Greenheck Fan Ventilation Hood TCB User Manual

PN 464115  
READ AND SAVE THESE INSTRUCTIONS  
Supplement for Model TCB with UL-762  
®
Installation Operation and Maintenance Manual  
Supplement for UL-762 Listed (Restaurant Exhaust) Fans  
This supplement to the TCB Installation Operation and Maintenance Manual is intended to provide additional  
information when dealing with fans used in applications involving grease laden air. Refer to the TCB Installation,  
Operation and Maintenance Manual (PN 456557) for items that are not specifically addressed (handling, storage,  
start-up, troubleshooting and maintenance) in this supplement.  
Installation Practices  
• All units used in applications with grease laden air are to be installed in  
accordance to NFPA 96, IMC 2203 and local codes. Consult local code  
authorities for your specific requirements.  
• Fans shall be located in an easily accessible area of adequate size to allow  
for service or removal. Exhaust fans with ductwork connected to both ends  
shall have access for cleaning and inspection within 3 ft (0.92 m) of each end  
of the fan (NFPA 96).  
• Maintain a minimum clearance of at least 18 inches (457 mm) to combustible  
material and 6 inches (125.4 mm) to either limited-combustible or  
noncombustible material (NFPA 96).  
• Fans are to be installed with the motors in the 3 or 9 o’clock (C or G) positions. Motors located in this  
configuration may cause an unbalanced load that should be considered if isolators are to be used. Equalized  
loading between isolators can be achieved through the use of mounting rails. Refer to the TCB IOM for details  
and installation instructions involving mounting rails.  
• It is recommended to install the fan near the end of the duct run. This limits the amount of positive pressure in  
the system. The diagram below illustrates an inline fan exhausting air near the final termination point. See local  
codes and NFPA 96 for any restrictions and requirements for wall terminations.  
E
xhaust air  
e
x
i
t
i
n
g
the  
bu  
il  
d
in  
g
M
i
n
i
m
u
m
d
u
ct  
F
an  
A
irflow  
at d  
ischar  
g
e
E
x
te  
r
i
o
r
Wall  
• A drain is provided for single-point drainage of water and residue. When installed correctly, one of the two  
housing drains will be located on the bottom. This drain is used to remove any accumulated grease and / or  
cleaning solutions. Some means for collection of this residue must be provided, either a container directly under  
the drain or use an adapter and pipe to carry the residue to a remote collection point. Remove drain plug prior  
to connection to grease collection device.  
• Provision to open and remove the access door is required for periodic cleaning and maintenance. The access  
door is clearly labeled and indicates that access to this location must be maintained. Any enclosure openings  
required to reach the access panel shall be large enough to allow for the removal of the panel.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Grizzly Staple Gun H8236 User Manual
Hayter Mowers Lawn Mower 111 2842 Rev B User Manual
Honeywell Home Theater Server 301C User Manual
Hotpoint Ventilation Hood HHC67AB User Manual
Hotpoint Washer WMF 760 P G A K User Manual
HP Hewlett Packard Network Hardware HP 4396A User Manual
HP Hewlett Packard Printer 175X User Manual
HP Hewlett Packard Projector Ep9012 User Manual
Hubbell Water Heater ST User Manual
Humminbird Fish Finder 383c User Manual