HSM Power Supply CMN3000R User Manual

Owner’s  
Operating  
Manual  
CMN SERIES  
CONTINUOUS POWER SYSTEM  
MODEL COVERED:  
CMN3000R  
CMN4000R  
CLARY CORPORATION  
150 E. Huntington Dr.  
Monrovia, California 91016  
Telephone 626-359-4486  
800-44 CLARY  
Fax. 626-305-0254  
World Wide Web HTTP: // WWW.CLARY.COM  
E-Mail SALES @ CLARY.COM  
Information contained herein is the property of Clary Corporation, is proprietary, confidential, and not to be  
disclosed, disseminated or used except for the purpose provided by  
CLARY CORPORATION  
P/N 510-14040 REV.NR  
11/15/04  
Download from Www.Somanuals.com. All Manuals Search And Download.  
T H E C O N T I N U O U S P O W E R C O M P A N Y  
INTRODUCTION  
This Owners’s Operating Manual is provided with  
your new CMN SERIES unit. It will enhance your  
understanding of the product and its functions.  
Read this handbook carefully in the order it is  
presented prior to operating your unit. This will  
save you time and effort in your installation and  
application. The illustrations provided will familiarize  
you with this product’s operating modes and  
components. Always operate the unit within the  
guidelines and specifications provided to maximize  
safety and the lifetime of the unit. Also, your  
understanding of the product is a key element in  
getting the most out of your CMN SERIES.  
ongratulations! You have selected the  
highest quality protection for your continuous  
power needs. This unit offers a quiet and  
compact package with superior performance  
C
you can depend on. You now own a CMN SERIES  
Continuous Power System (CPS) which is an all  
Digital Technology (DT) product manufactured by  
Clary Corporation, the first name in uninterruptible  
power system (UPS) reliability. The Continuous  
Power System is the highest order in the hierarchy  
of UPS products. When power problems occur,  
there can be no compromising the reliability of your  
power solution. The CMN SERIES Continuous  
Power System is your complete power solution.  
IMPORTANT SAFETY INSTRUCTIONS,  
SAVE THESE INSTRUCTIONS  
This symbol indicates that there  
This symbol indicates that  
are important operating and  
maintenance instructions in the  
literature accompanying this  
unit.  
CAUTION  
dangerous voltage constituting  
a risk of electrical shock is  
present within the unit.  
RISK OF ELECTRIC  
SHOCK DO NOT OPEN  
!
!
This manual contains important safety instructions that should be followed during installation and maintenance of  
the UPS and batteries. Be aware of the following symbols and their meaning as they appear throughout the  
manual:  
This equipment generates and uses radio frequency energy and if  
not installed and used properly in strict accordance with the  
manufacturer's instructions, may cause interference to radio and  
television reception. All units in this manual have been tested and  
found to comply with the limits for a Class A computing device in  
accordance with the specifications in Subpart J of Part 15 of FCC  
Rules, which are designed to provide reasonable protection  
against such interference in a commercial installation. However,  
there is no guarantee that interference will not occur in a  
particular installation. If this equipment does cause interference  
to radio and television reception, which can be determined by  
turning the equipment off and on, the user is encouraged to try to  
correct the interference by one or more of the following measures:  
Reorient the receiving antenna.  
Relocate the UPS with respect to the receiver.  
Move the UPS away from the receiver.  
Plug the UPS into a different outlet so that the UPS and  
receiver are on different branch circuits.  
If necessary, the user should consult the dealer or an experienced  
radio/television technician for additional suggestions. The user  
may find the following booklet prepared by the Federal  
Communications Commission helpful:  
"How To Identify and Resolve Radio-TV Interference Problems"  
This booklet is available from the U.S. Government Printing  
Office, Washington, DC 20402, Stock No. 004000003454.  
Page 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
T H E C O N T I N U O U S P O W E R C O M P A N Y  
TECHNICAL DESCRIPTION  
he Digital Technology-High Temperature  
CMN Series Continuous Power System (CPS)  
Reference the block diagram for a simplified  
explanation of the system’s operation. The AC utility  
source is connected to the power and micro  
electronics when the input switch is closed. The  
input line is filtered, power factor corrected and  
rectified for enhanced performance without  
disturbing other equipment that may share the same  
utility circuit.  
is a revolutionary new concept in total power  
protection and management. The CMN  
T
SERIES is a microprocessor-based UPS that now  
allows the user to set most of the control feature  
parameters. By directly linking a personal computer  
to the RS232 port, frequency settings and operation,  
alarm signals, load switching, etc. can all be  
programmed to meet specific application  
requirements.  
The microprocessor controls an Inverter Generator  
that produces a low harmonic, AC sinewave for  
continuous power applications.  
The CMN SERIES is a true on-line, continuous  
power UPS. In the tradition of Clary products, the  
CMN SERIES generates the same high quality and  
proven reliability to provide the best power  
When the input AC utility line fails, the battery circuit  
within this system takes over to ensure continuous  
power. Only until properly rated power is returned,  
does the microprocessor reconnect the input source  
back into the system.  
protection available for today’s critical applications.  
In keeping with state-of-the-art design, the power  
electronics are completely governed by an on-board  
microprocessor. Given the powerful memory  
capability of today’s micro controllers, this  
The microprocessor is directly tied to an external  
RS232 connector port. This allows the user to  
monitor and even set some of the operating  
parameters. With a simple link to a personal  
computer using the UPS software program, you can  
actually view, on your monitor, the event history of  
the power distribution system with the  
CMN SERIES unit as the central hub. More  
sophisticated users may implement the optional  
SNMP package to accomplish full Network Power  
Management.  
microprocessor has evolved the UPS into an all-in-  
one complete power distribution and monitoring  
center. Not only is your critical load insured of the  
most reliable and constant power available, but the  
user may now continuously track status of the  
supply components that keep the entire system  
operational. Production downtime can now be  
virtually eliminated by knowing exactly what patterns  
the supply utility power maintains and by knowing  
exactly the condition and life expectancy of the  
battery reserve.  
.
DB-9  
CONTACTS  
DB-9  
RS232  
UTILITY  
INPUT  
MICROPROCESSOR  
CONTROLLER  
EMERGENCY  
CUTOFF  
SWITCH  
COMMON  
MODE  
CHOKE  
VOLTAGE  
WINDOW  
DETECTOR  
POWER  
FACTOR  
CORRECTOR  
AC  
COMMON  
MODE  
CHOKE  
INPUT  
ISOLATION  
TRANSFORMER  
+ DC  
RAILS  
RECTIFIER  
INVERTER  
GENERATOR  
LOAD  
STANDBY  
BATTERY  
CHARGER  
BYPASS LINE  
Page 4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CMN SERIES  
REAR PANEL  
AC IN  
DC IN  
BATTERY BANK  
+
-
+
+
-
+
-
-
+
+
-
-
+
+
-
-
SIMPLIFIED SYSTEM INTERCONNECT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
T H E C O N T I N U O U S P O W E R C O M P A N Y  
PACKAGING  
the shipping carton. Save all packing material for  
future use.  
Take extra precaution when removing or returning it  
to the box. Because this unit contains a battery, it  
can be quite heavy. Never attempt to unpackage  
the equipment unassisted.  
The packaging also contains important information  
on use and care as well as valuable warranty  
information. Read all materials before storing this  
literature with your other valuable product  
documents.  
our CMN SERIES has been carefully  
packaged to withstand most abuse sustained  
during shipment. The packing material has  
been specifically designed to protect this  
Y
system for normal handling, using most shipping  
carriers. If there is significant damage to the carton,  
or if there is any physical damage to this unit, report  
this to your carrier.  
!
These units are encapsulated in a protective wrap  
that comes apart once the product is removed from  
Page 6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
T H E C O N T I N U O U S P O W E R C O M P A N Y  
PHYSICAL DESCRIPTION  
his section will point out and illustrate the  
various indicators, functions and controls of  
the CMN SERIES UPS. Pictured is the front  
Visual indicators used on the front panel are long  
lasting, very efficient, light emitting diodes (LED).  
When operating the push-button switches, always  
hold the switch in for at least two seconds to insure  
function confirmation. This feature has been  
implemented into the system design to avoid  
inadvertent operation of any of the user-available  
functions.  
T
view of the system, then followed by the rear  
view. The important attributes of the CMN SERIES  
unit is numbered to assist you in locating them on  
your machine and also to fully explain its function  
and how it relates to system operation.  
Numbers on the drawing will correspond to the  
operating component’s name at the bottom with a  
brief identification. In the next section, a complete  
explanation of all numbered items will be enhanced  
to ensure you have a full understanding of the  
operation of this system.  
The rear panel has been engineered with the user’s  
multiple applications in mind. Two load outputs are  
provided with three receptacles per output. The  
outputs can be independently switched on or off.  
3
10  
9
13  
14  
8
7
6
5
2
STATUS BATTERY  
LOAD  
COLD  
AC IN  
FULL  
OVER  
LOAD I  
LOAD II  
START  
OK  
100%  
75%  
50%  
25%  
ALARM  
LOW  
ALARM  
SILENCE/  
TEST  
INV  
(800)-44-CLARY WWW.CLARY.COM  
18  
17  
11  
12  
16  
19  
1
4
15  
RACKMOUNT FRONT PANEL VIEW  
1
2
3
4
5
6
7
8
9
SYSTEM POWER SWITCH  
11 LOAD II - Enable switch for bottom row of output receptacles  
12 LOAD II ACKNOWLEDGE INDICATOR  
13 ALARM SILENT/TEST - Dual function switch  
14 ALARM SILENT/TEST ACKNOWLEDGE INDICATOR  
15 ALARM - Fault indicator  
HANDLES  
AC In Ok- Input line indicator  
INVERTER - Inverter operating indicator  
BATTERY – Battery level indicators  
LOAD – Load level indicators  
16 INPUT CIRCUIT BREAKER  
COLD START - DC start switch  
COLD START ACKNOWLEDGE INDICATOR  
LOAD I - Enable switch for top row of output receptacles  
17 20A CIRCUIT BREAKER FOR LOADI  
18 20A CIRCUIT BREAKER FOR LOAD II  
19 AC INPUT INDICATOR  
10 LOAD I ACKNOWLEDGE INDICATOR  
Page 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
21  
22  
25  
23  
21  
24  
20  
26  
RACKMOUNT REAR PANEL VIEW  
20 INPUT - AC Line Plug  
24 SIGNAL – Open Collector  
25 RS232 - RS232 communications signals  
26 SNMP- Optional  
21 DC INPUT - Auxiliary battery connector  
22 120VAC OUTPUT (LOAD 1)- System output  
23 120VAC OUTPUT (LOAD 2)- System output  
Page 8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
T H E C O N T I N U O U S P O W E R C O M P A N Y  
SUMMARY OF INDICATORS AND CONTROLS  
SYSTEM POWER SWITCH - The main control  
switch that engages utility power to the entire unit.  
By activating this switch it initializes normal  
operation. Input circuit breaker must be on.  
Alarm Silent/Test - A momentary push-button  
switch that controls two different functions  
depending on the mode of operation. In the normal  
mode of operation, if this switch is depressed and  
held in, the above indicator will blink. Once it stops  
blinking, the unit will perform an internal 1 to 2  
minute battery check. Once the test is completed, if  
the battery is below standards, the system will  
indicate that the battery needs replacing. The  
system will not run this battery test unless the  
battery is detected to be fully charged. During  
battery or abnormal operation, an audible alarm will  
accompany this mode. By depressing this switch,  
the adjacent indicator will blink. When it stops  
blinking, the alarm will be silenced. Once the fault or  
reason for the alarm is corrected, this audible alarm  
condition will automatically reset. The audible alarm  
can be re-enabled during abnormal conditions by  
pressing and holding the switch again.  
AC In - The utility input indicator that identifies  
status of the line voltage. If the line voltage is within  
the specified range, it will remain lit. If the AC input  
is out of range, this indicator will flash in 1 to 2  
second intervals.  
Inverter - This indicator identifies the status of the  
regenerated, conditioned protected output power.  
This indicator will stay ON as long as protected  
power is available from the power inverter generator.  
Battery Level - This is the battery status bar graph.  
During normal operation, this bar graph will show the  
charging of the battery; all indicators lit will represent  
a fully charged battery. During battery operation,  
this bar graph represents a discharge meter  
indicating less battery time available as each L.E.D.  
turns OFF.  
NOTE - All switches must be held in for at least two  
seconds to engage their function. This is to prevent  
any inadvertent switch operation.  
Load Level - This is the system output capacity  
status bar. The number of L.E.D.s on the graph  
indicate an approximate percentage of system full  
load. All lights being ON would indicate full load.  
Alarm - This is a fault indicator that will light in the  
event that the inverter generator is non-operable.  
This could be due to an “over-temperature” situation  
or an inverter malfunction.  
DC INPUT - The battery input connector to add  
batteries.  
Cold Start - A momentary push-button switch to  
activate the system in the event no utility power is  
present. The system will be allowed to start up by  
using power from its batteries. Turn on the System  
Power Switch. Press and hold the Cold Start Switch  
until the audible alarm beeps once. Press and hold  
the LOAD I or II switch. The system will maintain a  
load depending upon the condition of the battery.  
120VAC OUTPUT (Load I & Load II) - The output  
groupings that can be independently controlled by  
the corresponding front panel switch. During normal  
operation, inverter generator power is supplied at  
these outlets.  
Load I and Load II - A momentary push-button  
switch that toggles the output LOAD I or II AC output  
outlets at the rear panel “ON /OFF”. The indicator  
above the switch will be ON to represent that LOAD I  
OR II Is activated. The output can be turned OFF by  
pressing and holding the switch. While the switch is  
depressed, the indicator will blink to represent  
transition. Once the indicator stops blinking, the  
switch can be released for a successful transition.  
SIGNAL - A DB-9 subminiature, female connector  
that outputs the open collector signal contacts for  
utility interrupt, low battery and inverter active  
conditions.  
RS232 - A DB-9 subminiature, female connector that  
outputs true RS232 communications signals.  
COOLING FAN - The cooling device necessary to  
maintain operation without defect. This cooling fan  
draws air directly across the internal heatsink.  
IDENTIFICATION LABEL - The model number and  
serial number of the system is located here. Always  
refer to this information when corresponding with the  
factory.  
Page 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
T H E C O N T I N U O U S P O W E R C O M P A N Y  
INSTALLATION  
he CMN Series unit is designed for installation  
The air should remain free from excessive dust  
in a protected environment. Units may be  
installed in a 19" rack system. The system is  
lightweight and can be easily moved. Some  
and chemical fumes.  
T
The front panel is designed to fit in a standard 19"  
rack. This panel fills a 5 ¼” slot. Guide Rails or  
slides are recommended to support the unit's  
mainframe. This system weighs in excess of 85  
pounds; front panel mounting is not intended to  
support the entire unit. The system has pre-tapped  
aluminum slide bars available to accept some  
standard slide configurations. Contact the factory  
for optional slide kits and accessories if assistance  
is required in properly mounting in a rack.  
important points to consider when positioning a unit  
for operation:  
A properly rated (preferably dedicated) outlet is  
accessible for the power cord supplied with the unit.  
It is not recommended to modify the supplied cord in  
any way nor should an extension cord of any kind be  
used.  
The cord paths in the system installation should  
remain clear of foot traffic or anything else that may  
disturb permanent connection.  
Once a location has been selected and the external  
battery pack is connected, it is ready for operation.  
Allow at least 48 hours, after the system is first  
installed, to fully charge the external battery to a  
maximum state. Charge time depends on the size  
of batteries used.  
The installation site should maintain an ambient air  
temperature of less than 40oC. When the  
environment for the system remains cooler during  
operation, there is less stress on the batteries and  
the internal electronics.  
The air inlets, vents and fan should not be  
obstructed or blocked in any way.  
OPTIONS  
This rackmountable UPS is supplied with a matching rackmountable auxiliary battery box. This battery box is  
designed to host one or two strings of batteries, to extend battery support times. The additional time is dependent  
on the unit capacity and load size.  
The battery pack is rated at 96VDC and comes with a mating cable that directly connects to the battery port at the  
rear of the UPS. This connector is exposed, after removing the attached cover plate. The connector on the  
battery and UPS are the same so that the cable can be plugged in either way. The connector used is a locking  
type, when fully engaged, will not allow the cable to be pulled apart, unless the locking ears are depressed.  
The battery box fits a 3 1/2” slot into a 19” rack, just like the UPS. The full depth of the battery, however, is only  
23”. It is slide ready and weighs approximately 48 pounds in a single battery configuration. It weighs 85 pounds  
in a dual battery configuration. An additional port is available at the rear of the battery box to add continuous  
battery strings if necessary.  
The battery box is designed to be upgradeable. If the single string is not adequate, the user may order an  
additional string of batteries that can be easily installed in the existing box. By removing the existing mounting  
screws on the existing battery, it can slide over and the additional set can now be secured, with four additional  
screws, adjacent to the original set. The internal harness has an open connector provided for the second set.  
After plugging this connector together, the upgrade is complete.  
Page 10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
T H E C O N T I N U O U S P O W E R C O M P A N Y  
OPERATION  
nce the system has been properly installed, it  
Position the System Power Switch to the ON  
position.  
is ready to operate. The following procedures  
will explain how to start-up the system while  
plugged into rated electrical power and also  
O
Push and hold in the COLD START switch until  
the audible alarm beeps.  
how to start-up with no AC power available.  
The unit will start up similarly to normal AC start-up  
except the AC IN L.E.D. will continue to flash. The  
LOAD outputs will come up in the OFF mode when  
using the COLD START feature. You must press and  
hold the LOAD I or LOAD II switch to activate the  
inverter.  
Normal Operation on AC Start-Up:  
Verify that the unit is plugged into properly rated  
electrical power.  
Connect Cable from Aux. Battery Box to UPS.  
Position the Input Circuit Breaker to the ON  
position.  
Loading the System  
The system can be loaded up to full rated load. As  
load is applied, the LOAD METER will start to turn  
ON. The LOAD METER will not work when you are in  
a “Manual Bypass”. Once full load is achieved, the  
full LOAD METER should be lit. As additional load is  
applied, the top red OVERLOAD L.E.D. will come ON.  
If too much overload is applied, the audible alarm will  
sound. If this increased load is not removed within  
five seconds, the unit will discontinue output  
operation and latch into an alarm condition. The  
audible alarm will continue to sound and the ALARM  
L.E.D. will light. Reducing the load and cycling the  
System Power Switch OFF then ON can reset the  
system.  
Position the System Power Switch to the ON  
position and the BYPASS SWITCH to the INV  
position. You will now have Bypass power at the  
receptacles.  
The system will proceed through about a three  
second diagnostic where all the L.E.D.s will sequence  
ON then OFF. The AC IN L.E.D. will flash several  
times and the audible alarm will give a short burst.  
The AC IN light L.E.D. will then stay ON and the  
battery level meter will light to at least an 80% level.  
The INVERTER L.E.D. will come ON and inverter  
power will now be available at all the output  
receptacles. The LOAD I and LOAD II will come ON.  
Actual load may be connected at any time during this  
procedure, however inverter power is only available  
when the L.E.D. above either of the LOAD switches is  
ON continuously.  
Programming the Outputs:  
The outputs on startup can be programmed ON or  
OFF. The default mode is programmed to turn both  
load circuits ON whenever you power up the UPS on  
AC startup. They will stay energized until you turn  
OFF the UPS, the batteries run down during a power  
outage or if the appropriate load button is pressed.  
Battery Operation after AC Start-Up:  
Unplug the unit from the standard wall outlet.  
The AC In L.E.D. will flash at two to three second  
intervals. Within 5 seconds, the audible alarm will  
sound at half-second intervals.  
To program both loads to be OFF when the UPS is  
turned ON:  
Push and hold in the ALARM SILENT/TEST  
switch until the audible alarm is inhibited.  
Turn the UPS OFF.  
Turn the UPS ON while pressing and holding the  
LOAD I OR II switch.  
If operation were to continue in this mode, the  
BATTERY LEVEL meter would start to turn OFF, one  
L.E.D. at a time starting from the top. Once the last  
L.E.D. is left, the alarm will sound in a constant tone.  
Had the alarm been previously silenced, it would still  
re-enable to alert the user of limited operation. This  
alarm can also be silenced as before. If the unit is  
allowed to operate further, it will time shut off the  
loads. If power were to return, the unit will  
The UPS will come ON with both loads OFF and  
will remember this setting each time the unit is  
turned ON.  
To program both loads to come ON:  
Turn the UPS OFF.  
Turn the UPS ON while pressing and holding both  
LOAD I and LOAD II switches (this definitely  
requires both hands). The UPS will remember  
this combination the next time it is powered ON.  
automatically restart and return to the condition it was  
in at the moment it went into Battery Mode.  
DC Start Operation (Cold Start)  
To program LOAD I or LOAD II to come ON  
If no utility power is available at the time backup  
power is required, the unit may be started to  
accomplish abbreviated tasks. The limitations of the  
battery prevent extended operations at full load.  
individually at startup:  
Turn the UPS OFF.  
Turn the UPS ON while pressing and holding  
either LOAD I or LOAD II switches.  
Page 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
T H E C O N T I N U O U S P O W E R C O M P A N Y  
SIGNALS AND INTERFACING  
t the rear of the unit are two DB-9,  
subminiature, female connectors. These are  
provided for communications links to a  
computer or sophisticated monitoring device.  
This conserves the battery life once an orderly  
shutdown has been accomplished. The system may  
be configured to shutdown by simply shorting pins 6  
and 7. Contact the factory for configuration details.  
A
SIGNAL PORT DB-9 provides open collector type  
closures that typically signal Utility Interrupt, Low  
Battery and Inverter Active conditions. A system  
shutdown feature is also available on this port.  
Applying a +5-12V signal across the appropriate  
pins will cause the system to shutdown in battery  
mode.  
RS232 DB-9 is a true RS232 communications signal  
port. On rackmount units, this port is on a  
removable plate, which can be substituted with an  
optional SNMP card. Below is the pin out of the two  
connectors with their default assignments:  
SIGNAL PORT-(DB9) OPEN COLLECTOR  
2-  
3-  
4-  
5-  
6-  
UTILITY INTERRUPTED SIGNAL  
INVERTER ACTIVE SIGNAL  
COMMON SIGNAL RETURN  
LOW BATTERY SIGNAL  
+ UPS SHUTDOWN  
7-  
- UPS SHUTDOWN  
RS232 CONNECTOR  
2-  
3-  
5-  
6-  
8-  
TRANSMITTING DATA (TX)  
RECEIVING DATA (RX))  
GROUND  
DATA SET READY (DSR)  
REQUEST TO SEND (RTS)  
Page 12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
T H E C O N T I N U O U S P O W E R C O M P A N Y  
SPECIFICATIONS  
DESIGN  
ELECTRICAL  
Standard Features  
Power Factor Corrected, Digital  
RegenerativeOn-Line, Sinewave  
Inverter Powers Load Continuously  
Extended Brownout Protection  
Designed for Non-linear Loads  
Continuous Operation on  
-25%,+12% Line  
Input  
CMN3000R/CMN4000R  
Voltage  
120V +10%, -20% (without  
Battery discharge)  
Power Factor Corrected  
Frequency  
IAW MIL STD. 1399 Sec. 300  
45 to 65Hz  
Automatic Bypass  
RS232 Data Interface  
Current(Amps) @ 120VAC  
21A/28A @ 100% Non-Linear  
Software Selectable Output  
Frequency  
AC Output Switch  
Output  
Voltage  
120VAC ± 3%  
Auxiliary Battery Connector  
Rear Mounted Ground Stud  
Optional SNMP Interface  
Frequency  
50Hz / 60Hz (software select)  
Line Sync (software select)  
Current(Amps)  
25A/33A @ 100% Non-Linear  
Specifications  
UL 1778, CUL, FCC Class A,  
IEEE 587/ANSI C62.41,  
IEC 555 @ 120VAC  
Crest Factor Ratio  
(Non-linear load and  
less than 5% THD) Typical  
@50% Load  
@75% Load  
Up to 4.8:1  
Up to 3.2:1  
@100% Load Up to 2.4:1  
MTBF  
In Excess of 100,000 Hours  
Total Harmonic Distortion (THD)  
Dynamic Response  
Overload  
3% Typ; 5% Max.  
(@100% Non-linear load)  
CONTROLS AND INDICATORS  
Visual Indicators  
Sequenced LEDs  
±4% for 100% Step Load Change,  
0.5 Millisecond Recovery Time  
Battery Level, Load Level  
Single LED AC Input, Inverter On, Load On  
Summary Alarm, Alarm Silence,  
Cold Start,  
110% for 10 Minutes;  
200% for 50 Milliseconds  
Efficiency (UPS)  
UPS Protection  
85-87% Typical  
Front Panel Controls  
Power On, Cold Start  
Alarm Silence, Battery Test  
AC Output On/Off, Bypass  
Input and Output Short Circuit;  
Input and Output Overload;  
Excessive Battery Discharge  
Audible Alarms  
Utility Interrupt, Inverter Failure  
Overload, Low Battery  
ENVIRONMENTAL  
Operating Temperature  
Humidity  
0oC to 40oC  
RS232 Data Interface (DB-9F) Full Interactive, Remote Computer  
Monitoring and Control of UPS  
Functions.  
0% to 95% Non-condensing  
Sea Level to 10,000 Feet  
42 dBA at Five Feet  
Altitude  
Compatible with Systems  
EnhancementTM UPS Monitor &  
Control Software  
Audible Noise  
MECHANICAL  
Open Collector (DB-9F)  
Optional SNMP Interface  
Allows Alarm Function Monitoring  
Input  
CPC Type 3 Position Inlet  
Connectors  
Allows Full Control and Monitoring  
(RJ45 or BNC) Over Network Connection.  
Output (Qty.)  
Cooling  
Load 1 and Load 2 (3 each)  
NEMA Type 5-20R  
Specifications subject to change without notice  
Low Velocity, Temperature  
Controlled Reversible Forced  
Air  
Dimensions: HxWXD In.  
Weight: Lbs. (Kg)  
5.25 x 19 x 23  
85 (38.8)  
Page 13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
T H E C O N T I N U O U S P O W E R C O M P A N Y  
CARE AND MAINTENANCE  
his device is designed to be maintenance-free.  
It can be cleaned with a damp cloth or  
CAUTION - Do not open or mutilate the battery or  
batteries. Released electrolyte is harmful to the skin  
and eyes. It may be toxic.  
CAUTION - A battery can present a risk of electrical  
shock and high short circuit current. The following  
precautions should be observed when working on  
batteries.  
1. Remove watches, rings, or other metal objects.  
2. Use tools with insulated handles.  
3. Wear rubber gloves and boots.  
nonabrasive cleanser.  
T
WARNING: Do not use ACETONE-BASE  
cleaning solutions. Keep cleaning solutions out of  
the electrical receptacles on this device.  
Be sure filters, vents and fans are kept free from  
accumulation of dust, dirt or lint. Below is a simple  
maintenance schedule that will assist you in keeping  
the system at its peak level of performance and also  
minimizing potential premature failures.  
4. Do not lay tools or metal parts on top of  
batteries.  
Your system contains sealed maintenance-free  
batteries. When situated in the proper environment,  
with the proper charging and limited cycling, these  
batteries can last many years.  
WARNING: Never attempt to service batteries.  
High voltage exists within the unit which could cause  
electrical shock. Servicing of batteries should be  
performed or supervised by personnel  
knowledgeable of batteries and the required  
precautions. Keep unauthorized personnel away  
from batteries. When replacing batteries, use the  
same number and type batteries.  
CAUTION - Do not dispose of battery or batteries in  
a fire. The battery may explode.  
5. Disconnect the charging source prior to  
connecting or disconnecting battery terminals.  
6. Determine if the battery is inadvertently  
grounded. If inadvertently grounded, remove  
source of ground. Contact with any part of a  
grounded battery can result in electrical shock.  
The likelihood of such shock will be reduced if  
such grounds are removed during installation  
and maintenance.  
The internal rechargeable battery is recyclable. At  
the end of its useful life, under various state and  
local laws, it may be illegal to dispose of this battery  
into the municipal waste stream. Check with the  
factory for details in your area for recycling options  
or proper disposal.  
CAUTION  
RISK OF ELECTRIC  
SHOCK DO NOT OPEN  
!
RECOMMENDED PREVENTATIVE MAINTENANCE SCHEDULE  
TIME  
TASK  
Test battery operation, check back-up time  
TOOLS REQ’D  
None  
INITIALꢃ  
Every 6 mo.  
Every 12 mo. Thoroughly clean unit  
Every 42 mo. Replace battery  
Vacuum, brush  
3/8 Hex Nut Driver  
Screwdriver  
Every 72 mo. Replace cooling fans  
Page 14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
T H E C O N T I N U O U S P O W E R C O M P A N Y  
SERVICE AND REPAIR  
our CMN SERIES is backed by one of the  
finest customer service teams available.  
Write or call them at any time to obtain more  
information about your unit.  
The RMA number issued to you should appear on  
the outside of the carton, if the unit is returned, or on  
any correspondence regarding your unit. When  
shipping a unit back to the factory, try to use the  
original packing container and shipping materials.  
The Service Department cannot take responsibility  
for any unit damaged in return shipment. All units  
must be returned prepaid to:  
Y
Clary Corporation  
150 E. Huntington Dr.  
Monrovia, CA 91016  
1-800-551-6111  
If a problem should occur, it is important that you  
obtain a Return Material Authorization (RMA)  
number from the Service Department to process any  
unit returned to the factory. In consulting the factory,  
always have the unit model number and serial  
number at hand. This information is located on the  
identification label and is essential in retrieving your  
unit’s performance and history record.  
Clary Corporation  
SERVICE DEPT.  
150 E. Huntington Dr.  
Monrovia, CA 91016  
Page 15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
T H E C O N T I N U O U S P O W E R  
C O M P A N Y  
CLARY CORPORATION  
LIMITED WARRANTY  
STANDARD CMN SERIES  
DEPOT REPAIR  
Clary Corporation warrants the electronics of the Clary CMN Series UPS to be free from defects in material  
and workmanship for a period of two years from the Date of Purchase. If, in Clary’s opinion, the  
electronics fail to meet its published specification due to a defect in material and workmanship covered by  
this warranty, Clary Corporation will repair or replace the warranted Unit at no cost to the customer for  
parts and labor.  
This warranty is applicable only to the initial purchaser and is not transferable. The LIMITED WARRANTY  
is:  
(a) Two (2) year Parts and Labor (Electronics)  
(b) Two (2) year Battery pro-rated*  
*Battery Pro-Ration Calculation: Credit toward new batteries= Current battery list price x Months of  
unexpired life ÷ 24.  
Equipment supplied by Clary Corporation, but not manufactured by Clary Corporation, is warranted solely  
by the manufacturer of such equipment. Clary Corporation does not warrant equipment not manufactured  
by Clary Corporation.  
This warranty does not apply to any unit that has been subject to neglect, accident, abuse, misuse,  
misapplication, incorrect connection/installation, or that has been subject to repair or alteration not  
authorized in writing by Clary Corporation. Incorrectly installed and/or non-application use voids all stated  
warranties. THIS WARRANTY IS THE PURCHASER’S (USER’S) SOLE REMEDY AND IS EXPRESSLY IN  
LIEU OF ANY OTHER WARRANTY, AND THERE ARE NO OTHER EXPRESSED OR IMPLIED GUARANTEES  
OR WARRANTIES (INCLUDING ANY IMPLIED WARRANTY OF MERCHANT ABILITY OR FITNESS FOR  
PURPOSE). In no case will Clary Corporation’s liability under this contract exceed the value of the Unit  
furnished.  
In no event shall Clary Corporation be liable for indirect, incidental, special or consequential damages.  
Clary Corporation shall not be responsible for failure to provide service or parts due to causes beyond  
Clary Corporation’s reasonable control.  
Any advice furnished the Purchaser (User) before or after delivery in regards to use or application of Clary  
Corporation equipment is furnished without charge and on the basis that it represents Clary Corporation’s  
best judgement under the circumstances. The use of any such device by the Purchaser (User) is sole and  
entirely at his or her own risk.  
This limited warranty applies only to equipment installed in the fifty United States and Canada.  
Clary Corporation reserves the right to make changes, additions, and/or improvements in its products  
without any obligation to install them on its products previously sold.  
Equipment requiring in-warranty service must be returned to the factory, DEPOT REPAIR, Monrovia,  
California. A Returned Merchandis Authorization Number (RMA#) must be obtained by calling (800) 551-  
6111 prior to returning any equipment to Clary Corpoation . Inbound transportation charges are  
customer’s responsibility. Equipment should be tagged stating the nature of the trouble experienced. The  
RMA# must be clearly visible on shipping container, shipping label or packing slip. It is recommended to  
return equipment to Clary Corporation in the original shipping container. The equipment will be returned  
collect to the location specified via the best least expensive carrier available or via customer’s  
shipping instructions  
ADM-01 (Rev. 2)  
1 of 1  
Date: 2/17/2003  
Page 16  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graco Stroller PD223368A 9 12 2 User Manual
Grundig Electric Shaver LS 4940 User Manual
Harbor Freight Tools Cordless Saw 93808 User Manual
Hasbro Games 57768 User Manual
Havis Shields Automobile Accessories KK F VAK User Manual
Heath Zenith Home Safety Product BL 1100 User Manual
Honeywell Door RDI User Manual
HP Hewlett Packard Computer Hardware RMC User Manual
Huffy Games 89135 User Manual
Hunter Fan Outdoor Ceiling Fan 41535 01 User Manual