Hearth and Home Technologies Indoor Fireplace Cinch Pipe Termination Cap System User Manual |
Installation
Instructions
TM
Models:
Cinch Pipe & Termination Cap System
These instructions are replacing VP (for Heatilator) and DV (for Heat-N-Glo) pipe assembly
instructions. See the appliance installation instructions for configuration of vent assembly
and clearances to pipe.
If you need assistance during installation, contact your local dealer or the Technical Serices Dept., Hearth & Home Technologies
Inc., phone 1-800-927-6841 or 1-888-427-3973.
If DVP-AD adapters are used off the top of the appliance, the termination height will be raised by 2-3/4 in. overall
height.
CAUTION
Sharp Edges
•
Wear protective gloves and safety glasses
during installation.
WARNING
Hearth & Home Technologies disclaims any
responsibility for, and the warranty will be
voided by, the following actions:
•
Installation and use of any damaged vent
system component.
•
•
Modificatoin of the vent system.
Installation other than as instructed by
Hearth & Home Technologies.
Installation and/or use of any component
part not approved by Hearth & Home
Technologies.
•
Any such action may cause a fire hazard.
WARNING
Do not mix pipe, fittings or joining
methods from different manufacturers.
Note: An arrow (ꢀ) found in the text signifies change in content.
Hearth & Home Technologies Inc. • Cinch Pipe & Term Caps • 4033-900 Rev K • 05/05
1
Download from Www.Somanuals.com. All Manuals Search And Download.
DVP-TRAPFL
DVP-TRAP1 or DVP-TRAP2 termination
cap rain flashing
DVP-TRAPFL
Flashing
DVP-TRAP1
DVP-TRAP2
Termination Cap
COOL ADD
DRC-RADIUS
Cap shield
Cap shield
Components
Description
DRC-RADIUS
Cap Shield
COOL-ADDM
DVP-TV
DVP45
Cap Shield - pack of six
Vertical Termination Cap
45° Elbow
DVP90ST
RF6M
90° Elbow
Roof Flashing (vertical termination for 0/12 to 6/12 pitch) - pack of four
Steep Pitch Roof Flashing (for 7/12 to 12/12 pitch) - pack of six
4 in. length Vent Pipe
RF12M
DVP4
DVP6
6 in. length Vent Pipe
DVP12
12 in. length Vent Pipe
DVP24
24 in. length Vent Pipe
DVP36
36 in. length Vent Pipe
DVP48
48 in. length Vent Pipe
DVP6A
3 in. - 6 in. Slip Section Vent Pipe (to be used with another piece of pipe)
3 in. - 12 in. Slip Section Vent Pipe (to be used with another piece of pipe)
12 in. Vent Pipe - non-unitized (can be cut to length)
24 in. Vent Pipe - non-unitized (can be cut to length)
Vent Support
DVP12A
DVP12MI
DVP24MI
DVP-HVS
DVP-WS
DVP-FS
DVP-TRAP1
DVP-TRAP2
DVP-TB1
DVP-TRAPK1
DVP-TRAPK2
DVP-HSM
BEK
Wall Shield to ensure horizontal clearances
Firestop Spacer
Horizontal Termination Cap with 1-3/4 in. telescoping flue and wall shield with heat shield
Horizontal Termination Cap with 4 in. telescoping flue and wall shield with heat shield
Basement Horizontal Termination Cap
Top Vent Horizontal Kit with DVP-TRAP1 Termination Cap, wall shield with heat shield, and 90° elbow
Top Vent Horizontal Kit with DVP-TRAP2 Termination Cap, wall shield with heat shield, and 90° elbow
Extended Heat Shield
Brick Extension Kit
DVP-AS
Attic Insulation Shield
Hearth & Home Technologies Inc. • Cinch Pipe & Term Caps • 4033-900 Rev K • 05/05
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Vent depth is measured from the back of the appliance to the outer edge of the exterior wall. See Table 1 and Figure 1.
TRAP CAP SPECIFICATION CHART
DVP-TRAPK1
Top Vent
Depth
DVP-TRAP1
Rear Vent
Depth
DVP-TRAPK2
Top Vent
Depth
DVP-TRAP2
Rear Vent
Depth
Appliance
Novus
NXT
Caliber
Maxus
GNTC50
Designer*
Titan
4-1/2 in. to 6-1/4 in.
4-1/8 in. to 5-7/8 in.
4-1/8 in. to 5-7/8 in.
4-1/2 in. to 6-1/4 in.
5 in. to 6-3/4 in.
3-1/2 in. to 4-3/4 in.
4-5/8 in. to 6-3/8 in.
3-5/8 in. to 5-3/8 in.
4-1/8 in. to 5-7/8 in.
4-7/8 in. to 6-5/8 in.
5-3/4 in. to 7-1/2 in.
N/A
3-1/8 in. to 4-7/8 in.
3-1/8 in. to 4-7/8 in.
N/A
7 in. to 11 in.
6-1/2 in. to 10-1/2 in.
6-1/2 in. to 10-1/2 in.
6-7/8 in. to 10-7/8 in.
7-3/8 in. to 11-3/8 in.
6-3/8 in. to 10-3/8 in.
6 in. to 10 in.
5-1/4 in. to 9-1/4 in.
5-1/4 in. to 9-1/4 in.
6 in. to 10 in.
5-1/2 in. to 9-1/2 in.
7-1/4 in. to 11-1/4 in.
6-1/4 in. to 10-1/4 in.
6-3/4 in. to 10-3/4 in.
7-3/8 in. to 11-3/8 in.
8-1/8 in. to 12-1/8 in.
N/A
5-5/8 in. to 9-5/8 in.
5-5/8 in. to 9-5/8 in.
N/A
4 in. to 5-3/4 in.
3-1/2 in. to 5-1/4 in.
2-3/4 in. to 4-1/2 in.
2-3/4 in. to 4-1/2 in.
3-1/2 in. to 5-1/4 in.
7-1/2 in. to 9-1/4 in.
4-1/2 in. to 6-1/4 in.
N/A
6000
8000
Olympian
Multisided
Gem
SL units
ICON
3-1/8 in. to 4-7/8 in.
N/A
3-1/8 in. to 4-7/8 in.
N/A
10 in. to 14 in.
7 in. to 11 in.
5-5/8 in. to 9-5/8 in.
N/A
5-5/8 in. to 9-5/8 in.
N/A
N/A
3-1/2 in. to 5-1/4 in.
4 in. to 5-3/4 in.
6-1/2 in. to 10-1/2 in.
6-3/4 in. to 7-3/4 in.
GDST5244I**
N/A
N/A
* Top vented appliance - Designer needs a DVP12 after the elbow.
** GDST5244I requires a DVP12 and DVP6 after the elbow.
Table 1
Figure 1 - Measuring Required Vent Depth
4
Hearth & Home Technologies Inc. • Cinch Pipe & Term Caps • 4033-900 Rev K • 05/05
Download from Www.Somanuals.com. All Manuals Search And Download.
Installing Vent Pipe
2
Note: Heat shields MUST overlap by 1-1/2 in. min. for rear
Note: For termination cap installations only, go directly to Sec-
vented appliances.
tion E.
B. Penetrating a Wall
A. Clearances for the Vent Sections
Wherever a combustible wall is penetrated, the hole must
be framed with an interior wall shield (DVP-WS) as shown in
Figures 2.3-2.4. This shield maintains minimum clearances
and restricts cold air infiltration. If the wall being penetrated is
of noncombustible materials (material which will not ignite or
burn, or has a UL fire rating of zero), a 9 in. diameter hole is
acceptable. Whenever a wall is penetrated the wall shield is only
required on one side and no heat shield is necessary. If your
local inspector requires the wall shield on both sides, then both
wall shields must have a heat shield attached to them.
•
Top Vented Direct Vent Appliances
For all top vented, direct vent appliances, clearances to
combustible materials from the venting system need to
be maintained as shown in Figure 2.1.
•
Rear Vented Direct Vent Appliances
See Figure 2.2.
Note: Refer to the appliance installation instructions for al-
lowed vent lengths and configurations.
Figure 2.3 Exterior Wall Hole
Figure 2.1 Horizontal Venting Clearances to Combustible Materi-
als - Top Vent
Note: Heat shields
MUST overlap by a
minimum of
1-1/2 in. (38 mm).
3 in. (76 mm)
Heat
Shield
top clearance
Figure 2.4 Interior Wall Shield
Heat
Shield
WARNING
Fire Risk
Explosion Risk
1 in. (25 mm)
Wall
Shield
clearance
Maintain vent clearance to combustibles as
specified.
bottom & sides
•
Do not pack air space with insulation or
other materials.
WALL
Failure to keep insulation or other materials
away from vent pipe may cause fire.
Figure 2.2 Horizontal Venting Clearances to Combustible Materi-
als - Rear Vent
Hearth & Home Technologies Inc. • Cinch Pipe & Term Caps • 4033-900 Rev K • 05/05
5
Download from Www.Somanuals.com. All Manuals Search And Download.
C. Assemble Vent Sections
WARNING
Fire Risk
Exhaust Fumes Risk
•
Overlap pipe slip sections at least
1-1/2 inches.
•
•
•
Use pilot holes for screws.
Screws must not exceed one inch long.
Pipe may separate if not properly
joined.
Figure 2.5 Lances
Attaching Vent to the Firebox Assembly
To attach the first pipe section to the collars, slide the male
end of the inner vent of the pipe section over the inner collar
on the firebox assembly. At the same time, slide the outer
flue over the outer collar on the appliance. Push the pipe
section into the appliance collar until all the lances (see Fig-
ure 2.5) have snapped in place. Tug slightly on the section
to confirm it has completely locked into place.
A
A
Assemble Pipe Sections
Insert the inner flue of section A into the flared inner flue of
section B.
B
Start the outer flue of section A over the outer flue of section
B (see Figure 2.6).
B
Note: The end of the pipe sections with the lances/tabs on
it will face towards the appliance.
Figure 2.7 Snapped
Figure 2.6 Inner/Outer
Once both inner and outer flues are started, press section
A onto section B firmly until all lances have snapped into
place. Check to make sure they have snapped together (see
Figure 2.7) and the seams are not aligned (see Figure 2.8).
Tug slightly on section A to confirm it has completely locked
into place.
Make sure the seams are not aligned to prevent unintentional
disconnection.
For 90° and 45° elbows that are changing the vent direction
from horizontal to vertical, one screw minimum should be
put in the outer flue at the horizontal elbow joint to prevent
the elbow from rotating.
CORRECT
Figure 2.8 Seams
INCORRECT
6
Hearth & Home Technologies Inc. • Cinch Pipe & Term Caps • 4033-900 Rev K • 05/05
Download from Www.Somanuals.com. All Manuals Search And Download.
Assemble Minimum Installation (MI) Sections
MI sections are non-unitized so that they can be cut to a
specific length. Cut these sections to length from the non-
expanded end (see Figure 2.9).
They can then be attached by first connecting the expanded
end of the MI inner flue with the inner pipe from the adjacent
pipe section and securing with three screws. The expanded
portion of the MI inner flue must overlap completely with the
unexpanded end of the adjacent pipe section.
The outer flue can then be inserted into the adjacent outer
flue expanded end and attached to the next pipe section with
three screws. The other end of the MI pipe section can then
be attached by fitting another pipe section to it and snapping
it together, as normal.
Figure 2.9 MI Sections
Assemble Slip Sections
The outer flue of the slip section should slide over the outer
flue of the pipe section and into (inner flue) the last pipe sec-
tion (see Figure 2.10) .
Slide together to the desired length, making sure that a
1-1/2 in. outer flue overlap is maintained between the pipe
section and slip section.
The pipe and slip section need to be secured by driving two
screws through the overlapping portions of the outer flues
using the pilot holes (see Figure 2.11).
Figure 2.10 Slip Section Pilot Holes
This will secure the slip section to the desired length and
prevent it from separating. The slip section can then be at-
tached to the next pipe section.
If the slip section is too long, the inner and outer flues of the
slip section can be cut to the desired length.
Figure 2.11 Screws into Slip Section
Hearth & Home Technologies Inc. • Cinch Pipe & Term Caps • 4033-900 Rev K • 05/05
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Secure the Vent Sections
Vertical sections of pipe must be supported every 8 ft after
the 25 ft maximum unsupported rise. The vent support or
plumber’s strap (spaced 120° apart) may be used to do this
(see Figures 2.12 and 2.13).
Horizontal sections of vent must be supported every 5 ft with
a vent support or plumber’s strap.
D. Disassemble Vent Sections
To disassemble any two pieces of pipe, rotate either section
(see Figure 2.14), so that the seams on both pipe sections
are aligned (see Figure 2.15). They can then be carefully
pulled apart.
Figure 2.12 Securing Vertical Pipe Sections
WARNING
Fire Risk
Explosion Risk
Asphyxiation Risk
Use vent run supports per installation
instructions.
Connect vent sections per installation
instructions
•
•
Maintain all clearances to combustibles.
Do NOT allow vent to sag below
connection point to appliance.
•
Maintain specified slope (if required).
Figure 2.13 Securing Horizontal Pipe Sections
Improper support may allow vent to sag or
separate.
Figure 2.14 Rotate Seams for Disassembly
Figure 2.15 Align and Disassembly Vent Sections
8
Hearth & Home Technologies Inc. • Cinch Pipe & Term Caps • 4033-900 Rev K • 05/05
Download from Www.Somanuals.com. All Manuals Search And Download.
E. Install the Heat Shield and Horizontal Termination Cap
on the extended heat shield should rest on the top of the vent
(pipe section) to properly space it from the pipe section.
WARNING
A 1-1/2 in. minimum overlap MUST be maintained on
the telescoping flue section of the cap.
Install the Horizontal Termination Cap
Vent termination must not be recessed in the wall. Siding
may be brought to the edge of the cap base.
Caulk the outside edges of the cap.
WARNING
Fire Risk
Exhaust Fumes Risk
Impaired performance of appliance.
When installing a horizontal termination cap, follow the cap
location guidelines as prescribed by current ANSI Z223.1
and CAN/CGA-B149 installation codes.
•
•
•
•
Overlap pipe slip sections at least 2 in.
Use pilot holes for screws.
Screws must not exceed 1 in. long.
Pipe may separate if not properly
joined.
WARNING
Burn Risk
•
Local codes may require installation of a
cap shield to prevent anything or anyone
from touching the hot cap.
Heat Shield Requirements for Horizontal Termination
For all horizontally vented appliances, a heat shield MUST
be placed 1 in. above the top of the vent between the wall
shield and the base of the termination cap.
Rear Vent
Heat Shield
1-1/2 in. (38 mm) min.
overlap
Heat Shield or
Extended
Heat Shield
There are two sections of the heat shield. One section at-
taches to the wall shield with two screws. The remaining
section is attached to the cap in the same manner. See
Figure 2.16.
Wall Shield
If the wall thickness does not allow the required 1-1/2 in.
heat shield overlap, an extended heat shield must be used.
The extended heat shield will need to be cut to the thickness
of the wall and be attached to the wall shield. The small leg
Inner Vent
Outer Vent
INTERIOR
EXTERIOR
SHEATHING
Figure 2.16 Venting through the Wall
WARNING
Do NOT connect a pipe section to a termination cap
without using the telescoping flue section found on the
termination cap.
Note: Where required, an exterior wall flashing is available.
When penetrating a brick wall, a brick extension kit is
available for framing the brick.
Hearth & Home Technologies Inc. • Cinch Pipe & Term Caps • 4033-900 Rev K • 05/05
9
Download from Www.Somanuals.com. All Manuals Search And Download.
F. Vertical Penetration Framing
WARNING
Fire Risk
Keep loose materials or blown insulation
from touching the vent pipe.
•
•
National building codes recommend using
attic shield to keep loose materials/blown
insulation from contacting vent.
Hearth & Home Technologies requires
the use of an attic shield.
Attic Above
10 in. (254 mm)
Install the Firestop Spacer
•
•
•
Frame an opening 10 in. by 10 in. whenever the vent
system penetrates a ceiling/floor (see Figure 2.17).
Frame the area with the same sized lumber as used in
ceiling/floor joist.
When installing a top vent vertical appliance the hole
should be directly above the appliance, unless the flue is
offset.
10 in.
(254 mm)
Hole should measure
10 in. x 10 in.
(254 mm x 254 mm)
inside to inside
•
Do not pack insulation around the vent. Insulation must
be kept away from the pipe.
Note: The firestop spacer is not required if attic insulation
shield is used.
Install Attic Insulation Shield
•
•
Frame opening for attic insulation shield.
Attic insulation shield may be installed above or below
ceiling (see Figure 2.18).
Figure 2.17 Installing Firestop Spacer
•
•
Secure with three fasteners on each side.
Fold tabs at top of attic shield in toward vent pipe. Tabs
must keep vent pipe centered within shield.
Field construct additional shield height if insulation is
deeper than height of attic shield.
•
Bend tabs in
around pipe
3 fasteners
per side
Attic insulation shield
installed below ceiling.
Attic insulation shield
installed above ceiling.
Figure 2.18 Installing the Attic Insulation Shield
10
Hearth & Home Technologies Inc. • Cinch Pipe & Term Caps • 4033-900 Rev K • 05/05
Download from Www.Somanuals.com. All Manuals Search And Download.
G. Install Roof Flashing and Vertical Termination Cap
To install roof flashing see Figure 2.19.
To attach the vertical termination cap, slide the inner collar
of the cap into the inner flue of the pipe section and place
the outer collar of the cap over the outer flue of the pipe
section.
For installation of vertical termination cap see minimum vent
heights for various pitched roofs (Figure 2.19) .
Horizontal
overhang
Secure with three screws into the outer flue. Secure the cap
by driving the three self-tapping screws (supplied) through
the pilot holes in the outer collar of the cap into the outer flue
of the pipe (see Figure 2.20).
20 in.
24 in. min.
(508 mm)
(610 mm)
Vertical
wall
Lowest
Discharge
Opening
Termination Cap
Termination
Cap
X
Storm Collar
12
(1 of three)
Brackets/
Roof
Flashing
Bolts
Roof Pitch
is X / 12
Storm
Collar
H (min.) - Minimum height
from roof to lowest
discharge opening.
Screws
Caulk
Figure 2.20 Secure with Screws
Roof Pitch
Flat to 6/12
6/12 to 7/12
Over 7/12 to 8/12
Over 8/12 to 9/12
Over 9/12 to 10/12
H (Min.) Ft.
1.0*
Roof Pitch
H (Min.) Ft.
Over 11/12 to 12/12
Over 12/12 to 14/12
Over 14/12 to 16/12
Over 16/12 to 18/12
Over 18/12 to 20/12
Over 20/12 to 21/12
4.0
5.0
6.0
7.0
7.5
8.0
1.25*
1.5*
2.0*
2.5
WARNING
Over 10/12 to 11/12 3.25
Fire Risk
* 3 ft. minimum in snow regions
Explosion Risk
Inspect external vent cap regularly.
Figure 2.19 Minimum Height from Roof to Lowest Discharge
Opening
•
Ensure no debris blocks cap.
Combustible materials blocking cap may
ignite.
•
•
Restricted air flow affects burner
operation.
Hearth & Home Technologies Inc. • Cinch Pipe & Term Caps • 4033-900 Rev K • 05/05
11
Download from Www.Somanuals.com. All Manuals Search And Download.
H. Assemble and Install Storm Collar
CAUTION
Sharp Edges!
•
Wear protective gloves and safety
glasses during installation.
Connect both halves of the storm collar with two screws (see
Figure 2.21).
Wrap the storm collar around the exposed pipe section and
align brackets. Insert a bolt (provided) through the brackets
and tighten nut to complete the storm collar assembly (see
Figure 2.22). Make sure the collar is tight against the pipe
section.
Slide the assembled storm collar down the pipe section until
it rests on the roof flashing (see Figure 2.19).
Figure 2.21 Assembling the Storm Collar
Caulk around the top of the storm collar.
Figure 2.22 Assembling the Storm Collar Around the
Pipe
12
Hearth & Home Technologies Inc. • Cinch Pipe & Term Caps • 4033-900 Rev K • 05/05
Download from Www.Somanuals.com. All Manuals Search And Download.
|