HP Hewlett Packard Plumbing Product 2180206H User Manual

Combi HP  
Thermostatic  
mixer shower  
Installation and  
operating  
instructions  
T00
Installers please note these InstructIons are to be left wIth the user  
2180206H March 2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Combi HP thermostatic mixer shower  
InTROducTIOn  
INTRODUCTION  
SAFETY WARNINGS  
This book contains all the necessary fitting and  
operating instructions for your Triton high  
pressure thermostatic mixer shower. Please read  
them carefully.  
a. Layout and sizing of pipework MUST be such  
that when other services are used, pressures  
at the shower control inlets do not fall below  
the recommended minimum.  
Please read through the whole of this book  
before beginning your installation.  
b. DO NOT choose a position where the shower  
could become frozen.  
The installation MUST be carried out by a  
suitably competent person and in sequence of  
this instruction book.  
c. The outlet of this appliance MUST NOT be  
connected to any form of tap or fitting not  
recommended by the manufacturer.  
Care taken during the installation will give a long  
and trouble free life from your mixer shower.  
d. The showerhead MUST be regularly cleaned  
to remove scale and debris.  
Thermostatic mixers will automatically maintain  
your chosen temperature, even if taps are turned  
on elsewhere in the house, and shut off if either  
the hot or cold supply fails.  
e. Conveniently situated isolating valves in each  
inlet supply MUST be fitted as an  
independent method of isolating the shower  
should maintenance or servicing be necessary.  
For the best performance within the specified  
running pressure range a minimum flow of  
eight litres per minute should be available to  
both inlets.  
f. If it is intended to operate the shower in areas  
of hard water (above 200 ppm temporary  
hardness), a scale inhibitor may have to be  
fitted. For advice on the Triton scale inhibitor,  
please contact Customer Service.  
The mixer shower MUST NOT be subjected to  
water temperatures above 80°C.  
g. Do not operate the shower outside the  
C-006-A  
guidelines as laid out in ‘site requirements’.  
This mixer is designed to operate on higher  
pressure systems found in the UK up to a  
maximum of 5 bar running pressure.  
The high pressure valve is suitable for modulating  
type combination boilers and multi-point hot  
water heaters. It is also suitable for thermal  
storage, unvented systems and pumped gravity  
systems.  
IMPORTANT: Before installing with a gas  
instantaneous water heater, make sure it is  
capable of delivering hot water at a minimum  
switch-on flow rate of 3 litres per minute. At  
flow rates between 3 and 8 litres per minute,  
the appliance must be capable of raising the  
water temperature to a minimum of 52°C.  
The water temperature at the inlet to the mixer  
must remain relatively constant when flow rate  
adjustments are made.  
Inlet connections are by compression fittings for  
15 mm copper pipe.  
This valve unit is supplied with a mounting  
bracket to suit installation in a chased out cavity  
in a solid wall, a stud partition wall, dry lined wall  
or fixing to a shower cubicle or panel.  
Replacement parts can be ordered from Customer  
Service. See ‘spare parts’ for details and part numbers.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Combi HP thermostatic mixer shower  
MAIN COMPONENTS (fig.ꢀ)  
1. Inlet nuts and olives  
2. Inlet elbows  
9. Temperature knob  
10. Knob trim  
16. Flush mount plate  
17. Flush mount cover  
18. Trim ring  
3. Valve housing  
11. Max. temperature override  
button  
4. Outlet adaptor  
5. Outlet nut and olive  
6. Outlet blanking plug  
7. cartridge assembly  
8. Flow knob  
19. cartridge fixing screws  
20. nut covers  
12. cover  
13. Inlet trims  
21. Pipe trims  
14. Outlet trim  
15. Outlet blanking trim  
22. Hexagonal nut  
23. Shroud (flush fit only)  
Fig.ꢀ  
5
1
4
16  
2
3
1
7
18  
17  
19  
2
11  
8
19  
19  
20  
20  
9
6
10  
13  
23  
14  
20  
13  
21  
22  
12  
18  
15  
T00220  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Combi HP thermostatic mixer shower  
SITInG REquREMEnTS  
SITE REQUIREMENTS  
The installation must be in accordance with  
Water Regulations/Bylaws.  
Minimum running water pressure: 1 bar.  
Maximum running water pressure: 5 bar.  
Maximum static water pressure: 10 bar.  
For the best performance within the specified  
pressure range both hot and cold water supplies  
must be fed from a common supply and a  
minimum flow of 8 litres per minute should be  
available to both inlets.  
While the mixer valve is operational (open  
outlet), inlet pressures MUST NOT be capable of  
exceeding 7 bar. For effective operation of the  
internal seals, the maximum static pressure must  
not be exceeded.  
Note: On sites where the running pressure is  
above 5 bar, the use of a suitably sized pressure  
reducing valve fitted in the cold mains supply  
pipework can provide nominally equal pressures  
at the mixer valve. This should be installed as  
indicated on the appropriate diagrams shown on  
the following pages, and set to within the  
D-003-A  
specification of the valve.  
For the best performance of this shower both hot  
and cold water supplies to the shower valve  
should be fed at nominally equal pressures.  
The pipework should be installed such that the  
flow is not significantly affected by other taps  
and appliances being operated elsewhere on the  
premises.  
Note: Where thermal store/combi boilers or  
multi-point heaters are used, if excessive draw  
offs take place the boiler may not be able to  
maintain an adequate output temperature. This  
could result in the shower temperature becoming  
noticeably cooler.  
For effective thermostatic control the  
temperature of the hot water entering the mixer  
should remain a minimum of 10°C above the  
selected output temperature.  
The supply pipework must be flushed to clear  
debris before connecting to the shower control  
accordance with Water Regulations and Bylaws.  
DO NOT use jointing compounds on the  
pipework.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Combi HP thermostatic mixer shower  
TYPICAL SUITABLE INSTALLATIONS  
a) Instantaneous gas-heated showers,  
e.g. combination boilers (fig.ꢁ)  
Fig.ꢁ diagrammatic view (not to scale)  
The shower control MuST be installed with a  
multipoint gas water heater or combination  
boiler of a fully modulating design (i.e. where  
the water draw-off rate indirectly controls the  
gas flow to the burner). A drop tight pressure  
reducing valve MuST be fitted if the supply  
pressures exceed 5 bar maintained.  
Shower  
mixer  
valve  
Combination  
boiler  
Service  
valves  
An expansion vessel (shown in fig.ꢁ) MuST be  
fitted, and regularly maintained, to make sure  
the unit is not damaged by excess pressures.  
This may already be installed within the boiler  
(check with manufacturer) and is in addition to  
the normally larger central heating expansion  
vessel.  
Hot water  
The layout and sizing of pipework must be  
such that nominally equal inlet supply pressures  
are achieved and the effects of other draw-offs  
are minimised. The hot supply temperature  
MuST remain a minimum of 10°c hotter than  
the required blend temperature for the best  
performance.  
CH flow  
CH return  
Expansion  
vessel  
Stop tap  
Cold  
mains  
supply  
Pressure  
reducing valve  
T00221  
Fig.ꢂ diagrammatic view (not to scale)  
Stop valve  
b) Pump assisted gravity fed systems  
(fig.ꢂ)  
Riser  
rail  
The pump MuST be fed from a cold water  
cistern and hot water cylinder providing  
nominally equal pressures. The pump must be  
capable of maintaining a minimum running  
pressure of 1 bar.  
Cold supply  
Cold water  
cistern  
Alternative  
supply  
(must be  
below  
Mixer  
Valve  
vent pipe tee)  
Gate  
valve  
c) Unvented mains pressure showers  
(fig.ꢃ)  
Hot  
supply  
Cold  
water  
mains  
supply  
The shower control can be installed with an  
unvented, stored hot water cylinder.  
For systems with no cold water take off after the  
appliance reducing valve, it will be necessary to  
fit an additional drop tight pressure reducing  
valve when the mains pressure is over 5 bar. The  
drop tight pressure reducing valve MuST be  
set at the same value as the unvented package  
pressure reducing valve.  
Service  
valve  
Service  
valve  
Hot water  
cylinder  
Pump  
Ring main  
Isolating switch  
or pull cord  
switch (both  
fused at 3A)  
Drain  
valve  
Other  
draw-offs  
Draw-off must point  
down to avoid airlock  
issues  
Note: An additional expansion vessel (fig.ꢃ)  
may be required if a second pressure reducing  
valve is installed. This does not apply to  
T00222  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Combi HP thermostatic mixer shower  
packages with a cold take off after the pressure  
reducing valve to the cylinder.  
Fig.ꢃ diagrammatic view (not to scale)  
The layout and sizing of pipework must be such  
that nominally equal inlet supply pressures are  
achieved and the effects of other draw-offs are  
minimised.  
Mixer  
shower  
d) Mains pressurised thermal store  
(fig.ꢄ)  
Safety devices  
not shown  
Packages of this type, fitted with a tempering  
valve (blender valve) can be used. A drop tight  
pressure reducing valve MuST be fitted if the  
supply pressures exceed 5 bar maintained.  
Service  
valves  
Unvented  
hot water  
storage unit  
An expansion vessel (shown in fig.ꢄ) MuST be  
fitted, and regularly maintained, to make sure  
the unit is not damaged by excess pressures. This  
may already be installed externally or internally  
within the thermal store (check with thermal store  
manufacturer).  
Pressure  
reducing valve  
Expansion  
vessel  
Balanced cold  
mains supply  
Pressure  
The layout and sizing of pipework MuST be such  
that nominally equal inlet supply pressures are  
achieved and the effects of other draw-offs are  
minimised.  
reducing valve  
Cold mains supply  
Stop tap  
T00223  
Fig.ꢄ diagrammatic view (not to scale)  
Mixer valve  
Service  
valves  
Blender  
valve  
Hot  
water  
Expansion  
vessel  
Pressure  
reducing valve  
Return Flow  
Boiler  
Stop tap  
Cold mains supply  
T00224  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Combi HP thermostatic mixer shower  
PREPARING THE MIXER VALVE  
Before starting the installation, make sure all the  
openings on the valve are carefully covered to  
prevent ingress of any debris etc.  
Fig.ꢅ diagrammatic view (not to scale)  
Note: It is not necessary to remove the control  
knobs at any stage.  
SITING OF THE SHOWER  
WARNING!  
The showermustnotbe positioned  
where it will be subjected to freezing  
conditions.  
Height of  
showerhead  
and shower  
to suit user’s  
requirement.  
Refer to fig.ꢅ for correct siting of the shower.  
Position the shower and showerhead on the wall  
so that all controls can be comfortably reached  
while using the shower. The showerhead and  
riser rail can be positioned either side of the  
shower.  
Shower can be  
mounted either side  
of the riser rail  
Note: Pipe entry for both surface-mounted and  
flush-fitted valves can be from the top, bottom  
or rear.  
The hot entry port is on the left-hand side of the  
valve and is marked on the valve with a letter ‘H’  
(fig.7).  
Surface-mounted illustrated  
T00225  
Fig.7  
T00226  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Combi HP thermostatic mixer shower  
FITTING THE SHOWER TO THE WALL  
Exposed  
Fig.8  
Note: The outlet of the shower must not be  
connected to anything other than the hose and  
showerhead supplied.  
dO nOT use jointing compounds on any pipe  
fittings for the installation.  
dO nOT solder fittings near of the shower unit,  
as heat transfer can damage components.  
Note: Suitable isolating valves (complying with  
water Regulations) must be fitted on the hot  
and cold water supplies to the shower as an  
independent means of isolating water supplies  
should maintenance or servicing be necessary.  
T00227  
Fig.9  
when connecting pipework avoid using tight  
90° elbows. Swept or formed bends will give the  
best performance.  
=
ImportaNt: The water circuit should be  
installed such that the flow is not significantly  
affected by other taps and appliances being  
operated elsewhere on the premises. Water  
pressure must not fall below specification of  
the shower.  
=
T002
Note: The hot water pipe entry must be on the  
left.  
Fig.ꢀ0  
Rising and falling supplies  
Having decided on the position of the shower  
and direction of pipe entry, complete the  
pipework to the shower area.  
Note: The final separation between pipe  
centres needs to be about 153 mm but absolute  
accuracy is not needed as the inlet elbows are  
adjustable between 146 mm and 160 mm.  
T00229  
Flush pipework to clear the system of all  
debris and check for leaks.  
Fig.ꢀꢀ  
Fig.ꢀꢁ  
ImportaNt: The inlet elbows contain check  
valves that may be damaged if debris is not  
flushed through prior to fitting.  
/RQJ  
VLGH  
where this is not possible refer to the ‘flushing  
procedure’ on page 20.  
clip the pipework to the wall surface so that the  
pipe centres are 21 mm off the wall.  
Offer the valve, together with the inlet elbows,  
to the pipework. Make sure the inlet elbow grub  
T00231  
T00230  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Combi HP thermostatic mixer shower  
screws are slack allowing the inlet elbows to  
Fig.ꢀꢂ  
Fig.ꢀꢃ  
rotate to the correct position and move freely in  
and out of the valve housing (fig.8).  
Place the valve housing centrally between the  
two pipes, and mark the two diagonal fixing  
holes (figs.9 and ꢀ0).  
Remove the valve. drill and plug the holes. (The  
wall plugs supplied are suitable for most brick walls  
— use an appropriate masonry drill, but if wall is  
plasterboard or a soft building block, you must use  
suitable wal lplugs and an appropriate drill bit).  
T00232  
T00233  
Fit the nut covers on to the pipes (fig.ꢀꢀ).  
Note: Slide the pipes into the small diameter  
end of the nut cover. It will not fit if inserted  
from the other end.  
Fig.ꢀꢄ  
Slide the inlet nuts and olives onto the pipes,  
followed by the inlet trims.  
Note: The holes in the inlet trims are offset to  
allow for adjustable inlet pipe separation widths.  
If pipe centre separation is 153 mm or less, then  
have the short side of the inlet trims between  
the pipes. If the pipe separation gap is 153 mm  
or greater, have the long side of the inlet trims  
between the pipes (fig.ꢀꢁ). If in any doubt try  
the cover to see if it fits properly (i.e. no visible  
gaps between the inlet trims and the cover —  
fig.ꢀꢂ). If there is a gap (fig.ꢀꢃ) then reverse  
the trim.  
T00234  
Fig.ꢀꢅ  
Outlet  
Adaptor  
‘O’ Ring  
while trying the cover make sure the inlet nuts  
are sitting in the holes in the inlet trim holes so  
that the inlet trims are at the correct separation.  
Having positioned the inlet trims correctly, refit  
the valve to the pipework. Make sure the hot  
inlet port (marked with the letter ‘H’ on the  
valve housing) is connected to the hot pipework  
which must be on the left.  
T00237  
Hose end  
(flat)  
Pipe end  
(chamfered)  
Fig.ꢀ7  
Screw to the wall with the two screws supplied  
(fig.ꢀꢄ). Tighten the inlet nuts and inlet elbow  
grub screws.  
If installing a tamperproof fixed head, fit the  
outlet adaptor into the top outlet hole in the  
valve housing (fig.ꢀꢅ). The adaptor is sealed  
with an ‘O’ ring. Make sure the adaptor is fitted  
with the hose end in the valve housing. Fit the  
blanking plug into the bottom outlet hole using  
an ‘O’ ring to seal it.  
T00022  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Combi HP thermostatic mixer shower  
If installing a riser rail, fit the outlet adaptor into  
Fig.ꢀ8  
Fig.ꢀ9  
Fig.ꢁ0  
Fig.ꢁꢀ  
the bottom outlet hole in the valve housing. The  
adaptor is sealed with an ‘O’ ring.  
Make sure the adapter is fitted with the pipe end  
in the valve housing (fig.ꢀ7)  
Fit the blanking plug into the top outlet hole  
using an ‘O’ ring to seal it (fig.ꢀ8). Make sure  
both the adaptor and blanking plug do not  
protrude, and finish flush with the inner face of  
the housing.  
T00238  
If fitting a tamperproof fixed head, refer to  
‘Fitting the tamperproof fixed head’ section and  
complete the outlet pipework as follows:  
determine the required height of pipe and cut to  
size. Slide nut cover onto the pipe, followed by  
nut and olive. Insert the pipe into outlet adaptor,  
place the outlet trim onto the adaptor and fully  
tighten the compression nut (fig.ꢀ9).  
Outlet  
trim  
Before securing the tamperproof fixed head to  
the wall, connect a hose to the pipework and  
direct to waste.  
If fitting a riser rail, connect the shower hose to  
the outlet and direct to waste.  
0239  
Open the isolating valves to the shower and  
flush through making sure the flow control  
is opened fully and the temperature control  
is rotated to ‘HOT’ and then to ‘cOld’ (if  
necessary depress the maximum temperature  
override button). check for any leaks and  
remedy if necessary.  
Slide the outlet blanking trim onto the cover  
where it is required i.e. bottom outlet for fixed  
head, top outlet for a hose (fig.ꢁ0).  
Fit the cover on and secure with two screws  
(fig.ꢁꢀ). locate the lugs on the trim ring in the  
holes on the cover and twist clockwise (fig.ꢁꢁ).  
Finally, pull nut covers over nuts.  
T00240  
complete the fitting of the shower accessories  
by referring to the appropriate section.  
T00241  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Combi HP thermostatic mixer shower  
Rear entry supplies  
Fig.ꢁꢁ  
Note: The final separation between pipe  
centres needs to be about 153 mm but absolute  
accuracy is not essential as the inlet elbows  
are adjustable between 146 mm and 160 mm  
(fig.ꢁꢂ).  
using a spirit level, mark the route of incoming  
hot and cold water supply pipes at a distance of  
153 mm centres.  
Remove the plaster and brickwork to the  
required depth to conceal the supply pipework.  
Note: It is advisable that pipework installed  
in solid walls be provided with enough free  
play inside a cavity to allow entry into the inlet  
elbows for tightening, before securing the valve  
to the finished wall surface.  
T00242  
Install the hot and cold pipework — the hot pipe  
must enter from the left. Make sure the finished  
pipework projects from the front face of the tiled  
surface of the wall by 9.5 mm (fig.ꢁꢃ).  
Fig.ꢁꢂ  
Allow for two circular recesses measuring 32 mm  
diameter by 14 mm depth, to accept the rear  
entry pipe trims (fig.ꢁꢂ).  
m
.
32 m  
dia  
m approx  
Flush pipework to clear the system of all  
debris and check for leaks.  
153 m  
9.5 mm  
ImportaNt: The inlet elbows contain check  
valves that may be damaged if debris is not  
flushed through prior to fitting.  
where this is not possible refer to the ‘flushing  
procedure’ on page 20.  
T00243  
Make good the wall and complete the tiling.  
check that the rear entry pipe trims are sealed in  
with either silicon sealant or grout (fig.ꢁꢃ).  
Fig.ꢁꢃ  
Pipe  
trim  
Note: Failure to fit the rear entry pipe trims  
could result in the entry of water into the wall  
cavity.  
Inlet  
nut  
Offer the valve, together with the inlet elbows,  
to the pipework making sure the inlet elbow  
grub screws are slack allowing the inlet elbows  
to be rotated to the correct position and move  
freely in and out of the valve housing (fig.8).  
check that the valve is central between the  
two pipes, then mark two diagonal fixing holes  
(figs.ꢁꢄ and ꢁꢅ).  
9.5  
mm  
T00244  
ꢀ0  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Combi HP thermostatic mixer shower  
Remove the valve. drill and plug the holes using  
Fig.ꢁꢄ  
Fig.ꢁꢅ  
Fig.ꢁ7  
the wall plugs supplied.  
=
using two hexagonal nuts (supplied), refit the  
valve to the pipework. Make sure the hot inlet  
port (marked with the letter ‘H’ on the valve  
housing) is connected to the hot pipework  
which must be on the left.  
=
Tighten the inlet nuts with the spanner supplied  
(fig.ꢁ7) then tighten the inlet elbow grub  
screws.  
Screw to the wall with the screws supplied.  
If installing a tamperproof fixed head, fit the  
outlet adaptor into the top outlet hole in the  
valve housing (fig.ꢀꢅ). The adaptor is sealed  
with an ‘O’ ring. Make sure the adaptor is fitted  
with the hose end in the valve housing (fig.ꢀ7).  
Fit the blanking plug into the bottom outlet hole  
using an ‘O’ ring to seal it.  
T00245  
T00246  
=
If installing a riser rail, fit the outlet adaptor into  
the bottom outlet hole in the valve housing. The  
adaptor is sealed with an ‘O’ ring. Make sure the  
adaptor is fitted with the pipe end in the valve  
housing (fig.ꢀ7).  
=
Fit the blanking plug into the top outlet hole  
using an ‘O’ ring to seal it (fig.ꢀ8).  
If fitting a tamperproof fixed head, refer to  
‘Fitting the tamperproof fixed head’ section and  
complete the outlet pipework as follows:  
determine the required height of pipe and cut to  
size if necessary. Slide nut cover on to the pipe,  
followed by nut and olive. Insert pipe into outlet  
adaptor, place the outlet trim onto the adaptor  
and fully tighten the compression nut (fig.ꢀ9).  
Before securing the fixed head to the wall,  
connect a hose to the pipework and direct to  
waste.  
If fitting a riser rail, connect the shower hose to  
the outlet and direct to waste.  
Open the isolating valves to the shower and  
flush through, making sure the flow control  
is opened fully and the temperature control  
is rotated to ‘HOT’ and then to ‘cOld’ (if  
necessary depress the maximum temperature  
override button). check for any leaks and  
remedy if necessary.  
Slide the outlet blanking trim onto the cover  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Combi HP thermostatic mixer shower  
where it is required i.e. bottom outlet for fixed  
Fig.ꢁ8  
head, top outlet for a hose (fig.ꢁ0).  
Fit the inlet blanking trims on the underside of  
the cover (fig.ꢁ8).  
Fit the outlet trim over the outlet adaptor and  
slide the cover on (fig.ꢀ9). Secure the cover  
with two screws (fig.ꢁꢀ). locate the lugs on  
the trim ring in the holes on the cover and twist  
clockwise (fig.ꢁꢁ).  
complete the fitting of your shower accessories.  
Note: The flush-fitted shower valve comes  
complete with a built-in pvc shroud. DO NOT  
remove it. It is important when making good  
the wall after installation, the plastering and  
sealing must be made tight up to the shroud in  
order to prevent ingress of water.  
ꢀꢁ  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Combi HP thermostatic mixer shower  
FITTING THE SHOWER TO THE WALL  
Flush fit  
Fig.ꢁ9  
Note: The outlet of the shower must not be  
connected to anything other than the hose,  
showerhead or fixed showerhead supplied.  
220 mm  
77.5 m  
dO nOT use jointing compounds on any pipe  
fittings for the installation.  
m
dO nOT solder fittings near of the shower unit,  
as heat transfer can damage components.  
65  
mm  
m
m
35 m  
20  
Note: Suitable isolating valves (complying with  
water Regulations) must be fitted on the hot  
and cold water supplies to the shower as an  
independent means of isolating water supplies  
should maintenance or servicing be necessary.  
m
Opening needs  
to be at the bottom  
if using a bulkhead  
48 m  
m
when connecting pipework avoid using tight  
90° elbows. Swept or formed bends will give the  
best performance.  
10 -  
12.5  
m
50 m  
m
ImportaNt: The water circuit should be  
installed such that the flow is not significantly  
affected by other taps and appliances being  
operated elsewhere on the premises. Water  
pressure must not fall below the specification  
of the valve.  
m
T00249  
The hot water pipe entry must be on the left-  
hand side.  
Fig.ꢂ0  
This mixer valve also includes a wall bracket  
which allows the installer to mount the shower  
into a solid, stud partition or other hollow wall  
structures. The bracket can also be used for  
fitting in a shower cubicle providing the back of  
the cubicle is accessible.  
when installing into a stud partition or other  
hollow wall structure the installer may wish to  
consider building rear supports or other options.  
Such options are beyond the scope of this guide.  
Solid wall  
The building-in depth for the shower into a  
solid wall is between 57 mm and 66 mm. The  
building-in depth calculation must include the  
thickness of the plaster and tiles. This dimension  
determines how much of the shower control is  
visible through the concealing plate when the  
installation is completed.  
decide on the shower position and whether  
the hot and cold water supplies will enter the  
T00250  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Combi HP thermostatic mixer shower  
shower from the top (falling), the bottom (rising)  
Fig.ꢂꢀ  
or the rear.  
Mark the route of the incoming and outgoing  
pipework.  
Note: The final separation between pipe  
centres needs to be about 153 mm but absolute  
accuracy is not essential as the inlet elbows are  
adjustable between 146 mm and 160 mm.  
Remove the plaster and brickwork to the depth  
shown (fig.ꢁ9). where applicable, chase out  
any additional areas of the wall for the pipework  
to either the bulkhead or fixed head.  
Offer the mounting bracket up to the wall and  
mark the two plain fixing holes (fig.ꢂ0). drill  
and plug then screw bracket to the wall.  
T00251  
Note: The valve can be fitted to the mounting  
bracket if required or secured directly to the wall  
with the screws supplied.  
Fig.ꢂꢁ  
If installing a fixed head, the outlet adaptor  
needs to be fitted into the top outlet hole in the  
valve housing (fig.ꢀꢅ). The adaptor is sealed  
with an ‘O’ ring. Make sure the adaptor is fitted  
with the hose end (fig.ꢀ7) in the valve housing.  
Fit the blanking plug into the bottom outlet hole  
using an ‘O’ ring to seal it.  
If fitting a bulkhead outlet, the outlet adaptor  
needs to be fitted into the bottom outlet hole in  
the valve housing. The adaptor is sealed with an  
‘O’ ring. Make sure the adaptor is fitted with the  
hose end in the valve housing (fig.ꢀ7).  
T00252  
Fit the blanking plug into the top outlet hole  
using an ‘O’ ring to seal it (fig.ꢀ8).  
Fig.ꢂꢂ  
Seal tight up  
to shroud  
Make sure the inlet elbows are positioned  
correctly. Offer the valve up to the mounting  
bracket or wall surface, and secure using the  
screws provided (fig.ꢂꢀ).  
complete the pipework to the shower marking  
off the length to enter the elbows. Remove the  
valve and cut the pipes to length.  
Flush pipework to clear the system of all debris  
and check for leaks.  
ImportaNt: The inlet elbows contain check  
valves that may be damaged if debris is not  
flushed through prior to fitting.  
T00253  
ꢀꢃ  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Combi HP thermostatic mixer shower  
where this is not possible refer to the ‘flushing  
Fig.ꢂꢃ  
Fig.ꢂꢄ  
Fig.ꢂꢅ  
procedure’ on page 20.  
Refit the valve to the mounting bracket/wall  
surface and pipework (fig.ꢂꢁ). Tighten the inlet  
nuts and inlet elbow grub screws.  
If fitting a fixed head, refer to the ‘Fitting the  
fixed head’ section and complete the outlet  
pipework to the fixed head position.  
Note: The outlet pipe for the fixed head should  
protrude from the surface of the wall between  
50 mm and 65 mm. Before fitting the fixed head  
to the wall, connect a hose to the pipework and  
direct to waste.  
If fitting a riser rail kit, refer to ‘Fitting the  
bulkhead’ and complete outlet pipework.  
T00254  
T00255  
T00256  
Before fitting the bulkhead to the wall connect  
the shower hose and direct it to waste.  
Open the isolating valves to the shower and  
flush through checking that the flow control  
is opened fully and the temperature control  
is rotated to ‘HOT’ and then to ‘cOld’ (if  
necessary depress the maximum temperature  
override button). check for leaks and remedy if  
necessary.  
If a fixed head is installed, make good the outlet  
pipe channel.  
Note: If fitting a fixed head, the tiling around  
the outlet pipe must be as tight as possible so  
that the special lock washer will seat, otherwise  
a larger diameter washer will have to be placed  
behind the lock washer.  
Make good the wall surface around the valve  
and make sure the plastering/sealing is taken  
tight to the PVc shroud (fig.ꢂꢂ).  
Should the shroud protrude beyond the wall  
surface, trim flush with a sharp knife (fig.ꢂꢃ).  
Offer the flush mount plate up to the finished  
tile surface and making sure the valve and plate  
are aligned, mark the ‘arrowed’ fixing holes  
(fig.ꢂꢄ). Remove the flush mount plate then  
drill and plug holes.  
Break off the alignment tabs on the flush mount  
plate (fig.ꢂꢅ). Place a ring of silicon sealant  
round the plate so that the plate seals against  
the wall. Secure the plate to the wall using the  
screws provided. wipe off any excess sealant.  
Alignment  
tab  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Combi HP thermostatic mixer shower  
Fit the flush mount cover (fig.ꢂ7). locate the  
Fig.ꢂ7  
lugs on the trim ring in the holes on the cover  
(fig.ꢂ8) and twist clockwise.  
complete the fitting of your shower accessories.  
Hollow wall  
The wall mounting bracket supplied with the  
shower is suitable for use on a plasterboard wall  
of 9.5 mm or 12.5 mm in thickness.  
decide on the shower position and whether  
the hot and cold water supplies will enter the  
shower from the top (falling), the bottom (ris-  
ing) or the rear.  
Mark an opening as shown plus the route of  
T00257  
inlet and outlet pipework (fig.ꢂ9).  
Note: The final separation between pipe  
centres needs to be about 153 mm but absolute  
accuracy is not essential as the inlet elbows are  
adjustable between 146 mm and 160 mm.  
Fig.ꢂ8  
Take out the plasterboard and offer the  
mounting bracket up to the wall (fig.ꢃ0). Mark  
the outer fixing holes and drill. Insert the wall  
bracket into wall cavity and secure using the  
bolts and washers provided (fig.ꢃꢀ).  
If a fixed head is to be installed, the outlet  
adaptor needs to be fitted into the top outlet  
hole in the valve housing (fig.ꢀꢅ). The adaptor  
is sealed with an ‘O’ ring. Make sure the adaptor  
is fitted with the hose end in the valve housing  
(fig.ꢀ7). Fit the blanking plug into the bottom  
outlet hole using an ‘O’ ring to seal it.  
T00258  
If a bulkhead outlet is to be fitted, the outlet  
adaptor needs to be fitted into the bottom  
outlet hole in the valve housing. The adaptor is  
sealed with an ‘O’ ring (fig.ꢀꢅ). Make sure the  
adaptor is fitted with the hose end in the valve  
housing (fig.ꢀ7). Fit the blanking plug into  
the top outlet hole using an ‘O’ ring to seal it  
(fig.ꢀ8).  
Fig.ꢂ9  
77.5 mm  
65 mm  
77.5 mm  
35 mm  
If installing a fixed head, make a hole in the wall  
for the fixed head pipe.  
Opening needs  
to be at the bottom  
if using a bulkhead  
115 mm  
Note: If fitting a fixed head, the hole in the wall  
for the pipe must be close to 15 mm diameter as  
possible. It must not exceed the diameter of the  
special lock washer, otherwise a larger diameter  
washer will have to be placed behind the lock  
220 mm  
T00259  
ꢀꢅ  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Combi HP thermostatic mixer shower  
washer.  
Fig.ꢃ0  
Fig.ꢃꢀ  
Fig.ꢃꢁ  
Make sure the inlet elbows are positioned the  
correct way. Offer the valve up to the mounting  
bracket and secure using the screws provided  
(fig.ꢃꢁ).  
complete the pipework to the shower marking  
off the length to enter the elbows. Remove the  
valve and cut the pipes to length.  
Flush pipework to clear the system of all  
debris and check for leaks.  
ImportaNt: The inlet elbows contain check  
valves that may be damaged if debris is not  
flushed through prior to fitting.  
where this is not possible refer to the ‘flushing  
procedure’ on page 20.  
T00260  
Refit the valve to the mounting bracket and  
pipework. Tighten the inlet nuts and inlet elbow  
grub screws.  
If fitting a fixed head, refer to the ‘Fitting the  
fixed head’ section and complete the outlet  
pipework to the fixed head position.  
Note: The outlet pipe for the fixed head should  
protrude from the surface of the wall between  
50 mm and 65 mm. Before fitting the fixed head  
to the wall, connect a hose to the pipework and  
direct to waste.  
If fitting a riser rail kit refer to ‘Fitting the  
bulkhead’ and complete the outlet pipework.  
Before fitting the bulkhead to the wall, connect  
the shower hose and direct it to waste.  
T00261  
Open the isolating valves to the shower and  
flush through. Make sure the flow control  
is opened fully and the temperature control  
is rotated to ‘HOT’ and then to ‘cOld’ (if  
necessary depress the maximum temperature  
override button). check for leaks and remedy if  
necessary.  
Make good the wall surface and make sure  
the plastering/sealing is taken tight to the PVc  
shroud (fig.ꢃꢂ). Should the shroud protrude  
beyond the wall surface, trim flush with a sharp  
knife (fig.ꢂꢃ).  
Offer the flush mount plate up to the finished  
surface. Make sure the valve and the plate are  
aligned and mark the ‘arrowed’ fixing holes  
(fig.ꢂꢄ). Remove the flush mount plate then  
T00262  
Download from Www.Somanuals.com7. All Manuals Search And Download.  
Combi HP thermostatic mixer shower  
drill and plug the holes.  
Fig.ꢃꢂ  
Seal tight up  
to shroud  
Note: If fitting to plasterboard, use suitable  
cavity fixings.  
Break off the alignment tabs on the flush mount  
plate (fig.ꢂꢅ). Place a ring of silicon sealant  
round the plate so that the plate seals against  
the wall. Secure the plate to the wall using the  
screws provided. wipe off any excess sealant.  
Fit the flush mount cover (fig.ꢂ7). locate the  
lugs on the trim ring in the holes on the plate  
and twist clockwise (fig.ꢂ8).  
complete the fitting of your shower accessories  
by referring to the appropriate section.  
T00253  
Shower cubicle or panel  
To use the wall mounting bracket supplied with  
a shower cubicle or a laminated panel, wooden  
blocks are required to increase the depth of the  
bracket. These blocks need to increase the depth  
of the bracket to between 56 mm and 67 mm  
from the finished surface (fig.ꢃꢃ).  
Fig.ꢃꢃ  
decide on the shower position and whether  
the hot and cold water supplies will enter the  
shower from the top (falling), the bottom (rising)  
or the rear.  
ꢀꢁꢂꢃꢂꢁꢄꢂPP  
Mark the wall for an opening of about 93 mm  
diameter.  
cut the opening and offer the mounting bracket  
up to the back of the panel (fig.ꢃꢄ). Mark  
the inner fixing holes and drill the panel and  
wooden support blocks.  
T00263  
If installing a fixed head, fit the outlet adaptor  
into the top outlet hole in the valve housing  
(fig.ꢀꢅ). The adaptor is sealed with an ‘O’  
ring. Make sure the adaptor is fitted with the  
hose end in the valve housing (fig.ꢀ7). Fit the  
blanking plug into the bottom outlet hole using  
an ‘O’ ring to seal it.  
Fig.ꢃꢄ  
3ODWHꢀIL[LQJ  
KROH  
0DUNꢀERWK  
KROHV  
If installing a bulkhead outlet, fit the outlet  
adaptor into the bottom outlet hole in the valve  
housing. The adaptor is sealed with an ‘O’ ring.  
%UDFNHW  
IL[LQJꢀKROH  
Make sure the adaptor is fitted with the hose  
end in the valve housing (fig.ꢀ7). Fit the  
blanking plug into the top outlet hole using an  
‘O’ ring to seal it (fig.ꢀ8).  
9LHZꢀIURP  
EHKLQGꢀSDQHO  
T00264  
Make sure that the inlet elbows are facing the  
ꢀ8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Combi HP thermostatic mixer shower  
correct way. Offer the valve up to the mounting  
Fig.ꢃꢅ  
Fig.ꢃ7  
Fig.ꢃ8  
Fig.ꢃ9  
bracket and secure using the screws provided.  
Secure the mounting bracket together with  
the valve to the panel using two bolts in the  
innermost fixing holes (fig.ꢃꢅ).  
complete the pipework to the shower marking  
off the length to enter the elbows. Remove the  
valve and mounting bracket and cut the pipes  
to length.  
If fitting a fixed head, make a hole in the panel  
for the fixed head position.  
T00265  
T00266  
T002
T00268  
Note: Make sure the hole in the panel for the  
outlet pipe is no larger than required (either  
½” BSP or 15 mm).  
Should the shroud protrude beyond the wall  
surface, trim flush with a sharp knife (fig.ꢂꢃ).  
Place a ring of silicon sealant round the flush  
mount plate up to the finished surface. Make  
sure the valve and plate are aligned, and secure  
in the outer fixing holes using the two bolts  
supplied (fig.ꢃ7).  
Break off the alignment tabs on the flush mount  
plate (fig.ꢂꢅ) and fit the flush mount cover  
(fig.ꢃ8).  
locate the lugs on the trim ring in the holes on  
the cover and twist clockwise (fig.ꢃ9).  
complete the fitting of your shower accessories.  
Download from Www.Somanuals.com9. All Manuals Search And Download.  
Combi HP thermostatic mixer shower  
FLUSHING PROCEDURE  
Removal and/or fitting of check valves  
for maintenance  
Fig.ꢄ0  
ImportaNt: It is preferable to flush the  
pipework before installing the valve. Where  
this is not possible, the procedure using a  
flushing cartridge should be followed.  
a. Isolate the supplies.  
b. Remove the trim ring by twisting anti-  
clockwise.  
c. Remove the valve cover.  
d. Remove the four screws holding the valve  
cartridge, and carefully remove the cartridge  
assembly from housing (fig.ꢄ0).  
T00269  
Fig.ꢄꢀ  
e. Insert the plastic tool provided into the inner  
sleeve located inside the elbow and twist  
anti-clockwise (fig.ꢄꢀ). Take care not to  
damage the check valve.  
Note: The sleeve may stick, in which case  
it must be carefully hooked out using a  
suitable tool such as an allen key.  
T00270  
f. Push the flushing cartridge into the housing  
(fig.ꢄꢁ). Attach a hose to the flushing  
cartridge outlet and make sure it is directed  
to waste. Flush the pipes clean.  
Fig.ꢄꢁ  
g. wash out the sleeve and check valve. Take  
care not to damage them.  
h. Replace the check valve into the sleeve,  
making sure it is in the correct way (fig.ꢄꢂ).  
i. Refit sleeve into the elbow. carefully replace  
the valve cartridge and refit the cover.  
j. Reinstate supplies and test the valve  
operation.  
Note: It may be necessary to service the check  
valves at regular intervals to prevent cross flow  
of water.  
T00271  
Note: Flushing cartridges and replacement  
check valve tools are available from Triton  
customer Service.  
Fig.ꢄꢂ  
Flush the pipework to clear system of debris  
and check for leaks.  
T00272  
ꢁ0  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Combi HP thermostatic mixer shower  
FITTING THE TAMPERPROOF FIXED  
HEAD  
(Exposed option only)  
Fig.ꢄꢃ  
Fig.ꢄꢄ  
Fig.ꢄ7  
Fig.ꢄ8  
complete the outlet pipework from the valve  
and cut the pipe to required length.  
Place the fixed head unit on top of the pipe  
work and mark the position of the three fixing  
holes (fig.ꢄꢃ).  
drill and plug the holes using the plugs supplied.  
Secure the pipe to the fixed head unit using the  
compression nut and olive supplied (fig.ꢄꢄ).  
T00273  
Secure the fixed head to the wall with the three  
screws supplied (fig.ꢄꢅ).  
Screw on the adjustable showerhead. Make  
sure the supplied flat sealing washer is in place  
(fig.ꢄ7).  
Note: The showerhead must be screwed on  
tight to make sure of a watertight connection.  
use a suitable tool if necessary.  
using the allen key supplied, lock the  
showerhead in position by tightening the grub  
screw (fig.ꢄ8).  
T00274  
Fig.ꢄꢅ  
Sealing  
washer  
T00275  
T00277  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Combi HP thermostatic mixer shower  
FITTING THE TAMPERPROOF FIXED  
HEAD  
(Built in option only)  
Fig.ꢄ9  
Fig.ꢅ0  
Wall  
surface  
complete outlet pipework from the valve  
ending in a ½” BSP female threaded fitting (not  
supplied) (fig.ꢄ9).  
Note: The depth of thread on the fixed head  
unit from wall surface is 18 mm (fig.ꢅ0). It is  
advisable that pipework installed in solid walls be  
provided with enough free play inside a cavity to  
allow any slack to be accommodated.  
18  
mm  
8  
T00279  
Make good the wall  
Fig.ꢅꢀ  
Fig.ꢅꢁ  
Screw the fixed head assembly to the female  
fitting. Screw tight to the wall and make sure  
fixed head is in the correct attitude.  
Mark the position of the three fixing holes  
(fig.ꢅꢀ). Remove the fixed head. drill and plug  
the holes using the plugs supplied.  
Screw the fixed head assembly to the female  
fitting using PTFE tape to seal the joint. Secure  
the fixed head to the wall with the three screws  
supplied (fig.ꢅꢁ).  
T00280  
T00281  
Screw on the adjustable showerhead, making  
sure the supplied flat sealing washer is in place  
(fig.ꢅꢂ).  
Fig.ꢅꢂ  
Sealing  
washer  
Note: The showerhead must be screwed on  
tight in order to make sure of a watertight  
connection. use a suitable tool if necessary.  
using an allen key, lock the showerhead in  
position by tightening the grub screw (fig.ꢅꢃ).  
T00282  
Fig.ꢅꢃ  
T00283  
ꢁꢁ  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Combi HP thermostatic mixer shower  
FITTING THE FIXED HEAD  
(Built in option only)  
Fig.ꢅꢄ  
The outlet pipe should protrude from the  
surface of the wall between 50 mm and 65 mm  
(fig.ꢅꢄ).  
50 mm – 65 mm  
Mark four fixing hole positions by using the fixed  
arm as a template. drill and plug the wall using  
the plugs supplied. care must be taken not to  
drill into the buried pipework.  
Outlet pipe  
Remove burrs on the pipework to prevent  
damage to the ‘O’ ring.  
T00284  
Slide the special lock washer over the pipe and  
push it tight to the wall.  
Fig.ꢅꢅ  
Note: Make sure the lock washer is placed on  
the pipe correctly with the inscription ‘FROnT’  
facing away from the wall. This washer holds the  
pipe in position.  
50 mm – 65 mm  
Trim  
Fixed arm  
'O' ring  
Slide the bushing over the pipe and push it tight  
against the wall.  
Slide the ‘O’ ring onto the pipe up against the  
bushing.  
Push the fixed arm assembly onto the pipe tight  
to the wall. An automatic watertight seal is thus  
created.  
Special lock washer  
Bushing  
Secure to the wall with the four fixing screws  
supplied. Push-fit the trim into place (fig.ꢅꢅ).  
T00285  
Finally, screw on the adjustable showerhead  
making sure the sealing washer is in place  
(fig.ꢅ7). Screw on tight to make sure of a  
watertight connection.  
Fig.ꢅ7  
Turn on the water supplies.  
Washer  
T00286  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Combi HP thermostatic mixer shower  
FITTING THE BULKHEAD  
(Riser rail option only)  
Fig.ꢅ8  
complete the outlet pipework ending in a  
½" x 15 mm female thread fitting (fig.ꢅ8).  
Note: This fitting is not supplied as variations  
in installations needs the selection of the most  
suitable fitting.  
Appropriate  
fitting  
Screw the supplied male-thread connector into  
the female fitting using PTFE tape to make sure  
of a watertight joint (fig.ꢅ9).  
T000
Note: The supplied male-thread connector has  
a nutted shoulder. If fitting to a flush wall, make  
an additional 8 mm allowance for this shoulder  
at the finished surface. The connector can be cut  
to size if required.  
Fig.ꢅ9  
The threaded connector should protrude from  
the wall surface between 8 mm and 13 mm.  
Make good the wall.  
Finished surface  
8mm 13mm  
Screw the bulkhead elbow to the threaded  
connector using PTFE tape to seal the thread  
(fig.70).  
T00082  
Slide the bulkhead over the elbow, offer up  
to the wall and mark the two fixing holes for  
securing the bulkhead to the wall (fig.7ꢀ).  
Fig.70  
Fig.7ꢀ  
Remove the bulkhead then drill and plug the  
holes using the plugs supplied.  
Refit the bulkhead and secure to the elbow using  
two screws (fig.7ꢁ).  
Secure the bulkhead to the wall using the two  
fixing screws supplied. Push on the trim disc  
making sure the two location lugs locate in the  
small holes as shown (fig.7ꢂ).  
T00288  
Fig.7ꢁ  
Fig.7ꢂ  
T00290  
T00289  
ꢁꢃ  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Combi HP thermostatic mixer shower  
OPERATING THE SHOWER  
Make sure all plumbing supplies are connected  
and turned on.  
Fig.7ꢃ  
Starting the shower  
To start the shower, turn the outer knob (flow  
control) anti-clockwise (fig.7ꢃ).  
Adjusting the shower temperature  
To adjust the temperature, turn the inner  
knob — temperature control (fig.7ꢄ). The  
temperature disc is numbered for ease of use  
and ranges from 1 (fully cold) to 10 (fully hot).  
Flow control  
T00291  
T00292  
T00293  
T00294  
Fig.7ꢄ  
Once at the preferred temperature, no further  
adjustment is required, providing the hot and  
cold water supplies remain constant.  
Stopping the shower  
To stop the shower, turn the flow control  
clockwise to the stop position (fig.7ꢅ). This  
automatically stops the water flow.  
As a safety measure the shower has a built-  
in maximum temperature stop to prevent  
accidentally exceeding the highest desired  
temperature. The stop comes in a factory set  
position. (If adjustment is required see ‘Adjusting  
the maximum temperature stop’ on page 26).  
Temperature  
control  
Fig.7ꢅ  
To override this stop, depress the button and  
turn the control clockwise to the higher settings  
(fig.77). To return to the normal temperature  
range just turn the temperature control  
anti-clockwise until it is past the maximum  
temperature stop.  
Make sure that the temperature control is in the  
normal temperature range when the shower is  
turned off.  
Flow control  
Fig.77  
Maximum  
temperature  
override  
button  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Combi HP thermostatic mixer shower  
ADJUSTING THE MAXIMUM  
TEMPERATURE STOP  
Fig.78  
As a safety measure the shower has a built-in  
maximum temperature stop to prevent you  
accidentally exceeding your highest desired  
temperature. This is set in the factory to provide  
a maximum temperature of 42°c based on the  
hot and cold water supplies being 65°c and  
15°c respectively at nominally equal pressures.  
Procedure  
To adjust the maximum temperature stop, first  
rotate the temperature knob to the 12 o’clock  
position.  
Remove the temperature knob trim using a thin  
T00295  
bladed screwdriver (fig.78).  
unscrew the central fixing screw and remove  
the temperature control knob (fig.79). now  
remove the temperature control disc, together  
with the wavy washer. The control disc houses  
the maximum temperature stop mechanism  
(fig.80).  
Fig.79  
Temperature  
control disc  
To increase the temperature stop setting,  
reposition the temperature stop mechanism  
clockwise within the arc of the grooves (fig.80).  
Fixing screw  
To decrease the temperature stop setting,  
reposition the stop mechanism anti-clockwise  
within the arc of the grooves.  
Temperature  
control knob  
when the stop mechanism is set at the preferred  
position, refit the temperature control disc  
T00296  
making sure the name ‘TriTonis at the bottom.  
Replace the wavy washer, then refit the  
temperature control knob, making sure it is  
replaced in the same attitude as when removed  
(i.e. 12 o’clock position).  
Fig.80  
7HPSHUDWXUHꢀFRQWUROꢀGLVF  
*URRYHV  
Refit the central screw and replace the knob  
trim.  
ImportaNt: Only adjust the maximum  
temperature stop when the hot water is at its  
usual supply temperature.  
0D[LPXPꢀWHPSHUDWXUHꢀVWRSꢀPHFKDQLVP  
ꢁ'HFUHDVHꢀVWRSꢀSRVLWLRQꢂꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢁ,QFUHDVHꢀVWRSꢀSRVLWLRQꢂꢀ  
T00297  
ꢁꢅ  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Combi HP thermostatic mixer shower  
SPARE PARTS  
Ref. Description  
Part No.  
3
1. HP valve cartridge  
(built-in valve)  
83304970  
4
2. HP cartridge and brass housing  
(exposed valve)  
83304960  
6
2
3. Outlet adaptor  
chrome  
1
7031462  
7031463  
gold  
7
4. Inlet elbow assembly  
5. Outlet blanking plug  
6. cartridge ‘O’ rings  
7. Knob set − white  
8. Knob trim  
83303810  
7031460  
83303710  
83304810  
7051466  
4
6
5
2
8
9. cover shroud  
white (exposed valve)  
chrome (exposed valve)  
gold (exposed valve)  
7041444  
7041445  
7041446  
9
10. Trim ring  
white  
7051441  
7051442  
7051443  
7051477  
chrome  
gold  
gold (flush)  
10  
12  
11. Trim sets  
white  
83303680  
83303670  
83303690  
chrome  
gold  
11  
12. cover plate  
white (built-in valve)  
chrome (built-in valve)  
gold (built-in valve)  
7051448  
7051449  
7051450  
13. Mounting plate  
13  
(built-in valve)  
7051447  
Outlet pipe  
white  
TAS00404  
TAS00004  
TAS00304  
chrome effect  
gold effect  
10  
T00298  
Download from Www.Somanuals.com7. All Manuals Search And Download.  
Combi HP thermostatic mixer shower  
SPARE PARTS  
Ref. Description  
Part No.  
14  
15  
14. Bulkhead assembly  
white  
chrome effect  
gold effect  
83303780  
83303770  
83303790  
Trim disc  
(use with flush gold effect)  
7051451  
83303660  
7011766  
22003530  
83303810  
7011453  
7051476  
7052032  
15. Inlet & outlet nuts  
16. Spanner  
16  
17  
19  
Flow regulator  
17. check valve/sleeve assembly  
18. wall bracket  
19. check valve tool  
18  
20. Flushing cartridge  
(available on request)  
21. nutted male thread fitting  
7032915  
20  
22. Tamperproof fixed head  
built-in  
96200250  
23. Tamperproof fixed head  
exposed  
96200240  
22450060  
22009490  
Fixed head assembly − white  
Fixing kit  
21  
22  
Flexible hoses available in the following  
sizes:  
1.00 m in white, chrome and gold  
1.25 m in white, chrome and gold  
1.75 m in chrome only  
PVc shroud (flush fit only)  
Screw pack  
7052165  
83303800  
23  
Extended control lever  
(can be fitted easily to make the controls  
easier to use. Available on request from  
Triton customer Service).  
T00299  
ꢁ8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Combi HP thermostatic mixer shower  
FAULT FINDING  
Action/Cure  
Problem/Symptom  
Cause  
1
2
3
Water too hot.  
1.1 Not enough cold 1.1.1 Turn the control knob anti-clockwise.  
water flowing  
through shower.  
1.2 Increase in the  
ambient cold  
water  
1.2.1 Turn the control anti-clockwise.  
temperature.  
1.3 High volume of  
cold water  
1.3.1 Reduce the simultaneous demand from  
supply — make sure a dedicated supply  
to mixer.  
drawn off  
elsewhere.  
1.4 Excessive flow  
1.4.1 Contact Customer Service for advice on  
rate.  
flow regulators.  
1.5 Dirty check  
1.5.1 Clean – refer to ‘Flushing Procedure’.  
valves.  
Water too cold.  
2.1 Not enough hot  
water flowing  
2.1.1 Turn the temperature control clockwise.  
(Override the max. temperature stop if  
necessary).  
through shower.  
2.2 Decrease in the  
ambient cold  
water  
2.2.1 Turn the temperature control clockwise.  
(Override the max. temperature stop if  
necessary).  
temperature.  
2.3 Not enough hot  
water supplied  
from the heating  
appliance.  
2.3.1 Make sure heating cylinder is set to  
maximum hot water output.  
2.4 Excessive flow  
2.4.1 Contact Triton Customer Service for  
rate.  
advice on flow regulators.  
2.5 Dirty check  
2.5.1 Clean – refer to ‘Flushing Procedure’.  
valves.  
Water does not  
flow or shower  
pattern collapses  
when another  
3.1 Water supplies  
3.1.1 Check water elsewhere in house and if  
cut off.  
necessary contact local water company.  
3.2 Shower unit  
3.2.1 Inspect the flow regulators (if fitted) and  
the check valves – refer to ‘Flushing  
Procedure’. Clean if necessary.  
outlet is turned on.  
blocked.  
X-006-A  
3.3 Showerhead  
3.3.1 Clean showerhead.  
blocked.  
3.4 Reduced flow  
rate when other  
outlets in use.  
3.4.1 Reduce the simultaneous demand —  
make sure a dedicated supply to mixer.  
3.4.2 Make sure service valves are fully open.  
Download from Www.Somanuals.com9. All Manuals Search And Download.  
Combi HP thermostatic mixer shower  
FAULT FINDING  
Problem/Symptom  
Cause  
Action/Cure  
4
Water too cold or  
too hot.  
4.1 Water supply  
blocked or  
4.1.1 Turn off the shower and consult a  
competent plumber or contact Triton  
Customer Service.  
restricted.  
5
Water does not  
flow or shower  
pattern collapses  
when another  
5.1 Blockage in  
5.1.1 Turn off the shower and consult a  
pipework.  
suitably competent plumber.  
outlet is turned on.  
6
Shower will not  
shut off.  
6.1 Pipework not  
flushed before  
connecting the  
unit(‘O’ rings  
damaged).  
6.1.1 Renew cartridge (internal seals are not  
serviceable).  
Any maintenance or repair to the shower must be carried out by a suitably  
qualiedperson  
ꢂ0  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Combi HP thermostatic mixer shower  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Combi HP thermostatic mixer shower  
ꢂꢁ  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Combi HP thermostatic mixer shower  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Service Policy  
TRiTon STandaRd GuaRanTee  
In the event of a complaint occurring, the following  
procedure should be followed:  
Triton guarantee this product against all mechanical  
defects arising from faulty workmanship or materials  
for a period of three years for domestic use only,  
from the date of purchase, provided that it has been  
installed by a competent person in full accordance  
with the fitting instructions.  
Any part found to be defective during this  
guarantee period we undertake to repair or replace  
at our option without charge so long as it has been  
properly maintained and operated in accordance  
with the operating instructions, and has not been  
subject to misuse or damage.  
This product must not be taken apart, modified or  
repaired except by a person authorised by Triton.  
This guarantee applies only to products installed  
within the United Kingdom and does not apply to  
products used commercially. This guarantee does  
not affect your statutory rights.  
1 Telephone Customer Service on  
0870 067 3333 (0845 762 6591 in Scotland and  
in Northern Ireland), having available the model  
number and power rating of the product, together  
with the date of purchase.  
2 Triton Customer Service will be able to confirm  
whether the fault can be rectified by either the  
provision of a replacement part or a site visit  
from a qualified Triton service engineer.  
3
If a service call is required the unit must be fully  
installed for the call to be booked and the date  
confirmed. In order to speed up your request,  
please have your postcode available when  
booking a service call.  
4 It is essential that you or an appointed  
representative (who must be a person of 18 years  
of age or more) is present during the service  
engineer's visit and receipt of purchase is shown.  
What is not covered:  
1 Breakdown due to: a) use other than domestic  
use by you or your resident family;  
5 A charge will be made in the event of an aborted  
service call by you but not by us, or where a call  
under the terms of guarantee has been booked  
and the failure is not product related (i.e. scaling  
and furring, incorrect water pressure).  
6 If the product is no longer covered by the  
guarantee, a charge will be made for the site  
visit and for any parts supplied.  
7 Service charges are based on the account being  
settled when work is complete, the engineer  
will then request payment for the invoice. If this  
is not made to the service engineer or settled  
within ten working days, an administration  
charge will be added.  
b) wilful act or neglect; c) any malfunction  
resulting from the incorrect use or quality of  
water or incorrect setting of controls; d) faulty  
installation.  
2 Repair costs for damage caused by foreign  
objects or substances.  
3 Total loss of the product due to non-availability  
of parts.  
4 Compensation for loss of use of the product or  
consequential loss of any kind.  
5 Call out charges where no fault has been found  
Replacement Parts Policy  
with the appliance.  
Availability: It is the policy of Triton to maintain  
availability of parts for the current range of  
products for supply after the guarantee has  
expired. Stocks of spare parts will be maintained  
for the duration of the product’s manufacture and  
for a period of five years thereafter.  
6 The cost of repair or replacement of  
showerheads, hoses, riser rails and/or wall  
brackets or any other accessories installed at the  
same time.  
7 The cost of routine maintenance, adjustments,  
overhaul modifications or loss or damage arising  
therefrom, including the cost of repairing  
damage, breakdown, malfunction caused by  
corrosion, furring, pipe scaling, limescale, system  
debris or frost.  
In the event of a spare part not being available a  
substitute part will be supplied.  
Payment: The following payment methods can be  
used to obtain spare parts:  
1 By post, pre-payment of pro forma invoice by  
cheque or money order.  
2 By telephone, quoting credit card (MasterCard  
or Visa) details.  
Customer Service:  
0870 067 3333  
%
Scottish and northern ireland  
Customer Service:  
0845 762 6591  
%
%
Triton Showers  
Triton Road  
Nuneaton  
Trade installer Hotline:  
0870 067 3767  
Fax: 0870 067 3334  
Warwickshire CV11 4NR  
Triton is a division of Norcros Group (Holdings) Limited  
e mail: [email protected].uk  
TRITON reserve the right to change product specification without prior notice. E&OA. © TRITON SHOWERS 2008  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graco Crib PD120168B User Manual
Haier Dishwasher HDW100SST User Manual
Harbor Freight Tools Switch 92688 User Manual
Harman Kardon Home Theater System PM645 User Manual
Hasbro Games 07148 User Manual
Honeywell Home Security System LYNXR 2 User Manual
Honeywell Thermostat 69 1496 User Manual
Hotpoint Dishwasher LFT 228 User Manual
Hotpoint Washer Dryer WF101 User Manual
Huawei Cell Phone U8510 User Manual