Greenheck Fan Smoke Alarm DH100ACDCLP User Manual

DUCT SMOKE DETECTOR  
DH100ACDCLP  
Purpose/Application  
National and local safety standards and codes recognize  
the ability of air duct systems to transfer smoke, toxic  
gases, and flame from area to area. Sometimes smoke can  
be of such quantity as to be a serious hazard to life safety  
unless blowers are shut down and dampers are actuated.  
The primary purpose of duct smoke detection is to prevent  
injury, panic, and property damage by reducing the spread  
(recirculation) of smoke. The detector samples air currents  
passing through a duct and gives dependable performance  
for management of smoke and combination fire smoke  
dampers. Duct smoke detection can also serve to protect the  
air conditioning system itself from fire and smoke damage.  
There are several important documents that provide guidance  
concerning the performance, application and installation of  
duct detectors:  
1) NFPA Standard 90A, Installation of Air Conditioning  
and Ventilating Systems  
2) NFPA Standard 92A, Recommended Practice for  
Smoke Control Systems  
3) NFPA Standard 72, National Fire Alarm Code  
4) NFPA Standard 101, Life Safety Code  
5) UL Standard 268A, Standard for Smoke Detectors for  
Duct Applications  
6) ASHRAE Handbook and Product Directory, “Fire and  
Smoke Control”  
7) System Sensor, Guide for Proper Use of Smoke  
Detectors in Duct Applications.  
Duct detectors are:  
NOT a substitute for an open area smoke detector.  
NOT a substitute for early warning detection, and  
NOT a replacement for a building’s regular fire detection  
system.  
Configuration  
Maximum wall thickness: 6 in. (152mm) on FSD & SSFSD  
applications  
(Consult factory for walls greater  
than 6 in. [152mm])  
Specifications  
Type: Photoelectric  
Air duct velocity: 100 to 4000 fpm (.5 m/s to  
20.3 m/s)  
Actuator Location: Must be right hand drive  
Must be externally mounted  
Operating temperature range: 32°F to 131°F (0°C to 55°C)  
Operating humidity range: 10% to 93% R.H.  
Operation Voltage: 24 VAC/DC or  
120/240 VAC  
Detector Location: Mounts opposite actuator side  
Must be external  
Sampling tubes longer than three feet must be supported  
on each end. Holes in duct smoke detector sampling tubes  
must face into the airflow.  
Features  
Textured cover for convenient visual inspection.  
• The detector provides a trouble signal in the event that the  
front cover is removed.  
• Integral filter system included to reduce dust and residue  
effects on detector and housing, thereby reducing  
maintenance and servicing.  
Availability  
For use with all FSD, SSFSD, SMD, SSSMD, and CFSD  
models. Not available on SMDR models.  
Terminal connections are of the strip and clamp method  
suitable for 12-18 AWG wiring.  
Listings  
• Outside mounting tabs for easy connection to sleeve or  
ductwork (when detector ships loose).  
UL 268A  
Refer to Greenheck Installation Supplement: Part #463813 IOM-Smoke Detector Supplement  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPACE ENvELOPES  
ELECTRiCAL RATiNgS  
Dampers Less Than 25 inches (635mm) in Height  
Typical Actuator  
(ML series shown; other  
actuators available)  
3 in.  
3
6
⁄4 in.  
Single Point Wiring (Standard)  
Smoke detector, actuator, and all  
control options are prewired to  
junction box at the factory.  
Dampers Equal To Or greater Than 25 inches (635mm) in Height  
2 3/4 in.  
(70mm)  
Typical Actuator  
(other actuators available)  
15 in.  
(381mm)  
Single Point Wiring  
(Standard): Smoke  
detector, actuator, and  
all control optiong are  
prewired to junction box  
at the factory.  
Electrical Ratings  
Power Supply Voltage: 20-29 VDC  
24 VAC 50-60 Hz  
270 µF max.  
120 VAC 50-60 Hz 220/240 VAC 50-60 Hz  
Input Capacitance:  
Reset Voltage:  
Reset Time:  
Power Up Time:  
Alarm Response Time:  
Sensitivity Test:  
270 µF max.  
3.0 VDC min.  
0.6 sec. max.  
34 sec. max.  
2-17 sec.  
N/A  
N/A  
2.0 VAC min.  
0.6 sec. max.  
34 sec. max.  
2-17 sec.  
10 VAC min.  
0.6 sec. max.  
34 sec. max.  
2-17 sec.  
20 VAC min.  
0.6 sec. max.  
34 sec. max.  
2-17 sec.  
See detector label  
See detector label  
See detector label  
See detector label  
Current Requirements  
Max. Standby Current:  
Max. Alarm Current:  
15 mA  
70 mA  
35 mA RMS  
125 mA RMS  
25 mA RMS*  
35 mA RMS*  
15 mA RMS*  
25 mA RMS*  
Contact Ratings  
Alarm Initiation Contacts (SPST):  
2.0A @ 30 VAC/DC (0.6 power factor)  
Alarm Auxiliary Contacts (DPDT):  
10A @ 30 VDC  
10A @ 250 VDC  
Note:  
Alarm auxiliary contacts must switch 100 mA minimum at 5 VDC. Alarm auxiliary contacts shall not be connected  
to initiating circuits of control panels. Use the alarm initiation contact for this purpose.  
Trouble Contacts (SPDT):  
2.0A @ 30 VDC (resistive)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WiRiNg DiAgRAMS  
DUCT SMOKE DETECTOR  
Fusible Link  
RED  
DH100ACDCLP DUCT DETECTOR  
1
2
3
4
5
6
7
8
9
10  
A
B
C
24 VAC/VDC  
11 12 13 14 15 16 17 18 19 20  
BLUE  
RED  
DH100ACDCLP DUCT DETECTOR  
1
2
3
4
5
6
7
8
9
10  
A
B
C
L1  
L2  
115 VAC  
11 12 13 14 15 16 17 18 19 20  
RED  
BLUE  
DH100ACDCLP DUCT DETECTOR  
MOTOR  
OPTIONAL  
SECOND MOTOR  
220/240 VAC  
1
2
3
4
5
6
7
8
9
10  
A
B
C
11 12 13 14 15 16 17 18 19 20  
MOTOR  
OPTIONAL  
THIRD MOTOR  
BLUE  
MOTOR  
1. CONDUIT RUNS WHICH EXCEED 72" MUST HAVE GREEN GROUND WIRE.  
2. FLEX CONDUIT MUST BE SECURED WITH A CONDUIT CLAMP (458296) WITHIN 12" OF CONDUIT TERMINATION AT THE HANDI-BOX OR ACTUATOR. CONDUIT RUNS MUST ALSO BE  
SECURED ALONG SLEEVE AT A MAXIMUM OF 24" ON CENTER.  
OCI  
RED  
DH100ACDCLP DUCT DETECTOR  
THE OCI WIRES MUST BE CHECKED TO VERIFY WHICH SET INDICATES THE CLOSED POSITION OF  
DAMPER. THIS SET OF WIRES SHOULD THEN BE LABELED WITH A BLUE WIRE MARKER (382169).  
OCI  
1
2
3
4
5
6
7
8
9
10  
A
B
C
24 VAC/VDC  
11 12 13 14 15 16 17 18 19 20  
BLUE  
SWITCH #2  
SWITCH #1  
RED  
DH100ACDCLP DUCT DETECTOR  
1
2
3
4
5
6
7
8
9
10  
A
B
C
L1  
L2  
115 VAC  
11 12 13 14 15 16 17 18 19 20  
RED  
BLUE  
DH100ACDCLP DUCT DETECTOR  
MOTOR  
OPTIONAL  
SECOND MOTOR  
220/240 VAC  
1
2
3
4
5
6
7
8
9
10  
A
B
C
11 12 13 14 15 16 17 18 19 20  
MOTOR  
OPTIONAL  
THIRD MOTOR  
BLUE  
MOTOR  
1. CONDUIT RUNS WHICH EXCEED 72" MUST HAVE GREEN GROUND WIRE.  
2. FLEX CONDUIT MUST BE SECURED WITH A CONDUIT CLAMP (458296) WITHIN 12" OF CONDUIT TERMINATION AT THE HANDI-BOX OR ACTUATOR. CONDUIT RUNS MUST ALSO BE  
SECURED ALONG SLEEVE AT A MAXIMUM OF 24" ON CENTER.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WiRiNg DiAgRAMS  
DUCT SMOKE DETECTOR  
RRL  
RED  
DH100ACDCLP DUCT DETECTOR  
RRL  
1
2
3
4
5
6
7
8
9
10  
A
B C  
24 VAC/VDC  
11 12 13 14 15 16 17 18 19 20  
BLUE  
RED  
DH100ACDCLP DUCT DETECTOR  
1
2
3
4
5
6
7
8
9
10  
A
B
C
115 VAC  
L1  
L2  
11 12 13 14 15 16 17 18 19 20  
RED  
BLUE  
DH100ACDCLP DUCT DETECTOR  
MOTOR  
OPTIONAL  
SECOND MOTOR  
220/240 VAC  
1
2
3
4
5
6
7
8
9
10  
A
B
C
11 12 13 14 15 16 17 18 19 20  
MOTOR  
OPTIONAL  
THIRD MOTOR  
BLUE  
MOTOR  
1. CONDUIT RUNS WHICH EXCEED 72" MUST HAVE GREEN GROUND WIRE.  
2. FLEX CONDUIT MUST BE SECURED WITH A CONDUIT CLAMP (458296) WITHIN 12" OF CONDUIT TERMINATION AT THE HANDI-BOX OR ACTUATOR. CONDUIT RUNS MUST ALSO BE  
SECURED ALONG SLEEVE AT A MAXIMUM OF 24" ON CENTER.  
RRL/OCI  
RED  
DH100ACDCLP DUCT DETECTOR  
THE OCI WIRES MUST BE CHECKED TO VERIFY WHICH SET INDICATES THE CLOSED POSITION OF  
DAMPER. THIS SET OF WIRES SHOULD THEN BE LABELED WITH A BLUE WIRE MARKER (382169).  
RRL  
1
2
3
4
5
6
7
8
9
10  
A
B
C
24 VAC/VDC  
11 12 13 14 15 16 17 18 19 20  
BLUE  
SWITCH #2  
SWITCH #1  
RED  
DH100ACDCLP DUCT DETECTOR  
1
2
3
4
5
6
7
8
9
10  
A
B
C
115 VAC  
L1  
L2  
11 12 13 14 15 16 17 18 19 20  
RED  
BLUE  
DH100ACDCLP DUCT DETECTOR  
MOTOR  
OPTIONAL  
SECOND MOTOR  
220/240 VAC  
1
2
3
4
5
6
7
8
9
10  
A
B
C
11 12 13 14 15 16 17 18 19 20  
MOTOR  
OPTIONAL  
THIRD MOTOR  
BLUE  
MOTOR  
1. CONDUIT RUNS WHICH EXCEED 72" MUST HAVE GREEN GROUND WIRE.  
2. FLEX CONDUIT MUST BE SECURED WITH A CONDUIT CLAMP (458296) WITHIN 12" OF CONDUIT TERMINATION AT THE HANDI-BOX OR ACTUATOR. CONDUIT RUNS MUST ALSO BE  
SECURED ALONG SLEEVE AT A MAXIMUM OF 24" ON CENTER.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WiRiNg DiAgRAMS  
DUCT SMOKE DETECTOR  
TOR  
RED  
THE OCI WIRES MUST BE CHECKED TO VERIFY WHICH SET INDICATES THE CLOSED POSITION OF  
DAMPER. THIS SET OF WIRES SHOULD THEN BE LABELED WITH A BLUE WIRE MARKER (382169).  
DH100ACDCLP DUCT DETECTOR  
TOR  
1
2
3
4
5
6
7
8
9
10  
A
B
C
24 VAC/VDC  
11 12 13 14 15 16 17 18 19 20  
BLUE  
SWITCH #2  
SWITCH #1  
RED  
SWITCHING DEVICE  
(BY OTHERS)  
DH100ACDCLP DUCT DETECTOR  
(OVERRIDE)  
1
2
3
4
5
6
7
8
9
10  
A
B
C
L1  
115 VAC  
(PRIMARY)  
11 12 13 14 15 16 17 18 19 20  
L2  
RED  
BLUE  
DH100ACDCLP DUCT DETECTOR  
MOTOR  
OPTIONAL  
SECOND MOTOR  
220/240 VAC  
1
2
3
4
5
6
7
8
9
10  
A
B
C
11 12 13 14 15 16 17 18 19 20  
MOTOR  
OPTIONAL  
THIRD MOTOR  
BLUE  
MOTOR  
1. CONDUIT RUNS WHICH EXCEED 72" MUST HAVE GREEN GROUND WIRE.  
2. FLEX CONDUIT MUST BE SECURED WITH A CONDUIT CLAMP (458296) WITHIN 12" OF CONDUIT TERMINATION AT THE HANDI-BOX OR ACTUATOR. CONDUIT RUNS MUST ALSO BE  
SECURED ALONG SLEEVE AT A MAXIMUM OF 24" ON CENTER.  
OCI w/ EP Switch  
RED  
DH100ACDCLP DUCT DETECTOR  
THE OCI WIRES MUST BE CHECKED TO VERIFY WHICH SET INDICATES THE CLOSED POSITION OF  
DAMPER. THIS SET OF WIRES SHOULD THEN BE LABELED WITH A BLUE WIRE MARKER (382169).  
OCI  
1
2
3
4
5
6
7
8
9
10  
A
B
C
24 VAC/VDC  
11 12 13 14 15 16 17 18 19 20  
BLUE  
SWITCH #2  
SWITCH #1  
RED  
DH100ACDCLP DUCT DETECTOR  
1
2
3
4
5
6
7
8
9
10  
A
B
C
L1  
L2  
115 VAC  
11 12 13 14 15 16 17 18 19 20  
E/P SWITCH  
RED  
BLUE  
DH100ACDCLP DUCT DETECTOR  
RED  
RED  
RED  
RED  
OPTIONAL  
SECOND E/P SWITCH  
220/240 VAC  
1
2
3
4
5
6
7
8
9
10  
A
B
C
11 12 13 14 15 16 17 18 19 20  
E/P SWITCH  
RED  
OPTIONAL  
THIRD E/P SWITCH  
BLUE  
E/P SWITCH  
RED  
1. CONDUIT RUNS WHICH EXCEED 72" MUST HAVE GREEN GROUND WIRE.  
2. FLEX CONDUIT MUST BE SECURED WITH A CONDUIT CLAMP (458296) WITHIN 12" OF CONDUIT TERMINATION AT THE HANDI-BOX OR ACTUATOR. CONDUIT RUNS MUST ALSO BE  
SECURED ALONG SLEEVE AT A MAXIMUM OF 24" ON CENTER.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WiRiNg DiAgRAMS  
RRL W/ EP Switch  
DUCT SMOKE DETECTOR  
RED  
DH100ACDCLP DUCT DETECTOR  
RRL  
1
2
3
4
5
6
7
8
9
10  
A
B
C
24 VAC/VDC  
11 12 13 14 15 16 17 18 19 20  
BLUE  
RED  
DH100ACDCLP DUCT DETECTOR  
1
2
3
4
5
6
7
8
9
10  
A
B
C
115 VAC  
L1  
L2  
11 12 13 14 15 16 17 18 19 20  
E/P SWITCH  
RED  
BLUE  
DH100ACDCLP DUCT DETECTOR  
RED  
RED  
RED  
RED  
OPTIONAL  
SECOND E/P SWITCH  
220/240 VAC  
1
2
3
4
5
6
7
8
9
10  
A
B C  
11 12 13 14 15 16 17 18 19 20  
E/P SWITCH  
RED  
BLUE  
OPTIONAL  
THIRD E/P SWITCH  
E/P SWITCH  
RED  
1. CONDUIT RUNS WHICH EXCEED 72" MUST HAVE GREEN GROUND WIRE.  
2. FLEX CONDUIT MUST BE SECURED WITH A CONDUIT CLAMP (458296) WITHIN 12" OF CONDUIT TERMINATION AT THE HANDI-BOX OR ACTUATOR. CONDUIT RUNS MUST ALSO BE  
SECURED ALONG SLEEVE AT A MAXIMUM OF 24" ON CENTER.  
RRL/OCI W/ EP Switch  
RED  
THE OCI WIRES MUST BE CHECKED TO VERIFY WHICH SET INDICATES THE CLOSED POSITION OF  
DAMPER. THIS SET OF WIRES SHOULD THEN BE LABELED WITH A BLUE WIRE MARKER (382169).  
DH100ACDCLP DUCT DETECTOR  
RRL  
1
2
3
4
5
6
7
8
9
10  
A
B
C
24 VAC/VDC  
11 12 13 14 15 16 17 18 19 20  
BLUE  
SWITCH #2  
SWITCH #1  
RED  
DH100ACDCLP DUCT DETECTOR  
1
2
3
4
5
6
7
8
9
10  
A
B
C
115 VAC  
L1  
L2  
11 12 13 14 15 16 17 18 19 20  
RED  
E/P SWITCH  
BLUE  
DH100ACDCLP DUCT DETECTOR  
RED  
RED  
RED  
RED  
OPTIONAL  
SECOND E/P SWITCH  
220/240 VAC  
1
2
3
4
5
6
7
8
9
10  
A
B
C
11 12 13 14 15 16 17 18 19 20  
E/P SWITCH  
RED  
BLUE  
OPTIONAL  
THIRD E/P SWITCH  
E/P SWITCH  
RED  
1. CONDUIT RUNS WHICH EXCEED 72" MUST HAVE GREEN GROUND WIRE.  
2. FLEX CONDUIT MUST BE SECURED WITH A CONDUIT CLAMP (458296) WITHIN 12" OF CONDUIT TERMINATION AT THE HANDI-BOX OR ACTUATOR. CONDUIT RUNS MUST ALSO BE  
SECURED ALONG SLEEVE AT A MAXIMUM OF 24" ON CENTER.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WiRiNg DiAgRAMS  
DUCT SMOKE DETECTOR  
TOR w/ EP Switch  
RED  
DH100ACDCLP DUCT DETECTOR  
THE OCI WIRES MUST BE CHECKED TO VERIFY WHICH SET INDICATES THE CLOSED POSITION OF  
DAMPER. THIS SET OF WIRES SHOULD THEN BE LABELED WITH A BLUE WIRE MARKER (382169).  
TOR  
1
2
3
4
5
6
7
8
9
10  
A
B C  
24 VAC/VDC  
11 12 13 14 15 16 17 18 19 20  
BLUE  
SWITCH #2  
SWITCH #1  
RED  
SWITCHING DEVICE  
(BY OTHERS)  
DH100ACDCLP DUCT DETECTOR  
(OVERRIDE)  
1
2
3
4
5
6
7
8
9
10  
A
B
C
L1  
115 VAC  
(PRIMARY)  
11 12 13 14 15 16 17 18 19 20  
L2  
E/P SWITCH  
RED  
BLUE  
RED  
RED  
RED  
RED  
DH100ACDCLP DUCT DETECTOR  
OPTIONAL  
SECOND E/P SWITCH  
220/240 VAC  
1
2
3
4
5
6
7
8
9
10  
A
B C  
11 12 13 14 15 16 17 18 19 20  
E/P SWITCH  
RED  
OPTIONAL  
THIRD E/P SWITCH  
BLUE  
E/P SWITCH  
RED  
1. CONDUIT RUNS WHICH EXCEED 72" MUST HAVE GREEN GROUND WIRE.  
2. FLEX CONDUIT MUST BE SECURED WITH A CONDUIT CLAMP (458296) WITHIN 12" OF CONDUIT TERMINATION AT THE HANDI-BOX OR ACTUATOR. CONDUIT RUNS MUST ALSO BE  
SECURED ALONG SLEEVE AT A MAXIMUM OF 24" ON CENTER.  
Copyright © 2008 Greenheck Fan Corporation  
DH100 Smoke Detector Rev. 6 May 2008  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Grizzly Drill CR550H User Manual
Gyration Computer Keyboard GP3200 User Manual
Haier Air Conditioner HWR05XC9 User Manual
Haier Dishwasher HDW12 TFESS User Manual
Harbor Freight Tools Water Pump 68328 User Manual
HP Hewlett Packard Car Video System L1725 User Manual
HP Hewlett Packard Laptop 345561 001 User Manual
HP Hewlett Packard Portable Media Storage ESL9322S2 User Manual
IKEA Plumbing Product AA 291347 1 User Manual
Image Treadmill IMTL07611 User Manual