Haier Air Conditioner hsu 71hek03 r2db 0 User Manual

Installation manual  
for room air conditioner  
HSU-26HEK03/R2(DB)/I  
HSU-35HEK03/R2(DB)/I  
HSU-53HEK03/R2(DB)/I  
HSU-71HEK03/R2(DB)/I  
HSU-26HEK03/R2(DB)/O  
HSU-35HEK03/R2(DB)/O  
HSU-53HEK03/R2(DB)/O  
HSU-71HEK03/R2(DB)/O  
Read this manual before installation and keep it for future reference.  
Please explain to the user how the product works and refer them to the operation manual.  
NO.0010553937  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Preparation  
Accessory parts  
Remote controller (1)  
AAA dry battery (2)  
Mounting plate (1)  
Drain hose (1)  
Necessary tools for installation  
Cushion (4)  
Driver  
Nibbler  
Drain-elbow (1)  
Pipe supporting plate (1)  
Hacksaw  
Plastic cap (4)  
Ø4X25 Screw (4)  
Hole core drill  
Spanner (17,19 and 26mm)  
Gas leakage detector or soap-and-water solution  
Vacuum pump  
Torque wrench (17mm, 22mm, 26mm)  
Pipe cutter  
Selection of pipe  
Flaring tool  
Model  
Liquid pipe (Ø)  
Gas pipe (Ø)  
9.52mm (3/8")  
9.52mm (3/8")  
12.7mm (1/2")  
15.88mm (5/8")  
Knife  
HSU-26HEK03/R2(DB)/O  
HSU-35HEK03/R2(DB)/O  
HSU-53HEK03/R2(DB)/O  
HSU-71HEK03/R2(DB)/O  
")  
")  
")  
")  
Measuring tape  
Reamer  
Refrigeration gauges  
Power source  
NOTE: The thickness of the pipe must be at least 0.8mm.  
Install an exclusive circuit for the power.  
Check the power source voltage is the same as the rating plate.  
Power requirements  
Selection of installation place  
Indoor Unit  
The place chosen to install the indoor unit should be:  
Model  
Max rated current  
6.1  
HSU-26HEK03/R2(DB)/O  
HSU-35HEK03/R2(DB)/O  
HSU-53HEK03/R2(DB)/O  
HSU-71HEK03/R2(DB)/O  
6.0  
Not affected by heat or steam generated in the vicinity, where inlet and outlet  
of the unit are not blocked or restricted.  
10.5  
13.8  
Where it is possible to drain easily, and where piping can be connected  
with the outdoor unit.  
Where conditioned air can be evenly distributed through the whole room.  
Where there is more than 1m distance from televisions, radios, wireless  
are on.  
Outdoor Unit  
The place chosen to install the outdoor unit should be:  
Strong enough to bear the unit, where vibration and noise are not increased.  
Where discharged air and noise do not cause a nuisance to the neighbours.  
Where a distance marked  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Drawing for the installation of indoor and outdoor units  
Attention must be  
paid to the rising up  
Optional parts for piping  
More than 5cm (26/35/53)  
of drain hose  
More than 10cm (71)  
A
Non-adhesive tape  
Adhesive tape  
B
C
D
Saddle (L.S.) with screws  
Connecting electric cable  
for indoor and outdoor  
G
Drain hose  
More than 10cm  
E
F
Heating insulating material  
Piping hole cover  
G
Arrangement of  
piping directions  
More than 10cm  
the outdoor unit (Unit:mm)  
F
Rear left  
A
Rear  
right  
Left  
Z
Right  
C
X
Y
X
Below  
More than 10cm (26/35/53)  
More than 15cm (71)  
Dimensions  
More than 10cm (26/35/53)  
More than 20cm (71)  
Model  
HSU-26HEK03/R2(DB)/O  
x
y
z
140  
140  
500  
500  
256  
256  
HSU-35HEK03/R2(DB)/O  
HSU-53HEK03/R2(DB)/O 113.5 583 319.5  
HSU-71HEK03/R2(DB)/O 113.5 633  
340  
A
and  
are supplied parts  
G
D
Fixing of outdoor unit  
Fix the unit to concrete or block with  
pipe length is 2m.  
E
horizontally.  
earthquake or strong wind.  
More than 60cm  
More than 15cm (9/12/18)  
More than 25cm (24)  
unit by attaching  
a vibration-proof mat.  
The picture above is just for your reference. Please refer to the actual product purchased.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indoor Unit  
1 Fitting of the Mounting Plate and Positioning of the Wall Hole  
2 Making a Hole on the Wall and Fitting the Piping Hole Cover  
Make a hole of ‘B’mm in diameter, slightly descending to outside the wall.  
Install piping hole cover and seal it off with putty after installation.  
1. Find a suitable mounting location, ensuring there is adequate support to hold  
the weight of the unit, check it is level, then temporarily fasten the plate.  
Wall hole  
2. Check the plate is level, by hanging a thread with a weight from  
the central top of the plate or using a spirit level, then fasten securely.  
ØBmm  
3. Determine the wall hole location ‘A’ using a measuring tape.  
Outdoor side  
Indoor side  
Thickness of wall  
(Section of wall hole)  
Piping hole pipe  
G
3 Installation of the Indoor Unit  
Drawing of pipe  
[ Rear piping ]  
Draw pipes and the drain hose, then fasten them with adhesive tape  
[ Left Left-rear piping ]  
HSU-26HEK03/R2(DB)/I  
In case of left side piping, cut away, with a nibbler, the lid for left piping.  
In case of left-rear piping, bend the pipes according to the piping direction to the  
mark of hole for left-rear piping which is marked on heat insulation materials.  
938  
1. Insert the drain hose into the cavity of heat insulation materials of indoor unit.  
2. Insert the indoor/outdoor electric cable from the back of the indoor unit, and  
pull it out on the front side, then connect them.  
3. Coat the  
seal face with refrigerant oil and connect pipes. Cover the  
connection part with heat insulation materials, and  
it with adhesive tape.  
60  
100  
60  
229  
480  
110  
Indoor/outdoor electric cable  
Piping  
Heat insulation  
material  
Lid for right  
piping  
HSU-35HEK03/R2(DB)/I  
Pipe supporting  
plate  
Drain hose  
Lid for left piping  
Lid for under piping pipe  
Fix with adhesive tape  
1046  
Indoor/outdoor electric cable and drain hose must be bound with refrigerant  
piping by protecting tape.  
[ Other direction piping ]  
Cut away, with a nibbler, the lid for piping (according to the piping direction)  
and then bend the pipe according to the position of wall hole. When  
bending, be careful not to crush the pipes.  
70  
191  
85  
70  
667  
135  
Connect the indoor/outdoor electric cable.  
HSU-53HEK03/R2(DB)/I  
Fixing the indoor unit body  
Hang the unit body onto the upper notches of the  
mounting plate. Move the body from side to side to  
1156  
it is  
securely.  
In order to  
the body onto the mounting plate,hold  
up the body on an angle from the underside and  
then pull it down perpendicularly.  
mounting plate  
Unloading of indoor unit body  
70  
40  
70  
When you remove the indoor unit,  
use your hand to raise the  
138  
860  
105  
body from the hooks, then lift the  
bottom of the body outward  
HSU-71HEK03/R2(DB)/I  
slightly and lift the unit on an angle  
until it separates from the mounting plate.  
mounting plate  
Hooks  
Fix a mounting bar to the side bar and lintel (sold separately), and then fasten  
the plate to the mounting bar.  
Refer to note 1, “ When the mounting plate is  
“, for the position of wall hole.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indoor unit cont.  
DRED Function  
6.Please consult your reseller and/or installer to determine if you have a DRED appliance.  
Connect output from your home's electricity power meter (where available) to the RJ45  
connector on the outdoor unit, as shown.  
4 Connecting the indoor/outdoor Electric Cable  
Removing the wiring cover  
Remove terminal cover at right bottom corner of indoor unit,  
then take off wiring cover by removing its screws.  
(This function is unavailable on some models.)  
When connecting the cable after installing the indoor unit  
1. Insert from outside the room cable into left side of the wall  
hole, in which the pipe is fitted or installed.  
2. Pull out the cable on the front side, and connect the cable  
making a loop.  
When connecting the cable before installing  
the indoor unit  
Loosen the screws and insert the cable ends fully into terminal block,  
then tighten the screws.  
Pull the cable slightly to make sure the cables have been properly  
inserted and tightened.  
1 Installation of Outdoor Unit  
After the cable connection, always fasten the connected cable  
with the wiring cover.  
Install according to ‘Drawing for the installation of indoor and outdoor units’  
(see page 4)  
2 Connection of pipes  
To bend a pipe, use the correct bending tool, so as not to crush the  
pipe, and the bending radius should be 30 to 40 mm or longer.  
Connect the pipe gas side  
The connection pipe is specialized for R410A.  
When connecting the cable,  
the terminal number of indoor  
Note  
and outdoor units carefully. If wiring is not correct, the system will  
not operate correctly. Damage to the PCB due to incorrect  
wiring is not covered by warranty.  
Forced fastening without careful centering may  
damage the threads and cause a leakage of gas.  
damage the threads and cause a leakage of gas.  
Forced fastening without careful centering may  
Half union  
Flare nut  
PipeLidqiuaimd esitdeer6(Ø.3)5mm(1/4F")asteningtorque
18N.m  
Liquid side 6.35mm (1/4")  
18 N.m  
Electrical connection  
Liquid/Gas side9.52mm(3/8")  
Liquid/Gas side 9.52mm (3/8") 42 N.m  
Gas side 12.7mm(1/2")  
42 N.m  
55N.m  
60 N.m  
Gas side 12.7mm (1/2")  
55 N.m  
Outdoor unit  
Indoor unit  
Gas side 15.88mm(5/8")  
Gas side 15.88mm (5/8") 60 N.m  
Spanner  
Torque wrench  
Be careful that foreign materials such as sand, etc. do not enter the pipe. The  
charge of refrigerant must be conducted by professional air conditioner engineer.  
Before adding additional refrigerant, perform air evacuation from the refrigerant  
pipes and indoor unit using a vacuum pump, then charge additional refrigerant.  
4G0.75mm2  
CAUTION  
Power cable: 3G1.5mm2  
POWER  
Outdoor unit  
HSU-26HEK03/R2(DB)/O  
HSU-35HEK03/R2(DB)/O  
Indoor unit  
B
Outdoor unit  
B
A
Indoor unit  
Indoor unit  
A
Outdoor unit  
4G0.75mm2  
Max.Elevation: Amax  
Outdoor unit  
= 10m (HSU – 26/35)  
= 15m (HSU – 53/71)  
Oil trap  
POWER  
{
B
In case the elevation A is more  
Power cable:  
3G2.5mm2  
than 5m, oil trap shoud be  
installed every 5~7m  
Indoor unit  
A
HSU-53HEK03/R2(DB)/O  
HSU-71HEK03/R2(DB)/O  
Max. Length: Bmax  
= 15m (HSU – 26/35)  
= 25m (HSU – 53/71)  
1. If the supply cord is damaged, it must be replaced by the manufacturer or its  
service agent or a similar qualied person. The type of connecting wire  
and power cable is  
H05RN-F or H07RN-F.  
Pre charge  
Base charge pipe length  
Additional  
charge amount  
20g/m  
Model  
2. If the PC board fuse is broken replace with a T.3.15A/250VAC (Indoor)  
or T.25A/250VAC (Outdoor).  
HSU-26HEK03/R2(DB)/O 1000g  
HSU-35HEK03/R2(DB)/O 1080g  
HSU-53HEK03/R2(DB)/O 1550g  
HSU-71HEK03/R2(DB)/O 2100g  
7m  
3. The wiring method should be in line with the local and national wiring  
standards.  
7m  
20g/m  
10m  
10m  
20g/m  
4. After installation, the power isolator should be easily reached.  
50g/m  
5. A breaker should be incorporated into  
wiring. The breaker should be  
all-pole switch and the distance between its two contacts should be not less  
than 3mm.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Outdoor unit cont.  
Connection of Electrical Cable  
3
Step 4  
Open the 2-way valve to an angle of anticlockwise 90 degrees.  
Use the same method on indoor unit. Loosen the screws on terminal block  
and insert the plugs fully into terminal block, then tighten the screws.  
After 6 seconds, close the 2-way valve and test for refrigerant gas leakage.  
If wiring is not correct, proper operation can not be carried out and the  
controller may be damaged.  
2-way valve  
3-way valve  
Fix the cable with a clamp.  
Open 90O  
Attaching Drain-Elbow  
4
If the drain-elbow is used,  
please attach it as  
(Note: Only for heat pump unit.)  
Step 5  
No gas leakage? If ok, proceed to Step 6.  
Evacuation Method: Use vacuum pump  
5
In case of refrigerant leakage, tighten parts of pipe connections. If leakage  
stops, then proceed to Step 6.  
Step 1  
Remove the service port cap from the 3 way valve, the valve caps for the  
2 way & 3 way valves. Connect hose to the service port (low) side of the  
manifold gauge.  
If this does not stop gas leakage, reclaim all refrigerant from the service  
port. After  
and repeating vacuuming on the system, with the  
prescribed refrigerant level. Check again for leaks.  
Then connect the centre hose from the manifold gauge to the vacuum pump.  
2-way valve Liquid Side  
3-way valve Gas Side  
Step 6  
Gauge manifold (for  
R410A)  
Detach the charge hose from the service port, open 2-way valve and 3-way valve.  
Turn the valve anticlockwise until closed.  
2-way valve  
3-way valve  
Vacuum pump (for R410A)  
Tube (for R410A)  
Step 2  
Open the tap on the low side of the manifold and operate the vacuum pump.  
If the gauge (low) reaches a vacuum immediately repeat step 1 above again.  
Step 7  
To prevent refrigerant leakage, tighten the service port’s taps and caps to ensure  
they are  
sealed.  
2-way valve  
3-way valve  
Open  
Valve rod cap  
Valve rod cap  
Step 3  
Service port cap  
Vacuum for over 15min. Check the (low) gauge which should read  
-0.1 MPa (-76 cm Hg) at Iow pressure side. After completion of vacuuming  
the system, close the low tap on the manifold and turn off the vacuum pump.  
Check the low side gauge to see if it holds for 1-2 min. If the gauge does not  
Step 8  
After  
hold pressure, check all the  
and return to the beginning of Step 3.  
the caps, check for refrigerant gas leakage around the caps.  
Close  
CAUTION  
If the refrigerant of the air conditioner leaks, it is necessary to reclaim all  
the refrigerant, then pull a vacuum BEFORE recharging the refrigerant into  
the air conditioner according to the amount marked on the name plate.  
Please do not charge with refrigerant, except as  
(R410A), or  
allow air to enter into the cooling circulation system. Otherwise, this may  
cause abnormal high pressure in the system which may lead to personal  
injuries or damage to piping.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Refrigerant charge label  
Outdoor unit cont.  
Contains fluorinated greenhouse gases  
covered by the Kyoto Protocol  
1 Power Source Installation  
The air conditioner must be wired with a dedicated circuit to the distribution  
board. The protection device should be sized to meet the current  
requirements of the unit as shown on page 3 and comply with local and  
national wiring standards.  
If installing the air conditioner in a moist place, please install an earth  
leakage breaker.  
For installation in other places, use a circuit breaker.  
Protocol. Do not vent into the atmosphere.  
Refrigerant type: R410A  
2 Cutting and Flaring Work of Piping  
GWP* value:1975  
Pipe cutting is carried out with a pipe cutter and burrs must be removed.  
GWP=global warming potential  
Flare tool for R410A  
Clutch-type  
Conventional are tool  
clutch-type(Rigid-type) Wing-nut type (Imperial-type)  
A
0~0.5mm  
1.0~1.5mm  
1.5~2.0mm  
be adhered in the proximity of the product charging port (e.g. onto the inside of the  
stop value cover).  
1.Cut pipe  
2.Remove burs  
Flare tooling die  
A
B factory refrigerant charge of the product: see unit name plate  
C
D total refrigerant charge  
E outdoor unit  
3.Insert the are nut  
4.Flare pipe  
F refrigerant cylinder and manifold for charging  
Check for installation and test run  
Correct  
Incorrect  
Please kindly explain to our customers how to operate the unit through  
the instruction manual.  
Put check mark  
in boxes  
Check items for test run  
Lean  
Damage of are  
Partial Too outside  
Crack  
Gas leak from connecting pipe?  
Insulation of pipe connecting ?  
3 On Drainage  
Please install the drain hose to be always sloping downhill.  
Examples of incorrect  
Are the indoor and outdoor interconnecting cables  
interconnecting cables  
Is drainage securely carried out?  
Is the earth line securely connected?  
Less than  
5cm  
It becomes  
high midway  
The end is imm-  
ersed in water  
It waves.  
The gap with the  
ground is too small. smell from a ditch  
There is the bad  
Is power source voltage correct?  
Is there any noise?  
Is the indicator lamp lit?  
condensate is carried to outdoor.  
In case that the attached drain hose is in a room, please apply  
insulation to drain  
Are cooling and heating (when in heat pump) performing normally?  
Is the operation of room temperature adjustment normal?  
.
8
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graco Automobile Parts CORIOLIS MASS FLOW User Manual
Graco Inc Power Roller 218938 User Manual
Grizzly Drill G0484 User Manual
Halo Lighting System Indoor Furnishings H2586 User Manual
HANNspree Flat Panel Television HANNSzzebra User Manual
Hearth and Home Technologies Indoor Fireplace 350TRS CE User Manual
HP Hewlett Packard Switch 480 0005 00 15 User Manual
Hunter Fan Humidifier 31006 User Manual
Husqvarna Chainsaw 345 User Manual
Impex Home Gym MWM900 User Manual