Greenheck Fan Ventilation Hood FDR 510 User Manual

Model FDR-510  
Static Rated Round Fire Dampers  
Application and Design  
1
1 /2 Hour Fire Resistance Rating  
Model FDR-510 is a round fire damper for use in walls or  
partitions with less than 3 hour fire resistance rating. It is  
qualified to be mounted vertically and horizontally. This  
model carries a 1 1/2 hour UL fire damper label. UL555  
classifies static rated fire dampers for use in HVAC systems  
that are automatically shut down in the event of fire.  
Model FDR-510 meets the requirements for fire dampers  
established by:  
National Fire Protection Association  
(NFPA Standards 80, 90A & 101)  
Underwriters Laboratories Standard 555  
(Listing #R-13317)  
Ratings  
Temperature:  
165º F (74ºC)  
IBC International Building Codes  
Standard Construction  
Frame/Sleeve: 20 ga. (1mm) galvanized steel  
Blade: 20 ga. (1mm) galvanized steel  
Closure Device: 165ºF (82ºC) Fusible Link  
Axle: 1/2 in. (6mm) dia. plated steel.  
Bearing: Stainless Steel sleeve type  
Size Limitations  
Minimum size: 4 in. (102mm) diameter  
Maximum size: 24 in. (610mm) diameter  
Features:  
• Stainless steel closure springs  
• Fusible links - 165ºF (74ºC) standard; 212ºF (100ºC) and 286ºF  
(141ºC) available  
• Can be mounted horizontally or vertically  
• Only one retainer plate required (one retainer plate supplied  
with damper)  
• Additional retainer plate available  
• 14 ga. (2mm) or 16 ga. (1.5mm) frame/sleeve  
These dimensions are furnished approximately 1/8 in. (3mm)  
*
smaller than nominal.  
OPENING + 2.00 MIN.  
CLEARANCE FOR  
EXPANSION  
RETAINER PLATE  
RETAINER PLATE  
(OPTIONAL)  
BLADE LATCH  
ACCESS DOOR TO BE ON  
SAME SIDE AS BLADE LATCH  
CLAMPING  
SCREW  
DUCT CONNECTION  
AREA  
WALL/FLOOR  
OPENING  
2 in.  
= Nominal size + 7/8 Min.  
1.00 TYP.  
AIRFLOW  
FASTENERS  
DUCT CONNECTION  
AREA  
2 in.  
NUT  
DO NOT PLACE RETAINER  
PLATE IN THIS GROOVE  
6 in. max.  
6 in. max.  
RETAINING  
PLATE ASSEMBLY  
TW  
SLEEVE LENGTH  
CLAMPING SCREW  
WALL THICKNESS  
Up to 6.5  
SLEEVE LENGTH  
13.625  
Up to 8.5  
Up to 10.5  
Over 10.5  
15.625  
17.625  
Consult Greenheck  
Copyright ©2008 Greenheck Fan Corporation  
FDR-510 Rev. 6 Aug 2008  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Grizzly Drill G0485 User Manual
Grizzly Grinder G5785 User Manual
Hague Quality Water Intl Water System H2000 User Manual
Haier Flat Panel Television HL37E User Manual
Hotpoint Cooktop GD64 User Manual
Hotpoint Refrigerator CTX18GACAA User Manual
Hunter Fan Outdoor Ceiling Fan 28682 User Manual
Hunter Fan Ventilation Hood 81003 User Manual
Husqvarna Trimmer 326C User Manual
Impex Tent MS 93 User Manual