Standby Power Rating
100 kW 60 Hz
Liquid Cooled Gas Engine Generator Sets
Whisper-Test™
Low Speed Exercise
61 dB(A) at 23 feet
GENERAC 6.8L ENGINE
Naturally Aspirated
Gaseous Fueled
UL 2200 Listed
Transfer Switch is sold separately
STANDARD EQUIPMENT
•
•
•
•
•
•
•
•
•
•
•
UV/Ozone resistant hoses
Watertight state of the art electrical connectors
Mainline circuit breaker
Oil drain extension to frame rail
Radiator drain extension
•
•
•
•
•
•
•
•
•
•
•
All input connections in one single area
High coolant temperature shutdown
Low oil pressure shutdown
Low coolant level automatic shutdown
Low fuel pressure
Battery charge alternator
Overspeed automatic shutdown
Adjustable cranking timer
Adjustable exercise timer
Oil drain extension
Cool flow radiator
2 Amp static battery charger
Battery, battery rack and battery cables
Fan and belt guards
Isochronous governor
Flex fuel line pigtail
Closed coolant recovery system
FEATURES
•
•
•
•
•
•
Built-in kW, kVAR and power factor meters
Watertight electrical connectors
Rodent proof construction
High efficiency, low distortion Generac designed alternator
Vibration isolated from mounting base
Matching Generac transfer switches engineered and
tested to work as a system
All components easily accessible for maintenance
Electrostatically applied powder paint
•
•
•
•
•
•
•
•
•
Innovative design and fully prototype tested
UL 2200 Listed
Solid state frequency compensated voltage regulator
Dynamic and static battery charger
Sound attenuated acoustically designed enclosure
Whisper-Test™ for low noise level exercise
Acoustically designed engine cooling system
High flow low noise factory engineered exhaust system
State of the art digital control system with H-100
microprocessor control panel
•
•
COMMERCIAL SERIES
Download from Www.Somanuals.com. All Manuals Search And Download.
COMMERCIAL 100 kW
OPERATING DATA
KW RATING
COMMERCIAL SERIES
COMMERCIAL 100 kW
100
ENGINE SIZE
6.8 Liter V-10
GENERATOR OUTPUT VOLTAGE/KW - 60Hz
120/240V, single phase, 1.0 pf
120/208V, 3-phase, 0.8 pf
120/240V, 3-phase, 0.8 pf
277/480V, 3-phase, 0.8 pf
KW
AMP
CB Size
100 LP / 98 NG
100 LP / 98 NG
100 LP / 98 NG
100 LP / 98 NG
416.6 LP / 408.3 NG
347.4 LP / 340.4 NG
301 LP / 295 NG
150.5 LP / 147.5 NG
450
400
350
175
GENERATOR LOCKED ROTOR KVA
AVAILABLE @ VOLTAGE DIP OF 35%
Single phase or 208V & 240V 3-phase
480V 3-phase
190
225
ENGINE FUEL CONSUMPTION (Natural Gas) (Propane)
Natural Gas
(ft /hr.)
130
371
713
994
1260
Propane
3
(gal/hr.)
1.42
4.06
7.81
10.88
13.80
cu ft/hr
Exercise cycle
52.3
149.4
287.4
400.4
507.8
25% of rated load
50% of rated load
75% of rated load
100% of rated load
ENGINE COOLING
Air flow (inlet air including alternator and combustion air)
System coolant capacity
Heat rejection to coolant
Max. operating air temp. on radiator
Max. ambient temperature
3
ft /min
5,500
4.5
342,000
60 (150)
50 (140)
US gal.
BTU/hr.
°C (°F)
°C (°F)
COMBUSTION AIR REQUIREMENTS
Flow at rated power 60 Hz
cfm
262
SOUND EMISSIONS IN DBA
db(A) @ 23 feet in exercise mode
db(A) @ 23 feet at normal operating load
61
72
EXHAUST
Exhaust flow at rated output 60 Hz
Exhaust temp. at muffler outlet
cfm
°F
888
960
ENGINE PARAMETERS
Rated synchronous RPM
HP at rated KW
60 Hz
60 Hz
2300
168
POWER ADJUSTMENT FOR AMBIENT CONDITIONS
Temperature Deration
3% for every 10 °C above - °C
1.65% for every 10 °F above - °F
25
77
Altitude Deration
1% for every 100 m above - m
3% for every 1000 ft. above - ft.
183
600
RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility
source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and
specifications are subject to change without notice. Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power
and condition, etc.
Download from Www.Somanuals.com. All Manuals Search And Download.
INTERCONNECTIONS
COMMERCIAL 100 kW
100
100
100
100
240 1 ø
208 3ø
240 3ø
480 3ø
450
400
350
175
3-2/0 to 400 mcm
2-3/0 to 500 mcm
2-3/0 to 500 mcm
#6 to 350 mcm
COMMERCIAL SERIES
INSTALLATION LAYOUT
NOTE:
Door access
from both sides
UNIT WEIGHT: Steel 2705 lbs., Aluminum 2531 lbs.
GENERAC® POWER SYSTEMS, INC. • P.O. BOX 297 • WHITEWATER, WI 53190
www.guardiangenerators.com
Bulletin 0174700SBY / Printed in USA 06.07, 08.07
Download from Www.Somanuals.com. All Manuals Search And Download.
© 2007 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice.
|