Greenheck Fan Ventilation Hood CFSD XXX Series User Manual

Part number 468236  
Single Side Retaining Angle-Horizontal Mount  
INSTALLATION INSTRUCTION SUPPLEMENT  
Refer to:  
FD & DFD Series  
‘Installation Instructions for FD, DFD, SSFD, & KFD Models’  
11/2 Hour Fire Dampers and  
(Part #452763)  
or  
FSD Series  
11/2 Hour Combination Fire Smoke  
Dampers-Horizontal Mount  
‘Installation Instructions for FSD-XXX, DFD-XXX, SSFSD-XXX &  
CFSD-XXX Series Fire & Combination Fire Smoke Dampers’ (Part  
#461336)  
or  
‘Installation Instructions for FD & DFD 150X Series Curtain Fire  
Dampers’ (Part #453946) for additional details.  
“UL CLASSIFIED  
These instructions apply to 11 hour rated combination fire smoke  
dampers and curtain fire dampers mounted horizontally in concrete  
floors. Specific requirements in these instruction are mandatory. These  
instructions meet the requirements of UL 555. Installation shall comply  
with the requirements of NFPA 90A (Standard for the Installation of Air  
Conditioning and Ventilating Systems) and UL Classification R13317.  
(see complete marking on product)”  
“UL CLASSIFIED to Canadian safety standards  
(see complete marking on product)”  
Standards UL 555 & 555S  
Classifications Filed at UL under Listing #R13317  
Dampers up to a maximum size of 144 in. W x 96 in. H (3658mm x 2438mm) may be installed as illustrated  
below.  
Fire damper and sleeve assemblies 144 in. W x 96 in. H (3658mm x 2438mm) and smaller only require  
retaining angles on top of the concrete floor. Retaining angles must be installed on top of the floor and attached to the sleeve  
and the floor.  
Retaining angles must be attached to the sleeve.  
• Retaining angles must be a minimum of 16 gauge (1.5mm) steel and have a minimum of 11 in. x 11 in.  
(38mm x 38mm) legs.  
• Retaining angles must be attached to the sleeve using one of the methods shown below:  
• tack or spot welds  
• #10 sheet metal screws or 1/4 in. nuts and bolts  
•Retaining angles must be attached to the concrete floor using the method shown below:  
• Steel anchors or self tapping concrete screws penetrating concrete floor a minimum of 11 in. (32mm)  
• A minimum of two connections per side with a maximum spacing of 6 in. (152mm) on center  
• Retaining angles must overlap the floor a minimum of 1 in. (25mm)  
A = Damper  
B = Retaining Angle  
C = Screws  
B
C
DAMPER  
SLEEVE  
CONCRETE  
FLOOR  
A
Copyright © 2008 Greenheck Fan Corporation  
468236 Single Side Retaining Angle-Horizontal  
Mount Rev.3 August 2008  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graco GPS Receiver 10 User Manual
Haier Clothes Dryer CRDE350AW User Manual
Harbor Freight Tools Doll 94883 User Manual
Hasbro Robotics 87776 User Manual
Honeywell Home Security System EKZ008200B User Manual
Honeywell Scanner 3800g User Manual
Husqvarna Trimmer 325HDA65X Series 323HE3 325HE3X Series 325HE4X Series User Manual
Hypertec Carrying Case 3501 User Manual
Icom Car Stereo System IC R100 User Manual
IKEA Landscape Lighting AA 96974 4 User Manual