Heatcraft Refrigeration Products Air Compressor H IM 72A User Manual |
Parallel
Compressor
Systems
Installation
Part No. 25000102
H-IM-72B
October 1999
Replaces H-IM-72A
Installation, Operation and
Maintenance Guide
Parallel Compressor Systems
HEATCRAFT INC. REFRIGERATION PRODUCTS DIVISION
WWW.HEATCRAFTRPD.COM • E-MAIL: HRPD.FEEDBACK@HEATCRAFT.COM
Download from Www.Somanuals.com. All Manuals Search And Download.
Model definition:
HEATCRAFT INC.
1st digit - Brand (B, C, H, or L)
Parallel Compressor Units
2nd digit - Compressor Type
H - Hermetic
INTRODUCTION
R - Reciprocating
S - Screw
O - Open
Z - Scroll
C - Compound
Parallel Compressor systems are central refrigeration units
employing 2 to 8 parallel piped compressors, a control
panel, and receiver mounted on one common base frame.
The system may be designed for either Indoor or Outdoor
use. The Outdoor design may include the condenser
mounted and piped.
3rd digit - Unit Construction
R - Remote Condenser
The selection and design of the system is based on the
needs of the individual customer. The most important point
in planning an installation of the Heatcraft parallel system is
the proper selection of the system components for the
particular application.
U - Attached Condenser
H - Hybrid
M - Multi-compressor Platform
F - Frame Hybrid (Frame + Standard Unit)
4th digit - Compressor Quantity
2 - 2 compressor
3 - 3 compressor
4 - 4 compressor
Etc.
Component parts have been selected for their dependability
and availability to keep service problems to a minimum.
Simplicity of design has also made the Heatcraft parallel
system one of the easiest to service and install. The
simplicity and compactness of the Heatcraft design make
the addition of hot gas defrost and/or heat reclaim a simple
and economical feature.
5th, 6th, & 7th digit - Horsepower
030 - 30 HP
075 - 75 HP
100 - 100 HP
Etc.
In the following pages will be found explanations of system
components, wiring and piping diagrams, control settings,
and operational guides.
8th digit - Condenser Type
A - Air
INSPECTION
Unit inspection should be assigned to a dependable
individual. Inspect the parallel system and any accessories
shipped with them for damages or shortages before and
during unloading. All items on bill of lading should be
accounted for prior to signing the shipping receipt. Note any
shortages or damage on carrier’s delivery receipt (Specify
the extent and type of damage found). Unit should be
inspected carefully for concealed damage. Notify the
Heatcraft sales representative and the carrier of the damage
immediately. Request an immediate joint inspection with the
carrier (Do not repair the unit until inspected by carrier’s
representative). Care should be exercised when uncrating
units to prevent damage.
W - Water
E - Evaporative
9th digit - Control Voltage
A - 115/1/60
B - 208-230/1/60
C - 24/1/60
10th digit - Defrost Type
A - Air / Off Cycle
E - Electric
G - Hot Gas
M - Multiple
W - Water
The system is shipped with a holding charge of dry nitrogen.
Check to see that pressure is still in the unit upon receipt.
Report lack of pressure immediately to the Heatcraft service
department.
11th digit - Temperature Range
L - Low
M - Medium
H - High
C - Combination
X - Ultra Low
NOTE: Accessory items such as drier cores,
mounting pads, modems, etc. may be packaged
in a separate carton. Be sure that you receive
all items.
12th digit - Refrigerant Type
2 - R22
4 - R134a
6 - R404a, R507
8 - Multiple
UNIT DESIGNATION
Units are identified by letter, brand, compressor type,
quantity of compressors, horsepower, condenser type,
control voltage, defrost type, refrigerant / range, unit voltage
and application. Unless otherwise requested by the
customer all refrigeration circuits are numbered from one to
the highest and from left to right while facing the electrical
panel.
13th digit - Unit Voltage
C - 208 - 230/3/60
D - 460/3/60
E - 575/3/60
J - 208/3/60
K - 230/3/60
M - 380/3/60
14th digit - Application
1 - Indoor
2 - Outdoor
3
Download from Www.Somanuals.com. All Manuals Search And Download.
SYSTEM WARRANTY
Floor & Foundation Requirements
This equipment is designed to operate properly and produce
the rated capacity when installed in accordance with good
refrigeration practice.
The total weight of a single unit will vary between 1200
pounds and 10,000 pounds. Allowances must be made for
the parallel rack and all other equipment installed in the
same area as the parallel units. The location and installation
of all equipment should be in accordance with all local and
national code requirements.
The following conditions should be adhered to when
installing this unit to maintain the manufacturers warranty.
(a) System piping must be in accordance with good
refrigeration practices.
(b) Inert gas must be charged into the piping during
brazing.
(c) The power supply to the unit must meet the
following conditions:
While each unit is constructed with a welded steel base
frame adequately designed to withstand vibration, the
natural pulsating action of the interconnected motor-
compressors may cause considerable noise and vibration if
the unit is not mounted on a firm level surface and isolated
from the structure of the building.
• All voltages must be +/- 10% of the
nameplate ratings.
• Phase (voltage) imbalance cannot
exceed 2%.
Vibration Mounts
In ordinary ground level or basement installations, all that is
necessary to assure a vibration-free installation is to place
the unit on the concrete floor with the waffle-surfaced
resilient pads supplied. See Figure 2 for suggested pad
locations. Mezzanine and other installations require some
special considerations. The equivalent of 6 inch thick
properly reinforced concrete floor must be provided for
mounting parallel units above grade. It is recommended that
the suggestions previously given for rigid floor construction
on above-grade installations be closely adhered to. If this is
not possible, special vibration absorbing spring mounts
(optional equipment) must be placed under the base frame
of each unit. See Figure 1 for view of Spring Isolator. The
spring mounts are placed under the unit and the unit
carefully lowered on to the mounts. Note that no other
mounting hardware is required and any unevenness in the
floor or uneven weight distribution may be compensated for
by turning the spring mount leveling nuts with an open-end
wrench. This adjustment should be made after all piping is
installed and the system is charged with refrigerant.
(d) All control and safety switch circuits must be
properly connected according to the wiring
diagram.
(e) The factory installed wiring must not be changed
without written factory approval.
RIGGING
Warning: Careful considerations for lifting should be made
before the unit is lifted by any means. The only part of the
unit designed to carry any of the lifting load is the welded
channel base. The unit may be lifted at the base with a
forklift or by means of cables at the four corners of the base.
If cables are used, the lifting cables should be prevented
from contacting any of the unit piping or electrical
components.
LOCATION OF EQUIPMENT - INDOOR
Clearances
The parallel systems should be located so they are level and
easily serviced. The minimum suggested clearance around
the units should be 24 inches at the rear and 42 inches in
the front of panel (or as required by National or Local
Codes). For parallel system units placed end to end, 24
inches between units is suggested.
NOTE: Turn each leveling nut until the tip
casting rises 1/4" to 3/8" above the bottom
casting. MOUNT ADJUSTMENT SHOULD
NEVER EXCEED 3/4".
Figure 1. Vibration Pad and Spring Isolator
Figure 2. Vibration Pad Locations
4
Download from Www.Somanuals.com. All Manuals Search And Download.
LOCATION OF EQUIPMENT - OUTDOOR
• The mounting platform or base should be level and located
so as to permit free access of supply air.
COMPRESSOR SPRING VIBRATION
ISOLATORS
On units with this option, the compressors are secured rigidly
to make sure there is no transit damage. Before operating
the unit, it is necessary to follow these steps:
• Units must not be located in the vicinity of steam, hot air or
fume exhausts.
• The unit should be mounted away from noise sensitive
spaces such as offices.
1. Remove the upper nuts and washers.
2. Discard the shipping spacers.
• The unit must have adequate support to avoid vibration and
noise transmission into the building. Sound and structural
consultants should be retained for recommendations.
3. Install the neoprene spacers. (Spacers located in
the electrical panel or tied to compressor.)
4. Replace the upper mounting nuts and washers.
Ground Mounting
5. Allow 1/16 inch space between the mounting
nut/washer and the neoprene spacer.
The unit must be set on a flat and level foundation. A single
piece concrete slab with footings extending below the frost
line and raised approximately six inches above ground level
provides a suitable base. Raising the base above ground
level provides some protection from ground water and wind
blown matter. The concrete slab should be isolated from the
building structure. Finally, before tightening mounting bolts,
recheck the level of the unit.
Figure 3. Spring Mount
Roof Mounting
Rooftop installations require adequate structural beams to
support the weight of the unit and service personnel. The
design of the beams/supports must minimize deflection and
attendant vibration transmission.
Due to the weights involved, a structural analysis by a
qualified engineer may be required before mounting. Also,
for sound sensitive applications, unit vibration isolators
should be used.
UNIT VIBRATION ISOLATION
Under certain critical conditions, it is recommended that
vibration isolators, of a suitable type, be installed under the
base. The isolators must be designed for the operating
weight of the unit. Rubber-in-shear or spring type isolators
(by others) are available for this purpose.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
UNIT ACCESS
Always provide sufficient clearance for unit maintenance and
service. Minimum clearances for most situations are
described below (except 60 Inches of free space is required
in front of the control panel). Please note that these are
minimums and more clearance may be required by local
codes.
Vertical Clearance
Overhead obstructions are not permitted. Vertical air
discharge from the condenser must have no obstructions that
can cause the discharge air to be recirculated back to the
inlet side of the unit.
Lateral Clearance
(Walls or Obstructions)
The unit should be located so that air may circulate freely and
not be recirculated. For proper air flow and access, all sides
of the unit (except control panel end ) should be a minimum
of four feet (1.2 m) away from any wall or obstruction. It is
preferred that this distance be increased whenever possible.
Care should be taken to see that ample room is left for
maintenance work through access doors and panels. When
the unit is in an area where it is enclosed by three walls the
unit must be installed under the guidelines for unit
installations in pits.
Decorative Fences
Fences may be installed closer than the four foot (1.2 m)
lateral minimum (except on the control panel end)
requirement whenever fences permit sufficient free area to
allow adequate air flow to the unit. Once again, care should
be taken to leave ample room for unit service. Recommended
service clearances are listed above.
Units in Pits
The top of the unit should be level with the top of the pit. If the
top of the unit is not level with the top of the pit, a wider pit or
discharge stacks must be used to raise discharge air to the
top of the pit. This is a minimum requirement.
Multiple Units
(Unit-to-Unit Clearance)
For units placed side by side, the minimum distance between
units is eight feet (2.4 M) to prevent air recirculation.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Ventilation Requirements
Proper size refrigeration lines are essential to good
refrigeration performance. Suction lines are more critical
than liquid or discharge lines. Oversized suction lines may
prevent proper oil return to the compressor. Undersized lines
can rob refrigeration capacity and increase operating cost.
Consult the line sizing charts in this manual for proper pipe
sizes.
INDOOR UNITS
If compressors or condensing units are located in a machine
room, adequate ventilation air must be provided to avoid an
excessive temperature rise in the room. To allow for peak
summer temperatures a 10°F temperature rise is
recommended, although a 15°F rise might be acceptable.
The following procedures should be followed:
With compressors with remote condensers, approximately
10% of the heat rejected is given off by the compressor
casting and the discharge tubing. The correct formula for
calculating the ventilation requirement of the Indoor Parallel
unit is:
1. Do not leave dehydrated compressors or
filter-driers open to the atmosphere.
2. Use only refrigeration grade copper tubing,
properly sealed against contamination.
CFM = 10% of THR/hr
3. Suction lines should slope 1/4" per 10 feet
towards the compressor.
10° TD
The air intake should be positioned so that air passes over
the units. All State, Local, and National codes should be
followed.
4. Discharge lines should slope 1/4" per 20 feet
toward the condenser.
SUCTION P-TRAPS
ELECTRICAL
* Provide P-traps at the base of each suction
riser of four (4) feet or more to enhance oil
return to the compressor. Use a P-trap for
each 20 feet section of riser. See Figure 4
below.
To insure the proper operation of equipment and reduce the
possibility of interruption of refrigeration due to electrical
power failure, the following precautions must be observed:
• All electrical work must be done in accordance
with the National Electrical Code and existing
local codes.
Figure 4. P-trap Requirements
• The power supply must be the same as
specified on the unit data plate.
• An adequate power supply must be provided.
• Voltage fluctuations in excess of 10 percent
must be corrected.
• Overload relays (Carrier compressors only)
are selected in accordance with specified
limits as determined by the motor-compressor
manufacturer. They must not be changed in
size or shorted-out.
• Control panels must be provided with a single
phase, 60 Hertz supply. See the unit wiring
diagram for the voltage requirement.
• Before starting up a parallel unit, insure that all
fuses and motor-protective devices are in
place and that all wiring is secure. A
complete wiring diagram for troubleshooting
the unit will be found inside the control panel
cover.
* The P-trap should be the same size as the
horizontal line. See Figure 5 below.
REFRIGERANT PIPING
Figure 5. P-Trap Construction
The system as supplied by Heatcraft, was thoroughly cleaned
and dehydrated at the factory. Foreign matter may enter the
system by way of the field piping required. Therefore, care
must be used during installation of the piping to prevent
introduction of foreign matter.
Install all refrigeration system components in accordance with
all applicable local and national codes and in conformance
with good practice required for the proper operation of the
system.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
• In systems equipped with capacity control
compressors, or where multiple compressors
are used with one or more compressors
cycled off for capacity control, double suction
risers should be installed. See Figure 6
below. The two lines should be sized so that
the total cross-section area is equivalent to
the cross section area of a single riser that
would have both satisfactory gas velocity and
acceptable pressure drop at maximum load
conditions. The two lines normally are
different in size, with the larger line trapped
as shown. The smaller line must be sized to
provide adequate velocities and acceptable
pressure drop when the entire minimum load
is carried in the smaller riser.
• When brazing refrigerant lines, an inert gas
should be passed through the line at low
pressure to prevent scaling and oxidation
inside the tubing. Dry nitrogen is preferred.
• Use long radius ell’s for lower pressure drop.
• Provide expansion loops in long straight
refrigerant lines that are subject to expansion
and contraction. See Expansion Loops in
this manual for more information.
Refrigerant Line Insulation
• Insulate suction lines from the evaporators to
the parallel unit with minimum 3/4" thickness
closed-cell type insulation on low temperature
circuits. Insulate suction lines on medium
temperature circuits with minimum 1/2" thick
insulation to prevent condensation.
Figure 6. Double Suction Risers
• Long liquid lines run in areas exposed to high
temperatures should be fully insulated with
minimum 1/2" insulation.
• Suction and liquid lines should never be taped
or soldered together.
Refrigerant Line Support
• Strap and support tubing to prevent excessive
line vibration and noise. All tubing clamps
should have an insulating material (i.e. Hydra
Sorb bushing) to prevent metal to metal
contact.
• In operation, at maximum load conditions gas
and entrained oil will be flowing through both
risers. At minimum load conditions, the gas
velocity will not be high enough to carry oil up
both risers. The entrained oil will drop out of
the refrigerant gas flow and accumulate in the
"P" trap forming a liquid seal. This will force
all of the flow up the smaller riser, thereby
raising the velocity and assuring oil circulation
through the system.
Figure 8. Pipe Support
• Straight runs should be supported near each
end.
• When connecting more than one suction line
to a main trunk line, connect each branch line
with an inverted trap. See Figure 7 below.
• Long runs require additional supports. A
general guide is
* 3/8" to 7/8" every 5 feet.
Figure 7. Inverted Trap
* 1 1/8" to 1 3/8" every 7 feet.
* 1 5/8" to 2 1/8" every 10 feet.
• When changing directions, supports should be
placed a maximum of 2 feet in each direction.
• Piping attached to a vibrating object (such as a
compressor or compressor base) must be
supported in such a manner that will not
restrict the movement of the vibrating object.
Rigid mounting will fatigue the copper tubing.
• Use only a suitable silver solder alloy on
suction and liquid lines.
• Limit the soldering paste or flux to the
minimum required to prevent contamination of
the solder joint internally. Flux only the male
portion of the connection, never the female.
After brazing, remove excess flux.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
Expansion Loops
Suction, liquid and remote condenser lines are subject to
In order to compensate for the expansion of the tubing, it is
necessary to estimate the amount of expansion and then
expansion and contraction and proper piping techniques must provide offsets or loops in the refrigerant piping. Normally the
be employed (especially on hot gas lines) to prevent line
breakage. This is critical on long straight runs of generally
70’ or more where expansion loops must be provided and
hangers should allow for longitudinal movement of the piping.
area to be most concerned with is the straight line distance
from the fixture to the parallel compressor unit.
A simple form of expansion loop can be made of soft
tempered copper tube by bending it to the correct size and
shape. A neater type is made by assembling hard tube with
solder elbows as in Figure 9. The correct proportions of such
expansion loops to meet various conditions are shown in
Table 1.
On a refrigeration system with gas defrost, the refrigerant
lines expand and contract with temperature changes. The
suction line normally has the greatest movement since it has
the largest temperature change during defrost. If the
expansion and contraction is not planned for during the
installation of refrigeration lines, kinking and breaking of the
lines could occur.
In compensating for expansion and contraction, two items are
very important.
Figure 9. Offsets
• Liquid and suction lines can not be joined
together and should not touch at any point.
• Pipe hangers must be located and installed in
such a manner as not to restrict the
expansion and contraction of the tubing. All
tubing clamps should have an insulating
material (i.e. Hydra Sorb bushing) to prevent
metal to metal contact.
Table 1. Expansion Chart
Table of Values for "L"
Ref. Line
O.D. "
7/8
Amount of Expansion (Inches)
1/2
10
11
11
12
14
16
1
11/2
19
20
21
23
25
27
2
21/2
25
27
29
31
34
37
3
4
5
6
15
16
17
18
20
22
22
24
26
28
31
32
27
29
32
35
38
42
30
33
36
39
44
47
34
38
42
46
51
56
38
42
47
51
57
62
11/8
13/8
15/8
21/8
25/8
NOTE: Calculations for expansion and contraction should be based on the average coefficient of expansion of copper
which is .0000094 per degree Fahrenheit between 77°F and 212°F. Example, the expansion for each 100 feet of
length of any size of tube heated from room temperature of 70°F to 170°F, a rise of 100°F, is:
100°F (rise °F) X 100 (linear feet) X 12 (inches) X.0000094 (coefficient) = 1.128 inches
(Reprinted from Copper & Brass Research Association)
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 2.Pressure Loss of Liquid Refrigerants
(In Liquid Line Risers - Expressed in Pressure Drop, PSIG, and Subcooling Loss, °F)
Liquid Line Rise in Feet
10’
15’
20’
25’
30’
40’
50’
75’
100’
Refrigerant PSIG °F PSIG °F PSIG °F PSIG °F PSIG °F PSIG °F PSIG °F PSIG °F PSIG °F
R12
R22
5.4 2.8 8.1 4.2 10.7 5.4 13.4 6.9 16.1 8.3 21.5 11.3 26.9 14.3 40.3 22.4 53.7 31.0
4.8 1.6 7.3 2.3 9.7 3.1 12.1 3.8 14.5 4.7 19.4 6.2 24.2 8.0 36.3 12.1 48.4 16.5
4.9 1.5 7.3 2.2 9.7 3.0 12.1 3.7 14.6 4.5 19.5 6.0 24.3 7.6 36.4 11.5 48.6 14.8
4.9 2.0 7.4 2.9 9.8 4.1 12.3 5.2 14.7 6.3 19.7 8.8 24.6 11.0 36.8 17.0 49.1 23.7
R502
R134A
R507, R404A 4.1 1.1 6.1 1.6 8.2 2.1 10.2 2.7 12.2 3.3 16.3 4.1 20.4 5.6 30.6 8.3 40.8 11.8
Based on 110°F liquid temperature at bottom of riser.
Table 3. Equivalent Feet of Pipe
(Due to Valve and Fitting Friction)
Copper Tube,
O.D., Type "L"
Globe Valve (Open)
Angle Valve (Open)
90° Turn Through Tee
Tee - Straight Through
or Sweep Below
1/2
14
7
5/8
16
9
7/8
22
12
5
11/8
28
15
6
13/8
36
18
8
15/8
42
21
9
21/8
57
28
12
25/8
69
34
14
31/8
83
42
17
35/8
99
49
20
41/8
118
57
51/8
138
70
61/8
168
83
3
4
22
28
34
.75
1
1
2
1.5
2
2
3
2.5
4
3
4
3.5
5
4
7
5
8
6
7
9
11
16
90° Elbow or Reducing
Tee (Straight Through)
10
12
14
10
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 4. Weight of Refrigerants in Copper Lines During Operation
(Pounds per 100 Lineal feet of type "L" tubing.)
Line Size
Suction Line at Suction Temperature
O.D.
Liquid
Line
4.0
Hot Gas
Line
.15
in Inches
Refrigerant
12, 134a
22
-40°F
.01
-20°F
.01
0°F
.02
+20°F
.04
+40°F
.06
3/8
1/2
3.9
.22
.02
.03
.04
.06
.08
R507, 502, 404A
12, 134a
22
3.4
.31
.03
.04
.06
.09
.13
7.4
.30
.01
.03
.04
.07
.11
7.4
.41
.03
.05
.07
.11
.15
R507, 502, 404A
12, 134a
22
6.4
.58
.04
.07
.13
.16
.24
11.9
11.8
10.3
24.7
24.4
21.2
42.2
41.6
36.1
64.2
63.5
55.0
90.9
90.0
78.0
158
156
134
244
241
209
348
344
298
471
465
403
612
605
526
.47
.02
.05
.07
.12
.17
5/8
.65
.05
.08
.12
.17
.25
R507, 502, 404A
12, 134a
22
.93
.07
.11
.17
.25
.35
.99
.05
.10
.15
.24
.36
7/8
1.35
1.92
1.70
2.30
3.27
2.57
3.50
4.98
3.65
4.96
7.07
6.34
8.61
12.25
9.78
13.70
18.92
13.97
18.95
27.05
18.90
25.60
36.50
24.56
33.40
47.57
.10
.16
.24
.36
.51
R507, 502, 404A
12, 134a
22
.15
.23
.37
.51
.72
.08
.17
.26
.41
.60
1 1/8
1 3/8
1 5/8
2 1/8
2 5/8
3 1/8
3 5/8
4 1/8
.17
.28
.42
.61
.87
R507, 502, 404A
12, 134a
22
.26
.39
.63
.86
1.24
1.91
1.33
1.87
1.30
1.88
2.64
2.24
3.26
4.58
3.47
5.03
7.07
4.96
7.18
9.95
6.69
9.74
13.67
8.75
12.70
17.80
.14
.26
.40
.61
.27
.42
.64
.93
R507, 502, 404A
12, 134a
22
.40
.58
.95
1.32
.87
.20
.37
.57
.37
.59
.90
1.33
1.86
1.51
2.30
3.23
2.32
3.54
5.00
3.31
5.05
7.14
4.48
6.83
19.65
5.84
8.90
12.58
R507, 502, 404A
12, 134a
22
.56
.82
1.35
.98
.34
.64
.65
1.03
1.43
.99
1.57
2.35
1.51
2.42
3.62
2.16
3.45
5.17
2.92
4.67
6.97
3.81
6.08
9.09
R507, 502, 404A
12, 134a
22
.98
.52
1.01
1.51
.75
1.59
2.21
1.41
2.28
3.15
1.91
3.08
4.25
2.49
4.01
5.55
R507, 502, 404A
12, 134a
22
1.44
2.16
.99
R507, 502, 404A
12, 134a
22
1.94
2.92
1.29
2.53
3.80
R507, 502, 404A
12, 134a
22
R507, 502, 404A
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 5A. Recommended Line Sizes for R-404A and R507 *
SUCTION LINE SIZE
SUCTION TEMPERATURE
SYSTEM
CAPACITY
BTU/H
+20˚F
+10˚F
-10˚F
-20˚F
Equivalent Lengths
Equivalent Lengths
Equivalent Lengths
Equivalent
25'
3/8
3/8
3/8
1/2
5/8
5/8
5/8
7/8
7/8
7/8
50'
75' 100' 150' 200' 25'
50' 75'
3/8 3/8
1/2 1/2
1/2 1/2
1/2 5/8
5/8 7/8
7/8 7/8
7/8 7/8
7/8 7/8
100' 150' 200' 25'
50'
75' 100' 150' 200' 25' 50' 75'
1,000
3,000
3/8
3/8
1/2
1/2
5/8
7/8
7/8
7/8
7/8
3/8
1/2
1/2
5/8
7/8
7/8
7/8
7/8
3/8
1/2
1/2
5/8
7/8
7/8
7/8
3/8
1/2
5/8
7/8
7/8
7/8
7/8
3/8
5/8
5/8
7/8
7/8
7/8
3/8
3/8
1/2
1/2
5/8
5/8
3/8
1/2
5/8
5/8
7/8
7/8
7/8
3/8
5/8
5/8
7/8
7/8
7/8
1/2
5/8
7/8
7/8
7/8
3/8
1/2
1/2
1/2
5/8
3/8
1/2
5/8
5/8
7/8
7/8
7/8
3/8
5/8
5/8
5/8
7/8
7/8
1/2
5/8
5/8
7/8
7/8
7/8
1/2
5/8
7/8
7/8
1/2
7/8
7/8
7/8
3/8
1/2
1/2
5/8
3/8 1/2
1/2 5/8
5/8 5/8
5/8 7/8
7/8 7/8
7/8 7/8
7/8 1 1/8
4,000
6,000
9,000
7/8 1 1/8 5/8
12,000
15,000
18,000
24,000
30,000
36,000
42,000
48,000
54,000
60,000
66,000
72,000
78,000
84,000
90,000
120,000
150,000
180,000
210,000
240,000
300,000
360,000
480,000
600,000
720,000
900,000
1 1/8 7/8
1 1/8 1 1/8 7/8
1 1/8 7/8
1 1/8 1 1/8 7/8
7/8 1 1/8 1 1/8 1 1/8 7/8
7/8 1 1/8 1 1/8 7/8
1 1/8 1 1/8 1 1/8 7/8
7/8 1 1/8 1 1/8 1 1/8 1 3/8 7/8 1 1/8 1 1/8
7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 1 1/8 1 3/8 7/8 1 1/8 1 1/8 1 1/8 1 3/8 1 3/8 1 1/8 1 1/8 1 1/8
7/8 1 1/8 1 1/8 1 1/8 1 3/8 7/8 1 1/8 1 1/8 1 1/8 1 3/8 1 3/8 1 1/8 1 1/8 1 1/8 1 3/8 1 3/8 1 3/8 1 1/8 1 1/8 1 1/8
7/8 1 1/8 1 1/8 1 1/8 1 3/8 1 3/8 1 1/8 1 1/8 1 1/8 1 3/8 1 3/8 1 3/8 1 1/8 1 1/8 1 3/8 1 3/8 1 3/8 1 5/8 1 1/8 1 1/8 1 3/8
1 1 /8 1 1/8 1 1/8 1 3/8 1 3/8 1 3/8 1 1/8 1 1/8 1 3/8 1 3/8 1 3/8 1 5/8 1 1/8 1 3/8 1 3/8 1 3/8 1 5/8 1 5/8 1 1/8 1 3/8 1 3/8
1 1/8 1 1/8 1 3/8 1 3/8 1 3/8 1 3/8 1 1/8 1 1/8 1 3/8 1 3/8 1 5/8 1 5/8 1 1/8 1 3/8 1 3/8 1 3/8 1 5/8 1 5/8 1 1/8 1 3/8 1 3/8
1 1/8 1 1/8 1 3/8 1 3/8 1 3/8 1 5/8 1 1/8 1 3/8 1 3/8 1 3/8 1 5/8 1 5/8 1 3/8 1 3/8 1 3/8 1 5/8 1 5/8 1 5/8 1 3/8 1 3/8 1 5/8
1 1/8 1 1/8 1 3/8 1 3/8 1 5/8 1 5/8 1 1/8 1 3/8 1 3/8 1 5/8 1 5/8 1 5/8 1 3/8 1 3/8 1 5/8 1 5/8 1 5/8 2 1/8 1 3/8 1 3/8 1 5/8
1 1/8 1 3/8 1 3/8 1 3/8 1 5/8 1 5/8 1 1/8 1 3/8 1 3/8 1 5/8 1 5/8 1 5/8 1 3/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 3/8 1 5/8 1 5/8
1 1/8 1 3/8 1 3/8 1 5/8 1 5/8 1 5/8 1 1/8 1 3/8 1 5/8 1 5/8 1 5/8 1 5/8 1 3/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 3/8 1 5/8 1 5/8
1 1/8 1 3/8 1 3/8 1 5/8 1 5/8 2 1/8 1 3/8 1 3/8 1 5/8 1 5/8 1 5/8 2 1/8 1 3/8 1 5/8 1 5/8 1 5/8 1 5/8 2 1/8 1 5/8 1 5/8 1 5/8
1 1/8 1 3/8 1 5/8 1 5/8 1 5/8 2 1/8 1 3/8 1 3/8 1 5/8 1 5/8 2 1/8 2 1/8 1 3/8 1 5/8 1 5/8 1 5/8 2 1/8 2 1/8 1 5/8 1 5/8 1 5/8
1 3/8 1 3/8 1 5/8 1 5/8 2 1/8 2 1/8 1 3/8 1 5/8 1 5/8 1 5/8 2 1/8 2 1/8 1 5/8 1 5/8 1 5/8 2 1/8 2 1/8 2 5/8 1 5/8 1 5/8 2 1/8
1 3/8 1 5/8 1 5/8 2 1/8 2 1/8 2 1/8 1 3/8 1 5/8 2 1/8 2 1/8 2 1/8 2 1/8 1 5/8 2 1/8 2 1/8 2 1/8 2 5/8 2 5/8 1 5/8 2 1/8 2 1/8
1 5/8 1 5/8 2 1/8 2 1/8 2 1/8 2 1/8 1 5/8 2 1/8 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 1/8 2 1/8
1 5/8 2 1/8 2 1/8 2 1/8 2 1/8 2 5/8 1 5/8 2 1/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 2 5/8 3 1/8 2 1/8 2 1/8 2 5/8
1 5/8 2 1/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 3 1/8 3 1/8 2 1/8 2 5/8 2 5/8
1 5/8 2 1/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 3 1/8 3 1/8 2 1/8 2 5/8 2 5/8
2 1/8 2 1/8 2 5/8 2 5/8 2 5/8 3 1/8 2 1/8 2 5/8 2 5/8 2 5/8 3 1/8 3 1/8 2 5/8 2 5/8 2 5/8 3 1/8 3 1/8 3 5/8 2 5/8 2 5/8 2 5/8
2 1/8 2 1/8 2 5/8 2 5/8 3 1/8 3 1/8 2 1/8 2 5/8 2 5/8 2 5/8 3 1/8 3 1/8 2 5/8 2 5/8 3 1/8 3 1/8 3 5/8 3 5/8 2 5/8 2 5/8 3 1/8
2 1/8 2 5/8 2 5/8 3 1/8 3 1/8 3 5/8 2 5/8 2 5/8 2 5/8 2 5/8 3 5/8 3 5/8 2 5/8 3 1/8 3 1/8 3 5/8 3 5/8 4 1/8 2 5/8 3 1/8 3 1/8
2 5/8 2 5/8 3 1/8 3 1/8 3 5/8 3 5/8 2 5/8 2 5/8 3 1/8 3 1/8 3 5/8 3 5/8 3 1/8 3 1/8 3 1/8 3 5/8 4 1/8 4 1/8 3 1/8 3 1/8 3 1/8
2 5/8 3 1/8 3 1/8 3 5/8 3 5/8 4 1/8 3 1/8 3 1/8 3 5/8 3 5/8 4 1/8 4 1/8 3 5/8 3 5/8 4 1/8 5 1/8 5 1/8 5 1/8 3 5/8 4 1/8 5 1/8
3 1/8 3 1/8 3 5/8 3 5/8 4 1/8 4 1/8 3 1/8 3 5/8 3 5/8 4 1/8 5 1/8 5 1/8 3 5/8 4 1/8 5 1/8 5 1/8 5 1/8 5 1/8 4 1/8 5 1/8 5 1/8
* NOTES:
1. Sizes that are highlighted indicate maximum suction line sizes that should be used for risers. Riser size should not
exceed horizontal size. Properly placed suction traps must also be used for adequate oil return.
All sizes shown are for O.D. Type L copper tubing.
2. Suction line sizes selected at pressure drop equivalent to 2˚F. Reduce estimate of system capacity accordingly.
3. Recommended liquid line size may increase with reverse cycle hot gas systems.
4. If system load drops below 40% of design, consideration to installing double suction risers should be made.
12
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 5B. Recommended Line Sizes for R-404A and R507 (continued) *
SUCTION LINE SIZE
LIQUID LINE SIZE
Receiver to
SUCTION TEMPERATURE
-20˚F
-30˚F
-40˚F
Expansion Valve
Equivalent Lengths
SYSTEM
CAPACITY
BTU/H
Lengths
Equivalent Lengths
Equivalent Lengths
100' 150' 200' 25'
50'
3/8
1/2
5/8
5/8
7/8
7/8
75'
1/2
5/8
5/8
7/8
7/8
7/8
100' 150'
200' 25'
50'
1/2
1/2
5/8
5/8
7/8
7/8
7/8
75'
1/2
5/8
5/8
7/8
7/8
7/8
100' 150' 200' 25' 50' 75' 100' 150' 200'
1/2
5/8
7/8
7/8
7/8
1/2
7/8
7/8
7/8
1/2
7/8
7/8
7/8
3/8
1/2
5/8
5/8
1/2
5/8
7/8
7/8
7/8
1/2
7/8
5/8
7/8
7/8
7/8
3/8
1/2
1/2
5/8
1/2
5/8
7/8
7/8
7/8
5/8
7/8
7/8
5/8
7/8
7/8
3/8 3/8 3/8 3/8 3/8
3/8 3/8 3/8 3/8 3/8
3/8 3/8 3/8 3/8 3/8
3/8
3/8
3/8
3/8
3/8
1/2
1/2
1/2
1/2
1/2
5/8
5/8
5/8
5/8
5/8
5/8
5/8
7/8
7/8
7/8
7/8
1,000
3,000
7/8
4,000
7/8
7/8 1 1/8 3/8 3/8 3/8 3/8 3/8
1 1/8 1 1/8 3/8 3/8 3/8 3/8 3/8
6,000
1 1/8 1 1/8 5/8
1 1/8
1 1/8 5/8
1 1/8 7/8
1 3/8 7/8
1 3/8 7/8
9,000
1 1/8 1 1/8 1 1/8 7/8
1 1/8 1 1/8 1 3/8 7/8
1 1/8 1 1/8
1 1/8 1 1/8
1 1/8 1 3/8
1 3/8 1 3/8
1 3/8 1 3/8
1 3/8 1 3/8
1 3/8 1 5/8
1 3/8 1 5/8
1 5/8 1 5/8
1 5/8 1 5/8
1 5/8 1 5/8
1 5/8 1 5/8
1 5/8 2 1/8
2 1/8 2 1/8
2 1/8 2 1/8
2 1/8 2 5/8
2 5/8 2 5/8
2 5/8 2 5/8
2 5/8 3 1/8
3 1/8 3 1/8
3 1/8 3 5/8
3 5/8 3 5/8
4 1/8 4 1/8
4 1/8 4 1/8
5 1/8 5 1/8
5 1/8 6 1/8
1 1/8 1 1/8 1 1/8 3/8 3/8 3/8 3/8 3/8
12,000
15,000
18,000
24,000
30,000
36,000
42,000
48,000
54,000
60,000
66,000
72,000
78,000
84,000
90,000
120,000
7/8 1 1/8
1 1/8 1 1/8 1 1/8 1 3/8 3/8 3/8 3/8 3/8 1/2
1 1/8 1 3/8 1 3/8 7/8 1 1/8 1 1/8
1 1/8 1 1/8 1 1/8 1 3/8 1 3/8 3/8 3/8 3/8 1/2 1/2
1 3/8 1 3/8 1 3/8 1 1/8 1 1/8 1 1/8
1 3/8 1 1/8 1 1/8 1 1/8 1 3/8 1 3/8 1 3/8 3/8 3/8 1/2 1/2 1/2
1 5/8 1 1/8 1 1/8 1 3/8 1 3/8 1 3/8 1 5/8 3/8 1/2 1/2 1/2 1/2
1 5/8 1 1/8 1 3/8 1 3/8 1 3/8 1 5/8 1 5/8 1/2 1/2 1/2 1/2 1/2
1 5/8 1 1/8 1 3/8 1 3/8 1 3/8 1 5/8 1 5/8 1/2 1/2 1/2 1/2 5/8
1 5/8 1 1/8 1 3/8 1 3/8 1 3/8 1 5/8 1 5/8 1/2 1/2 1/2 5/8 5/8
2 1/8 1 3/8 1 3/8 1 3/8 1 5/8 1 5/8 2 1/8 1/2 1/2 1/2 5/8 5/8
2 1/8 1 3/8 1 3/8 1 5/8 1 5/8 1 5/8 2 1/8 1/2 1/2 5/8 5/8 5/8
2 1/8 1 3/8 1 5/8 1 5/8 1 5/8 1 5/8 2 1/8 1/2 1/2 5/8 5/8 5/8
2 1/8 1 3/8 1 5/8 1 5/8 1 5/8 1 5/8 2 1/8 1/2 5/8 5/8 5/8 5/8
2 1/8 1 5/8 1 5/8 1 5/8 1 5/8 2 1/8 2 1/8 5/8 5/8 5/8 5/8 5/8
2 1/8 1 5/8 1 5/8 1 5/8 2 1/8 2 1/8 2 1/8 5/8 5/8 5/8 5/8 7/8
2 5/8 1 5/8 1 5/8 2 1/8 2 1/8 2 1/8 2 5/8 5/8 5/8 5/8 7/8 7/8
2 5/8 1 5/8 2 1/8 2 1/8 2 1/8 2 5/8 2 5/8 5/8 5/8 7/8 7/8 7/8
1 3/8
1 3/8 1 5/8 1 1/8 1 1/8 1 3/8
1 3/8 1 3/8 1 5/8 1 1/8 1 3/8 1 3/8
1 5/8 1 5/8 1 5/8 1 1/8 1 3/8 1 3/8
1 5/8
1 5/8 1 5/8 1 1/8 1 3/8 1 3/8
1 5/8 1 5/8 1 5/8 1 3/8 1 3/8 1 3/8
1 5/8 1 5/8 2 1/8 1 3/8 1 3/8 1 5/8
1 5/8 1 5/8 2 1/8 1 3/8 1 5/8 1 5/8
1 5/8 1 5/8 2 1/8 1 3/8 1 5/8 1 5/8
1 5/8 2 1/8 2 1/8 1 5/8 1 5/8 1 5/8
2 1/8 2 1/8 2 1/8 1 5/8 1 5/8 1 5/8
2 1/8 2 1/8 2 5/8 1 5/8 2 1/8 2 1/8
2 1/8 2 5/8 2 5/8 1 5/8 2 1/8 2 1/8
2 5/8 2 5/8 2 5/8 2 1/8 2 1/8 2 1/8
2 5/8 2 5/8 3 1/8 2 1/8 2 1/8 2 5/8
2 5/8 3 1/8 3 1/8 2 1/8 2 5/8 2 5/8
2 5/8 3 1/8 3 1/8 2 5/8 2 5/8 2 5/8
3 1/8 3 5/8 3 5/8 2 5/8 2 5/8 3 1/8
3 5/8 3 5/8 4 1/8 2 5/8 3 1/8 3 1/8
3 5/8 3 5/8 4 1/8 3 1/8 3 5/8 3 5/8
3 5/8 3 5/8 4 1/8 3 1/8 3 5/8 3 5/8
5 1/8 5 1/8 5 1/8 4 1/8 5 1/8 5 1/8
5 1/8 5 1/8 5 1/8 4 1/8 5 1/8 5 1/8
2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 2 5/8 2 5/8 5/8 7/8 7/8 7/8 7/8 1 1/8 150,000
3 1/8 2 1/8 2 1/8 2 5/8 2 5/8 2 5/8 3 1/8 7/8 7/8 7/8 7/8 1 1/8 1 1/8 180,000
3 1/8 2 1/8 2 5/8 2 5/8 2 5/8 3 1/8 3 1/8 7/8 7/8 7/8 1 1/8 1 1/8 1 1/8 210,000
3 5/8 2 5/8 2 5/8 2 5/8 3 1/8 3 1/8 3 5/8 7/8 7/8 1 1/8 1 1/8 1 1/8 1 3/8 240,000
4 1/8 2 5/8 2 5/8 3 1/8 3 5/8 3 5/8 4 1/8 7/8 1 1/8 1 1/8 1 1/8 1 3/8 1 3/8 300,000
4 1/8 2 5/8 3 1/8 3 5/8 3 5/8 4 1/8 4 1/8 1 1/8 1 1/8 1 1/8 1 3/8 1 3/8 1 5/8 360,000
4 1/8 3 1/8 3 5/8 3 5/8 4 1/8 4 1/8 4 1/8 1 1/8 1 1/8 1 3/8 1 3/8 1 5/8 1 5/8 480,000
5 1/8 3 1/8 3 5/8 3 5/8 4 1/8 4 1/8 5 1/8 1 1/8 1 3/8 1 3/8 1 5/8 1 5/8 1 5/8 600,000
6 1/8 4 1/8 5 1/8 5 1/8 5 1/8 5 1/8 6 1/8 1 1/8 1 3/8 1 3/8 1 5/8 1 5/8 2 1/8 720,000
6 1/8 5 1/8 5 1/8 5 1/8 5 1/8 6 1/8 6 1/8 1 3/8 1 3/8 1 5/8 2 1/8 2 1/8 2 1/8 900,000
* NOTES:
1. Sizes that are highlighted indicate maximum suction line sizes that should be used for risers. Riser size should not exceed
horizontal size. Properly placed suction traps must also be used for adequate oil return.
All sizes shown are for O.D. Type L copper tubing.
2. Suction line sizes selected at pressure drop equivalent to 2˚F. Reduce estimate of system capacity accordingly.
3. Recommended liquid line size may increase with reverse cycle hot gas systems.
4. If system load drops below 40% of design, consideration to installing double suction risers should be made.
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 6A. Recommended Line Sizes for R-22 *
SUCTION LINE SIZE
SUCTION TEMPERATURE
+20˚F
SYSTEM
CAPACITY
BTU/H
+40˚F
+10˚F
0˚F
Equivalent Lengths
Equivalent Lengths
100' 150' 200' 25'
Equivalent Lengths
Equivalent
25'
3/8
3/8
3/8
1/2
1/2
5/8
5/8
5/8
5/8
7/8
50'
75' 100' 150' 200' 25'
50' 75'
3/8 3/8
1/2 1/2
1/2 1/2
1/2 5/8
5/8 5/8
5/8 7/8
7/8 7/8
7/8 7/8
7/8 7/8
7/8 7/8
50'
75' 100' 150' 200' 25' 50' 75'
1,000
3,000
3/8
3/8
3/8
1/2
5/8
5/8
5/8
7/8
7/8
7/8
3/8
3/8
1/2
1/2
5/8
5/8
7/8
7/8
7/8
3/8
1/2
1/2
5/8
5/8
7/8
7/8
7/8
3/8
1/2
1/2
5/8
7/8
7/8
7/8
7/8
3/8
1/2
1/2
5/8
7/8
7/8
7/8
3/8
3/8
3/8
1/2
1/2
5/8
5/8
3/8
1/2
1/2
5/8
5/8
7/8
7/8
7/8
7/8
3/8
5/8
5/8
5/8
7/8
7/8
7/8
7/8
3/8
5/8
5/8
5/8
7/8
7/8
7/8
3/8
3/8
1/2
1/2
5/8
5/8
7/8
3/8
1/2
1/2
5/8
5/8
7/8
7/8
7/8
3/8
1/2
1/2
5/8
7/8
7/8
7/8
7/8
3/8
1/2
5/8
5/8
7/8
7/8
7/8
7/8
3/8
5/8
5/8
7/8
7/8
7/8
1/2
5/8
5/8
7/8
7/8
7/8
3/8
1/2
1/2
5/8
5/8
5/8
3/8 3/8
1/2 1/2
1/2 5/8
5/8 5/8
7/8 7/8
7/8 7/8
7/8 7/8
7/8 1 1/8
4,000
6,000
9,000
12,000
15,000
18,000
24,000
30,000
36,000
42,000
48,000
54,000
60,000
66,000
72,000
78,000
84,000
90,000
120,000
150,000
180,000
210,000
240,000
300,000
360,000
480,000
600,000
720,000
900,000
1 1/8 1 1/8 7/8
1 1/8 5/8
1 1/8 7/8
1 1/8 1 1/8 7/8
7/8 1 1/8 1 1/8 7/8
1 1/8 1 1/8 7/8
7/8 1 1/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8
7/8 1 1/8 1 1/8 1 1/8 7/8
1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 1 1/8 1 3/8 7/8 1 1/8 1 1/8
7/8 1 1/8 1 1/8 1 1/8 1 1/8 1 3/8 7/8 1 1/8 1 1/8 1 1/8 1 1/8 1 3/8 7/8 1 1/8 1 1/8 1 1/8 1 3/8 1 3/8 1 1/8 1 1/8 1 1/8
7/8 1 1/8 1 1/8 1 1/8 1 1/8 1 3/8 7/8 1 1/8 1 1/8 1 1/8 1 3/8 1 3/8 1 1/8 1 1/8 1 1/8 1 3/8 1 3/8 1 3/8 1 1/8 1 1/8 1 3/8
7/8 1 1/8 1 1/8 1 1/8 1 1/8 1 3/8 7/8 1 1/8 1 1/8 1 1/8 1 3/8 1 3/8 1 1/8 1 1/8 1 3/8 1 3/8 1 3/8 1 5/8 1 1/8 1 3/8 1 3/8
7/8 1 1/8 1 1/8 1 1/8 1 3/8 1 3/8 1 1/8 1 1/8 1 1/8 1 3/8 1 3/8 1 3/8 1 1/8 1 3/8 1 3/8 1 3/8 1 5/8 1 5/8 1 1/8 1 3/8 1 3/8
7/8 1 1/8 1 1/8 1 1/8 1 3/8 1 3/8 1 1/8 1 1/8 1 1/8 1 3/8 1 3/8 1 5/8 1 1/8 1 3/8 1 3/8 1 3/8 1 5/8 1 5/8 1 1/8 1 3/8 1 3/8
7/8 1 1/8 1 1/8 1 3/8 1 3/8 1 3/8 1 1/8 1 1/8 1 3/8 1 3/8 1 3/8 1 5/8 1 1/8 1 3/8 1 3/8 1 3/8 1 5/8 1 5/8 1 1/8 1 3/8 1 5/8
1 1/8 1 1/8 1 1/8 1 3/8 1 3/8 1 3/8 1 1/8 1 3/8 1 3/8 1 3/8 1 5/8 1 5/8 1 1/8 1 3/8 1 3/8 1 5/8 1 5/8 1 5/8 1 3/8 1 3/8 1 5/8
1 1/8 1 1/8 1 3/8 1 3/8 1 3/8 1 5/8 1 1/8 1 3/8 1 3/8 1 3/8 1 5/8 1 5/8 1 1/8 1 3/8 1 5/8 1 5/8 1 5/8 2 1/8 1 3/8 1 3/8 1 5/8
1 1/8 1 1/8 1 3/8 1 3/8 1 3/8 1 5/8 1 1/8 1 3/8 1 3/8 1 3/8 1 5/8 1 5/8 1 3/8 1 3/8 1 5/8 1 5/8 1 5/8 2 1/8 1 3/8 1 5/8 1 5/8
1 1/8 1 3/8 1 3/8 1 3/8 1 5/8 1 5/8 1 1/8 1 3/8 1 3/8 1 5/8 1 5/8 2 1/8 1 3/8 1 3/8 1 5/8 1 5/8 2 1/8 2 1/8 1 3/8 1 5/8 1 5/8
1 1/8 1 3/8 1 3/8 1 5/8 1 5/8 2 1/8 1 3/8 1 3/8 1 5/8 1 5/8 2 1/8 2 1/8 1 3/8 1 5/8 1 5/8 2 1/8 2 1/8 2 1/8 1 5/8 1 5/8 2 1/8
1 3/8 1 3/8 1 5/8 1 5/8 2 1/8 2 1/8 1 3/8 1 5/8 1 5/8 2 1/8 2 1/8 2 1/8 2 1/8 1 5/8 1 5/8 2 1/8 2 1/8 2 5/8 1 5/8 2 1/8 2 1/8
1 3/8 1 5/8 1 5/8 2 1/8 2 1/8 2 1/8 1 3/8 1 5/8 2 1/8 2 1/8 2 1/8 2 1/8 1 5/8 2 1/8 2 1/8 2 1/8 2 5/8 2 5/8 1 5/8 2 1/8 2 1/8
1 3/8 1 5/8 1 5/8 2 1/8 2 1/8 2 1/8 1 5/8 2 1/8 2 1/8 2 1/8 2 1/8 2 5/8 1 5/8 2 1/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 1/8
1 5/8 1 5/8 2 1/8 2 1/8 2 1/8 2 5/8 1 5/8 2 1/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8
1 5/8 2 1/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 2 5/8 3 1/8 2 1/8 2 5/8 2 5/8
2 1/8 2 1/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 2 5/8 3 1/8 2 1/8 2 5/8 2 5/8 2 5/8 3 1/8 3 1/8 2 1/8 2 5/8 2 5/8
2 1/8 2 1/8 2 5/8 2 5/8 2 5/8 3 1/8 2 1/8 2 5/8 2 5/8 2 5/8 3 1/8 3 1/8 2 1/8 2 5/8 2 5/8 3 1/8 3 1/8 3 5/8 2 5/8 2 5/8 3 1/8
2 1/8 2 5/8 2 5/8 2 5/8 3 1/8 3 1/8 2 1/8 2 5/8 3 1/8 3 1/8 3 1/8 3 5/8 2 5/8 2 5/8 3 1/8 3 1/8 3 5/8 3 5/8 2 5/8 3 1/8 3 1/8
2 1/8 2 5/8 3 1/8 3 1/8 3 1/8 3 5/8 2 5/8 3 1/8 3 1/8 3 5/8 3 5/8 4 1/8 2 5/8 3 1/8 3 5/8 3 5/8 4 1/8 4 1/8 3 1/8 3 5/8 3 5/8
2 5/8 3 1/8 3 1/8 3 1/8 3 5/8 3 5/8 3 1/8 3 1/8 3 5/8 3 5/8 4 1/8 4 1/8 3 1/8 3 5/8 3 5/8 4 1/8 4 1/8 4 1/8 3 1/8 3 5/8 4 1/8
* NOTES:
1. Sizes that are highlighted indicate maximum suction line sizes that should be used for risers. Riser size should not
exceed horizontal size. Properly placed suction traps must also be used for adequate oil return.
All sizes shown are for O.D. Type L copper tubing.
2. Suction line sizes selected at pressure drop equivalent to 2˚F. Reduce estimate of system capacity accordingly.
3. Recommended liquid line size may increase with reverse cycle hot gas systems.
4. If system load drops below 40% of design, consideration to installing double suction risers should be made.
14
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 6B. Recommended Line Sizes for R-22 (continued) *
SUCTION LINE SIZE
LIQUID LINE SIZE
Receiver to
SUCTION TEMPERATURE
0˚F
-10˚F
-20˚F
Expansion Valve
Equivalent Lengths
SYSTEM
CAPACITY
BTU/H
Lengths
Equivalent Lengths
Equivalent Lengths
100' 150' 200' 25'
50'
3/8
1/2
1/2
5/8
7/8
7/8
7/8
7/8
75'
3/8
1/2
5/8
5/8
7/8
7/8
7/8
100' 150'
200' 25'
50'
3/8
1/2
5/8
5/8
7/8
7/8
7/8
75'
3/8
5/8
5/8
7/8
7/8
7/8
100' 150' 200' 25' 50' 75' 100' 150' 200'
3/8
5/8
5/8
5/8
7/8
7/8
7/8
1/2
5/8
5/8
7/8
7/8
1/2
5/8
7/8
7/8
7/8
3/8
1/2
1/2
1/2
5/8
3/8
5/8
5/8
7/8
7/8
7/8
1/2
5/8
1/2
5/8
7/8
7/8
7/8
3/8
1/2
1/2
5/8
5/8
1/2
5/8
5/8
7/8
7/8
1/2
5/8
7/8
7/8
1/2
7/8
7/8
7/8
3/8 3/8 3/8 3/8 3/8
3/8 3/8 3/8 3/8 3/8
3/8 3/8 3/8 3/8 3/8
3/8 3/8 3/8 3/8 3/8
3/8
3/8
3/8
3/8
3/8
3/8
1/2
1/2
1/2
1/2
1/2
5/8
5/8
5/8
5/8
5/8
5/8
7/8
7/8
7/8
7/8
7/8
1,000
3,000
5/8
4,000
7/8
6,000
7/8
1 1/8 1 1/8 3/8 3/8 3/8 3/8 3/8
9,000
7/8 1 1/8 7/8
1 1/8 1 1/8 7/8
1 18
1 1/8 7/8
1 1/8 7/8
1 1/8 7/8
1 3/8 7/8
1 1/8 1 1/8 1 1/8 3/8 3/8 3/8 3/8 3/8
12,000
15,000
18,000
24,000
30,000
36,000
42,000
48,000
54,000
60,000
66,000
72,000
78,000
84,000
90,000
120,000
150,000
1 1/8 1 1/8
1 1/8 1 1/8 1 1/8 1 1/8 3/8 3/8 3/8 3/8 3/8
1 1/8 1 1/8 1 1/8 7/8
1 1/8 1 1/8 1 1/8
1 1/8 1 1/8 1 1/8 1 1/8 1 3/8 3/8 3/8 3/8 3/8 1/2
1 1/8 1 1/8 1 3/8 1 3/8 1 3/8 3/8 3/8 1/2 1/2 1/2
1 1/8 1 1/8 1 3/8 7/8 1 1/8 1 1/8 1 1/8 1 3/8
1 1/8 1 3/8 1 3/8 7/8 1 1/8 1 1/8 1 3/8 1 3/8
1 3/8 1 3/8 1 3/8 1 1/8 1 1/8 1 3/8 1 3/8 1 3/8
1 3/8 1 3/8 1 5/8 1 1/8 1 1/8 1 3/8 1 3/8 1 5/8
1 3/8 1 5/8 1 5/8 1 1/8 1 3/8 1 3/8 1 3/8 1 5/8
1 3/8 1 5/8 1 5/8 1 1/8 1 3/8 1 3/8 1 5/8 1 5/8
1 5/8 1 5/8 2 1/8 1 1/8 1 3/8 1 3/8 1 5/8 1 5/8
1 5/8 1 5/8 2 1/8 1 3/8 1 3/8 1 5/8 1 5/8 1 5/8
1 5/8 2 1/8 2 1/8 1 3/8 1 3/8 1 5/8 1 5/8 2 1/8
1 5/8 2 1/8 2 1/8 1 3/8 1 5/8 1 5/8 1 5/8 2 1/8
1 5/8 2 1/8 2 1/8 1 3/8 1 5/8 1 5/8 2 1/8 2 1/8
2 1/8 2 1/8 2 1/8 1 3/8 1 5/8 1 5/8 2 1/8 2 1/8
2 1/8 2 1/8 2 1/8 1 5/8 1 5/8 2 1/8 2 1/8 2 1/8
2 1/8 2 5/8 2 5/8 1 5/8 2 1/8 2 1/8 2 1/8 2 5/8
2 1/8 2 5/8 2 5/8 1 5/8 2 1/8 2 1/8 2 5/8 2 5/8
2 5/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 2 5/8
2 5/8 2 5/8 3 1/8 2 1/8 2 1/8 2 5/8 2 5/8 2 5/8
2 5/8 3 1/8 3 1/8 2 1/8 2 5/8 2 5/8 2 5/8 3 1/8
3 1/8 3 1/8 3 1/8 2 1/8 2 5/8 2 5/8 3 1/8 3 1/8
3 1/8 3 5/8 3 5/8 2 5/8 3 1/8 3 1/8 3 1/8 3 5/8
3 5/8 3 5/8 4 1/8 2 5/8 3 1/8 3 1/8 3 5/8 3 5/8
4 1/8 4 1/8 5 1/8 3 1/8 3 5/8 4 1/8 4 1/8 5 1/8
1 3/8 1 1/8 1 1/8 1 3/8 1 3/8 1 3/8 1 5/8 3/8 3/8 1/2 1/2 1/2
1 5/8 1 1/8 1 3/8 1 3/8 1 3/8 1 5/8 1 5/8 3/8 1/2 1/2 1/2 1/2
1 5/8 1 1/8 1 3/8 1 3/8 1 5/8 1 5/8 1 5/8 3/8 1/2 1/2 1/2 1/2
1 5/8 1 1/8 1 3/8 1 3/8 1 5/8 1 5/8 2 1/8 1/2 1/2 1/2 1/2 1/2
1 5/8 1 3/8 1 3/8 1 5/8 1 5/8 2 1/8 2 1/8 1/2 1/2 1/2 1/2 5/8
2 1/8 1 3/8 1 3/8 1 5/8 1 5/8 2 1/8 2 1/8 1/2 1/2 1/2 5/8 5/8
2 1/8 1 3/8 1 5/8 1 5/8 1 5/8 2 1/8 2 1/8 1/2 1/2 5/8 5/8 5/8
2 1/8 1 3/8 1 5/8 1 5/8 2 1/8 2 1/8 2 1/8 1/2 1/2 5/8 5/8 5/8
2 1/8 1 3/8 1 5/8 1 5/8 2 1/8 2 1/8 2 1/8 1/2 1/2 5/8 5/8 5/8
2 1/8 1 3/8 1 5/8 2 1/8 2 1/8 2 1/8 2 1/8 1/2 5/8 5/8 5/8 5/8
2 1/8 1 3/8 1 5/8 2 1/8 2 1/8 2 1/8 2 1/8 1/2 5/8 5/8 5/8 7/8
2 5/8 1 5/8 2 1/8 2 1/8 2 1/8 2 5/8 2 5/8 5/8 5/8 5/8 7/8 7/8
2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 2 5/8 2 5/8 5/8 7/8 7/8 7/8 7/8
2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 2 5/8 3 1/8 5/8 7/8 7/8 7/8 7/8 1 1/8 180,000
2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 3 1/8 3 1/8 7/8 7/8 7/8 7/8 7/8 1 1/8 210,000
3 1/8 2 1/8 2 5/8 2 5/8 2 5/8 3 1/8 3 1/8 7/8 7/8 7/8 7/8 1 1/8 1 1/8 240,000
3 1/8 2 1/8 2 5/8 3 1/8 3 1/8 3 1/8 3 5/8 7/8 7/8 1 1/8 1 1/8 1 1/8 1 1/8 300,000
3 5/8 2 5/8 2 5/8 3 1/8 3 1/8 3 5/8 3 5/8 7/8 7/8 1 18 1 1/8 1 1/8 1 1/8 360,000
3 5/8 2 5/8 3 1/8 3 5/8 3 5/8 3 5/8 4 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 3/8 1 3/8 480,000
4 1/8 3 1/8 3 1/8 3 5/8 3 5/8 4 1/8 4 1/8 1 1/8 1 1/8 1 1/8 1 3/8 1 3/8 1 3/8 600,000
5 1/8 3 5/8 4 1/8 4 1/8 5 1/8 5 1/8 5 1/8 1 1/8 1 1/8 1 3/8 1 3/8 1 3/8 1 5/8 720,000
4 1/8 5 1/8 5 1/8 3 5/8 4 1/8 4 1/8 5 1/8 5 1/8 5 1/8 3 5/8 4 1/8 5 1/8 5 1/8 5 1/8 6 1/8 1 1/8 1 3/8 1 3/8 1 5/8 1 5/8 1 5/8 900,000
* NOTES:
1. Sizes that are highlighted indicate maximum suction line sizes that should be used for risers. Riser size should not
exceed horizontal size. Properly placed suction traps must also be used for adequate oil return.
All sizes shown are for O.D. Type L copper tubing.
2. Suction line sizes selected at pressure drop equivalent to 2˚F. Reduce estimate of system capacity accordingly.
3. Recommended liquid line size may increase with reverse cycle hot gas systems.
4. If system load drops below 40% of design, consideration to installing double suction risers should be made.
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 7. Recommended Remote Condenser Line Sizes
R-12 & R-134a
Liquid Line
R-22
R-502
Liquid Line
R507 & R-404A
Liquid Line
Liquid Line
Cond. to
Receiver
(O.D.)
3/8
Net
Evaporator
Capacity
Total
Equiv.
Length
50
100
50
100
50
100
50
Discharge
Line
(O.D.)
3/8
Cond. to
Receiver
(O.D.)
3/8
Discharge
Line
(O.D.)
3/8
Discharge
Line
(O.D.)
3/8
Cond. to
Receiver
(O.D.)
3/8
Discharge
Line
(O.D.)
3/8
Cond. to
Receiver
(O.D.)
3/8
3,000
1/2
3/8
3/8
3/8
3/8
3/8
3/8
3/8
1/2
3/8
3/8
3/8
3/8
3/8
1/2
3/8
6,000
9,000
1/2
3/8
1/2
3/8
1/2
3/8
1/2
3/8
5/8
3/8
1/2
3/8
1/2
3/8
1/2
3/8
5/8
3/8
1/2
3/8
1/2
3/8
5/8
3/8
5/8
1/2
1/2
3/8
1/2
3/8
1/2
3/8
12,000
18,000
100
50
100
50
7/8
1/2
5/8
3/8
5/8
3/8
5/8
3/8
7/8
1/2
1/2
3/8
5/8
1/2
5/8
1/2
7/8
1/2
5/8
3/8
5/8
1/2
5/8
1/2
7/8
7/8
7/8
5/8
5/8
5/8
5/8
7/8
7/8
7/8
7/8
7/8
7/8
7/8
7/8
1 1/8
1 1/8
1 3/8
1 3/8
1 5/8
1 5/8
1 5/8
1 5/8
1 5/8
1 5/8
2 1/8
2 1/8
2 1/8
2 1/8
2 5/8
2 5/8
2 5/8
2 5/8
3 1/8
3 1/8
3 1/8
3 1/8
3 5/8
3 5/8
3 5/8
3 5/8
4 1/8
4 1/8
5/8
5/8
7/8
7/8
7/8
7/8
7/8
7/8
1/2
1/2
5/8
5/8
5/8
5/8
7/8
7/8
7/8
7/8
7/8
7/8
1 1/8
1 1/8
1 3/8
1 3/8
1 3/8
1 3/8
1 5/8
1 5/8
1 5/8
1 5/8
2 1/8
2 1/8
2 1/8
2 1/8
2 5/8
2 5/8
2 5/8
2 5/8
3 1/8
3 1/8
3 1/8
3 1/8
3 1/8
3 1/8
3 5/8
3 5/8
3 5/8
3 5/8
5/8
7/8
7/8
7/8
7/8
7/8
5/8
5/8
5/8
5/8
7/8
7/8
7/8
7/8
7/8
7/8
7/8
7/8
7/8
1 1/8
7/8
5/8
5/8
5/8
5/8
7/8
7/8
7/8
7/8
24,000
36,000
48,000
60,000
72,000
90,000
120,000
100
50
100
50
100
50
100
50
100
50
100
50
100
50
100
50
100
50
100
50
100
50
100
50
100
50
100
50
100
50
100
50
1 1/8
1 1/8
1 1/8
1 1/8
1 3/8
1 1/8
1 3/8
1 3/8
1 3/8
1 3/8
1 5/8
1 5/8
2 1/8
1 5/8
2 1/8
2 1/8
2 1/8
2 1/8
2 5/8
2 1/8
2 5/8
2 5/8
3 1/8
2 5/8
3 1/8
2 5/8
3 1/8
3 1/8
3 1/8
3 1/8
3 5/8
3 1/8
3 5/8
3 1/8
3 5/8
3 5/8
4 1/8
1 1/8
1 1/8
1 1/8
1 1/8
1 1/8
1 1/8
1 1/8
1 3/8
1 3/8
1 5/8
1 5/8
1 5/8
1 5/8
2 1/8
1 5/8
2 1/8
2 1/8
2 1/8
2 1/8
2 5/8
2 1/8
2 5/8
2 5/8
2 5/8
2 5/8
2 5/8
2 5/8
3 1/8
2 5/8
3 1/8
3 1/8
3 1/8
3 1/8
3 5/8
1 1/8
1 1/8
1 1/8
1 1/8
1 3/8
1 1/8
1 3/8
1 3/8
1 5/8
1 5/8
1 5/8
1 5/8
2 1/8
2 1/8
2 1/8
2 1/8
2 1/8
2 1/8
2 5/8
2 1/8
2 5/8
2 5/8
2 5/8
2 5/8
3 1/8
2 5/8
3 1/8
2 5/8
3 1/8
3 1/8
3 5/8
3 1/8
3 5/8
7/8
1 1/8
7/8
7/8
7/8
7/8
7/8
1 1/8
1 1/8
1 3/8
1 3/8
1 3/8
1 3/8
1 5/8
1 5/8
1 5/8
1 5/8
2 1/8
2 1/8
2 1/8
2 1/8
2 5/8
2 5/8
3 1/8
3 1/8
3 1/8
3 1/8
3 1/8
3 1/8
3 5/8
3 5/8
3 5/8
3 5/8
4 1/8
4 1/8
4 1/8
4 1/8
1 1/8
1 1/8
1 1/8
1 1/8
1 3/8
1 3/8
1 5/8
1 5/8
2 1/8
2 1/8
2 1/8
2 1/8
2 1/8
2 1/8
2 1/8
2 1/8
2 5/8
2 5/8
3 1/8
3 1/8
3 1/8
3 1/8
3 1/8
3 1/8
3 5/8
3 5/8
3 5/8
3 5/8
4 1/8
4 1/8
1 1/8
1 1/8
1 1/8
1 3/8
1 3/8
1 5/8
1 5/8
1 5/8
1 5/8
1 5/8
2 1/8
2 1/8
2 1/8
2 1/8
2 1/8
2 1/8
2 5/8
2 1/8
2 5/8
2 5/8
2 5/8
2 5/8
2 5/8
2 5/8
3 1/8
2 5/8
3 1/8
2 5/8
3 1/8
180,000
240,000
300,000
360,000
480,000
600,000
720,000
840,000
960,000
1,080,000
100
50
100
50
100
50
100
1,200,000
1,440,000
1,680,000
16
Download from Www.Somanuals.com. All Manuals Search And Download.
Leak Checking, Evacuation,
and Start-up
4. With all compressor and control breakers and toggle
switches turned off, apply power to the unit. If the unit is
using a phase monitor, the green light must come on
before going any further. (See instructions for phase
protector elsewhere in this manual.) A red light indicates
incorrect phasing or voltage. Check with a volt meter to
see if correct voltage is connected to the unit. Correct the
Power Supply before proceeding.
Warning: It is illegal to knowingly vent or discharge
any CFC’s and HCFC’s to the atmosphere. ALL
CFC’s and HCFC’s must be reclaimed or recycled.
5. Turn on the circuit breaker for the control power. If an
electronic control system is installed on the unit, it will
initiate at this time. The Heatcraft preferred controller is
manufactured by Computer Process Control (CPC).
Review the manual for the controller supplied with the
system.
Leak Check
1. To check the systems for leaks, leave all valves closed on
suction, liquid and hot gas manifolds. The unit is shipped
with a holding charge of dry nitrogen and should be leak
free. Build up the pressure in each circuit to a maximum
of 150 psig dry nitrogen and check each individual circuit.
6. Turn on circuit breakers to all compressors. The
compressors can be started by turning on the compressor
toggle switches. Likewise, each circuit control can be
started by turning on the circuit toggle switch. It is
recommended that one compressor at a time be started
and checked before allowing them all to operate. It is also
advisable to check one circuit at a time to be certain all
components work when called upon and that the circuit
wiring is correct.
2. After each circuit has been checked, open all valves to
allow the pressure into the unit assembly. Check to be
sure pressure is throughout the assembly. Check all
connections and accessories for leaks.
Evacuation
1. After the system is leak checked, connect a good high
vacuum pump with fresh oil to both the low and high side
evacuation valves. Connections between the pump and
evacuation valves should be made with copper tubing or
high vacuum hose having a diameter of at least 3/8”.
Evacuate the system to 1500 microns for the first
evacuation.
7. When each circuit and compressor has been tested and
the appropriate amount of refrigerant has been added for
proper operation, allow the system to operate and pull-
down the room/fixture temperatures.
8. Once the system is operating, set all regulating valves.
2. After each evacuation, the vacuum should be broken by
the introduction of refrigerant into the system. The
refrigerant should be passed through a drier when
breaking the vacuum until the pressure is brought up to 0
psig.
9. When the room and/or the fixture temperatures are at
design, the expansion valves should be set. (See
instructions elsewhere in this manual.)
10.Adjust the electronic or manual pressure controls as
necessary to maintain proper pressures and
temperatures.
3. Between the first and second evacuation, the liquid filter
driers and suction filters should be installed in each
replaceable core shell.
11. Check the refrigerant level in the receiver. The minimum
level that should be maintained is 20%.
4. A triple evacuation is recommended. The third and final
evacuation should achieve a value of 500 microns or less.
After this vacuum is reached, add as much refrigerant as
possible into the receiver. Now the system is ready to be
started.
12.All circuit defrost controls must be set and checked.
Again, one circuit at a time should be tested.
13.Set condenser fan controls to maintain the proper
discharge pressure.
Start-up
14.All safety controls should be checked and verified. Check
that the alarm circuitry is operating at this time.
1. Set all pressure controls as recommended elsewhere in
this manual. Recheck all service valves and shut-off
valves to be sure they are open.
15.Check the oil reservoir during the start-up and add oil as
necessary. The oil level should be between the upper and
lower reservoir sight glass. Do not add more than two
gallons of oil to a system. If more oil is needed, recheck
the piping as oil is not returning to the unit properly.
2. Check and be sure the condenser fan motors are running
in the correct rotation.
3. All evaporator fan motors should be checked for proper
rotation. The fans in low temperature boxes generally
have a fan delay for defrost purposes that keep the fans
from operating until the evaporator coil has reached a
certain temperature. It will be necessary to jump-out the
fan controls on freezer units to make them run through
final charging and room temperature pull-down. The
wiring diagram for the unit will have to be consulted to
determine how to best force the fans to operate for this
step.
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Refrigerant Distribution
Hot discharge gas is injected into the suction line at the
parallel rack and flows to the evaporator being defrosted. The
discharge gas will condense into liquid as it flows through the
cold evaporator.
The distribution system is selected based upon the type of
defrost for that particular system. For each set of liquid /
suction lines a distribution system must be selected.
The liquid exits the coil at the distributor side-port, then flows
through the liquid line by pass check valve into the drain
manifold and then returned to the condenser inlet.
Liquid solenoids are recommended to be installed at the
evaporator on all systems, particularly systems with long line
runs. The solenoid will prevent continued feed to the
evaporator through the expansion valve when it is not in
operation. A solenoid is mentioned in each of the refrigerant
distribution analysis, and are shipped loose to be installed at
the evaporators.
The pressure in the condenser is controlled to be below the
returning liquid pressure by a discharge gas regulator valve.
The returning liquid pressure helps in driving refrigerate from
the condenser to the receiver to maintain liquid refrigerant
flows to the refrigerating evaporators. The Priority I system
requires that no more than 20% of the evaporators defrost at
one time.
Heatcraft offers three types of defrost : Off cycle defrost,
Electric defrost and the Priority I hot gas defrost system for
Racks. The type of defrost is generally a matter of either
contractor or owner preference. Typical operation is as
follows:
The discharge gas regulator valve (DDGR) is normally set to
maintain approximately 25 psig differential pressure. The
next part of the Priority I system consists of a small capacity
control system located at the compressor rack. The
discharge gas bypass regulator valve should be set to
maintain the normal suction pressure during normal
refrigeration. There is a desuperheating TXV mounted to
prevent overheating the suction line. The expansion valve
should not require an adjustment as it is preset to maintain
20°F superheat. See page 31 of this manual for more
information on the adjustment of the discharge gas bypass
regulator valve.
Off cycle
The off cycle system consists of liquid and suction line ball
valves for circuit isolation, liquid solenoid and defrost
controller. Defrost is initiated by the controller. The liquid
solenoid closes pumping down the circuit, the evaporator fans
remain in operation and room air melts the ice on the coil.
The controller terminates the defrost period after a
predetermined time period and opens the liquid solenoid
putting the system back into refrigeration.
Electric defrost
Head pressure control system
The electric defrost system consists of liquid and suction line
ball valves for circuit isolation, liquid solenoid, evaporator
heater contactor, heater fusing, evaporator fan motor
contactor and fuses if three phase fans are used, and defrost
controller.
Almost all refrigeration systems require some form of year
round head pressure control. This is due to the fixed amount
of condenser surface which has been selected for summer
conditions. During the winter, the condenser is oversized for
the system and low head pressure will result. This will cause
erratic operation of the system.
Defrost is initiated by the controller. The liquid solenoid
closes, the evaporator fan contactor opens stopping the fans,
and the defrost heater contactor is energized.
The following method of head pressure control is considered
the most effective means and has the advantage of
When the defrost heaters warm the coil to a predetermined
level an adjustable defrost termination device within the
evaporator signals the defrost controller to end the defrost
period. A fan delay is provided at the end of each defrost
cycle to allow the evaporator to cool before the fans start.
This also prevents warm air and condensation from being
discharged from the unit. The liquid solenoid opens putting
the system back into refrigeration.
performing well at low outside ambient temperatures. The
disadvantage is the fact that a relatively large quantity
refrigerant must be used to flood the condenser and sufficient
receiver storage must be provided during summer operation.
Head pressure control system consists of a condenser
drain line valve and a discharge bypass valve. In order to
maintain moderate head pressure the condenser drain valve
senses condensing pressure. As condensing pressure falls in
response to lower ambient temperatures, the drain valve will
begin to restrict flow of liquid from the condenser filling
condenser tubes with liquid refrigerant. This results in
decreased surface area causing the discharge pressure to
rise.
Priority I hot gas defrost
For Racks Only
The Priority I hot gas defrost system consists of liquid and
suction line ball valves for circuit isolation, liquid line solenoid
with by pass check valve, suction solenoid valve, hot gas
solenoid valve, liquid drain solenoid valve, liquid drain
manifold, and defrost controller.
When pressure reaches the midpoint setting the valve begins
to open allowing liquid to flow to the receiver. Simultaneously
the discharge bypass valve installed in a line between the
discharge manifold and the receiver maintains minimum
receiver pressure to insure liquid flow.
Defrost is initiated by the defrost controller closing the liquid
solenoid and suction solenoid. The hot gas and liquid drain
solenoids open (Unlike typical systems wherein the
condensed liquid from the defrosting evaporator is returned
into the liquid manifold, the Priority I design returns the liquid
to the condenser through a liquid drain manifold).
18
Download from Www.Somanuals.com. All Manuals Search And Download.
Electronic control system
High suction superheat will result in excessive discharge
temperatures that can cause a breakdown of the oil. This
action results in piston ring wear, piston and cylinder wall
damage.
The electronic controller has become the standard on parallel
compressor systems. The increased capabilities of the
controllers magnify the efficiency of the parallel compressor
system making it a very attractive accessory item.
Also, as the superheat increases, the suction pressure
decreases resulting in reduced capacity. For maximum
system capacity, suction superheat should be kept as low as
is practical. HEATCRAFT recommends that the superheat at
the compressor be no lower than 20°F.
The electronic control system preferred by Heatcraft is the
Computer Process Control (RMCC) controller. The RMCC
offers a complete control and monitoring package through
one or more input boards (16AI). The controller continuously
monitors the parameters for refrigerant pressures, defrost
operation, temperature control, and system alarms.
If adjustments to the suction superheat need to be made, the
expansion valve at the evaporator should be adjusted. See
instructions in next section.
As the RMCC monitors the system in operation, it compares
the reported values against programmed set points it is to
maintain, thus cycling compressors, unloaders, condenser
fans, defrost periods and sounding alarms as required.
Evaporator Superheat
Check Your Superheat after the box temperature has reached
or is close to reaching the desired temperature, the
evaporator superheat should be checked and adjustments
made if necessary. Generally, systems with a design TD of
10°F should have a superheat value of 6° to 10° F for
maximum efficiency.
Interface with the actual devices being controlled is through
one or more pressure transducers, watt transducer,
temperature sensors, refrigerant sensors, humidity sensors,
refrigerant level sensor, phase loss, and output boards (8R0).
The 8RO boards can be mounted remotely for lower
installation cost, when controlling devices such as air cooled
condensers. These boards are connected to the RMCC via a
three wire network and are purchased as needed for the
application. Remote communications capabilities is standard
with the RMCC through a modem that is supplied.
To properly determine the superheat of the evaporator, the
following procedure is the method Heatcraft recommends.
1. Measure the temperature of the suction line at
the point the bulb is clamped.
2. Obtain the suction pressure that exists in the
suction line at the bulb location by either of the
following methods:
System Balancing
a) A gauge in the external equalized line
will indicate the pressure directly and
accurately.
Important: In order to obtain the maximum
capacity from a system, and to ensure trouble-
free operation, it is necessary to balance each
and every system.
b) A gauge directly in the suction line near
the evaporator or directly in the suction
header of the evaporator will yield the
same reading as above.
System Superheat
3. Convert the pressure obtained in 2a or 2b
above to saturated evaporator temperature by
using a temperature-pressure chart.
This is extremely important with any refrigeration system.
The critical value that must be checked is suction
superheat.
4. Subtract the Saturated temperature from the
actual suction line temperature. The difference
is Superheat.
Superheat is not preset at the factory.
Suction superheat should be checked at the compressor as
follows:
Alternative Superheat Method
1. Measure the suction pressure at the suction
service valve of the compressor and determine
the saturation temperature corresponding to
this pressure from a “Temperature-Pressure”
chart.
The most accurate method of measuring superheat is found
by following the previous procedure, Temperature / Pressure
method. However, that method may not always be practical.
An alternative method which will yield fairly accurate results is
the temperature / temperature method.
2. Measure the suction temperature of the
suction line about one foot back from the
compressor using an accurate thermometer.
1. Measure the temperature of the suction line at
the point the bulb is clamped (outlet).
2. Measure the temperature of one of the
distributor tubes close to the evaporator coil
(inlet).
3. Subtract the Saturated temperature from the
actual suction line temperature. The difference
is Superheat.
3. Subtract the outlet temperature from the inlet
temperature. The difference is approximate
Superheat.
If suction superheat is too low, it can result in liquid refrigerant
being returned to the compressor. This will cause dilution of
the oil and eventual failure of the bearings and piston rings.
In extreme cases, the compressor will fail as a result of the
diluted oil.
This method will yield fairly accurate results as long as the
pressure drop through the evaporator coil is low.
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Compressors
reciprocating systems or as directed by the specific
compressor manufacturer. A high pressure cutout and oil
failure control are installed and wired for each compressor.
The majority of the Heatcraft Parallel systems incorporate the
Copeland compressor. Other brand compressors are
available upon customer request. The compressors are solid
mounted to a base frame or mounted on the refrigerant
receiver. All reciprocating compressors incorporate oil floats.
Crankcase heaters will be installed and wired. Cylinder head
cooling fans will be installed on all low temperature
Many compressors are available with unloading for capacity
control. The unloading of a compressor adds many capacity
steps to those normally available to an electronic controller.
Usually, the more steps available the better the load can be
matched.
Copeland Compressors
Table 8. 3D / 4D / 6D Solid State Modules
Control Voltage
Model
Number
Copeland
Kit
Copeland
Number
T.I.
Number
Number
115 - 230 Volts
3D-FSM
4D / 6D
998-0524-00
071-0524-00
31AA-1600E
Table 9. Typical Voltage Ranges
Voltage
60 Hertz Rating
50 Hertz Rating
Code
B
C
D
E
K
M
N
Rating
230-1
208/230-3
460-3
575-3
208/230/460-3
-
Min.
207
187
414
518
187
-
Max.
Rating
-
200/220-3
380/420-3
500-3
200/380/400-3
380/420-3
200/400-3
-
Min.
-
Max.
-
253
253
506
633
506
-
180
342
450
180
342
180
-
240
462
550
440
462
440
-
230/460-3
200-3
207
180
506
220
U
Refer to voltage rating of specific models.
Table 10. Unloader Factors
Model
Factors
3D
See Copeland Application Bulletin Number AE 21-1278
Moduload - Capacity Control for 3D Compressors
Full Load
One Bank
Two Bank
Unloading
MT
Unloading
Performance
CAPACITY
POWER
AMPS
CAPACITY
POWER
HT
MT
LT
HT
.50
.56
.60
.70
.70
.75
LT
.50
.56
.74
.70
.72
.84
HT
-
-
MT
-
-
LT
-
-
1.00
1.01
1.01
1.00
1.01
1.03
1.00
1.03
1.03
1.00
1.03
1.04
1.00
1.02
1.02
1.00
1.02
1.02
.50
.56
.60
.70
.71
.77
4D
6D
-
-
-
.36
.40
.55
.36
.42
.60
.36
.43
.72
AMPS
Multiply compressor rating data by above factors when used with blocked suction unloading.
Refer to Copeland AE 17-1287 for Demand Cooling Restrictions on unloading.
Table 11. Oil Safety Switch
Pressure
Alarm
Copeland
Part No.
MFGRS.
Model No.
Diff. Psi (bar)
Circuit
Cut-In
Cut-Out
Sentronic
P45NCA-12
P30-5826
PD21-2502
PD21-1006
P45NCB-3
LG21-2501
7 – 9
12 - 14
Yes
No
Yes
No
Yes
Yes
Yes
085-0062-00
Penn
Ranco
Robertshaw
Robertshaw
Penn
9 (± 2)
14
085-0088-00
085-0101-00
Robertshaw
All controls are Manual Reset type with a 120 second nominal time delay at the rated voltage.
20
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 12. Oil Charges
Model
Standard
Deep Sump
Family
Initial (oz)
Recharge (oz)
Initial (oz)
Recharge (oz)
2D
3D
80
72
110
190
-
95
170
-
115
140
135
135
130
130
140
140
255
255
105
130
120
120
120
120
125
130
245
245
4DA3-100E
4DL3-150E
4DA3-200E
4DT3-220E
4DH3-250E
4DJ3-300E
6D
250
250
245
245
255
255
255
255
235
235
235
235
240
245
245
245
6DT3-300*
6DJ3-400*
Approved Copeland Lubricants
Mineral Oil - Suniso 3GS or Equivalent
POE - Copeland Ultra 22CC / Mobil EAL™ Arctic 22 CC / ICI
Emkarate™ RL32CF / Thermal Zone 22CC
Alkyl Benzene - Copeland Ultra 200 / Shrieve Zerol 200 TD /
Soltex AB 200A / Thermal Zone 200
Bitzer Screw / Copeland Contour Screw compressor
lubricant: Solest 170
Carlyle Compressors
Oil Pressure
Approved Carlyle Lubricants
The O6D and O6E oil pump is a positive displacement vane
type. It produces high volume oil flow at a low oil pressure.
The compressor utilizes an internal pressure regulator valve
to maintain oil pressure at a constant 12 to 36 psi above
suction pressure.
For CFC and HCFC refrigerants use:
Totaline 150 / Suniso 3GS / Shrieve Zerol 150 / Texaco WFI-
32-150 / IGI Petroleum Cryol-150
For HFC refrigerants use:
CPI Solest 120 / ICI Emkarate™ RL68H / +Lubrizol Lubrikuhl
2916S / *Mobil Arctic EAL™ 68 / *Castrol SW68
+ Lubrizol ISO68 also sold under Texaco Capella HFC 68NA brand
* Medium temperature applications only
Table 13. O6D/E Oil Pressure History
O6D MODELS
O6E MODELS
PSI (BAR)
PSI (BAR)
Before May 1984
12 to 18
(.83 to 1.24)
16 to 22
12 to 18
(.83 to 1.24)
16 to 22
(Prior S/N 2084J...)
May 1984 to March 1994
(Between S/N 2084J... & 1094J)
Starting March 1994
(1.1 to 1.52)
18 to 26
(1.1 to 1.52)
18 to 34
(Starting S/N 1094J....)
(1.24 to 1.8)
(1.24 to 2.3)
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 14. Oil Safety Switch
Pressure
Carlyle
Part No.
634-2008
OR
P529-2130
634-2050
OR
Danfoss
Part No.
Time
Delay
Diff. Psi (bar)
Cut-In
Cut-Out
Reset
60B2101
60B2151
45 sec.
8 – 11
4 - 8
Manual
(.55 - .76)
(.28 - .55)
P529-2100
Pressure
Diff. Psi (bar)
Carlyle
Part No.
O6DA660115
Johnson
Part No.
P345
Time
Delay
45 sec.
Cut-In
Cut-Out
4 - 8
Reset
Manual
8 – 11
(.55 - .76)
(.28 - .55)
Table 15. Part Load Performance Multipliers
Multiplication Factor
For 1 Bank Unloaded
Multiplication Factor
For 2 Bank Unloaded
Compressor Model
Capacity
.49
Power
.57
.73
EER
.86
.92
Capacity
Power
EER
-
.70
All 4 Cylinder Models
All 6 Cylinder Models
-
-
.67
.32
.46
Table 16. Required Differential Pressure
for Unloader Operation
Suction Pressure
Range PSI (Bar)
∆P Required-Discharge Minus
Application
Suction Pressure PSI (Bar)
O6D
O6E
L.T. R-502, 404A, 507
M.T. R-502, 404A, 507
L.T. R-12, 134a
10-25
(1.7-2.7)
30
40
30
50
(2.1)
(2.8)
(2.1)
(3.5)
30
45
35
55
(2.1)
(3.1)
(2.4)
(3.8)
30-60
10-30
30-90
(3.1-5.2)
(1.7-3.1)
(3.1-7.2)
M.T. R-22 or H.T. R-22
Multiply compressor rating data by above factors when used with blocked suction unloading.
3-Phase Voltage Monitor
The microprocessor-based voltage and phase sensing circuit
constantly monitors the three phase voltages to detect
harmful power line conditions. When a harmful condition is
detected, the phase monitor output relay is deactivated after
a specified trip delay. The output relay reactivates after
power line conditions return to an acceptable level for a
specified amount of time (Restart Delay). The trip delay
prevents nuisance tripping due to rapidly fluctuating power
line conditions.
reversed. Each main power line should be checked for
proper voltage and imbalance prior to reversing a phase.
Also check the settings of the Voltage Monitor for proper field
conditions.
For semi-hermetic compressor units, two of the three power
monitor leads on the Voltage Monitor to L1, L2, and L3 may
need to be switched. For units with Scroll or Screw
compressors, which are rotation sensitive, two of the main
power lines to the compressor unit will have to be switched to
match the correct rotation of the compressors. The rotation
of Screw and Scroll compressors has been properly phased
in the manufacturing plant prior to shipping.
The Bicolor LED indicator light is green in normal conditions
and red during trip conditions. On initial start-up, if the light is
continuously red, the unit electrical phase may need to be
22
Download from Www.Somanuals.com. All Manuals Search And Download.
Sight Glass & Moisture
Indicator
With a suitable Relief Device installed on the Vessel, the
refrigerant is released at a controlled rate and a safe
pressure is maintained in the Vessel.
Figure 11. Direct Type Relief Valves
The sight glass/moisture indicator helps determine that a unit
has sufficient refrigerant charge and/or when the liquid line
filter drier cores need to be replaced.
Bubbles in the glass may indicate a shortage of refrigerant or
a restriction in the liquid line (i.e. plugged liquid line filter
drier). Moisture typically results from a leak in the refrigerant
system or service operations which open the refrigerant
system to the atmosphere.
Moisture is detrimental because it leads to the formation of
acids which attack components in the system. A change of
color in the indicating dial from green to either chartreuse or
yellow indicates unacceptable moisture in the system in
which case the liquid line filter drier cores need to be
changed.
Upon changing the cores, the indicating dial should return to
green within 12 hours of returning system to operation.
Figure 10. Sight Glass
After a “Direct Type” Relief Device has discharged once, it
should be replaced. The “Direct Type” Relief Device is
designed to re-close automatically at a predetermined
pressure, but reliability of the Device to reseal tightly and to
operate at the designed pressure can not be guaranteed after
discharging. Be safe and replace the Device after such an
occurrence.
Figure 12. 3-way Relief Valve
Safety Relief Devices
A refrigerant Safety Relief Device is designed to prevent
pressure in a Vessel from rising above a safe limit when
operating controls fail or when the Vessel is exposed to
excessive heat.
When a Vessel, containing liquid refrigerant, is shut off from
other parts of the system a rise in temperature will cause a
rise in pressure. If the Vessel is completely filled with liquid a
small rise in temperature will cause a rapid and excessive
rise in pressure due to the expansion of the liquid. If the
Vessel contains both liquid and vapor, which is normal for
Refrigerant Receivers, the pressure will rise according to the
temperature-pressure saturation characteristic of the
refrigerant.
If pressure builds up high enough to cause the Vessel to
rupture, large quantities of liquid refrigerant are released.
This causes a sudden reduction of pressure so that the liquid
released is vaporized almost instantly with explosive results.
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 17. Henry Relief Valve Capacity Ratings
Pounds of Air per Minute for all Refrigerants Except Ammonia R717
SIZE CONNECTION STANDARD PRESSURE SETTINGS PSIG
TYPE
CATALOG
NUMBER
526E
INLET
OUTLET
3/8 FLARE
5/8 FLARE
3/8 FLARE
1/2 FLARE
5/8 FLARE
5/8 FLARE
3/4 F.P.T.
350
10.2
28.5
11.2
18.6
18.6
28.1
41.2
41.2
74.0
129.7
400
11.6
32.4
12.7
21.1
21.1
32.0
46.8
46.8
84.2
147.5
425
12.3
34.4
13.5
22.4
22.4
33.9
49.1
49.1
89.3
156.4
450
13.0
36.3
14.3
23.7
23.7
35.8
52.5
52.5
94.4
165.4
ANGLE
3/8 M.P.T.
1/2 M.P.T.
3/8 M.P.T.
3/8 M.P.T.
1/2 M.P.T.
1/2 M.P.T.
1/2 M.P.T.
3/4 M.P.T.
1 M.P.T.
527E
5231
5231-A
5231
5232
STRAIGHT
THROUGH
5240-1/2
5242-3/4
5244-1
5246-1-1/4
3/4 F.P.T.
1 F.P.T.
1-1/4 F.P.T.
1-1/4 M.P.T.
Table 18. Discharge Piping Table
RELIEF DEVICE
MAXIMUM LENGTH OF DISCHARGE PIPE IN FEET
* FOR 400 PSIG PRESSURE SETTING
CAPACITY
LBS. AIR/MIN.
SOFT COPPER TUBE O.D.
SCHEDULE 40 PIPE
1”
3/8”
3 1/2
2 1/2
2
1/2”
19 1/4
12 1/4
9 1/2
5 1/4
4 1/4
2 1/2
2
5/8”
61
44
32
19 1/4
16
9 1/2
7
1/2”
108
75
56
33
28
18
12
9
7
4
3
2
3/4”
445
308
228
137
110
72
49
37
28
18
9
1 1/4”
1 1/2”
2”
10
12
14
18
20
25
30
35
40
50
70
80
90
125
150
371
238
165
121
93
60
30
23
2
5 1/4
3 1/2
2 1/2
366
233
119
91
257
198
156
81
7
5
3
2
2
18
72
10
37
282
196
7
26
56
For Relief Devices set at 400 psig
• Obtain the capacity at 400 psig setting.
• Locate this capacity or the nearest larger capacity in the left-hand column of the discharge piping table above and read across to obtain the
maximum lengths for each tube and pipe size.
For relief devices set at 350 psig, use the above table and multiply by .75 to determine maximum lengths.
For relief devices set at 425 psig, use the above table and multiply by 1.15 to determine maximum lengths.
For relief devices set at 450 psig, use the above table and multiply by 1.25 to determine maximum lengths.
24
Download from Www.Somanuals.com. All Manuals Search And Download.
Liquid Level Switch
Series P100 Pressure
Control
The P100 series, manufactured by Johnson Control, Inc., are
encapsulated, non adjustable, single-pole single throw, direct
mount pressure controls typically used for low or high
pressure cutouts. On the Heatcraft manufactured parallel
systems, the control is used for High Pressure cutout.
S-9400 Level Switch Series
OPTION – Not available on all systems or receivers.
Table19. Level Switch Table
CAT
NO.
VOLTAGE
RESISTIVE
RATING
CONTACTS
LIQ. PRESENT
There are two types available. Auto Reset Models and
Manual Reset Models.
S-9420
208/240
50/60 Hz
.5 Amp
N.C.
Figure 13.
CAT
NO.
REPLACEMENT REPLACEMENT
WIRE COLOR MODULE NO. SIGHT GLASS
CODE
S-9420 RED & WHITE
NO.
2-044-015
3-020-063
Figure 14.
Operation
Auto Reset Models
The S-9400 Series Level Switches manufactured by A C & R
COMPONENTS uses light reflecting from a conical glass prism as
a means of detecting the absence of a fluid at the level of the
glass cone. When no fluid covers the lower half of the cone,
infra-red light from the module reflects from the mirror-like
inner surface of the cone back to a light detector signaling the
electronic module to switch. When fluid covers the lower half
of the glass cone, the light from the module passes into the
fluid. This absence of light is detected by the module which
switches into the opposite direction. The module provides a
.06/.10 differential distance from the cone point down.
When pressurized to the selected actuation pressure setting,
the internal snap-acting disc reverses its shape and drives a
set of electrical contacts either open or closed. When the
pressure drops below the de-actuation pressure setting, the
disc snaps back to its preset position thus resetting the
electrical contacts.
Manual Reset Models
The snap-acting disc in the manual reset model opens the
electrical contacts when actuated by the pressure sensor.
Once the disc snaps, the contacts are held open until an
external force on the push button closes them. Because of
the disc’s link with the pressure sensor, the contacts cannot
be reset until the pressure drops to a predetermined level.
The latching mechanism inside the manual reset model is trip
free. The electrical contacts will cutout even if the reset
button is held fully depressed. The control can only be reset
when the pressure returns to a predetermined level.
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Low Pressure Oil System
Module Replacement
This type system is normally used for parallel compressors
and uses three basic components: Oil Separator, Oil
Reservoir, and Oil Level Regulators. The common discharge
is piped to the inlet of the oil separator and the outlet of the oil
separator is piped to the condenser. An oil return line is
brought from the oil separator to the top valve of the oil
reservoir. A vent line is installed to the suction line with a
pressure valve in line to lower the pressure in the reservoir,
making a low pressure oil system. This valve will keep the
reservoir pressure a set pressure above suction depending
on the value of the valve, either 5 or 20 psig to the oil level
regulator. Mechanical oil level regulators are rated for
pressures ranging from 5 to 90 psig differential. The bottom
valve of the oil reservoir is piped to oil level regulators
mounted on the compressor crankcases. These regulators
open to feed oil as the oil level drops and closes as the oil
level raises to the set level. In this manner, the oil level in the
compressor is kept at a constant level. Either one oil strainer
per regulator or one oil filter per separator must be used to
remove debris from the oil.
1. Disconnect power at the fuse box.
2. Remove wiring box from the retainer.
3. Remove the IRR 4000-93 Ring with an IRR P-101
or equivalent retaining ring pliers.
4. Remove the Retainer.
5. Pull out the module by the leads.
6. Install new Module.
7. Verify the voltage rating.
8. Reassemble the Retainer, Ring, and wiring.
Figure 15.
Figure 16. Low Pressure Oil System
Oil Control
A proper oil control system is essential to insure compressor
lubrication. An oil control system can be very cost effective
alternative to replacing expensive compressors due to loss of
oil. Oil traveling through the system tends to build up in the
evaporator, condenser, and vessels of a refrigeration system.
This causes a lack of oil return to the compressor until finally,
a large amount returns as a “slug” of oil.
A slug of oil down the suction line can be just as damaging to
the compressor as a slug of liquid refrigerant. This delay in
oil return requires an additional amount of oil to be added to
the system, depending on the size of the system, the piping,
the temperatures, the miscibility of the refrigerant/oil mix, and
the refrigerant velocity.
Oil Separators
There are two types of oil separator that may be used in the
Heatcraft parallel racks. One type utilizes the standard
impingement screen. This type separator works by having
the compressed mass flow enter into a large separator
chamber which lowers the velocity and then the atomized oil
droplets collect on the impingement screen surface. As the
oil droplets collect into larger particles they fall to the bottom
of the separator.
By removing oil from the discharge gas of compressors, not
only is the oil level for each compressor more accurately
controlled, the efficiency of the system is increased. Oil does
not change phase from liquid to gas in a refrigeration system
and therefore makes a very poor refrigerant. Oil also takes
up volume through the system that otherwise could be filled
with refrigerant. Additionally, oil tends to film the condenser
tubing wall lowering heat transfer and as oil and refrigerant
exits the expansion valve, the oil will foam insulating the
evaporator walls and again lowering heat transfer.
The second separator more commonly used is the coalescent
type. This type separator contains a matrix type borosilicate
coalescent filter to do the work impingement screens formerly
did. The exceptionally pure, extremely fine glass fibers
matrices excite the oil molecules to collide into one another
thus agglomerating them into bigger droplets until they are
forced to the outer drain layer of the filter. These droplets fall
to the bottom of the separator reservoir and the oil is then
returned to the compressor.
IMPORTANT: An oil control system does not
replace the need for proper system design. An oil
control system will drastically reduce the amount
of oil going through the system. Correct piping,
suction traps, and proper sizing of valves, con-
trols, and components must still be implemented
to insure the system will work properly.
26
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 21. Temprite Models
TEMPRITE MODEL
NO.
Before the oil separator is installed, an initial charge of oil
must be added to it. This initial charge of oil is the amount
that is needed to just float the needle valve float. This
amount of oil will stay in the oil separator when in operation
and will seal the needle and prevent damage to the float
mechanism. Oil Precharge is very important. Failure to
Precharge the separator sump may result in damage to the
oil return float mechanism by the turbulent hot gas bouncing
the float and causing the needle valve to leak.
OIL PRECHARGE
77 oz. / 2.2 L
922R, 923R
924R , 925R
926R, 927R
928R
109 oz. / 3.22 L
1.8 gal./ 6.7 L
3.5 gal. / 13.25 L
5.7 gal . / 21.25 L
930R
New systems from the factory have been Precharged.
Use the same type of oil that is in the compressor crankcase.
See the table below for the proper amount of oil to be
Precharged.
Figure 17. Temprite Oil System
Table 20. AC & R Models
HELICAL MODEL
NO.
OIL PRECHARGE
4 oz. / 11 cl
S-5180, S-5181
S-5182, 85, 87, 88
S-5190, 92, 94
14 oz. / 40 cl
40 oz. / 114 cl
25 oz. / 71 cl
S-5200 / S-5410 series
CONVENTIONAL
MODEL NO.
OIL PRECHARGE
12 oz. / 34 cl
30 oz. / 86 cl
S-5500 series
S-5600 series
S-1900, S-5700 series
S-5800 series
25 oz. / 71 cl
12 oz. / 34 cl
Temprite Models
Oil Level Regulators
The Temprite brand used is the coalescent filter type
separator. Because this filter is finer than a filter/drier, it will
pick up any and all effluent and dirt circulating in the system
down to 0.3 microns. These filters should be changed after
24 to 48 hours of initial run time. A second filter is supplied
with the system for this purpose. If the filter becomes dirty, it
will not function at its optimum performance level. In the
event of a compressor burnout, all the effluent will be
contained in the oil separator.
The A C & R adjustable oil regulators are designed to feed oil
between 1/4 and 5/8 sight glass levels. The regulator may
adjust beyond this range due to the actual oil pressure.
Adjustable regulators include an adjustment mechanism to
raise or lower the oil set point. The A C & R design
eliminates the need to shut the system down in order to
adjust the oil level. The oil level may be adjusted while the
system is under pressure and running. Adjust the oil level by
removing the seal cap, the locking disk (S-9130 & S-9190
series only), and rotating the adjustment clockwise to lower,
counter clockwise to raise the oil level. Replace the cap and
locking disk when done. Each full turn of the adjustment
mechanism moves the oil level approximately 1/16”. Oil
levels on these regulators are typically factory set just below
1/2 sight glass.
When the Temprite coalescent separator is used, the
separate oil reservoir is not required. The oil separator
serves the additional function as the reservoir. There is a
constant pressure valve used between the oil return outlet
and the oil level regulators to maintain a low pressure oil flow
to the regulators. This valve should be adjusted to maintain
oil pressure to the level regulators at 20 psig higher than the
highest suction pressure group. This valve can be adjusted
by removing the external cap and rotating the adjusting spring
in or out as required.
All level regulators have a operating pressure differential
range that should not be confused with its working pressure.
The operating differential is the difference of pressure
between the oil feeding into the regulator and the component
where the regulator is controlling oil level. Specifically, the
reservoir pressure minus the crankcase pressure. If the
differential pressure is too low for that regulator, insufficient
oil flow to the compressor may result. If the differential
pressure is too high, the regulator will overfill.
The valve currently used is manufactured by Parker and is a
model A7 constant pressure expansion valve with a range of
0 to 90 psig. Temprite Part No. is 67070000. An alternative
valve manufactured by Sporlan is Model ADRI - 11/4 - 0/90.
Temprite Valve Adjustment
Turn in (clockwise) to increase pressure. Turn out
(counterclockwise) to decrease pressure. Approximately 7
psi per turn. Factory set at 40 psi ±2.
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Note that there is no way to clean or repair welded oil
separators. If it is determined that the float is clogged or
otherwise malfunctioning, the entire oil separator must be
replaced.
Table 22. A C & R Model Regulators
A C & R CONNECTION OPERATION OIL LEVEL,
MODEL
NO.
SIZE
PRESSURE
DIFF, psig
5 - 30
SIGHT
GLASS
1/2
When the refrigerant and/or oil types are changed in a
system, there is the potential for leaks around o-ring seals.
Most elastomers absorb oil and refrigerant and may swell or
shrink when exposed to a new oil or refrigerant. In these
cases replace the o-rings and seals in the system as needed.
S-9010
S-9010A
S-9015
S-9090
S-9090A
S-9110
S-9120
S-9130
S-9190
3 BOLT
4 BOLT
5 - 30
1/2
3/4” NPTF F.
3 BOLT
5 - 30
1/2
5 - 90
Adjustable
Adjustable
1/2
4 BOLT
5 - 90
3 BOLT
5 - 30
Liquid Filter-Driers &
Suction Filters
3 BOLT
5 - 30
1/4 +
3 BOLT
5 - 90
Adjustable
Adjustable
3 BOLT
30 - 90
A replaceable core liquid filter/drier is supplied as standard
on all Rack units and is an option in all other parallel
systems. A Schrader type access valve is installed in the
flange plate of some models. The liquid cores are always
shipped loose for field installation. (See No. 5 of Leak
Checking, Evacuation, and Start-up section in this manual).
Troubleshooting Oil System
The oil return line should always be checked. Feeling the oil
return line and seeing how often it gets hot is the main way to
tell if the separator is working properly. It is easier if an oil
line sight glass is installed, mainly because if the oil line is hot
you don’t know if it is oil or hot gas causing it to be hot. If the
oil line cycles between hot and cold at least a few times per
hour, the separator is most likely working properly. The float
tends to open and feed a few ounces of oil at a time and shut
until the oil builds back up. If the oil return is cycling there is
no need to drain the separator to look at the float
components.
Always check the oil reservoir level during a service call. Oil
levels in the reservoir will normally vary during periods of
varying loads: compressors shutdown, hot-gas defrost, etc.
This is normal, however if the level is consistently low or high,
the oil system should be checked thoroughly.
Compressor oil levels can be deceiving. It is sometimes hard
to tell if the regulator is feeding oil or if oil is coming down the
suction line. If the reservoir has too much pressure, often
times this pressure will force oil out of the regulator and show
a low level, even though there may be excessive oil in the
compressor. Many times the best way to check the oil in the
compressor is to shut off the oil feeding to the regulator while
the compressor is operating and wait a few minutes. If oil is
pushed out of the regulator or trapped in the motor cavity on
semi-hermetic models, the compressor will overfill.
Table 23. Sporlan Valve Co.
SPORLAN
MODEL
NO. OF
CORES
DESICCANT
VOLUME
(CU IN)
48
#
CORE
PART NO.
C-489-(G)
C-969-(G)
C14411-(G)
C-19211-(G)
C-4021-(G)
C-4025-(G)
1
2
3
4
4
4
96
144
192
192
RC-4864
RC-4864-HH
RCW-48
192
“G” indicates flange plate supplied with _” FPT
#“RC__” Standard Core, “RC__HH” Burnout Core
“RCW_” High Water Capacity
The oil line sight glass is a good way to see how the
separator is working. Look for movement in the glass. If the
separator is not feeding on single or low pressure systems,
the sight glass will have little or no movement and normally
will appear empty. If the separator is feeding, the sight glass
will show a rush of oil and foam past the glass. Most of the
time, viewing this sight glass can prevent having to open the
system.
Table 24. Alco Controls
ALCO
MODEL
NO. OF
CORES
DESICCANT
VOLUME
(CU IN)
48
#
CORE
PART NO.
To check the oil level in the separator if the separator has a
drain, shut off the oil return line to prevent further feeding,
pump down the system, shut off the system, evacuate the
separator, and drain the oil from the bottom. The separator
should hold the pre-charge amount plus or minus a few
ounces during operation. By looking at the amount above or
below the pre-charge, any problem with the separator or float
can be determined.
STAS-489-T*
STAS-969-T
STAS-14411-T
STAS-19211-T
STAS-19213-T
STAS-19217-T
1
2
3
4
4
4
96
144
192
192
D-48
H-48
UK-48
W-48
192
* “T” indicates Liquid Line Service
#“D” Standard Capacity, “H” High Capacity
”UK” High Capacity, “W” Burnout Block
28
Download from Www.Somanuals.com. All Manuals Search And Download.
Suction Filter
11. Check the
system again
after
Replaceable core suction filters are supplied as standard on
all units. The flanged shell holds replaceable pleated filter
elements suitable for installation in the suction line of
refrigeration systems. In this way any contaminants left in the
system at start-up can be removed before they circulate back
to the compressor. The suction filters are shipped loose for
field installation. (See No. 3 of Leak Checking, Evacuation,
and Start-up section in this manual).
approximately 2
weeks of
operation. If the
oil is still
discolored, or
checks acid,
replace the
liquid and
suction line
filter-driers.
Compressor Motor Burnout Cleanup
Procedure
Another benefit of the suction filter is its use in cleanup of a
system after a burnout. Standard liquid cores can be
installed in the shell to aid in the cleanup of acids and other
contaminants from a motor burnout.
12. Cleanup is
complete when
the oil is clean,
odor free, and is
determined to
be acceptable
by testing for
The following procedure can be used in case of a motor
burnout.
acids or other contaminants.
1. Determine the extent of the burnout. For mild
burnout’s where contamination has not spread through
the system, it may be economical to save the
refrigerant. Normally it is economical to save the
refrigeration charge if the system has service valves.
A severe burnout exists if the oil is discolored, an acid
odor is present and contamination products are found
in the high and low side. With this condition, extreme
caution should be exercised to avoid breathing the
acid vapors and to prevent contaminated liquid from
making contact with the skin.
13. Replace the suction line filter-drier with suction line
filters cores to minimize suction line pressure drop and
to provide maximum compressor protection.
For more detailed information on burnout cleanup procedures
and recommendations, consult the RSES Service Manual,
section 91.
Sporlan Valve Company
2. Thoroughly clean and replace all system controls, such
as expansion valves, solenoids, check valves,
reversing valves, oil separators, suction accumulators,
etc. Remove all strainers and filter-driers.
Replaceable Suction Filter
The correct replacement suction filter element in Sporlan
Valve replaceable shells is Sporlan part number RFE-48-BD.
However any suitable filter that is sized to fit a 48 cu. inch
vessel will substitute.
3. Install a replacement compressor and make a
complete electrical check.
4. Make sure the suction line adjacent to the compressor
is clean. Install a liquid line filter-drier or a replaceable
cartridge designed for “cleanup” into the suction line
shell.
5. Install a burnout core in the liquid line shell.
6. If the refrigerant is removed from the system, follow
the evacuation procedure found on page 17 of this
manual.
7. Start the compressor and put the system in operation.
Record the pressure drop across the suction line filter
and keep for reference.
8. Replace the suction line filter-drier blocks if the
pressure drop becomes excessive.
9. Observe the system during the first 4 hours. Repeat
step 8 as often as required, until no further change in
pressure drop is observed.
10. After the system has been in operation for 48 hours,
check the condition of the oil for Acids. If the oil test
indicates an acid condition, replace the liquid and
suction line filter-driers.
29
Download from Www.Somanuals.com. All Manuals Search And Download.
Superior Valve Company
Replaceable Suction Filter
Table 28. Type AFD (for cleanup)
Replaceable Cartridges -
• On many parallel systems, the Superior Valve Co.
suction filter is installed.
Shell
No.
Filter
Core
Cartridge
OD (in)
1 - 29/32
2 - 3/4
Filter Area
Area (in2)
66
BTAS-2
BTAS-3
BTAS-4
BTAS-5
A2F-D
A2F-D
A2F-D
A2F-D
Table 25. Type F Filter
Replaceable Cartridges
115
3 - 3/4
189
4 - 5/16
270
Shell
No.
Catalog
No.
IBCA
No.
Cartridge
OD (in)
1 - 23/32
2 - 5/8
Filter
Area (in2)
66
2CFA
3CFA
4CFA
5CFA
F25A
F35A
F45A
F55A
51071
51072
51073
51074
115
Head Pressure Control
3 - 17/32
4 - 1/16
189
In a system with variable pressure control the receiver
pressure is maintained at the desired pressure by supplying
discharge gas to it through an adjustable outlet regulator.
Further power savings may be realized by directing only the
hot gas to the top of the receiver to minimize the mixing of
cold liquid and hot gas. As a result subcooled liquid is fed to
the evaporators resulting in increased refrigeration effect and
efficiency. Also, the amount of hot gas, that would otherwise
condense to wary liquid, is reduced and a lower cost, smaller
regulator can be used. In general, only one third of bypass is
needed compared to mixing the gas and liquid entering the
receiver.
270
Table 26. Type DF (for cleanup)
Replaceable Cartridges
Shell No. Catalog
IBCA
No.
Cartridge
OD (in)
1 - 23/32
2 - 5/8
Filter
Area (in2)
66
No.
No.
2CFA
3CFA
4CFA
5CFA
DF25A
DF35A
DF45A
DF55A
51053
51059
51060
51061
115
3 - 17/32
4 - 1/16
189
270
Valve Functions
Alco Controls
Referring to the Figure above, Valve A is an Inlet Pressure
Regulator in the liquid drain line from the condenser, and
senses the condenser pressure. The regulator closes as the
condenser pressure drops below the set point, thus back-
flooding the condenser and reducing the inside surface area
available for condensing.
Alco Suction Filter
Comparable to the Superior suction filters and
interchangeable cores.
Table 27. Type AF Filter
Valve B is and Outlet Pressure Regulator in the bypass line
from compressor discharge to the condenser liquid drain line.
This valve senses the receiver pressure and opens when this
pressure drops below the set point, thus maintaining the
receiver pressure.
Replaceable Cartridges -
Shell
No.
Filter
Core
A2F
A3F
A4F
A5F
Cartridge
OD (in)
1 - 29/32
2 - 3/4
Filter Area
Area (in2)
66
BTAS-2
BTAS-3
BTAS-4
BTAS-5
Valve C is an In-line Check Valve in the liquid drain line to
prevent higher pressure from backing up into the condenser
during low ambient conditions when the compressor is idle.
115
3 - 3/4
189
4 - 5/16
270
30
Download from Www.Somanuals.com. All Manuals Search And Download.
Liquid Drain Control Method
This method is ideal for large capacity systems since a
smaller regulator is required for liquid line than for discharge
line.
5. Final adjustments should be made when the outdoor
ambient is below 65°F. Ideally the ambient should be
near minimum system outdoor temperature to allow the
system pressures to drop below the regulator pressure
settings. Before adjusting make sure that all manual
opening stems on the regulators are set for automatic
operation. It may be necessary to temporarily deactivate
the low pressure cut out controls to keep the compressors
running during adjustment.
During warm ambient temperature conditions valves A and C
will be open and Valve B will be closed. When the ambient
temperature at the condenser drops, the condenser pressure
will tend to become lower. As this pressure is reduced, when
the pressure becomes as low as its setting, Valve A will begin
to close, thus causing the refrigerant to back up inside the
condenser tubes, reducing the condensing surface and
allowing the pressure to be maintained. As Valve A closes,
the receiver pressure may be reduced by the cold entering
liquid to a level below the setting of Valve B, which will begin
to open to bypass sufficient gas to maintain the receiver
pressure at the set point of Valve B. Check valve C will
prevent the high pressure from backing up to the condenser
when the receiver pressure is higher than the condenser
pressure, as would be the case during shutdown in a system
with a warm receiver.
6. The regulators should be preset using information in
Table 29.
7. When the valves are adjusted with the system operating,
enough time must be allowed for the system to stabilize.
Check the sight glass to make sure sufficient liquid is
supplied to the evaporators.
8. Turn the condenser fans off to allow the discharge
pressure to build up. The regulator A should be adjusted
to open when the pressure reaches the desired control
point. Listen for flow through regulator A while watching
the pressure gauge.
When the condenser pressure builds up to the setting of
Valve A, it will open allowing liquid to flow to the receiver.
To determine the final setting of regulator B, allow the
condenser fans to run long enough to subcool the liquid
supplied to the receiver. Adjust the regulator until the desired
receiver pressure is obtained. Flow through the valve can be
determined by listening at the valve for gas flow or by feeling
the outlet for change in temperature. The setting of regulator
B should be at least 10 psi lower than the setting of regulator
A.
To describe it again, during cold ambient temperature
conditions this liquid will be considerably subcooled and will
tend to lower the receiver pressure. Valve B will sense the
drop in pressure and open to admit hot gas into the drain line,
thus pressurizing and warming the liquid and maintaining the
receiver pressure.
Recommended Valve Settings
Regulators ordered for a Condenser Pressure Control system
for use with common refrigerants will be furnished with the
ranges and factory settings shown in Table 29 below. Turning
the adjusting stem in (clockwise) will raise the set point;
turning the stem out (counterclockwise) will lower the set
point. See Table 29 below for ranges and amount of
pressure change per turn.
Hot Gas Bypass Regulator
Adjustment
Discharge Bypass Valves (DVB) respond to changes in
downstream or suction pressure. When the evaporating
pressure is above the valve setting, the valve remains closed.
As the suction pressure drops below the valve setting, the
valve responds and begins to open. as with all modulating
type valves, the amount of opening is proportional to the
change in the variable being controlled - in this case the
suction pressure. As the suction pressure continues to drop,
the valve continues to open farther until the limit of the valve
stoke is reached.
Table 29. Pressure Range, Set point & Change per Turn
Factory
Valve
Type
A4A
ARA0
A7A
Range
Set Point
psig
Change Per Turn
psig
psig kg/cm2
75 to 5.2 to
kg/cm2
kg/cm2
D
D
B
140
120
120
9.8
53
3.7
280
75 to 5.3 to
280 19.7
19.7
On refrigeration systems discharge bypass valves are used to
prevent the suction pressure from going below the minimum
value determined by the job requirements.
A7A1
A72
8.4
8.4
75
25
5.3
1.8
80 to 5.6 to
220 15.5
Sporlan Valve Company
Valve Setting and Adjustment
A9
A complete discussion on valve settings is given in Sporlan
Application Bulletin 90-40. The fully adjustable models
ADRS(E)-2, ADRP(E)-3, and ADRH(E)-6 are available with
two adjustment ranges - 0/30 and 0/80 psig. The standard
factory settings for these are 20 and 60 psig, respectively.
The ADRI(E)-1-1/4 is available with a 0/55 psig range and the
standard factory setting is 28 psig.
Field Adjustment
Before final field adjustment of regulators for Condenser
Pressure Control, the following should be done:
1. Install gauges to read compressor discharge, condenser
and receiver pressures.
To adjust these valves, remove the cap an turn the
2. Fully charge the system.
adjustment nut with a 5/16” hex wrench for fully adjustable
models ADRS(E)-2, ADRP(E)-3, and ADRH(E)-6. The
ADRI(E)-1-1/4 model has a 3/8” adjustment screw on top of
the adjustment housing. A clockwise rotation increases the
setting and a counterclockwise rotation decreases the setting.
3. Have other controls and components functioning
properly.
4. Have the system as fully loaded as possible.
31
Download from Www.Somanuals.com. All Manuals Search And Download.
Adjusting these valves can be complicated because the load
must be varied during the setting procedure and it is difficult
to determine exactly when the bypass valve opens unless a
pressure gauge can be located at the valve outlet.
Table 30. Control settings for R404A (507)
Air Temp
°F
EPR
psig
69
LP C/I
psig
72
LP C/O
psig
64
38-42
34-38
34-36
33-35
28-32
24-28
-10-/0
-10-/-5
-15/-10
-20/-15
Therefore, sufficient load must be available in some form to
raise the suction pressure above the desired valve setting.
Once this is accomplished, the load can be slowly decreased
until the DBV opens (a hissing sound and/or an
accompanying pressure rise at the outlet connection will
indicate that the bypass valve has opened).
64
66
57
60
62
55
59
61
53
55
58
50
48
50
35
21
24
15
Alco Controls
Valve Setting and Adjustment
20
22
14
15
17
14
CPHE and DGRE regulators are commonly used to prevent
the suction pressure from falling below a predetermined set
point. Complete information about these valves can be found
in ALCO CONTROLS Catalog 24-D.
12
15
8
Table 31. Control settings for R22
The first step after installation is to determine the set point for
the minimum suction pressure allowable for the application.
The following procedure should be followed.
Air Temp
°F
EPR
psig
54
50
47
45
43
36
13
11
8
LP C/I
psig
57
LP C/O
psig
50
43
41
40
38
25
8
38-42
34-38
34-36
33-35
28-32
24-28
-10-/0
-10-/-5
-15/-10
-20/-15
1. Start the system and determine if it is operating properly:
Install a gauge on the compressor suction line and
measure the suction pressure after the system has
stabilized. To make certain that hot gas is not being
bypassed, listen to the main regulator flow or feel the
outlet piping. If the piping is warm, this would indicate
hot gas is flowing.
48
50
47
45
38
17
14
7
2. Stop the flow of hot gas by de-energizing the hot gas
solenoid valve or by turning the power assembly
adjusting stem full COUNTERCLOCKWISE.
10
5
5
8
2
3. Reduce the evaporator load until the suction pressure
lowers to the point at which bypass is desired.
4. If the hot gas solenoid was de-energized to stop hot gas
flow, make sure it is now energized.
Low Pressure Switch Setting for RMCC
Some systems use a form of electronic control such as CPC’s
RMCC solid state controller for Rack operation. On these
systems, there is one mechanical low pressure control for
each suction group that may be on the rack. This control is
for backup emergency control in the event of a board or other
electronic component failure. This low pressure control must
be set for the minimum suction pressure that the rack would
be expected to operate at to keep from interfering with the
RMCC control.
5. Turn the power assembly adjusting stem in a CLOCKWISE
direction until bypass occurs and suction pressure does
not fall below the predetermined set point. A CLOCKWISE
turn of the adjusting stem will increase the pressure
setting; a COUNTERCLOCKWISE turn will decrease it.
Standard pressure pilot is adjustable from 0 to 80 psig,
with one complete turn equal to approximately 4 psi
change. Adjustments should be made in small
increments, allowing for the system to stabilize after each
turn.
Example, for a low temperature suction group, this control
should be set for 0 - 2 psig cutout and approximately 10 psig
cutin. A medium temperature suction group can be set
higher. In the event that this control is needed to actually
control the compressors, set the cutin and cutout for the
suction pressure that you want the compressors to operate to
maintain case or box temperatures.
6. Vary the evaporator load to test at various conditions that
the suction pressure does not fall below the
predetermined set point.
7. Replace the seal cap on the adjusting stem.
NOTE: This low pressure control will gener-
ally be mounted on a compressor with
the braided stainless steel tubing
connecting to the appropriate suction
group header.
Control Settings
The following tables are for use when mechanical low
pressure switches are incorporated for rack pressure control.
All control settings are approximate and should be adjusted
for actual field conditions and equipment. All settings are
based on 10°F T.D. evaporator.
32
Download from Www.Somanuals.com. All Manuals Search And Download.
General Maintenance Schedule
(Service/Maintenance should be performed only by a
qualified / certified refrigeration service technician.)
Weekly
Quarterly
• Check refrigerant charge using the liquid line sight glass.
With unit in stable operation, record all operating conditions:
• Check compressor oil level.
• Suction / discharge / liquid refrigerant pressure(s) and
temperature(s)
• Check compressor crankcase heater operation.
• Check main power and control voltage
• Check appearance of area around the unit.
• Check system pressures
• System superheat, liquid subcooling, ambient
temperature
• Compressor amperage
• Test all operating and safety controls.
Monthly
• Check the refrigerant system for leaks.
Annually
• Check suction filters and liquid line filter driers.
• Obtain oil sample for analysis. Change oil if required.
• Check all flanged connection bolts, fittings and line
clamps for tightness.
• Clean condenser coil.
• Straighten condenser fins as required.
• Change liquid line filter drier and suction filter cores.
• Inspect condenser fan blades and motor mounts for
cracks, loose set screws or mounting bolts.
• Tighten all electrical connections.
Note: The above information is provided only
as a general guideline to aid servicing
personnel and equipment owners in
maintaining equipment. Due to vari-
ables in the actual equipment
• Check operation and condition of contacts on
compressor / fan motor contactors. Check appearance of
control panel interior.
• Check appearance of exterior conduit / junction boxes.
• Check appearance of insulation.
application, operating conditions, and
environment recommended service
intervals may vary.
• Check operation of auxiliary equipment.
33
Download from Www.Somanuals.com. All Manuals Search And Download.
SERVICE DIAGNOSIS CHART
Symptom
Cause
Remedy
Compressor
does not run
1.
2.
3.
4.
Motor Line open.
1. Close starter or disconnect switch
2. Replace fuse
Fuse blown
Tripped overload
Control contacts dirty or jammed in
open position
3. See electrical section
4. Repair or replace
5.
6.
Piston seized
5. Remove motor-compressor head, look for
broken valve and jammed parts.
6. Repair or replace.
Frozen compressor or motor bearings
Unit short
cycles
1.
2.
3.
Control differential set too close
Discharge valve leaking
Motor compressor ???
1. Widen differential
2. Replace valve plate
3. Check for high head pressure, tight bearings,
seized pistons, clogged air-cooled condenser.
4. Repair leak and recharge.
4.
5.
6.
Refrigerant shortage
Refrigerant over charge
Cycling on high pres. cutout
5. Remove some refrigerant.
6. Check condenser / or non condensable in system
Compressor
will not start -
Hums
1.
2.
Improperly wired
Low voltage
1. Check wiring against diagram
2. Check main line voltage - determine location
of voltage drop
intermittently
3.
4.
Relay contacts not closing
Open circuit in start-winding
3. Check my operating manually. Replace relay
if defective
4. Check stator leads. If leads are all right,
replace stator.
5.
6.
7.
Stator winding grounded
High discharge pressure
Tight compressor
5. Check stator. If leads are all right, replace stator.
6. Eliminate cause of excessive pressure
7. Check oil level. Correct binding.
Unit operates
long or
1.
2.
3.
4.
5.
6.
Control contacts sticking in closed position.
Insufficient refrigerant in system
Dirty condenser.
1. Clean points or replace control.
2. Check for leaks. Repair and add charge
3. Clean condenser
continuously
Air or non-condensables in system
Compressor inefficient
4. Purge high point in system
5. Check valves and pistons
Improper wiring
6. Check wiring and correct if necessary
Fixture
1.
2.
3.
4.
5.
6.
7.
8.
9.
Insufficient refrigerant in system
Control set too high
1. Check for leaks. Repair and add charge
2. Reset control
temperature
too high
Control wiring loose
3. Check wiring to control
4. Clean or replace
Expansion valve or strainer plugged
Compressor inefficient
Expansion valve set too high
Iced or dirty coil
5. Check valves and pistons
6. Lower setting
7. Defrost or clean coil
Unit too small
8. Add unit or replace
Clogged or small refrigerant lines
9. Clear line or increase line size
10. Remove excessive oil, check refrigerant charge
10. Oil logged in system
High
1.
2.
3.
4.
5.
6.
Refrigerant overcharge
Non-condensables in system
Dirty condenser coil
1. Remove the excess
2. Remove the non-condensables
3. Clean
discharge
pressure
High side restriction
4. Check all valves or remove restriction
5. Adjust controls
Head pressure control setting
Fan not running
6. Check electrical circuit
34
Download from Www.Somanuals.com. All Manuals Search And Download.
Symptom
Cause
Remedy
Low
1.
2.
3.
Insufficient refrigerant in system
Faulty condenser temp. regulation
Compressor suction or discharge valve
inefficiencies.
1. Check for leaks. Repair and add charge
2. Check condenser control operation
3. Clean or replace leaky valve plates
discharge
pressure
4.
5.
Low suction pressure
4. See corrective steps for low suction pressure
5. Adjust valve or install a head pressure
control valve.
Head pressure control valve set wrong
or no head pressure control valve
High suction
pressure
1.
2.
Excessive load
1. Reduce load or add additional equipment
2. Check remote bulb. Regulate superheat.
Expansion valve overfeeding
Low suction
pressure
1.
2.
3.
4.
Lack of refrigerant
1. Check for leaks. Repair and add charge
2. Defrost or clean coil
Evaporator dirty or iced.
Clogged liquid line filter drier
Clogged suction line or compressor
suction strainer
3. Replace cartridge(s)
4. Clean strainer or replace filters
5.
6.
Expansion valve malfunctioning
Condensing temperature too low
5. Check and reset for proper superheat
6. Check means for regulating
condensing temperature
7.
Improper TXV
7. Check for proper sizing
Little or No
oil pressure
1.
2.
Clogged suction oil strainer
Excessive liquid in crankcase
1. Clean
2. Check crankcase heater. Reset TXV for
higher superheat. Check liquid line solenoid
valve for proper operation.
3. Replace
3.
4.
5.
Low oil pressure safety switch defective
Worn oil pump
4. Replace
Oil pump reversing gear stuck in
the wrong position.
5. Reverse direction of compressor rotation
6.
7.
8.
9.
Low oil level
6. Determine where the oil is or add oil.
7. Replace compressor
Worn bearings
Loose fitting on oil lines
Pump house gasket leaks.
8. Check and tighten fittings
9. Replace gasket
Compressor
loses oil
1.
2.
3.
4.
Lack of refrigerant
1. Check for leaks. Repair and add charge
2. Replace compressor
Excessive compression ring blowby
Refrigerant floods back
Improper piping or traps
3. Maintain proper superheat at compressor
4. correct piping
Compressor
thermal
1.
Operating beyond design limits
1. Add facilities so that conditions are within
allowable limits.
protector
2.
3.
4.
5.
Discharge valve partially shut
Blown valve plate gasket
Dirty condenser coil
2. Open valve
switch open
3. Replace gasket
4. Clean coil
Overcharged system
5. Reduce charge
35
Download from Www.Somanuals.com. All Manuals Search And Download.
SERVICE RECORD
A permanent data sheet should be prepared on each installation, with a copy for the owner and the original for the installing
contractor’s files. If another firm is to handle service and maintenance, additional copies should be prepared as necessary.
System Reference Data
The following information should be filled out and signed by the Refrigeration Installation Contractor.
Date System Installed:
Installer and Address:
_______________________
Date Started:
_______________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
__________________________________________________________________
Job Name / Location:
Compressor Unit Model: __________________________________________________________________
Compressor Unit Serial No.: ___________________________________________________________
_______________________ Phase: _______________________
_______________________ Serial No.: ________________________
Group __________________ Group _________________
__________________ / __________________ Group: __________________
Electrical :
Condenser Model:
Design SST: Group __________________
Compressor Model / Serial No.
Compressor Model / Serial No.
Compressor Model / Serial No.
Compressor Model / Serial No.
Compressor Model / Serial No.
Compressor Model / Serial No.
__________________ / __________________
__________________ / __________________
__________________ / __________________
__________________ / __________________
__________________ / __________________
Group: __________________
Group: __________________
Group: __________________
Group: __________________
Group: __________________
Evacuation: # Times __________________
Final Micron: __________________
System Suction P (Group ____): ________________________
System Suction P (Group ____): ________________________
System Suction P (Group ____): ________________________
Ambient: ________________________
System Discharge P: ________________________
System Discharge P: ________________________
System Discharge P: ________________________
Superheat at Compressors: __________________________________________________________________________
Since product improvement is a continuing effort at Heatcraft, we reserve the right to make changes in specifications without notice.
HEATCRAFT INC. REFRIGERATION PRODUCTS DIVISION
2175 WEST PARK PLACE BLVD., STONE MOUNTAIN, GA 30087 • 770-465-5600 • FAX 770-465-6016
WWW.HEATCRAFTRPD.COM • E-MAIL: HRPD.FEEDBACK@HEATCRAFT.COM
Download from Www.Somanuals.com. All Manuals Search And Download.
|