Heatcraft Refrigeration Products Refrigerator H IM 79E User Manual |
Beacon II™
Refrigeration Systems
H-IM-79E
JANUARY 2011
Part No. 25001401
Replaces H-IM-79E (09/07)
Table of Contents
Installation and
Operation Manual
Beacon II™ Board Layout........................................................ 3
Installation Tips ........................................................................ 4
Refrigerant Line Brazing........................................................... 5
Power Supply........................................................................... 5
Wiring ....................................................................................... 5
Multiple Evaporator Configuration ........................................... 6
Box Temperature Control Settings........................................... 7
Leak Testing ............................................................................. 7
Refrigerant Charging ............................................................... 7
Start-Up Operation..............................................................8-11
Operating Mode Display......................................................... 11
Programming and Reviewing Settings and Changes .......12-13
Program Review Button
Select Button
Enter Button
Monitoring Items .................................................................... 14
Monitor Button
Force Defrost Button
Force Service Button
Reset Time Button
Clear/Test Button
Locking The Beacon II Board................................................. 15
Status Indicator LED .........................................................15-16
Low Ambient Operation ......................................................... 16
Pumpdown........................................................................16-17
Defrost...............................................................................17-18
Alarms ................................................................................... 18
Error Indicator......................................................................... 19
Checking Operation of Expansion Valve...........................20-21
Power Failures........................................................................ 21
Spare Sensor Terminals.......................................................... 21
Checking Sensors .................................................................. 21
Sensor Resistance/Temperature Table................................... 22
System Defaults ..................................................................... 22
InterLink Replacement Parts List ........................................... 23
Operational Limits .................................................................. 23
Expansion Valve Capacity...................................................... 24
Diagnostics........................................................................24-27
Wiring Diagrams................................................................28-33
Preventive Maintenance......................................................... 34
Service Record..................................................................35-36
™
Download from Www.Somanuals.com. All Manuals Search And Download.
Beacon II™ Board Layout
BEACON II™ BOARD
Defrost
Heater
Relay
Evaporator
Expansion
Valve
Connection
Fan
Relay
LED
Display
Selection
Buttons
Room
Sensor
Defrost
Sensor
24V
Terminal
Block
Suction
Sensor
Suction
Pressure
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Installation Tips
•
Use a minimum 18 gauge wire for all low
•
Some systems may require the crankcase
voltage connections
heater be energized 24 hours prior to
start-up. The Beacon should be de-
energized for this period by placing it in
the SERVICE MODE. This is done by
pressing the FORCE SERVICE button
twice. To start the system cooling, press the
CLEAR button.
•
The Beacon II board gets its 24 VAC power
supply from a transformer mounted in the
electrical end of each evaporator. On
208-240 volt systems the multi-tap
transformer is shipped from our factory wired
for 240 volts. If your supply voltage is 208
volt you must change to the 208 volt tap on
the transformer.
•
•
Room sensors must be left connected on
ALL evaporators.
NOTE: On multiple evaporators, since a
transformer is in each evaporator, the
voltage tap must be set on each
evaporator.
A pressure transducer is installed on the
evaporator. Do not leak test system above
150 PSI or damage to transducer could
occur. If leak testing must be greater than
150 psig, disconnect the transducer from
he suction header and reconnect after
testing is complete.
•
Refer to wiring schematic shipped on units
for unit wiring. Schematics in this Installation
& Operation Manual are typical wiring
schematics only.
Condensing Unit
•
•
Program ALL slave evaporators as SLAVES.
The condensing unit control panel contains the relays,
contactors, time delay and a terminal block which is
appropriately marked to match the low voltage wiring
connections. A sensor for outdoor air temperature
measurement is installed on the condensing unit.
Evaporators are shipped from our factory
with a preset box setpoint temperature of
35°F for air defrost and -10°F for electric
defrost. If your box setpoint temperature
requirements are different this must be set
using directions outlined under “Room
Temperature Control”.
Condensing unit must be installed using proper
refrigeration practices and codes. Make sure there is
sufficient clearances around unit for adequate air flow
and access.
•
The suction line temperature sensor MUST
be removed from the suction line before
brazing the suction tubing. The sensor
MUST then be reinstalled on the suction
line after brazing is completed and the tubing
has cooled. Insulate when finished.
Evaporator Unit
The evaporator contains the Beacon II controller, electric
expansion valve, pressure transducer, distributor, orifice,
transformer and three sensors. These components are
all factory mounted and wired. The three sensors are
factory mounted and provide input to the controller from
the following: defrost temp., suction temp., room temp.
•
•
The low pressure switch time delay relay,
located in the condensing unit, must be set
to 1 minute.
Each evaporator unit must be installed using proper
refrigeration practices and codes. Make sure the
piping is correctly sized and properly routed. It is highly
recommended that the liquid and suction lines be
insulated. There must also be good clearance around
unit. See Heatcraft Refrigeration Installation & Operation
Manual for more details.
If electrical power will be connected prior to
evacuation and charging of system, unplug
electric expansion valve from board until
system is ready to be evacuated, leak tested
and charged.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Brazing
Refrigerant Line Brazing (Caution)
The electric expansion valve and the suction temperature
sensor on the suction line are factory installed.
Care must be taken when brazing these lines at the
evaporator.
•
Low voltage - 24V Class II control circuit.
A total of five low voltage leads are required
to connect the condensing unit to the
evaporator. (See wiring diagram.) Two of
these leads are for connecting the outdoor
temperature sensor. The other three leads
are for connecting the compressor relay,
service relay and 24V Common inputs.
All 24 volt wiring must be run separate
from the line voltage wiring.
Too high a temperature may destroy these
components. Heat absorbing compounds or “wet
rags” must be used to protect the electric expansion
valve when brazing the refrigerant line connections.
The suction line sensor should be removed before
brazing.
•
Low voltage wiring must be 18 gauge
minimum. For low voltage wiring, maximum
distances are:
Power Supply
The Beacon II board gets its 24 VAC power supply from
a transformer mounted in the electrical end of each
evaporator. On 208-240 volt systems the multi-tap
transformer is shipped from our factory wired for 240
volts. If your supply voltage is 208 volt you must change
to the 208 volt tap on the transformer.
Condensing unit to Master evaporator
Between evaporators
Smart Controller to Master evaporator
500 ft.
500 ft.
1000 ft.
•
•
•
Multiple units – The multi-in and multi-out
are the communication connections.
Connection sequence must follow the multi-
out terminal to the multi-in terminal and
the multi-out back to the multi-in terminal in
a daisy chain loop.
VERY IMPORTANT: If the supply voltage to the
evaporator is 208 volts, the primary tap of the
transformer must be moved to the 208 volt tap.
This must be done for all the evaporators on that
system.
Alarm circuit - The onboard alarm is a
dry set of NC contacts which closes to
indicate an alarm. The type and wiring for
the alarm is customer specified. Note that
the alarm circuit does not distinguish or
indicate what has caused the alarm.
If the 24 VAC power supply falls below 18 VAC the
system may power down and shut off. When the power
supply is corrected to 24 VAC the system will restart
after the four minute hold-off period and resume normal
operation.
On Beacon II systems the main power for the evaporator
can be supplied separately from the power supply of the
condensing unit. All wiring, however, must comply with
local electrical codes.
All wiring must comply with all applicable
codes and ordinances.
Wiring
Wiring between the condensing unit and the unit
cooler(s) will be as follows (see wiring diagrams):
•
High voltage - There may be high voltage on
the defrost heater relay and the fan relay.
The evaporator may also be connected to a
separate power supply from the condensing
unit. See unit cooler spec. plate for ampacity.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration
Multiple Evaporator Configuration (Master/slave)
If there are multiple evaporators on a system, the
factory default as a MASTER evaporator. Place all
program for each SLAVE evaporator must be changed to boards in the “SERVICE” mode while you program the
identify it as a SLAVE. To do so, press the “PROGRAM
REVIEW” button repeatedly until “SLA” appears then
use the “SELECT” knob to select “YES” then press
“ENTER”. All Beacon II boards are shipped with the
setpoints to avoid errors and alarms which may cause
troubles at startup.
VERY IMPORTANT: This must be done for each slave
board.
PROGRAM
REVIEW
SELECT
Up to 4 evaporators can be connected as a
master/slave configuration. DO NOT remove the room
sensor from any of the Beacon II boards.
This also applies when connected to the optional Smart
Controller.
S
S
M
S
CU
M = Master Evaporator
S = Slave Evaporator
CU = Condensing Unit
Each Beacon II board power is supplied by a transformer in the evaporator on which
it is mounted. Do not run any 24 VAC wires between Beacon II boards on the evaporators.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Box Temp Control Settings
Leak Testing
Box Temperature Control Settings
After all lines are connected, the entire system must be
leak tested. The complete system should be pressurized
to not more than 150 psig with refrigerant and dry
nitrogen. The use of an electronic type leak detector is
highly recommended because of its greater sensitivity
to small leaks. As a further check it is recommended
that this pressure be held for a minimum of 12 hours
and then rechecked. For a satisfactory installation, the
system must be leak tight.
•
There is an on board room thermostat on
the Beacon II board which can be adjusted
to the desired room temperature. The
temperature differential is 2° F.
Temperature Differential
When a system is in the cooling mode and
the box setpoint is 35°F, the system will
continue to cool until the box temperature
gets to 34°F. At this point the compressor
will pumpdown and shut off. The system will
restart cooling when the box temperature
has risen to 36°F.
Refrigerant Charging
Beacon II systems are shipped standard with a head
master valve (scroll compressor models have a 100 PSI
head master valve. All other models have a 180 PSI head
master valve). The maximum system refrigerant capacity
is the receiver capacity as listed in the sales literature
plus the liquid line capacity. Do not add more refrigerant
to the system than 90% of the receiver capacity.
It is important to note that Beacon II has
a minimum 2 minute “ON” time and a
minimum 4 minute “OFF” time. This
means that the system will run in the cooling
mode a minimum of 2 minutes even
if the setpoint temperature is met. In
applications where the system is grossly
oversized, the box temperature could go
below the differential temperature before the
system cycles off.
In the “OFF” cycle the system will be off for
a minimum of 4 minutes even if the
box temperature goes above the differential
temperature, before cooling will be restarted.
•
The on board room thermostat is factory
set at 35°F for Air Defrost systems and
-10°F for electric defrost system.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Start-Up Operation
Start-Up Operation
Single System With 1 Evaporator
•
Check all wiring connections to be sure
they are correct and tight.
•
On the evaporator
-
-
Use the “PROGRAM REVIEW”
button to scroll through settings.
•
On the condensing unit
-
-
Check the setting of time delay
relay. It should be set at 1 minute
(the second marker).
Check “rEF” (Refrigerant Type).
Factory defaults are: Air Defrost
R-22, Electric Defrost R-404A.
Change to the refrigerant being used.
Check the low pressure switch
setting on freezer units. It must be
set to 0 psig cut-out, 10 psig cut-in
to allow positive start and operation,
especially in cold ambients. This
can be changed to a higher value in
warmer climates. On cooler units, the
low pressure switch has a fixed
setting and cannot be adjusted.
-
Check “bot” (Box Temperature).
Factory defaults are: air defrost
35°F and electric defrost –10°F.
Change to the desired temperature.
-
-
Review and change other setting if
necessary
See procedures below on how to
change settings.
•
Turn power on
CU
M
M = Master Evaporator
CU= Condensing unit
8
Download from Www.Somanuals.com. All Manuals Search And Download.
Start-Up Operation
Single System With Multiple
Evaporators
•
Check all wiring connections to be sure
they are correct and tight.
-
-
Check “rEF” (Refrigerant Type).
Factory defaults are: air defrost
R-22, electric defrost R-404A.
Change to the refrigerant being used.
•
On the condensing unit
-
-
Check the setting of time delay
relay. It should be set at 1 minute
(the second marker).
Check “bot” (Box Temperature).
Factory defaults are: air defrost
35°F and electric defrost –10°F.
Change to the desired temperature.
Check the low pressure switch
setting on freezer units. It must be
set to 0 psig cut-out, 10 psig cut-in
to allow positive start and operation,
especially in cold ambient. This
can be changed to a higher value
in warmer climates. On cooler units,
the low pressure switch has a fixed
setting and cannot be adjusted.
-
-
Review and change other setting if
necessary.
See procedures below on how to
change settings.
•
On the SLAVE evaporators. All Beacon II
boards are shipped with the factory
default as a “MASTER” evaporator.
•
•
Turn power on.
-
-
DO NOT REMOVE the Room Sensor
from any evaporator
On the MASTER evaporator
-
-
DO NOT REMOVE the room sensor
from any evaporator
Each SLAVE Evaporator must be
changed to identify it as a SLAVE.
Use the “PROGRAM REVIEW” button
to scroll until “SLA” appears, then
use the “SELECT” knob to select
“YES” then press “ENTER.”
Use the “PROGRAM REVIEW” button
to scroll through settings.
S
S
M
S
CU
M = Master Evaporator
S = Slave Evaporator
CU = Condensing Unit
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Start-Up Operation
Multiple Systems With Multiple
Evaporators (Requires A Smart
Controller)
•
Check all wiring connections to be sure
they are correct and tight.
•
•
On the MASTER evaporator
-
DO NOT REMOVE the room sensor
from any evaporator
•
On the condensing units
-
-
Check setting of time delay relay.
It should be set at 1 minute
(the second marker).
On the SLAVE evaporators. All Beacon II
boards are shipped with the factory
default as a “MASTER” evaporator.
Check the low pressure switch
-
Each SLAVE evaporator must be
changed to identify it as a SLAVE.
Use the “PROGRAM REVIEW”
button to scroll until “SLA” appears,
then use the “SELECT” knob to
select “YES” then press “ENTER.”
setting on freezer units. It must be set
to 0 psig cut-out, 10 psig cut-in to
allow positive start and operation,
especially in cold ambient. This
can be changed to a higher value in
warmer climates. On cooler units,
the low pressure switch has a fixed
setting and cannot be adjusted.
•
Use the Beacon II Smart Controller to
set system parameters. See Beacon
II Smart Controller installation
•
Turn power on.
instructions for more details.
MULTIPLE SYSTEM CONNECTION
(See Smart Controller instruction manual for more details)
SYSTEM 2
SYSTEM 3
SYSTEM 1
S
S
S
S
S
S
S
CU
S
M
M
S
M
CU
CU
M
S
CU
SMART
CONTROLLER
S
S
SYSTEM 4
CU = Condensing Unit
M = Master Evaporator
S = Slave Evaporator
10
Download from Www.Somanuals.com. All Manuals Search And Download.
Start-Up Operation
Initial Power On
At the initial application of power to the system, the
compressor and the evaporator fans will be in a 4 minute
hold-off cycle and will not start immediately. When there
is a call for COOLING, the expansion valve (EEV) opens,
then the compressor is started. The compressor will
then run for a minimum of 2 minutes in the “hold-on”
cycle. (This means that the compressor will run for a
minimum of 2 minutes before shutting off even if the box
temperature is met).
When the room sensor detects a rise in temperature of
approximately 2°F, and the compressor has been off for
at least 4 minutes, the EEV will open to its last position
then the compressor will start. The valve is then adjusted
as necessary to obtain the setpoint superheat setting.
During this time, the compressor will run for a minimum
2 minutes “hold-on” cycle.
The four minute “HOLD-OFF” can be bypassed and the
system started immediately by pressing the “RESET”
button on the Beacon II board.
The LED alternately displays BOX TEMPERATURE
and MODE of operation. On a call for cooling, dLY will
show while the expansion valve is opening. After the
compressor starts the LED will alternately display BOX
TEMPERATURE and Coo.
Operating Mode Display
On multiple evaporator systems the MASTER evaporator
will display BOX TEMPERATURE and Coo. The SLAVE
evaporators will display Coo only.
oFF - Off
Coo - Cooling
Pdn - Pumpdown
dEF - Defrost
drn - Draining
dLY - Delay
tSt - Test
When the room thermostat setting is satisfied, and if
the compressor ran for at least 2 minutes, the EEV will
close and the compressor will pumpdown and shut off.
The evaporator fans will continue to run. The LED will
alternately display oFF and BOX TEMPERATURE.
SEr - Service
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming & Reviewing
Programming And Reviewing Settings / Changes
“PROGRAM REVIEW” ITEMS
The PROGRAM REVIEW button is used to program,
review and change all program settings for the system.
A-E - Set Defrost type
Press “PROGRAM REVIEW” button. The Setpoint
item will appear on the LED. After a few seconds delay
the Setpoint value will display. Each time the button is
pressed a different setpoint item is displayed.
(Air or ELE)
rEF - Set Refrigerant type
(R22, R404A or R507)
bot - Set Box temperature
(-30°F to +70°F)
SUP - Set Superheat
(4°F to 20°F)
SLA - Set Board as a Slave
Next, use the “SELECT” knob to change value of
Setpoint Item.
(Yes or No)
dFn - Set Number of defrosts per day
(1, 2, 3, 4, 5, 6, 8,10 or 12 per day)
dFF - Set Defrost Fail-safe time
(10 to 200 minutes)
dFt - Set Defrost End temperature
(40°F to 100°F)
dFS - Set Defrost Delay Start Time
Next, When the desired value is selected, press the
“ENTER” button to place it in program memory. If the
“ENTER” button is not pressed the value will not be
stored in the memory and thus will not be changed.
(0.5 Hours to 23.5 Hours)
ALH - Set Alarm High temperature
(-40°F to 90°F)
ALL - Set Alarm Low temperature
(-40°F to 90°F)
ALt - Set Alarm time
(2 to 120 minutes)
F-C - Set Fahrenheit / Celsius
temperature units (°F/°C)
12
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming & Reviewing
Programming And Reviewing Settings / Changes (cont’d.)
Use the “PROGRAM REVIEW” button to select these items:
•
Defrost Type – “A-E ” - Selection is made for air
defrost or electric defrost coil. This will
automatically set the system factory defaults for
air defrost and electric defrost. (See default
settings.) Please note that the refrigerant type
default for air defrost is R-22 and for electric
defrost it is R404A. All units are shipped with
factory defaults settings.
selection is made, Defaults: electric defrost 4 per
day and air defrost 2 per day.
•
Defrost fail-safe - “dFF” - This is the maximum
time allowed for a coil to remain in defrost.
Defrost will be terminated if the defrost end
temperature is not attained when this time
has expired. On multiple evaporator systems this
is controlled by the Master unit. Each board
should have the same setting. Defaults: electric
defrost 30 minutes and air defrost 40 minutes.
•
•
•
Refrigerant Type - “rEF” - Selection for type of
refrigerant - R-22, R-404A or R-507. Default:
Air defrost is R-22 and for electric defrost it is
R-404A.
•
Defrost End Temperature - “dFt” - This is the
temperature at which the Defrost will be
terminated. Defaults: electric defrost +60°F and
air Defrost +45°F.
Box Temperature - “bot” - Select box
temperature setpoint. Selection range is -30°F to
+70° F. Defaults: Electric defrost -10°F and air
defrost +35°F.
•
•
Defrost Delay Start Time - “dFS” - This allows
the delay of the start of the first defrost. Defaults:
0.5 hours to 23.5 hours.
Superheat - “SUP” - Evaporator superheat is
controlled by the board on each evaporator.
Each board measure the evaporator saturation
suction temperature and the suction pressure to
determine the superheat. The superheat value
at the evaporator can be changed to ensure a
20°F to 30°F superheat at the Compressor.
Default: 8°F.
Alarm High Temperature - “ALH” - Temperature
at which a high box temperature alarm will be
triggered. This does not apply during defrost.
Defaults: electric defrost +5°F and air defrost
+50°F.
•
•
Alarm Low Temperature - “ALL” - Temperature
at which a Low Box Temperature alarm will be
triggered. Defaults: Electric Defrost -15°F and Air
Defrost +30°F.
•
Evaporator Board: Slave? - “SLA” - On multiple
evaporator systems, each evaporator board has
to be programmed to be a Master or a Slave.
Each board is shipped from our factory set as
a Master. You must make this change to each
Slave evaporator. A selection of “YES” is made
for this setting.
Alarm Time - “ALt” - Time which High
Temperature or Low Temperature condition must
exceed before alarm is triggered. Default:
60 minutes.
The default for each board is a Master, so on
Single Evaporator systems no change is
required.
•
•
°F/°C - “F-C” - Select units to display
temperature. Fahrenheit or Celsius. Default:
Fahrenheit.
•
No. of Defrost per Day - “dFn” - A selection must
be made for the number of defrosts cycles per
day – 1,2,3,4,5,6,8,10 or 12 per day. If no
When °C is selected a red dot will appear in the
right bottom corner of the LED display of the
Beacon II board.
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming & Reviewing
Use this button to “FORCE DEFROST” To force a
MONITOR
defrost , press the “FORCE DEFROST” button. The
system will pumpdown and shut off the compressor. The
heaters are then turned on. The display will show “dEF”
and room temp.
FORCE
DEFROST
Use the “MONITOR”
button to review these items:
SUP - Superheat
(°F/°C)
ESP - Expansion valve steps
Use this button to “RESET TIME” Pressing this button
will reset the time clock in the microprocessor to zero.
At initial power up, pressing this button will bypass
the “four minute” hold-off and the system will start
immediately after the expansion valve opens. This
display will show “dLy”.
(0 to 255 steps)
SCt - Suction temperature
(°F/°C)
SSt - Saturated Suction temperature
(°F/°C)
RESET
TIME
SCP - Suction pressure at Evaporator
(PSIG/HG)
Odt - Outdoor temperature
(°F/°C)
dFt - Defrost sensor temperature
Use this button to “FORCE SERVICE”
(°F/°C)
Pressing this button TWICE will cause the system to
pumpdown and the compressor to shut off. The system
will remain off until the “CLEAR” button is pressed.
While in the “FORCE SERVICE”, the LED display will
only show “SEr”.
dFS - Time left until next defrost
(hours) (on version 1.8 boards)
dFE - Last Defrost Elapsed time
(minutes)
FORCE
SERVICE
AC - Board Voltage
SPt - Spare Temperature reading
14
Download from Www.Somanuals.com. All Manuals Search And Download.
Programming & Reviewing
Programming And Reviewing
Settings/Changes (Cont’d.)
Locking The Beacon II Board
The Beacon II board is lockable to prevent programmed
setting changes by unauthorized personnel. When
locked, the program setpoints cannot be changed.
To lock the setting:
Use this button to “CLEAR/TEST”
Pressing this button ONCE will return the LED display to
the default display. With the system in the OFF mode,
pressing and holding this button will start the “TEST”
mode. In the “TEST” mode it will cycle through each
output for 10 seconds. The display will only show “tst”
during “TEST” mode. Test mode will automatically
terminate after 3 sequences.
•
•
•
Press “PROGRAM REVIEW” button.
Press and hold “MONITOR” button.
While holding “MONITOR” button,
press “ENTER” button.
•
The LCD will display Loc.
This will prevent unauthorized personnel program
changes. To unlock, repeat steps above. LCD will
display “UnL”.
STATUS INDICATOR LED
A RED, three-digit , alphanumeric LED on the
Beacon II board indicates status, alarms and
error codes.
• OFF
All Evaporators
Box Temp / oFF
Box Temperature/ Mode is displayed
Box Temperature/ Mode is displayed
• COOLING
Single Evaporator-
Multiple Evaporators
Master Evap -
Box Temp /Coo
Box Temp / Coo
Box Temperature/ Mode is displayed
Operating Mode is displayed
Slave Evaps -
Coo
• Pumpdown
All Evaporators
Pdn
dEF
tSt
• DEFROST
All Evaporators
• TEST
All Evaporators
• SERVICE
All Evaporators
SEr
• ALARMS
A 1
A 2
A 3
High Box Temp
Low Box temp
System Start-up failure
Compressor pumps down and tries
to restart after 4 minutes.
Input Fault
A 4
Box Temp., Suction Temp., Pressure
Transducer open or not installed
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Status Indicator LED
STATUS INDICATOR LED
•
ERRORS
E 1 - Room temperature sensor shorted, open or not installed
E 2 - Defrost temperature sensor shorted, open or not installed
E 3 - Suction temperature sensor shorted, open or not installed
E 4 - Suction pressure transducer shorted, open or not installed
E 5 - Outdoor temperature sensor shorted
E 6 - Low superheat during cooling
E 7 - Compressor shutdown
(high or low refrigerant pressure or low oil pressure)
E 9 - Multi-in/Multi-out wiring error
•
OTHERS
Coo - Room Temperature sensor open or not connected
(Instead of displaying box temperature)
Loc - Board is locked. Settings cannot be changed
UnL - Unlock the board settings
Low Ambient Operation
All units are shipped standard with Head Master valves.
(Scroll compressor units have a 100 PSI Head Master
valve and all other systems have a 180 PSI head master
valve.) Condensing units with multiple condenser fans
will have one or more fans cycle on Pressure Fan Cycling
switch.
When any of these three conditions occurs the
compressor will turn off and not restart until there is a
call for cooling or a periodic pumpdown.
Periodic Pumpdown
An adjustable Time Delay relay, factory set at 1 minute,
is wired across the Low Pressure switch (LPS). In cold
ambient this allows time for the suction pressure to build
up and prevent nuisance tripping of the LPS.
While in the OFF cycle, if there isn’t a call for cooling
(Box setpoint temperature is met) but:
•
•
The evaporator suction pressure has
risen to 10 psig
Pumpdown
The low pressure switch has closed
At the end of each cooling cycle, when the box
temperature is met, the Beacon system will pump down
and shut off the compressor.
The system will initiate pumpdown. This periodic
pumpdown will occur at 4 minute intervals when these
two conditions are met.
To pumpdown, the EEV closes and the compressor runs
until one of the following occurs:
•
•
The low pressure switch opens
The suction pressure at the evaporator
is 4 psig
•
A total of two minutes has elapsed
16
Download from Www.Somanuals.com. All Manuals Search And Download.
Pumpdown / Defrost
Service Mode
Defrost Delay Start Time
Example: The system is first powered up at 8:00 AM and
is programmed for 4 defrost per day. The user would like
the first defrost at 10:00 AM. To accomplish this, use the
“PROGRAM REVIEW” button to scroll to dFS. Use the
“SELECTOR” switch to select 2 hours delay start, then
press “ENTER.” The 1st defrost will now occur at 10:00
AM and then a defrost will occur every 6 hours thereafter.
A single pole, single throw switch (SPST) is supplied in
each condensing unit for shutting off the system. Closing
the “SERVICE” switch in the condensing unit will cause
the system to pumpdown and shut off. “Ser” will be
displayed on the Beacon board LED and “SERVIC”
is displayed on the Smart Controller LCD display. The
evaporator fan and heaters will be de-energized in the
Service Mode.
Time Remaining Until Next Defrost
(On Version 1.8 Boards)
The system will not restart until the SPST switch is
placed in the “NORMAL” or “OFF” position.
OR
To find out how much time is left until the next defrost is
scheduled, use the “MONITOR” button to scroll to dFS.
The time displayed will be how much time until the next
scheduled defrost.
A remote “SERVICE” switch can be added to the
Beacon II board across the “Ser” and “C” connections of
the terminal block. It will operate in the same manner as
the switch above.
Defrost Schedule In Memory
OR
Beacon II does not have a real time clock but it keeps
track of the time that has elapsed in its memory. It also
keeps in memory the number of defrosts scheduled
and how much time has elapsed between defrosts. If a
power failure occurs, when power is restored Beacon
II remembers how many defrosts are scheduled and
it remembers how much time was left until the next
defrost. It will then defrost based on this timing. So, if the
power failure lasted 15 minutes, the defrost schedule will
be off by 15 minutes.
The system can be pumped down by pressing the
“SERVICE” button twice. To restart the system, press
the “CLEAR” button.
OR
The system can be pumpdown for service by closing
the liquid line service valve in the condensing unit, then
closing the suction line service valve when the system
trips on the low pressure switch.
In order for air defrost evaporator fan motors to cycle off
during “SERVICE” mode, the fan motors must be wired
through the fan relay on the Beacon II board.
Resetting Defrost Schedule
When a power interruption causes a severe lag in the
defrost schedule, the defrost schedule can be reset in
the following manner. First, press the reset time button
on the board to zero out the internal counters. Then,
program the appropriate defrost delay start time for the
next desired defrost period. The defrost schedule will be
Defrost
Defrost Timing
correct until you have another power outage.
When power is first applied to the system, its timer
starts counting time. If 4 defrost are programmed, it will
initiate a defrost every 6 hours from when power was
first applied. Beacon II does not have a real time clock.
Beacon II does provide the ability to delay the starting of
the first defrost.
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Defrost / Alarms
Electric Defrost Mode
When a defrost is initiated, the EEV closes, the
compressor is allowed to pumpdown and shut off. The
evaporator fans are cycled off and the defrost heaters
are energized.
•
Low Box Temperature - LED Display:
A 2 - Room temperature has dropped
below the Alarm Low ALL value for the
Alarm time ALt, programmed
On multiple evaporator systems, all controllers must
terminate their defrost, either on temperature or fail-safe
time, before the master controller will end the defrost
cycle.
There is a 2 minute condensate drain-down period after
which the compressor is started for a refreeze period.
The evaporator fan stays off (fan delay). The refreeze
period will last until the evaporator suction temperature
is at 28°F or 3 minutes has elapsed. After this sequence,
the system is back in the refrigerating mode and
evaporators fans are now running.
•
System Start-up failure – LED Display:
A 3 - Compressor pumps down and tries
to restart after 4 minutes. After 4
unsuccessful attempts to restart, the
alarm code A 3 is displayed. System
continues trying to restart.
•
•
Input Fault – LED Display: A 4 - Box
Temp., Suction Temp., Pressure
Transducer open or not installed.
Air Defrost Mode
Power failure – Loss of power to the
Evaporator
The sequence is the same as for electric defrost except
that there are no heaters and the evaporator fans run
continuously. If the air defrost for motors are wired
through the fan relay on the board, they will remain
energized during defrost mode.
Alarm Codes
A 1 High Box Temp
A 2 Low Box temp
Alarms
A 3 System Start-up failure
Compressor pumps down and tries to
restart after 4 minutes
A 4 Input Fault
Beacon provides a set of dry contacts for use in
signaling an alarm. These contacts can be connected
to a light, a buzzer, a bell etc., which will be activated
when an alarm condition occurs. When the Beacon II is
energized, the alarm contacts are OPENED. When an
alarm condition is detected, the contacts are CLOSED.
Box Temp., Suction Temp., Pressure
Transducer open or not installed
Conditions under which the alarm contacts will close are:
Clearing Alarms
Alarms A1 – High Box Temp. and A2 – Low Box Temp.
will clear automatically if the Box Temp. decreases
or increases to below or above the Alarm setpoint
temperature. Placing the system in the “SERVICE
MODE” or turning off power will clear the A3 Alarm.
Replacing the Room Sensor, Suction Sensor or Pressure
Transducer will clear the A4 Alarm.
•
High Box Temperature – LED Display:
A 1 - Room temperature has exceeded
the Alarm High ALH value for the Alarm
time ALt, programmed.
18
Download from Www.Somanuals.com. All Manuals Search And Download.
Error Indicator
Error Indicator Led
ERROR CODES
E1 - Room temperature sensor shorted,
open or not installed
E2 - Defrost temperature sensor shorted,
open or not installed
At initial power up, each Beacon II board checks for
system errors. The system error check involves checking
the various temperature sensors to determine whether
any of these sensors are shorted or open.
E3 - Suction temperature sensor shorted,
open or not installed
E4 - Suction pressure transducer shorted,
open or not installed
The system will pumpdown and cycle off and will not
restart until the fault is cleared or the circuit breaker
reset, for the following conditions:
E5 - Outdoor temperature sensor shorted
E6 - Low superheat
-
-
-
Suction sensor shorted, open
or not installed
E7 - Compressor shut down
(high or low pressure switch open or
oil pressure switch open)
Room temperature sensor shorted
or not installed
E9 - Multi-in/multi-out wiring error
Pressure Transducer open
or not installed
The system will pumpdown, cycle off and try to restart
for these faults. Each try will be after the 4 minutes
“Hold Off” period, for the following fault conditions:
Air Defrost fan motors must be wired through the fan
relay on the Beacon II board for this to be effective on Air
Defrost systems. The entire system will be shut off and
remain off until the SPST switch is opened.
- High pressure or low pressure cutout
- Oil pressure
Air Defrost evaporator fans are setup to run constantly.
If there is a need to shut down the evaporator fans on
an Air Defrost system, this can be accomplished by
wiring the evaporator fan motor or evaporator fan motor
contactor through the fan relay on the Beacon II board.
When this is done and the Air Defrost system
After the fourth try, the Alarm contacts will be closed
and an alarm message displayed on the LED. To clear
this condition, the system should be cycled through the
“SERVICE MODE” after the correction is completed.
is placed in “SERVICE,” the evaporator fans
will shut off when the system is in pumpdown.
Evaporator Fans Shut Off
In some installations, it is desirable to shut off the
evaporator fans periodically. This is easily accomplished
on Beacon II by wiring a single pole, single throw switch
(SPST) between the terminals marked “SERVICE” and
“COM” on the Beacon II board. Closing this switch will
cause the system to pumpdown and shut off.
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Checking Operation of Expansion Valve
Checking Operation Of Expansion
Valve (EEV)
The Expansion valve position can be monitored from
the LED display pressing the “MONITOR” button and
scrolling to ESP. This will indicate the number of steps
the valve is open.
To check if the expansion valve is closing properly:
Install a pressure gauge-set to suction line at
the condensing unit. With the system running,
close the valve on the liquid line, at the con
densing unit. The system should pumpdown
and shut off on the Low Pressure switch (LPS).
If the system does not pumpdown and trip on
the LPS then the compressor valves are weak
and needs to be changed.
This can also be checked by using the EXV test pins on
the board. This is indicated by a 0 to 5 Volts DC signal.
At 0 Volt the valve is closed and at 5 Volts the valve is
fully open. At values between 0 and 5 Volt, the valve will
be opened proportionately.
Use the “MONITOR” button to display “SCP””
Evaporator Suction Pressure. Record the pressure
displayed. Start the system and observe the pressure
displayed. If the pressure does not increase, the
expansion valve could be defective.
After the system pumps-down and trip on the
LPS, put the system in the service mode. This
will cause the Expansion valve to close. Open
the valve on the liquid line, at the condensing
unit. The suction pressure reading on the gauge
set should not increase. If the suction pressure
increases then the expansion valve is leaking
and should be changed.
If the system is running, use the “MONITOR” button to
display “SCP” Evaporator Suction Pressure. Record the
pressure displayed. While the system is running, press
the “FORCE SERVICE” button. Observe the pressure
while the system is pumping down. The pressure should
decrease. If it does not, this indicates a defective valve.
Expansion Valve Motor Winding Resistance
If the expansion valve is suspected of not functioning
properly the motor windings resistance should be
measured. This is a bipolar motor with two windings.
Measure the resistance at the pins, on top of the valve,
between locations A and B
(Note that the pins are not labeled A, B, C, D. This
labeling is just for reference. Also, two of the pins, at
location B and location D, have a wider spacing between
them than between location A and C)
or C and D.
Expansion Valve
A• •C
Motor Winding
Pins
•
•
B
D
For valve size 29320003 and 2930004, the resistance
measured between pin locations A and B or C and D
should be approximately 336 Ohms when valve is at
75ºF.
For valve size 2930007, 29320008, 29320013 and
29320014, the resistance measured between pin
locations A and B or C and D should be approximately
116 Ohms when the valve is at 75ºF.
Continues to Page 21
20
Download from Www.Somanuals.com. All Manuals Search And Download.
Power Failures
Continued from Page 20
Measuring resistance between locations A and C or B
and D will always show “Open” because these locations
are between the motor windings.
Measuring the DC volt of the EXV TEST pins, on the
board, will also indicate if the expansion valve is open
or close. 0 volts DC indicates the valve is closed. 5 volts
DC indicates the valve is fully open. A value between
0 and 5 volts indicates how much the valve is open or
close.
When the valve is opening or closing, the voltage
measured between A and B or C and D should be
between 20 to 22 VAC.
Power Failures
Checking Sensors
In the event of a power failure Beacon II will
automatically close the expansion valve to prevent
refrigerant from migrating throughout the system. After
power returns, with 24 VAC at the board, the system will
restart in the cooling mode after the four-minute hold off
period.
DO NOT REMOVE SENSORS FROM EVAPORATORS
FOR CHECKING.
Use the monitor button to display the value
the sensors are reading on the LED (suction temp. SCt,
defrost temp. dFt or room temp.). Compare this value to
the measured value with a thermometer at each of these
points. If they do not match, change the sensor.
Spare Sensor Terminals
Beacon II provides a set of input terminals for customers
who may want to monitor an additional temperature or
items such as Product Temperature. This input terminal
requires a signal from a thermistor which meets the
temperature/resistance values in Table 1 on page 22.
OR
The sensors can be checked for their proper operation
by placing it in a cup of ice water. Stir the ice water
and measure the resistance of the sensor. At 32°F the
resistance should be 32,650 ohms. If it is higher or lower
by 5,000 ohms approximately, the sensor should be
replaced.
If a product temperature simulator is used it must meet
the resistance/temperature specification listed in Table
1. The temperature range for this input is –30°F to 140°F.
Sensors on the Beacon system, as supplied, will not
simulate product temperature.
This input can be monitored on the LED display by using
the “MONITOR” button and scrolling to SPt. The values
displayed will be the temperature of the spare sensor.
21
Download from Www.Somanuals.com. All Manuals Search And Download.
System Defaults
Table 1. Resistance/Temperature Specification
Temperature °F
Ohms
5,320
Temperature °F
Ohms
32,650
42,330
55,330
72,950
97,070
130,410
176,960
104
86
77
68
59
50
41
32
23
14
5
-4
-13
-22
8,060
10,000
12,490
15,710
19,900
25,400
Table 2. System Defaults
PARAMETERS
CODE
AIR
ELECTRIC
Refrigerant
Box Temperature
Superheat
Slave Evaporator
No. of Defrost per Day
Defrost Fail-safe time
Defrost End Temperature
Defrost Delay Start Time
Alarm High Temperature
Alarm Low Temperature
Alarm Time
rEF
bot
SUP
SLA
dFn
dFF
dFt
dFS
ALH
ALL
ALt
F-C
R-22
35°F
8°F
No
2
40 min.
45°F
0 hrs.
50°F
30°F
60 min.
°F
R-404A
-10°F
8°F
No
4
30 min.
60°F
0 hrs.
5°F
-15°F
60 min.
°F
Temperature Units
22
Download from Www.Somanuals.com. All Manuals Search And Download.
InterLink Replacement Parts List
Replacement Parts by
Commercial Refrigeration Parts
InterLink is your link to a complete line of dependable and certified commercial refrigeration parts, accessories
and innovative electronic controls for all Heatcraft Refrigeration Products (HRP) brands - including Bohn, Larkin,
Climate Control and Chandler. At InterLink, we provide our wholesalers with a comprehensive selection of product
solutions and innovative technologies for the installed customer base. And every product is built to ensure the
same high performance standards with which all HRP brands are built — backed by a dedicated team to serve
every customer need, delivering at the best lead times in the industry.
Table 3. InterLink Replacement Parts List
PART DESCRIPTION
Beacon II Control Board
PART NUMBER
28910101
*Temperature Sensor kit – White Leads
Transformers:
89904902
120/24 volt – 40 VA
240/24 volt – 40 VA
460/24 volt – 40 VA
575/24 volt – 40 VA
22529601
22529602
22529603
22529701
22511401
2252440
Pilot Relay
Contactor for Compressor 40 amp with 24 volt Coil
Terminal Block – Condensing Unit
Low Pressure Switch Time Delay Relay
Electric Expansion Valve
2251266
22536801
ESB 1 – 3/8” x 3/8” Conn
ESB 4 – 3/8” x 3/8” Conn
ESB 10 – 3/8” x 3/8” Conn
ESB 10 – 1/2” x 1/2” Conn
ESB 15 – 7/8” x 1 3/8” Conn
ESB 20 – 7/8” x 1 3/8” Conn
Expansion Valve Molded Connector
(Bipolar valves)
29320003
29320004
29320007
29320008
29320013
29320014
22515201
Pressure Transducer
28911201
22515101
89704301
89704101
89708001
Pressure Transducer Harness
Beacon II Smart Controller
**Smart Controller Software Package
Beacon II Communications Hub
*Only the sensor with white leads is shipped as a service replacement part
**Smart Controller Software package is sold separately
Table 4. Operational Limits
OPERATIONAL LIMITS
Voltage Range
18 VAC to 30 VAC
Controlling Box Temp. Range
Temperature Differential
Cold Ambient Limits
-30°F to 70°F
2°F
Start & operate to -20°F
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Expansion Valve Capacity
R-22
R-404A / R-507
Evaporator Temperature (°F.)
+20 -20
Pressure Drop Across Valve (psi)
Evaporator Temperature (°F.)
+20
-20
Pressure Drop Across Valve (psi)
Part Number
29320003
29320004
29320007 - 08 ESVB-10
29320013
29320014
Valve
ESVB-1
ESVB-4
100
0.68
3.27
8.02
15.14
22.18
BTUH
8160
39240
96240
181680
266160
100
0.64
3.07
7.54
14.25
20.87
BTUH
7680
36840
90480
171000
250440
100
0.48
2.31
5.65
10.69
15.65
BTUH
5760
27720
67800
128280
187800
100
0.42
2.05
5.01
9.47
13.86
BTUH
5040
24600
60120
113640
166320
ESVB-15
ESVB-20
Diagnostics
Beacon II Troubleshooting Guide
PROBLEM
Step ACTION ITEM
IF OK
IF NOT OK
1.
2.
3.
4.
5.
Check Primary Power Supply Disconnect
Check Voltage to Evaporator Transformer
Check Transformer Secondary Output Volts next step
Check Voltage at Control Board (24V and C)
Replace Control Board
1. Check fuses and circuit breakers
2. Check field wiring for breaks
3. Replace if necessary
Go to
LED is not lit.
4. Check factory wiring and connections
1.
2.
Check Compressor internal overloads
Check Control Power to Condensing Unit
(24 Volts across “COMP” and “C” at board)
Check Compressor Contactor Coil Voltage
Check Compressor Contactor “pulled in”
1. Wait for reset
2. Check transformer voltage (secondary and
primary) and wiring of 208V power taps.
3. Check internal condensing unit wiring
4. Replace as needed
LED shows Coo, but
compressor will not run.
Go to
next step
3.
4.
ERROR CODES:
E1 Room Sensor
Check Sensor and Board Connection
Check Sensor and Board Connection
Check Sensor and Board Connection
Check Transducer and Board Connection
Check Sensor, wiring and Board Connection
Replace as needed
Replace as needed
Replace as needed
Replace as needed
Replace or remove
E2 Defrost Sensor
E3 Suction Sensor
E4 Suction Transducer
E5 Outdoor Sensor
1.
2.
Check Refrigerant Type
Check coil for ice
1. Compare board setpoint and refrigerant
2. Defrost coil and check defrost cycle
settings/setpoints, defrost sensor and
heater amps.
E6 Low Superheat
During Cooling
3.
4.
Check Control Board step position from board LED
3. Replace board if EEV steps not at 2.
4. Pumpdown system see if LPS opens or if it
times out (EEV is bad or LPS is set
incorrectly, if times out) – See Pumpdown.
5. Check overloads and contactor.
6. Compare board sensor reading against
actual suction line temperature.
Check Electric Expansion Valve Closure
Go to
next step
(0°F for 2 minutes)
5.
6.
Compressor Not Operating
Check Suction Temperature Sensor
7.
Check Suction Pressure Transducer
7. Compare pressure reading against gauges.
24
Download from Www.Somanuals.com. All Manuals Search And Download.
Diagnostics
Beacon II Troubleshooting Guide (continued)
PROBLEM
Step ACTION ITEM
IF OK
IF NOT OK
1.
2.
Check wiring connection to the board
• Correct field wiring to the board
Low Pressure Safety (LPS) Tripped:
• Check for correct refrigerant type
• Check refrigerant charge
• Change setpoint to match refrigerant
• Add more refrigerant to proper charge
• Correct LPS setting
• Check LPS setting
• Check LPS wiring
• Correct LSP wiring
• Check EEV operation (stuck?)
• Check coil for icing
• Check for correct superheat reading
• Check for correct nozzle selection
• Check for clogged EEV inlet screen
• Check line sizing
• Clean or replace EEV
• Defrost coil (see E6, step 2)
• Check/replace sensor or transducer
• Replace distributor nozzle
• Replace EEV
• Correct line sizing
• Check LPS time delay relay setting
• Check operation of LPS
• Reset to 1 minute
• Replace Low Pressure Safety Switch
3.
High Pressure Safety (HPS) Tripped:
• Check for system overcharge
• Check for non-condensables
• Check condenser fan motor and blade
• Check for dirty condenser coil
• Check head pressure controls
• Check fan cycling controls
• Reclaim/recover excess charge
• Remove all non-condensables
• Repair or replace motor and/or blade
• Clean condenser coil
• Adjust or replace faulty controls
• Adjust or replace faulty controls
• Correct line sizing
• Check liquid line sizing
• Check for liquid line restrictions
• Check operation of HPS
• Repair line or remove restrictions
• Replace HPS if necessary
E7 Compressor
Shutdown
4.
Oil Pressure Safety (OPS) Tripped:
• Check oil level in compressor
• Check oil sump screen pickup
• Check oil pump pressure
• Check for proper piping practices
• Check for low superheat (see E6)
• Check operation of auxiliary relay (R6)
• Check OPS sensor
• Add oil to crankcase to minimum level
• Clean or replace pickup screen
• Replace compressor oil pump
• Correct piping to minimize oil logging
• Correct per steps in E6
• Replace auxiliary relay
• Replace faulty OPS sensor
• Replace faulty OPS
Go to
next step
• Check operation of OPS
5.
6.
Compressor Module Tripped (when supplied):
• Check module
• Check superheat at compressor inlet
• Check compressor for overheating
• Check suction pressure (too low?)
• Replace faulty module
• Reduce superheat (TXV adjust, etc.)
• Correct overheating problem
• Consider crankcase pressure regulator
or other measures
Phase Loss Monitor (PLM) Tripped:
• Check presence of all phase legs
• Check power supply
• Correct power phase problem
• Correct power supply problems
• Replace faulty PLM
• Check operation of PLM
7.
8.
Demand Cooling (when supplied):
• Check auxiliary relay
• Check demand cooling device
• Replace auxiliary relay
• Replace faulty demand cooling device
Check compressor relay on board
• Replace board if relay is faulty
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Diagnostics
Beacon II Troubleshooting Guide (continued)
PROBLEM
Step ACTION ITEM
IF OK
IF NOT OK
E9 Multi-out to Multi-in
Communication Wiring
(only shows after initial
successful connection)
1.
2.
Check for 24 volts power to the board
1. If no voltage, see “LED is not lit” above
for low voltage, see “88888 LED display”
2. Correct wiring from “Master” unit Multi-out
to Multi-in of “Slave” unit, etc. to all Slaves
and return to Master. (See wiring diagrams)
3. Correct wiring between first Slave with
error to previous board in the sequence.
Check for crossed communication wiring
(multi-out not wired to multi-in terminals)
Go to
next step
3.
Check for broken communication wiring
(E9 continued)
Communication Error
Occurrence:
Slave 1
Master
Slave 2
in out
Slave 3
in out
in out
in out
3
1
2
Break in the designated
lines will cause errors
as follows:
4
Line #
Master
E9
E9
E9
E9
Slave1
E9
no error
no error
no error
Slave 2
E9
E9
no error
no error
Slave 3
E9
E9
E9
no error
1
2
3
4
Beacon II Smart
Master
in out
Slave 1
in out
Slave 2
in out
Slave 3
in out
Controller
in out
3
4
1
2
[With Beacon II Smart Controller]
5
Line #
SMART
+COMM+
+COMM+
+COMM+
+COMM+
+COMM+
Master
E9
no error
no error
no error
no error
Slave1
no error
E9
no error
no error
no error
Slave 2
no error
E9
E9
no error
no error
Slave 3
no error
E9
E9
E9
1
2
3
4
5
no error
PROBLEM
Step ACTION ITEM
IF OK
IF NOT OK
888 LED display
(power is below 18V and
appears at initial power)
1.
2.
3.
4.
Check Voltage to Evaporator Transformer
Check Transformer Secondary Output Volts
Check Voltage at Control Board (24 and C)
Check Voltage at Beacon II Smart Controller
1. Check field wiring for breaks or shorts
2. Replace if necessary
3. Check factory wiring and connections
4. Check field wiring from board
Go to
next step
1.
2.
3.
Check for low voltage
1. Check all steps for “888 LED display”
Voltage could drop off too fast to show.
LED displays dLy
then oFF with no
displayed errors
Go to
Check for short in field wiring from “comp” on next step. 2. Check internal factory wiring to
board to condensing unit terminal connection
Replace defective contactor (holding coil)
compressor contactor.
26
Download from Www.Somanuals.com. All Manuals Search And Download.
Diagnostics
Beacon II Troubleshooting Guide (continued)
PROBLEM
Step
ACTION ITEM
IF OK
IF NOT OK
1. Check system operation: Is it running?
1. Check power to condensing unit
Check position of Service Mode switches
Check compressor overloads and contactor
2. Add or remove refrigerant to proper charge
3. Check EEV operation
2. Check system charge
3. Check for proper operating superheat
Check control board EEV signal
Check suction sensor and transducer
4. Check EEV inlet screen and restrictions
Check liquid line sizing
4. Check for high superheat and EEV wide open
Check head pressure controls
5. Check Low Pressure Safety Switch
6. Compare equipment capacity with requirements
7. Check box temperature setpoint
5. Check everything for E7 LPS above
6. Add or replace with more/larger equipment
Cannot get to box
temperature
Go to
next step 7. Correct setpoint to proper value
8. Check compressor application limitations
Check integrity of compressor operation
(impaired, worn or damaged components)
9. Clean condenser coil
8. Check compressor performance
9. Check condenser coil for dirt/debris
10. Check condenser for non-condensables
11. Check condenser fan operation
10. Remove all non-condensables
11. Replace/repair fan blade, motor, cycling
switch or make corrective adjustments.
12. Compare board setpoint and refrigerant
13. Defrost coil and check defrost cycle (see E2)
settings/setpoints and defrost sensor
14. Correct defrost setpoints in program
(frequency and termination of defrosts)
15. Correct setpoint for more cooling surface
16. Correct setpoint for proper display values
12. Check for correct refrigerant type
13. Check for iced evaporator coil
14. Check defrost parameters
15. Check superheat setpoint (too high?)
16. Check display values (°F or °C)
Placing system into SERVICE MODE
(BOARDS ONLY)
Terminating SERVICE MODE
(BOARDS ONLY)
1. Use Remote Service Switch in condensing unit
2. Pressing “Force Service” button board* twice
3. Connection between “Ser” and “C” on board*
(all are wired in parallel; all will activate mode)
*ONLY Master board on multiple evaporator systems
1. Must terminate using same switch
2. Press “Clear” button on board
3. Open connection between “Ser” and “C”
(Note: If multiple switches were placed in Service
Mode, all must be “open” to terminate the mode.)
Service Mode
(SEr is displayed)
(with Beacon II Smart Controller)
1. Use Remote Service Switch in condensing unit
2. Connection between “Ser” and “C” on board*
3. From program menu of Beacon II Smart Controller,
Change SERVICE setpoint to “On”.
(with Beacon II Smart Controller)
1. Must terminate using same switch
2. Open connection between “Ser” and “C”
3. From program menu of Beacon II Smart Controller,
Change SERVICE setpoint to “Off”
[all are wired in parallel; any/all will activate mode.]
*ONLY Master board on multiple evaporator systems
[Note: If multiple switches were placed in Service
Mode, all must be “open” to terminate the mode.
)
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Wiring
28
Download from Www.Somanuals.com. All Manuals Search And Download.
Wiring
29
Download from Www.Somanuals.com. All Manuals Search And Download.
Wiring
30
Download from Www.Somanuals.com. All Manuals Search And Download.
Wiring
31
Download from Www.Somanuals.com. All Manuals Search And Download.
Wiring
32
Download from Www.Somanuals.com. All Manuals Search And Download.
Wiring
33
Download from Www.Somanuals.com. All Manuals Search And Download.
Preventive Maintenance
EVAPORATORS
All evaporator units should be checked once a month
or more often for proper defrosting because the amount
and pattern of frosting can vary greatly. It is dependent
on the coil temperature, the temperature of the room,
the type of product being stored, how often new product
is brought into the room and the percentage of time
the door to the room is open. It may be necessary to
periodically change the number of defrost cycles or
adjust the duration of defrost.
CONDENSING UNITS / EVAPORATORS
Under normal usage conditions, maintenance should
cover the following items at least once every 6 months:
1. Check and tighten ALL electrical connections
2. Check all wiring and insulators
8. Check that all defrost controls are functioning
properly
9. Clean the evaporator coil surface
3. Check contactors for proper operation and for
worn contact points
10. Clean the drain pan and check the drain pan and
drain line for proper drainage
4. Check all fan motors. Tighten motor mount bolts
and nuts and tighten fan set screws
11. Check the drain line heater for proper operation,
cuts and abrasions
5. Clean the condenser coil surface
12. Check and tighten all flare connections
6. Check the refrigerant and oil level in the system
7. Check the operation of the control system. Make
certain all safety controls are operating properly
Check-Out & Start-Up
After the installation has been completed, the following points
should be covered before the system is placed in operation:
(i) Observe system pressures during charging and initial
operation. Do not add oil while the system is short of
refrigerant unless oil level is dangerously low.
(a) Check all electrical and refrigerant connections.
Be sure they are all correct and tight.
(b) Check voltage taps on transformer. The transformer is
shipped wired to 240 voltage tap/connection. If your
supply voltage is 208 volt systems, change to 208
voltage tap.
(j) Continue charging until system has sufficient refrigerant
for proper operation. Do not overcharge. Remember that
bubbles in a sight glass may be caused by a restriction
as well as a shortage of refrigerant.
(c) Check setting of time delay relay for low pressure switch
in condensing unit. It should be set at one minutes
(the second marker).
(k) Do not leave unit unattended until the system has
reached normal operating conditions and the oil charge
has been properly adjusted to maintain the oil level at
the center of the sight glass.
(d) Check high and low pressure controls, pressure
regulating valves, oil pressure safety controls, and all
other safety controls and adjust them, if necessary.
(l) At initial start-up, the system may cycle off at 2 minutes
and display a low superheat error, then restart itself. This
cycle may be repeated a few times. Do not shut the
system off. Let the system run, as it may take a few
cycles for the electric expansion valve to attain the
correct setting for the desired superheat.
(e) On freezers only, check the low pressure switch setting.
It must be set to 0 PSIG cut out, 10 PSIG cut in, to allow
start and operation, especially in cold ambients.
(f) Liquid line should always be insulated.
(g) Wiring diagrams, instruction bulletins, etc. attached to
the condensing units should be read and filed for future
reference.
CAUTION: Extreme care must be taken in starting
compressors for the first time after system charging. At
this time, all of the oil and most of the refrigerant might be
in the compressor creating a condition which could cause
compressor damage due to slugging. Activating the crankcase
heater for 24 hours prior to start-up is recommended. If no
crankcase heater is present, then directing a 500 watt heat
lamp or other safe heat source on the lower shell of the
compressor for approximately thirty minutes will be beneficial
in eliminating this condition which might never reoccur.
(h) All fan motors on air cooled condensers, evaporators,
etc. should be checked for proper rotation. Fan motor
mounts should be carefully checked for tightness and
proper alignment.
34
Download from Www.Somanuals.com. All Manuals Search And Download.
Service Record
Date of Start-up
Location Address
CONDENSING UNIT
MODEL #
SERIAL #
COOLER UNIT
MODEL #
SERIAL #
FREEZER UNIT
MODEL #
SERIAL #
ELECTRICAL
COOLER
• Check Primary Supply voltage.
Refrigerant Type
Box Setpoint Temp.
Superheat
No. of Defrost/Day
Defrost End Temp.
R22
35°F.
8°F.
2
If 208 V, change transformer wiring in the
Cooler and Freezer to the 208 V tap
YES
• Check Compressor Amps for COOLER and
FREEZER compressors. Should match
nameplate.
50°F.
SYSTEM CHECKS
• Check Compressor Superheat for the
YES
NO
PIPING
COOLER (Should be between 20°F. & 30°F.)
• Is suction line trapped at the Cooler?
YES NO
• Is suction line trapped at the Freezer?
YES NO
YES
NO
• Check Compressor Superheat for the
FREEZER (Should be between 20°F. & 30°F.)
YES
NO
• Force unit into a Defrost Check heater amps.
Should match nameplate amps.
DRAIN LINES
• Are drain lines sloped properly?
YES
NO
YES
NO
• Check LPS Time Delay Relays. Should be
set at 1 minute for both the COOLER and
FREEZER.
• Is drain line trapped outside the Cooler?
YES
• Is drain line trapped outside the Freezer?
YES NO
• Is heat tape wrapped along entire length of
the drain line in the Freezer?
NO
YES
NO
• Check Low Pressure Switch on FREEZER. Should
be set at 0 psig Cut-out/10 psig Cut-in.
YES
NO
YES
NO
• Did FREEZER and COOLER cycle off on LPS at
Setpoint Temperature?
• Is heat tape plugged in and heating the drain
line?
YES
NO
YES
NO
• Is the sight glass free of bubbles?
INSULATION
• Are Liquid lines fully insulated?
YES
NO
• Are the COOLER and FREEZER fans at proper
speeds?
YES
NO
• Are Suction lines fully insulated?
YES
NO
YES
NO
• Check system for refrigerant leaks. Are there any
leaks on the COOLER, FREEZER, CONDENSING
UNIT or INTERCONNECTING PIPING?
SETTINGS
• Check Beacon II board settings for the
following:
FREEZER
Refrigerant Type
Box Setpoint Temp.
Superheat
No. of Defrost / Day
Defrost End Temp.
YES
NO
• Check system piping for unusual vibration or
noise. Is there any unusual vibration or noise on
the COOLER, FREEZER, CONDENSING UNIT or
INTERCONNECTING PIPING?
R404A
-10°F.
8°F.
4
65°F.
YES
NO
• Start the FREEZER only. Does the compressor
start and evaporator fans run for this FREEZER?
YES
NO
35
Download from Www.Somanuals.com. All Manuals Search And Download.
Service Record
RECORD
OUTDOOR TEMPERATURE
______°F
______Volts
SYSTEM VOLTAGE
______PH
______L2
______L2
______Hz
______L3
______L3
Cooler Compressor Amps
Freezer Compressor Amps
Cooler Discharge Pressure
Freezer Discharge Pressure
Cooler Suction Pressure
Freezer Suction Pressure
Cooler Suction Temp.
______L1
______L1
______PSIG
______PSIG
______PSIG
______PSIG
______°F
Freezer Suction Temp.
______°F
Cooler Refrigerant Charge
Freezer Refrigerant Charge
Cooler Compressor Superheat
Freezer Compressor Superheat
Cooler Evaporator Superheat
Freezer Evaporator Superheat
Cooler Discharge Temp.
Freezer Discharge Temp.
______lbs.
______lbs.
______°F
______°F
______°F
______°F
______°F
______°F
™
Since product improvement is a continuing effort, we reserve the right to make changes in
specifications without notice.
The name behind the brands you trust.™
CLIMATE
Commercial Refrigeration Parts
CONTROL
Download from Www.Somanuals.com. All Manuals Search And Download.
|