Part #457831
VSU Make-Up Air Unit
®
Installation, Operation and Maintenance Manual
Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the
product described. Protect yourself and others by observing all safety information. Failure to comply with instructions
could result in personal injury and/or property damage! Retain instructions for future reference.
2. The rotation of the wheel is critical. It must be
Model VSU
free to rotate without striking or rubbing any
stationary objects.
3. Motor must be securely and adequately
grounded.
4. Do not spin fan wheel faster than the maximum
cataloged fan rpm. Adjustments to fan speed
significantly affects motor load. If the fan RPM is
changed, the motor current should be checked
to make sure it is not exceeding the motor
nameplate amps.
5. Do not allow the power cable to kink or come
in contact with oil, grease, hot surfaces,
or chemicals. Replace cord immediately if
damaged.
6. Verify that the power source is compatible with
Optional Service
Platform Shown
the equipment.
7. Never open blower access doors while the fan is
running.
General Safety Information
FOR YOUR SAFETY
Only qualified personnel should install this unit.
Personnel should have a clear understanding of these
instructions and should be aware of general safety
precautions. Improper installation can result in electric
shock, possible injury due to coming in contact with
moving parts, as well as other potential hazards.
Other considerations may be required if high winds
or seismic activity are present. If more information
is needed, contact a licensed professional engineer
before moving forward.
If you smell gas:
1. Open windows.
2. Do not touch electrical switches.
3. Extinguish any open flame.
4. Immediately call your gas supplier.
FOR YOUR SAFETY
The use and storage of gasoline or
other flammable vapors and liquids in
open containers in the vicinity of this
appliance is hazardous.
1. Follow all local electrical and safety codes, as
well as the National Electrical Code (NEC), the
National Fire Protection Agency (NFPA), where
applicable. Follow the Canadian Electric Code
(CEC) in Canada.
WARNING
DANGER
Improper installation, adjustment,
alteration, service or maintenance can
cause property damage, injury or death.
Read the installation, operating and
maintenance instructions thoroughly
before installing or servicing this
equipment.
Always disconnect power before working on or
near a unit. Lock and tag the disconnect switch or
breaker to prevent accidental power up.
CAUTION
When servicing the unit, motor may be hot enough
to cause pain or injury. Allow motor to cool before
servicing.
Model VSU Make-Up Air Unit
Download from Www.Somanuals.com. All Manuals Search And Download.
1
Table of Contents
Installation
Installation
1. Filter/Stand Section
Filter/Stand Section . . . . . . . . . . . . . . . . . . . . . .3-4
Burner/Blower Section . . . . . . . . . . . . . . . . . . . . . 4
Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . 5
Direct Gas Piping . . . . . . . . . . . . . . . . . . . . . . . .6-7
Start-Up
The unit should be mounted on a concrete slab four
inches thick with a proper gravel drainage bed. Allow
one foot on each side of the unit as shown in the
Concrete Slab and Unit Footprint drawing below.
Concrete Slab Dimensions
Blower . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8-9
Direct Gas . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-12
Operation
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Troubleshooting
Blower . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15-17
Maintenance
Housing Size
40
78
A
B
C
D
E
135
43
54
111
All dimensions are shown in inches.
Routine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18-19
Fall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Reference
Building Wall
Approx. Stand Feet Locations
Typical Control Center Layout . . . . . . . . . . . . . . 20
Typical Gas Train Layout. . . . . . . . . . . . . . . . . . . 20
Start-Up Check List . . . . . . . . . . . . . . . . . . . . . . 21
Maintenance Log . . . . . . . . . . . . . . . . . . . . . .22-23
Warranty . . . . . . . . . . . . . . . . . . . . . . . . .Backcover
Concrete Slab
D
A
E
12
12
C
B
Concrete Slab and Unit Footprint
The filter section ships inside the stand (see drawing
on next page). After the unit is set on the slab, it can
be anchored through the stand feet. The unit footprint
of the unit is shown above.
Greenheck recommends having a three foot clearance
on the controls side and a two foot clearance on the
other three sides of the unit for serviceability.
The following statement pertains to direct gas units
only. When ordered with insulation, this unit has a
zero-inch clearance tolerance to any combustibles,
on all sides and top. Without insulation, the clearance
tolerance is six inches.
Model VSU Make-Up Air
3
®
Download from Www.Somanuals.com. All Manuals Search And Download.
4. Complete Installation
A typical horizontal discharge installation is shown.
Gas and/or electrical lines can be connected at this
time.
Installation continued
2. Burner/Blower Section
Use a crane and a spreader bar hooked to the factory
lifting lugs (shown below) to lift and center the unit
onto the filter stand section. The sections can be
caulked together, but it is not needed with the water
kickouts provided with this section.
For upblast units, a duct elbow may be needed to
turn the ductwork into the building. Follow proper
ductwork methods recommended by AMCA to make
this elbow to minimize duct losses.
3. Install Ductwork
This table shows the duct sizes and straight lengths
recommended for optimal performance (AMCA
Publication 201-90). Using duct sizes less than
recommended will affect fan performance. Good
duct installation practices should be followed for
the remaining ductwork. See the drawings in the
Dimensional Data section for duct locations.
Recommended Supply Ductwork Sizes
VSU
Blower Size
Duct
Size
Straight Duct
Length
220
68 x 26 inches
117 inches
Model VSU Make-Up Air
4
®
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional Data
Upblast Discharge
Elevation View
F
H
K
J
Lifting Lugs
Electrical Controls
Gas Controls*
C
A
E
24^
B
*Direct Gas units only
^Standard factory clearance. Additional stand heights are available from the factory.
Unit Dimensional Data
Blower Dimensional Data
Unit Weight
Housing
Size
Blower
Size
A
B
C
E
Filters
F
H
J
K
Blower/Heater*
Stand/Filter
40
111
54
95
144
(20) 20x25
220
26
20
68
12
2000 lbs.
700 lbs.
All dimensions are shown in inches.
* Weights will vary with blower and horsepower.
Model VSU Make-Up Air
5
®
Download from Www.Somanuals.com. All Manuals Search And Download.
1. Determine the Supply Gas
Requirements
Installation of Direct Gas Piping
The unit’s direct gas nameplate states the requirements
for the gas being supplied to the unit. The direct gas
nameplate is located on the outside of the unit on the
control center side.
Minimum gas pressure for
maximum output
IMPORTANT
All gas piping must be installed in accordance
with the latest edition of the National Fuel Gas
Code ANSI/Z223.1 and any local codes that may
apply. In Canada, the equipment shall be installed
in accordance with the Installation Code for Gas
Burning Appliances and Equipment (CGA B149)
and Provincial Regulations for the class. Authorities
having jurisdiction should be consulted before
installations are made.
MAX BTU/HR
BTU/H MAX
MIN BTU/HR
BTU/H MIN
NORMAL MANIFOLD
PRESSURE
PRESSION DÕADMISSION
NORMALE
MIN GAS PRESSURE
FOR MAX OUTPUT
PRESSION DE GAZ MIN
POUR PUISSANCE MAX
“ W.C.
“ W.C.
“ W.C.
“ W.C.
“ W.C.
WARNING
MIN GAS
PRESSURE
PRESSION DE GAZ
MAX GAS
PRESSURE
PRESSION DE GAZ
MAX
All components of this or any other gas-fired heating
unit must be leak tested prior to placing the unit
into operation. A soap and water solution should be
used to perform this test. NEVER test for gas leaks
with an open flame.
MIN BURNER
MAX BURNER
PRESSURE DROP
PERTE MIN DE PRESSION
DANS LE BRULEUR
PRESSURE DROP
PERTE MAX DE PRESSION
DANS LE BRULEUR
PSI
TYPE OF GAS
NATURE DU GAZ
DESIGN ∆T
∆T NORMALE
F
WARNING
EQUIPPED FOR
CONCU POUR
AGAINST
CONTE
EXTERNAL STATIC PRESSURE
SCFM
“ W.C.
If pressure testing in excess of 1/2 psig (3.5 kPa),
the heater and manual shutoff valve must be
disconnected from the supply gas line.
PRESSION STATIQUE EXTERIEURE
Type of gas
Maximum gas pressure
WARNING
Direct Gas Nameplate
If pressure testing at or below 1/2 psig (3.5 kPa), the
heater must be isolated from the supply gas line by
closing its manual shutoff valve.
2. Install Additional Regulator if Required
When the supply gas pressure exceeds the maximum
gas pressure shown on the direct gas nameplate, an
additional regulator (by others) is required to reduce
the pressure. The regulator must have a listed leak
limiting device or it must be vented to the outdoors.
IMPORTANT
All piping should be clean and free of any foreign
matter. Foreign material entering the gas train can
damage the valves, regulators and burner.
IMPORTANT
NOTE
Do NOT connect the unit to gas types other than
what is specified and do NOT connect the unit to
gas pressures that are outside of the pressure range
shown on the label.
The regulator located inside the unit is used to
adjust the unit’s maximum output temperature.
3. Connect the Supply Gas Line
NOTE
A manual shut off valve (gas cock), 1/8 in. plugged
test port and 6 in. drip leg must be installed prior to
the gas train. The valve and the test port must be
accessible for the connection of a test gauge. Supply
gas connections must be made by a qualified installer
and are not furnished by Greenheck.
When connecting the gas supply, the length of the
run must be considered in determining the pipe size
to avoid excessive pressure drop. Refer to a Gas
Engineer’s Handbook for gas pipe capacities.
To
Controls
Gas Cock
Ground Joint Union
From
Gas
Supply
1/8 in. Plugged Ta p
6 in. Trap
Supply Gas Line
Model VSU Make-Up Air
6
®
Download from Www.Somanuals.com. All Manuals Search And Download.
4. Pipe the Optional Vent Line
If an optional vent line is located between the safety
shutoff valves it must be piped to the outdoors.
WARNING
Reference the National Fuel Gas Code for additional
vent line requirements.
Vent Line Solenoid
To Outdoors
To Burner
From Supply
Safety
Shut-off Valves
Optional Vent Line
5. Test the System for Leaks
Check both the supply lines and the factory piping for
leaks. Apply a soap and water solution to all piping
and watch for bubbling which indicates a leak.
WARNING
NEVER test for a gas leak with an open flame.
NOTE
The factory piping has been checked for leaks, but
should be rechecked due to shipping and installation.
Model VSU Make-Up Air
7
®
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Check the Blower Rotation
Open the blower access door
and run the blower momentarily
to determine the rotation.
Start-Up - Blower
Refer to the Start-Up Checklist in the Reference
section before proceeding further!
Arrows are placed on the
Pre Start-Up Check
blower scroll to indicate the
proper direction or reference
the example shown to the right.
Rotate the fan wheel by hand and make sure no parts
are rubbing. Check the V-belt drive for proper alignment
and tension (a guide for proper belt tension and
alignment is provided in the Belt Maintenance section).
Check fasteners, set screws and locking collars on the
fan, bearings, drive, motor base, and accessories for
tightness.
Blower
Housing
Blower Rotation
NOTE
To reverse the rotation on three phase units,
disconnect and lock-out the power, then
interchange any two power leads.
WARNING
Disconnect and lock-out all power and gas before
performing any maintenance or service to the unit.
Failure to due so could result in serious injury or
death and damage to equipment.
NOTE
To reverse the rotation on single phase units,
disconnect and lock-out the power, then rewire the
motor per the manufacturer’s instructions.
IMPORTANT
SPECIAL EQUIPMENT REQUIRED
If the blower is rotating in the wrong direction, the
unit will move some air, but will not perform as
designed. Be sure to perform a visual inspection to
guarantee the correct blower rotation.
Required and recommended tools. Equivalent
products may be used.
Manufacturer:
Model:
Phone:
Fluke
177
1-800-44-FLUKE
Voltage &
Amperage
Meter
3. Check for Vibration
Check for unusual noise, vibration or overheating of
the bearings. Reference the Troubleshooting section
for corrective actions.
Manufacturer:
Model:
Phone:
Fluke
50
1-800-44-FLUKE
Thermometer
IMPORTANT
Manufacturer:
Model:
Fluke
116
1-800-44-FLUKE
Excessive vibration may be experienced during
the initial start-up. Left unchecked, it can cause a
multitude of problems including structural and/or
component failure.
Micro Amp
Meter
Phone:
Manufacturer:
Model:
Dwyer
Slack Tube
1-219-897-8000
IMPORTANT
U-Tube
Manometer
Phone:
Generally, fan vibration and noise is transmitted
to other parts of the building by the ductwork. To
minimize this undesirable effect, the use of heavy
canvas duct connectors is recommended.
Manufacturer: Monarch
Model:
Phone:
Pocket Tach 100
1-800-999-3390
Tachometer
4. Motor Check
Measure the motor’s voltage, amps and RPM.
Compare to the specifications. Motor amps can be
reduced by lowering the motor RPM or increasing
system static pressure.
WARNING
Check the housing, blower, and ductwork for any
foreign objects before running the blower.
1. Check the Voltage
Before starting the unit, compare the supplied voltage,
hertz, and phase with the unit and motor’s nameplate
information.
Voltage, Hertz, Phase
VOLTS
HZ
EXH HP
MOP
PH
SUP HP
MCA
Electrical Nameplate
Model VSU Make-Up Air
8
®
Download from Www.Somanuals.com. All Manuals Search And Download.
5. Air Volume Measurement & Check
Measure the unit’s air volume (cfm) and compare it with
it’s rated air volume. If the measured air volume is off,
adjust the fan’s RPM by changing/adjusting the drive.
NOTE
The most accurate way to measure the air volume is
by using a pitot traverse method downstream of the
blower. Other methods can be used, but should be
proven and accurate.
IMPORTANT
Changing the air volume can significantly increase
the motor’s amps. If the air volume is changed,
the motor’s amps must be checked to prevent
overloading the motor.
NOTE
To ensure accuracy, the dampers are to be open
when measuring the air volume.
6. Set-up Optional Components
Adjust the settings on the optional components. See
the Control Center Layout in the Reference section for
location of optional components.
• Heating Inlet Air Sensor
Typical setting: 60-70ºF
Model VSU Make-Up Air
9
®
Download from Www.Somanuals.com. All Manuals Search And Download.
3. Set the Burner Air Pressure Differential
With the fan running and discharging 70ºF (21ºC) air,
connect a U-Tube manometer to the outer sensing
probes (see below) and measure the static pressure
across the burner.
Start-Up Direct Gas
IMPORTANT
For proper unit function and safety, follow the start-
up procedure in the exact order that it is presented.
Outer Sensing Probes
IMPORTANT
This start-up should begin after all of the installation
procedures and the blower start-up have been
completed.
7
0.625 - 0.675 in. wc
1. Check the Supply Gas Pressure
Check the supply gas pressure and compare it with
the unit’s nameplate pressure requirements. Adjust
the supply regulator as needed until the supply gas
pressure is within the specified range. The direct gas
nameplate is located on the outside of the unit on the
control center side.
6
U-Tube
Manometer
Measuring the Pressure Drop
Minimum and maximum gas
pressures for maximum output
The proper static pressure should be between 0.625
and 0.675 inches wc (155.68 and 168.64 Pa). If
needed, evenly adjust the baffles on both sides of the
burner, keeping the burner centered in the opening
until the required pressure is obtained.
MAX BTU/HR
BTU/H MAX
MIN BTU/HR
BTU/H MIN
NORMAL MANIFOLD
PRESSURE
PRESSION DÕADMISSION
NORMALE
MIN GAS PRESSURE
FOR MAX OUTPUT
PRESSION DE GAZ MIN
POUR PUISSANCE MAX
“ W.C.
“ W.C.
“ W.C.
“ W.C.
“ W.C.
MIN GAS
PRESSURE
PRESSION DE GAZ
MAX GAS
PRESSURE
PRESSION DE GAZ
MAX
Burner
MIN BURNER
MAX BURNER
PRESSURE DROP
PERTE MIN DE PRESSION
DANS LE BRULEUR
PRESSURE DROP
PERTE MAX DE PRESSION
DANS LE BRULEUR
PSI
Adjustable
Baffle
Adjustable
Baffle
TYPE OF GAS
NATURE DU GAZ
DESIGN ∆T
∆T NORMALE
F
Airflow
Airflow
EQUIPPED FOR
CONCU POUR
AGAINST
CONTE
EXTERNAL STATIC PRESSURE
“ W.C.
SCFM
PRESSION STATIQUE EXTERIEURE
Type of gas
Burner and Baffles
Direct Gas Nameplate
NOTE
2. Check the Pilot Gas Pressure
The pressure drop was set at the factory and may
not need adjustment.
Check the pilot gas pressure. The recommended
gas pressure is 3 in. wc. Adjust the pilot regulator as
needed. See the Gas Train Layout in the Reference
section for the location of the pilot pressure test port
and pilot regulator.
NOTE
When required pressure is obtained, be sure to
reconnect the outer sensing probes.
IMPORTANT
IMPORTANT
This process may need to be repeated until the
proper pressure is achieved. This adjustment
will change the air quantity delivered by the unit
and therefore the air quantity delivered should be
rechecked. Refer to the Blower Start-Up section.
Proper air velocity over the burner is critical on direct
fired gas units. If the air velocity is not within the unit
specifications, the unit will not operate efficiently,
may have sporadic shutdowns, and may produce
excessive carbon monoxide (CO) or other gases.
NOTE
To increase the static pressure decrease the
opening. To decrease the static pressure increase
the opening.
Model VSU Make-Up Air
10
®
Download from Www.Somanuals.com. All Manuals Search And Download.
4. Set the Maximum Firing Rate
Monitor the unit’s actual temperature rise by placing
a thermocouple in the unit’s inlet and a second in the
discharge, three duct diameters downstream of the
burner.
Regulators and Modulating Valves
Remove one wire to
Remove cap to access
maximum firing rate
adjustment
send the unit to the
minimum firing rate
Send the unit to maximum fire by disconnecting and
isolating the wire connected to Terminal 4 on the
Maxitrol 14.
While monitoring the units temperature rise, set the
maximum firing rate by adjusting the regulator until the
designed temperature rise is achieved. After setting the
maximum firing rate, reconnect the wire to the amplifier.
Minimum
firing rate
adjustment
NOTE
Separate Regulator and Modulating Valves
Do not set the burner maximum firing rate based on gas
pressure. It should be set based on the unit’s designed
temperature rise shown on the direct gas label.
5. Set the Minimum Firing Rate
Disconnect and isolate one of the wires running to
the modulating valve to send the unit to its minimum
firing rate. Set the minimum firing rate by adjusting the
needle valve shown above.
MIN GAS
MAX GAS
PRESSURE
PRESSION DE GAZ
PRESSURE
PRESSION DE GAZ
MAX
“ W.C.
“ W.C.
“ W.C.
After setting the minimum firing rate, shut off the
pilot to ensure that the flame safeguard can still read
the main flame signal. Reconnect the wire to the
modulation valve and open the pilot shut-off valve.
MIN BURNER
MAX BURNER
PRESSURE DROP
PERTE MIN DE PRESSION
DANS LE BRULEUR
PRESSURE DROP
PERTE MAX DE PRESSION
DANS LE BRULEUR
PSI
TYPE OF GAS
NATURE DU GAZ
DESIGN ∆T
∆T NORMALE
F
EQUIPPED FOR
CONCU POUR
AGAINST
CONTE
EXTERNAL STATIC PRESSURE
NOTE
“ W.C.
SCFM
PRESSION STATIQUE EXTERIEURE
The minimum setting for the maximum firing rate
may be higher than required. This is acceptable. The
burner will modulate as needed.
Direct Gas Nameplate
IMPORTANT
Maxitrol Series 14 — 7 terminals
The proper minimum firing rate setting results in a
small ribbon of continuous flame which covers the
flame road and runs across the entire burner.
Remove the wire from terminal #4 to
send the unit to maximum fire
IMPORTANT
Do not allow the disconnected wire to come in
contact with a potential ground. Damage to the
amplifier or transformer could result.
NOTE
Gas trains are equipped with separate regulators
and modulating valves.
Low fire time delay setting (75% of maximum)
NOTE
IMPORTANT
Adjusting the maximum and minimum firing rate
requires the inlet air sensor to be set higher than the
outdoor air temperature in order to start the burner(s).
Once high and low fire have been set, the inlet air
sensor should be set to the desired temperature.
Setting the maximum firing rate during mild weather
conditions may cause the high limit to trip out during
extreme conditions requiring manual resetting.
NOTE
NOTE
Gas trains are equipped with either separate
regulators and modulating valves or with a
combined modulating valve.
Counterclockwise rotation increases the minimum
fire rate setting, clockwise rotation decreases the
setting.
NOTE
Clockwise rotation increases the temperature
rise, counterclockwise rotation decreases the
temperature rise.
Model VSU Make-Up Air
11
®
Download from Www.Somanuals.com. All Manuals Search And Download.
6. Set the Unit’s Operating Temperature
Set the operating temperature. The operating
temperature setting depends on which Maxitrol controller
is used.
Maxitrol Series 14
The Maxitrol Series 14 should be set to the desired
discharge temperature. The temperature selector is built
into the amplifier.
Set the discharge temperature
Typical: 65ºF
Series 14 Discharge Temperature Setting
7. Flame Signal Check
To measure the flame signal connect a standard DC
voltmeter to the flame amplifier test jacks + and -
(com) as shown to
the right. The flame
signal should be
above 1.25 VDC and
steady.
Check the flame
signal with the
burner at pilot only,
minimum fire, mid
fire and high fire.
DC Voltmeter and
Flame Amplifier
IMPORTANT
If the flame signal is not above 1.25 VDC and steady,
consult the troubleshooting section.
Model VSU Make-Up Air
12
®
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation - Electrical
Electrical Sequence
Direct Gas Burner Sequence
1. Supply Fan Contact (S2) Closed
1. Supply Fan Contact Closed
• Power passes to damper which opens
• Power passes to the supply fan and heat switch
• When damper is fully opened, damper relay
(D1) is energized an optional N.O. damper limit
switch (DL1) closes
2. Heat Contact Closed
• Power passes to the heat relay then to the
Flame Safeguard
• Power passes through a N.C. fault contact on
soft starter (PST(FAULT))
• Power passes to and energizes supply fan relay
(RI)
3. Flame Safeguard (FSG) Sequence
• Checks for proper airflow
• Verifies no flame present at burner
• Initiates 10 second prepurge
• Sends power to open pilot gas valve (V1) and
energizes the spark generator (SG) (clicking of
the spark generator may be heard)
• Tries for up to 10 seconds to light pilot and
confirm flame
• Powers the main gas valves open
• Shuts down spark generator
• Continuously monitors the flame and airflow
• Supply fan starts
2. Heat Contact (S4) Closed
• Power passes to N.O. fan relay which is
energized and closed
• Power passes to inlet air sensor contact (TS)
which is energized and closed if the inlet air
temperature is below the set point
• Power passes to and energizes the heat relay
(RH)
• N.O. heat relay contact (RH) closes
• Power passes to and energizes terminal 5 of the
• Performs self-diagnostic check every five
seconds
Flame Safeguard (FSG).
• Power passes to N.C. high limit control contact
(HLC) which is closed if temperature has
remained below the high limit set point
• Power passes to terminal 6 of the Flame
Safeguard (FSG)
• Flame Safeguard (FSG) begins direct gas burner
sequence (see Direct Gas Burner sequence)
Model VSU Make-Up Air
13
®
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
Blower Does Not Operate
No
115 VAC between
Check Main Voltage
(See Blower Start-Up Step #1)
Main Disconnect (DS1) Off
(Turn Main Disconnect DS1 On)
Primary Fuses Blown
terminals 102 and 101?
Yes
(Replace Fuses)
Main Transformer Defective
(Replace Transformer)
No
No
No
24 VAC between
terminals R and X?
Main Transformer Defective
Yes
(Replace Transformer)
24 VAC between
terminals G and X?
Supply Switch (S2) Off
(Turn Supply Switch (S2) On)
Yes
24 VAC between
terminals 7 and X?
Yes
Damper Limit Switch (DL1) Holding
(Wait for actuator to open fully or adjust limit switch)
Broken Fan Belt
(Replace - Reference Maintenance section)
Defective motor or capacitor
(Repair/Replace)
Blown Motor Fuse
(Replace)
One or more legs of 3 phase is out
(Restore missing legs)
At this time the supply should be energized., passing
power to the supply motor and the blower should start.
Model VSU Make-Up Air
14
®
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
Heater Does Not Operate
Does not attempt to light (No visible spark)
No
No
No
24 VAC between
terminals W1 and X?
Heat Switch (S4) Off
(Turn Heat Switch (S4) On)
Heat Switch Not Wired
(Wire Heat Switch (S4))
Yes
115 VAC between
terminals 102 and 101?
Primary Fuses Blown
(Replace Fuses)
Main Transformer (TR4) Defective
(Replace Transformer)
Yes
115 VAC between
terminals 103 and 101?
Inlet Air Sensor (TS) Holding
(Adjust TS setting — Reference Blower Start-Up Step #6)
Heat Relay (RH) Defective
Yes
(Replace Heat Relay (RH))
The power light on the flame safeguard should
blink approximately every 5 seconds as it
performs a self-diagnostics check.
No
No
115 VAC between
terminals 104 and 101?
High Limit (HLC) Tripped
(Reset/Replace High Limit (HLC))
(Check on cause of control loss)
Yes
Continuity between
terminals 107 and 108?
Airflow Switch (PS) Holding for Proper Airflow
(Correct airflow across burner)
Yes
(Reference Direct Gas Start-Up Step #3)
At this time the heater should attempt to light.
(The pilot light on the flame safeguard should illuminate).
Model VSU Make-Up Air
15
®
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
Heater Does Not Operate
Attempts to light, but no pilot (visible spark)
Check inlet gas pressure.
Note: The minimum and maximum gas pressures
for your unit are shown on the direct gas label.
(Reference Direct Gas Start-Up – Step #1)
(Direct Gas Start-Up Step #1)
Yes
Gas pressure between the
No
minimum and maximum shown
on the direct gas label?
Correct gas pressure
(Reference Direct Gas Start-Up – Step #1)
Yes
Air in the gas line?
Purge gas line
(Verify gas at the pilot)
No
Check for proper airflow
(Direct Gas Start-Up Step #3)
Note: The airflow may satisfy the airflow switch,
but may make lighting the pilot difficult. Adjust the
pressure drop across the burner between 0.625 and
0.675 in. wc shown in Direct Gas Start-Up – Step #3
Yes
Pressure drop across the burner
between 0.625 and 0.675 in. wc?
No
Adjust burner baffles
(Reference Direct Gas Start-Up – Step #3)
Yes
Crossed flame and spark wires
(Uncross wires and reconnect)
Incorrect spark plug gap
(Set spark plug gap to 0.062 in.)
Defective spark plug
No
Proper spark?
Yes
(Replace spark plug)
Check for proper pilot pressure
(Direct Gas Start-Up Step #2)
Note: A high pilot pressure will make lighting more
difficult. Lower the pilot pressure in increments
until the unit lights. Then set the pilot per the
instruction in Direct Gas Start-Up – Step. #2
No
No
Pilot pressure correct?
Adjust the pilot pressure
(Reference Direct Gas Start-Up – Step #2)
Yes
With proper airflow, gas pressure and spark,
the unit should light.
If problems remain, consult the factory
Model VSU Make-Up Air
16
®
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
Heater Does Not Operate
Visible pilot
Measure the flame signal
when there is a visible pilot
Note: The flame signal should be steady and
above 1.25 VDC with a visible pilot.
(Reference Direct Gas Start-Up – Step #7)
Flame signal greater
than 1.25 VDC
No
Unit is not grounded
(Properly ground unit)
Flame rod is grounding out
(Adjust the flame rod to avoid contact with the burner or the unit)
Cracked porcelain on flame rod
(Replace flame rod)
Yes
Check for proper airflow
(Direct Gas Start-Up Step #3)
Note: When the pressure is low or marginal and the unit
begins heating, the air density will change. This can cause
the pressure to drop below the minimum setting. Also, low
airflow can cause the flame to walk out of the burner and
away from the flame sensor, causing the unit to recycle.
Pressure drop across the burner
between 0.625 and 0.675 in. wc?
No
Adjust burner baffles
(Reference Direct Gas Start-Up – Step #3)
Yes
Check the minimum firing rate
(Direct Gas Start-Up Step #4
No
No
Is the minimum firing rate
set correctly?
Adjust the minimum firing rate
(Reference Direct Gas Start-Up – Step #4)
Yes
Does the flame signal
remain constant?
If the signal slowly drops off, typically the airflow is too low
(Reference Blower Start-Up – Step #4)
If it suddenly drops to zero, the flame rod is grounding out
(Adjust the flame rod to avoid contact with the burner or the unit)
Yes
If the flame signal is above 1.25 VDC and constant,
the main gas valves will remain open until the call
for heat is interrupted or the unit is shut down.
Model VSU Make-Up Air
17
®
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance - Routine
Motors
CAUTION
Motor maintenance is generally limited to cleaning
and lubrication (where applicable).
Cleaning should be limited to exterior surfaces only.
Removing dust and grease build-up on the motor
assures proper motor cooling.
Motors supplied with grease fittings should be
greased in accordance with the manufacturer’s
recommendations.
Lock-out the gas and the electrical power to the
unit before performing any maintenance or service
operations to this unit.
V-Belt Drives
V-belt drives must be checked on a regular basis for
wear, tension, alignment, and dirt accumulation.
Check the tension by measuring the deflection in the
belt as shown below.
IMPORTANT
Check the alignment by using a straight edge across
both sheaves as shown below.
Do not allow water or solvents to enter the motor
or bearings. Motors and bearings should never be
sprayed with steam, water or solvents.
IMPORTANT
IMPORTANT
Premature or frequent belt failures can be caused by
improper belt tension or misaligned sheaves.
Greasing motors is only intended when fittings are
provided. Many motors are permanently lubricated,
requiring no additional lubrication.
• Abnormally high belt tension or drive misalignment
will cause excessive bearing loads and may result
in failure of the fan and/or motor bearings.
• Abnormally low belt tension will cause squealing
on start-up, excessive belt flutter, slippage, and
overheated sheaves.
Wheels
Wheels require little attention when moving clean air.
Occasionally oil and dust may accumulate on the wheel
causing imbalance. When this occurs the wheel and
housing should be cleaned to assure proper operation.
IMPORTANT
Do not pry belts on or off the sheave. Loosen belt
tension until belts can be removed by simply lifting
the belts off the sheaves.
Filters
IMPORTANT
Filter maintenance is generally limited to cleaning and
replacement.
When replacing V-belts on multiple groove drives,
all belts should be changed to provide uniform drive
loading.
Aluminum mesh filters can be washed in warm soapy
water.
An adhesive spray can be added to aluminum mesh
filters to increase their efficiency.
IMPORTANT
Do not install new belts on worn sheaves. If the
sheaves have grooves worn in them, they must be
replaced before new belts are installed.
IMPORTANT
When reinstalling filters, be sure to install them
with the airflow in the correct direction. An airflow
direction arrow is located on the side of the filters.
Belt Span
Deflection =
64
IMPORTANT
Replacement filters should be from the same
manufacturer and the same size as the original
filters provided with the unit.
Belt Span
Belt Tension
Drive Alignment
Model VSU Make-Up Air
18
®
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance - Fall
Bearings
Start-Up
Repeat the Blower Start-Up Step #5 and Direct Gas Start-
Up Steps #1 through #4. This will ensure that the gas and
air are set properly before the heating season begins and
should lead to trouble free operation all winter.
The bearings for Greenheck fans are carefully selected
to match the maximum load and operating conditions
of the specific class, arrangement and fan size. The
instructions provided in this manual and those provided
by the bearing manufacturer will minimize any bearing
problems.
High Limit
The high limit switch may have tripped over the
summer; it should be checked and reset if necessary.
IMPORTANT
Burner
Lubricate bearings prior to periods of extended
shutdowns or storage and rotate shaft monthly to
aid in corrosion prevention. If the fan is stored more
than three months, purge the bearings with new
grease prior to start-up.
Inspect the burner for accumulation of scales on both
the upstream and downstream sides of the mixing
plates. Any scaling or foreign material should be
removed with a wire brush.
Visually check that all holes in the mixing plates are clear.
If any burner ports are plugged (even partially), clear
them with a piece of wire or another appropriate tool.
Recommended Bearing Lubrication Schedule (in Months*)
Bearing Bore Size (inches)
Fan
RPM
1
⁄2
-1
11⁄8 -11⁄2
15⁄8 - 17⁄8 115⁄16 -23⁄16
27⁄16 -3
3
Replace or tighten any loose or missing fasteners on
the mixing plates. Always use zinc plated or stainless
steel fasteners.
750
6
5
4
3
*Suggested initial greasing interval is based on 12 hour per
day operation and 150°F maximum housing temperature.
For continuous (24 hour) operation, decrease greasing
interval by 50%
Inspect and clean the flame and spark rod. Occasional
replacement of the flame rod and spark rod may be
necessary to ensure optimum unit performance.
• If extended grease lines are present, relubricate while in
operation, only without endangering personnel.
WARNING
• For ball bearings (operating) relubricate until clean grease
is seen purging at the seals. Be sure not to unseat the seal
by over lubricating.
• For ball bearings (idle) add 1-2 shots of grease up to
2 inch bore size, and 4-5 shots above 2 inch bore sizes
with a hand grease gun.
• For roller bearings add 4 shots of grease up to 2 inch bore
size, and 8 shots for 2-5 inch bore size with a hand grease
gun.
Do not enlarge burner ports when clearing a
blockage, performance could be affected.
NOTE
Flame rods can last many years, but because of
thermal expansion of the porcelain, flame rods can
fail over time.
• Adjust relubrication frequency based on condition of
purged grease.
• A high quality lithium based grease conforming to NLGI
Grade 2 consistency, such as those listed here:
Mobil 532
Mobilux #2
Texaco Multifak #2
Texaco Premium #2 Exxon Unirex #2
B Shell Alavania #2
Model VSU Make-Up Air
19
®
Download from Www.Somanuals.com. All Manuals Search And Download.
Reference
Typical Control Center Layout
1
5
7
2
3
4
6
12
8
9
10
11
1. Spark Generator
7. Motor Fuses
2. Temperature Selector
3. Amplifier
4. 24V Transformer
5. 120V Transformer
6. Transformer Fuses
8. Heating Inlet Air Switch
9. Flame Safeguard
10. High Limit Switch
11. Disconnect
12. Soft Start
Typical Gas Train Layout
High/Low
Gas Pressure
Airflow Switch*
View Port
Pilot Solenoid
Valve
Modulating
Valve
Pilot Regulator
Manual Shutoff*
Hand
Valve
Gas Supply
Connection
Fluid Valve
*Two are provided on Canadian units.
Model VSU Make-Up Air
20
®
Download from Www.Somanuals.com. All Manuals Search And Download.
Reference
Start-Up Checklist
Start-Up Direct Gas – refer to Direct Gas Start-
Up section for further detail.
Unit Model Number _______________________________
(e.g. VSU-220-H40-UB)
o Check supply gas pressure
________ Maximum
________ Minimum
Unit Serial Number _______________________________
(e.g. 04c99999 or 10111000)
Start-Up Date
_______________________________
________ Actual
Start-Up Personnel Name__________________________
Start-Up Company _______________________________
o Check Pilot Gas Pressure
________ Actual Setting
Typical 3.0 inch wc
Phone Number
_______________________________
o Set optional High Gas Pressure Switch
________ Actual Setting
Typical 8.0 inch wc
Pre Start-Up Checklist – check boxes as items
are completed.
o Check tightness of all factory wiring connections
o Verify control wiring wire gauge
o Hand-rotate blower to verify free rotation
o Verify supply voltage to the main disconnect
o Verify the supply gas pressure
o Set optional Low Gas Pressure Switch
________ Actual Setting
Typical 3.0 inch wc
o Set Burner Pressure Differential
________ Actual Setting
Typical 0.65 inch wc
o Set the maximum firing rate
________ temp rise
o Verify remote controls wiring
Start-Up Blower Checklist – refer to Blower
Start-Up section for further detail.
o Check line voltage
L1-L2 __________
L2-L3 __________
L1-L3 __________
o Set the minimum firing rate
________ check
o Check blower rotation
o Check for vibration
o Supply fan RPM
o Motor nameplate amps
o Actual motor amps
o Actual CFM delivered
o Set the unit’s operating temperature
________ ºF
_________ RPM
_________ Amps
_________ Amps
_________ CFM
Optional Accessories – refer to Blower Start-Up
section, Step #6 for further detail.
o Heating Inlet Air Sensor
________ Actual Setting
Typical setting 60º-70ºF
Model VSU Make-Up Air
21
®
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance Log
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Model VSU Make-Up Air
22
®
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance Log
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Model VSU Make-Up Air
23
®
Download from Www.Somanuals.com. All Manuals Search And Download.
Warranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from
the shipment date. Any units or parts which prove defective during the warranty period will be replaced at our option
when returned to our factory, transportation prepaid. Motors are warranted by the motor manufacturer for a period of
one year. Should motors furnished by Greenheck prove defective during this period, they should be returned to the
nearest authorized motor service station. Greenheck will not be responsible for any removal or installation costs.
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.
Greenheck’s Model VSU catalog provides additional
information describing the equipment, fan performance,
available accessories, and specification data.
AMCA Publication 410-96, Safety Practices for Users and
Installers of Industrial and Commercial Fans, provides
additional safety information. This publication can be
®
Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: [email protected] • Web site: www.greenheck.com
457831 • Model VSU IOM, Rev. 3, March 2009
Copyright 2009 © Greenheck Fan Corporation
24
Download from Www.Somanuals.com. All Manuals Search And Download.
|