Goodman Mfg Heating System PG 15 User Manual

INSTALLATION INSTRUCTIONS  
FOR SINGLE PACKAGE  
GAS-ELECTRIC HEATING & COOLING UNITS  
*PG 15 SEER “M” SERIES  
Affix this manual and Users Information Manual adjacent to the unit.  
This Forced Air Central Unit Design Complies With  
Requirements Embodied in The American National  
Standard / National Standard of Canada Shown Below.  
ANSI Z21.47•CSA-2.3 Central Furnaces  
RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.  
ATTENTION INSTALLING PERSONNEL  
Prior to installation, thoroughly familiarize yourself with this Installation Manual. Observe all safety warnings. During  
installation or repair, caution is to be observed.  
It is your responsibility to install the product safely and to educate the customer on its safe use.  
These installation instructions cover the outdoor  
*NOTE: Please contact your distributor or  
installation of single package gas electric heating and  
our website for the applicable  
cooling units. See the Specification Sheet applicable to  
Specification Sheet referred to in this  
your model* for information regarding accessories.  
manual.  
Goodman Manufacturing Company, L.P.  
5151 San Felipe, Suite 500, Houston, TX 77056  
© 2006 - 2009, 2012 Goodman Manufacturing Company, L.P.  
IO-324H  
11/12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INDEX  
MAINTENANCE .................................................................................................................................................................. 17  
FILTER REPLACEMENT OR CLEANING.................................................................................................................... 17  
CABINET FINISH MAINTENANCE ........................................................................................................................... 17  
CLEAN OUTSIDE COIL (QUALIFIED SERVICER ONLY)............................................................................................. 17  
CONDENSER, EVAPORATOR, AND INDUCED DRAFT MOTORS ..................................................................................... 17  
FLAME SENSOR (QUALIFIED SERVICER ONLY) ...................................................................................................... 17  
FLUE PASSAGES (QUALIFIED SERVICER ONLY) ..................................................................................................... 17  
CLEANING FLUE PASSAGES (QUALIFIED SERVICER ONLY) ...................................................................................... 17  
MAIN BURNER FLAME (QUALIFIED SERVICER ONLY).............................................................................................. 18  
CLEANING BURNERS ......................................................................................................................................... 18  
ACCESSORIES AND FUNCTIONAL PARTS ...................................................................................................................... 18  
SHEET METAL ACCESSORIES .............................................................................................................................. 18  
FUNCTIONAL PARTS .......................................................................................................................................... 18  
GENERAL INFORMATION ..................................................................................................................................... 18  
APPENDIX ......................................................................................................................................................................... 19  
IGNITION CONTROL DIAGNOSTIC INDICATOR CHART .................................................................................................. 21  
HEATING TIMING CHART .................................................................................................................................... 21  
COOLING TIMING CHART ................................................................................................................................... 21  
UNIT DIMENSIONS ............................................................................................................................................ 22  
*PG15*****41A* WIRING DIAGRAM .................................................................................................................. 23  
*PG15*****41B* WIRING DIAGRAM ................................................................................................................. 23  
MINIMUM CLEARANCES ..................................................................................................................................... 27  
RECOMMENDED FILTER SIZES ............................................................................................................................ 27  
BLOWER PERFORMANCE DATA ............................................................................................................................ 28  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
REPLACEMENT PARTS  
ORDERING PARTS  
When reporting shortages or damages, or ordering repair  
parts, give the complete unit model and serial numbers as  
stamped on the unit’s nameplate.  
Replacement parts for this appliance are available through  
your contractor or local distributor. For the location of your  
nearest distributor, consult the white business pages, the  
yellow page section of the local telephone book or contact:  
CONSUMERAFFAIRS  
GOODMAN MANUFACTURING COMPANY, L.P.  
7401 SECURITY WAY  
HOUSTON, TEXAS 77040  
(713) 254-4729  
SAFETY INSTRUCTIONS  
TO THE INSTALLER  
Before installing this unit, please read this manual to  
familiarize yourself on the specific items which must be  
adhered to, including maximum external static pressure to  
unit, air temperature rise, minimum or maximum CFM and  
motor speed connections.  
TO THE OWNER  
A warranty certificate is provided with the unit. Read the  
warranty carefully and note what is covered. Keep the warranty  
certificate in a safe place so you can find it when necessary.  
Keep this literature in a safe place for future reference.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
To avoid possible illness or death of the building occupants,  
do NOT locate outside air intake device (economizer,  
manual fresh air intake, motorized fresh air intake) too  
close to an exhaust outlet, gas vent termination, or  
plumbing vent outlet. For specific distances required,  
consult local codes.  
Allow minimum clearances from the enclosure for fire  
protection, proper operation, and service access (see  
appendix). These clearances must be permanently  
maintained.  
The combustion air inlet and flue outlet hoods on the unit  
must never be obstructed. If used, do not allow the  
economizer/manual fresh air damper/ motorized fresh air  
damper to become blocked by snow or debris. In some  
climates or locations, it may be necessary to elevate the  
unit to avoid these problems.  
CARBON MONOXIDE POISONING HAZARD  
Special Warning for Installation of Furnaces or Air Handling Units in  
Enclosed Areas such as Garages, Utility Rooms or Parking Areas  
Carbon monoxide producing devices (such as an automobile, space  
heater, gas water heater, etc.) should not be operated in enclosed areas  
such as unventilated garages, utility rooms or parking areas because of  
the danger of carbon monoxide (CO) poisoning resulting from the exhaust  
emissions. If a furnace or air handler is installed in an enclosed area such  
as a garage, utility room or parking area and a carbon monoxide producing  
device is operated therein, there must be adequate, direct outside  
ventilation.  
When the unit is heating, the temperature of the return air  
entering the unit must be between 50° F and 100° F.  
GROUND LEVEL INSTALLATIONS ONLY:  
This ventilation is necessary to avoid the danger of CO poisoning which  
can occur if a carbon monoxide producing device continues to operate in  
the enclosed area. Carbon monoxide emissions can be (re)circulated  
throughout the structure if the furnace or air handler is operating in any  
mode.  
When the unit is installed on the ground adjacent to the  
building, a level concrete (or equal) base is recommended.  
Prepare a base that is 3” larger than the package unit  
footprint and a minimum of 3” thick.  
CO can cause serious illness including permanent brain damage or death.  
The base should also be located where no runoff of water  
from higher ground can collect in the unit.  
B10259-216  
UNIT LOCATION  
IMPORTANT NOTE: Remove wood shipping rails prior to instal-  
lation of the unit.  
ALL INSTALLATIONS:  
For proper flame pattern within the heat exchanger and  
proper condensate drainage, the unit must be mounted  
level.  
The flue outlet hood must be at least 12 inches from any  
opening through which flue gases could enter a building,  
and at least three feet above any forced air inlet located  
within ten feet. The economizer/manual fresh air intake/  
motorized fresh air intake and combustion air inlet  
mounted on the unit are not affected by this restriction.  
OutsideSlabInstallation  
ROOFTOP INSTALLATIONS ONLY:  
To avoid possible corrosion of the heat exchanger, do  
not locate the unit in an area where the outdoor air (i.e.  
combustion air for the unit) will be frequently  
contaminated by compounds containing chlorine or  
fluorine. Common sources of such compounds include  
swimming pool chemicals and chlorine bleaches, paint  
stripper, adhesives, paints, varnishes, sealers, waxes  
(which are not yet dried) and solvents used during  
construction and remodeling. Various commercial and  
industrial processes may also be sources of chlorine/  
fluorine compounds.  
NOTE: To ensure proper condensate drainage, unit must be  
installed in a level position.  
To avoid possible property damage or personal injury, the  
roof must have sufficient structural strength to carry the  
weight of the unit(s) and snow or water loads as required  
by local codes. Consult a structural engineer to determine  
the weight capabilities of the roof.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
GENERAL INFORMATION  
This unit is approved for outdoor installation ONLY. Rated  
performance is achieved after 72 hours of operation. Rated  
performance is delivered at the specified airflow. See outdoor  
unit specification sheet for split system models or product  
specification sheet for packaged and light commercial  
models. Specification sheets can be found at  
www.goodmanmfg.com for Goodman® brand products or  
www.amana-hac.com for Amana® brand products. Within  
either website, please select the residential or commercial  
products menu and then select the submenu for the type of  
product to be installed, such as air conditioners or heat  
pumps, to access a list of product pages that each contain  
links to that model’s specification sheet.  
To assure that your unit operates safely and efficiently, it must  
be installed, operated, and maintained in accordance with  
these installation and operating instructions, all local building  
codes and ordinances, or in their absence, with the latest  
edition of the National Fuel Gas Code NFPA 54/ANSI Z223.1  
and National Standard of Canada CAN/CSA B149 Installation  
Codes.  
RooftopInstallation  
The unit may be installed directly on wood floors or on  
Class A, Class B, or Class C roof covering material.  
To avoid possible personal injury, a safe, flat surface for  
service personnel should be provided.  
The heating and cooling capacities of the unit should be  
greater than or equal to the design heating and cooling loads  
of the area to be conditioned. The loads should be calculated  
by an approved method or in accordance with A.S.H.R.A.E.  
Guide or Manual J - Load Calculations published by the Air  
Conditioning Contractors of America.  
ROOF CURB INSTALLATIONS ONLY:  
Sufficient structural support must be determined prior to  
locating and mounting the curb and package unit.  
Ductwork must be constructed using industry guidelines.  
The duct work must be placed into the roof curb before  
mounting the package unit.  
Obtain from:  
American National Standards Institute  
1430 Broadway  
Curb insulation, cant strips, flashing and general roofing  
material are furnished by the contractor.  
New York, NY 10018  
TRANSPORTATION DAMAGE  
Check the carton upon arrival for external damage. If damage  
is found, a request for inspection by carrier agent should be  
made in writing immediately.  
Carefully inspect the unit for damage including damage to  
the cabinetry. Any bolts or screws which may have loosened  
in transit must be re-tightened. In the event of damage, the  
receiver should:  
1. Make notation on delivery receipt of any visible damage to  
shipment or container.  
2. Notify carrier promptly and request an inspection.  
3. In case of concealed damage, carrier should be notified  
as soon as possible-preferably within 5 days.  
4. File the claim with the following supporting documents:  
a. Original Bill of Lading, certified copy, or indemnity bond.  
b. Original paid freight bill or indemnity in lieu thereof.  
c. Original invoice or certified copy thereof, showing trade  
and other discounts or reductions.  
d. Copy of the inspection report issued by carrier  
representative at the time damage is reported to the  
carrier. The carrier is responsible for making prompt  
inspection of damage and for a thorough investigation  
of each claim. The distributor or manufacturer will not  
accept claims from dealers for transportation damage.  
RoofCurbInstallation  
NOTE: When inspecting the unit for transportation damage,  
remove all packaging materials. Recycle or dispose of the  
packaging material according to local codes.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
burners must not exceed the rated input shown on the rating  
plate. Overfiring of the unit could result in premature heat  
exchanger failure.  
RIGGING DETAILS  
HIGH ALTITUDE DERATE (U.S. INSTALLATIONS ONLY)  
IMPORTANT NOTE: The gas/electric units naturally derate with  
altitude. Do not attempt to increase the firing rate by changing  
orifices or increasing the manifold pressure. This can cause  
poor combustion and equipment failure. At all altitudes, the  
manifold pressure must be within 0.3 inches W.C. of that listed  
on the nameplate for the fuel used. At all altitudes and with  
either fuel, the air temperature rise must be within the range  
listed on the unit nameplate.  
IMPORTANT NOTE: If using bottom discharge with roof curb,  
ductwork should be attached to the curb prior to installing the  
unit. Ductwork dimensions are shown in roof curb installation  
instructions.  
Refer to the Roof Curb Installation Instructions for proper curb  
installation. Curbing must be installed in compliance with the  
National Roofing Contractors Association Manual.  
Refer to the Installation Manual provided with the LP kit for  
conversion from natural gas to propane gas and for altitude  
adjustments.  
Lower unit carefully onto roof mounting curb. While rigging  
unit, center of gravity will cause condenser end to be lower  
than supply air end.  
Use HA02 for installations above 2000’.  
PIPING  
IMPORTANT NOTE: To avoid possible unsatisfactory operation  
or equipment damage due to under firing of equipment, do  
not undersize the natural/propane gas piping from the meter/  
tank to the unit. When sizing a trunk line, include all appliances  
on that line that could be operated simultaneously.  
The rating plate is stamped with the model number, type of  
gas and gas input rating. Make sure the unit is equipped to  
operate on the type of gas available. The gas line installation  
must comply with local codes, or in the absence of local codes,  
with the latest edition of the National Fuel Gas Code NFPA 54/  
ANSI Z223.1.  
NaturalGasConnection  
Natural Gas Capacity of Pipe  
in Cubic Feet of Gas Per Hour (CFH)  
Nominal Black Pipe Size (inches)  
Length of  
Pipe in Feet  
1
1/2  
132  
92  
73  
63  
56  
50  
46  
43  
40  
38  
3/4  
278  
190  
152  
130  
115  
105  
96  
1
1/4  
1050  
730  
590  
500  
440  
400  
370  
350  
320  
305  
1
1/2  
1600  
1100  
980  
760  
670  
610  
560  
530  
490  
460  
10  
20  
30  
40  
50  
60  
70  
80  
90  
100  
520  
350  
285  
245  
215  
195  
180  
170  
160  
150  
Rigging  
GAS PIPING  
90  
84  
79  
IMPORTANT NOTE: This unit is factory set to operate on natural  
gas at the altitudes shown on the rating plate.  
Pressure = .50 PSIG or less and Pressure Drop of 0.3" W.C. (Based  
on 0.60 Specific Gravity Gas)  
BTUH Furnace Input  
CFH =  
Heating Value of Gas (BTU/Cubic Foot)  
Refer to the Proper Piping Practice drawing for the general  
layout at the unit. The following rules apply:  
1. Use black iron pipe and fittings for the supply piping. The  
use of a flex connector and/or copper piping is permitted  
as long as it is in agreement with local codes.  
2. Use pipe joint compound on male threads only. Pipe joint  
compound must be resistant to the action of the fuel used.  
The rating plate is stamped with the model number, type of gas  
and gas input rating. Make sure the unit is equipped to operate on  
the type of gas available. Conversion to LP gas is permitted with  
the use of the factory authorized conversion kit LPM-05.  
3. Use ground joint unions.  
INLET GAS PRESSURE  
4. Install a drip leg to trap dirt and moisture before it can  
enter the gas valve. The drip leg must be a minimum of  
three inches long.  
5. Use two pipe wrenches when making connection to the  
gas valve to keep it from turning.  
6. Install a manual shut-off valve in a convenient location  
(within six feet of unit) between the meter and the unit.  
7. Tighten all joints securely.  
Natural  
Min. 5.0" W.C., Max. 10.0" W.C.  
Min. 11.0" W.C., Max. 13.0" W.C.  
Propane  
Inlet Gas Pressure Must Not Exceed the Maximum Value Shown in  
Table Above.  
The minimum supply pressure should not vary from that  
shown in the table above because this could prevent the unit  
from having dependable ignition. In addition, gas input to the  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
There will be air in the gas supply line after testing for leaks  
on a new installation. Therefore, the air must be bled from the  
line by loosening the ground joint union until pure gas is  
expelled. Tighten union and wait for five minutes until all gas  
has been dissipated in the air. Be certain there is no open  
flame in the vicinity during air bleeding procedure. The unit is  
placed in operation by closing the main electrical disconnect  
switch for the unit.  
8. The unit must be connected to the building piping by one  
of the following methods:  
Rigid metallic pipe and fittings  
Semirigid metallic tubing and metallic fittings  
(Aluminum alloy tubing must not be used in exterior  
locations)  
Listed gas appliance connectors used in accordance  
with the terms of their listing that are completely in the  
same room as the equipment  
PROPANE GAS INSTALLATIONS  
In the prior two methods above the connector or tubing  
must be protected from physical and thermal damage.  
Aluminum alloy tubing and connectors must be coated  
to protect against external corrosion when in contact  
with masonry, plaster or insulation or are subject to  
repeated wettings by liquids (water - not rain water,  
detergents or sewage)  
IMPORTANT NOTE: Propane gas conversion kits must be  
installed to convert units to propane gas. Refer to the gas  
piping section for the correct LP kit for conversion.  
MANUAL  
SHUT-OFF  
VALVE  
All propane gas equipment must conform to the safety  
standards of the National Board of Fire Underwriters (See  
NBFU Manual 58).  
For satisfactory operation, propane gas supply pressure must  
be within 9.7 - 10.3 inches W.C. at the manifold with all gas  
appliances in operation. Maintaining proper gas pressure  
depends on three main factors:  
DRIP LEG  
1. Vaporization rate, which depends on (a) temperature of  
the liquid, and (b) wetted surface area of the container or  
containers.  
GROUND JOINT UNION  
(INSTALLED AHEAD OF GAS VALVE)  
2. Proper pressure regulation.  
GROMMET  
3. Pressure drop in lines between regulators, and between  
second stage regulator and the appliance. Pipe size  
required will depend on length of pipe run and total load of  
all appliances.  
Proper Piping Practice  
NOTE: The unit gas supply entrance is factory sealed with  
plugs. Keep plugs in place until gas supply is ready to be  
installed. Once ready, replace the plugs with the supplied  
grommets and install gas supply line.  
TANKS AND PIPING  
Complete information regarding tank sizing for vaporization,  
recommended regulator settings and pipe sizing is available  
from most regulator manufacturers and propane gas  
suppliers.  
GAS PIPING CHECKS  
Since propane gas will quickly dissolve white lead or most  
standard commercial compounds, special pipe dope must  
be used. Shellac base compounds resistant to the actions of  
liquefied petroleum gases such as Gasolac®, Stalactic®,  
Clyde’s® or John Crane® are satisfactory.  
See below for typical propane gas piping.  
5 to 15 PSIG  
First Stage  
(20 PSIG Max.)  
Regulator  
Continuous  
11" W.C.  
200 PSIG  
Maximum  
Second Stage  
Regulator  
TypicalPropaneGasPiping  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Sizing Between First and Second Stage Regulator  
Maximum Propane Capacities listed are based on 1 PSIG Pressure Drop at 10  
PSIG Setting. Capacities in 1,000 BTU/HR  
cooling. Units which will have economizers may use thermostats  
with two or three stages of cooling.All units can use single stage  
or multi-stage thermostats. Refer to figures later in this section  
for wiring.  
PIPE OR  
NOMINAL PIPE SIZE,  
SCHEDULE 40  
TUBING  
LENGTH,  
FEET  
TUBING SIZE, O.D., TYPE L  
3/8"  
1/2"  
5/8"  
3/4"  
7/8"  
1/2"  
3/4"  
30  
40  
309  
700  
1,303  
2,205  
3,394  
1,843  
3,854  
265  
235  
213  
196  
182  
171  
161  
130  
111  
90  
599  
531  
481  
446  
412  
386  
365  
293  
251  
222  
201  
185  
172  
1,115  
988  
896  
824  
767  
719  
679  
546  
467  
414  
378  
345  
321  
1,887  
1,672  
1,515  
1,394  
1,297  
1,217  
1,149  
923  
2,904  
2,574  
2,332  
2,146  
1,996  
1,873  
1,769  
1,421  
1,216  
1,078  
976  
1,577  
1,398  
1,267  
1,165  
1,084  
1,017  
961  
3,298  
2,923  
2,649  
2,437  
2,267  
2,127  
2,009  
1,613  
1,381  
1,224  
1,109  
1,020  
949  
50  
60  
70  
The units are designed for operation on 60 hertz current and at  
voltages as shown on the rating plate. All internal wiring in the  
unit is complete. It is necessary to bring in the power supply to  
the contactor as shown on the unit wiring diagram which is  
supplied with each unit. The low voltage wiring must be connected  
between the unit control panel and the room thermostat.  
80  
90  
100  
150  
200  
250  
300  
350  
400  
772  
790  
660  
700  
585  
89  
634  
530  
82  
584  
898  
488  
76  
543  
836  
454  
To convert to Capacities at 15 PSIG Settings -- Multiply by 1.130  
To convert to Capacities at 5 PSIG Settings -- Multiply by 0.879  
(
Thermostat  
Two-Stage Heating  
with  
Sizing Between Single or Second Stage Regulator and Appliance*  
Maximum Propane Capacities Listed are Based on 1/2" W.C. Pressure Drop at  
11" W.C. Setting. Capacities in 1,000 BTU/HR  
Y2  
Y1  
R
C
(
Two-Stage Cooling  
PIPE OR  
NOMINAL PIPE SIZE,  
SCHEDULE 40  
TUBING SIZE, O.D., TYPE L  
TUBING  
LENGTH,  
FEET  
W1  
G
W2  
3/8"  
1/2"  
5/8"  
3/4"  
7/8"  
1/2"  
3/4"  
1"  
1-1/4"  
1-1/2"  
10  
20  
49  
110  
206  
348  
539  
291  
608  
1,146  
2,353  
3,525  
34  
27  
23  
20  
19  
16  
14  
12  
11  
10  
9
76  
61  
52  
46  
42  
36  
32  
28  
26  
22  
19  
18  
16  
15  
141  
114  
97  
86  
78  
67  
59  
52  
48  
41  
36  
33  
30  
28  
239  
192  
164  
146  
132  
113  
100  
89  
368  
296  
253  
224  
203  
174  
154  
137  
124  
106  
94  
200  
161  
137  
122  
110  
94  
418  
336  
284  
255  
231  
198  
175  
155  
141  
120  
107  
97  
788  
632  
541  
480  
436  
372  
330  
292  
265  
227  
201  
182  
167  
156  
1,617  
1,299  
1,111  
985  
2,423  
1,946  
1,665  
1,476  
1,337  
1,144  
1,014  
899  
30  
40  
Furnace Integrated  
Control Module  
50  
60  
892  
G Y1 Y2  
C W1W2  
R
80  
764  
100  
125  
150  
200  
250  
300  
350  
400  
84  
677  
Two-Stage Heating with Two-Stage Cooling  
ThermostatDiagram  
74  
600  
80  
67  
544  
815  
69  
58  
465  
697  
SINGLE STAGE THERMOSTAT  
61  
51  
412  
618  
To use a single stage thermostat, move jumper located to the  
left of the terminal strip labeled “Stage Delay” from NONE to  
“5” or “10” minutes. This selection will cause the control to  
run on low stage for the selected time (5 or 10 minutes) then  
shift to HIGH STAGE. This option controls both cooling and  
heating modes. If the jumper is not moved, only low-stage  
cool and low-stage heat will operate.  
8
55  
85  
46  
374  
560  
7
51  
78  
43  
89  
344  
515  
7
47  
73  
40  
83  
320  
479  
*DATA IN ACCORDANCE WITH NFPA PAMPHLET NO. 54  
Propane Gas Pipe Sizing  
5 MINUTE DELAY  
PERIOD WITH  
JUMPER IN THIS  
POSITION  
10 MINUTE DELAY  
PERIOD WITH  
JUMPER IN THIS  
POSITION  
ELECTRICAL WIRING  
THERMOSTAT LOCATION  
Mount the thermostat approximately five feet above the floor,  
in an area that has an inside, vibration-free wall and has  
good air circulation.  
Movement of air must not be obstructed by furniture, door,  
draperies, etc. The thermostat must not be mounted where it  
will be affected by drafts, hot or cold water pipes or air ducts in  
walls, radiant heat from fireplace, lamps, the sun, television,  
etc. Consult the Instruction Sheet packaged with thermostat  
for mounting instructions.  
Two-Stage Heating (timed) and Two-Stage Cooling (timed)  
with Single Stage Thermostat Diagram  
Refer to the unit wiring diagram for electrical connections.  
When installed, the unit must be electrically grounded in  
accordance with local codes or in the absence of local codes,  
with the National Electrical Code, ANSI/NFPA No. 70, and/or  
the CSA C22.1 Electrical Code. Ensure low voltage  
connections are waterproof.  
NOTE: *PG1524, *PG1530, *PG1537, and *PG1549 units have  
one stage of mechanical cooling and two stages of heat.All other  
units have two stages of heating and two stages of mechanical  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
UNIT VOLTAGE  
The unit transformer is factory connected for 230V operation.  
If the unit is to operate on 208V, reconnect the transformer  
primary lead as shown on the unit wiring diagram. The induced  
draft blower on some models is equipped with a low speed  
230V lead (blue) and a low speed 208V lead (black). If  
equipped, connect the induced draft blower low speed 208V  
lead (black) in place of the low speed 230V lead (blue). Place  
the unused 230V lead on the “PARK” terminal located on  
ignition control.  
HEAT ANTICIPATOR SETTING  
The heat anticipator is to be set by measuring the load  
(amperage) at the “R” circuit. Follow the instructions provided  
with the thermostat for more details.  
For unit protection, use a fuse or HACR circuit breaker that is in  
excess of the circuit ampacity, but less than or equal to the  
maximum overcurrent protection device. DO NOT EXCEED  
THE MAXIMUM OVERCURRENT DEVICE SIZE SHOWN ON  
UNIT DATAPLATE.  
All line voltage connections must be made through  
weatherproof fittings. All exterior power supply and ground  
wiring must be in approved weatherproof conduit. Low voltage  
wiring from the unit control panel to the thermostat requires  
coded cable. See below for ground level and rooftop wiring.  
CIRCULATING AIR AND FILTERS  
AIRFLOW CONVERSION  
Units can easily be converted from horizontal to down-  
discharge airflow delivery. In down-discharge or high static  
installations, the installer should measure the total external  
static and review the blower performance charts before  
performing the installation. In some installations it will be  
necessary to change the blower speed to provide proper air  
flow.  
HorizontalAirFlow  
Note:Junction box location  
shown is optional and is  
for illustration purposes only.  
Single phase models are shipped without horizontal duct  
covers. If needed, these kits may be ordered through  
Goodman’s Service Parts department.  
JUNCTION BOX  
Electrical Power Directly To Junction Box  
DuctCoverInstallation  
DownDischargeApplications  
Cut insulation around bottom openings and remove panels  
from the bottom of the unit, saving the screws holding the  
panels in place.  
NOTE: Single phase models require installation of horizontal  
duct kit #20464501PDGK (medium chassis) and  
#20464502PDGK (large chassis).  
DUCTWORK  
Duct systems and register sizes must be properly designed  
for the C.F.M. and external static pressure rating of the unit.  
Ductwork should be designed in accordance with the  
recommended methods of Air Conditioning Contractors of  
America Manual D (Residential) or Manual Q (Commercial).  
Electrical Power Routed Through Bottom of Unit  
Typical Electrical Wiring Unit Voltage  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
All ductwork exposed to the outdoors must include a weatherproof  
barrier and adequate insulation.  
Aduct system should be installed in accordance with Standards  
of the National Board of Fire Underwriters for the Installation of  
Air Conditioning, Warm Air Heating and Ventilating Systems.  
Pamphlets No. 90A and 90B.  
HOOD  
The supply duct from the unit through a wall may be installed  
without clearance. However, minimum unit clearances as  
shown in the appendix must be maintained. The supply duct  
should be provided with an access panel large enough to  
inspect the air chamber downstream of the heat exchanger. A  
cover should be tightly attached to prevent air leaks.  
LOWER  
FLUE  
HOOD  
SCREEN  
LIP  
For duct flange dimensions on the unit refer to the Unit  
Dimension illustration in the appendix.  
For down-discharge applications, the ductwork should be  
attached to the roof curb prior to installing the unit. Ductwork  
dimensions are shown in the roof curb installation manual.  
If desired, supply and return duct connections to the unit may  
be made with flexible connections to reduce possible unit  
operating sound transmission.  
INSTALLATION - COMBUSTION AIR INTAKE HOOD  
1. Locate the second hood.  
2. Using the three screws provided, attach the hood (with  
the opening facing down) to the heat exchanger access  
door.  
FILTERS  
Even though a return air filter is not supplied with this unit,  
there must be a means of filtering all return air. All units may  
be externally filtered.  
Refer to the unit filter size chart in the appendix for filter size  
information.  
Filters installed external to the unit should be sized in  
accordance with their manufacturer recommendations. A  
throwaway filter must be sized for a maximum face velocity of  
300 feet per minute.  
FilterInstallation  
IMPORTANT NOTE: When installing a filter, the air flow arrows  
on the filter must point toward the circulator blower.  
CONDENSATE DRAIN  
CONDENSATE DRAIN CONNECTION  
VENTING  
A 3/4” NPT drain connection is supplied for condensate piping.  
An external trap must be installed for proper condensate  
drainage.  
NOTE: Venting is self-contained. Do not modify or block.  
DRAIN  
CONNECTION  
INSTALLATION -FLUE HOOD EXHAUST  
1. Locate the flue hood assembly box from the blower  
compartment.  
2. Slide screen over flanges on the lower flue hood.  
3. Slide screen into hood.  
UNIT  
2" MINIMUM  
4. Using the three screws provided, attach the hood (with the  
opening facing down) over the flue exhaust opening in the  
utility panel.  
FLEXIBLE  
TUBING-HOSE  
OR PIPE  
3" MINIMUM  
A POSITIVE LIQUID  
SEAL IS REQUIRED  
DrainConnection  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NORMAL SEQUENCES OF OPERATION  
FAN ONLY  
1. Thermostat calls for FAN ONLY by energizing “G”.  
2. The indoor blower is immediately energized at the low  
heat speed.  
3. The indoor blower is immediately de-energized once  
thermostat call for FAN is removed.  
HEATING  
This unit is equipped with an ignition control that automatically  
lights the main burner. DO NOT attempt to light the main  
burners by any other method.  
1. Thermostat calls for low or high stage heating.  
2. Induced draft blower energizes for 15-second pre-purge.  
3. The spark igniter and low and high stage gas valve are  
energized for 7 seconds. NOTE: The igniter produces a  
very intense electrical spark that ignites the gas.  
4. Main burners light and control detects presence of flame.  
5. If the call is for low stage heat, the induced draft blower  
switches to low speed and the high stage gas valve closes  
5 seconds after the main burners light. If call is for high  
stage heat, induced draft blower remains at high speed  
and high stage gas valve remains open.  
STARTUP, ADJUSTMENTS, AND CHECKS  
HEATING STARTUP  
This unit is equipped with an electronic ignition device to  
automatically light the main burners. It also has a power vent  
blower to exhaust combustion products.  
On new installations, or if a major component has been  
replaced, the operation of the unit must be checked.  
Check unit operation as outlined in the following instructions.  
If any sparking, odors, or unusual sounds are encountered,  
shut off electrical power and check for wiring errors, or  
obstructions in or near the blower motors. Duct covers must  
be removed before operating unit.  
NOTE: If a single stage thermostat is used, the control will  
step to low stage after the main burners light and remain  
at low stage for 5 or 10 minutes, depending on jumper  
position. If the call for HEAT remains after the transition  
delay time expires, the control will transition from low stage  
to high stage.  
HeatAnticipatorSetting  
Set the heat anticipator on the room thermostat to 0.4 amps  
to obtain the proper number of heating cycles per hour and to  
prevent the room temperature from overshooting the room  
thermostat setting.  
6. The 30-second HEAT FAN ON delay time begins after the  
main burners light.  
7. The unit delivers heat to the conditioned space until the  
thermostat is satisfied.  
RolloutProtectionControl  
8. Gas valve(s) de-energizes. The induced draft blower  
continues operation for a 30-second post-purge.  
9. Induced draft blower remains at low speed (or switches  
from high to low if operating at high stage heat) for the 30-  
second post purge.  
10.Ignition control begins timing the HEAT FAN OFF delay.  
There is an adjustable HEAT FAN OFF delay of  
approximately 90/120/150/180 seconds (factory set at  
150). If the unit is operating at high stage when the call for  
heat is removed, the blower will operate for 30 seconds at  
high heat speed then switch to low heat speed for the  
remainder of the selected HEAT FAN OFF delay.  
NOTE: After the HEAT FAN OFF delay time has elapsed,  
the blower will de-energize. This allows any additional  
heat in the heat exchanger to be transferred to the  
conditioned space.  
The rollout protection device opens, cutting power to the gas  
valve, if the flames from the burners are not properly drawn  
into the heat exchanger. The rollout protection device is located  
on the burner bracket. The reason for elevated temperatures  
at the control must be determined and repaired prior to  
resetting this manual reset control.  
Rollout Protection  
COOLING  
1. Thermostat calls for low or high stage cooling.  
2. If the thermostat call is for low stage cooling, the  
compressor and outdoor fan are energized at low stage. If  
the thermostat call is for high stage cooling, the  
compressor and outdoor fan are energized at high stage.  
3. The indoor blower will energize approximately 6 seconds  
later.  
4. The unit delivers cooling to the conditioned space until the  
thermostat is satisfied.  
5. The compressor and outdoor fan will be de-energized  
when the thermostat opens.  
Rollout Protection on Burner Bracket  
SecondaryLimitControl  
6. The indoor blower continues to run at low cool speed for  
approximately 60 seconds after the thermostat is satisfied.  
This allows additional cooling from the indoor coil to be  
transferred to the conditioned space. Then, the indoor  
blower is de-energized.  
The secondary limit control is located on the top of the blower  
scroll assembly. This control opens when elevated  
temperatures are sensed. Elevated temperatures at the  
control are normally caused by blower failure. The reason for  
the opening should be determined and repaired prior to  
resetting.  
NOTE: A 180-second anti-short cycle is integral to the control  
and prevents recycling of the compressor.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
If the power to the unit is interrupted during the heating cycle, it  
may cause the secondary limit to trip. Once the blower  
compartment temperature drops below the limit reset  
temperature, the limit will automatically reset.  
Gas Supply And Manifold Check  
Gas supply pressure and manifold pressure with the burners  
operating must be as specified on the rating plate.  
Gas Inlet Pressure Check  
Gas inlet pressure must be checked and adjusted in  
accordance to the type of fuel being consumed.  
Secondary  
Control Limit  
With Power And Gas Off:  
1. Connect a water manometer or adequate gauge to the  
inlet pressure tap of the gas valve.  
Inlet gas pressure can also be measured by removing the  
cap from the dripleg and installing a predrilled cap with a  
hose fitting.  
With Power And Gas On:  
2. Put unit into heating cycle and turn on all other gas  
consuming appliances.  
Back of Unit  
INLET GAS PRESSURE  
Natural  
Min. 5.0" W.C., Max. 10.0" W.C.  
Min. 11.0" W.C., Max. 13.0" W.C.  
SecondaryLimitControl  
Pre-Operation Checks  
Propane  
NOTE: Inlet Gas Pressure Must Not Exceed the Maximum  
1. Close the manual gas valve external to the unit.  
2. Turn off the electrical power supply to the unit.  
3. Set the room thermostat to its lowest possible setting.  
4. Remove the heat exchanger door on the side of the unit by  
removing screws.  
Value Shown.  
If operating pressures differ from above, make necessary  
pressure regulator adjustments, check piping size, etc., and/  
or consult with local utility.  
5. This unit is equipped with an ignition device which  
automatically lights the main burner. DO NOT try to light  
burner by any other method.  
Gas Line  
Gas  
Shutoff  
Valve  
6. Move the gas control valve switch to the OFF position. Do  
not force.  
Gas Line  
To Furnace  
7. Wait five minutes to clear out any gas.  
8. Smell for gas, including near the ground. This is important  
because some types of gas are heavier than air. If you  
have waited five minutes and you do smell gas,  
immediately follow the warnings on page 4 of this manual.  
If having waited for five minutes and no gas smell is noted,  
move the gas control valve switch to the ON position.  
9. Replace the heat exchanger door on the side of the unit.  
10. Open the manual gas valve external to the unit.  
11. Turn on the electrical power supply to the unit.  
12. Set the thermostat to desired setting.  
Open To  
Atmosphere  
Drip Leg Cap  
With Fitting  
Manometer Hose  
Manometer  
Measuring Inlet Gas Pressure  
Alternate Method  
Open to  
Atmosphere  
eter  
Manom  
Hose  
High Fire Regulator  
Adjust  
Manifold Pressure Check  
Outlet  
Pressure Boss  
Regulator  
Vent  
1
Turn OFF gas to furnace at the manual gas shutoff valve  
external to the furnace.  
2. Turn off all electrical power to the system.  
3. Back outlet pressure test screw (inlet/outlet pressure boss)  
out one turn (counterclockwise, not more than one turn).  
A
4. Attach a hose and manometer to the outlet pressure boss  
of the valve.  
5. Turn ON the gas supply.  
Low Fire  
Regulator Adjust  
6. Turn on power and energize main (M) solenoid. Do not  
energize the HI solenoid.  
7. Measure gas manifold pressure with burners firing. Adjust  
manifold pressure using the Manifold Gas Pressure table  
shown below.  
Inlet  
Pressure Boss  
High Fire  
Coil Terminal (HI)  
Coaxial Coil  
Terminal (M)  
Common  
Terminal (C)  
Manometer  
On/Off Switch  
White-Rodgers Model 36G54 connected to Manometer  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
With a properly designed system, the proper amount of  
temperature rise will normally be obtained when the unit is  
operated at rated input with the recommended blower speed.  
If the correct amount of temperature rise is not obtained, it may  
be necessary to change the blower speed.Ahigher blower speed  
will lower the temperature rise.Aslower blower speed will increase  
the temperature rise.  
Manifold Gas Pressure  
Range  
Gas  
Nominal  
Natural Low Stage  
High Stage  
Propane Low Stage  
High Stage  
1.6 - 2.2" w.c.  
3.2 - 3.8" w.c.  
5.7 - 6.3" w.c.  
2.0" w.c.  
3.5" w.c.  
6.0" w.c.  
9.7 - 10.3" w.c. 10.0" w.c.  
8. Remove regulator cover screw from the low (LO) outlet  
pressure regulator adjust tower and turn screw clockwise  
to increase pressure, or counterclockwise to decrease  
pressure.  
NOTE: Blower speed MUST be set to give the correct air  
temperature rise through the unit as marked on the rating  
plate.  
External Static Pressure Check  
9. Energize main (M) solenoid as well as the HI terminal.  
The total external static pressure must be checked on this  
unit to determine if the airflow is proper.  
10. Remove regulator cover screw from the HI outlet pressure  
regulator adjust tower and turn screw clockwise to increase  
pressure, or counterclockwise to decrease pressure.  
Blower Speed Adjustments  
11. Turn off all electrical power and gas supply to the system.  
12. Remove manometer hose from outlet pressure boss.  
13. Turn outlet pressure test screw in to seal pressure port  
(clockwise, 7 in-lb minimum).  
WARNING  
TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRIC SHOCK, REMOVE  
ELECTRICAL POWER FROM THE UNIT BEFORE CHANGING SPEED TAPS ON THE  
BLOWER MOTOR.  
14. Turn on electrical power and gas supply to the system.  
15. Turn on system power and energize valve.  
16. Using a leak detection solution or soap suds, check for  
leaks at pressure boss screw. Bubbles forming indicate  
a leak. SHUT OFF GASAND FIXALLLEAKS IMMEDIATELY.  
Refer to the wiring diagram in the appendix to verify speed tap  
settings.  
Depending upon the model, blower speeds are changed at  
the indoor blower. The ignition control board has four blower  
speeds: LOW HEAT, HI HEAT, LOW COOL and HIGH COOL.  
NOTE:  
For gas to gas conversion, consult your  
dealer for appropriate conversion.  
NOTE: FAN ONLY energizes at LOW HEAT speed.  
Gas Input (Natural Gas Only) Check  
The *PG15 models are equipped with EEM motors. EEM motors  
are constant torque motors with very low power consumption.  
This motor is energized by 24VAC. Adjust the CFM for the unit  
by changing the 24VAC leads to the speed terminal block on the  
motor.  
To measure the gas input use a gas meter and proceed as  
follows:  
1. Turn off gas supply to all other appliances except the unit.  
2. With the unit operating, time the smallest dial on the meter  
for one complete revolution. If this is a 2 cubic foot dial,  
divide the seconds by 2; if it is a 1 cubic foot dial, use the  
seconds as is. This gives the seconds per cubic foot of  
gas being delivered to the unit.  
3. INPUT=GAS HTG VALUE x 3600 / SEC. PER CUBIC FOOT  
Example: Natural gas with a heating value of 1000 BTU per cubic  
foot and 34 seconds per cubic foot as determined by Step 2, then:  
Input = 1000 x 3600 / 34 = 106,000 BTU per Hour. NOTE:  
BTU content of the gas should be obtained from the gas  
supplier. This measured input must not be greater than  
shown on the unit rating plate.  
HEATING  
COOLING  
Speed  
Tap  
Lead Speed  
Lead  
Color  
Definition  
Definition  
Color  
White  
Brown  
Tap  
Low  
Speed Heat  
Low Speed  
Cool  
T1  
T2  
T3  
Purple  
Yellow  
High  
Speed Heat  
High Speed  
Cool  
T4  
High Speed  
Cool Hi-Static  
T5  
4. Relight all other appliances turned off in step 1. Be sure  
all pilot burners are operating.  
NOTE: Heating airflow must be adjusted to provide the  
temperature rise shown on rating plate. A higher speed tap  
may not provide more airflow. Blower speeds are  
programmed to deliver adequate airflow at rated external static  
pressure (ESP). Refer to airflow table provided in the Appendix  
for details.  
Main Burner Flame Check  
Flames should be stable, soft and blue (dust may cause  
orange tips but they must not be yellow) and extending directly  
outward from the burner without curling, floating or lifting off.  
Temperature Rise Check  
Limit Check  
Check the temperature rise through the unit by placing  
thermometers in supply and return air registers as close to  
the unit as possible. Thermometers must not be able to  
sample temperature directly from the unit heat exchangers,  
or false readings could be obtained.  
Check limit control operation after 15 minutes of operation  
by blocking the return air grille(s).  
1. After several minutes the main burners must go OFF.  
Blower will continue to run.  
2. Remove air restrictions and main burners will relight  
after a cool down period of a few minutes.  
Adjust the thermostat setting below room temperature.  
1. All registers must be open; all duct dampers must be in  
their final (fully or partially open) position and the unit  
operated for 15 minutes before taking readings.  
2. The temperature rise must be within the range specified  
on the rating plate.  
1. Main burners must go OFF.  
2. Circulating Air Blower will continue to run for 90, 120,  
150 or 180 seconds, depending on the setting.  
NOTE: Air temperature rise is the temperature difference  
between supply and return air.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
space. It is the installing contractors responsibility to ensure  
the proper refrigerant sub-cooling at the condenser is adjusted  
for each application. As the outdoor ambient temperature  
rises the sub-cooling decreases and as the outdoor ambient  
temperature lowers, the sub-cooling increases. NOTE: Proper  
sub-cooling adjustment optimizes cooling performance.  
Models equipped with thermostatic expansion valve, charge  
the system to sub-cooling, range shown on chart, when  
necessary, adjust expansion valve stem for superheat setting.  
LOCOOL  
HICOOL  
U6  
U7  
U4  
LOHEAT  
HIHEAT  
U3  
K2  
K1  
U5  
P1  
NOTE: The expansion valve will not need adjustment for most  
applications. Ensure system superheat is set within range listed  
on chart.  
SPEEDUP  
F1  
SW1  
FAULT  
BLOWER STAGE  
ECON  
G
Y1 Y2  
R
C
W1 W2  
RECALL OFFDELAY DELAY  
Control Board (Top)  
Design superheat & subcooling @ 95 °F outdoor ambient temperature  
NOTE: If necessary, adjust fan OFF delay settings to obtain satis-  
factory comfort level.  
Models #  
GPG152407041  
GPG153009041  
GPG153709041  
GPG154211541  
GPG154911541  
GPG156014041  
Superheat °F  
Subcooling °F  
8 12  
8 12  
5 9  
‐‐‐  
‐‐‐  
‐‐‐  
‐‐‐  
‐‐‐  
5 9  
5 9  
5 9  
12 18  
UnitShutdown  
Superheat Adjustment  
1. Set the thermostat to lowest setting.  
2. Turn off the electrical power supply to the unit.  
3. Remove the heat exchanger door on the side of the unit by  
removing screws.  
4. Move the gas control valve switch to the OFF position. Do  
not force.  
5. Close manual gas shutoff valve external to the unit.  
6. Replace the heat exchanger door on the unit.  
7. If cooling and/or air circulation will be desired, turn ON the  
electrical power.  
To adjust superheat, remove the control box cover and locate  
the expansion valve on the liquid line of the evaporator.  
Unscrew the cover from the expansion valve, locate the  
adjustment screw, and turn it clockwise (in) to increase  
superheat or counterclockwise (out) to decrease superheat.  
Replace adjustment cap. Wait a minimum of 10 minutes  
between adjustments to allow time for the TXV and pressures  
to stabilize.  
CoolingOperation  
COOLING STARTUP  
NOTE: Check all manual reset limit controls in heating circuit if  
cooling mode does not operate.  
NOTE: Mechanical cooling cannot be reliably provided at  
ambient temperatures below 50° F.  
1. Turn on the electrical power supply to the unit.  
2. Place the room thermostat selector switch in the COOL  
position (orAUTO if available, and if automatic changeover  
from cooling to heating is desired).  
Compressor Protection Devices  
The compressor includes components which are designed  
to protect the compressor against abnormal operating  
conditions.  
3. Set the room thermostat to the desired temperature.  
TROUBLESHOOTING  
IGNITION CONTROL ERROR CODES  
The following presents probable causes of questionable unit  
operation. Refer to Diagnostic Indicator Chart for an  
interpretation of the signal and to this section for an explanation.  
Refrigerant Charge Check (Units with Fixed Orifice Devices)  
Remove the control box access panel and note the number of  
diagnostic LED flashes. Refer to Diagnostic Indicator Chart  
for an interpretation of the signal and to this section for an  
explanation.  
After completing airflow measurements and adjustments the  
unit’s refrigerant charge must be checked. All package units with  
fixed orifice devices are charged using the super heat method at  
the compressor suction line.  
For charge adjustments, see superheat and charts shown for  
each model.  
FAULT RECALL  
The ignition control is equipped with a momentary push-button  
switch that can be used to display on the diagnostic LED the last  
five faults detected by the control. The control must be in Standby  
Mode (no thermostat inputs) to use the feature. Depress the push-  
button switch for approximately 2 seconds. NOTE: Do not hold  
for longer than 4 seconds. Holding the button for 4 seconds  
or higher will erase the memory! Release the switch when the  
LED is turned off. The diagnostic LED will then display the  
flash codes associated with the last five detected faults. The  
order of display is the most recent fault to the least recent  
Cooling Refrigerant Charging (Models with TXV)  
Check unit charge before putting the cooling section into full  
operation. The unit has a thermostatic expansion valve metering  
device. To ensure the unit is properly charged for the intended  
application, check the unit refrigerant sub-cooling at the  
condenser. The refrigerant sub-cooling is a function of outdoor  
ambient temperature and return air temperature of the conditioned  
15 fault.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ABNORMAL OPERATION -HEATING  
OPEN THERMAL PROTECTION DEVICE  
If a limit switch opens, the gas valve is immediately de-  
energized, the induced draft and air circulating blowers are  
energized. The induced draft and air circulator blowers remain  
energized until the limit switch re-closes. The diagnostic LED  
(red) code for an open limit is four (4) flashes.  
INTERNAL CONTROL FAILURE  
If the integrated ignition control in this unit encounters an  
internal fault, it will go into a “hard” lockout and turn off the  
diagnostic LED. If diagnostic LED indicates an internal fault,  
check power supply to unit for proper voltage, check all fuses,  
circuit breakers and wiring. Disconnect electric power for five  
seconds. If LED remains off after restoring power, replace  
control.  
PRIMARY LIMIT  
A primary limit will open due to excessive supply air  
temperatures. This can be caused by a dirty filter, excessive  
duct static, insufficient air flow, or a faulty limit. Check filters,  
total external duct static, blower motor, blower motor speed  
tap (see wiring diagram), and limit. This limit will automatically  
reset once the temperature falls below a preset level.  
EXTERNAL LOCKOUT  
An external lockout occurs if the integrated ignition control  
determines that a measurable combustion cannot be  
established within three (3) consecutive ignition attempts. If  
flame is not established within the seven (7) second trial for  
ignition, the gas valve is de-energized, 30 second inter-purge  
cycle is completed, and ignition is re-attempted. The control  
will repeat this routine three times if a measurable combustion  
is not established. The control will then shut off the induced  
draft blower and go into a lockout state.  
If flame is established but lost, the control will energize the  
circulator blower at the heat speed and then begin a new  
ignition sequence. If flame is established then lost on  
subsequent attempts, the control will recycle the ignition  
sequence.  
AUXILIARY/SECONDARY LIMIT  
A dirty filter, excessive duct static, insufficient air flow, a faulty  
limit, or a failed circulator blower can cause this limit to open.  
Check filters, total external duct static, circulator blower motor,  
blower motor speed tap (see wiring diagram), and limit. An  
interruption in electrical power during a heating cycle may  
also cause the auxiliary limit to open. The automatic reset  
secondary limit is located on top of the circulator blower  
assembly.  
ROLLOUT LIMIT  
The diagnostic fault code is 1 flash for a lockout due to failed  
ignition attempts. The integrated control will automatically  
reset after one hour, or it can be reset by removing the  
thermostat signal or disconnecting the electrical power supply  
for over five seconds. If the diagnostic red LED indicates an  
external lockout, perform the following checks:  
If the burner flames are not properly drawn into the heat  
exchanger, the flame rollout protection device will open.  
Possible causes are restricted or blocked flue passages,  
blocked or cracked heat exchanger, a failed induced draft  
blower, or insufficient combustion air. The rollout protection  
device is a manual reset limit located on the burner bracket.  
The cause of the flame rollout must be determined and  
corrected before resetting the limit.  
Check the supply and manifold pressures  
Check the gas orifices for debris  
Check gas valve for proper operation  
Check flame sensor  
FLAME DETECTED WITH GAS VALVE CLOSED  
A drop in flame signal can be caused by nearly invisible  
coating on the sensor. Remove the sensor and carefully  
clean with steel wool.  
If flame is detected with the gas valve de-energized, the  
combustion and air circulator blowers are energized. The  
diagnostic fault code is five (5) flashes (red LED) for this  
condition. The flame diagnostic LED (amber) will flash (2)  
times to indicate this condition. The control can be reset by  
removing the power supply to the unit or it will automatically  
reset after one hour. Miswiring is the probable cause for this  
fault.  
Check wiring  
Check wiring for opens/shorts and miswiring.  
IMPORTANT NOTE: If you have to frequently reset your gas/  
electric package unit, it means that a problem exists that  
should be corrected. Contact a qualified servicer for further  
information.  
LOW FLAME SIGNAL  
PRESSURE SWITCH STUCK OPEN  
Under some conditions, the fuel or air supply can create a nearly  
invisible coating on the flame sensor. This coating acts as an  
insulator causing a drop in the flame signal. If the flame signal  
drops below a predetermined value, the ignition control will display  
an error code of (1) flash on the amber diagnostic LED. The unit  
will continue to operate until the control can no longer detect flame.  
A pressure switch stuck open can be caused by a faulty pressure  
switch, faulty wiring, a disconnected or damaged hose, a blocked  
or restricted flue, or a faulty induced draft blower.  
If the control senses an open pressure switch during the pre-  
purge cycle, the induced draft blower only will be energized. If  
the pressure switch opens after ignition has begun the gas  
valve is de-energized, the circulator blower heat off cycle  
begins, and the induced draft blower remains on. The  
diagnostic LED (red) code is two (2) flashes.  
ABNORMAL OPERATION - COOLING  
SHORT CYCLE COMPRESSOR DELAY  
The automatic ignition control has a built-in feature that  
prevents damage to the compressor in short cycling  
situations. In the event of intermittent power losses or  
intermittent thermostat operation, the ignition control will delay  
output to the compressor contactor for three minutes from the  
time power is restored or thermostat call for cooling is  
restored. (Compressor is off a total of three minutes). The  
diagnostic red LED will flash six (6) times to indicate the  
compressor contactor output is being delayed.  
PRESSURE SWITCH STUCK CLOSED  
A stuck closed pressure switch can be caused by a faulty  
pressure switch or faulty wiring. If the control encounters a  
pressure switch stuck closed, the induced draft blower  
remains off. The diagnostic red LED code for this fault is  
three (3) flashes.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CONDENSER, EVAPORATOR, AND INDUCED DRAFT MOTORS  
Bearings on the air circulating blower motor, condenser motor  
and the combustion fan motor are permanently lubricated.  
No additional oiling is required.  
NOTE: Some electronic thermostats also have a built-in  
compressor short cycle timer that may be longer than the  
three minute delay given above. If you are using an electronic  
thermostat and the compressor has not started after three  
minutes, wait an additional five minutes to allow the  
thermostat to complete its short cycle delay time.  
FLAME SENSOR (QUALIFIED SERVICER ONLY)  
A drop in the flame current can be caused by a nearly invisible  
coating on the flame sensor. This coating, created by the fuel  
or combustion air supply, can be removed by carefully cleaning  
the flame sensor with steel wool.  
HIGH PRESSURE SWITCH/LOSS OF CHARGE SWITCH  
Some models include a high pressure cutout switch and/or a  
loss of charge cutout switch. The high pressure cutout switch  
protects the refrigeration system from excessive operating  
pressures. The loss of charge cutout switch protects the  
refrigeration system from very low operating pressures due  
to a loss of refrigerant. Compressor operation will be disabled  
if either of these devices opens. If either devices opens, the  
diagnostic red LED will flash (9) times to indicate that a  
refrigeration system pressure switch is open.  
NOTE: After cleaning, the microamp signal should be stable  
and in the range of 4 - 6 microamps DC.  
Flame  
Sensor  
MAINTENANCE  
Have the gas heating section of the unit checked at least  
once a year before the heating season begins, to be sure that  
the combustion air inlet and flue outlet hoods are not blocked  
by debris, which would prevent adequate combustion air and  
a properly operating vent system.  
Flame Sensor  
FLUE PASSAGES (QUALIFIED SERVICER ONLY)  
At the start of each heating season, inspect and, if necessary,  
clean the unit flue passage.  
FILTER REPLACEMENT OR CLEANING  
A return air filter is not supplied with this unit; however, there  
must be a means of filtering all of the return air. The filter(s)  
may be located in the return air duct(s), or return air filter  
grille(s). Consult with your installing dealer for the actual  
location of the return air filter(s) for your unit.  
CLEANING FLUE PASSAGES (QUALIFIED SERVICER ONLY)  
1. Shut off electric power and gas supply to the unit.  
2. Remove burner assembly by disconnecting the gas line  
and removing the manifold bracket from the partition panel.  
3. Remove the flue from the induced draft blower and the  
collector box cover from the partition panel.  
4. The primary heat exchanger tubes can be cleaned using a  
round wire brush attached to a length of high grade stainless  
steel cable, such as drain cleanout cable. Attach a variable  
speed reversible drill to the other end of the spring cable.  
Slowly rotate the cable with the drill and insert it into one of  
the primary heat exchanger tubes. While reversing the drill,  
work the cable in and out several times to obtain sufficient  
cleaning. Use a large cable for the large tube, and then repeat  
the operation with a small cable for the smaller tube. Repeat  
for each tube.  
Dirty filters are the most common cause of inadequate heating  
or cooling performance. Filter inspection should be made at  
least every two months; more often if necessary because of local  
conditions and usage.  
Dirty throwaway filters should be discarded and replaced with a  
new, clean filter. Dirty permanent filters should be washed with  
water, thoroughly dried and sprayed with a filter adhesive before  
being reinstalled. (Filter adhesives may be found at many  
hardware stores.) Permanent filters should last several years.  
However, should one become torn or uncleanable, it should be  
replaced.  
5. When all heat exchanger tubes have been cleaned,  
replace the parts in the reverse order in which they were  
removed.  
6. To reduce the chances of repeated fouling of the heat  
exchanger, perform the steps listed in “Startup,  
Adjustments, and Checks”.  
CABINET FINISH MAINTENANCE  
Use a fine grade automotive wax on the cabinet finish to  
maintain the finish’s original high luster. This is especially  
important in installations with extended periods of direct  
sunlight.  
CLEAN OUTSIDE COIL (QUALIFIED SERVICER ONLY)  
The coil with the outside air flowing over it should be inspected  
annually and cleaned as frequently as necessary to keep the  
finned areas free of lint, hair and debris.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MAIN BURNER FLAME (QUALIFIED SERVICER ONLY)  
Flames should be stable, soft and blue (dust may cause  
orange tips but must not be yellow). The flames must extend  
directly outward from the burner without curling, floating or  
lifting off.  
For further information on the yearly inspection, consult the  
User Manual. It is recommended that a qualified servicer  
inspect and service the unit at least once each year.  
Check the burner flames for:  
1. Good adjustment  
2. Stable, soft and blue  
Turn the unit on at the thermostat. Wait a few minutes, since  
any dislodged dust will alter the normal flame appearance.  
Flames should be predominantly blue and directed into the  
tubes. They should not be yellow. They should extend directly  
outward from the burner ports without curling downward,  
floating or lifting off the ports.  
3. Not curling, floating, or lifting off.  
Burner Flame  
ACCESSORIES AND FUNCTIONAL PARTS  
SHEET METAL ACCESSORIES  
Additional accessories can be purchased to fit specific application  
needs. Parts and instructions are available from your distributor.  
At least once a year, prior to or during the heating season,  
make a visual check of the burner flames.  
FUNCTIONAL PARTS  
NOTE: This will involve removing and reinstalling the heat exchanger  
door on the unit, which is held by two screws. If you are uncertain  
about your ability to do this, contact a qualified servicer.  
If a strong wind is blowing, it may alter the airflow pattern within the  
unit enough that an inspection of the burner flames is not pos-  
sible.  
FUNCTIONAL PARTS  
Auxiliary Limit Switch  
Blower Housing  
Circulator Blower Motor  
Blower Wheel  
Flame Rollout Switch  
Flame Sensor  
Gas Orifice  
Gas Valve  
CLEANING BURNERS  
Burner  
Heat Exchanger  
High Limit Switch  
Igniter  
1. Shut off electric power and gas supply to the unit.  
2. Remove the screws securing the manifold to the burner  
retention bracket. Remove the manifold and rotate each  
burner counterclockwise to remove.  
Capacitor  
Compressor  
Condenser Coil  
Condenser Fan Blade  
Condenser Fan Motor  
Contactor  
Ignition Control  
Induced Draft Blower  
Pressure Switch  
Pressure Switch Hose  
Thermostatic Expansion Valve  
Transformer  
Burner  
Burner  
Bracket  
Gas Manifold  
Evaporator Coil  
Functional Parts List  
GENERAL INFORMATION  
Manifold  
1. Refer to the description in Functional Parts List when  
ordering any of the listed functional parts. Be sure to provide  
the unit model and serial numbers with the order.  
2. Although only functional parts are shown, all sheet metal  
parts, doors, etc. may be ordered by description.  
3. Parts are available from your distributor.  
ManifoldAssembly  
3. Remove the burners.  
4. Use a bottle brush to clean burner insert and inside of the  
burners.  
5. Replace burners and manifold, inspect the burner  
assembly for proper seating of burners in retention slots.  
6. Reconnect electrical power and gas supply.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IGNITION CONTROL DIAGNOSTIC INDICATOR CHART  
Red Light Signal Refer to Abnormal Heating or Cooling Operation Sections of this Manual  
Off  
Internal Control Failure  
1 Flash  
External Lockout  
2 Flashes  
3 Flashes  
4 Flashes  
5 Flashes  
6 Flashes  
7 Flashes  
8 Flashes  
9 Flashes  
Pressure Switch Stuck Open  
Pressure Switch Stuck Closed  
Thermal Protection Device Open  
Flame Detected with Gas Valve Closed  
Short Cycle Compressor Delay (Cooling Only)  
Limit Opened Five (5) Times Within The Same Call For Heat  
Indoor/Outdoor Thermostat Open (Cooling Only; Devices Not present On All Models)  
High Pressure/Loss of Charge Switch Open (Cooling Only; Devices Not Present On All Models)  
Amber Light Signal Refer to Abnormal Heating or Cooling Operation Sections of this Manual  
Off  
No Flame Present  
On  
Normal Flame  
1 Flash  
2 Flashes  
Low Flame Current  
Flame Detected with Gas Valve De-energized.  
HEATING TIMING CHART  
HIGH  
LOW  
OFF  
Circulator  
Blower  
HIGH  
LOW  
OFF  
Gas Valve  
Igniter  
ON  
OFF  
Induced  
Draft  
Blower  
HIGH  
LOW  
OFF  
HIGH  
LOW  
OFF  
Thermostat  
Seconds  
0
15  
22  
27  
52  
0
30  
90, 120, 150, 180  
COOLING TIMING CHART  
HIGH  
LOW  
OFF  
Circulator  
Blower  
HIGH  
LOW  
OFF  
Compressor  
Outdoor Fan  
HIGH  
LOW  
OFF  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UNIT DIMENSIONS  
47  
51  
FLUE EXHAUST  
HOOD  
18 7/16  
FLUE EXHAUST  
16  
A
1 3/8  
5 1/2  
C
16  
7 15/16  
B
SUCTION/LIQUID PRESSURE PORTS  
BEHIND COMPRESSOR ACCESS PANEL  
2 3/4  
COMBUSTION AIR INTAKE  
RETURN  
B
3
HEAT EXCHANGE ACCESS PANEL  
GAS SUPPLY ENTRANCE  
4 3/4  
SUPPLY  
CONDENSATE DRAIN CONNECTION  
3/4" NPT FEMALE  
EVAPORATOR/CONTROL PANEL ACCESS PANEL  
16 1/8  
19 1/8  
7 5/16  
DIMENSION  
(INCHES)  
LARGE  
MEDIUM  
7 7/8  
20  
A
B
C
32  
16  
40  
18  
14  
9 1/2  
24  
POWER WIRE ENTRANCE  
CONTROL WIRE ENTRANCE  
5 1/4  
EXHAUST FLUE HOOD  
BLOWER ACCESS PANEL  
COMBUSTION  
AIR INTAKE  
11  
5 3/4  
22  
22  
11  
SUPPLY  
RETURN  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
*PG15*****41A* WIRING DIAGRAM  
HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING.  
MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO  
SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.  
YL/BK  
YL/BK  
BL/PK  
YL  
BK  
LPS  
RD  
PU  
RD  
SEE NOTE 6  
S R C  
T1  
L1  
T2  
L2  
GND  
BL  
PU  
BL/PK  
COMP  
SOL  
YL  
CC  
HPS  
BL  
PU  
BK  
POWER SUPPLY  
208-230/1/60  
SEE NOTE 3  
BR  
BK  
GR  
BL  
CM  
3
2
1
6
5
4
PU  
1
C
2
208  
3
240  
PU  
BK  
BK  
YL  
TR  
24V  
PU  
PU  
GR  
PU  
RD  
YL  
BL  
RD  
BL  
C
L G N  
EM  
PU  
BK  
BL  
PU  
BK  
WH  
PU  
PU  
BR  
RD  
PU  
YL  
BK  
IGN  
OR  
LS  
L2  
T1  
LOW  
HIGH L1 LOW  
HI  
ALS  
PARK  
ODF  
INDUCER  
OR  
OR  
BK  
FS  
YL  
PU  
FS  
RD  
PS  
RS  
YL  
YL  
YL  
6
3
2
1
YL  
5
LO COOL  
PU  
BL  
5
4
YL  
BR  
PU  
4
3
2
1
24VAC COM  
HI COOL  
OR  
YL  
SEE NOTE 7  
YL  
BL  
BL  
YL  
HI HEAT  
LO HEAT  
OR  
BR  
1
2
3
4
5
7
8
9
BR  
OR  
YL  
W. R.  
GAS VALVE  
6
OR  
PU  
180  
150  
120  
F
WH  
NONE  
5 MIN  
90 10 MIN  
M
GV  
PU  
BLOWER STAGE  
OFF DELAY DELAY  
ECON R C W1W2 G Y1 Y2  
H
C
BR  
BL  
VM  
BL  
BK  
RD  
F
PU  
RD  
PU  
BK  
H
C
RD  
YL  
YL  
PU  
BL  
RCCF  
BR  
BR  
0140G00533 REV A  
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
*PG15*****41A* WIRING DIAGRAM  
HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING.  
MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO  
SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.  
L1  
L1  
SUPPLY VOLTAGE  
208-230/1/60  
L2  
L2  
CC  
T1  
CC  
T2  
C
COMPONENT LEGEND  
FACTORY WIRING  
R
C
LINE VOLTAGE  
LOW VOLTAGE  
OPTIONAL HIGH VOLTAGE  
ALS  
AUXILLARY LIMIT SWITCH  
S
H
COMP  
COMPRESSOR  
LO  
HI  
CM  
CC  
CONDENSER MOTOR  
CONTACTOR  
F
CM  
L2  
ECON ECONOMIZER  
LO  
EM  
F
FS  
GND  
GV  
IIC  
IGN  
LS  
FIELD WIRING  
EVAPORATOR MOTOR  
FUSE  
FLAME SENSOR  
EQUIPMENT GROUND  
GAS VALVE  
INTEGRATED IGNITION CONTROL  
IGNITOR  
LIMIT SWITCH  
L2  
L2  
L2  
VM  
EM  
HIGH VOLTAGE  
LOW VOLTAGE  
HI  
L1  
WIRE CODE  
BK BLACK  
BL BLUE  
BR BROWN  
GR GREEN  
OR ORANGE  
PK PINK  
PU PURPLE  
RD RED  
L1  
2
SEE NOTE 2  
TR  
F
P1  
TH  
PS  
PRESSURE SWITCH  
RCCF  
RUN CAPACITOR FOR COMPRESSOR/FAN  
ROLLOUT SWITCH  
SOLENOID (2ND STAGE COOL)  
TRANSFORMER  
ALS  
PS  
LS  
RS  
HLO  
HLI  
RS  
SOL  
TR  
1
3
R
WH WHITE  
YL YELLOW  
VM  
VENT MOTOR  
PSW  
PSW  
MVL  
6
8
W 1  
W 2  
TO  
MICRO  
9
M
NOTES  
GV  
MVH  
MVC  
Y2  
C
7
5
HI  
C
1. REPLACEMENT WIRE MUST BE THE SAME SIZE AND TYPE OF  
INSULATIONAS ORIGINAL.(USE COPPER CONDUCTOR ONLY).  
2. FOR 208 VOLT TRANSFORMER OPERATION MOVE BLACK WIRE  
COM  
P2  
Y1  
1
4
FROM TERMINAL  
3
TO TERMINAL  
2
ON TRANSFORMER.  
3. USE COPPER CONDUCTORS ONLY.  
HPS  
5
3
4. FOR 208V OPERATION, REMOVE BLUE LEAD FROM INDUCER LOW  
TERMINAL. MOVE BLACK LEAD FROM PARK TERMINAL ONTO  
INDUCER LOW TERMINAL. PLACE BLUE LEAD ON PARK TERMINAL.  
LPS  
SEE NOTE 7  
5. USE NEC CLASS 2 WIRE FOR THERMOSTAT FIELD WIRING.  
6. COMPRESSOR 2ND STAGE SOLENOID NOT PRESENT ON ALL MODELS.  
7. OPTIONAL REFRIGERANT SWITCHES  
SEE NOTE 8  
ECON  
5
6
2
1
2
CC  
8. FOR ECONOMIZER, REMOVE PLUG FROM ECONOMIZER HARNESS.  
CONNECT PLUG FROM ECONOMIZER TO HARNESS.  
5
4
ECON  
SOL  
ECON  
3
ECON  
LO HEAT  
HI HEAT  
G
TO  
MICRO  
EM  
C
LO COOL  
HI COOL  
DIAGNOSTIC  
LED - RED  
DIAGNOSTIC  
LED - RED  
CHECK  
-
STATUS  
CHECK  
STATUS  
ON  
NORMAL OPERATION  
LIMIT OPEN 5 TIMES IN  
SAME CALL FOR HEAT  
CHECK MAIN LIMIT SWITCH  
CHECK AUXILIARY LIMIT SW.  
7 FLASHES  
CHECK INPUT POWER  
CHECK FUSE(S)  
NO POWER OR  
INTERNAL CONTROL  
FAULT  
OFF  
CHECK JUMPER BETWEEN  
1 AND 4 ON 6-CIRCUIT  
CONNECTOR  
CHECK OPTIONAL  
GAS FLOW  
GAS PRESSURE  
GAS VALVE  
8 FLASHES  
9 FLASHES  
IDT/ODT OPEN  
PSW/LOC OPEN  
1 FLASH  
IGNITION FAILURE  
REFRIGERANT SWITCHES  
FLAME SENSOR  
CHECK REFRIGERANT  
SWITCHES FOR LOSS OF  
CHARGE OR HIGH HEAD  
PRESSURE  
CHECK PRESSURE SWITCH  
CHECK TUBING  
CHECK VENT MOTOR  
2 FLASHES  
PRESSURE SWITCH OPEN  
PRESSURE SWITCH CLOSED  
WITHOUT INDUCER ON  
CHECK PRESSURE SWITCH  
CHECK WIRING FOR SHORTS  
3 FLASHES  
4 FLASHES  
DIAGNOSTIC  
LED - AMBER  
CHECK MAIN LIMIT SWITCH  
CHECK AUXILIARY LIMIT SW.  
CHECK ROLLOUT LIMIT SW.  
CHECK  
STATUS  
OPEN LIMIT SWITCH  
FALSE FLAME DETECTED  
COMPR. SHORT CYCLE DELAY  
OFF  
ON  
NO FLAME PRESENT  
-
-
CHECK GAS VALVE  
CHECK FOR SHORTS IN  
FLAME SENSOR WIRING  
NORMAL FLAME PRESENT  
5 FLASHES  
6 FLASHES  
GAS FLOW  
GAS PRESSURE  
GAS VALVE  
1 FLASH  
LOW FLAME SIGNAL  
3 MIN COMP. SHORT  
CYCLE DELAY  
FLAME SENSOR  
CHECK GAS VALVE  
CHECK FOR SHORTS IN  
FLAME SENSOR WIRING  
FALSE FLAME DETECTED  
2 FLASHES  
0140G00533 REV A  
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
*PG15*****41B* WIRING DIAGRAM  
HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING.  
MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO  
SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.  
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
*PG15*****41B* WIRING DIAGRAM  
HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING.  
MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO  
SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.  
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MINIMUM CLEARANCES  
48" MIN  
12" MIN  
3"  
MIN  
.
12" MIN  
36" MIN  
(FOR SERVICE)  
NOTE: Roof overhang should be no more than 36".  
RECOMMENDED FILTER SIZES  
-
UNIT  
2 Ton  
2 1/2 Ton  
3 Ton  
3 1/2 / 4 Ton  
5 Ton  
Min. Filter Size  
(1)20 x 20 x 1 (1)20 x 25 x 1 (1)25 x 25 x1 (2)20 x 20 x 1 (2)20 x 25 x 1  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BLOWER PERFORMANCE DATA  
*PG152407041** - Rise Range: 35° - 65° F  
T1 T2  
CFM WATTS RISE CFM WATTS RISE  
T3 T4  
CFM WATTS CFM WATTS  
T5  
WATTS  
E.S.P  
CFM  
1047  
998  
948  
899  
850  
801  
---  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
729  
680  
631  
582  
532  
---  
55  
63  
71  
79  
87  
---  
---  
---  
52  
57  
62  
X
913  
864  
815  
766  
717  
667  
---  
103  
111  
119  
127  
135  
143  
---  
57  
61  
64  
X
X
X
897  
848  
799  
750  
701  
652  
---  
99  
107  
115  
123  
131  
139  
---  
897  
848  
799  
750  
701  
652  
---  
99  
107  
115  
123  
131  
139  
---  
139  
146  
154  
162  
170  
178  
---  
X
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
*PG153009041** - Rise Range: 45° - 75° F  
T1  
ST Stage Heating  
T2  
T3 T4  
CFM WATTS CFM WATTS  
T5  
Cooling Speed Cooling Speed Cooling Speed  
E.S.P  
1
2nd Stage Heating Speed  
CFM WATTS RISE CFM WATTS RISE  
CFM  
1326  
1282  
1237  
1192  
1148  
1103  
---  
WATTS  
248  
256  
263  
271  
279  
287  
---  
0.1 1050  
0.2 1006  
139  
147  
154  
162  
170  
178  
185  
193  
49  
52  
54  
57  
60  
63  
69  
72  
1256  
1211  
1167  
1122  
1077  
1033  
988  
220  
228  
236  
243  
251  
259  
267  
---  
55  
57  
59  
62  
64  
68  
70  
---  
1123  
1079  
1034  
989  
168  
176  
183  
191  
199  
206  
214  
222  
1123  
1079  
1034  
989  
168  
176  
183  
191  
199  
206  
214  
222  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
961  
916  
872  
827  
782  
738  
945  
900  
945  
900  
855  
811  
855  
811  
---  
---  
---  
*PG153709041** - Rise Range: 45° - 75° F  
T1  
ST Stage Heating  
Speed  
CFM WATTS RISE CFM WATTS RISE  
T2  
2nd Stage Heating Speed  
T3  
Cooling Speed Cooling Speed Cooling Speed  
T4  
T5  
1
E.S.P  
CFM WATTS CFM WATTS  
CFM  
1408  
1362  
1315  
1269  
1223  
1177  
---  
WATTS  
304  
311  
319  
326  
334  
341  
---  
0.1 1053  
0.2 1007  
143  
151  
158  
165  
173  
180  
188  
195  
49  
52  
54  
57  
60  
63  
69  
72  
1257  
1211  
1165  
1119  
1073  
1027  
980  
236  
243  
250  
258  
265  
273  
280  
---  
55  
57  
59  
62  
64  
68  
70  
---  
1184  
1138  
1092  
1046  
1000  
954  
203  
210  
217  
225  
232  
240  
247  
255  
1184  
1138  
1092  
1046  
1000  
954  
203  
210  
217  
225  
232  
240  
247  
255  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
961  
915  
869  
823  
777  
731  
908  
862  
908  
862  
---  
---  
---  
*PG154211541** - Rise Range: 45° - 75° F  
T1  
1ST Stage Heating  
Speed  
T2  
T3  
Cooling Speed Cooling Speed Cooling Speed  
T4  
T5  
nd Stage Heating Speed  
E.S.P  
2
CFM WATTS RISE CFM WATTS RISE  
CFM WATTS CFM WATTS  
CFM  
1609  
1556  
1504  
1451  
1399  
1347  
1294  
1242  
WATTS  
365  
373  
381  
388  
396  
404  
412  
420  
0.1 1090  
0.2 1025  
150  
158  
166  
174  
181  
189  
197  
205  
52  
57  
62  
X
1286  
1225  
1165  
1105  
1045  
984  
231  
239  
247  
255  
262  
270  
278  
---  
57  
61  
64  
X
1354  
1296  
1237  
1178  
1120  
1061  
1002  
944  
260  
267  
275  
283  
291  
299  
306  
314  
1354  
1296  
1237  
1178  
1120  
1061  
1002  
944  
260  
267  
275  
283  
291  
299  
306  
314  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
960  
895  
830  
765  
699  
634  
X
X
X
---  
---  
---  
---  
---  
924  
---  
*PG154911541** - Rise Range: 45° - 75° F  
T1  
ST Stage Heating  
Speed  
CFM WATTS RISE CFM WATTS RISE  
T2  
2nd Stage Heating Speed  
T3  
Cooling Speed Cooling Speed Cooling Speed  
T4  
T5  
1
E.S.P  
CFM WATTS CFM WATTS  
CFM  
1709  
1659  
1609  
1559  
1509  
1459  
1409  
---  
WATTS  
407  
414  
422  
430  
438  
446  
453  
---  
0.1 1164  
0.2 1100  
0.3 1037  
180  
188  
196  
204  
212  
220  
227  
235  
56  
59  
62  
65  
70  
75  
X
1435  
1378  
1322  
1265  
1208  
1152  
1095  
1038  
293  
301  
309  
316  
324  
332  
340  
348  
61  
63  
65  
68  
70  
73  
X
1477  
1421  
1365  
1310  
1254  
1198  
1143  
1087  
310  
318  
326  
334  
342  
349  
357  
365  
1477  
1421  
1365  
1310  
1254  
1198  
1143  
1087  
310  
318  
326  
334  
342  
349  
357  
365  
0.4  
0.5  
0.6  
0.7  
0.8  
974  
910  
847  
784  
720  
X
X
*PG156014041** - Rise Range: 45° - 75° F  
T1  
ST Stage Heating  
Speed  
CFM WATTS RISE CFM WATTS RISE  
T2  
2nd Stage Heating Speed  
T3  
Cooling Speed Cooling Speed Cooling Speed  
T4  
T5  
1
E.S.P  
CFM WATTS CFM WATTS  
CFM  
2108  
2058  
2009  
1960  
1911  
---  
WATTS  
704  
713  
721  
729  
737  
---  
0.1 1792  
0.2 1743  
0.3 1693  
0.4 1644  
0.5 1595  
0.6 1546  
0.7 1496  
514  
522  
530  
538  
546  
554  
563  
---  
X
1792  
1743  
1693  
1644  
1595  
1546  
1496  
514  
522  
530  
538  
546  
554  
563  
58  
61  
61  
63  
65  
68  
70  
---  
1366  
1317  
1267  
1218  
1169  
1120  
1071  
---  
257  
265  
273  
281  
290  
298  
306  
---  
1939  
1889  
1840  
1791  
1742  
1693  
1643  
---  
603  
611  
619  
627  
635  
643  
651  
---  
45  
45  
46  
48  
50  
52  
---  
---  
---  
---  
---  
0.8  
---  
X = Outside of Temperature Rise Range - Not Recommended.  
NOTE: The shaded area indicates ranges in excess of maximum external static pressure allowable when heating. For satisfactory operation,  
external static pressure should not exceed 0.5" w.c.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PACKAGE UNITS - DUAL FUEL & GAS  
HOMEOWNER’S ROUTINE MAINTENANCE RECOMMENDATIONS  
We strongly recommend a bi-annual maintenance checkup be performed  
by a qualified service agency before the heating and cooling seasons begin.  
COMPRESSOR  
The compressor motor is hermetically sealed and does not re-  
quire additional oiling.  
ANNUAL INSPECTION (QUALIFIED SERVICER ONLY)  
Your package unit should be inspected by a qualified installer,  
or service agency at least twice every year. This check should  
be performed before the heating and cooling seasons begin.  
This will ensure that adequate combustion air is being drawn  
and the vent system is working properly. Particular attention  
should be paid to the following items. Repair as necessary.  
REPLACE OR CLEAN FILTER  
Check physical support of the unit. Ensure it is sound  
without any sagging, cracks, or gaps, around the base.  
Check for obvious signs of deterioration of the unit.  
Flue Hood and Combustion Air Inlet. Check for blockage  
(wasp nest, etc.) and corrosion.  
IMPORTANT NOTE: Never operate unit without a filter installed as  
dust and lint will build up on internal parts resulting in loss of  
efficiency, equipment damage and possible fire.  
A return air filter is not supplied with this unit; however, there must  
be a means of filtering the return air. An indoor air filter must be  
used with your comfort system. A properly maintained filter will  
keep the indoor coil of your comfort system clean. A dirty coil could  
cause poor operation and/or severe equipment damage.  
The installer of your unit can tell you where your filter(s) are and  
how to clean or replace them.  
Check your return filter(s) at least once every two months. When  
they are dirty, replace or clean as required. Disposable type  
filters should be replaced. Reusable type filters may be cleaned.  
NOTE: Reusable type filters should be washed with warm water,  
dried completely and sprayed with an adhesive according to the  
manufacturers recommendations.  
You may want to ask your dealer about high efficiency filters. High  
efficiency filters are available in both electronic and non-electronic  
types. These filters can do a better job of catching small airborne  
particles.  
Improper filter maintenance is the most common cause of inad-  
equate heating or cooling performance. Filters should be cleaned  
(permanent) or replaced (disposable) every two months or as re-  
quired. When replacing a filter, it must be replaced with a filter of  
the same type and size and always make certain the air flow  
arrows on the filter point in the proper direction.  
CONDENSER, EVAPORATOR AND INDUCED DRAFT MOTORS  
The bearings on the air circulating blower motor, condenser motor  
and the combustion fan motor are permanently lubricated and  
require no further lubrication.  
FLUE HOOD (QUALIFIED SERVICER ONLY)  
Return Air Connection. Check for physical soundness  
and ensure that the connection is firmly sealed to the  
package unit casing.  
Heat exchanger. Check for corrosion and/or obstructions  
within the heat exchanger passageways.  
Burners. Check for proper ignition, burner flame, and  
flame sense.  
Wiring. Check wires for damage.Check electrical  
connections for tightness and/or corrosion.  
Filters. Check that filters are clean and in the proper  
placement in the unit or duct system.  
Louvers. Inspect air inlet louvers inside the heat  
exchanger compartments. Ensure the area is clean and  
free of dirt and debris.  
CLEAN OUTSIDE COIL (QUALIFIED SERVICER ONLY)  
The outdoor coil should be inspected annually. It is important to  
keep the outdoor coil clean. Dirt, leaves, or debris could restrict the  
airflow. If cleaning of the outdoor coil becomes necessary, hire a  
qualified servicer. Inexperienced people could easily puncture the  
tubing in the coil.  
BEFORE CALLING YOUR SERVICER  
Check the thermostat to confirm that it is properly set.  
Check the disconnect switch near the unit to confirm that  
it is closed.  
Check the electrical panel for tripped circuit breakers or  
failed fuses . Reset the circuit breakers or replace fuses  
as necessary.  
Check for blockage of the indoor air inlets and outlets.  
Confirm that they are open and have not been blocked by  
objects (rugs, curtains or furniture).  
Check for obstructions on the unit . Confirm that it has  
not been covered on the sides or the top. Remove any  
obstruction that can be safely removed. If the unit is  
covered with dirt or debris, call a qualified servicer to  
clean it.  
Check the filter. If it is dirty, clean or replace it.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Electro Voice Microphone PL60 N D User Manual
Extron electronic Stereo System 26 018 02 User Manual
FEIN Power Tools Grinder WSG 12 125 User Manual
Ford Remote Starter SK5W7J 19A361 AA User Manual
Frigidaire Freezer FFH17F7HW User Manual
Furuno Marine Radio IB 782 User Manual
Gaggenau Range EB 270 User Manual
GE Freezer FUM17SMRWH User Manual
GE Microwave Oven ZSC2000CBB User Manual
Generac Portable Generator 004700 0 User Manual