model Fsd-312
Combination Fire smoke dampers
APPLICATION
Steel Airfoil Blades
Model FSD-312 is a high performance combination fire smoke
damper with class II leakage. High strength airfoil blades ensure the
lowest resistance to airflow in HVAC systems with velocities to 3000
fpm (15.2 m/s) and pressures to 4 in. wg (1 kPa) Model FSD-312 may
be installed vertically (with blades running horizontal) or horizontally
and is rated for airflow and leakage in either direction.
UL 555S Leakage Class II
UL555 11⁄2 Hour Fire Resistance Rating
Model FSD-312 meets the requirements for fire
dampers, smoke dampers and combination fire
smoke dampers established by:
RATINgs
National Fire Protection Association
UL 555 Fire Resistance Rating:
NFPA Standards 80, 90A, 92A, 92B, 101 & 105
Fire Rating:
1½ hours
IBC International Building Codes
ICBO uniform Building Codes
CsFm California state Fire marshal
Fire Damper Listing (#3225-0981:103)
Leakage (Smoke) Damper Listing (#3230-0981:104)
New York City (MEA listing #260-91-M)
Dynamic Closure Rating: Actual ratings are size dependent
Max. Velocity:
Max. Pressure:
up to 3000 fpm (15.2 m/s)
4 in. wg (1 kPa)
UL555S Leakage Rating:
Leakage Class:
II
Operational Rating:
Max. Velocity:
Max. Pressure:
Actual ratings are size dependent
up to 3000 fpm (15.2m/s)
4 in. wg (1 kPa)
Maximum Temperature: 350°F (177°C)- depending upon the
“uL CLAssIFIed (see complete marking on prod-
uct)”
actuator
“uL CLAssIFIed to Canadian safety standards
(see complete marking on product)”
Standard 555 & 555S (Listing #R13317)
sTANdARd CONsTRuCTION
Frame:
5 in. x 1 in. (127mm x 25 mm)
galvanized steel hat channel with
reinforced corners. A low profile
head and sill are used on sizes less
than 17 in. (432mm)
Greenheck Fan Corporation certifies that the
model FSD-312 shown herein is licensed to
bear the AMCA Seal. The ratings shown are
based on tests and procedures performed
in accordance with AMCA Publication 511
and comply with the requirements of the
Blades:
seals:
Double skin airfoil shape of
galvanized steel with full length
structural reinforcement. 14 ga.
(2 mm) equivalent thickness.
Extruded silicone rubber blade seals.
Flexible stainless steel jamb seals.
Concealed in jamb.
AMCA Certified Ratings Programs. The
R
AMCA Certified Ratings Seal applies to air
performance ratings only.
Linkage:
Closure device:
Axles:
RRL 165°F (74°C)
1
⁄2 in. (13mm) dia. plated steel.
Bearings:
Bronze sleeve type.
sIze LImITATIONs:
minimum size:
8 in. W x 6 in. H
(203 mm W x 152mm H)
maximum size:
Single Section:
32 in. W x 50 in. H
(813mm W x 1270mm H)
96 in. W x 50 in. H
(2435mm W x 1270mm H)
128 in. W x 100 in. H
(3251mm W x 2540mm H)
Multiple Section:
Vertical Only:
LH
OPTIONAL FeATuRes:
H*
• RRL/OCI (Open closed indication switches)
• 165ºF (74°C), 212ºF (100°C), 250ºF (121°C), 350ºF (177°C) RRL’s
available
• TOR (remote override closure allows damper to perform smoke
management functions during a fire emergency.)
• Electric or pneumatic actuators to accomplish smoke
management and system functions.
• POC retaining angles
W*
RH
• Smoke detectors
• Momentary Switch
• Transitions (R, C, O)
• PRV (pneumatic relief valve)
1
*W&H dimensions furnished approximately /4 in. ( 6 mm) undersize.
(Add sleeve thickness for overall sleeved damper dimension)
Right hand drive is shown. Left hand drive is available upon request.
• Security Bars
• Sealed transitions and sleeves
Installation instructions available at www.greenheck.com
Download from Www.Somanuals.com. All Manuals Search And Download.
AmCA 5.2 Pressure drop
Fsd-312
5D
*
36x36
12x48
48x12
12x12
24x24
* Sizes are in inches.
Velocity
(fpm)
Pressure Drop
(in. wg)
Velocity
(fpm)
Pressure Drop
(in. wg)
Velocity
(fpm)
Pressure Drop
(in. wg)
Velocity
(fpm)
Pressure Drop
(in. wg)
Velocity
(fpm)
Pressure Drop
(in. wg)
500
0.03
0.12
0.26
0.46
0.72
1.04
1.41
1.84
500
0.01
0.06
0.12
0.22
0.34
0.49
0.67
0.87
500
0.01
0.06
0.12
0.22
0.34
0.49
0.67
0.88
500
0.01
0.05
0.12
0.21
0.33
0.48
0.65
0.85
500
1000
1500
2000
2500
3000
3500
4000
0.02
0.08
0.18
0.33
0.51
0.74
1.00
1.31
1000
1500
2000
2500
3000
3500
4000
1000
1500
2000
2500
3000
3500
4000
1000
1500
2000
2500
3000
3500
4000
1000
1500
2000
2500
3000
3500
4000
Greenheck Fan Corporation certifies that the
model FSD-312 shown herein is licensed to bear
the AMCA Seal. The ratings shown are based on
tests and procedures performed in accordance
with AMCA Publication 511 and comply with
the requirements of the AMCA Certified Ratings
Programs. The AMCA Certified Ratings Seal
applies to air performance ratings only.
R
Download from Www.Somanuals.com. All Manuals Search And Download.
AmCA 5.3 Pressure drop
Fsd-312
5D
6D
*
24x24
12x12
36x36
48x12
12x48
* Sizes are in inches.
Pressure Drop
Pressure Drop
Pressure Drop
Pressure Drop
Pressure Drop
Velocity (fpm)
(in. wg)
Velocity (fpm)
(in. wg)
Velocity (fpm)
(in. wg)
Velocity (fpm)
(in. wg)
Velocity (fpm)
(in. wg)
500
1000
1500
2000
2500
3000
3500
4000
0.01
0.06
0.13
0.23
0.37
0.53
0.73
0.95
500
0.01
0.02
0.06
0.10
0.16
0.23
0.32
0.42
500
1000
1500
2000
2500
3000
3500
4000
0.01
0.02
0.05
0.09
0.14
0.21
0.29
0.38
500
1000
1500
2000
2500
3000
3500
4000
0.01
0.02
0.06
0.10
0.16
0.24
0.33
0.43
500
0.01
0.04
0.10
0.18
0.29
0.42
0.57
0.74
1000
1500
2000
2500
3000
3500
4000
1000
1500
2000
2500
3000
3500
4000
Greenheck Fan Corporation certifies that the
model FSD-312 shown herein is licensed to bear
the AMCA Seal. The ratings shown are based on
tests and procedures performed in accordance
with AMCA Publication 511 and comply with the
requirements of the AMCA Certified Ratings Pro-
grams. The AMCA Certified Ratings Seal applies
to air performance ratings only.
R
Download from Www.Somanuals.com. All Manuals Search And Download.
AmCA 5.5 Pressure drop
Fsd-312
*
36x36
48x12
12x12
12x48
24x24
* Sizes are in inches.
Velocity
(fpm)
Pressure Drop
(in. wg)
Velocity
(fpm)
Pressure Drop
(in. wg)
Velocity
(fpm)
Pressure Drop
Velocity
(fpm)
Pressure Drop
(in. wg)
Velocity
(fpm)
Pressure Drop
(in. wg)
(in. wg)
500
1000
1500
2000
2500
3000
3500
4000
0.04
0.18
0.42
0.75
1.17
1.68
2.29
2.09
500
1000
1500
2000
2500
3000
3500
4000
0.03
0.13
0.29
0.52
0.81
1.17
1.60
2.14
500
1000
1500
2000
2500
3000
3500
4000
0.03
0.12
0.27
0.48
0.75
1.08
1.48
1.93
500
1000
1500
2000
2500
3000
3500
4000
0.03
0.12
0.27
0.49
0.77
1.11
1.51
1.97
500
1000
1500
2000
2500
3000
3500
4000
0.03
0.14
0.32
0.57
0.89
1.28
1.75
2.29
Greenheck Fan Corporation certifies that the
model FSD-312 shown herein is licensed to bear
the AMCA Seal. The ratings shown are based on
tests and procedures performed in accordance
with AMCA Publication 511 and comply with the
requirements of the AMCA Certified Ratings Pro-
grams. The AMCA Certified Ratings Seal applies
to air performance ratings only.
R
Download from Www.Somanuals.com. All Manuals Search And Download.
Application data
damper sleeve dimensional data
The drawings below and corresponding table show the position of the FSD-312 damper when mounted in a factory sleeve.
The standard mounting locations provide enough space for the mounting of actuators, controls and allow space for installa-
tion of retaining angles and duct connections.
The standard location of a damper mounted in a
/2" max.
1
1
factory sleeve ("A" dimension) is shown below. The
damper can be positioned at other locations within
a range of 6 in. (152 mm) to 12 in. (305mm) for the "A"
dimension.
"A" Dimension
in. (mm)
33/4"
Standard
7 3/16 (183)
12 (305)
Maximum
12 (305)
12 (305)
All Dampers*
When H is 11 in. (279mm) or
less with OCI, RRL, or TOR
6"
Varies
53/8"
*With the exception of dampers 10 in. high (254mm) or less.
NOTE: Entire damper frame is not required to be installed within the
wall. The damper blades, when closed should be contained within
the wall.
LH
RH
A
5"
Sleeve Length
T*
Right hand drive is shown
Left hand drive available upon request
Actuators and Accessories
S
space envelopes
Externally mounted actuators always require space
outside of the damper sleeve. The “S” dimension il-
lustrates the clearance required for various available
actuators.
On dampers less than 18 in. (457mm) high, actuators
may also require clearances above and/or below the
sleeve. “B” and “T” dimensions are worst case clear-
ance requirements for some dampers less than 18 in.
(457 mm) high. All damper sizes under 18 in. (457mm)
high do not require these worst case clearances. If
space availability above or below the damper sleeve is
limited, each damper size should be individually evalu-
ated.
B*
B*
T*
Actuator Type/Model
S
With
With
RRL, RRL/OCI, or TOR RRL, RRL/OCI, or TOR
120 Volt AC
ML-4XXX Series Honeywell
MS-4XXX Series Honeywell
MS-4120 Series Honeywell
5¼ in. (133mm)
6 in. (152mm)
6 in. (152mm)
¾ in.(19mm)
3/8 in. (10mm)
3/8 in. (10mm)
6 in. (152mm)
6 in. (152mm)
6 in. (152mm)
24 Volt AC
ML-8XXX Series Honeywell
MS-8XXX Series Honeywell
MS-8120 Series Honeywell
5¼ in. (133mm)
6 in. (152mm)
6 in. (152mm)
¾ in.(19mm)
6 in. (152mm)
6 in. (152mm)
6 in. (152mm)
6 in. (152mm)
6 in. (152mm)
Pneumatic (25 psi min.)
331-4551 Powers
331-2976 Powers
MK2-7121 Invensys
1 in. (25mm)
2 3/8 in. (60mm)
3 3/4 in. (95mm)
6¼ in. (159mm)
12 1/8 in. (308mm)
16½ in. (419mm)
6½ in. (165mm)
9¼ in. (235mm)
10 in. (254mm)
* For dampers 18 in. (457mm) or more in height these dimensions are 0 in. .
Download from Www.Somanuals.com. All Manuals Search And Download.
damper sizing Information
Dampers larger than maximum single section size are supplied as a factory assembly of two or more sections of equal size. The
following figures show maximum damper section size and assembly configurations for multi-section dampers.
Double Section
Single Section
50 in.
(1270mm)
50 in.
(1270mm)
32 in. (813mm)
64 in. (1626mm)
32 in. (813mm)
Transitioned damper When a fire/smoke damper is being used in conjunction with round or oval ductwork, the
FSD-312 can be supplied in a factory sleeve with round or oval transitions on both ends of
the sleeve. Dampers should be ordered to the duct dimensions. Drawings below show over-
all damper size.
dimensions
D*+
2 in. (51mm) +T
s
W*+ 2 in. (51mm)+T
s
W*+ 2 in. (51mm)+T
s
D*+ 2 in. (51mm)+T
s
H*+ 2 in. (51mm)+T
H*+ 2 in. (51mm)+T
s
s
H*
H*
21/8in.
21/8in.
(54mm)
These dimensions are furnished
*
21/8in.
(54mm)
(54mm)
approximately 1/4 in. (6mm) undersize,
except round and oval dimensions
which are approximately 1/8 in.(3mm)
undersize.
*
W
W*
D*
16 in. (406mm)
Min.
16 in. (406mm)
Min.
16 in. (406mm)
Min.
T
= (2)(Sleeve Thickness)
s
TYPE R
TYPE O
TYPE C
specifications
Combination Fire Smoke Dampers meeting the following specifica-
tions shall be furnished and installed where shown on plans and/or
as described in schedules. Dampers shall meet the requirements of
NFPA 80, 90A, 92A, 92B, 101 & 105 and further shall be tested, rated
and labeled in accordance with the latest edition of UL Standards
555 and 555S. Dampers shall have a UL555 fire rating of 1½ hours
and be of low leakage design qualified to UL 555S Leakage Class II.
be galvanized steel formed into a structural hat channel shape with
reinforced corners. Bearings shall be sintered bronze sleeve type
rotating in extruded holes in the damper frame. Blade edge seals
shall be silicone rubber designed to inflate and provide a tighter seal
against leakage as pressure on either side of the damper increases.
Jamb seals shall be stainless steel compression type. Blades shall
be completely symmetrical relative to their axle pivot point, present-
ing identical resistance to airflow in either direction or pressure on
either side of the damper.
Each damper/actuator combination shall have a UL555S elevated
temperature rating of 250° F (121°C) minimum and shall be opera-
tional and dynamic rated to operate at maximum design air flow at
its installed location. Each damper shall be supplied with an appro-
priate actuator installed by the damper manufacturer at the time of
damper fabrication. Damper actuator shall be (specifier select one
of the following) electric type for 120 (24 or 230) volt operation or
pneumatic type for 25 psi minimum (30 psi maximum) operation.
Damper must be rated for mounting vertically (with blades running
horizontal) or horizontally and be UL 555S rated for leakage and
airflow in either direction through the damper. Each damper shall be
supplied with a 165°F (74°C) RRL. Testing and ratings to be in ac-
cordance with AMCA standard 500-D.
The basis of design is Greenheck Model FSD-312.
Damper blades shall be of the double skin airfoil type and shall
have an equivalent thickness of 14 ga. (2mm) . Damper frame shall
Copyright © 2006 Greenheck Fan Corporation
FSD-312 Rev 3 June 2006
Download from Www.Somanuals.com. All Manuals Search And Download.
|