on multiple evaporator systems  
1. Must terminate using same switch  
2. Press “Clear” button on board  
3. Open connection between “Ser” and “C”  
(Note: If multiple switches were placed in Service  
Mode, all must be “open” to terminate the mode.)  
Service Mode  
(SEr is displayed)  
(with Beacon II Smart Controller)  
1. Use Remote Service Switch in condensing unit  
2. Connection between “Ser” and “C” on board*  
3. From program menu of Beacon II Smart Controller,  
Change SERVICE setpoint to “On”.  
(with Beacon II Smart Controller)  
1. Must terminate using same switch  
2. Open connection between “Ser” and “C”  
3. From program menu of Beacon II Smart Controller,  
Change SERVICE setpoint to “Off”  
[all are wired in parallel; any/all will activate mode.]  
*ONLY Master board on multiple evaporator systems  
[Note: If multiple switches were placed in Service  
Mode, all must be “open” to terminate the mode.  
)
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Preventive Maintenance  
EVAPORATORS  
All evaporator units should be checked once a month  
or more often for proper defrosting because the amount  
and pattern of frosting can vary greatly. It is dependent  
on the coil temperature, the temperature of the room,  
the type of product being stored, how often new product  
is brought into the room and the percentage of time  
the door to the room is open. It may be necessary to  
periodically change the number of defrost cycles or  
adjust the duration of defrost.  
CONDENSING UNITS / EVAPORATORS  
Under normal usage conditions, maintenance should  
cover the following items at least once every 6 months:  
1. Check and tighten ALL electrical connections  
2. Check all wiring and insulators  
8. Check that all defrost controls are functioning  
properly  
9. Clean the evaporator coil surface  
3. Check contactors for proper operation and for  
worn contact points  
10. Clean the drain pan and check the drain pan and  
drain line for proper drainage  
4. Check all fan motors. Tighten motor mount bolts  
and nuts and tighten fan set screws  
11. Check the drain line heater for proper operation,  
cuts and abrasions  
5. Clean the condenser coil surface  
12. Check and tighten all flare connections  
6. Check the refrigerant and oil level in the system  
7. Check the operation of the control system. Make  
certain all safety controls are operating properly  
Check-Out & Start-Up  
After the installation has been completed, the following points  
should be covered before the system is placed in operation:  
(i) Observe system pressures during charging and initial  
operation. Do not add oil while the system is short of  
refrigerant unless oil level is dangerously low.  
(a) Check all electrical and refrigerant connections.  
Be sure they are all correct and tight.  
(b) Check voltage taps on transformer. The transformer is  
shipped wired to 240 voltage tap/connection. If your  
supply voltage is 208 volt systems, change to 208  
voltage tap.  
(j) Continue charging until system has sufficient refrigerant  
for proper operation. Do not overcharge. Remember that  
bubbles in a sight glass may be caused by a restriction  
as well as a shortage of refrigerant.  
(c) Check setting of time delay relay for low pressure switch  
in condensing unit. It should be set at one minutes  
(the second marker).  
(k) Do not leave unit unattended until the system has  
reached normal operating conditions and the oil charge  
has been properly adjusted to maintain the oil level at  
the center of the sight glass.  
(d) Check high and low pressure controls, pressure  
regulating valves, oil pressure safety controls, and all  
other safety controls and adjust them, if necessary.  
(l) At initial start-up, the system may cycle off at 2 minutes  
and display a low superheat error, then restart itself. This  
cycle may be repeated a few times. Do not shut the  
system off. Let the system run, as it may take a few  
cycles for the electric expansion valve to attain the  
correct setting for the desired superheat.  
(e) On freezers only, check the low pressure switch setting.  
It must be set to 0 PSIG cut out, 10 PSIG cut in, to allow  
start and operation, especially in cold ambients.  
(f) Liquid line should always be insulated.  
(g) Wiring diagrams, instruction bulletins, etc. attached to  
the condensing units should be read and filed for future  
reference.  
CAUTION: Extreme care must be taken in starting  
compressors for the first time after system charging. At  
this time, all of the oil and most of the refrigerant might be  
in the compressor creating a condition which could cause  
compressor damage due to slugging. Activating the crankcase  
heater for 24 hours prior to start-up is recommended. If no  
crankcase heater is present, then directing a 500 watt heat  
lamp or other safe heat source on the lower shell of the  
compressor for approximately thirty minutes will be beneficial  
in eliminating this condition which might never reoccur.  
(h) All fan motors on air cooled condensers, evaporators,  
etc. should be checked for proper rotation. Fan motor  
mounts should be carefully checked for tightness and  
proper alignment.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Service Record  
Date of Start-up  
Location Address  
CONDENSING UNIT  
MODEL #  
SERIAL #  
COOLER UNIT  
MODEL #  
SERIAL #  
FREEZER UNIT  
MODEL #  
SERIAL #  
ELECTRICAL  
COOLER  
Check Primary Supply voltage.  
Refrigerant Type  
Box Setpoint Temp.  
Superheat  
No. of Defrost/Day  
Defrost End Temp.  
R22  
35°F.  
F.  
2
If 208 V, change transformer wiring in the  
Cooler and Freezer to the 208 V tap  
YES  
• Check Compressor Amps for COOLER and  
FREEZER compressors. Should match  
nameplate.  
50°F.  
SYSTEM CHECKS  
• Check Compressor Superheat for the  
YES  
NO  
PIPING  
COOLER (Should be between 20°F. & 3F.)  
• Is suction line trapped at the Cooler?  
YES NO  
• Is suction line trapped at the Freezer?  
YES NO  
YES  
NO  
• Check Compressor Superheat for the  
FREEZER (Should be between 20°F. & 3F.)  
YES  
NO  
• Force unit into a Defrost Check heater amps.  
Should match nameplate amps.  
DRAIN LINES  
• Are drain lines sloped properly?  
YES  
NO  
YES  
NO  
• Check LPS Time Delay Relays. Should be  
set at 1 minute for both the COOLER and  
FREEZER.  
• Is drain line trapped outside the Cooler?  
YES  
• Is drain line trapped outside the Freezer?  
YES NO  
• Is heat tape wrapped along entire length of  
the drain line in the Freezer?  
NO  
YES  
NO  
• Check Low Pressure Switch on FREEZER. Should  
be set at 0 psig Cut-out/10 psig Cut-in.  
YES  
NO  
YES  
NO  
• Did FREEZER and COOLER cycle off on LPS at  
Setpoint Temperature?  
• Is heat tape plugged in and heating the drain  
line?  
YES  
NO  
YES  
NO  
• Is the sight glass free of bubbles?  
INSULATION  
• Are Liquid lines fully insulated?  
YES  
NO  
• Are the COOLER and FREEZER fans at proper  
speeds?  
YES  
NO  
• Are Suction lines fully insulated?  
YES  
NO  
YES  
NO  
• Check system for refrigerant leaks. Are there any  
leaks on the COOLER, FREEZER, CONDENSING  
UNIT or INTERCONNECTING PIPING?  
SETTINGS  
• Check Beacon II board settings for the  
following:  
FREEZER  
Refrigerant Type  
Box Setpoint Temp.  
Superheat  
No. of Defrost / Day  
Defrost End Temp.  
YES  
NO  
• Check system piping for unusual vibration or  
noise. Is there any unusual vibration or noise on  
the COOLER, FREEZER, CONDENSING UNIT or  
INTERCONNECTING PIPING?  
R404A  
-10°F.  
F.  
4
65°F.  
YES  
NO  
• Start the FREEZER only. Does the compressor  
start and evaporator fans run for this FREEZER?  
YES  
NO  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Service Record  
RECORD  
OUTDOOR TEMPERATURE  
______°F  
______Volts  
SYSTEM VOLTAGE  
______PH  
______L2  
______L2  
______Hz  
______L3  
______L3  
Cooler Compressor Amps  
Freezer Compressor Amps  
Cooler Discharge Pressure  
Freezer Discharge Pressure  
Cooler Suction Pressure  
Freezer Suction Pressure  
Cooler Suction Temp.  
______L1  
______L1  
______PSIG  
______PSIG  
______PSIG  
______PSIG  
______°F  
Freezer Suction Temp.  
______°F  
Cooler Refrigerant Charge  
Freezer Refrigerant Charge  
Cooler Compressor Superheat  
Freezer Compressor Superheat  
Cooler Evaporator Superheat  
Freezer Evaporator Superheat  
Cooler Discharge Temp.  
Freezer Discharge Temp.  
______lbs.  
______lbs.  
______°F  
______°F  
______°F  
______°F  
______°F  
______°F  
Since product improvement is a continuing effort, we reserve the right to make changes in  
specifications without notice.  
The name behind the brands you trust.™  
CLIMATE  
Commercial Refrigeration Parts  
CONTROL  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graco Heat Pump Model 260408 User Manual
Grizzly Automobile Parts H8097 User Manual
Grizzly Router H7507 User Manual
Grizzly Saw G0605X G0606X User Manual
Honeywell Switch 272630D User Manual
HP Hewlett Packard Flat Panel Television HP z558 User Manual
HP Hewlett Packard Server AD117 9003A ED3 User Manual
HP Hewlett Packard Work Light xw4600 User Manual
Hubbell Work Light SM 24 User Manual
Hunter Fan Outdoor Ceiling Fan 4112B User Manual