Hearth and Home Technologies Indoor Fireplace Cinch Pipe Termination Cap System User Manual

Installation  
Instructions  
TM  
Models:  
Cinch Pipe & Termination Cap System  
These instructions are replacing VP (for Heatilator) and DV (for Heat-N-Glo) pipe assembly  
instructions. See the appliance installation instructions for configuration of vent assembly  
and clearances to pipe.  
If you need assistance during installation, contact your local dealer or the Technical Serices Dept., Hearth & Home Technologies  
Inc., phone 1-800-927-6841 or 1-888-427-3973.  
If DVP-AD adapters are used off the top of the appliance, the termination height will be raised by 2-3/4 in. overall  
height.  
CAUTION  
Sharp Edges  
Wear protective gloves and safety glasses  
during installation.  
WARNING  
Hearth & Home Technologies disclaims any  
responsibility for, and the warranty will be  
voided by, the following actions:  
Installation and use of any damaged vent  
system component.  
Modificatoin of the vent system.  
Installation other than as instructed by  
Hearth & Home Technologies.  
Installation and/or use of any component  
part not approved by Hearth & Home  
Technologies.  
Any such action may cause a fire hazard.  
WARNING  
Do not mix pipe, fittings or joining  
methods from different manufacturers.  
Note: An arrow () found in the text signifies change in content.  
Hearth & Home Technologies Inc. • Cinch Pipe & Term Caps • 4033-900 Rev K • 05/05  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
DVP-TRAPFL  
DVP-TRAP1 or DVP-TRAP2 termination  
cap rain flashing  
DVP-TRAPFL  
Flashing  
DVP-TRAP1  
DVP-TRAP2  
Termination Cap  
COOL ADD  
DRC-RADIUS  
Cap shield  
Cap shield  
Components  
Description  
DRC-RADIUS  
Cap Shield  
COOL-ADDM  
DVP-TV  
DVP45  
Cap Shield - pack of six  
Vertical Termination Cap  
45° Elbow  
DVP90ST  
RF6M  
90° Elbow  
Roof Flashing (vertical termination for 0/12 to 6/12 pitch) - pack of four  
Steep Pitch Roof Flashing (for 7/12 to 12/12 pitch) - pack of six  
4 in. length Vent Pipe  
RF12M  
DVP4  
DVP6  
6 in. length Vent Pipe  
DVP12  
12 in. length Vent Pipe  
DVP24  
24 in. length Vent Pipe  
DVP36  
36 in. length Vent Pipe  
DVP48  
48 in. length Vent Pipe  
DVP6A  
3 in. - 6 in. Slip Section Vent Pipe (to be used with another piece of pipe)  
3 in. - 12 in. Slip Section Vent Pipe (to be used with another piece of pipe)  
12 in. Vent Pipe - non-unitized (can be cut to length)  
24 in. Vent Pipe - non-unitized (can be cut to length)  
Vent Support  
DVP12A  
DVP12MI  
DVP24MI  
DVP-HVS  
DVP-WS  
DVP-FS  
DVP-TRAP1  
DVP-TRAP2  
DVP-TB1  
DVP-TRAPK1  
DVP-TRAPK2  
DVP-HSM  
BEK  
Wall Shield to ensure horizontal clearances  
Firestop Spacer  
Horizontal Termination Cap with 1-3/4 in. telescoping flue and wall shield with heat shield  
Horizontal Termination Cap with 4 in. telescoping flue and wall shield with heat shield  
Basement Horizontal Termination Cap  
Top Vent Horizontal Kit with DVP-TRAP1 Termination Cap, wall shield with heat shield, and 90° elbow  
Top Vent Horizontal Kit with DVP-TRAP2 Termination Cap, wall shield with heat shield, and 90° elbow  
Extended Heat Shield  
Brick Extension Kit  
DVP-AS  
Attic Insulation Shield  
Hearth & Home Technologies Inc. • Cinch Pipe & Term Caps • 4033-900 Rev K • 05/05  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Vent depth is measured from the back of the appliance to the outer edge of the exterior wall. See Table 1 and Figure 1.  
TRAP CAP SPECIFICATION CHART  
DVP-TRAPK1  
Top Vent  
Depth  
DVP-TRAP1  
Rear Vent  
Depth  
DVP-TRAPK2  
Top Vent  
Depth  
DVP-TRAP2  
Rear Vent  
Depth  
Appliance  
Novus  
NXT  
Caliber  
Maxus  
GNTC50  
Designer*  
Titan  
4-1/2 in. to 6-1/4 in.  
4-1/8 in. to 5-7/8 in.  
4-1/8 in. to 5-7/8 in.  
4-1/2 in. to 6-1/4 in.  
5 in. to 6-3/4 in.  
3-1/2 in. to 4-3/4 in.  
4-5/8 in. to 6-3/8 in.  
3-5/8 in. to 5-3/8 in.  
4-1/8 in. to 5-7/8 in.  
4-7/8 in. to 6-5/8 in.  
5-3/4 in. to 7-1/2 in.  
N/A  
3-1/8 in. to 4-7/8 in.  
3-1/8 in. to 4-7/8 in.  
N/A  
7 in. to 11 in.  
6-1/2 in. to 10-1/2 in.  
6-1/2 in. to 10-1/2 in.  
6-7/8 in. to 10-7/8 in.  
7-3/8 in. to 11-3/8 in.  
6-3/8 in. to 10-3/8 in.  
6 in. to 10 in.  
5-1/4 in. to 9-1/4 in.  
5-1/4 in. to 9-1/4 in.  
6 in. to 10 in.  
5-1/2 in. to 9-1/2 in.  
7-1/4 in. to 11-1/4 in.  
6-1/4 in. to 10-1/4 in.  
6-3/4 in. to 10-3/4 in.  
7-3/8 in. to 11-3/8 in.  
8-1/8 in. to 12-1/8 in.  
N/A  
5-5/8 in. to 9-5/8 in.  
5-5/8 in. to 9-5/8 in.  
N/A  
4 in. to 5-3/4 in.  
3-1/2 in. to 5-1/4 in.  
2-3/4 in. to 4-1/2 in.  
2-3/4 in. to 4-1/2 in.  
3-1/2 in. to 5-1/4 in.  
7-1/2 in. to 9-1/4 in.  
4-1/2 in. to 6-1/4 in.  
N/A  
6000  
8000  
Olympian  
Multisided  
Gem  
SL units  
ICON  
3-1/8 in. to 4-7/8 in.  
N/A  
3-1/8 in. to 4-7/8 in.  
N/A  
10 in. to 14 in.  
7 in. to 11 in.  
5-5/8 in. to 9-5/8 in.  
N/A  
5-5/8 in. to 9-5/8 in.  
N/A  
N/A  
3-1/2 in. to 5-1/4 in.  
4 in. to 5-3/4 in.  
6-1/2 in. to 10-1/2 in.  
6-3/4 in. to 7-3/4 in.  
GDST5244I**  
N/A  
N/A  
* Top vented appliance - Designer needs a DVP12 after the elbow.  
** GDST5244I requires a DVP12 and DVP6 after the elbow.  
Table 1  
Figure 1 - Measuring Required Vent Depth  
4
Hearth & Home Technologies Inc. • Cinch Pipe & Term Caps • 4033-900 Rev K • 05/05  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing Vent Pipe  
2
Note: Heat shields MUST overlap by 1-1/2 in. min. for rear  
Note: For termination cap installations only, go directly to Sec-  
vented appliances.  
tion E.  
B. Penetrating a Wall  
A. Clearances for the Vent Sections  
Wherever a combustible wall is penetrated, the hole must  
be framed with an interior wall shield (DVP-WS) as shown in  
Figures 2.3-2.4. This shield maintains minimum clearances  
and restricts cold air infiltration. If the wall being penetrated is  
of noncombustible materials (material which will not ignite or  
burn, or has a UL fire rating of zero), a 9 in. diameter hole is  
acceptable. Whenever a wall is penetrated the wall shield is only  
required on one side and no heat shield is necessary. If your  
local inspector requires the wall shield on both sides, then both  
wall shields must have a heat shield attached to them.  
Top Vented Direct Vent Appliances  
For all top vented, direct vent appliances, clearances to  
combustible materials from the venting system need to  
be maintained as shown in Figure 2.1.  
Rear Vented Direct Vent Appliances  
See Figure 2.2.  
Note: Refer to the appliance installation instructions for al-  
lowed vent lengths and configurations.  
Figure 2.3 Exterior Wall Hole  
Figure 2.1 Horizontal Venting Clearances to Combustible Materi-  
als - Top Vent  
Note: Heat shields  
MUST overlap by a  
minimum of  
1-1/2 in. (38 mm).  
3 in. (76 mm)  
Heat  
Shield  
top clearance  
Figure 2.4 Interior Wall Shield  
Heat  
Shield  
WARNING  
Fire Risk  
Explosion Risk  
1 in. (25 mm)  
Wall  
Shield  
clearance  
Maintain vent clearance to combustibles as  
specified.  
bottom & sides  
Do not pack air space with insulation or  
other materials.  
WALL  
Failure to keep insulation or other materials  
away from vent pipe may cause fire.  
Figure 2.2 Horizontal Venting Clearances to Combustible Materi-  
als - Rear Vent  
Hearth & Home Technologies Inc. • Cinch Pipe & Term Caps • 4033-900 Rev K • 05/05  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
C. Assemble Vent Sections  
WARNING  
Fire Risk  
Exhaust Fumes Risk  
Overlap pipe slip sections at least  
1-1/2 inches.  
Use pilot holes for screws.  
Screws must not exceed one inch long.  
Pipe may separate if not properly  
joined.  
Figure 2.5 Lances  
Attaching Vent to the Firebox Assembly  
To attach the first pipe section to the collars, slide the male  
end of the inner vent of the pipe section over the inner collar  
on the firebox assembly. At the same time, slide the outer  
flue over the outer collar on the appliance. Push the pipe  
section into the appliance collar until all the lances (see Fig-  
ure 2.5) have snapped in place. Tug slightly on the section  
to confirm it has completely locked into place.  
A
A
Assemble Pipe Sections  
Insert the inner flue of section A into the flared inner flue of  
section B.  
B
Start the outer flue of section A over the outer flue of section  
B (see Figure 2.6).  
B
Note: The end of the pipe sections with the lances/tabs on  
it will face towards the appliance.  
Figure 2.7 Snapped  
Figure 2.6 Inner/Outer  
Once both inner and outer flues are started, press section  
A onto section B firmly until all lances have snapped into  
place. Check to make sure they have snapped together (see  
Figure 2.7) and the seams are not aligned (see Figure 2.8).  
Tug slightly on section A to confirm it has completely locked  
into place.  
Make sure the seams are not aligned to prevent unintentional  
disconnection.  
For 90° and 45° elbows that are changing the vent direction  
from horizontal to vertical, one screw minimum should be  
put in the outer flue at the horizontal elbow joint to prevent  
the elbow from rotating.  
CORRECT  
Figure 2.8 Seams  
INCORRECT  
6
Hearth & Home Technologies Inc. • Cinch Pipe & Term Caps • 4033-900 Rev K • 05/05  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Assemble Minimum Installation (MI) Sections  
MI sections are non-unitized so that they can be cut to a  
specific length. Cut these sections to length from the non-  
expanded end (see Figure 2.9).  
They can then be attached by first connecting the expanded  
end of the MI inner flue with the inner pipe from the adjacent  
pipe section and securing with three screws. The expanded  
portion of the MI inner flue must overlap completely with the  
unexpanded end of the adjacent pipe section.  
The outer flue can then be inserted into the adjacent outer  
flue expanded end and attached to the next pipe section with  
three screws. The other end of the MI pipe section can then  
be attached by fitting another pipe section to it and snapping  
it together, as normal.  
Figure 2.9 MI Sections  
Assemble Slip Sections  
The outer flue of the slip section should slide over the outer  
flue of the pipe section and into (inner flue) the last pipe sec-  
tion (see Figure 2.10) .  
Slide together to the desired length, making sure that a  
1-1/2 in. outer flue overlap is maintained between the pipe  
section and slip section.  
The pipe and slip section need to be secured by driving two  
screws through the overlapping portions of the outer flues  
using the pilot holes (see Figure 2.11).  
Figure 2.10 Slip Section Pilot Holes  
This will secure the slip section to the desired length and  
prevent it from separating. The slip section can then be at-  
tached to the next pipe section.  
If the slip section is too long, the inner and outer flues of the  
slip section can be cut to the desired length.  
Figure 2.11 Screws into Slip Section  
Hearth & Home Technologies Inc. • Cinch Pipe & Term Caps • 4033-900 Rev K • 05/05  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Secure the Vent Sections  
Vertical sections of pipe must be supported every 8 ft after  
the 25 ft maximum unsupported rise. The vent support or  
plumber’s strap (spaced 120° apart) may be used to do this  
(see Figures 2.12 and 2.13).  
Horizontal sections of vent must be supported every 5 ft with  
a vent support or plumber’s strap.  
D. Disassemble Vent Sections  
To disassemble any two pieces of pipe, rotate either section  
(see Figure 2.14), so that the seams on both pipe sections  
are aligned (see Figure 2.15). They can then be carefully  
pulled apart.  
Figure 2.12 Securing Vertical Pipe Sections  
WARNING  
Fire Risk  
Explosion Risk  
Asphyxiation Risk  
Use vent run supports per installation  
instructions.  
Connect vent sections per installation  
instructions  
Maintain all clearances to combustibles.  
Do NOT allow vent to sag below  
connection point to appliance.  
Maintain specified slope (if required).  
Figure 2.13 Securing Horizontal Pipe Sections  
Improper support may allow vent to sag or  
separate.  
Figure 2.14 Rotate Seams for Disassembly  
Figure 2.15 Align and Disassembly Vent Sections  
8
Hearth & Home Technologies Inc. • Cinch Pipe & Term Caps • 4033-900 Rev K • 05/05  
Download from Www.Somanuals.com. All Manuals Search And Download.  
E. Install the Heat Shield and Horizontal Termination Cap  
on the extended heat shield should rest on the top of the vent  
(pipe section) to properly space it from the pipe section.  
WARNING  
A 1-1/2 in. minimum overlap MUST be maintained on  
the telescoping flue section of the cap.  
Install the Horizontal Termination Cap  
Vent termination must not be recessed in the wall. Siding  
may be brought to the edge of the cap base.  
Caulk the outside edges of the cap.  
WARNING  
Fire Risk  
Exhaust Fumes Risk  
Impaired performance of appliance.  
When installing a horizontal termination cap, follow the cap  
location guidelines as prescribed by current ANSI Z223.1  
and CAN/CGA-B149 installation codes.  
Overlap pipe slip sections at least 2 in.  
Use pilot holes for screws.  
Screws must not exceed 1 in. long.  
Pipe may separate if not properly  
joined.  
WARNING  
Burn Risk  
Local codes may require installation of a  
cap shield to prevent anything or anyone  
from touching the hot cap.  
Heat Shield Requirements for Horizontal Termination  
For all horizontally vented appliances, a heat shield MUST  
be placed 1 in. above the top of the vent between the wall  
shield and the base of the termination cap.  
Rear Vent  
Heat Shield  
1-1/2 in. (38 mm) min.  
overlap  
Heat Shield or  
Extended  
Heat Shield  
There are two sections of the heat shield. One section at-  
taches to the wall shield with two screws. The remaining  
section is attached to the cap in the same manner. See  
Figure 2.16.  
Wall Shield  
If the wall thickness does not allow the required 1-1/2 in.  
heat shield overlap, an extended heat shield must be used.  
The extended heat shield will need to be cut to the thickness  
of the wall and be attached to the wall shield. The small leg  
Inner Vent  
Outer Vent  
INTERIOR  
EXTERIOR  
SHEATHING  
Figure 2.16 Venting through the Wall  
WARNING  
Do NOT connect a pipe section to a termination cap  
without using the telescoping flue section found on the  
termination cap.  
Note: Where required, an exterior wall flashing is available.  
When penetrating a brick wall, a brick extension kit is  
available for framing the brick.  
Hearth & Home Technologies Inc. • Cinch Pipe & Term Caps • 4033-900 Rev K • 05/05  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
F. Vertical Penetration Framing  
WARNING  
Fire Risk  
Keep loose materials or blown insulation  
from touching the vent pipe.  
National building codes recommend using  
attic shield to keep loose materials/blown  
insulation from contacting vent.  
Hearth & Home Technologies requires  
the use of an attic shield.  
Attic Above  
10 in. (254 mm)  
Install the Firestop Spacer  
Frame an opening 10 in. by 10 in. whenever the vent  
system penetrates a ceiling/floor (see Figure 2.17).  
Frame the area with the same sized lumber as used in  
ceiling/floor joist.  
When installing a top vent vertical appliance the hole  
should be directly above the appliance, unless the flue is  
offset.  
10 in.  
(254 mm)  
Hole should measure  
10 in. x 10 in.  
(254 mm x 254 mm)  
inside to inside  
Do not pack insulation around the vent. Insulation must  
be kept away from the pipe.  
Note: The firestop spacer is not required if attic insulation  
shield is used.  
Install Attic Insulation Shield  
Frame opening for attic insulation shield.  
Attic insulation shield may be installed above or below  
ceiling (see Figure 2.18).  
Figure 2.17 Installing Firestop Spacer  
Secure with three fasteners on each side.  
Fold tabs at top of attic shield in toward vent pipe. Tabs  
must keep vent pipe centered within shield.  
Field construct additional shield height if insulation is  
deeper than height of attic shield.  
Bend tabs in  
around pipe  
3 fasteners  
per side  
Attic insulation shield  
installed below ceiling.  
Attic insulation shield  
installed above ceiling.  
Figure 2.18 Installing the Attic Insulation Shield  
10  
Hearth & Home Technologies Inc. • Cinch Pipe & Term Caps • 4033-900 Rev K • 05/05  
Download from Www.Somanuals.com. All Manuals Search And Download.  
G. Install Roof Flashing and Vertical Termination Cap  
To install roof flashing see Figure 2.19.  
To attach the vertical termination cap, slide the inner collar  
of the cap into the inner flue of the pipe section and place  
the outer collar of the cap over the outer flue of the pipe  
section.  
For installation of vertical termination cap see minimum vent  
heights for various pitched roofs (Figure 2.19) .  
Horizontal  
overhang  
Secure with three screws into the outer flue. Secure the cap  
by driving the three self-tapping screws (supplied) through  
the pilot holes in the outer collar of the cap into the outer flue  
of the pipe (see Figure 2.20).  
20 in.  
24 in. min.  
(508 mm)  
(610 mm)  
Vertical  
wall  
Lowest  
Discharge  
Opening  
Termination Cap  
Termination  
Cap  
X
Storm Collar  
12  
(1 of three)  
Brackets/  
Roof  
Flashing  
Bolts  
Roof Pitch  
is X / 12  
Storm  
Collar  
H (min.) - Minimum height  
from roof to lowest  
discharge opening.  
Screws  
Caulk  
Figure 2.20 Secure with Screws  
Roof Pitch  
Flat to 6/12  
6/12 to 7/12  
Over 7/12 to 8/12  
Over 8/12 to 9/12  
Over 9/12 to 10/12  
H (Min.) Ft.  
1.0*  
Roof Pitch  
H (Min.) Ft.  
Over 11/12 to 12/12  
Over 12/12 to 14/12  
Over 14/12 to 16/12  
Over 16/12 to 18/12  
Over 18/12 to 20/12  
Over 20/12 to 21/12  
4.0  
5.0  
6.0  
7.0  
7.5  
8.0  
1.25*  
1.5*  
2.0*  
2.5  
WARNING  
Over 10/12 to 11/12 3.25  
Fire Risk  
* 3 ft. minimum in snow regions  
Explosion Risk  
Inspect external vent cap regularly.  
Figure 2.19 Minimum Height from Roof to Lowest Discharge  
Opening  
Ensure no debris blocks cap.  
Combustible materials blocking cap may  
ignite.  
Restricted air flow affects burner  
operation.  
Hearth & Home Technologies Inc. • Cinch Pipe & Term Caps • 4033-900 Rev K • 05/05  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
H. Assemble and Install Storm Collar  
CAUTION  
Sharp Edges!  
Wear protective gloves and safety  
glasses during installation.  
Connect both halves of the storm collar with two screws (see  
Figure 2.21).  
Wrap the storm collar around the exposed pipe section and  
align brackets. Insert a bolt (provided) through the brackets  
and tighten nut to complete the storm collar assembly (see  
Figure 2.22). Make sure the collar is tight against the pipe  
section.  
Slide the assembled storm collar down the pipe section until  
it rests on the roof flashing (see Figure 2.19).  
Figure 2.21 Assembling the Storm Collar  
Caulk around the top of the storm collar.  
Figure 2.22 Assembling the Storm Collar Around the  
Pipe  
12  
Hearth & Home Technologies Inc. • Cinch Pipe & Term Caps • 4033-900 Rev K • 05/05  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Grizzly Saw G0661 User Manual
Grizzly Switch G8291 User Manual
Grizzly Work Light H8027 User Manual
Heartland Bakeware Range 9200 7200 User Manual
HP Hewlett Packard Work Light 8153A User Manual
HTC Cell Phone F5151 User Manual
Hyundai Car Video System H CMD4007 User Manual
IBM Switch ZG09 0629 User Manual
Iluv Printer ISP200 User Manual
Image Hot Tub IMSB53950 User Manual