MA7200 PLUS INVERTER
SERIES
FAN Quick Start Manual
1 to 2 HP
Models- MA7200 -2001/2-N1 (230V)
&
MA7200-4001/2-N1 (460V)
Rev. 1.2 – April 14th 2008
Download from Www.Somanuals.com. All Manuals Search And Download.
MA7200 PLUS Inverter 1 to 2 HP Fan Quick Start Manual
_______________________________________________________________
Step 4 - Check Fan Motor Operation
• Enter 10.00Hz for the frequency reference and set parameter Sn-08 = 1 to disable Reverse
Direction operation. Note: The output from the inverter is displayed in Hz as factory default. If
desired, the output may be displayed in per cent (%) of full speed. (see appendix)
to
;
0
1
1 - Press the
2 - Press the
key twice
key
Flashing
Flashing
3 - Press the
2 Seconds
key to
.
1
Flashing
______________________________________________________________ 3
TECO – Westinghouse Motor Company
Download from Www.Somanuals.com. All Manuals Search And Download.
MA7200 PLUS Inverter 1 to 2 HP Fan Quick Start Manual
_______________________________________________________________
• Press the RUN key, and check the fan direction of rotation. If the direction is not correct, press
the STOP key and wait until the fan has come to a complete STOP. Next, power down the
inverter.
Danger
After the power has been turned OFF, wait at least 5 minutes until the charge
indicator extinguishes completely before touching any wiring, circuit boards or
components.
• Reverse any two of the fan motor connections at the inverter ( U(T1),V(T2), or W(T3) ). Next,
following STEP 2, power-up the inverter; the motor direction should now be correct.
Step 5 – Select Method of Control
• Before selecting the method of control, verify that the inverter is in the STOP mode.
• There are two methods of control or combinations thereof that may be selected; Keypad and
Analog Signal.
RUN / STOP Command - Can be provided from the keypad or from an external contact
(see Fig. 2a).
Speed Reference – Can be from the keypad or from an external analog signal (0 – 10 VDC or
4 – 20 mA). see Fig’s 3a,3b, and 3c.
• The RUN/STOP method of control is set by parameter Sn – 04 and the Speed Reference is set
by parameter Sn – 05. The following table shows the values to be set when selecting.
Start / Stop
Sn – 04=
Speed Reference
Value
Sn – 05=
*0
1
Keypad
External Contact
Keypad
External Analog
* NOTE
The factory default for Sn – 04 and Sn – 05 is set to 0; Digital Operator (Keypad) No
further parameter changes are necessary if this is the desired method of control. If
External Contact set to Sn – 04 or External Analog set to Sn – 05 is desired then proceed
as follows.
______________________________________________________________ 4
TECO – Westinghouse Motor Company
Download from Www.Somanuals.com. All Manuals Search And Download.
MA7200 PLUS Inverter 1 to 2 HP Fan Quick Start Manual
_______________________________________________________________
______________________________________________________________ 5
TECO – Westinghouse Motor Company
Download from Www.Somanuals.com. All Manuals Search And Download.
MA7200 PLUS Inverter 1 to 2 HP Fan Quick Start Manual
_______________________________________________________________
• After the method of control has been selected, if external control wiring is required, (e.g. external
analog), power down the inverter before removing any covers or making any connections.
In the following pages are wiring examples for Start / Stop, E-Stop, Restart, and Analog
Connections.
Danger
After the power has been turned OFF, wait at least 5 minutes until the charge
indicator extinguishes completely before touching any wiring, circuit boards, or
components.
______________________________________________________________ 6
TECO – Westinghouse Motor Company
Download from Www.Somanuals.com. All Manuals Search And Download.
MA7200 PLUS Inverter 1 to 2 HP Fan Quick Start Manual
_______________________________________________________________
DIGITAL INPUT / OUTPUT terminal connections (1 – 2 HP)
Fig’s 2a, 2b, and 2c below show the control terminal connections for input control functions. The
connections shown are typical and the user is referred to the MA7200 Manual if additional
information is required. Fig. 2d shows an example for the use of the Fault Output Relay.
STOP
RUN
______________________________________________________________ 7
TECO – Westinghouse Motor Company
Download from Www.Somanuals.com. All Manuals Search And Download.
MA7200 PLUS Inverter 1 to 2 HP Fan Quick Start Manual
_______________________________________________________________
ANALOG INPUT terminal connections (1 – 2 HP)
Fig’s 3a,3b, and 3c.show the various analog input schemes that can be used to control the
output frequency and thus the speed of the fan motor when External Analog is selected by
Sn-05 in Step 5. Only one method may be used as the input source with Fig. 3a Potentiometer
Input being most common.
______________________________________________________________ 8
TECO – Westinghouse Motor Company
Download from Www.Somanuals.com. All Manuals Search And Download.
MA7200 PLUS Inverter 1 to 2 HP Fan Quick Start Manual
_______________________________________________________________
MA7200 PLUS BLOCK DIAGRAM
Fig. 4 is an overall basic electrical connection diagram for MA7200 PLUS inverters rated 1 to 2
HP. It is used in conjunction with the other sections of this guide to give the user the ability to
successfully start up a Fan application. More detailed information is available in the MA7200
PLUS Manual to which the user is referred if further information is required.
______________________________________________________________ 9
TECO – Westinghouse Motor Company
Download from Www.Somanuals.com. All Manuals Search And Download.
MA7200 PLUS Inverter 1 to 2 HP Fan Quick Start Manual
_______________________________________________________________
Appendix A-
Changing display to read output speed in percent (%) of full speed.
The display is factory defaulted to show the inverter output frequency in Hz. If desired, the
display can be changed to show the output frequency as a percentage of full speed. To do this
parameter Cn-28 must be changed from (00000) to (00001) as follows:
To set parameter Cn-28 = 1
(Display Percent)
Resulting Display
Keypad Steps
PRGM
An – 01 -
key
1 - Press the
DRIVE
Freq. Cmd. 1
Cn – 01 -
Input Voltage
DSPL
2 - Press the
3 - Press the
key 3 times
Cn-28-
key until display shows
Operator DSPL Unit
Flashing
EDIT
Cn-28 = 00000
4 - Press the
key
ENTER
Operator DSPL Unit
Flashing
Cn-28 = 00001
5 - Press the
6 - Press the
key
Operator DSPL Unit
Flashing
EDIT
key to save
Entry Accepted
2 Seconds
Flashing
ENTER
Cn-28 = 00001
Operator DSPL Unit
PRGM
DRIVE
7 - Press the
key to return to the main display.
______________________________________________________________ 10
TECO – Westinghouse Motor Company
Download from Www.Somanuals.com. All Manuals Search And Download.
MA7200 PLUS Inverter 1 to 2 HP Fan Quick Start Manual
_______________________________________________________________
Appendix B -
Removing the LCD Digital Operator and Inverter Cover(s)
______________________________________________________________ 11
TECO – Westinghouse Motor Company
Download from Www.Somanuals.com. All Manuals Search And Download.